Smoke and Fire Detector Models DI-3
Smoke and Fire Detector Models DI-3
Smoke and Fire Detector Models DI-3
Smoke and Fire Detector Models DI-3, DI-3H, DI-3IS*, DI-A3, and DI-A3H
To initiating circuit of
compatible control End-of-line
unit (See †NOTE and device
Compatibility Chart) observe
polarity
if applicable
Connection for listed remote lamp †NOTE: The Models DI-3, DI-3H, DI-3IS*, DI-A3, and
RL-30 or equivalent, audible base DI-A3H are rated at 16-25.7 VDC—3 volt peak to
ADB-3, or relay RR-3, 40mA max, at peak maximum ripple. Supervisory current 110μA
24V (one per detector.) CAUTION: Only max steady state. 350μA peak surge upon
one critical function remote should be application of power, and 135mA max in alarm.
used in each circuit, since only one alarm
per circuit is guaranteed.
*NOTE: The DI-3IS is FM listed only. Do not use remote function with the DI-3IS.
These instructions are written in accordance with the of all facets of the area being protected. Such factors as air
installation guidelines of NFPA 72, National Fire Alarm currents, temperature, humidity, pressure, and the nature of
Code, and CAN/ULC-S524, The Installation of Fire Alarm the load have been carefully considered. Especially noted have
Systems. been the room or area configuration and the type of ceiling
(sloped or flat, smooth or beamed). Siemens Industry, Inc.'s
DETECTOR PLACEMENT extensive experience in the design of the system assures the
optimum detector placement and is reflected in these drawings.
Although no specific spacings have been allocated for the Sound engineering judgment by qualified personnel must
detectors used for the 0 to 300 ft/min clean air velocity prevail.
application, use 30 foot center spacing (900 sq ft) from NFPA
Standard 72 Chapter 5 and CAN/ULC-S524, if practical, as a
guide or starting point for a detector installation layout. This
TO AVOID NUISANCE ALARMS:
spacing, however, is based on ideal conditions — smooth
ceiling, no air movement, and no physical obstructions. In DO NOT locate the DI-3, DI-3H, or DI-3IS detectors where
some applications, therefore, considerably less area is excessive smoke concentrations exist under normal conditions
protected adequately by each smoke detector. This is why it or in areas of prolonged high relative humidity where
is mandatory to closely follow the installation drawings. In all condensation will occur.
installations (except in special circumstances, such as in
computer room underfloors where the velocity may be DO NOT locate the DI-3, DI-3H, or DI-3IS detectors adjacent
between 300 and 1200 ft/min) the detector should be located to an oil burner, kitchen, or garage where exhaust fumes could
on the ceiling, a minimum of 6 inches from a side wall, or on trigger an alarm. Other causes of false alarms are dust
a wall, 6 inches from the ceiling. accumulation, high wind velocity, heavy concentrations of
steam, heavy pipe or cigar smoke, and certain aerosol sprays.
Should questions arise regarding detector placement,
drawings provided or approved by Siemens Industry, Inc., or DO NOT locate the DI-A3 or DI-A3H detectors in an area of
by its authorized distributors should be followed. This is prolonged high relative humidity when condensation will occur
extremely important! The detector placements shown on or adjacent to oil burners or in garages, where exhaust fumes
these drawings have been chosen after a careful evaluation could trigger an alarm.
2
• If loop continuity is acceptable, remove jumper at each
detector location and proceed with detector head
installation.
CAUTION
Detection Device Storage
DO NOT install this detection device until all
construction is completed.
DO NOT store this detection device where it can
be contaminated by dirt, dust, or humidity. Figure 4
TESTING
INSTALLATION OF DETECTOR HEAD
Testing should be performed by qualified personnel. To
1. Align notch in detector cover to raised surface on outer
ensure that the DI-3, DI-3H, DI-3IS, DI-A3, and DI-A3H are
ring of base (See Figure 3).
within factory-specified sensitivity limits, a sensitivity jack test
is provided to directly measure the sensitivity of the detector
in its mounted position while powered by the system. Access
to the sensitivity test jack is obtained through five holes
located on the front face of the detector (See Figure 4). Use
sensitivity tester Model TM-I3 to test. Refer to the sensitivity
test OPERATION MANUAL for Model TM-I3, P/N 315-
086641. Test frequency should be in accordance with
installation and test guidelines of NFPA Standard 72.
MAINTENANCE
Figure 3 Dust accumulations may cause a shift in detector sensitivity.
For this reason, it is important that each unit be given a
2. Push detector head into base and rotate clockwise to periodic check and a light cleaning if necessary. The minimum
engage electrical connections. The detector will test schedule may be found in the current edition of NFPA
automatically stop and lock into place. 72, Chapter 7 for installations in the U.S., and CAN/ULC-
3. To remove, push detector head up into the base while S537, The Verification of Fire Alarm Systems, for installations
rotating the detector head counterclockwise. Continue in Canada. Cleaning program intervals should be geared to
to rotate counterclockwise until stop is reached. Then the individual detector environment.
pull downward to disengage from base.
Clean a detector by lightly brushing all open slots. You can
DETECTOR SENSITIVITY also clean a detector with the suction of a vacuum cleaner,
but the suction may cause the detector to alarm; therefore, it
The normal sensitivity range of each Siemens Industry, Inc., is recommended that power be disconnected during cleaning.
detector can be found on the back of the detector. In general,
any condition which causes the detector sensitivity to The detectors are not designed for thorough cleaning in the
decrease to a value outside its normal sensitivity range is field. When the detector sensitivity falls outside the acceptable
approaching alarm and indicates that (a) a detector requires limits for that detector, and cannot be brought back with
cleaning, (b) a change in ambient or environmental conditions sensitivity adjustment (where applicable), replace the detector
has occurred, or (c) the detector is faulty. head with an acceptable head. Send the removed head to
the nearest Siemens Industry, Inc. Authorized Service Center
The DI-3, DI-3H, and DI-3IS sensitivities are field adjustable. for servicing.
Access to the sensitivity adjustment potentiometer is through
a hole located on the detector head face. The DI-3, DI-3H, CAUTION: UNDER NO CIRCUMSTANCES IS THE
and DI-3IS sensitivity is adjustable ± 0.50 VDC of the nominal DETECTOR HEAD TO BE DISASSEMBLED. NO FIELD
factory setting. Adjustment towards “ + ” increases detector REPAIRS SHOULD BE ATTEMPTED. THE DETECTORS
sensitivity. Adjustment towards “ – ” decreases detector ARE FACTORY REPAIRABLE ONLY.
sensitivity. Refer to Figure 4. The sensitivity of the DI-A3 and
DI-A3H detectors is factory set and is not field adjustable.
3
NONINT RINSICALLY SAFE INT RINSICALLY SAFE (FM APPROVED ONLY)
MODELS DI-3, DI-3H, DI-A3, AND DI-A3H MODEL DI-IS ONLY
COMPAT IBLE CONT ROL EQUIPMENT
EQUIPMENT COMPAT IBILIT Y INSTALLAT ION/WIRING
EQUIPMENT COMPAT IBILIT Y INSTALLAT ION/WIRING
IDENT IFIER INST RUCT IONS
IDENT IFIER INST RUCT IONS
ZS-30 w ith Diode Shunt Barrier P/N 315-024056-16
CP-2ER P/N 315-093523-6
CZM-1 w ith D.C. Isolator P/N 315-090725-8
CP-35 (System 3) P/N 315-084902-20
CZM-1B6 w ith D.C. Isolator P/N 315-095355-5
* CZM-1 (MXL/MXL-IQ System) P/N 315-090725-8
T he detector model number is the compatibility identifier.
* CZM-1B6 (MXL/MXL-IQ System) P/N 315-095355-5
CZM-4 (MXL/MXL-IQ System) P/N 315-090726-8
PXL P/N 315-094131-4
PZC-4D (PXL) P/N 315-094164-2
PZE-4B (PXL) P/N 315-094065-4
* SXL P/N 315-092419-10
SXL-EX P/N 315-095997-5
* SZE-4R (SXL) P/N 315-092430-4
SZE-4X (SXL-EX) P/N 315-096018-4
SZE-8AX (SXL-EX) P/N 315-096022-4
ZNX-3 (XL3 System) P/N 315-088562B
ZU-35 (System 3) P/N 315-083222-14
T he detector model number is the compatibility identifier.
* Control Equipment does not support remote accessories;
e.g. lamps or relays.