BHEL TRAINING REPORT Transformer-2 PDF
BHEL TRAINING REPORT Transformer-2 PDF
BHEL TRAINING REPORT Transformer-2 PDF
S.No. Contents
1 Products Range
2 Transformer Introduction
3 Electrical isolation
4 Autotransformers
5 Generation Transformer
6 Manufacturing of Transformers
7 Testing of Transformers
8 Bushings
9 Current Transformers
11 Reactors
12 Capacitor Bank
TRANSFORMERS, CAPACITOR BANKS AND BUSHINGS MANUFACTURING BLOCK AT BHEL,
BHOPAL
Scope:
1. Power Transformers: Upto 765kV Class; 1000 MVA 3 Phase; 1500 MVA 1 Phase Bank.
Recently BHEL Bhopal has built 1200/400 KV 333 MVA Transformer.
2. Gapped Core Reactors: Upto 765kV Class; 110 MVAR with Neutral Grounding
Reactor.
5. Instrument Transformers:
Upto 800kV Class
Transformer Bushings
Tap Changers - M&V Type
Radiators and Air/ Water Coolers
Products:
Capacitors
Shunt Capacitor banks with all film dielectric impregnated with non PCB
Impregnate of desired ratings from 6.6 to 400 kV complete with manual /
automatic control equipment for Industrial and power system application.
Pole mounted Capacitors for mounting in line with Rural Electrification
scheme up to 11 KV
Roof Capacitor in Traction Motor application: 4 microfarad, 2 KV DC
Series capacitors for Reactive compensation and voltage regulation in power
system from 33kV to 400 KV
Capacitor to improve power factor of traction substations suitable for Railway
Electrification.
Surge Capacitor for protection of Rotating Machine and Generator
transformers winding 15 kV and 40 kV, 0.125 micro farad.
AC filter Capacitor for Harmonic filtering suitable for HVDC application up to
500 kV.
Coupling capacitors / CVT up to 800 kV class for Power line carrier
communication application, meeting and protection.
Transformers
Power Transformers upto 420kV class, 50/60 Hz 945 MVA, 3-phase Bank.
Power Transformers upto 420kV class, 50/60 Hz 500 MVA, 3-phase Unit.
HVDC Converter Transformers and Smoothing Reactors.
500 MVA, ± 500kVDC, 3 winding, 1- Phase. Convertor Transformer.
254 MVAR, 360mH, 1568A, ±500 kV DC 1 –Phase Smoothing Reactor.
Instrument Transformers
Reactors
Gapped core Shunt Reactors up to 420 kV class, 125 MVAR 3 Phase Unit.
Series and Neutral Grounding Reactors.
Controlled Shunt Reactor up to 420 kV class, 80 MVAR 3 Phase Unit.
The DC test plant is adequate for test levels suitable up to +800 kV HVDC
transmission.
Suitability for testing AC equipments up to 1200KV class.
Customer in India:
National Thermal Power Corporation (NTPC), PGCIL, NJPC, NHPC, NLC, NPCIL, NEEPCO,
APTRANSCO, APGENCO, JPPCL, TATA Power, Adani Power, Jindal Power, ALL State Electricity
Utilities
Abroad:
TNB Malaysia, PPC Greece, MEW Oman, OCC Oman, GECOL Libya, Trinidad & Tobago, New
Zealand, Tanzania etc.
INTRODUCTION: TRANSFORMERS
Transformer is a static device that transfers electrical power from one circuit at a voltage
level to another circuit at another voltage level through a magnetic medium at constant
frequency.
Note: 1. Transformer is not a machine because it does not have any moving or rotating part.
. . . (2)
Turns ratio
Magnetizing reactance is XM
Vector Group notation: Vector group shows the phase displacement between HV and LV
windings.
a- Autotransformer
e.g. Dy11
HV coil- Delta connected, LV coil- Star connected, phase shift +30°.
Dyn11 Group:
The Dyn winding vector groups do not allow zero sequence currents (commonly known as
earth fault current) to pass across the transformer.
Thus, the yn side of the transformer is a 'separately derived system' in which all earth fault
current must flow through the neutral of this transformer. With this configuration, earth
fault protection is possible and practical. Likewise, earth fault protection on the primary side
is not affected by earth faults on the secondary side.
The choice of Dyn11 vs Dyn1 or some other angle (5,7, etc) is simply due to user
standardization.
Electrical Isolation: Electrical isolation means that there is no electrical connection between
the coupled circuits.
1. Therefore the neutrals of both the circuits can have different potentials or one
neutral may be grounded and other is left ungrounded.
Largely isolation will prevent shock
hazards. With no common reference
and each device floating you cannot
build up a harmful voltage difference
between two independent systems to
get a shock.
Let us assume that the signal input on left side is connected to a micro controller and on the
right side we have a BJT connected to Vcc = 24 v. Micro-controller can handle a maximum of
5 volts. So, we cannot interface the base of the BJT with the micro-controller directly
because if the collector and base regions are shorted due to some fault, the micro-controller
will have 24 volts on its interfaced pins which damage the micro-controller.
Note: Electrical isolation is not important at EHV and UHV systems because sufficient
protection is provided by the circuit breakers and other protective equipments.
Tertiary windings:
The impedance offered by the return path of unbalanced load current is very high where
very low reluctance return path is provided for unbalanced flux. In other words, very high
impedance to the flow of unbalanced current in 3 phase system is offered between line and
neutral. Any unbalanced current in three
phase system can be divided into three
sets of components likewise positive
sequence, negative sequence and zero
sequence components. The zero
sequence current is actually co-phasial
current in three lines. If value of co-
phasial current in each line is Io, then
total current flows through the neutral of
secondary side of transformer is In = 3.Io.
This current cannot be balanced by
primary current as the zero sequence
current cannot flow through the isolated
neutral star connected primary. Hence
the said current in the secondary side set up a magnetic flux in the core. The impedance
offered to the zero sequence current is very high. The delta connected tertiary winding of
transformer permits the circulation of zero sequence current in it. This circulating current in
this delta winding balances the zero sequence component of unbalance load, hence
prevents unnecessary development of unbalance zero sequence flux in the transformer
core. Therefore, placement of tertiary winding in star - star-neutral transformer
considerably reduces the zero sequence impedance of transformer.
Types of transformers:
In Auto Transformer, one single winding is used as primary winding as well as secondary
winding. But in two windings transformer two different windings are used for primary and
secondary purpose.
Weight of copper in winding is directly proportional to product of number of turns and rated
current of the winding.
Therefore, weight of copper in the section AC proportional to,
and similarly, weight of copper in the section BC proportional to,
Hence, total weight of copper in the winding of auto transformer proportional to,
⇒ N1I1 + N2I2
⇒ 2N1I1 (Since, in a transformer N1I1 = N2I2)
Let's assume, Wa and Wtw are weight of copper in auto transformer and two winding
transformer respectively,
Notes:
(b) They have lower losses and thus better efficiency compared to normal power
transformers.
(c) They have superior voltage regulation compared to normal power transformers
as they have lower impedance.
(d) They also have lower magnetisation current. All these advantages are present in
autotransformers because a major part of power is directly conducted into the
common winding.
3. Drawbacks of autotransformer:
(a) Because of electrical conductivity of the primary and secondary windings the
lower voltage circuit is liable to be impressed upon by higher voltage. To avoid
breakdown in the lower voltage circuit, it becomes necessary to design the low
voltage circuit to withstand higher voltage.
(b) Since the impedance is low therefore it results into severer short circuit currents
under fault conditions.
(c) Only star/star connection is practically possible in autotransformer. Also the
neutral points are not isolated.
Constructional Features:
1. There are four windings in autotransformer- LV, IV, HV and tap winding.
LV- Low voltage (generally 33 KV) – Helical winding
IV- Intermediate voltage winding (generally 220 KV or 400 KV) - Disc type winding
HV- High voltage winding (generally 400/765/1200 KV) - Disc type winding
Tap winding- it is a part of HV winding.
The two extra limbs are used to reduce the height of the core so that it is easy to transport.
If these limbs are not there then height of the core will be much higher so as to provide the
necessary area for developing the required flux.
3. There are 10 bushings on autotransformer- 3-HV, 3-IV, 3-LV, 1-Neutral.
Core Design:
Generation Transformer:
Generation Transformer is employed in power plant for stepping up the voltage for
transmitting the power to the grid. Electrical power is generated in the power plant at lower
voltages (typically generation voltage will be between 11kV to 33kV).
Constructional Features:
1. These transformers are generally built as three single phase transformers because
the size of single three phase unit would be excessive.
2. There are three windings in generating station transformer - LV, HV and tap winding.
LV- Low voltage (generally 33 KV) – Helical winding
HV- High voltage winding - Disc type winding
Tap winding- it is a part of HV winding.
3. The core is generally has three or four limbs (single phase transformer).
Transformer Manufacturing:
1. Core Manufacturing:
(a) Material Used: CRGO (Cold Rolled grain oriented) silicon steel. The
permeability is increased and core losses are decreased by using CRGO.
(b) For all transformers above 100 MVA core material is imported from China.
(c) CRGO is laminated with mica insulation on both sides. Lamination reduces
eddy current losses.
(d) Core of transformer is isolated from end plate (which is earthed), otherwise
dangerous currents may flow in the core. Isolation test is performed to
check this.
(e) Generally 20 Step core is manufactured. The pallets are cut at 450
(f) Ceramic spacers are provided in between the pallets to create an oil duct.
(g) Holes are punched in core so that it can be clamped on end plate. End Plate
is made of mild steel.
(h) The limbs and yokes are bound by epoxy resin tape which shrinks on
heating.
Block Diagram:
Assembled Unit:
2. Insulation: Insulation is provided on core, windings, coils, Tank etc.
Material Used:
(a) Press board- Used in making insulating cylinder around coils
(b) Udel Wood- Used at the top and base of the coils
(c) Bakelite- Used in high temperature areas where there are chances of
sparking.
(d) Scrap Paper- Insulation of windings.
(e) Gas cut- Prevents leakage of oil from tank cover.
(f) Epoxy or Fibre glass- Provided on core for insulation.
Top and bottom shunts are used at top and bottom of the coils for leakage
flux control.
Strands: In case of very large conductor cross sectional area, the conductor is
stranded (or divided into many conductors) to reduced the eddy the current loss. It
also provides mechanical strength and makes the winding flexible.
Transposition: The different strands if not transposed would link different amount of
flux. Therefore different voltages will be induced across different strands and this
will allow a circulating current to flow in the coil as all the strands are connected to
each other at the end terminals.
(a) Helical winding: This type of winding is used in coil where there are lower
numbers of turns i.e. LV winding.
(b) Disc winding: This type of winding is used in a coil where there are large number
of turns i.e. HV and IV winding.
4. Coil Assembly:
The separately prepared HV, tap and LV coils are assembled as a single unit.
Type tests: These tests are done mainly in a prototype unit not in all manufactured units in a
lot. Type test of transformer confirms main and basic design criteria of a production lot.
Routine tests: These tests are mainly for confirming operational performance of individual
unit in a production lot. Routine tests are carried out on every unit manufactured.
Special tests: These tests are done as per customer requirement to obtain information
useful to the user during operation or maintenance of the transformer.
Periodic/condition monitoring tests: These tests are performed regularly for monitoring the
condition of Transformer.
Test current is injected to the winding and corresponding voltage drop across the
winding is measured.
By applying simple Ohm's law i.e. Rx = V ⁄ I, we can determine the value of resistance.
The test current shall not exceed 15% of the rated current of the winding. Large
values may cause inaccuracy by heating the winding and thereby changing its
resistance.
For star connected three phase winding, the resistance per phase would be half of
For delta connected three phase winding, the resistance per phase would be 0.67
Note: - Transformer winding resistance measurement shall be carried out at each tap.
Transformer Ratio Test
A phase voltage is applied to the one of the windings by means of a bridge circuit
3.
This theoretical turn ratio is adjusted on the transformer turn ratio tested or TTR by
the adjustable transformer as shown in the figure above and it should be changed
AN BN CN
4. Measure voltages between terminals 2U-1N, 2V-1N, 2W-1N, that means voltages
The vector group test of transformer for other group can also be done in similar way.
Procedure
1. First disconnect all the line and neutral terminals of the transformer.
2. Megger leads to be connected to LV and HV bushing studs to measure insulation
resistance IR value in between the LV and HV windings.
3. Megger leads to be connected to HV bushing studs and transformer tank earth point
to measure insulation resistance IR value in between the HV windings and earth.
4. Megger leads to be connected to LV bushing studs and transformer tank earth point
to measure insulation resistance IR value in between the LV windings and earth.
Transformer Coil Megger Size Min.IR Value Liquid Min.IR Value Dry Type T/C
Voltage Filled T/C
Voltage Test Voltage (DC) LV side Test Voltage (DC) HV side Min IR Value
Polarization Index: It is the ratio of Insulation resistance (Meg-ohm) at the end of 10 min
test to that at the end of 1 min test
Separate source voltage withstand test: This dielectric test is intended to check the ability of
main insulation to earth and between winding.
The test is successful if no breakdown in the dielectric of the insulation occurs during test.
Nominal system Highest system Rated short duration
415V 1.1 KV 3 KV
11 KV 12 KV 28 KV
33 KV 36 KV 70 KV
Here, three phase voltage, twice of rated secondary voltage is applied to the secondary
winding for 60 second by keeping the primary of the transformer open circuited. The
frequency of the applied voltage should be double of power frequency too. Here also if no
failure of insulation, the test is successful.
Impulse Test
Lightning impulse: Standard lightning impulse Front time T1 = 1,2 μs ± 30% Time to half-
value T2 = 50 μs ± 20%
System disturbance due to natural lightning strokes can be represented by three basic wave
shapes.
1) Full wave
3) Front of wave
Switching Impulse: It is a long wave having front time 250 μs and time to half value 2500 μs
Marx Generator:
The circuit generates a high-voltage pulse by charging a number of capacitors in parallel,
then suddenly connecting them in series.
At first, n capacitors (C) are charged in parallel to a voltage V by a high voltage DC power
supply through the resistors (RC)
To create the output pulse, the first spark gap is caused to break down (triggered); the
breakdown effectively shorts the gap, placing the first two capacitors in series, applying a
voltage of about 2V across the second spark gap. Consequently, the second gap breaks
down to add the third capacitor to the "stack", and the process continues to sequentially
break down all of the gaps.
Capacitive voltage dividers are used to measure the voltage generated by the impulse
generator.
The wave shape and the peak value of the impulse voltage are measured by means of an
Impulse Analysing System (DIAS 733) which is connected to the voltage divider.
The test is performed with standard lightning impulses of negative polarity. The front time
(T1) and the time to half-value (T2) are defined in accordance with the standard.
Impulse generator is used to produce the specified voltage impulse wave of 1.2/50 micro
seconds wave. For a three phase transformer, impulse is carried out on all three phases in
succession.
The voltage is applied on each of the line terminal in succession, keeping the other terminals
earthed. The current and voltage wave shapes are recorded on the oscilloscope and any
BIL(Basic Insulation Level): It is the peak value of the voltage impulse that equipment can
withstand.
fluid electrical insulation system under high voltage stress, which does not bridge the space
between two conductors. Partial discharges in a transformer deteriorate its insulation and
Measuring Circuit
1. Supply generator 2. Supply transformer 3. Test transformer 4. Voltage transformer and
measuring circuit 5. Filter 6. Measuring impedance 7. Selective switch 8. Measuring
instrument and oscilloscope qo - calibration generator
After the transformer is energised for measuring operations, the partial-discharge value
read at the measuring instrument is multiplied with the predefined K correction factor,
and real apparent partial-discharge value for each terminal is found.
q = K · qm
qm – load read at the measuring instrument m
K – Correction factor
q – Real apparent load
In case of any change in coil parameters or any damage the frequency response of the
transformer will not be same as the factory stage response. Therefore in SRFA test
frequency response of transformer coil is checked at commissioning site to detect any
damage.
Tan delta test: It determines the health of the insulators. It is used for cable, winding,
current transformer, potential transformer, transformer bushings.
ratio, IR to IC is tanδ
Method:
High voltage Schering Bridge is used to
determine the capacitance and tanδ.
Cx = (C1*R4)/R3
Rx = (C4*R3)/C1
tanδ = wC4R4
11 7
22 5
66 2.5
88 2
132 1.5
275 1
400 0.5
A very low frequency test voltage is applied across the equipment whose insulation to be
tested. First the normal voltage is applied. If the value of tan delta appears good enough,
the applied voltage is raised to 1.5 to 2 times of normal voltage, of the equipment. The tan
delta controller unit takes measurement of tan delta values.
A CVT/VT and CT are connected in LV side of the transformer as CVT or VT required for LV
side have lower rating. The voltage (110%) at rated frequency is applied to that LV side with
the help of an auto transformer. The HV side of the transformer is kept open.
Short Circuit Test on Transformer: This test is performed to determine the copper losses at
A CVT/VT and CT are connected in HV side of the transformer. The voltage at rated
frequency is applied to that HV side with the help of auto transformer.
The LV side of the transformer is short circuited. Now voltage is slowly increased until the
In this type test of transformer, we have to check oil temperature rise as well as winding
temperature rise limits of an electrical transformer.
After completion of temperature rise test for top oil of transformer the current is reduced to
its rated value for transformer and is maintained for one hour.
After one hour the supply is switch off and short circuit and supply connection to the HV
Then the resistances are measured at the same 3 to 4 minutes time intervals over a period
of 15 minutes.
Graph of hot resistance versus time is plotted, from which winding resistance (R 2) at the
Break down voltage is measured by observing at what voltage, sparking starts between two
electrodes immerged in the oil, separated by specific gap. Low value of BDV indicates
presence of moisture content and conducting substances in the oil.
BDV measuring kit is generally available at site. In this kit, oil is kept in a pot in which one
pair of electrodes are fixed with a gap of 2.5 mm (in some kit it 4mm) between them.
Now slowly rising voltage is applied between the electrodes. Rate of rise of voltage is
generally controlled at 2 KV/s and observe the voltage at which sparking starts between the
electrodes.
Minimum breakdown voltage of transformer oil or dielectric strength of transformer oil at
But recommended BDVs for new transformers with various voltage ratings are
1. <72.5 KV – 40KV
2. 72.5<V<170 KV – 50KV
3. >170KV – 60KV
Polarity Test:
This test is performed to ensure that transformer is able to withstand the mechanical stress
and temperature rise in case of actual short circuit.
Icw includes the Rated Peak Withstand Current (Ipk), which is a surge of current that
occurs on one phase of the system in the first full cycle, as well as the changes of electro-
magnetic forces that occur through the number of cycles seen during the test.
Methods:
Test method (a) involves closing of a breaker at the source terminal to energize the
previously short-circuited transformer. This means that the secondary winding is short
circuited in advance and power is switched on to the primary. In this method there is a
problem of uncontrolled magnetization of core.
Test method (b) involves closing a breaker at the faulted terminal to apply a short-circuit to
the previously energized transformer. By adapting this test method, the difficulty of
uncontrolled core magnetization disappears. The transformer is taken up at no-load to rated
voltage and the secondary short-circuit is then closed, at the predetermined phase angle, by
means of a synchronous make-switch.
For Transformers with Two Separate Windings there are three categories:
I fault = 100/z
The transformer is designed with the consideration of maximum calculated fault current and
corresponding forces and temperature rise. And an additional tolerance is taken by the
designer. Thus short circuit test only verifies that the transformer is actually able to
withstand the short circuit on field not just on paper.
The duration of the current is generally 1-2 s unless a different duration is specified.
BUSHINGS
In electric power, a bushing is an insulator that allows an electrical conductor to pass safely
through a (usually) earthed conducting barrier such as the wall of a transformer or circuit
breaker.
When an energized conductor is near any material at earth potential, it can cause very high
field strengths to be formed therefore insulation becomes necessity.
NOTE: Bushings are the weakest link in all transformer related equipments. Most often
bushing failure leads to failure of whole transformer.
Design:
Now oil impregnated paper and aluminium foil is wrapped around this rod alternatively.
This arrangement creates series capacitances and thus reduces the electric field stress on
each insulating paper unit.
A. Composite Bushing: - A bushing in which insulation consists of two or more coaxial layers
of different insulating materials.
B. Compound-Filled Bushing: - A bushing in which the space between the major insulation
(or conductor where no major insulation is used) and the inside surface of a protective
weather casing (usually porcelain) is filled with a compound having insulating properties.
These bushings are used for very high voltages as electric field is properly distributed by
formation of capacitors.
D. Oil-Filled Bushing: - A bushing in which the space between the major insulation (or the
conductor where no major insulation is used) and the inside surface of a protective weather
casing (usually porcelain) is filled with insulating oil.
Testing:
1. Capacitance and tan δ tests- Capacitance rise by more than 10% is considered
dangerous and occurs due breakdown of capacitive layers.
This reduced value of current is then used for metering, control and protection. Generally
multiple secondary coils are present in CTs.
Knee-point voltage- It is the magnitude of the secondary voltage above which the output
current ceases to linearly follow the input current within declared accuracy.
Note: Secondary winding of the CT must never be open circuited because dangerously high
voltages are developed across its secondary terminals as it is a step up transformer.
Practical current transformer:
1. Metering Accuracy CT’s are used where a high degree of accuracy is required from
low-load values up to full-load of a system. An example of this application would be
the current transformers utilized by utility companies for large capacity revenue
billing.
2. Relaying Accuracy CT’s are used for supplying current to protective relays. In this
application, the relays do not normally operate in the normal load range, but they
must perform with a reasonable degree of accuracy at very high overload and fault-
current levels which may reach twenty times the full-load amplitude.
The rated output classes in IEC are 5, 10, 15, 20, and 30 VA.
The preferred accuracy classes are 5P (5 percent maximum error) and 10P (10 percent
maximum error).
Lastly, IEC has an accuracy limit factor (ALF), which indicates the multiples of rated
secondary current at which the accuracy class applies. The typical value of the ALF is 10,
with values of 20 and 30 also available.
e.g. 20 VA class 5P10, signify a protective CT with less than 5 percent error at 10 times rated
current, with a load output of 20 VA.
Class PX CT's are defined by the position of the knee-point and the secondary wire
resistance RCT. They have low leakage reactance and their performance can be easily
calculated using available data.
Class PR CT's are defined like the PX CT's but they have a low remanence; less than 10%.
Note that remanence in CT's can be 60-80% that may cause quick saturation in case of a
fault-current DC offset in the remanent direction. A class PX CT can't have that problem.
CT's for transient response class "TP" are defined by their connected load RB, time
constant TS and their over current figure KSSC. These linearised CT's have air-gaps in the
core to obtain extreme high saturation voltage and current.
PS is “Protection Special Class” CT. This core is used particularly where current balance is
precisely required to be maintained. PS class CT's are special purpose CT's with minimal
error compared with 5P20 Class and is more sensitive.
Measurement CTs
These are aimed at measuring accurately current within their normal operating range of
0 to In.
For the protection of the measuring instruments in case of a fault current, it is
favourable that for currents far above rated current In, the core is saturated and the
output lowers so that the fault-current trough the meter is only a part of the expected
current trough the meter. This is expressed by the Instrument Security Factor SF.
The accuracy of a measurement CT is given by its accuracy class that corresponds to the
error% at rated current and at 1.2 times rated current In.
The standard accuracy classes according IEC are class 0.2, 0.5, 1, 3 and 5. For classes 3
and 5, no angle error is specified. The classes 0.2S and 0.5S have their accuracy shifted
toward the lower currents. This means that they have 5 measuring points instead of 4
(or 2 for class 3 & 5).
Testing
7. Impulse Test: To ensure lightning and switching impulse withstand capability of CT.
CAPACITIVE VOLTAGE TRANSFORMERS
CVTs are modified voltage transformers. They are also instrument transformers which
provide appropriately reduced voltage from high voltage power systems.
This reduced voltage is then used for metering, control and protection.
1. Revenue metering
Construction:
The medium voltage inductive voltage transformer is immersed in mineral oil and housed
inside a hermetically sealed metallic tank.
The secondary terminals are located inside a box (7) enabling connections and have space
with protection elements such as fuses or circuit breakers.
SECTIONS
1. Primary terminal
2. Oil volume compensating system
3. Insulator (porcelain or silicone rubber)
4. Capacitors
5. Intermediate voltage tap
6. High frequency terminal
7. Inductive voltage transformer
8. Oil level indicator
9. Carrier accessories
10. Oil sampling valve
11. Earthing terminal
12. Secondary terminal box
There are two types of voltage transformers
3. Measuring VT: These VT’s are used for measurement and metering purpose
4. Protection VT: These VT’s are used system protection purposes.
Phase Error
Accuracy Class Voltage Error (%) Application
(Minutes)
Precise
0.1 +0.1 +5
Measurement
0.2 +0.2 +10 Measurement
Reactors are basically inductors used for reactive power compensation and voltage control
in power system.
1. Transformer will have at least 6 bushings while reactor will have only 3 bushings
because reactor has only three single coils while transformer has six to nine coils.
2. Low reluctance path is present in the transformer core while high reluctance path is
present in reactor core so that it consumes large reactive power.
Since a Shunt Reactor magnetizing current is large, if it is designed with Iron alone as a
Power Transformer, there will be large hysteresis loss. Air gaps
in Iron core are provided in a Shunt Reactor to reduce this loss
and to minimize the remanent flux in the core.
Dry type Reactors are constructed as single phase units and are thus arranged in a fashion
to minimize stray magnetic field on surrounding. When such an arrangement is difficult,
some form of magnetic shielding is required.
One of the advantages of dry type reactor is absence of inrush current.
Oil immersed reactors can be core-less or with gapped iron core. These are either single
phase or three phase design with or without fan cooling. These are installed within tanks
which hold oil & act as metallic magnetic shields.
Reactors are thyristor controlled in order to adapt fast to the reactive power required.
Especially in industrial areas with arc furnaces the reactive power demand is fluctuating
between each half cycle.
Since inductor voltage can change abruptly so the firing angle of thyristors in reactor can be
smoothly varied while in case of capacitors this is not possible.
CAPACITOR BANK
Capacitor banks are used for reactive power compensation (series and shunt), load power
factor improvement, filters and in CVTs (capacitor units only).
A capacitor bank is a grouping of several identical capacitors interconnected in parallel or in
series with one another.
Construction:
Capacitors are intended to be operated at or below their rated voltage and frequency as
they are very sensitive to these values; the reactive power generated by a capacitor is
proportional to both of them (kVar ≈ 2π f V 2).
Bank Configurations
An individual fuse, externally mounted between the capacitor unit and the capacitor
bank fuse bus, typically protects each capacitor unit. The capacitor unit can be
designed for a relatively high voltage because the external fuse is capable of
interrupting a high-voltage fault. Use of capacitors with
the highest possible voltage rating will result in a
capacitive bank with the fewest number of series
groups.
Each capacitor element is fused inside the capacitor unit. The fuse is a simple piece
of wire enough to limit the current and encapsulated in a wrapper able to withstand
the heat produced by the arc. Upon a capacitor element
failure, the fuse removes the affected element only.
The capacitor units for fuseless capacitor banks are identical to those for externally
fused described above. To form a bank, capacitor units are connected in series
strings between phase and neutral.
When the capacitor element fails it welds and the capacitor unit remains in service.
The voltage across the failed capacitor element is then shared among all the
remaining capacitor element groups in the series.
Overvoltage due to an element failure is not severe
however successive failures of elements will lead to the
removal of the bank.