Seiko GD-B Earth Leakage Relay
High-speed operation, exposed type
Features
Reference Standard IEC60755-1983
Low cost
Compact
Small design means it fits easily into control centers,
control boards and even machinery.
1
Dimensional drawings M3.5 terminal screw (copper-zinc plate)
Operation indicator
Reset switch
Test switch 38 2-4.6mm dia. Holes
Case (polycarbonate, black)
(for M4)
80
94
41 74
84
51
Terminal cover (polycarbonate, clear)
indicator
P1 Leakage relay
Test switch
ZCT Reset switch
k C1
k Connect bar between k and n for
200, 500 and 1000 mA a1
ZCT n n
Connect between l and n for b1 Output
100, 200 and 500 mA contacts
C2
No bar on 30 mA model Current P3 a2
Select bar sensitivity Control
select bar P2
supply P1
AC 100 or
200 V
Caution: Factory setting is between k and n.
Adjust as needed.
Specifications
Model GD-B03T GD-B12T GD-B25T GD-B510T Operating temperature (C) -20 to +60 (average ambient 50C max.)
Rated current sensitivity (mA) 30 100/200 200/500 500/1000 Operating humidity (%) Relative 45 to 85 (no condensation)
Rated current threshold (mA) 50% min of rated current sensitivity Usage voltage range (%) 80 to 110
Rated control voltage (AC-V) 100, 110/200, 220 Operation indicator Red LED
Rated frequency (Hz) 50, 60 Leakage detection Electronic current operation
Power consumption (W) 2 max. Recovery Manual
Operating time (sec) 0.1 max. Weight (kg) 0.25
Output contacts 1a+1c
Applicable ZCT GDZ-16 to 80, GDZM-16 to 107.
Load
Voltage Resistive load (COS1) Inductive load (COS0.4) For GD-B03T use GDZ-16 to
Output contact ratings 40 and GDZM 16 to 42.
AC125V 5A 3A
AC250V 5A 2A
2
Seiko GD-C Earth Leakage Relay
Multi-function, exposed type
Features
Reference Standard IEC60755-1983
Rational wiring layout
Connecting wires can be run in either of two
directions to fit available space, providing
expanded freedom in layout.
N.P
DIN rail
3
Dimensional drawings M3.5 terminal screw (copper-zinc plate)
99
38 96
25 8
75
85
Specifications
Model GD-C Operating temperature (C) -20 to +60 (average ambient 50C max.)
Rated current sensitivity (mA) 30/100/200/500/1000 (selectable) Operating humidity (%) Relative 45 to 85 (no condensation)
Rated current threshold (mA) 50% min of rated current sensitivity Usage voltage range (%) 80 to 110
Rated control voltage (AC-V) 100, 110/200, 220 Operation indicator Red LED
Rated frequency (Hz) 50, 60 Leakage detection Electronic current operation
Power consumption (W) 2 max. Recovery Manual
Operating time (sec) 0.1 max. (high-speed)/0.3 (delay): (selectable) Weight (kg) 0.25
Output contacts 1a+1c GDZM-16 to 107
Load Applicable ZCT For 30-mA current sensitivity,
Voltage Resistive load (COS1) Inductive load (COS0.4) use GDZM-16 to 42.
Output contact ratings AC125V 5A 3A
See page 12 for explanation of model types.
AC250V 5A 2A
4
Seiko GD-D (embedded type) Earth Leakage Relay
Front Rear
Specifications
Current sensitivity
Selectable to 100, 200, 500 or 1000 mA with a rotary switch.
Operating time
Selectable to 0.3, 0.5, 1 or 2 s with a rotary switch.
Power indicator
Green LED provided to show when power is supplied from board.
Terminal cover
Clear terminal cover mounted. Holes for tightening
terminal screws are designed to protect fingers.
5
Features
Reference Standard IEC60755-1983
Wide range of supply voltages
Can be used at AC 120 and 240 V as well,
making it perfect for use outside Japan.
DIN size
Board footprint is DIN size, 48 x 96 mm, for easy board
standardization.
One-touch mounting
Quick mounting by just snapping into place on the board.
No screws are needed, only a square hole, reducing construction time and
labor requirements.
Time and labor are further reduced because no screw tightening is needed.
Quick-release terminals
Terminal screws cannot fall out, reducing connection time and labor requirements.
Dimensional drawings
One-touch panel mechanism
(applicable panel thickness 1 to 3.2 mm) Rear case
Operating information (polycarbonate, black)
48
12 65
Sensitivity current
Power indicator select switch
(green)
Leakage Operating time
indicator (red) select switch
Manual/automatic
recovery select switch
Test switch
91
Reset switch
96
Ratings
Front case
(polycarbonate,
black)
92 +0.8
0
44
Specifications
Model GD-D Operating temperature (C) -20 to +60 (average ambient 50C max.)
Rated current sensitivity (mA) 100/200/500/1000 (selectable) Operating humidity (%) Relative 45 to 85 (no condensation)
Rated current threshold (mA) 50% min of rated current sensitivity Usage voltage range (%) 80 to 110
Rated control voltage (AC-V) 100, 120/200, 240 Operation indicator Red LED
Rated frequency (Hz) 50, 60 Power indicator Green LED
Power consumption (W) 2 max. Leakage detection Electronic current operation
Operating time (sec) 0.3/0.5/1/2 (selectable) Recovery Manual or automatic (switchable)
7
Installation locations for ground short protector
An earth leakage breaker or earth leakage relay can be used with a breaker (line breaker, sole-
noid breaker, etc.) as a ground short protector. With an earth leakage relay board area can be
used effectively.
Quick reference chart for ground short protector installation locations Installation required Not required Not applicable
Voltage to ground 150 V max. Over 150 V
Law 200V
Installed equipment and environment Operating voltage 60 V max. 100V 3W 200V 415V
22 Installations over conductive surfaces such as steel plate, steel beams, workbenches, etc. (50 V max.X)
(Load) (Load)
(Load)
8
Zero-phase sequence
Seiko GDZM current transformer
GDZM16BT GDZM16B
GDZM30AT GDZM30A
GDZM42AT GDZM42A
GDZM65AT GDZM65A
GDZM80AT GDZM80A
GDZM107AT
9
Dimensional drawings
Models with terminals Models with leads
60 60
50 50
2 5-mm dia. Holes (for M4) 2 5-mm dia. Holes (for M4)
18
When terminal
cover used 42 M3.5 screw 42 18
16
16
49.5
46
46
22
22
0.5 mm2 lead, length 700, black
GDZM-16BT GDZM-16B
40
50
40
50
F
E
Mounting hole (for M5) 6 Mounting hole (for M5)
6
G F
B
When terminal B
cover used M3.5 screw
A A
E
D
D
C
C
0.5 mm2 lead,
length 700, black
Model A B C D E F G Model A B C D E F
GDZM-30AT,42AT,65AT GDZM-30A,42A,65A
M3.5 screw
27
40
50
27
40
50
6 6
100 Mounting hole (for M5) 100 Mounting hole (for M5)
126 126
When terminal
cover used
149.5
148
148
80
64.5
64.5
GDZM-80AT GDZM-80A
10
Dimensional drawings
76.5
62
130
175
46
Case SPCC
36.4
Terminal cover (option) Terminal strip (caution electrocoat) 30
210
209
194
10
7
GDZM-107AT
11
List of Seiko Electric earth leakage relays and zero-phase sequence current transformers
GD-B earth leakage relays
Model Specification
GD-B03T AC 100, 110/200, 220 V, sensitivity current 30 mA
GD-B12T AC 100, 110/200, 220 V, sensitivity current 100/200 mA
GD-B25T AC 100, 110/200, 220 V, sensitivity current 200/500 mA
GD-B510T AC 100, 110/200, 220 V, sensitivity current 500/1000 mA
GD-C options
Model Specification
GDTC-C Terminal cover (single unit)
GDAP-C DIN rail mount fittings (single unit)
12
Handling precautions
Do not disassemble earth leakage relays or zero-phase sequence current trans-
formers.
Never test to confirm electrical shock safety with your hand or other part of
your body.
It is impossible to prevent electrical shocks between wires.
When measuring circuit insulation resistance or dielectric strength it is impossi-
ble to measure between wires, so always disconnect the leakage relay first.
There are no problems, however, between chargers and ground.
Do not test dielectric strength between control supply terminals or between ter-
minals for input from the ZCT. This could damage the leakage detect circuit.
Where there are excessive branches or where line length is excessive, a high-
sensitivity relay on the main circuit could result in false triggers by weighted
leakage. Select an appropriate current sensitivity.
Precautions in use
Always prepare mounting holes to specified dimensions and mount securely.
Connection terminal torque is 0.7 to 1.0 N m. Excess torque will damage termi-
nals.
Do not mount in sites subject to excessive heat.
Do not mount in sites subject to excessive vibration or impact.
Do not mount in sits subject to corrosive or flammable gas, ash, steam or salt,
or subject to water or oil spray.
Do not run dedicated ground lines through zero-phase sequence current trans-
formers
Always run the common wire for single-phase 3-line and triple-phase 4-line sys-
tems through the ZCT.
The straight portion of the thru-conductor should be as long as possible to en-
sure ZCT balancing.
Thru-conductors should be bundled with cable ties to prevent damage from
electromagnetic repulsion in the event of shorts.
Connection between earth leakage relay and ZCT should be with twisted wire to
avoid induction effects.
Earth leakage relays and ZCT should be at least 10 cm distant from trunks carry-
ing several thousand A or more, to avoid external magnetic field effects.
Load equipment should be grounded in accordance with local law and regula-
tion.