Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manufacturing Data Sheet: Low Voltage XLPE Cable Design Code: LVIS09AXSWY2004C006SA002S Date: Rev No.

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Manufacturing Data Sheet: Low Voltage XLPE Cable

Design Code : LVIS09AXSWY2004C006SA002S


Date : Rev No. :

S.No Particulars 4 X 6 MM²

1 Name of Manufacturer Polycab Wires Pvt. Ltd


2 Type of cable A2XWY
3 Voltage Grade V 1100
4 No of cores X size in sqmm 4X6
5 Conductor
H2/H4 Grade Aluminium as per Class 1 of IS:
a) Material
8130/84,latest
Max. d.c. resistance of conductor at 20° C
b) 4.61
(ohm/km)
c) Shape of the conductor Solid Circular
6 Insulation
a) Material XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core Identification Red,Yellow, Blue & Black
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Minimum thickness (mm) 0.3
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal size of armour (mm) 1.40
9 Outer Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Thickness (mm) 1.24 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 5.91
(ohm/km)
b) Calculated Cable reactance (ohm/km) 0.0858
c) Impedance of cable (ohm/km) 5.91
d Approx. Cable Capacitance (mfd/km) 0.27
S.No Particulars 4 X 6 MM²

Maximum conductor temperature under


11 90°C
normal operating conditions
Maximum conductor temperature at the
12 250°C
termination of short circuit
Short Circuit rating of conductor for the
13 0.57
duration of 1 sec (kA)

14 Continuous Current carrying capacities :-


(a) In Ground at 30°C (A) 46
(b) In Air at 40°C (A) 42
IS 8130/84,IS 7098 Part I/88, IS 5831/84, IS
15 Applicable Standard
3975/88 etc. with latest up to date amendments

16 Nominal overall diameter of the cable in mm 17.5 ± 2.0

17 Minimum bending radius 12 times Overall diameter


18 Max. Tensile strength

(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm

ii) for Cables pulled with pulling eyes (N) 720


Standard Drum Length with ± 5% tolerance
19 1000 ± 5%
(m)
20 Non-Standard Drum Length mtrs Max. 5% Order Quantity
21 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE
XLPE , CABLE SIZE, CABLE TYPE WITH
22 Printing
SEQUENTIAL MARKING at every one meter
interval.
Note:-The values given above are subject to tolerances as per the relevant standards.