SmartLoop Fire Panels
SmartLoop Fire Panels
SmartLoop Fire Panels
EN 54-4
0051-CPD-0225
0051-CPD-0226
0051-CPD-0227
0051-CPD-0228
0051-CPD-0231
0051-CPD-0232
SmartLoop
Analogue fire alarm control panel
Installation manual
Installation manual
Copyright
The information contained in this document is the sole property of INIM Electronics s.r.l. No part may be
copied without written authorization from INIM Electronics s.r.l.
All rights reserved.
Copyright
Installation manual
Table of contents
Copyright ............................................................................ 2
European directive compliance ............................................... 2
Table of contents.................................................................. 3
Chapter 1
1.1
1.2
1.3
1.4
1.5
1.6
Chapter 2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
Chapter 3
3.1
3.2
3.3
Chapter 4
4.1
4.2
4.3
4.4
Chapter 5
5.1
5.2
5.3
Chapter 6
6.1
6.2
6.3
Chapter 7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
Table of contents
Introduction......................................................................... 5
Application and use 5
Other parts of the system 7
In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance
with EN54-2 regulations: 8
About the SmartLoop fire alarm panel series 8
Description of the models 8
Features 9
Technical description........................................................... 16
Panel 16
The motherboard 16
LED panel 18
Technical specifications 19
Accessory devices............................................................... 21
Attachment boards 21
SmartLoop/PRN Printer 25
The SmartLetUSee/LCD and SmartLetUSee/LED Repeater panels 26
Installation ........................................................................ 27
Choosing the mounting location 27
Installation flow, guidelines and testing 27
Connecting the SmartLoop/PRN printer module 28
Connections....................................................................... 29
Note to the Installer regarding wiring and connection compliancy 29
About the circuitry 29
Loop Connections 29
NAC Outputs (Notification Application Circuit) 32
PL Terminal 32
AUX output 33
AUX-R output 33
3
Installation manual
7.8
7.9
7.10
7.11
7.12
7.13
7.14
7.15
7.16
7.17
7.18
Chapter 8
Alarm relay 33
Fault relay 33
Connecting devices to the RS485 BUS 33
Connecting the SmartLoop/NET module 35
Connecting the SmartLoop/INOUT Board 35
Connecting to a PC 36
Connecting a SmartLAN (or SmartLAN/SF) equipped control panel to a PC 37
Connecting a serial printer 37
Batteries 37
Connecting the thermal probe 38
Connecting the mains power source 39
8.1
8.2
Chapter 9
Maintenance ...................................................................... 42
Chapter 10
Troubleshooting ................................................................. 43
10.1
10.2
10.3
10.4
10.5
Appendix
Appendix
Appendix
Appendix
Appendix
A
B
C
D
D
Enea devices...................................................................... 46
Argus Devices .................................................................... 49
Apollo Devices ................................................................... 53
Order Codes ...................................................................... 57
Notes: .............................................................................. 58
Table of contents
Installation manual
Chapter 1
Introduction
Note:
The control panels described in this manual have been designed and developed to the highest standards of
quality, reliability and performance. All product components are capable to application requirements and
able to operate in compliance with the related technical specifications when the temperature external to
their casing complies with Category 3k5 of EN60721-3-3:1995.
Danger:
The GAS control function is not EN54-2 compliant, as this feature is not mentioned in the
aforesaid standard.
Danger:
In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance with EN542 regulations, all the manual alarm buttons and fire detectors employed in the system must
be associated with fire detection and alarm functions.
1.1
The SmartLoop analogue-addressable fire alarm panel manages up to eight loops. The SmartLoop is
capable of working in a network environment (maximum configuration 30 nodes arranged in a token ring).
The loops accommodate different types of fire-security devices (detectors, input and output modules,
callpoints, fire bells, etc.). The maximum loop wire length is 2000 m. The SmartLoop also provides
supervised outputs which guarantee full control of peripheral device functions (e.g. fire bells). The panel
identifies and signals alarm, pre-alarm, fault, early warning, bypassed zone, test and monitoring
conditions. The system status is indicated on the display and on the system status LEDs. The SmartLoop
panel supports up to 14 Repeater panels (accessory items) which replicate system signals/data and allow
building occupants with Level 2 authorization to silence and reset the system. The panel can also be
connected to a PC or printer.
The self-addressing feature and reduced-complexity point programming allow fast and easy installation.
E
B
C
PSTN
line
Internet
D
Figure 1 - Example configuration: 6 node token-ring network layout (Hornet)
Introduction
Installation manual
[A] Loop
All the peripheral devices of the system must be connected in parallel to the loop circuit (2 pole STP). The
loop is a closed electrical circuit in which a wide variety of alarm devices can be accommodated. Opening or
closing the circuit at any point will generate a fault signal. The loop circuit communication path starts on
the Loop-Out terminals and ends on the Loop-In terminals. The panel controls and communicates with the
loop devices via digital protocol. The loop utilizes the same two poles for the power supply to the system
devices and the two-way communication channel. The loop accommodates:
1. Detectors: A smoke detector is an active fire protection device that detects smoke or flames and
issues an alarm thereby alerting building occupants to the danger of fire. Detectors can be:
- Optical smoke detectors which look for the presence of visible by-products of combustion in the
detection chamber (Tyndall effect).
- Optical/Heat detectors which operate as per optical smoke detectors but also sense for increase in the
environment temperature. The combination of both sensing methods (smoke and heat) provides faster
detection and reduces the false alarm rate.
- Heat detectors: sense for an increase in the temperature in the protected environment. There are two
types of heat detector: Fixed temperature that signal alarm when the temperature exceeds the
predefined threshold; and Rate-of-rise which, as well as monitoring the predefined fixed temperature,
also respond to rapid increase in temperature.
- Ionization smoke detectors: feature a harmless radioactive source within a dual detection chamber.
They operate by sensing for a change in electrical conductivity across the detection chamber.
- CO detectors: sense the levels of carbon monoxide given off by all carbon-based materials in the
smoldering stages of a fire (often combined with heat detection sensor).
2. Input Module: a device which monitors the status of another device (callpoint, detector, etc.) and
sends the respective information to the panel. The Input module allows the loop to accommodate any
type of device.
3. Output Module: provides a supervised ancillary output. The cause of activation of this output can be
defined during the system configuration phase. The output module interfaces all types of loop devices
(bells, signaling devices, fire door magnets, etc.).
4. Callpoint: a clearly labeled fire button with instructions for use in the event of fire. Usually placed near
building entrances/exits. These push-button alarm-trigger devices allow building occupants to activate
system alarms.
5. Sounder/Flasher: audible/visual alarm signaling devices.
For the list of the devices the loop accommodates, and for details regarding their wiring and operating
principles, refer to Appendix A - Enea devices, Appendix B - Argus Devices and Appendix C - Apollo
Devices.
The loop circuit configuration (as required by the local Fire code in force) is a fault-tolerant circuit which, in
the event of short-circuit or loop interruption, allows the panel to continue to communicate and drive the
elements on either side of the interruption.
Isolator
In order to provide a fault-tolerant loop circuit that is Fire code compliant, isolator modules must be
installed in series with the loop circuit. Isolators modules detect short-circuit conditions and consequently
interrupt the loop circuit. If a short-circuit occurs, the two isolators adjacent to the shorted section will
open and split the loop in such way as to allow the panel to drive the elements on either side of the
interruption. No more than 32 detectors/devices should be installed between two isolator modules.
Note:
Many detectors/devices have built-in isolators and therefore do not require isolator modules. Refer to
Appendix A, Appendix B and Appendix C for further details.
Introduction
Installation manual
station. The device can be connected to the control panel loop via an input/output module (not included),
installed inside the box, or by means of the RS485 BUS, thus allowing the complete supervision of the
power station and control of the 3 outputs.
[D] SmartLine-EXT fire-extinction panel (optional)
SmartLine-EXT fire-extinction panels are based on SmartLine conventional fire detection panels (4-zones).
These control panels provide all the functions of SmartLine conventional fire-detection panels plus 1
SmartLetLoose/ONE extinction channel.
They interface with SmartLoop control panels via a built-in RS485 BUS. It is possible to programme the
SmartLine-EXT fire-extinction control panel to activate its functions in response to local data/signals
(conventional zones, extinguishant terminals, Stop extinction, etc.), or in response to remote data/
signals coming from the SmartLoop control panel.
[E] Sounderflashers
These audible/visual signaling devices connect to the control panel outputs and activate when specific
conditions occurs. The cause of activation (alarm, pre-alarm, early warning, etc.) can be defined during the
system configuration phase.
1.2
Introduction
Installation manual
1.3
All the manual alarm buttons and fire detectors employed in the system must be associated with fire
detection and alarm functions.
The functions associated with the programmable LEDs on the control panel frontplate (Keypad/Display
board and LED board), and on SmartLetUSee/LCD and Smart LetUSee/LED Repeaters must be set up in
accordance with the colour of the LEDs.
- Red: fire alarm
- Yellow: fault, test and disabled status
Note:
1.4
The GAS control function is not EN54-2 compliant, as this feature is not mentioned in the aforesaid
standard.
There are 3 expandable models (expandable to 8 loops by means of 3 SmartLoop/2L expansion boards). All
have 2 loops and are housed in the same sized enclosure. Each expandable model has a technicallydownsized version (in same-sized enclosure) with 1 loop for reduced complexity applications.
All models manage the same functions and support a full spectrum of hardwired and wireless devices.
The SmartLoop fire alarm panel series provides the following models:
SmartLoop1010/P - fully-equipped frontplate model with 1 loop
SmartLoop2080/P - fully-equipped frontplate model with 2 loops expandable to 8
SmartLoop1010/G - keypad and display model with 1 Loop
SmartLoop2080/G - keypad and display model with 2 loops expandable to 8
SmartLoop1010/S - flush front model with 1 loop
SmartLoop2080/S - flush front model with 2 loops expandable to 8
SmartLoop1010/P
SmartLoop1010/G
SmartLoop1010/S
SmartLoop2080/P
SmartLoop2080/G
SmartLoop2080/S
1.5
The /P model is equipped with a keypad, display, fault LEDs, fast buttons and a Zone status LED pad.
This model is suitable for locations where extended visual signals and manual control are necessary. This
model can be enhanced with the SmartLoop/PRN thermal printer (accessory item).
Introduction
Installation manual
The /G model is equipped with a keypad, display, fault LEDs and fast buttons and is suitable for
installation in locations where visual signals and manual control are necessary. This model can be upgraded
at any time after installation (for example, if moved to a location where extended visual signals and
manual control are necessary) by replacing its door with a /P model door that is enhanced with a Zone
status LED pad and thermal printer option.
The /S model has an unequipped door (no keypad, display or LEDs) and is suitable for installation in
locations where visual indications and manual control are not required (e.g. basements). This model can
be upgraded at any time after installation (for example, if moved to a location where visual signals and
manual control are necessary) by replacing its door with a /G model or /P model door.
1.6
-
Features
3
1
1
1
1
1
1
SmartLoop/2L loop expansion boards with 2 loops per board (2080 expandable models only)
SmartLoop/NET network board
SmartLAN or SmartLAN/SF board
SmartLoop/PSTN board
SmartLoop/INOUT Input/Output expansion board
SmartLoop/LED zone-status LED module (for /P models only)
SmartLoop/PRN thermal printer module (for /P models only)
Note:
Introduction
The 1010 non-expandable models with 1-loop have exactly the same features and components as the
2080 expandable models with 2-loops.
Installation manual
Chapter 2
General information
2.1
Documentation supplied
2.2
2.3
Manual details
Firmware information
2.4
Level 1
All building occupants can view the system status (active events) and events log and silence the panel
beeper.
Level 2
ONLY authorized keyswitch users and PIN users (5 digit codes) can Enable/Disable loop devices, bell outputs,
software zones and network devices, and SILENCE or RESET the system.
Level 3
ONLY authorized technicians, appointed by the Installer company can, by means of a screw driver, remove
the screws and open the fire control panel enclosure to insert the J2 Jumper and then, after entering a 5
digit PIN (5 digit code) access the parameter programming phase and/or carry out maintenance work (for
example, change the battery, replace fuses, etc.).
Level 4
ONLY authorized technicians, appointed by the Manufacturer can, by means of special tools, carry out
repair work on the motherboard (for example, repair or replace SM components).
Note:
10
General information
Installation manual
2.5
The information contained in this document is private property. All rights reserved
No part of this document may be copied or reproduced unless expressly authorized in writing by INIM
Electronics, in particular the parts regarding the device specified in paragraph 4.1 Panel.
2.6
Disclaimer
INIM Electronics s.r.l. shall not be responsible for damage arising from improper application or use.
This control panel should be handled by qualified personnel only. Installation must be carried out strictly in
accordance with the instructions described in this manual, and in compliance with the local fire code in
force.
2.7
Recommendations
INIM Electronics recommends that the entire system be tested on a regular basis (refer to paragraph 2.8
Testing the system).
2.8
This system has been designed to the highest standards of quality and performance. The system may fail
to function as intended due to the failure of a component. Most problems which prevent a fire control
system from operating as intended can be found by regular testing and maintenance of the system devices
(refer to Chapter 9 - Maintenance).
Testing should include all detectors, signaling devices and any other operational devices that are part of the
system.
2.9
In order to provide adequate protection and instructions for proper use, you (the installer) must be familiar
with the operating procedure of this device. As the only individual in contact with system users, it is your
responsibility to instruct them on how to use this system properly and to bring to their attention that every
fire is different in the amount of smoke and rate of burning. Therefore, smoke and heat detectors may not
provide timely warning of fires caused by violent explosions, escaping gas or improper storage of
inflammable materials.
Regardless of its capabilities, a fire alarm system is not a substitute for the necessary precautions building
occupants must take to prevent or minimize the harmful effects of fire.
2.10
Technical support
Our professional engineers are readily available to assist you. Call our phone number and you will be
connected right away to a person who will answer all your questions and provide you with full technical
support.
2.11
Conventions
General information
11
Installation manual
Example
description
Refer to paragraph
Text in Italics
2.11.2 Graphic
conventions
<text>
#<CustomerCode>
Variable data.
[uppercase
letter] or
[number]
[A] or [1]
BUTTON
Note:
Attention:
The "Attention" prompts indicate that total or partial disregard of the procedure could
damage the connected devices.
Danger:
The danger warnings indicate that total or partial disregard of the procedure could injure the
operator or persons in the vicinity.
2.12
MADE IN ITALY
0051-CPD -0231
LBDTIN4ASLOOP11G
1010/G 02/2012
230V~ -15% + 10%
Alimentazione /
Power / Alimentacion
50/60 Hz
Consumo /
0.9 A
Consumption / Consumo
Isolamento /
Classe I
Isolation / Aislamiento
Approvato /
EN54-2, EN54-4
Approved / Aprobado
0051
0051
0051
0051
09
0051 - CPD - 0228
Control and signalling system with integrated
power-source.
SmartLoop/1010-S
09
0228
0051 - CPD - 0231
Control and signalling system with integrated
power-supply device.
SmartLOOP/1010-G
SmartLOOP/1010-S
09
0051 - CPD - 0232
Control and signalling system with integrated
power-supply device.
SmartLOOP/1010-P
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
12
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
General information
Installation manual
0051
0051
0051
0051
09
0051 - CPD - 0225
Control and signalling system with integrated
power-supply device.
SmartLOOP/2080-S
09
0051 - CPD - 0226
Control and signalling system with integrated
power-supply device.
SmartLOOP/2080-G
09
0051 - CPD - 0227
0228
Control and signalling system with integrated
power-supply device.
SmartLOOP/2080-P
SmartLOOP/1010-S
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Figure 4 - CE Mark
2.13
Warranty
INIM Electronics s.r.l. warrants the original purchaser that for a period of 24 months from the date of final
acceptance, the product shall be free of defects in materials and workmanship. The warranty applies only
to defects in parts and workmanship relating to normal use. It does not cover:
Improper use or negligence
Damage caused by fire, flood, wind or lightning
Vandalism
Fair wear and tear
INIM Electronics s.r.l. shall, at its option, repair or replace any defective products. Improper use, that is,
use for purposes other than those mentioned in this manual will void the warranty. For the full details and
conditions regarding the warranty, refer to the purchase order.
2.14
Safety laws
The aim of the instructions in this section is to ensure that the device is installed and handled properly. This
chapter contains vital information. The installer should be familiar with this section and bring each item to
the attention of the system users.
2.14.1 Compliancy
The design and manufacture of the SmartLoop panel comply with EN 54-2 Fire detection and signaling
systems - Control and signaling panels.
The design and manufacture of the power supply comply with EN 54-2 Fire detection and signaling systems
- Power supply devices.
13
Installation manual
1. When removing or handling the boards, hold the board edges only.
2. Do not touch the electronic components, the printed circuits or the metal parts of the connectors.
3. Do not hand the module to another person without first ensuring that you both have the same
electrostatic potential. This can be achieved by simply shaking hands.
4. Place the board on an anti-static surface or a conductor surface with the same potential.
Further information regarding procedures relating to safety when working with electronic devices can be
found in Directive IEC 60147-0F.
Disposal
Do not burn used electronic devices, or allow them to pollute the environment (countryside, rivers, etc.).
Electronic devices must be disposed of in a safe environment-friendly way. In order to avoid short-circuits,
take all the necessary precautions when removing used batteries. Contact your local municipal offices for
information regarding the disposal of batteries.
14
General information
Installation manual
Chapter 3
Device management
3.1
This device is safely packed inside a cardboard box, however, care must be taken to avoid accidental
damage during handling. Cartons/boxes should be placed in such a way as to avoid knocks and falls, and
special care must be taken to protect the devices from extreme heat and/or cold.
3.2
Environmental conditions
Temperature limits:
-10 / +55C for transport and storage
-5 / +40C operating temperature
3.3
Take due care when unpacking the product, and dispose of all waste packaging in accordance with the local
method of disposal.
The cardboard box contains the SmartLoop control panel (enclosure in metal).
Note:
3.3.1
All waste packaging must be disposed of in full respect of the local laws in force.
The 2032 lithium battery guarantees data retention. This battery must be fitted properly into
its housing (refer to paragraph 4.2 - [H]) with the + sign towards you.
In order to validate the IMQ-SECURITY SYSTEMS certification and comply with EN 54-4
requirements, installation of a thermal probe is essential.
Be sure you have this item on hand before starting the installation procedure.
Device management
15
Installation manual
Chapter 4
Technical description
4.1
Panel
E
D
A
C
F
B
G
E
Figure 5 - Overview
[A]
[B]
[C]
LED panel
[D]
[E]
[F]
[G]
Data label
4.2
SmartLoop/P only
All models
The motherboard
The SmartLoop motherboard has a 32 bit microprocessor that controls all the control panel functions, and
2 peripheral microprocessors (one per loop) that manage communications with the system peripherals.
INIMs R & D professionals have developed and designed the SmartLoop motherboard using groundbreaking new generation fire technologies that ensure maximum precision and performance. Deployment
of the most advanced reflow technology ensures high-noise immunity and extreme accuracy. Each
connection terminal is protected against electrical surges and is high-noise immune capable. All terminals
on the motherboard are clearly marked and easily identifiable.
The motherboard has been especially designed to accommodate with ease the various SmartLoop
attachment boards.
16
Technical description
Installation manual
G
F
B
Q
R
A6
A5
A4
A3
A2
A1
Connector for the connection with the display board (located on the frontplate)
[B]
[C]
[D]
[E]
[F]
[G]
Memory jumper (if removed and the panel is switched Off, the system will restore to factory default settings)
[H]
[I]
[J]
[K]
[L]
[M]
[N]
[O]
[P]
[Q]
[R]
[S]
Technical description
17
Installation manual
[T]
PL
PL and GND terminals for disconnected-battery signalling In the event of primary and
secondary power failure (mains and batteries), the PL terminal will connect to GND. Under
normal operating circumstances, the PL terminal is disconnected.
[U]
AUX
24V output for the external power load, protected by a 1.8A self-resettable fuse
[V]
AUX-R
24V output for external loads, protected by a 1.8A self-resettable fuse (with "Power Cutoff"
during reset.) Suitable for powering devices which require power loss in order to reset (e.g.
beam detectors)
[W]
RS485
REPEATER
[X]
ALARM
RELAY
[Y]
FAULT
RELAY
[Z]
FAULT OUT
[A1]
ALARM NAC
[A2]
NAC1,
NAC2,
NAC3
[A3]
LOOP2-I
[A4]
LOOP2-O
[A5]
LOOP1-I
[A6]
LOOP1-O
4.2.1
The loop status LEDs (paragraph 4.2 - [B] and paragraph 4.2 - [C]) provide visual information relating to
the communications between the control panel and its detectors. They indicate that the panel is
interrogating its devices, the protocol it is using and whether or not the interrogated devices have
responded.
The green LED on the right will flash each time a loop device responds. The control panel interrogates its
devices at regular intervals, starting from address 1 through to the last address (for information
regarding which devices can be connected to the loop, refer to Appendix A, Appendix B and Appendix C).
The red LED in the centre will blink each time a command is sent through the loop for a device using
either Enea (Appendix A) or Argus (Appendix B) protocol.
The red LED on the right will flash each time a command is sent through the loop for a device using
Apollo (Appendix C) protocol.
Under normal operating conditions, the red LED (relating to the protocol in question) will blink rapidly and
the green LED will flicker indicating the device response. The flickering phase depends on the number of
devices connected to the loop. The more devices the longer the LED will flicker.
4.3
LED panel
SmartLoop/P control panel models are equipped with a LED panel (located on the front of the control panel
enclosure) which is connected to the keypad/display board (paragraph 4.1 - [C]).
This panel has 48 red LEDs which provide one or more signals (configured during the programming phase).
The On/Off logic of each LED can be set up individually.
18
Technical description
Installation manual
4.4
Technical specifications
Operating voltage
0.9 A @ 230Vac
27.6 Vdc
4A
MAX 1%
Max current available for the external load (loop devices, external
loads, attachment boards, etc.)
2.8 A
600 mA
200mA
80 mA
1A
Battery specifications
12 V @ 7Ah or 12 V @ 17Ah
2.2 Ohm
Operating temperature
From -5 to +40 C
48 x 47 x 13.5 cm
8 Kg
stby:40mA MAX:300mA
stby:20mA MAX:60mA
stby:200mA MAX:200mA
stby:40mA MAX:80mA
stby:0 MAX:1A
Technical description
19
Installation manual
Motherboard
Loop output terminals
1.3 A MAX
RS485 BUS
1.8 A MAX
AUX, AUX-R
1.8 A MAX
1% MAX
PL
SmartLoop/INOUT
on each CH
PIN code to access default settings
20
0.9 A MAX
00004
Technical description
Installation manual
Chapter 5
Accessory devices
5.1
Attachment boards
[B]
1 SmartLoop/NET network board for the creation of a control panel network environment (Hornet
technology)
[C]
[D]
[E]
SmartLoop/P models also accommodate the SmartLoop/PRN thermal printer (to be located on the
frontplate). This device provides real-time printouts and enquiry printout.
Refer to the respective paragraphs for the board descriptions.
5.1.1
All expandable SmartLoop control panels have 2 on-board loops expandable to 8 by means of 3
SmartLoop/2L expansion boards. The non-expandable SmartLoop 1010 version have 1 loop only.
The loops accommodate either 126 or 240 fire detection/signalling devices, depending on the selected
protocol (refer to Appendix A, Appendix B and Appendix C).
Due to electrical incompatibility, different brand devices (i.e. devices using different protocols) cannot coexist on the same loop. However, the loops can be programmed separately in such way as to allow the
system to manage different brand devices on different loops.
Accessory devices
21
Installation manual
[B]
[C]
[D]
[E]
[F]
[G]
[H]
[I]
Screw locations
refer to paragraph
4.2.1 Loop status LED
[A]
5.1.2
The SmartLoop/NET board allows you to create a token-ring capable of managing 30 SmartLoop control
panels via a 3 -pole cable.
The network must be wired as a ring network with a maximum cable length between each panel of 2000
metres, in this way, the network will be fault tolerant (HorNet technology). Using a supplementary 2-pole
cable (5 poles in all), you can create a protection ring which can pass alarm conditions, coming from a fire
control panel with microprocessor fault, through the ring.
[A]
[B]
[C]
[D]
[E]
[F]
[G]
[H]
[I]
Screw locations
I
B
Accessory devices
Installation manual
Danger:
In order to allow the ring to operate properly, the Port-B and Alarm-B terminals must be
connected to the successive Port-A and Alarm-A terminals.
5.1.3
The SmartLAN board connects to any Ethernet network and allows remote access (via Internet) to the fire
control system (allows connection to all the fire control panels in the token-ring network).
SmartLAN This board can send detailed e-mails for each event and real-time event reports over TCP/
IP. It provides a web server for web-based access to the system via browser (Internet Explorer, Firefox,
Opera, etc.).
This board allows you to carry out remote programming operations (upload/download), manage the
system via INIM's SmartLook software application and also manage Dynamic DNS.
SmartLAN/SF This board allows you to carry out remote programming operations (upload/download),
manage the system via INIM's SmartLook software application.
To access the configuration phase of the SmartLAN board, the default IP address is: 192.168.1.92
J
G
[A]
[B]
[C]
Ethernet port
[D]
[E]
[F]
[G]
[H]
[I]
[J]
Screw locations
[A]
Ethernet port
[B]
[C]
[D]
[E]
[F]
[G]
[H]
[I]
Screw locations
E
D
J
H
I
H
I
A
23
Installation manual
5.1.4
The SmartLoop/PSTN board allows the SmartLoop fire control panel to use the land line (PSTN). It
manages (and monitors) 2 lines and uses the most widely used reporting protocols (SIA, Contact ID, etc.).
It has an 8-slot audio memory for up to eight voice call messages. Completely managed by its on-board
microcontroller, it generates emergency calls in the event of a CPU fault, and also any alarm calls triggered
during the CPU fault.
[A]
[B]
[C]
L.B. Terminals for the backup line (a secondary line to be used in the
event of "primary line-down" conditions)
[D]
[E]
[F]
[G]
Yellow Line-engaged LED (goes On when the PSTN board hooks the
PSTN line)
[H]
[I]
[J]
Screw locations
J
D
H
J
I
5.1.5
The SmartLoop/INOUT board provides 6 outputs (CH1 - CH6). Each of these can be configured as:
Supervised output (NAC 1A max.)
Supervised input
Conventional detector line
Gas detector line
During the programming phase, you can program the events which will activate the outputs and the actions
generated by the inputs.
The SmartLoop/PSTN package includes:
4 anchor screws
4 spacers
Resistors and diodes
24
Accessory devices
Installation manual
D
E
[A]
[B]
[C]
Input/Output terminals
[D]
[E]
Screw locations
E
C
Figure 13 - The SmartLoop/PSTN board
5.2
SmartLoop/PRN Printer
The SmartLoop/PRN thermal printer module uses 82mm thermal roll paper and can be connected directly
to the motherboard (connector cable included). It provides a continuous real-time printout of events and/
or date to date enquiry printouts. It can also printout complete reports for each separate loop, containing
information related to the status of each detector/module (dust accumulation, loop communication quality,
real-time values, etc.).
A
B
D
F
C
E
[B]
[C]
[D]
[E]
[F]
Power supply terminals (24V DC) to be connected to the red and black wires of the cable (included)
[G]
25
Installation manual
5.3
The SmartLoop fire control panel supports 14 SmartLetUSee/LCD remote Repeater panels. These remote
panels can be connected to the RS485 bus on the motherboard by means of a 4-pole cable. Repeater
panels replicate all the SmartLoop fire system data and allow authorized personnel to access and control
the system in accordance with access authorization (access requires code entry).
The repeater motherboard is located on the frontplate of the device, therefore, when you open the repeater
enclosure the reverse side of the motherboard is on view. The following is a description of the parts used
during the installation phase:
A
C
SmartLetUSee/LCD
Front of module
[B]
SmartLetUSee/LCD
Back of board
[C]
DIP switches
[D]
RS485 Terminals
From the bottom of the figure to the top +24V - + GND; for the connection
to the RS485 BUS
[E]
EOL Terminals
These terminal are for the setting jumper and, depending on the position of the
setting jumper, indicate the position of the repeater in the system.
[F]
SmartLetUSee/LED Terminals
You can connect a SmartLetUSee/LED module to each SmartLetUSee/LCD module by means of the
connection wire supplied with the module. The SmartLetUSee/LED provides 48 zone-status LEDs. The On/
Off of each LED can be configured individually during the programming phase.
Note:
The SmartLetUSee/LED module can be used only in combination with a SmartLetUSee/LCD module.
Accessory devices
Installation manual
Chapter 6
Installation
Danger:
Installation of this fire control panel must be carried out in full respect of the local fire
codes, laws and bylaws in force, and in accordance with the instructions and guidelines
herein.
The cable glands must be rated UL94-V1 flame class (or higher)
6.1
6.2
6.2.1
DO NOT apply mains power until all connections have been completed.
Care must be taken not to drill in the vicinity of electrical wiring, heating ducts and
plumbing.
2. Remove the knockout of the cable entry you intend to use (you can choose from knockouts on the sides
of the enclosure or use one of the cable entries on the back).
3. Fit a cable gland (not included) to the wire entry.
4. Using wall plugs, attach the enclosure securely to the wall.
5. Pull the cables through the cable entry.
6. Connect ant attachment boards to the motherboard.
7. Connect the SmartLoop/PRN module (if used) to the motherboard (paragraph 5.2 SmartLoop/PRN
Printer)
8. Complete the connections.
Installation
27
Installation manual
6.2.2
6.3
1. Unscrew the nuts from the screws which secure the printer-housing protection plate in place (paragraph
4.1 - [D]) then remove the plate.
2. Working from the front of the enclosure (door closed), insert the Printer into its location.
3. Holding the printer module firmly in place, open the door of the enclosure and position the hooks on the
guide (paragraph 5.2 - [E]) , ensure that the module is firmly positioned.
4. Connect the printer wire to the terminals on the reverse side of the module (paragraph 5.2 - [F] and
paragraph 5.2 - [G]) and to the motherboard via the respective connector (paragraph 4.2 - [M]).
5. Use the cable ties and plastic cable hooks (included in the SmartLoop/PRN kit) where necessary on the
reverse side of frontplate (above the motherboard), in order to secure the connection wires firmly in
place.
28
Installation
Installation manual
Chapter 7
Connections
7.1
7.1.1
For a system that is EN54 compliant, no more than 32 sensors can be connected when this type of wiring is
used.
7.1.2
For a system that is EN54 compliant, an insulation module must be installed for each group of 32 detectors
(refer to Appendix A, Appendix B and Appendix C for information regarding the devices with built-in
isolators).
If you are using a 2 wire connection, no more than 32 detectors can be connected to the
loop.
If you are using a 4 wire connection, T junctions are prohibited, that is unless the maximum
number of devices that risk isolation during any type loop fault does not exceed 32.
If the system loop devices do not have built-in isolators, you must install an isolator for each
group of 32 detectors. Refer to Appendix A, Appendix B and Appendix C for further details.
All circuits should be wired using the local country Fire Code compliant method.
7.2
The fire alarm system circuitry is critical to the safety and well being of the building occupants. It is
considered an essential communication path during evacuation or relocation of persons during a fire or
emergency situation. During such an event, it is critical for fire safety equipment such as fire alarm
signaling equipment to remain operational for a specified amount of time. Therefore, all circuits are to be
wired using the local country Fire Code compliant method.
7.2.1
Guidelines
The fire alarm system circuitry must not be commingled without proper separation, and must be kept
separate from all other wiring.
Junction boxes are required at splice points. All Junction boxes must be installed using the local country
Fire Code compliant method.
Any wires/cables inside the SmartLoop enclosure must be secured to the cable hooks on the back box by
means of plastic cable ties or similar fittings.
The mains power supply cable must enter the control panel enclosure through the appropriate cable
entry and must not cross other conductors. The mains power supply cable must be secured to the cable
hook on the back box by means of a plastic cable tie.
7.3
Loop Connections
The loops accommodate a vast array of fire system devices (detectors, manual callpoints, fire buttons,
Input and Output modules, etc.).
For a detailed description of the devices the loop accepts, refer to Appendix A, Appendix B and Appendix C.
Due to electrical incompatibility, different brand devices (i.e. devices using different protocols) cannot coexist on the same loop. However, the loops can be programmed separately in such way as to allow the
system to manage different brand devices on different loops.
Connections
29
Installation manual
Note:
Each loop output conductor must be fitted with a split ferrite core (included), as shown in the figure below.
7.3.1
Loop terminals
LOOP1-O and LOOP2-O - loop output (paragraph 4.2 - [A4] and paragraph 4.2 - [A6])
Terminals + and : connect all loop devices in parallel to these terminals, in accordance with the
specific device instructions.
Earth terminal
Note:
LOOP1-I and LOOP2-I - loop input (paragraph 4.2 - [A3] and paragraph 4.2 - [A5])
Terminals + e : connect the loop return loop wiring to these terminals.
These terminals allow the panel to check the loop integrity. In the event of a single interruption on the
circuit, the panel will communicate with the isolated trunk elements via these terminals.
Earth terminal
Note:
7.3.2
Loop limitations
Use suitably sectioned shielded twisted cable for the loop wiring. Connect the shield to earth using the
earth terminals to one end of the loop only.
In order to allow the loop to function properly, you must section the device connection cable in such way
that any voltage drop along does not exceed 8 V. The following table shows the minimum dimensions for
the loop wiring with regard the distance between the loop output terminals and the most distant device:
30
up to 500 m
minimum 1 mm2
up to 1000 m
up to 1500 m
minimum 2 mm2
up to 2000 m
Connections
Installation manual
7.3.3
Il loop wiring can be completed with 2 wires (open loop) or 4 wires (closed loop) using 2 pole STP.
If you are using a 4 wire connection, connect the STP cable shield to one end of the loop and leave the
other end disconnected.
Connections
31
Installation manual
7.4
7.4.1
Alarm NAC
The ALARM NAC (paragraph 4.2 - [A1]) is a fuse-protected, supervised-silenceable output which is to be
connected to the alarm signalling devices.
This output will activate when FIRE ALARM conditions are detected. In the event of activation, the output
will supply a 24V current in accordance with the polarity indicated on the terminals.
During the STANDBY phase a low supervisory current with reverse polarity (with respect to the silkscreened indications on the motherboard) circulates on the line. The diodes (connected in series to the
loads) will direct the current to the EOL resistor which must be connected in parallel to the last device
(refer to Figure 21 - Wiring diagram of the ALARM NAC, FAULT OUT, NAC1, NAC2 and NAC3 outputs).
7.4.2
Fault output
The FAULT OUT (paragraph 4.2 - [Z]) is a fuse-protected, supervised-silenceable output which is to be
connected to the fault signalling devices (LEDS, etc.).
This output will activate when fault conditions are detected. In the event of activation, the output will
supply a 24V current in accordance with the polarity indicated on the terminals.
During the standby phase, a low supervisory current with reverse polarity (with respect to the silkscreened indications on the motherboard) circulates on the line. The diodes (connected in series to the
loads) will direct the current to the EOL resistor which must be connected in parallel to the last device
(refer to Figure 21 - Wiring diagram of the ALARM NAC, FAULT OUT, NAC1, NAC2 and NAC3 outputs).
7.4.3
The NAC1, NAC2 and NAC3 outputs (paragraph 4.2 - [A2]) are programmable generic outputs, protected
by a 1A fuse. They can be connected to various types of signaling and control devices (pressure valves, fire
doors, etc.).
These outputs will activate in accordance with programming. In the event of activation, the output will
supply a 24V current in accordance with the polarity indicated on the terminals.
During the standby phase, a low supervisory current with reverse polarity (with respect to the silkscreened indications on the motherboard) circulates on the line. The diodes (connected in series to the
loads) will direct the current to the EOL resistor which must be connected in parallel to the last device
(refer to Figure 21 - Wiring diagram of the ALARM NAC, FAULT OUT, NAC1, NAC2 and NAC3 outputs).
VIOLET
YELLOW
ORANGE
GOLD
Figure 21 - Wiring diagram of the ALARM NAC, FAULT OUT, NAC1, NAC2 and NAC3 outputs
7.5
PL Terminal
32
Connections
Installation manual
7.6
AUX output
The AUX output (paragraph 4.2 - [U]) provides a 24 V (max 1.3 A) power supply output for external loads
(ancillary devices).
This output is short-circuit protected by a resettable fuse. In the event of a short-circuit, the panel will
signal an AUX output fault.
7.7
AUX-R output
The AUX-R output (paragraph 4.2 - [V]) supplies a 24 V (max. 1.3 A) power supply (which is removed
temporarily during control panel reset) to external loads (ancillary devices) that must switch off in order to
reset (e.g. beam detectors).
This output is short-circuit protected by a resettable fuse. In the event of short-circuit, the panel will signal
an AUX-R output fault.
7.8
Alarm relay
The ALARM RELAY provides (paragraph 4.2 - [X]) a voltage-free contact which can switch loads of up to
5A (max. 30 V). This relay toggles its status in the event of panel fault.
Attention:
7.9
In order to validate the IMQ-SECURITY SYSTEMS certification, this output should not be used
as a type C and/or E and/or J and/or G output (EN 54-1), therefore, it must not be used to
command fire alarm devices and/or fire alarm transmission devices.
Fault relay
The FAULT RELAY provides (paragraph 4.2 - [Y]) a voltage-free contact which can switch loads of up to
5A (max. 30 V). This relay toggles its status in the event of panel fault.
Attention:
7.10
In order to validate the IMQ-SECURITY SYSTEMS certification, this output should not be used as a
type J output (EN 54-1), therefore, it must not be used to command Fault transmission devices.
The RS485 BUS accepts up to 14 repeater panels, 4 power stations and 4 SmartLine-EXT conventional
extinction stations.
POWER
STATIONS
EXTINCTION
STATIONS
SmartLevel
SmartLine-EXT
REPEATERS
SmartLetUSee/LCD
33
Installation manual
DIP
switch
position
DIP
switch
position
Attention:
ON
ON
ON
ON
ON
ON
ON
Address
10
11
12
13
14
ON
ON
ON
ON
ON
ON
ON
2. Ensure that the EOL jumper (paragraph 5.3 - [E]) is in the EOL position (End Of Line) on the last repeater
or power station on the line but not on other devices.
34
Connections
Installation manual
7.11
Use either 4-pole shielded twisted cable for the connections or Cat 5 STP cable for Ethernet connections. The
latter will allow you to wire the data communication ring and the emergency alarm ring.
In order to allow the ring to operate properly, the PORT-B and ALARM-B terminals must be
connected to the successive PORT-A and ALARM-A terminals.
The control panel uses an RS485 BUS for the HorNet ring node to node communications. The RS485 BUS
communicates at speeds of up to 57600 baud over distances up to 2000 metres between two nodes. The
SmartLoop/NET ports are opto-isolated, as without isolation the connection to the data acquisition
hardware to the target carries the potential for creating ground loops which will cause excessive noise in
the signal.
7.12
Each of the terminals on the SmartLoop/INOUT board can be configured in one of the following ways:
A
VIOLET
YELLOW
ORANGE
GOLD
WHITE
ORANGE
RED
Conventional
smoke
detector
Connections
Conventional
smoke
detector
GOLD
35
Installation manual
Gas
detector
4-20mA
BLACK
BROWN
RED
GOLD
SmartLoop
control panel
D
VIOLET
YELLOW
GREEN
BROWN
ORANGE
GOLD
ORANGE
GOLD
[B]
Conventional Zone
[C]
Gas Zone
[D]
Supervised Input
7.13
Lines configured as Gas Zone 4-20mA will generate an early warning signal if the value of the
detector output exceeds 12mA, and an alarm signal if the value of the detector output exceeds
16mA.
In order to implement the early warning signal, it must be enabled (during the programming
phase) on both the control panel and the zone the line belongs. The early warning signal will stop
automatically, if a gas detector exceeds the 12mA early warning threshold then returns below this
value without reaching the alarm threshold.
Connecting to a PC
If the connection is through the USB port, the system may ask for the installation driver when the USB
cable (LINKUSBAB accessory item) is first inserted. The driver is included in the SmartLeague software
programme which, once installed, can be found in the following folder:
C:\Program files\Inim\SmartLeague\Drivers\
36
Connections
Installation manual
7.14
In this case, the RS232 and USB port will not be available for use. Therefore, the PC must be connected
directly to the Ethernet port of the SmartLAN board or through a network switch by means of an inverted
patch-cord.
The default IP address is 192.168.1.92
Consequently the integrated Ethernet board of the PC must be configured with an IP of the same class (e.g.
192.168.1.46). Once the configuration phase is complete, you will be able to open your browser and enter
the SmartLAN board address:
http://192.168.1.92
7.15
7.16
If you intend disconnecting the serial printer from the RS232 port in order to connect a PC, it will be
necessary to DISABLE the serial printer before doing so. If you do not DISABLE the serial printer, the PC
will be unable to communicate with the panel.
Batteries
The panel enclosure provides housing for two 12 V/17 Ah internal batteries.
Use YUASA batteries, model NP 17 -12 FR or similar with UL94-V2 flame class (or higher).
Once powered up, the panel will recharge and monitor the batteries automatically, as follows.
4. Connect the battery wire connector (Figure 27 - [C]) to the control panel (paragraph 4.2 - [R]).
Attention:
Connections
37
Installation manual
7.17
Attention:
In order to validate the IMQ-SECURITY SYSTEMS certification and comply with EN 54-4
requirements, installation of a thermal probe is essential.
This panel has an on-board connector (paragraph 4.2 - [O]) for a thermal probe (accessory item). The
ProbeTH thermal probe regulates the battery-charge system by interacting with the battery temperature,
this operating method avoids battery damage.
1. Disconnect the batteries (if already connected).
2. Connect the thermal probe (Figure 27 - [D]) to the connecter (paragraph 4.2 - [O]) on the
motherboard.
3. Using a strip of strongly-adhesive insulating tape (Figure 27 - [E]), attach the Thermal probe to one of
the batteries, in such way as to a provide optimized heat-transfer measurements.
4. Using a thermometer, measure the probe temperature.
5. Using the graph Figure 28 - Voltage charge in relation to the battery temperature find the optimized
heat-transfer measurement for the charge.
6. Using a voltmeter, measure the voltage on the AUX terminals (paragraph 4.2 - [U]).
7. Adjust the trimmer (Figure 29 - [B]) on the switching power-supply (Figure 29 - [A]) to the value
indicated on the graph.
Volt
29
28,5
28
27,5
27
26,5
26
25,5
0
10
15
20
25
30
35
40
45
50
Connections
Installation manual
7.18
D
C
A
C
Danger:
The protective earthing system must be compliant with the local safety regulations, fire
codes, laws and bylaws in force.
Note:
As a further safety measure, the electrical system of the building must be protected against
overload and short-circuit.
The connection wires (to the electrical mains, and also any other wires inside the enclosure) must be
secured by means of plastic cable ties or similar fittings. Use cable with double isolation for the connection
to the electrical mains. Ensure that the switching power supply is properly earthed and, if you are installing
a SmartLoop/PSTN, ensure that the metal supports are tightly screwed in place, in accordance with the
instructions in this manual.
3. Insert and connect the two 12 V/17 Ah internal batteries (refer to paragraph 7.16.4 Connecting the
batteries).
Note:
Connections
A protective earth connection ensures that all exposed conductive surfaces are at the same electrical
potential as the surface of the Earth, in order to avoid the risk of electrical shock if a person touches a
device in which an insulation fault has occurred. In the event of an insulation fault, a protective earth
connection will generate a high fault current which in turn will trigger an over current protection device
(fuse) and disconnect the power supply.
39
Installation manual
Chapter 8
8.1
When you think you have the system completely wired, double check the integrity of the
wiring and ensure that the earth connection has been completed properly before powering
up.
Work carefully through the following steps, use a multimeter or similar tool for the electrical
measurements.
1. Check there is no electric current flow between the cables and earthing system.
For accurate measurement, remove the extractable terminal boards from the motherboard.
2. Check there is no electric current flow between the cable shields and earthing system.
For accurate measurement, disconnect the shields from the respective terminals by removing the
extractable terminal boards.
3. Check the wiring integrity of each NAC output.
For accurate measurement, remove the respective extractable terminal boards from the motherboard
and measure the cable resistance. Test both polarities, at least one of them must have the same
resistance as the EOL resistance.
4. Check all cables are adequately separated, bunched (by means of cable ties) and attached firmly to the
cable hooks on the back of the enclosure.
5. Check the proper polarity of the primary power supply connections (230 Vac) and ensure the wire is
attached firmly (by means of a cable tie) to a cable hook on the back of the enclosure.
6. Ensure that the connected repeater panel DIP microswitches have been properly set (refer to paragraph
7.10.1 Setting the devices connected to the RS485 BUS).
7. Ensure that the EOL jumper [figure 42] is in the EOL position on the last repeater panel only.
8. If several panels are connected in a token ring network, check the integrity of the ring, as follows:
9. extract the network terminal boards from the SmartLoop/NET board (refer to paragraph 5.1.2 The
SmartLoop/NET board) of one of the panels and check the continuity of wiring in the D+ circuit
(between the D+ poles of ports A and B), and in the D- circuit (between the D- poles of ports A and B).
8.2
First power up
1. Insert the jumper for programming-data storage (paragraph 4.2 - [G]); data storage is guaranteed by
the 2032 lithium battery.
2. Connect the two 17Ah batteries as described in paragraph 7.16.4 Connecting the batteries.
3. The panel will take several seconds to stabilize and the screen will show Resetting.
4.
The CPU FAULT LED on the frontplate will blink to indicate board activation.
5. If the connection with mains power supply is not detected within 2 minutes, the control panel will signal
a fault. Power the panel from the mains.
6. If at this point the panel signals other faults, check the wiring integrity and clear all faults before
continuing (refer to Chapter 10 - Troubleshooting).
40
Installation manual
7. Once all fault conditions have been cleared, turn the key in the keyswitch to access Level 2 (refer to
paragraph 2.4 Operator classification - Access Levels) then press RESET. The display will show:
SmartLoop In Service
No Alarm
No Fault
11/11/11 06:23 Fri
Figure 30 - Message on display on first startup
8. Press the TEST button to check the integrity of the LEDs.
41
Installation manual
Chapter 9
Maintenance
The following operations must be carried out regularly.
1. Using a damp lint-free cloth, remove any dust that may have gathered on the control panel enclosure.
Attention:
2. Push the TEST button to check the proper operating capability of the LEDs and buzzer.
3. Check the battery efficiency and change them if necessary.
4. Check the integrity of all wires and connections.
5. Ensure that there are no insects inside the control panel.
6. Carry out maintenance on the smoke detectors (clean the outside and the detection chamber).
Note:
42
Points 1 and 2 can be carried out by authorized persons, whereas all other points must be carried out by
qualified technicians.
Maintenance
Installation manual
Chapter 10
Troubleshooting
10.1
Using a multimeter or similar tool, check the voltage on the terminals. During normal operating conditions
(standby status), the measurement should be around 15 V with reverse polarity with regard the silkscreened indications on the terminal board.
If the measurement is around 24 V with reverse polarity with regard the silk-screened indications on the
terminal board, then either the circuit does not end on the EOL resistance or there is an interruption on
the cable.
Check the integrity of the device connections and the EOL resistance on the last device.
Check the cable continuity.
If the measurement is around 0 V the cable is shorted.
Check the device connections and the various cable sections.
10.2
LOOP fault
If the Shorted Loop OUTwarning appears on the panel display, a short-circuit in the loop across the
Loop-O terminals and the first isolator has been detected.
Check the integrity of the connection wiring and the integrity cable in the first section of the loop.
If the Shorted Loop-I warning appears on the panel display (for loops with 4-wire circuitry only), a
short-circuit in the loop has been detected in the section across the Loop-I terminals and their nearest
isolator.
Check the integrity of the connection wiring and the integrity of the cable in the last section of the loop.
If the Shorted OPENwarning appears on the panel display (for loops with 4-wire circuitry only), the
Loop continuity across the Loop-O and Loop-I terminals is interrupted. This may be caused by:
- An open isolator in the loop
Check all the isolators in the loop. At least one of the isolator LEDs will signal Isolated status. Once
you have traced the isolator in question, check the successive isolator on the loop which, very probably,
will also be open.
Check the integrity of the wiring in the section between the two isolators.
- Cable Interruption
Disconnect the Loop-I terminals of the panel.
Check the condition of the loop-device LEDs (blinking) until you find the point where the loop is interrupted.
Once the last device in proper working order has been identified, check the integrity of the wiring and
the cable in the successive section.
- Missing loop devices (the panel is unable to find some of the connected loop devices)
Search the loop for the missing devices. Once the missing devices have been identified, check the
integrity of the wiring and the address of each missing device.
- Duplicated address (an address has been assigned to more than one device)
Switch On the LED of the devices that signal duplicated address.
Search the loop for the devices concerned. Once the devices have been identified, check the address of
each device and rectify the error.
Loop status LEDs
- Check that the blinking Loop transmission LED (red) corresponds to the respective loop settings. If the
LED does not correspond, check the loop parameters.
- The green LED of each loop will blink each time an interrogated device responds. If this LED is On solid,
it means the device response is masked by an anomalous current flow through the conductive path
between the two poles of the loop.
Troubleshooting
43
Installation manual
Attention:
10.3
Ensure that only the system devices are connected to the loop.
If the display shows Repeater Lost, Power Stat. Lost, Ext. Stat. Lost , the panel is
unable to find any devices connected to the BUS.
Check that the device addresses have been assigned correctly (refer to paragraph 7.10.1 Setting the
devices connected to the RS485 BUS).
Check the integrity of the wiring and the connection polarity.
Check that the EOL jumper is in the EOL position only on the last repeater or power station connected to
the BUS.
Using a multimeter or similar tool for the electrical measurements:
- Measure the voltage across the +24 V and GND terminals of the RS485 BUS. If the voltage is below 20
V, the resettable protection fuse is open, therefore, the current draw of the devices connected to the
BUS is excessive.
- Disconnect the devices connected to the BUS one at a time until you find the cause.
10.4
Battery Fault
If the Battery lost message is shown, the batteries are either disconnected or have failed the battery
efficiently test.
Allow them to recharge for several hours. If the trouble persists, disconnect the batteries from the panel
and, using a multimeter or similar tool, measure them separately.
If only one of the batteries is below 12.5 V: replace the battery concerned and allow it to recharge for
several hours until fully charged.
If both batteries are below 12.5 V .13 V: replace both batteries and allow them to recharge for several
hours until fully charged.
If the battery is equipped with a thermal probe, check that the voltage value corresponds to the value
calculated with the assistance of the graph (paragraph 7.16.4 Connecting the batteries). If there is a
discrepancy in the value, correct it by means of the trimmer on the power supply module.
If the Low Battery message is shown, the primary power source (230 Vac mains power) is
disconnected. This condition must be cleared before the batteries get too low and are unable to power to
the system.
10.5
SmartLoopNET Fault
44
Troubleshooting
Installation manual
An address has been duplicated, that is, assigned to more than one panel.
Access the main menu from the panel. Select Programming, Configuration, View configuration,
Network
Check the address of each panel in the token-ring network and rectify the error.
Network circuit open
The token-ring network cabling must be closed properly otherwise the system will be unable to configure
properly.
Check the integrity of the ring cabling, as follows:
- Restore all the panels in the token-ring network to address O.
- Disconnect the network terminals of the SmartLoop/NET board of one of the panels, then check the
continuity of the wiring between the D+ poles of the A and B ports and between the D- poles of the
A and B ports and the two - poles (refer to paragraph 5.1.2 The SmartLoop/NET board).
If the emergency alarm loop is not used, it must be disabled via software, otherwise it will signal a
persistent fault condition.
Troubleshooting
45
Installation manual
Appendix A
Enea devices
All devices in INIM's new Enea series of addressable-analogue detection
devices are LPCB certified and carry the CE mark according to CPD.
Each device is equipped with a short-circuit isolator which, in the event
of short-circuit between two control-panel (loop) connection wires, is capable of interrupting the negative
wire and isolating the wire section concerned. Up to 240 devices can be connected. Each device is identified
by a factory-assigned serial number which allows automatic addressing.
INIM's Enea series provides three analogue detector models:
Optical chamber with sealed upper-part and 500 micron hole-diameter mesh insect screen
Three-colour LED - Red for alarm, Green flash for standby and for identification from the control panel;
Yellow for fault status
Supervised remote output configurable from the control panel
Automatic recognition of remote signaller connection
Drift compensation for sensor drift caused by dust in the chamber
Sensitivity selection for smoke and heat thresholds
Operating mode selection (for ED300 version) - Only smoke; Only heat
AND mode, OR mode, PLUS mode
Complete diagnostics - provides contamination level and real-time values
Memory of the smoke and temperature levels measured in the five-minute period prior to the last alarm
detected
Bypass plate on base guarantees continuity in the event of removal of the detector from the line
For further details regarding the precise features and technical specification of each device, refer to the
respective instructions booklet.
Type
Detectors
Bases
Modules
Manual
callpoint
LED
46
Model
Description
ED100
ED200
Heat detector
ED300
EB0010
Mounting base
EB0020
Relay base
ESB010
ESB020
EM312SR
Input/Output module
EM110
Input module
EM311
Micromodule
EM344S
EC0010
Manual callpoint
EC0010E
FI100
Enea devices
Installation manual
Sounder
Driver
A.1
ES0010RE
ES0020RE
ES0010BE
ES0020BE
ES0020
EITK1000
EITK-DRV
Driver for zones with IRIS series devices or loops with ENEA
series devices
EITK-BASE
EITK-PWSP
The distinct serial number of each detector is shown on the device information label. Manual addressing is
unnecessary as the addressing phase is automatic. To address devices, connect them to the loop and work
through the following steps.
Enea devices
47
Installation manual
Loop N.
ENROLL DEVICES
RE-ADDRESS ALL.
1 2 3 4 5 6 7 8
: . . . . . . . .
: . . . . . . . .
Once this operation is complete (this operation may take several minutes), a summary screen showing the
total number of devices found will be shown. Ensure that the number of devices found corresponds to the
number of devices actually installed.
Via PC: select the loop > Parameter Tab to select the type of protocol and wiring method, select the icon
and select Re-address loop.
Once this operation is complete (which may take several minutes), the software programme will design a
layout of the loop wiring showing all the connected devices.
A.2
This operation allows the system to read the serial number of each device on the loop and acquire its logic
address (from 1 to 240), assigned during a previous addressing operation.
Note:
This operation can be carried out only when dealing with a previously addressed loop (addressed via a
control panel or EITK-DRV loop driver).
A.3
This operation must be carried out each time a device is replaced or added to a previously configured loop.
After replacing or adding devices to the loop, work through the following operations.
From panel:
Adding/Replacing a device:
<key>,
Programming,
<code>, Configuration,
Modify
Configuration, Manual Configuration, Loop, select the loop, Add/Modify Point, select
the point and enter the serial number of the new or replacement device.
Removing a device: <key>, Programming, <code>, Configuration, Modify Configuration, Manual
Configuration, Loop, select the loop, Remove point, select the point and press to
confirm.
Via software application: select the loop from the tree structure, then select the icon
Update Loop option.
Once this operation is complete (which may take several minutes), the software programme will show a
double layout which will allow you to compare the previously-saved loop configuration with the new one.
The parts with changes will be highlighted.
In order to continue, you must accept all the highlighted changes by double-clicking on the icons which are not
green (or press the Accept ALL button), then press CONTINUE. A new addressing phase (which may take
several minutes) will transfer the new configuration to the control panel.
48
Enea devices
Installation manual
Appendix B
Argus Devices
Note:
The ARGUS devices accepted by this control panel do not have IMQ-SECURITY SYSTEMS certification, refer
to the instructions leaflet provided with each device.
All Argus Vega devices have built-in loop isolators. Therefore, isolators are not required. A short-circuit on
the loop will not provoke loss of any device.
Each detector is equipped with a 3-colour LED: green (periodic blinking) indicates the detector is working
properly (if enabled). Yellow indicates that the detector is not operating properly (fault) or has an open
isolator, whereas red indicates alarm status.
Detectors are equipped with test LEDs: if you hold a magnet near the detector base (near to the two
notches) the detector should generate an alarm signal.
B.1
Devices
Model
Name
Description
V100
V200
V350
VCP100
VWCP100
VMI100
Input module
VMMI100
Input Minimodule
VMDI100
VUMI100
Input Micromodule
VMC100
Output Module
VMMC100
VMDC100
VUMC100
Output Micromodule
VMC120
VMMC120
VMDC120
VUMC140
VMIC100
Input/Output Module
VMMIC100
VMDIC100
VMIC120
VMMIC120
VMDIC120
Argus Devices
49
Installation manual
VMCZ100
VMIC404
VLS100
VWLS100
VLS100-AV
VWLS100-AV
VLBE100
Intelligent Flasher
Loop-powered beacon
VTAO10
VTAOA10
VFI100
VPU100
Programmer
a. Configured as Rate-of-rise detector at default (alarm is triggered by rapid rise in temperature or when the temperature
exceeds the 54C alarm threshold). To configure as High temperature detector (Rate-of-rise feature bypassed and fixed
temperature set at 70C) use the VPU100 programmer. The panel will recognize the configuration criteria automatically.
B.2
Device Bases
Model
Name
Description
VB100
Base
VDBS100
Deep Base
BLR100
Relay Base
VBS100
VBLS100
B.3
Wireless devices
Model
Name
VW2W
Wireless Translator
SGWE
Wireless Expansion
SG100
SG200
SG350
SGRBS100
SGRBS100-AV
SGMI100
SGMC100
SGMCB100
SGCP100
Wireless callpoint
SGRS100
Wireless sounder
SGVA100
SGFI100
Description
Connected to Loop, 32-device interface (Sagittarius series SG) wireless to panel
The control panel sees the 32 devices as loop-connected
devices with different addresses
(a)
a. Configured as Rate-of-rise detector at default (alarm is triggered by rapid rise in temperature or when the temperature
exceeds the 54C alarm threshold). To configure as High temperature detector ( Rate-of-rise feature bypassed and fixed
temperature set at 70C) use the VPU100 programmer. The panel will recognize the configuration criteria automatically.
50
Argus Devices
Installation manual
B.4
Device Consumption
Device
B.5
in stand-by
in alarm
Detectors
90 PA
6 mA
Modules
120 PA
6 mA
Every ARGUS device requires an address to identify it in the loop. You can address ARGUS devices by
either using a VPU (Vega Programming Unit) or by means of the Auto-addressing option.
1.00
If you exit the screen using the Esc button, the setting WILL NOT BE SAVED!
Loop N.
ENROLL DEVICES
RE-ADDRESS ALL.
1 2 3 4 5 6 7 8
: . . . . . . . .
: . . . . . . . .
51
Installation manual
240 addresses are available. Address entry errors can be corrected by simply readdressing the device
(deletion not required).
5. Remove the detector from the VPU100 and fit it to its placement.
240 addresses are available. Address entry errors can be corrected by simply readdressing the device
(deletion not required).
5. Disconnect the VPU100 wires and reconnect the module to the Loop.
52
Argus Devices
Installation manual
Appendix C
Apollo Devices
Note:
The APOLLO devices accepted by this control panel do not have IMQ-SECURITY SYSTEMS certification,
refer to the instructions leaflet provided with each device.
Apollo devices are not equipped with built-in loop isolators (that is, unless otherwise specified). Therefore,
you must install loop isolators in such way as to avoid the loss of devices in the event of short-circuit.
C.1
Devices
C.1.1
Note:
XP95 series detectors are especially designed to operate with a sensibility of 55 (sensibility at default).
Sensibility adjustment should be made only when absolutely essential, as any change may lead to delays
in loop response time.
Model
Name
Description
55000-885
Smoke/Temperature detector
55000-600
55000-500
55000-400
55000-401
55000-640
55000-440
55000-540
C.1.2
Model
Name
Description
58000-600
58000-400
58000-700
58000-300
Discovery CO detector
58000-500
C.1.3
Note:
Xplorer series detectors are especially designed to operate with a sensibility of 55 (sensibility at default).
Sensibility adjustment should be made only when absolutely essential, as any change may lead to delays
in loop response time.
Model
Name
Description
59000-405
Heat detector
59000-406
Apollo Devices
53
Installation manual
59000-407
59000-415
Heat detector
59000-416
59000-417
59000-605
Smoke detector
59000-606
59000-607
C.2
Device bases
Model
Name
Description
45681-210
Base
45681-215
45681-321
45681-242
45681-250
45681-276
C.3
Accessories
Model
Name
Description
55000-720
XP95 Isolator
59000-700
XPlorer Isolator
55000-855
C.4
Callpoints
Model
Name
Description
55000-905
55000-906
55000-940
58000-910
58000-920
59000-910
C.5
Model
Name
Description
55000-278
Sounder
Loop-powered sounder
55000-274
45681-265
55000-877
Loop-powered beacon
45681-331
Loop-powered sounderflasher
54
Apollo Devices
Installation manual
C.6
Modules
Model
Name
Description
55000-809
Module with 1 input with delay and reset output for waterflow
detectors (waterflow alarm)
55000-810
55000-813
55000-818
55000-819
55000-823
55000-875
55000-832
55000-833
59000-810
59000-820
C.7
Model
Name
Description
55000-803
55000-804
55000-821
DIN rail mount module with 1 delayed input and reset output
for waterflow detectors (waterflow alarm)
55000-822
55000-812
55000-826
55000-802
C.8
Model
Name
Description
55000-841
DIN rail mount module with 1 delayed input and reset output for waterflow
detectors (waterflow alarm)
55000-843
55000-845
55000-847
55000-849
55000-852
C.9
Every Apollo device requires an address to identify it on the loop. Apollo devices must be addressed
manually, as follows.
C.9.1
You can address Apollo detectors using the incorporated Xpert cards.
Work carefully through the following steps:
Apollo Devices
55
Installation manual
4. Using a felt-tip pen or printing device, write/print the respective address on the break-off tags.
Note:
This labeling method will provide visual identification of the system detectors during the system
installation phase. When you think you have the system detectors properly wired and addressed, you can
either break off the tags or leave them for future reference.
C.9.2
You can address all modules in the APOLLO range (Input,Output, In/Out, Manual Callpoint/Sounder/
Flasher/Emergency Light, etc.) using the incorporated DIP switches (see following figure).
1. Using the On/Off position of the incorporated DIP switch (refer to the Address Table in the device
instructions), set the module address (from 1 to 126).
2. Connect the module to the motherboard.
56
Apollo Devices
Installation manual
Appendix D
Order Codes
Following are the order codes of INIM Electronics s.r.l. products:
Code
Description
DCMIINE0SLOOP
Installation Manual
DCMPINE0SLOOP
Programming Manual
DCMUINE0SLOOP
User Manual
IPS24140
Link232F9F9
RS232 link
LinkUSBAB
ProbeTH
SmartLAN
SmartLAN/SF
SmartLeague
SmartLetUSee/LCD
SmartLetUSee/LED
SmartLook
SmartLoop/1010-G
Single loop, non-expandable control panel with command keypad and display
SmartLoop/1010-P
Single loop, non-expandable control panel, equipped with command keypad and
display, zone status LED pad and housing for optional SmartLoop/PRN thermal printer
SmartLoop/1010-S
SmartLoop/2080-G
Two-loop control panel, expandable to 8, equipped with command keypad and display
SmartLoop/2080-P
SmartLoop/2080-S
SmartLoop/2L
SmartLoop/INOUT
SmartLoop/NET
SmartLoop/PSTN
Order Codes
57
Installation manual
Notes:
58
Notes:
Installation manual
59