Fire Alarm System
Fire Alarm System
Fire Alarm System
RE - 104
1.2 General
The panel is self-contained with integral power supply and space
provision for two sealed lead-acid standby batteries and comply with
the requirements of IS 15908 : 2011. The panel functions are
microprocessor controlled and test and isolate functions are included.
Provision is made for a repeater function of panel status output. The
panel can accept, per zone, automatic detectors with a total
maximum loading of 2.4mA quiescent current rating (refer to chapter
2.2), and an unlimited number of manual call points.
Installation
The panel is easy to install and operate. The panel fascia is retained by
tamper-proof screws.
Fault Indication:
If the control panel indicates a Fault condition, make a note of all
illuminated indicators, refer to the chart on Page 23, and call the
service engineer.
Class – B wiring
Operating Nominal Voltage: 24 VDC
Hooter (NACs) output: 1A
End-Of-Line Resistor: 4.7K, 1/4watt
2.3.2 Controls
SILENCE Key: During fire/fault condition, silence key is used to
silence the external Sounders (NAC) and the internal buzzer
tone.
CURSOR KEYS: The cursor keys (Right / Left arrows) are used to
move the menu list and menu options.
ENTER Key: This key is used to enter into menu edit mode and
accept the changes of edited menu. This key also used for
lamp test in system normal condition.
MENU Key: This key is used to enter into the Main menu in the
LCD.
Installation Precautions
30 mm
290 mm
30 mm
185 mm
35 mm
175 mm
Place the panel in its mounting position and fix the panel to the
wall using the slots of the four screws. Ensure the enclosure and the
inner parts of the panel are given sufficient protection during
installation. All external cables are to be entered via the ∅19mm
preformed knockouts located at the top of the panel.
When the installation of all the cables has been completed, clean
the interior of the enclosure ensuring all masonry debris and drilling
swords are removed.
Standard Relay
The control panel provides three Form-C relays (2 for Fire & 1 fro Fault)
rated for 2.0 amps @ 30 VDC and 2.0 amps @ 30 VAC. Relay
connections are power-limited.
RESET Key: This key is used in only Fire Condition. The panel is reset
by pressing this key followed by password if enabled. During reset
condition, all the detector input voltages are cut off up to 3
seconds for Detectors and MCP’s, Then voltages are put on to the
loop.
ENTER Key: This key is used to check the all LED’s in panel is in good
condition with continuous buzzer tone in normal operating
condition. The same key is used to accept the selection of menu
and changes done in the menu.
CURSOR KEYS: The cursor keys (Right / Left arrows) are used to move
the menu list and menu options.
1. Zone 1
Enable
Normal: In the Normal Condition, SYSTEM ON, AC POWER ON, green LED will
be illuminated. There should be no other amber / red LED visual
indication or audible tone.
A.C POWER ON: This LED indicates the presence of main supply.
Whenever the Main Supply (220v A.C) is present this LED will glow.
Whenever the Main Supply (220v A.C) fails / fuse blown, the AC Power
on LED will OFF and it also indicated by fault Buzzer tone.
BATTERY ON: This LED indicates the presence of standby power supply.
Whenever the Main Supply (220v A.C) fails, the panel supply is
switched to standby power supply with BATTERY ON indication.
Whenever the backup battery fails / fuse blown, the battery fail is
indicated by LCD with fault Buzzer tone.
Note:
Whenever the backup battery voltage goes below the 21v, the
battery on LED will be blinking with toggle Buzzer tone.
Always the recent fired zone FIRE LED will blink continuously, rest of
the fired zone FIRE LED’s will glow constantly till it goes to RESET. The
FIRE LED indication will remain ON condition till the panel is RESET.
Note:
1. The Fire relay will be in ON condition till the fire and fault
LED’s go OFF.
1. Zon e 1 1. Zone 1
1. Zone 1
Enable d Zone Test
Default 1. Zone 1 1. Zone 1
D isa ble d W a lk T est
2. Zone 2
Note:
1. Use Cursor key ( ) to move the menu list previous or next
3. Zone 3 and to interchange the status of the menu.
2. Use Enter Key ( ) to select the menu list and conform the change of the status.
1. Zone 1
<Enabled>
Zone Test Mode: In this mode the zone is Tested for Fire,
Open, Short and Isolate automatically without disturbing
the normal operations.
Note1:
a. If there is no more testing, please ensure that the
zone is brought back to the normal Condition.
b. To bring back the zone loop to normal condition,
same procedure is followed as for the test.
c. If the zone is kept in Walk test mode for 10 minutes
with out any test the panel comes out of the walk
test mode automatically.
d. During test condition that the other zones that are
not in test mode fire will consider as actual fire.
4.3.5.2. Zone 2
From this menu, the zone 2 loop can configured as
enable, disable, Zone test and Walk test. The default
option is ‘Enable’. To change the options press ‘Enter’ key,
then change the options by using the left/ right cursor
keys. The Screen will be as shown below.
2. Zone 2
<Enabled>
4.3.5.3. Zone 3
From this menu, the zone 3 loop can configured as
enable, disable, Zone test and Walk test. The default
option is ‘Enable’. To change the options press ‘Enter’ key,
then change the options by using the left/ right cursor
keys. The Screen will be as shown below.
3. Zone 3
<Enabled>
4. Zone 4
<Enabled>
Enter Old
Password?
Enter New
Password?
Password
Updated
4.3.5.10. ZW Sounder
From this menu, the Zone wise Sounder can enabled
or disabled. By pressing the ‘Enter’ key from this menu the
option can be changed by using the Left / Right keys. The
default factory setting option is ‘disabled’.
After entering into the walktest mode, the fire relay contact
disablement is activated automatically and it will go back to
previous status while we are coming out from this mode.
This feature helps to perform the testing of devices by a
single person. In this mode if the panel detects any fire then
after 3 seconds the panel will get automatically silenced. After
6 seconds of silence, the panel will go to reset. This reset is
done for only that particular zone.
Once in Walktest Mode, the control panel will immediately:
Note:
a. If the other zone (Normal Zone) get triggered by actual fire, the FAP treat
as real fire and activates NACs and actuators.
b. The maintenance person should enter into the walktest mode in normal
condition of the panel.
c. If there is no more testing, ensure that the zone is brought back to the
normal Condition.
d. During in this mode, the Potential free Relay will not be activated while in
fire condition.
e. If there is no more testing for 10 minutes, the panel return back to normal
mode automatically.
5.3 Test:
This feature is used to test whether the LED and zone
card is working properly or not.
To test a particular zone, follow the procedure as below
1. Press the ‘menu’ key zone1 selects first.
2. Press ‘cursor’ key consequently until select the zone
which is to be test.
3. After selecting the zone press the ENTER KEY
4. After the ENTER KEY is pressed, Select the ‘Zone Test’
using the cursor key then press enter key, Open ,
Short & Fire test is Performed for that particular
zone.
Once the testing procedure is finished, the previous
conditions of the panel are retained.
A RS 485
B
_
24VDC
+ O/P
_
ZONE 4
+
_
ZONE 3
+_
ZONE 2
+
_
ZONE 1
+
_ 24VDC
Hooter
+ O/P
NC
Fault
NO
Relay
CO
NC
Fire
NO
Relay 2
CO
NC
Fire
NO
Relay 1
CO
_ 24VDC
Battery
+ I/P
P
230V AC
N
Input
E
DATE:
TEST CERTIFICATE
Serial No.:
WARRANTY CERTIFICATE
Serial No.:
Ravel Electronics warrants each product to be free from defects in material and
workmanship. This obligation is limited to servicing or part returned to the company for that
purpose and making good any parts thereof which shall be within warranty period, returned to the
company under a written intimation and which to the company’s satisfaction to be found defective.
The company reserves the right to decide the workplace for the repair work. The freight for
defective material will have to be borne by the purchaser, and the transit risk for such material will
rest with the purchaser.
This warranty will last for a period of 12 months from the date of Invoice of the product
from the factory. The warranty is applicable only if the product is used within its specifications.
The warranty for the replaced components will lapse along with that of the main product.
Authorised Signatory