3 Over Head Line Bay Protection: KALSEL-1 2 100MW Coal Fired Power Plant

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3
At a glance
Powered by AI
The document discusses the protection settings for the 150kV Tanjung existing substation. It provides details about the main protection unit, line characteristics, and fault current calculations for different lines.

The protection relay used for the main protection unit is Siemens Siprotec 7SL87.

Line 1 is the 5km line from KalseL to Tanjung substation. It uses ACSR 340/30 mm2 conductor with a rated current of 1,089A. The line impedances and parameters are provided.

KALSEL-1 2x100MW Coal Fired Power Plant

OHL BAY - MPU - GENERAL DATA

3 OVER HEAD LINE BAY PROTECTION

3.1 MAIN PROTECTION UNIT

3.1.1 MPU - PROTECTION RELAY DATA


Manufacturer : SIEMENS Device Type : Siprotec - 7SL87
Product Code : 7SL87-DAAA-AA0-0AAAA0-AK1111-12111B-BAF000-000AC0-CH1BA1-CE0

3.1.2 MPU - CT AND VT DATA


CT Ratio : 1,200 A / 1A VT Ratio : 150 kV/√3 / 110 V/√3
CT additional data Class : P X Pn : 30 VA
�_𝑖/�_𝑣= 〖�𝑎𝑡𝑖�〗
CT wire/cable data : 6 mm² 50 m Ti/Tv for Prim. to sec. conversion : 0.88 _�/ 〖�𝑎𝑡𝑖�〗 _�

3.1.3 MPU - LINE CHARACTERISTICS

LINE 1 (Protected Line) : KALSEL-1 Substation to TANJUNG Substation


Character convention for power flow : Export = positive
Conductor type and size : ACSR 340/30 mm2
Rated current of the conductor : 636 A Number of conductor / phase : 2
Rated current of the protected line : 1,089 A
Line Length : 5 km
Positive sequence Resistance R1 : 0.048Ω/km
Positive sequence Reactance X1 : 0.281Ω/km
Zero sequence Resistance R0 : 0.068Ω/km
Zero sequence Reactance X0 : 1.844Ω/km
Positive sequence Impedance Z1 : 0.285Ω/km 80.3 ° @ 5km: 1.4253 Ω
�_𝐿=�_𝐿+𝑗�_𝐿
Zero sequence Impedance Z0 : 1.846Ω/km 87.9 ° @ 5km: 9.2277 Ω
Positive sequence Capacitance C1 : 0.0130 μF/km
Zero sequence Capacitance C0 : 〖���〗 _3𝑃�=
0.0052 μF/km〖��〗 _3𝑃�/ 〖� 1 〗 _𝐿�𝑁� �𝑟 〖���〗 _�𝐿𝐺= 〖��〗 _�𝐿𝐺/ 〖� 1 〗

SIR3PH = 35.81958 Ω / 1.42527 Ω = 25.13 SIRSLG = 18.74712 Ω / 9.22771 Ω = 2.03


WITH THE ABOVE SIR VALUE, THIS LINE CONSIDERED AS SHORT LINE
Line contanst for Line 1 are from ATP-EMTP Line Check calculations, the project file and parameter input are the same as
the one used for KSL10-AE-SYTE-06-006 - 150kV Kalsel Switchyard Calculation (Insulation Coordination Study)

LINE 2 (Longest adjacent Line) : TANJUNG Substation to BUNTOK Substation


Line Length : 70 km
Positive sequence Impedance Z1 : 4.2 Ω + j 20.73 Ω = 21.15 Ω 78.5 °
Zero sequence Impedance Z0 : 18.28 Ω + j 86.19 Ω = 88.11 Ω 78 °
Relay at Line 2 Zone 1 or Zone 2 Time delay :

LINE 3 (Shortest adjacent Line) : TANJUNG Substation to PLTU MSW Remote Substation
Line Length : 5 km
Positive sequence Impedance Z1 : 0.59 Ω + j 2.03 Ω = 2.114 Ω 73.8 °
Zero sequence Impedance Z0 : 1.61 Ω + j 6.71 Ω = 6.9 Ω 76.5 °
Relay at Line 3 Zone 1 or Zone 2 Time delay :

KSL1E-AE-SYTE-06-003 PT. Graha Usaha Teknik....


150kV TANJUNG EXISTING SUBSTATION - CALCULATION (RELAY CALCULATION & COORDINATION)
Rev.A Page 1 of 3....
Line contanst for Line 2 and Line 3 are from PLN Study E-13_Laporan Final Kalseltengtim--Juli--_150313

KALSEL-1 2x100MW Coal Fired Power Plant


OHL BAY - MPU - GENERAL DATA

Circuit Breaker Characteristic O- 0.3 sec - CO - 3 min - CO

Tower general data Average tower base resistance : 10 Ω Total tower (incl. Gantry) : 17
Distance: Phase-to-tower/phase-to-ground (mid-span) : 3 m Effective Tower-Grounding Resistance
Distance: Phase-to-phase : 5 m due to the parallel connection : 0.59 Ω

3.1.4 MPU - POWER SYSTEM DATA

v Based on the source and line impedance, the minimum fault-current levels can be calculated as follows:

�_�𝐶=�_𝑟𝑎𝑡𝑒�/
(√3∙�_𝑡�𝑡𝑎� )

v For a 3-pole short circuit at the end of the line, Z total is calculated as follows:
| Ztotal | = Sum of synchronous source impedance and line impedance (since only the magnitude of the current
should be calculated, only the magnitude of the impedance is relevant)
| Ztotal | = | ( 1.787 Ω + 5 km x 0.048Ω/km ) + j( 35.775 Ω + 5 km x 0.281Ω/km )|Ω
= 37.24 Ω
Thus for 3-phase faults without fault resistance, there results a minimum fault current of:
150 kV
I3pol min = = 2,326 A
√3 x 37.24 Ω

v For 1-phase short circuits, Ztotal is calculated as follows:


| Ztotal | = 1/3 (sum of the positive-sequence, negative-sequence and zero-sequence source as well as line
impedance)
| Ztotal | = | 2 x [( 1.787 Ω + 5 km x 0.048Ω/km ) + j( 35.775 Ω + 5 km x 0.281Ω/km ) ] +
( 0.416 Ω + 5 km x 0.068Ω/km ) + j( 18.743 Ω + 5 km x 1.844Ω/km )| Ω / 3
= 1.60225 Ω + j 34.108 Ω = 34.15 Ω
For 1-phase short circuits without fault resistance, the minimum fault current is:
150 kV
I1pol min = = 2,536 A
√3 x 34.15 Ω

3.1.5 MPU - FUNCTION GROUP LINE

v The rated current (calculated for 2 unit) for the line to be protected is calculated as follows
283 MVA
Irated = = 1,089 A �_𝑟𝑎𝑡𝑒�=�/(√3∙�_𝑟𝑎𝑡𝑒� )
√3 x 150 kV

v The parameter X per length unit is used to configure the characteristic reactance per unit length of the line to be
protected, calculate the secondary setting value as follows: �_𝑠𝑒�^,= 〖�𝑎𝑡𝑖�〗 _�/ 〖�𝑎𝑡𝑖
�〗 _� ∙�_𝑝𝑟𝑖�^,
Xsec = 0.8800 x 0.281Ω/km = 0.2473Ω/km

arctan(�_𝐿/�_
v Line Angle 𝐿)
: 80.3 ° �_𝑟=�_𝑔𝑛�/�_𝑝ℎ �_𝑥=�_𝑔𝑛�/
=1/3∙(�_0/�_1 −1) �_𝑝ℎ

KSL1E-AE-SYTE-06-003 PT. Graha Usaha Teknik....


150kV TANJUNG EXISTING SUBSTATION - CALCULATION (RELAY CALCULATION & COORDINATION)
Rev.A Page 2 of 3....
v Residual compensation factor (scalar) : Kr : 0.14 Kx : 1.85

v Residual compensation factor (complex) : K0 : 1.83 K0 angle : 8.9 °

KSL1E-AE-SYTE-06-003 PT. Graha Usaha Teknik....


150kV TANJUNG EXISTING SUBSTATION - CALCULATION (RELAY CALCULATION & COORDINATION)
Rev.A Page 3 of 3....