EasyPact MVS
Catalogue
2013
Performance
without compromise
3
Choose the leader
5
The Key values
90%
The performance you need
EasyPact MVS provides the ideal level of capability for
re
ations a
your installation from 800 to 4000 A.
of a p p li c
covered
ock by up to
educe st At a cost-effective investment
30%
R
6
Gain peace of
mind and
optimised cost
for every
installation
EasyPact MVS General contents
Functions A-1
and characteristics
Installation
B-1
recommendations
Dimensions
C-1
and connection
Additional
E-1
characteristics
Catalogue numbers
F-1
Connections A-15
Overview of solutions and accessories A-15
Locking A-18
On the device A-18
Accessories A-25
A-1
Functions General overview
and characteristics Detailed contents
This overview describes all the functions offered by Circuit breakers and switch-disconnectors page A-4
EasyPact MVS devices.
b Ratings:
v EasyPact MVS 800 to 4000 A
b Circuit breakers type N, H
b Switch-disconnectors type NA, HA
CPB100000
b 3 or 4 poles
b Fixed or drawout versions
CDB500001
CDB500002
test test
setting delay test
test
b Rear connection:
tg
(s)
Ig
D E F (s) .4 .4 .3
C G .3
.2
B
H .2 .1
on.1 2 0off
v
A I
Horizontal
on I t off
ground fault
ground fault
DB101149
E46459
v Vertical
ET2I trip system. ET5S trip system. ET6G trip system. b Optional accessories:
v Interphase barriers Safety shutters
v Safety shutters and shutter locking Interphase barriers
blocks
DB101110
A-2
Indication contacts page A-20
PB104354A40
b Standard:
E46438
DB101112
v ON/OFF indication (OF)
b Optional:
DB101113
DB101114
v Gear motor
CPB100003
v XF closing or MX opening
voltage releases
b Remote tripping function:
v MN voltage release
- Standard
- Adjustable or non-adjustable
delay
MX, XF and MN volage
releases
Gear motor
E46668
E46669
b Operation counter
b Escutcheon (Door sealing frame)
b Transparent cover for escutcheon
b Escutcheon blanking plate
CPB100015
A-3
Functions Circuit breakers
and characteristics
and switch-disconnectors
MVS08 to MVS40
Common characteristics
Number of poles 3/4
Rated insulation voltage (V) Ui 1000
Impulse withstand voltage (kV) Uimp 12
Rated operational voltage (V AC 50/60 Hz) Ue 690
Suitability for isolation IEC 60947-2 Yes
Degree of pollution IEC 60664-1 4
Basic circuit-breaker
CPB100000
Type of switch-disconnector
Operational current AC23A
Rated making capacity (kA peak) Icm
Rated short-time withstand current (kA rms) Icw 1s
3s
Maintenance/Connection/Installation
Service life Mechanical with maintenance
C/O cyclesx1000 without maintenance
Electrical without maintenance 440 V
690 V
Connection Horizontal
Switch disconnector. Vertical
Dimensions (mm) Drawout 3P
(H x W x D) 4P
Fixed 3P
4P
Weight (kg) Drawout 3P/4P
(approximate) Fixed 3P/4P
A-4
MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40
20 20 20 20 20 20 20 20
10 10 10 10 10 10 10 10
6000 6000 6000 6000 6000 5000 5000 5000
4000 4000 4000 4000 4000 2500 2500 2500
Yes
Yes
439 x 441 x 395
439 x 556 x 395
352 x 422 x 297
352 x 537 x 297
70/85 90/120
40/50 60/80
A-5
Functions Identifying ET range of
and characteristics
trip system
connected loads. units guarantees a high degree of reliability and immunity to conducted or
maintain continuity of service and optimize installation. On ET range, measurement functions are managed by an independent
CPB100011
Accessories
Certain functions require the addition of trip unit accessories, described on
page A-14.
Protection:
long time
+ short time
+ instantaneous
DB101118
Protection:
long time
+ short time
+ instantaneous
+ earth fault
A-6
Protection and measurement functions
ET ETA ETV
b Fault indications b I1, I2, I3, IN, Iearth-fault, and maximeter for b Incorporates all the rms measurements of ETA trip
b Settings in amperes and in seconds these measurements: unit, plus voltage readings:
v Fault indications v Calculates the current demand value
v Settings in amperes and in seconds v “Quickview” function for the automatic cyclical
display of the most useful values
2I
2I
2I
CDB500028
CDB500000
CDB500035
ETA2I
ET2I Trip System 2I
ET6G Trip System
long time
long time long time
long time
Ir .8
tr 8
alarm
alarm Ir tr alarm
alarm
.7
.9
(s)
(s) 4
12
.8 8
.7
.9
(s)
(s) 4
12
.6 .95 2 16
.6 .95 2 16
long time
.4
x In
1 .5
at 6 Ir
24 .4
x In
1 .5
at 6 Ir
24 Ir .8 tr 8
alarm
alarm
[Ir .7 .9 (s)
(s) 4
instantaneous [Ir 12
instantaneous
short time instantaneous .6 .95 2 16
Isd I i
4 5 8 10 .5 .98 1 20
3 6
2.5 6 12 .4 1 .5 24
4 x In at 6 Ir
[Ir
2 8 3 15 instantaneous
1.5 10 2 off
off instantaneous
x Ir x In I i
8 10
test 6
4 12
3 15
2 off
off
x In
test
test
ground fault
5S
5S
5S
CDB500001
CDB500030
CDB500029
long time
long time
Ir tr alarm
alarm long time
long time long time
long time
.7
.8
.9
(s)
(s) 4
12 Ir tr alarm
alarm Ir .8
tr 8
alarm
alarm
.8 8
.7
.9
(s)
(s) 4
12
.6 .95 2
16 .7
.9
(s)
(s) 4 12
.6 .95 2 16
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24 .5 .98 1 20 .5 .98 1 20
x In at 6 Ir .4 1 .5 24
[Ir .4 1 .5 24 x In at 6 Ir
4 5 (s)
(s) .4 .4 .3 8 10 short time instantaneous
Isd tsd I i
2.5 6 .3 4 12 3 6 6
2 8 .2 .1 3 15 2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12
.2 .1
on.1
10 0off 2 off
off 2 8 . 2 .1 3 15
2 8 3 15
1.5 2
on.1
x Ir
on I t x In .1 0off off
off 1.5 10 2 0off 2 off
off
1.5 10 on 2 2 on I t
on I t x In x Ir x In
test x Ir
test test
ground fault
6G
6G
6G
CDB500002
CDB500003
CDB500004
long time
long time
Ir tr alarm
alarm long time
long time
.7
.8
.9
(s)
(s) 4
8
long time
long time Ir tr alarm
alarm
12
alarm .8
8
Ir .8
tr 8
alarm .7
.9
(s)
(s) 4
12
.6 .95 2
16
.7
.9
(s)
(s) 4 12 .6 .95 2 16
.5 .98 1 20 .6 .95 2 16
.5 .98 1 20
.4 1 .5 24
.5 .98 1 20
x In at 6 Ir
[Ir .4 1 .5 24
.4 1 .5 24
x In at 6 Ir
short time instantaneous x In at 6 Ir
[Ir
short time instantaneous [Ir short time instantaneous
Isd tsd Ii short time instantaneous
(s) .4 .4 .3
4 5 (s) short time instantaneous
8 10 Isd
tsd I i
(s) .4 .4
.3
6
.3
.2
12
Isd tsd
(s) .4 .4
.3
(s) I i
3
6
2.5
.1
4
4
5
8 10
6
.3
.2
12
2 8 .2 3 15
.3 .2
6
2.5 4
2.5 6 4 12 8 .2 .1 15
on.1
off 2 3
1.5 10
on
2
I
t
0off 2 off
2
8 .2 .1 3 15 10 .1 2 0 2 off
off
x Ir x In
.1
2 0 off
off
1.5 on
on I
t off x In
10
on 2
x Ir
on I t off
setting delay test
test
1.5
x Ir x In setting delay test
test
tg
(s)
Ig
D E F (s) .4 .4
.3
setting delay test tg
(s)
(s) .4 .4
.3
test Ig
.3 .2 tg
(s) D E F
.4 .4
.3 .2
C G Ig
.2
.1
D E F (s) C G .3
B H
C G .3 .2 B H .2 .1
A I on.1 2 0off
on I
t off B H .2
.1 A I on.1 2 0off
ground fault on I
t off
ground fault A I on.1 2
0off ground fault
on I
t off ground fault
ground fault
ground fault
A-7
CDB500002
A ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
Type Description
Residual b The function determines the zero-phase sequence current, i.e. the
vectorial sum of the phase and neutral currents
b It detects faults downstream of the circuit breaker
Instantaneous protection
The Instantaneous-protection function protects the distribution system against solid
short-circuits. Contrary to the short-time protection function, the tripping delay for
long time
long time instantaneous protection is not adjustable. The tripping order is sent to the circuit
tr alarm
Ir
.7
.8
.9 (s)
(s) 4
8
12
alarm
breaker as soon as current exceeds the set value, with a fixed time delay of
.6 .95 2 16 7 20 milliseconds.
.5 .98 1 20
.4
x In
1 .5
at 6 Ir
24 Neutral protection
[Ir
short time
short time
instantaneous
instantaneous On three-pole circuit breakers, neutral protection is not possible.
Isd tsd Ii
3
4 5 (s) .4 .4 .3
(s)
6
8 10 On four-pole circuit breakers, neutral protection may be set using a three-position
2.5 6 .3 .2 4 12 switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
2 8 .2 .1 3 15
1.5 10 on.1 2 0off 2 off
off protection at Ir (4P 4d).
on I t x In
x Ir
setting delay test
test
Zone selective interlocking (ZSI)
Ig
D E F
tg
(s)
(s) .4 .4 .3 A ZSI(2) terminal block may be used to interconnect a number of control units to
C G .3 .2 provide total discrimination for short-time and earth-fault protection, without a delay
B H .2 .1
A I on . 1 2 0off before tripping.
on I t off
ground fault
ground fault
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
Fault indications
1 Long-time threshold and tripping delay.
LEDs indicate the type of fault:
4 Instantaneous pick-up.
b Earth fault (Ig)
Test
A hand-held test kit may be connected to the test connector on the front to check
circuit-breaker operation. For ET6G trip unit, the operation of earth-fault protection
(1) The thermal memory continuously accounts for the amount
of heat in the cables , both before and after tripping , whatever
can be checked by pressing the test button located above the test connector.
the value of the current(presence of an overload or not).The
thermal memory optimises the long-time protection function of
the circuit breaker by taking into account the temperature rise
in the cables .The thermal memory assumes a cable cooling
time of approximately 20 minutes.
(2) Refer to page D-5 for more details on ZSI.
A-8
Protection ET2I
Long time ET2I
DB101126
Current setting (A) Ir = In x ... 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 80 ms
Protection ET5S/ET6G
Long time ET5S/ET6G
DB101127
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Short time
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous
Pick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 off
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault ET6G
DB101128
Pick-up (A) Ig = In x … A B C D E F G H J
Accuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Note: All current-based protection functions require no auxiliary source.
The test / reset button, clears the tripping indication and tests the battery.
A-9
Functions Overview of functions
and characteristics ETA trip system
ETA trip units include all functions offered by ET trip “Ammeter” measurements
unit. In addition, they also offer measurements, display ETA trip units measure the true (rms) value of currents.
and current maximeters. They provide continuous current measurements from 0.2 to 1.2 In and are accurate
A digital LCD screen continuously displays the most heavily loaded phase (Imax) or
CDB500003
displays the I1, I2, I3, IN, Ig, stored-current (maximeter) and setting values by
The optional external power supply makes it possible to display currents < 20 % In.
Below 0.1 In, measurements are not significant. Between 0.1 and 0.2 In, accuracy
changes linearly from 4 % to 1.5 %.
Protection
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Short-time protection
b The short-time protection function protects the distribution system against
impedant short-circuits
b The short-time tripping delay can be used to ensure discrimination with
downstream circuit breaker
b The I2t ON and I2t OFF options enhance discrimination with a downstream
protection devices
b Use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve
14 13
v I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 lr. Above 10 lr, the time curve is constant
Earth-fault protection on ETA6G trip system
Residual earth fault protection.
long time
long time Selection of I2t type (ON or OFF) for delay.
Ir tr 8
alarm
alarm
.7
.8
.9 (s)
(s) 4 12 A ground fault in the protection conductors can provoke local temperature rise at
.6 .95 2 16 7 the site of the fault or in the conductors. The purpose of the ground-fault protection
.5 .98 1 20
.4
x In
1 .5
at 6 Ir
24 function is to eliminate this type of fault.
[Ir
short time instantaneous
Isd
short time
tsd Ii
instantaneous Type Description
4 5 (s) .4 .4 .3
(s) 8 10
3 6 Residual b The function determines the zero-phase sequence current, i.e. the
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15 vectorial sum of the phase and neutral currents
1.5 10 on.1 2 0off 2 off
off b It detects faults downstream of the circuit breaker
on I t x In
x Ir
setting delay test
tg
test
Instantaneous protection
(s)
Ig
D E F (s) .4 .4 .3 The Instantaneous-protection function protects the distribution system against solid
C G .3 .2
B H .2 .1 short-circuits. Contrary to the short-time protection function, the tripping delay for
A I on.1 2 0off
instantaneous protection is not adjustable. The tripping order is sent to the circuit
on I t off
ground fault
ground fault
breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
4 Instantaneous pick-up.
11 Digital display.
Overload alarm
12 Three-phase bargraph and ammeter.
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
13 Navigation button to view menu contents.
(1) The thermal memory continuously accounts for the amount b Overload (long-time protection Ir)
of heat in the cables , both before and after tripping , whatever b Short-circuit (short-time Isd or instantaneous li protection)
thermal memory optimises the long-time protection function of b Internal fault (Ap)
A-10
Protection ETA2I
Long time ETA2I
DB101126
Current setting (A) Ir = In x ... 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 80 ms
Protection ETA5S/ETA6G
Long time ETA5S/ETA6G
DB101127
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Short time
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous
Pick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 off
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault ETA6G
DB101128
Pick-up (A) Ig = In x … A B C D E F G H J
Accuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Ammeter ETA2I/ETA5S/ETA6G
Type of measurements Range Accuracy
Instantaneous currents I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %
Ig (ETA6G) 0.2 x In to In ± 10 %
Current maximeters of I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %
Note: All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
A-11
Functions Overview of functions
and characteristics ETV trip system
Short-time protection
b The short-time protection function protects the distribution system against
impedant short-circuits
b The short-time tripping delay can be used to ensure discrimination with
downstream circuit breaker
b The I2t ON and I2t OFF options enhance discrimination with a downstream
protection devices
b Use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve
v I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 lr. Above 10 lr, the time curve is constant
Earth-fault protection on ETV6G trip system
15 14 Residual or source ground return earth fault protection.
13 A ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
long time
Ir
long time
.8 tr 8
alarm
alarm Type Description
.7 .9 (s)
(s) 4 12 b The function determines the zero-phase sequence current, i.e. the
Residual
.6 .95 2 16 7
.5 .98 1 20 vectorial sum of the phase and neutral currents
.4 1 .5 24
b It detects faults downstream of the circuit breaker
x In at 6 Ir
[Ir
short time instantaneous
short time instantaneous
Isd tsd Ii Instantaneous protection
3
4 5 (s) .4 .4 .3
(s) 8 10
6
2.5 6 .3 .2 4 12 The Instantaneous-protection function protects the distribution system against solid
2 8 .2 .1 3 15 short-circuits. Contrary to the short-time protection function, the tripping delay for
on.1
1.5 10 2 0off 2 off
off
x Ir
on I t x In instantaneous protection is not adjustable. The tripping order is sent to the circuit
test
setting
tg
delay
test breaker as soon as current exceeds the set value, with a fixed time delay of
(s)
Ig
D E F (s) .4 .4 .3 20 milliseconds.
C G .3 .2
B H .2 .1 Neutral protection
A I on.1 2 0off
on I t off
On three-pole circuit breakers, neutral protection is not possible.
ground fault
ground fault On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
Fault indications
10 Indication of tripping cause.
LEDs indicate the type of fault:
11 Digital display.
b Overload (long-time protection Ir)
Trip history
(1) The thermal memory continuously accounts for the amount The trip history displays the list of the last 10 trips. For each trip, the following
of heat in the cables , both before and after tripping , whatever indications are recorded and displayed:
the value of the current(presence of an overload or not).The b the tripping cause: Ir, Isd, Ii, Ig or Auto-protection (Ap) trips
thermal memory optimises the long-time protection function of Battery power
the circuit breaker by taking into account the temperature rise
The fault indicating LEDs are powered by an in-built battery. The fault indication
in the cables .The thermal memory assumes a cable cooling
time of approximately 20 minutes. LEDs remain on until the test/reset button is pressed.
(2) Refer to page D-5 for more details on ZSI. Test
A hand-held test kit may be connected to the test connector on the front to check
circuit-breaker operation. For ETV6G trip unit, the operation of earth-fault protection
Note: ETV trip units come with a transparent leadseal cover as can be checked by pressing the test button located above the test connector.
standard.
A-12
Protection ETV2I
Long time ETV2I
DB101126
Current setting (A) Ir = In x ... 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 80 ms
Protection ETV5S/ETV6G
Long time ETV5S/ETV6G
DB101127
Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
Tripping between 1.05 and 1.20 x Ir
Time setting tr (s) 0.5 1 2 4 8 12 16 20 24
Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory 20 minutes before and after tripping
(1) 0 to -40 % - (2) 0 to -60 %
Short time
Pick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350
(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500
Instantaneous
Pick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 off
Accuracy: ±10 %
Time delay Max resettable time: 20 ms
Max break time: 50 ms
Earth fault ETV6G
DB101128
Pick-up (A) Ig = In x … A B C D E F G H J
Accuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250 A 500 640 720 800 880 960 1040 1120 1200
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Time delay (ms) tg (max resettable time) 20 80 140 230 350
at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500
Energy ETV2I/5S/6G
Type of measurements Range Accuracy
Instantaneous currents I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %
Ig (ETV6G) 0.2 x In to In ± 10 %
Current maximeters of I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %
Demand currents of I1, I2, I3, Ig 0.2 x In to 1.2 x In ± 1.5 %
Voltages V12, V23, V31, V1N, V2N, V3N 100 to 690 V ± 0.5 %
Note: All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
A-13
Functions ET range of trip system
External sensors
DB101524
b Output voltage: 24 V DC ±5 %, 1 A
b Ripple < 1 %
External 24 V DC power supply module. b Overvoltage category: as per IEC 60947-1 cat. 4
Spare parts
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
PB100775-32
b It is impossible to modify settings using the keypad unless the settings lockout pin
Test equipment
Hand-held test kit
The hand-held mini test kit may be used to:
CDB500038
b Check operation of the control unit and the tripping and pole-opening system by
sending a signal simulating a short-circuit
b Power source: standard LR6-AA battery
A-14
Connections
Overview of solutions and accessories
PB104354A40
EasyPact MVS fixed and drawout devices.
Vertical
PB104355A40
Mixed
PB104359A40
Note: EasyPact MVS circuit breakers can be connected indifferently with bare-copper, tinned-
copper and tinned-aluminium conductors, requiring no particular treatment.
A-15
Functions Accessories and auxiliaries
and characteristics
DB101149
DB101149
barriers
Optional Optional
Safety shutters
DB101153
Standard
Safety shutters
E46460
locking blocks
Optional
Door interlock
E46452
Optional
Pushbutton
E46666
E46666
locking device
Optional Optional
OFF position locking
CDB500039
CDB500039
Optional Optional
“Disconnected”
E46451
position locking
Optional
ON/OFF indication
E46689
E46689
contacts(OF)
Standard Standard
Additional ON/OFF
E46689
E46689
indication contacts(OF)
Optional Optional
“Fault trip” indication
CDB500040
CDB500040
contact(SDE)
Standard Standard
A-16
Type of accessory EasyPact MVS08 to MVS40
Fixed breaker Drawout breaker
Rear connection Rear connection
“Connected, disconnected,
E46661
test position”
indication
contact(CE,CD,CT)
Optional
“Ready to close”
E46438
E46438
contact(PF)
Optional Optional
Escutcheon(CDP)
CDB500061
CDB500061
Standard Standard
Mechanical operation
DB125617
DB125617
counter(CDM)
Optional Optional
Escutcheon
E46670
E46670
blanking plate
Optional Optional
Auxiliary
E46458
terminal shield(CB)
Optional
Transparent
E46669
cover (IP54)
Optional
A-17
Functions Locking
and characteristics On the device
CDB500006
1 Reset button for mechanical trip indication.
2 OFF pushbutton.
3 OFF position lock.
4 Door interlock.
5 ON pushbutton. ET6G
ET6G
Trip Syste
System
Trip
m
9 Operation counter.
.2 0off x In test
2.5 8 .1 2
I t
test
2 10 on
on
1.5 Ir delay
x
setting tg . 4 .3 2
(s)
(s) .4 .
Ig D
E F .3 .1
G
C H
. 2 off
0off
B
on.1 2
I t
I on
A fault
ground
fault
ground
The transparent cover blocks access to the pushbuttons used to open and close
the device.
It is possible to independently lock the opening button and the closing button.
The locking device is often combined with a remote operating mechanism.
The pushbuttons may be locked using either:
b Three padlocks (not supplied)
b Lead seal
Access to pushbuttons protected by transparent cover. b Two screws
Profaulx Ronis
This option discharges the springs before the breaker is removed from the chassis.
Door interlock.
A-18
On the chassis
interlock
The “connected”, “disconnected” and “test” positions are shown by an indicator and
are mechanically indexed. The exact position is obtained when the racking handle
blocks. A release button is used to free it.
“Disconnected” position locking by padlocks or keylocks
VSPD
Mounted on the chassis and accessible with the door closed, these devices lock the
circuit breaker in the “disconnected” position in two manners:
4 b Using padlocks (standard), up to three padlocks (not supplied)
8 b Using keylocks (optional), one or two different keylocks are available
1 Profalux and Ronis keylocks are available in different options:
7 5 b One keylock
6 b Two identical key locks - one keylock mounted on the device + one identical
2
3 keylock supplied separately for interlocking with another device
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux).
1 Door interlock.
3 Padlock locking.
6 Racking-handle entry.
position.
7 Release button.
8 Racking-handle storage.
CPB100006
“Disconnected” position locking by keylock. Remove the key(s) The crank cannot be inserted.
A-19
Functions Indication contacts
and characteristics
Following tripping, the mechanical indicator must be reset before the circuit breaker
PB100818-16
SDE MVS
Supplied as standard 1
Breaking capacity (A) Standard Minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240/380 5
AC12/DC12 480 5
690 3
V DC 24/48 3
125 0.3
250 0.15
A-20
Remote operation
Remote ON / OFF
A point-to-point solution for remote operation of The remote ON / OFF function is used to remotely open and close the circuit breaker.
b An electric motor MCH equipped with a “springs charged” limit switch contact CH
v A closing release XF
PB104349A68
v An opening release MX
A-21
Functions Remote operation
and characteristics Remote ON / OFF
The electric motor automatically charges and recharges the spring mechanism when
the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible
following opening. The spring-mechanism charging handle is used only as a backup
if auxiliary power is absent.
The electric motor MCH is equipped as standard with a limit switch contact CH that
signals the “charged” position of the mechanism (springs charged).
Characteristics
Power supply V AC 50/60 Hz 100/130 - 200/240 - 380/415
V DC 24/30 - 48/60 - 100/125 - 200/250
Operating threshold 0.85 to 1.1 Un
Consumption (VA or W) 180
Motor overcurrent 2 to 3 In for 0.1 s
Charging time Maximum 4 s
Operating frequency Maximum 3 cycles per minute
CH contact 10 A at 240 V
Characteristics XF MX
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480
V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un
Consumption (VA or W) Hold: 4.5 Hold: 4.5
Pick-up: 200 (200 ms) Pick-up: 200 (200 ms)
Circuit-breaker response time at Un 70 ms ±10 50 ms ±10
Maximum number 1
Breaking capacity (A) Standard Minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240/380 5
AC12/DC12 480 5
690 3
V DC 24/48 3
125 0.3
250 0.15
A-22
Remote tripping
The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on
the release, it is impossible to close the circuit breaker, either manually or electrically.
Any attempt to close the circuit breaker has no effect on the main contacts. Circuit
breaker closing is enabled again when the supply voltage of the release returns to
85% of its rated value.
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480
V DC 24/30 - 48/60 - 100/130 - 200/250
MN voltage release. Operating threshold Opening 0.35 to 0.7 Un
Closing 0.85 Un
Consumption (VA or W) Pick-up: 200 (200 ms) Hold: 4.5
MN consumption Pick-up: 200 (200 ms) Hold: 4.5
with delay unit (VA or W)
Circuit-breaker response time at Un 90 ms ±5
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
056422N
A-23
Functions Source-changeover systems
and characteristics Mechanical interlocking
A-24
Accessories
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with manual and electrical control functions.
This option is compulsory for all the source-changeover systems.
Escutcheon CDP
DB101173
Standard equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP 40 (circuit breaker installed free standing: IP30) .
It is available in fixed and drawout versions.
Optional equipment mounted on the escutcheon, the cover is hinged and secured by
a screw. It increases the degree of protection to IP54, IK10. It adapts to drawout
devices.
A-25
Installation
recommendations
EasyPact MVS Installation recommendations
Temperature derating
B-1
Installation Operating conditions
recommendations
Ambient temperature
CDB500008
EasyPact MVS devices can operate under the following temperature conditions:
b The electrical and mechanical characteristics are stipulated for an ambient
temperature of -5°C to +60°C
b Circuit-breaker closing is guaranteed down to -35°C
Storage conditions are as follows:
ET6G
ET6G
Trip
Trip
System
System
b -40 to +85°C for a Easypact MVS device without its control unit
long
long
time tr
time
(s) 4
(s)
8 12
16
alarm
alarm
MVS08
IEC
N
60947-2
50/60H
b -25°C to +85°C for the control unit
Ir .8 .9.95 2 20
1 24
.6.7 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
6
shorttime tsd .4 .4 .3
time
short (s)
(s) .2 4 15
3 off
Isd
3
4 5 .3 .1 2
off
6
8
. 2 0off x In test
2.5 .1 2
I t
test
2 10 on
on
1.5 Ir delay
x
setting tg .4 .3 2
(s)
(s) .4 .
Ig
E F .3 .1
G
CD H
.2 off
0off
B
on.1 I2t
I on
A fault
groundfault
ground
(m)
2000
Altitude
At altitudes higher than 2000 metres, the modifications in the ambient air (electrical
CDB500011
N
MVS08
Electromagnetic disturbances
CDB500012
N
MVS08
Ir
.6.7
.5
Isd
2.5
Ig
2
3
long
long
.8 .9
.4 x In
4 5
1.5 Ir
CD
x
10
setting
E F
6
8
1
G
time tr
time
.95
.98
H
(s) 4
(s)
tg
2
1
.3
on
on
(s)
2
.1
(s) .4
.3
.2
8 12
on.1 I2t
16
.5 at 6IrIr
shorttime tsd .4 .4 .3
short
time
(s)
(s)
2
I t
delay
.4 .3.2
.1
off
0off
20
24
.2
.1
0off
alarm
alarm
instantaneous
Ii
4
3
instantaneous
2
8 1012
15
off
off
x In test
test
IEC
60947-2
50/60H
B-2
Installation in switchboard
Possible positions
CDB500013
CDB500014
CDB500015
Trip System
System
ET6G Trip
ET6G
N
MVS08
alarm
alarm 50/60H
time tr 60947-2
long
long
time 8 12 IEC
(s) 4
(s) 16
Ir .8 .9 2 20
.95
1 24
.6.7 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
6
shorttime tsd .4 .4 .3
time
short (s)
(s) .2 4 15
3 off
Isd
3
4 5 .3 .1 2
off
6
8
. 2 0off x In test
2.5 .1 2
I t
test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3.2
(s) .4
Ig
E F .3 .1
G
CD H
.2 off
0off
B
on.1 I2t
I on
A fault
groundfault
ground
Power supply
EasyPact MVS devices can be supplied either from the top or from the bottom
without reduction in performance, in order to facilitate connection when installed
in a switchboard.
CDB500016
Trip System
System
ET6G Trip
ET6G
N
MVS08
alarm
alarm 50/60H
60947-2
long
long
time tr
time 8 12 IEC
(s) 4
(s) 16
Ir .8 .9 2 20
.95
1 24
.6.7 .98 .5 at 6IrIr instantaneous
.5 instantaneous
1
.4 x In Ii 8 1012
6
shorttime tsd .4 .4 .3
time
short (s)
(s) .2 4 15
3 off
Isd
3
4 5 .3 .1 2
off
6
8
. 2 0off x In test
2.5 .1 2
I t
test
2 10 on
on
1.5 Ir delay
x
setting tg
(s) .4 .3.2
(s) .4
Ig
E F .3 .1
G
CD H
.2 off
0off
B
on.1 I2t
I on
A fault
groundfault
ground
CDB500018
Trip System
System
System
ET6G Trip Trip
System
Trip
ET6G ET6G
ET6G
N
MVS08 N
MVS08
alarm
alarm 50/60H 50/60H
alarm
alarm
time tr 60947-2 60947-2
long
long
time 8 12 IEC time tr 8 12 IEC
(s) 4
(s) 16 long
long
time
.8 .9.95 (s) 4 16
Ir
.7
2 20
Ir .8 .9.95 (s)2
1 s .7 20
24 s
.6 .98 .5 at 6IrIr instantaneou 1 24
instantaneous .6 .98 .5 at 6IrIr instantaneou
.5 1 instantaneous
.4 x In Ii 8 1012 .5 1
6 .4 x In Ii 8 1012
shorttime tsd .4 .4 .3
time 6
shorttime tsd .4 .4 .3
time
short (s) .2 4 15
(s)
.1 3 off short (s) .2 4 15
Isd 4 5 .3 off (s)
.1 3 off
3 6
. 2
2
x In test
Isd
3
4 5
6
.3 2
off
0off
2.5 8 .1 2
I t
test .2 2 0off x In test
2 10 on
on 2.5 8 .1 I t test
delay 2 10 on
on
1.5 Ir delay
x 1.5 Ir
setting tg . 4 .3 2 x
(s) .4 . setting tg . 4 .3 2
(s) (s)
(s) .4 .
Ig D
E F .3 .1
G
. 2 off Ig D
E F .3 .1
0off G
C H
on.1 2 .2 off
0off
I t C H
B I on
B
on.1 2
I t
A fault
I on
A fault
ground
fault
ground ground
fault
ground
Mounting on rails.
B-3
Installation Installation in switchboard
recommendations
Partitions
DB101434
Sufficient openings must be provided in partitions to
ensure good air circulation around the circuit breaker;
Any partition between upstream and downstream
connections of the device must be made of
nonmagnetic material.
For high currents, of 2500 A and upwards, the metal
supports or barriers in the immediate vicinity of a
conductor must be made of non-magnetic material A.
Metal barriers through which a conductor passes must
not form a magnetic loop.
Busbars
DB117045
DB101436
The mechanical connection must be exclude the
possibility of formation of a magnetic loop around
a conductor.
Interphase barrier
CDB500041
DB101439
453
B-4
Door interlock catch
DB117044
CDB500034
Mounted on the right or left-hand side of the chassis,
this device inhibits opening of the cubicle door when
the circuit breaker is in “connected” or “test” position.
It the breaker is put in the “connected” position with the
door open, the door may be closed without having to
disconnect the circuit breaker.
Dimensions (mm)
Type (1) (2)
MVS08-40 (3P) 215 215
MVS08-40 (4P) 330 215
DB102194
83
103
Note: Dimensions are in mm.
B-5
Installation Control wiring
recommendations
24 V DC power-supply module
Note: Wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be
connected to earth at both ends.
B-6
Power connection
Cables connections
DB101448
DB101449
If cables are used for the power connections, make
sure that they do not apply excessive mechanical
forces to the circuit breaker terminals.
For this, make the connections as follows:
b Extend the circuit breaker terminals using short
bars designed and installed according to the
recommendations for bar-type power connections:
v For a single cable, use solution B opposite
v For multiple cables, use solution C opposite
b In all cases, follow the general rules for connections
to busbars:
v Position the cable lugs before inserting the bolts
v The cables should firmly secured to the framework E
DB101450
Busbars connections
DB101451
DB101452
Electrodynamic stresses
The first busbar support or spacer shall be situated within a maximum distance from
the connection point of the breaker (see table below). This distance must be
respected so that the connection can withstand the electrodynamic stresses
between phases in the event of a short circuit.
Maximum distance A between busbar to circuit breaker connection and the first busbar
support or spacer with respect to the value of the prospective short-circuit current.
Isc (kA) 30 50 65
Distance A (mm) 350 300 250
B-7
Installation Power connection
recommendations
Clamping
DB101454
These values are for use with copper busbars and steel nuts and bolts, class 8.8. The
same torques can be used with AGS-T52 quality aluminium bars (French standard
NFA 02-104 or American National Standard H-35-1).
Examples
DB101455
DB101456
DB101457
1 Terminal screw factory-tightened to 16 Nm.
2 Breaker terminal.
3 Busbar. Tightening torques
4 Bolt. Ø (mm) Ø (mm) Tightening torques (Nm) Tightening torques (Nm)
5 Washer. Nominal Drilling with grower or flat washers with contact or corrugatec
6 Nut. washers
10 11 37.5 50
Busbar drilling
Examples
DB101458
DB101459
DB101460
Isolation distance
DB101461
Dimensions (mm)
Ui X min
600 V 8 mm
1000 V 14 mm
Busbar bending
When bending busbars maintain the radius indicated below(a smaller radius would
cause cracks).
DB101462
Dimensions (mm)
e Radius of curvature r
Min Recommended
5 5 7.5
10 15 18 to 20
B-8
Recommended busbars drilling
EasyPact MVS08 to MVS40
DB101464
DB101465
CDB500042
DB101474
CDB500054
CDB500055
CDB500043
DB101477
CDB500056
B-9
B-10
Temperature derating
Power dissipation
Temperature derating
The table below indicates the maximum current rating,
for each connection type, as a function of Ti around the
circuit breaker and the busbars.
For Ti greater than 60°C, consult us.
Ti: temperature around the circuit breaker and
its connection.
Power dissipation
Total power dissipation is the value measured at IN,
50/60 Hz, for a 3 pole or 4 pole breaker (values above
the power P = 3RI2). The resistance between input /
output is the value measured per pole (cold state).
B-11
Dimensions
and connection
EasyPact MVS Dimensions and connection
Accessories C-10
C-1
Dimensions MVS08 to MVS32 circuit breakers
and connection Fixed 3/4-poles device
Dimensions
DB101267
CDB500019
DB101270
Safety clearances
DB101271
CDB500020
DB101273
C-2
Connections
Horizontal rear connection Detail
DB101274
DB101276
DB101277
DB101278
Vertical rear connection Detail
DB101280
DB101287
DB101279
DB101282
View A detail.
C-3
Dimensions MVS08 to MVS32 circuit breakers
and connection Drawout 3/4-poles device
Dimensions
DB101289
CDB500021
DB101292
CDB500022
DB101295
C-4
Connections
Horizontal rear connection Detail
CDB500044
DB101297
DB101298
DB101278
Vertical rear connection Detail
CDB500045
DB101301
DB101307
DB101282
View A detail.
C-5
Dimensions MVS40 circuit breakers
and connection Fixed 3/4-poles device
Dimensions
CDB500019
DB101267
DB101270
DB101273
: Datum. A(*) An overhead clearance of 110 mm is required to remove the arc chutes.
C-6
Connections
Horizontal rear connection
DB101309
DB101276
Detail
CDB500049
DB101311
CDB500049
15
DB101315
400(3P)
DB101313
Detail
DB101287
DB101314
C-7
Dimensions MVS40 circuit breakers
and connection Drawout 3/4-poles device
Dimensions
DB101289
CDB500021
DB101292
DB101295
CDB500022
C-8
Connections
Horizontal rear connection
CDB500046
DB101297
Detail
CDB500050
CDB500050
DB101311
DB101315
15
400(3P)
DB101319
DB101314
View A detail.
Detail
DB101307
C-9
Dimensions Accessories
and connection
DB101360
Escutcheon
EasyPact MVS
Fixed device Drawout device
DB101365
DB101366
: Datum.
C-10
External modules
DB101367
DB101368
One conductor only per connection point.
DB102076
DB117025
C-11
Dimensions External modules
and connection
DB117024
DB117023
Installation
DB101386
DB101387
C-12
C-13
Electrical diagrams
EasyPact MVS
Electrical diagrams
D-1
Electrical diagrams Masterpact MVS08 to MVS40
Fixed and drawout devices
to-close
Ready-
Charged
Fault
Close
Stop
VN
V1
V2
V3
Open
ET trip system ETA/ETV trip system
U
E89955
NCT
E60065A
E46136A
E46137A
E60066A
E60067A
E89956
Z5 Z5 F2+ 84 D2 C2 A2 254 B2
Z3 Z4 T3 T4 Z3 Z4 T3 T4 VN 82 C3 A3 252 B3
Z1 Z2 T1 T2 Z1 Z2 T1 T2 F1 81 D1 C1 A1 251 B1
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
External sensor (CT). 1. MVS08 to MVS20: CT 400/2000;
2. MVS25 to MVS40: CT 1000/4000;
D-2
Indication contacts Chassis contacts
DB101409
44
34
24
14 144
134
124
114 834 824 814 334 324 314 934 924 914
42
32
22
12 142
132
122
112
832 822 812 332 322 312 932 922 912
41
31
21
11 141
131
121
111
831 821 811 331 321 311 931 921 911
Key:
D-3
Electrical diagrams EasyPact MVS
Earth-fault protection
Neutral Protection
DB125601
circuit for external neutral
VN
EasyPact MVS equipped with a ET/ETA/ETV 6G:
b Shielded cable with 2 twisted pairs
b T1 twisted with T2
b Maximum length 4 meters
b Cable cross-sectional area 0.4 to 1.5 mm2
b Recommended cable: Belden 9552 or equivalent
For proper wiring of neutral CT, refer to instruction
Bulletin 48041-082-03 shipped with it.
Do not remove factory-installed jumper between T1
and T2 unless neutral CT is connected.
If supply is via the top, follow the shematics. ET/ETA/ETV 6G
If supply is via the bottom, control wiring is identical; for
the power wiring, H1 is connected to the source side,
H2 to the load side.
For four-pole versions, for residual earth-fault
protection, the current transformer for the external
neutral is not necessary.
Shield Drain
External VN
Neutral CT
Neutral protection
b Three pole circuit breaker:
v Neutral protection is impossible
b Four pole circuit breaker:
v The current transformer for external neutral is not
necessary
D-4
Zone Selective Interlocking
DB101420
electrodynamic forces exerted on the installation by shortening
diagram above.
from downstream, the circuit breaker remains closed for the full
Fault 1.
Fault 2.
receives a signal from B and remains closed for the full duration
Wiring
v The common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)
D-5
Electrical diagrams EasyPact MVS
24 V DC external power supply
AD module
b The 24 V DC external power-supply (AD module) for the ET Trip system (F1- F2+)
DB128383
Note: In case of using the 24 V DC external power supply (AD module), maximum cable length
between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The internal voltage taps are connected to the bottom side of the circuit breaker.
D-6
D-7
Additional
characteristics
EasyPact MVS Additional characteristics
E-1
Additional Tripping curves
characteristics
DB105112
E-2
Earth fault protection (ET range of trip system - 6G)
DB101505
(1)
Ig = In x... A B C D E F G H I
In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In u 1250A 500 640 720 800 880 960 1040 1120 1200
E-3
Catalogue numbers
and order form
EasyPact MVS Catalogue numbers
and order form
Nomenclature F-2
Connection F-8
Clusters F-13
Instructions F-17
F-1
Catalogue numbers Nomenclature
and order form
Range Current rating Type Pole Operating mechanism Installation Protection No. Type
EasyPact MVS (from 800 to 4000A) Icu=Ics=Icw (1 sec)=50kA & 65kA
MVS 08 N 3 M F 2 L
10 H 4 N W 5 A
12
O 6 V
16 P 0 D
20 Q
25 R
32 S
40 T
3 2 1 1 1 1 1 1 11 digits
Type
L Basic protection
A Protection+current metering
V Protection+voltage metering
D Switch disconnector
Protections No.
2 LI protection
5 LSI protection
6 LSIG protection
0 No protection for switch disconnector
Type of installation
F Fixed
W Withdrawable/drawout
Operating mechanism
M Manually operated ACB/SD
N Electrical 200/240 VAC MCH + XF + MX
O Electrical 110/130 VAC MCH + XF + MX
P Electrical 380/415 VAC MCH + XF + MX
Q Electrical 200/250 VDC MCH + XF + MX
R Electrical 100/125 VDC MCH + XF + MX
S Electrical 48/60V DC MCH + XF + MX
T Electrical 24/30V DC MCH + XF + MX
Number of poles
3P 3 Poles
4P 4 Poles
Current rating
08 800A
10 1000A
12 1250A
16 1600A
20 2000A
25 2500A
32 3200A
40 4000A
Example 1 MVS32N4NW6L
MVS 32 N 4 N W 6 L
EasyPact 3200A 50kA 4 Pole Electrical operated Withdrawable LSIG protection Basic trip unit with LED indications
MVS 240V AC type
Example 2 MVS16H3MF0D
MVS 16 H 3 M F 0 D
EasyPact 1600A 65kA 3 Pole Manual operated Fixed No protection Switch disconnector
MVS
F-2
EasyPact MVS 800 to 4000A
EasyPact MVS fixed 50kA
1000A MVS10N3MF0D *
1250A MVS12N3MF0D *
1600A MVS16N3MF0D *
2000A MVS20N3MF0D *
2500A MVS25N3MF0D *
3200A MVS32N3MF0D *
4000A MVS40N3MF0D *
Electrical 800A MVS08N3NF0D *
240V AC(1) 1000A MVS10N3NF0D *
1250A MVS12N3NF0D *
1600A MVS16N3NF0D *
2000A MVS20N3NF0D *
2500A MVS25N3NF0D *
3200A MVS32N3NF0D *
4000A MVS40N3NF0D *
F-3
Catalogue numbers EasyPact MVS 800 to 4000A
and order form EasyPact MVS fixed 65kA
F-4
EasyPact MVS withdrawable 50kA
F-5
Catalogue numbers EasyPact MVS 800 to 4000A
and order form EasyPact MVS withdrawable 50kA
F-6
EasyPact MVS withdrawable 65kA
1000A MVS10H3MW0D *
1250A MVS12H3MW0D *
1600A MVS16H3MW0D *
2000A MVS20H3MW0D *
2500A MVS25H3MW0D *
3200A MVS32H3MW0D *
4000A MVS40H3MW0D *
Electrical 800A MVS08H3NW0D *
240V AC(1) 1000A MVS10H3NW0D *
1250A MVS12H3NW0D *
1600A MVS16H3NW0D *
2000A MVS20H3NW0D *
2500A MVS25H3NW0D *
3200A MVS32H3NW0D *
4000A MVS40H3NW0D *
F-7
Catalogue numbers EasyPact MVS
and order form Connection
Connection
3P 4P
Fixed circuit breakers
Horizontal mounting.
Installation manual MVS21735
Drawout circuit breakers
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
800-2000 A Vertical 47964 47965
E46445
Horizontal mounting.
Installation manual MVS21735
Connection accessories
Interphase barriers / Replacement kit (3 parts)
For fixed rear-connected circuit breaker 48599 48599
E46428
F-8
ET Trip System & accessories
CDB500057
Battery + cover
Battery (1 part) 33593
E95540
menu
External sensors
External sensor for earth-fault protection (TCE) / 1 part
Sensor rating 400/2000 A 34035
E46671
1000/4000 A
34036
DB105360
48-60 V DC
54441
100-125 V DC
54442
110-130 V AC
54443
200-240 V AC
54444
380-415 V AC
54445
CDB500038
F-9
Catalogue numbers EasyPact MVS
Remote operation
Gear motor
MCH (1 part)
E95172
AC 50/60 Hz 100/130 V
47893
200/240 V
47894
380/415 V
47896
DC 24/30 V
47888
48/60 V
47889
100/125 V
47890
200/250 V
47891
E95169
E95171
Fixed. Drawout.
Installation manual MVS21736
Closing release (XF)
E95170
DC 48/60 V DC, 48 V AC
33660
100/130 V AC/DC
MVS15511
200/250 V AC/DC MVS15512
380/480 V AC MVS15513
Terminal block (1 part) For fixed circuit breaker 47074
E95169
E95171
Fixed. Drawout.
Installation manual MVS21736
Opening release (MX)
Standard coil (1 part)
E95170
DC 48/60 V DC, 48 V AC
33660
100/130 V AC/DC
33661
200/250 V AC/DC
33662
380/480 V AC
33664
E95169
E95171
Fixed. Drawout.
F-10
Remote operation
Undervoltage release MN
Undervoltage release (1 part)
E95170
E95171
Fixed. Drawout.
Installation manual MVS21736
MN delay unit
MN delay unit (1 part)
E46694
R (non-adjustable) Rr (adjustable)
AC 50/60 Hz 48/60 V AC/DC 33680
DC 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33685 33682
380/480 V AC/DC 33683
Installation manual MVS21736
F-11
Catalogue numbers EasyPact MVS
and order form Chassis locking and accessories
Chassis locking
“Disconnected” position locking / 1 part
By padlocks
E46451
VCPO Standard
By Profalux keylocks
Profalux 1 lock with 1 key + adaptation kit 64934
2 locks 1 key + adaptation kit 64935
Profalux 1 lock+ 1 key (without adaptation kit) 42888
Profalux 2 locks + 1 key (without adaptation kit) 42878
Adaptation kit (without key locks) 48564
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 64937
2 locks 1 key + adaptation kit 64938
Ronis 1 lock+ 1 key (without adaptation kit) 41940
Ronis 2 locks + 1 key (without adaptation kit) 41950
Adaptation kit (without key locks) 48564
Installation manual MVS21737
Door interlock / 1 part
Right and left-hand side of chassis (VPECD or VPECG) 47914
E46452
4P 48596
4P 48723
F-12
Clusters
Clusters
1 disconnecting contact cluster for chassis (see table below) (part 1) 33166
E95538
Racking handle
Racking handle 47944
E95561
F-13
Catalogue numbers EasyPact MVS
and order form Circuit breaker locking and accessories
E46669
E46670
F-14
Mechanical interlocking for source
changeover
F-15
Catalogue numbers EasyPact MVS
Indication contacts
ON/OFF indication contacts (OF) / 12 parts
1 additional block of 4 contacts 47887
E46689
E46438
E46661
F-16
Instructions
Instructions
EasyPact MVS User Manual (English) MVS21734
Fixed & drawout circuit breaker MVS21735
Circuit breaker accessories MVS21736
Chassis accessories MVS21737
Interlocking of EasyPact MVS devices MVS21738
F-17
Catalogue numbers EasyPact MVS
To indicate your choices, check the applicable square boxes √ Indication contacts
OF - ON/OFF indication contacts
And enter the appropriate information in the rectangles Standard 1 block of 4 OF 10 A-240/380V AC
Additional 1 block of 4 OF 6 A-240/380V AC
SDE - “fault-trip” indication contact
Circuit breaker or switch-disconnector Quantity Standard 1 SDE 5A -240/380V AC
Optional
Rating A Carriage switches 8 A-240/380V AC
Circuit breaker N/ H CE - “Connected” position Max. 3 qty
Switch Disconnector NA/HA CT - “Test” position Max. 3 qty
Number of poles 3 or 4 CD - “Disconnected” position Max. 3 qty
Type of equipment Fixed Remote tripping MN - Under voltage release V
Draw out with chassis R - Delay unit (fixed time delay) 0.25s
Operating Mechanism Manual Operated Rr - Adjustable delay unit 0.5s……3s
Electrical Operated AD - External power-supply module V
MCH - Gear motor V TCE - External sensor (NCT) for neutral of 3 Phase-4 Wire systems 400/2000A
XF - Closing coil V TCE - External sensor (NCT) for neutral of 3 Phase-4 Wire systems 1000/4000A
MX - Shunt/Opening voltage release V PF - “Ready to close” contact 5A-240/380V AC
ET Range of Trip System Locks
ET- Without display 2I 5S 6G VBP - ON/OFF pushbutton locking (by transparent cover using padlock)
ETA - Current Metering 2I 5S 6G VSPO - Device locking in OFF position by key lock (Only one key lock per ACB possible)
ETV - Voltage Metering 2I 5S 6G Key lock kit (w/o key lock) Profalux Ronis
LR - Long-time rating plug Standard 0.4 to 1 Ir 1 key lock Profalux Ronis
Connection 2 identical key locks, 1 key Profalux Ronis
Horizontal Top Bottom Chassis locking in “Disconnected” position:
Vertical Top Bottom VSPD - by key locks Key lock kit (w/o key lock) Profalux Ronis
1 key lock Profalux Ronis
Trip System functions: 2 identical key locks, 1 key Profalux Ronis
2I : Basic protection (long time + inst.)
Notes:
Customer can provide only the reference no. of the product for the listed references. Kindly refer to product catalogue for list of references.
All breakers will be provided with 1 OF (4 c/o contacts), 1 SDE (trip contact), Escutcheon (Panel sealing frame) as standard.
All draw-out type devices will be supplied with Chassis & safety shutter.
For Electrical operated devices, indicate the voltage ratings of MCH,XF & MX
Refer to product catalogue for available voltage ratings of MCH/XF/MX/MN & AD Module
The orientation of customer connecting terminals can be changed at site from Horizontal to vertical or vice-versa.
F-18
© 2013 - Schneider Electric - All rights reserved.
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS 30323
F- 92506 Rueil Malmaison Cedex This document has been printed on ecological paper