Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ups 10 Kva Eaton Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 116

Powerware Series

®
Eaton 9355 UPS
10/15 kVA
User's Guide
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.

ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing
Equipment Regulations ICES‐003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du
Canada.

IEC 62040-2
Some configurations are classified under IEC 62040-2 as “C2 UPS for Unrestricted Sales Distribution.”

Eaton, Powerware, ABM, Powerware Hot Sync, and X-Slot are registered trademarks and ConnectUPS is a
trademark of Eaton or its subsidiaries and affiliates. Greenlee is a registered trademark of Greenlee Textron.
Modbus is a registered trademark of Schneider Automation. National Electrical Code and NEC are registered
trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective
companies.
ECopyright 2005–2015 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced
in any way without the express written approval of Eaton.
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:

RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.

CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for


additional information, such as important operating and maintenance
instructions.

This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead‐acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse or
hazardous waste center.

This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.

ON - Indicates that the switch is in the ON position.

OFF - Indicates that the switch is in the OFF position.

PHASE - The word “phase.”


Table of Contents

1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 UPS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Floor Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unloading the Cabinet(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Three-High Cabinets or Two-High EBMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Two-High UPS Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Selecting an Installation Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4 UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Version 1 Wall-Mounted Bypass Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . 29
6 Version 2 Wall-Mounted Bypass Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . 41
7 Stabilizing the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8 Extended Battery Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Installing Communication Options and Control Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
DB-9 Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
X-Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Remote Monitor Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Industrial Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Control Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Remote Emergency Power-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Relay Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Programmable Signal Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality i
TABLE OF CONTENTS

10 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Control Panel Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Changing the Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Display Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
User Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
UPS Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Normal Mode Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Starting the UPS on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Internal Bypass Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
UPS Maintenance Bypass Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Wall-Mounted Maintenance Bypass Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Configuring the UPS for EBMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
11 UPS Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
UPS and Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Storing the UPS and Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
When to Replace Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Recycling the Used Battery or UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Using the UPS Maintenance Bypass Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Using the Wall-Mounted Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
12 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
13 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Typical Alarms and Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Silencing the Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Service and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
14 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Limited Factory Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

ii Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 1 Introduction

The Eaton® 9355 uninterruptible power supply (UPS) is a true online,


double-conversion three-phase system that can be used to prevent loss
of valuable electronic information and minimize equipment downtime. It
is ideal for protecting essential information technology and electrical
engineering infrastructure in corporate, telecom, health care, banking,
and industrial applications.
The Eaton 9355 UPS continually monitors incoming electrical power and
removes the surges, spikes, sags, and other irregularities that are
inherent in commercial utility power. Working with a building's electrical
system, the UPS supplies clean, consistent power that sensitive
electronic equipment requires for reliable operation. During brownouts,
blackouts, and other power interruptions, batteries provide emergency
power to safeguard operation.
With the Eaton 9355 UPS, you can safely eliminate the effects of
electrical line disturbances and guard the integrity of your systems and
equipment. Figure 1 shows the Eaton 9355 UPS and an optional
Extended Battery Module (EBM).

Figure 1. The Eaton 9355 UPS and EBM (3-High Cabinets Shown)

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 1
INTRODUCTION

Providing outstanding performance and reliability, the Eaton 9355 UPS's


unique benefits including the following:
S Online UPS design with pure sine wave output. The UPS filters and
regulates incoming AC power and provides consistent power to your
equipment without draining the battery.
S More wattage in less space with a 0.9 power factor—protecting more
equipment and leaving more room for expansion.
S A UPS maintenance bypass switch that provides a
Make-Before-Break (MBB) wrap-around bypass for UPS maintenance
or service without shutting down the load.
S Support for Powerware Hot Sync® paralleling of multiple modules for
redundancy or extra capacity.
S Input current total harmonic distortion (THD) of less than five percent,
using active input power factor correction.
S ABM® technology that uses advanced battery management to
increase battery service life, optimize recharge time, and provide a
warning before the end of useful battery life.
S Up to three hours of extended runtime with added EBMs.
S Advanced power management with the Software Suite CD for
graceful shutdowns and power monitoring.
S Emergency shutdown control through the remote emergency
power-off (REPO) port.
S Start-on-battery capability for powering up the UPS even if utility
power is not available.
S Standard communication options with a DB-9 serial port, relay output
contacts, and programmable signal inputs.
S Optional X-Slot® cards with enhanced communication capabilities for
increased power protection and control.

2 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
INTRODUCTION

The following options for the Eaton 9355 UPS are available:
S Remote Monitor Panel
The optional Remote Monitor Panel (RMP) provides monitoring of the
operational status and alarm condition of the UPS from virtually any
location within the facility. You can install multiple RMPs at remote
locations to increase your monitoring capabilities.
S Power Distribution Module
The optional Power Distribution Module (PDM) comes equipped with
several different types of output receptacles.
S Parallel Tie Cabinet
An optional parallel system with up to four UPSs can be installed to
provide a parallel capacity and/or redundant system. This load sharing
system provides more capacity than a single UPS and can provide
backup, depending on the load and configuration. In addition, when
one UPS is taken out of service for maintenance or is not operating
properly, a redundant UPS continues to supply uninterrupted power
to the critical load. A parallel Powerware Hot Sync Controller Area
Network Bridge Card provides connectivity for system metering and
operational mode control. The parallel system consists of two to four
UPSs, each with a parallel CAN Bridge Card, and a parallel tie cabinet.
Refer to the Eaton 9355 Parallel UPS (10/15 kVA) User's Guide for
more information.
S Wall-Mounted Bypass Switch
The optional wall-mounted bypass switch is used to bypass the UPS
during maintenance or servicing, providing wrap-around bypass for
UPS service without shutting down the load.
S Input Isolation Transformer
The optional input isolation transformer is located at the bottom of a
3-high UPS model. The isolation transformer allows operation from a
480V or 600V 60-Hz source.
S Seismic Kit
The optional seismic kit secures the UPS and optional EBMs for
Zone 4 seismic installations.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 3
INTRODUCTION

4 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 2 Safety Warnings

IMPORTANT SAFETY INSTRUCTIONS


SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.

DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.

WARNING
S This UPS contains its own energy source (batteries). The UPS output may carry live
voltage even when the UPS is not connected to an AC supply.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95%
maximum).
S To reduce the risk of fire, connect only to a circuit provided with 100 amperes maximum
branch circuit overcurrent protection in accordance with the National Electrical Code®
(NEC®), ANSI/NFPA 70.
S Output overcurrent protection and disconnect switch must be provided by others.

CAUTION
S Batteries can present a risk of electrical shock or burn from high short circuit current.
Observe proper precautions. Servicing should be performed by qualified service
personnel knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 5
SAFETY WARNINGS

Consignes de Sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ
IMPORTANTES

DANGER!
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d'entretien et de
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.
AUCUNE PIÈCE RÉPARABLE PAR L'UTILISATEUR ne se trouve dans l'onduleur.

WARNING
S Cet onduleur renferme sa propre source d'énergie (batteries). Les prises de sortie
peuvent être sous tension même lorsque l'onduleur n'est pas branché sur le secteur.
S Pour réduire les risques d'incendie et de décharge électrique, installer l'onduleur
uniquement à l'intérieur, dans un lieu dépourvu de matériaux conducteurs, où la
température et l'humidité ambiantes sont contrôlées. La température ambiante ne doit
pas dépasser 40 °C. Ne pas utiliser à proximité d'eau ou dans une atmosphère
excessivement humide (95 % maximum).
S La protection contre une surintensité pour le(s) circuit(s) de sortie de courant alternatif
doit être fournie par un autre fournisseur.
S Les interrupteurs de déconnexion convenables pour le(s) circuit(s) de sortie de courant
alternatif doivent être fournie par un autre fournisseur.

ATTENTION!
S Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des
courts-circuits de haute intensité. Prendre les précautions nécessaires.
S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements
en vigueur dans votre localité.
S Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire
exploser.

6 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
SAFETY WARNINGS

Advertencias de Seguridad
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
GUARDE ESTAS INSTRUCCIONES
ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD
IMPORTANTES

PELIGRO
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben
ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay
NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.

WARNING
S Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de salida
pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un
suministro de corriente alterna (c.a.).
S Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar
cubierto, con temperatura y humedad controladas, libre de contaminantes conductores.
La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con
humedad excesiva (95% máximo).
S La protección contra exceso de corriente para el/los circuito(s) de CA de salida será
suministrada por terceros.
S Los interruptores de desconexión debidamente clasificados para el/los circuito(s) de CA
de salida serán suministrados por terceros.

PRECAUCIÓN
S Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones
correspondientes.
S Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales
para conocer los requisitos pertinentes.
S Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a
la llama.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 7
SAFETY WARNINGS

8 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 3 UPS Setup

This chapter describes:


S Equipment inspection
S Floor loading and clearances
S Unloading the cabinet(s)
The instructions are intended for the chief operator/system supervisor,
electrical consultants, and installation electricians. Local regulations and
electrical code must be followed during the UPS installation.

Inspecting the Equipment


If any equipment has been damaged during shipment, keep the shipping
and packing materials for the carrier or place of purchase and file a claim
for shipping damage. If you discover damage after acceptance, file a
claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.

NOTE Check the battery recharge date on the packaging label. If the date has expired and
the batteries were never recharged, do not use the UPS. Contact your service representative.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 9
UPS SETUP

Floor Loading
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.

Standard Model Floor Loadings (2-High/3-High Cabinets)

Maximum Point Loading


Eaton 9355
Weight lb/in2 (kg/cm2)

2-High UPS 381 lb (173 kg) 95 (6.7)

3-High UPS-32 587 lb (266 kg) 147 (10.3)

3-High UPS-64 619 lb (281 kg) 155 (10.9)

2-High EBM 480 lb (218 kg) 120 (8.4)

3-High EBM 710 lb (322 kg) 178 (12.5)

Clearances
The following clearances are recommended for the Eaton 9355 UPS:

From Front of Cabinet 36” (91.4 cm) working space

From Back of Cabinet 6” (15.2 cm) without PDM installed; with PDM installed,
clearance determined by customer-supplied mating plug

10 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS SETUP

Unloading the Cabinet(s)


The following tools are required for unloading the cabinet(s):
S 15 mm wrench or socket
S 7 mm nut driver or socket

CAUTION
The UPS and EBM are heavy (see page 10). Unloading the cabinets requires at least two
people to safely remove the cabinets from the pallet.

To unload three-high cabinets or two-high EBMs, continue to the


following section. To unload two-high UPS cabinets, proceed to page 15.

Three-High Cabinets or Two-High EBMs


To remove a three-high cabinet or a two-high EBM from the shipping
pallet:

1. Remove the two M10 bolts securing the stabilizing bracket to the
pallet (see Figure 2).

M10 Bolts

Figure 2. Removing the Stabilizing Bracket Bolts

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 11
UPS SETUP

2. Remove the four M4 screws securing the stabilizing bracket to the


cabinet rear panel and remove the bracket (see Figure 3). Retain the
hardware for later use.

NOTE Retain the stabilizing bracket and hardware for later re-assembly onto the cabinet.

3. Remove the front cover from the bottom cabinet to access the
front shipping bracket.

Press and release the handle latch at the bottom of the cover and
then lift the cover up and off the cabinet.

4. Remove the three M10 bolts securing the rear shipping pad to the
pallet and remove the shipping pad.

12 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS SETUP

NOTE Hold the back of the cabinet so that the bolts can be removed easily without the
cabinet rolling backward.

5. Remove the two M10 bolts securing the front shipping bracket and
remove the bracket.

If needed, adjust the leveling feet to release the bracket.

Front Shipping
Bracket

M10 Bolts

Stabilizing Bracket

M10 Bolts

M4 Screws

Shipping Pad

Figure 3. Removing the Brackets and Shipping Pad

6. Reinstall the front cover removed in Step 3.

Hang the top edge of the cover on the cabinet first, then lower the
bottom edge and snap into place.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 13
UPS SETUP

NOTE Support the front and back of the cabinet when rolling it off the pallet to prevent
tipping.

7. Slowly roll the cabinet toward the rear of the pallet. Once the pallet
tilts, continue rolling the cabinet down the pallet until the cabinet
touches the floor (see Figure 4).

If needed, adjust the leveling feet so that the cabinet rolls freely.

Figure 4. Unloading the Cabinet

8. With the cabinet supported, slowly pull the pallet away from the
cabinet (see Figure 5).

Figure 5. Removing the Pallet

9. Roll the cabinet to the desired location.

10. Continue to “Selecting an Installation Option” on page 18.

14 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS SETUP

Two-High UPS Cabinets


To remove a two-high UPS from the shipping pallet:

1. Remove the M10 bolt securing the vertical bracket to the pallet (see
Figure 6).

2. Remove and retain the three M4 screws securing the vertical


bracket to the UPS. Remove the vertical bracket.

M4 Screws

M10 Bolt

Figure 6. Removing the Vertical Bracket

3. Reinstall the M4 screws to the UPS (see Figure 7).

M4 Screws

Figure 7. Reinstalling the M4 Screws

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 15
UPS SETUP

4. Repeat Steps 1 through 3 to remove the vertical bracket on the


other side.

5. Remove the front cover from the bottom cabinet to access the
front shipping bracket.

Press and release the handle latch at the bottom of the cover and
then lift the cover up and off the cabinet.

6. Remove the three M10 bolts securing the rear shipping pad to the
pallet and remove the shipping pad (see Figure 8).

NOTE Hold the back of the cabinet so that the bolts can be removed easily without the
cabinet rolling backward.

7. Remove the two M10 bolts securing the front shipping bracket and
remove the bracket.

If needed, adjust the leveling feet to release the bracket.

Front Shipping
Bracket

M10 Bolts

M10 Bolts

Shipping Pad

Figure 8. Removing the Front Shipping Bracket and Shipping Pad

16 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS SETUP

8. Reinstall the front cover removed in Step 5.

Hang the top edge of the cover on the cabinet first, then lower the
bottom edge and snap into place.

NOTE Support the front and back of the cabinet when rolling it off the pallet to prevent
tipping.

9. Slowly roll the cabinet toward the rear of the pallet. Once the pallet
tilts, continue rolling the cabinet down the pallet until the cabinet
touches the floor (see Figure 9).

If needed, adjust the leveling feet so that the cabinet rolls freely.

Figure 9. Unloading the Cabinet

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 17
UPS SETUP

10. With the cabinet supported, slowly pull the pallet away from the
cabinet (see Figure 10).

Figure 10. Removing the Pallet

11. Roll the cabinet to the desired location.

12. Continue to the following section, “Selecting an Installation


Option.”

Selecting an Installation Option


You are now ready to install the Eaton 9355 UPS. Select one of the
following installation options according to your UPS configuration:

UPS Configuration Installation Chapter

UPS only Chapter 4, “UPS Installation” on page 19

UPS with an optional input isolation transformer Chapter 4, “UPS Installation” on page 19

UPS with an optional wall-mounted bypass switch Chapter 5, “Wall-Mounted Bypass Switch Installation” on page 29

Parallel UPS configuration Refer to the Eaton 9355 Parallel UPS (10/15 kVA) User's Guide.

18 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 4 UPS Installation

The Eaton 9355 has the following power connections:


S 3‐phase (L1, L2, and L3), neutral, and ground connection for
rectifier/bypass input
S 3‐phase (L1, L2, and L3), neutral, and ground connection for load
output
The nominal input/output voltages are:
S 120/208 or 127/220 Vac
S 480V or 600V 60-Hz input is available using the optional input isolation
transformer module
Output overcurrent protection and disconnect switch must be provided
by others.
Figure 15 through Figure 17 beginning on page 25 show the oneline
diagrams.

WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS
installation and initial startup. Risk of electrical shock.

To hardwire the UPS:

1. Verify that the electrical connections to the installation site have


been properly installed.

2. A wall-mounted, user‐supplied, readily‐accessible disconnection


device must be incorporated in the input wiring.

Compare the circuit breaker ratings to the ones in Table 1 on


page 22.

NOTE To accommodate the feature of easy system expandability, it is recommended that


initial installation of the Eaton 9355 UPS contain wiring to support the maximum capacity of
the UPS cabinet.

3. Switch off utility power to the distribution point where the UPS will
be connected. Be absolutely sure there is no power.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 19
UPS INSTALLATION

4. Determine your equipment's grounding requirements according to


your local electrical code.

5. Verify that the UPS battery circuit breaker is in the OFF position
(see Figure 11).

Battery Circuit Breaker

UPS Wiring
Access Cover

Conduit Landing Plates

Figure 11. UPS Rear View (3-High Shown)

6. For UPS only installations, continue to Step 7; for UPS installations


with an input isolation transformer, proceed to Step 10.

7. Remove the UPS wiring access cover and one of the conduit
landing plates and retain (see Figure 11).

8. Punch two holes in the conduit landing plate for the input and
output conduit using a Greenlee® punch or similar device.

9. Proceed to Step 12.

20 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS INSTALLATION

10. Verify that the input circuit breaker is in the OFF position (see
Figure 12).

11. Remove the input isolation transformer wiring access cover and
retain.

Battery Circuit Breaker

Input Isolation
Transformer
Wiring Access Cover

Input Circuit Breaker

Figure 12. UPS with Input Isolation Transformer Rear View

12. Hardwire the input, output, and ground terminations for the UPS or
input isolation transformer. See Table 1 for wiring specifications.

For a detailed view of the terminal block, see Figure 13 or Figure 14


on page 23.

NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral
will void the warranty. If the optional input transformer is installed, an input neutral is not
required.
NOTE The Eaton 9355 UPS is a single-feed UPS only.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 21
UPS INSTALLATION

Table 1. Terminal Block Wiring


Conduit Size2, 3
10 kVA Wire Feeder Circuit L1, L2, L3, N Ground Tightening
(Number of
System Voltage Function Breaker Rating Wire Size1 Wire Size Torque1
Conduits)

208 Input 45A 6 AWG 10 AWG


UPS Module,TB1
220 WYE / 4-Wire 45A 6 AWG 10 AWG 120 lb in
(13.5 Nm) 1.00” conduit (1)
480 Input 20A 12 AWG 12 AWG
XFMR Module
600 Delta / 3-Wire 20A 12 AWG 14 AWG

208 Output 6 AWG 10 AWG


UPS Module,TB1
220 6 AWG 10 AWG
WYE / 4-Wire 120 lb in
1.00” conduit (1)
480 (with transformer) (13.5 Nm)
8 AWG 10 AWG
600 (with transformer) 8 AWG 10 AWG
Conduit Size2, 3
15 kVA Wire Feeder Circuit L1, L2, L3, N Ground Tightening
(Number of
System Voltage Function Breaker Rating Wire Size1 Wire Size1 Torque
Conduits)

208 Input 60A 4 AWG 10 AWG


UPS Module,TB1 1.25” conduit (1)
220 WYE / 4-Wire 60A 4 AWG 10 AWG
120 lb in
480 Input 30A 10 AWG 10 AWG (13.5 Nm)
XFMR Module 1.00” conduit (1)
600 Delta / 3-Wire 25A 10 AWG 10 AWG

208 Output 6 AWG 10 AWG


UPS Module,TB1
220 6 AWG 10 AWG
WYE / 4-Wire 120 lb in
1.00” conduit (1)
480 (with transformer) (13.5 Nm)
6 AWG 10 AWG
600 (with transformer) 6 AWG 10 AWG
1 Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to National

Electrical Code (NEC) Table 310‐104(A). Code may require a larger AWG size than shown in this table because of
temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
2 Per NEC article 300‐20(a) for Ferrous Metal Raceways, all three-phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.
3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG
ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW, THHW, THW‐2.

22 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS INSTALLATION

Ground

Figure 13. UPS Terminal Block (3-High Shown)

L1 L2 L3 N L1 L2 L3 N N
INPUT OUPUT

Figure 14. Input Isolation Transformer Terminal Block

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 23
UPS INSTALLATION

13. For UPS only installations, replace the UPS wiring access cover and
conduit landing plate.

For UPS installations with an input isolation transformer, replace the


transformer wiring access cover.

14. Continue to “Stabilizing the Cabinet” on page 55 to complete the


UPS installation.

24 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS INSTALLATION

Figure 15. UPS Wiring Diagram

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 25
UPS INSTALLATION

*
*

Figure 16. UPS with Extended Battery Modules Wiring Diagram

26 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS INSTALLATION

Figure 17. UPS with Input Isolation Transformer Wiring Diagram

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 27
UPS INSTALLATION

28 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 5 Version 1 Wall-Mounted Bypass Switch
Installation

This chapter describes installing the wall-mounted bypass switch with


the UPS. The wall-mounted bypass switch is a Make-Before-Break
(MBB) maintenance bypass switch.

NOTE The input isolation transformer cannot be used with the wall-mounted bypass
switch.

The Eaton 9355 UPS has the following power connections:


S 3‐phase (L1, L2, and L3), neutral, and ground connection for
rectifier/bypass input
S 3‐phase (L1, L2, and L3), neutral, and ground connection for load
output
The nominal input/output voltages are:
S 120/208 or 127/220 Vac
Output overcurrent protection and disconnect switch must be provided
by others.
Figure 26 and Figure 27 beginning on page 39 show the oneline
diagrams.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 29
VERSION 1 WALL-MOUNTED BYPASS SWITCH

WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS
installation and initial startup. Risk of electrical shock.

To hardwire the bypass cabinet:

1. Verify that the electrical connections to the installation site have


been properly installed.

2. A wall-mounted, user‐supplied, readily‐accessible disconnection


device must be incorporated in the input wiring.

Compare the circuit breaker ratings to the ones in Table 2 on


page 34.

3. Switch off utility power to the distribution point where the bypass
cabinet and UPS will be connected. Be absolutely sure there is no
power.

4. Determine your equipment's grounding requirements according to


your local electrical code.

5. Remove the bypass cabinet front cover (see Figure 18).

Figure 18. Version 1 Bypass Cabinet Front Cover

30 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 1 WALL-MOUNTED BYPASS SWITCH

6. Remove the internal cover to gain access to the breakers (see


Figure 19).

Internal
Cover

Figure 19. Version 1 Internal Cover

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 31
VERSION 1 WALL-MOUNTED BYPASS SWITCH

7. Punch holes for the conduit (AC input, UPS output, load connection,
and maintenance bypass contact wires) using a Greenlee punch or
similar device.

8. Verify that the bypass breaker is in the OFF position (see Figure 20).

9. Mount the bypass cabinet to the wall and install the conduit.

Figure 20. Version 1 Bypass Breaker

32 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 1 WALL-MOUNTED BYPASS SWITCH

10. Verify that the UPS battery circuit breaker is in the OFF position
(see Figure 21).

11. Remove the UPS wiring access cover and one of the conduit
landing plates and retain.

12. Punch two holes in the conduit landing plate for the input and
output conduit using a Greenlee punch or similar device.

Battery Circuit Breaker

UPS Wiring
Access Cover

Conduit Landing Plates

Figure 21. UPS Rear View (3-High Shown)

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 33
VERSION 1 WALL-MOUNTED BYPASS SWITCH

13. Hardwire the UPS input terminations.

See Table 2 for specifications and Figure 22 for a detailed view of


the UPS terminal block.

NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral
will void the warranty. If the optional input transformer is installed, an input neutral is not
required.
NOTE The Eaton 9355 UPS is a single-feed UPS only.

Table 2. UPS Terminal Block Wiring


10 kVA Wire Feeder Circuit L1, L2, L3, N Ground Tightening Conduit Size2, 3
System Voltage Function Breaker Rating Wire Size1 Wire Size1 Torque (Number of Conduits)
208 Input 45A 6 AWG 10 AWG
120 lb in
1.00” conduit (1)
220 45A 8 AWG 10 AWG (13.5 Nm)

208 Output 8 AWG 10 AWG


120 lb in
1.00” conduit (1)
220 8 AWG 10 AWG (13.5 Nm)

15 kVA Wire Feeder Circuit L1, L2, L3, N Ground Tightening Conduit Size2, 3
System Voltage Function Breaker Rating Wire Size1 Wire Size1 Torque (Number of Conduits)
208 Input 60A 4 AWG 10 AWG 1.25” conduit (1)
120 lb in
220 60A 4 AWG 10 AWG (13.5 Nm) 1.25” conduit (1)
208 Output 6 AWG 10 AWG
120 lb in
1.00” conduit (1)
220 6 AWG 10 AWG (13.5 Nm)
1 Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code
Table 310‐104(A). Code may require a larger AWG size than shown in this table because of temperature, number of
conductors in the conduit, or long service runs. Follow local requirements.
2 Per NEC article 300‐20(a) for Ferrous Metal Raceways, all three-phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.
3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG
ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW, THHW, THW‐2.

34 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 1 WALL-MOUNTED BYPASS SWITCH

Maintenance
Bypass
Contacts

TB2

Ground

Figure 22. UPS Terminal Block (3-High Shown)

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 35
VERSION 1 WALL-MOUNTED BYPASS SWITCH

14. Hardwire the output terminations from the UPS to the bypass
cabinet (see Figure 23).

Ground
Neutral

Line 1
Line 2
Line 3

Figure 23. Version 1 UPS Output to Bypass Cabinet Wiring

36 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 1 WALL-MOUNTED BYPASS SWITCH

15. Hardwire the load to the bypass cabinet (see Figure 24).

16. Route the maintenance bypass wires through the conduit to the
UPS terminal block (see Figure 22 on page 35).

Connect the black and the red wire to TB2 on the UPS. Cap the
blue wire.

NOTE The maintenance bypass contacts are normally-open. To ensure proper bypass
operation, DO NOT use the blue wire (it is normally-closed).

17. Replace the UPS wiring access cover and conduit landing plate.

Maintenance Bypass
Wiring to UPS TB2

Ground Neutral

Line 1 Line 2 Line 3

Figure 24. Version 1 Load Connections

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 37
VERSION 1 WALL-MOUNTED BYPASS SWITCH

18. Wire the AC input to the bypass breaker (see Figure 25).

Line 2
Line 3
Line 1

Figure 25. Version 1 Bypass AC Input Wiring

19. Verify the bypass input.

20. Reinstall the internal cover.

21. Reinstall the bypass cabinet front cover.

22. Continue to “Stabilizing the Cabinet” on page 55 to complete the


UPS installation.

38 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 1 WALL-MOUNTED BYPASS SWITCH

Red Wire
(open when breaker is open)
Black Wire
225A Breaker (common)
Auxiliary Contacts
Blue Wire
225A (closed when breaker is open)

Bypass Input
80A (4X) LOAD
From UPS 1 Output

Not Used

Not Used

Not Used

Figure 26. Version 1 Bypass Wiring Diagram

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 39
VERSION 1 WALL-MOUNTED BYPASS SWITCH

Figure 27. UPS with Input Isolation Transformer and Version 1 Wall Mounted Bypass Cabinet Wiring Diagram

40 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 6 Version 2 Wall-Mounted Bypass Switch
Installation

This chapter describes installing the wall-mounted bypass switch with


the UPS. The wall-mounted bypass switch is a Make-Before-Break
(MBB) maintenance bypass switch.

NOTE The input isolation transformer cannot be used with the wall-mounted bypass
switch.

The Eaton 9355 UPS has the following power connections:


S 3‐phase (L1, L2, and L3), neutral, and ground connection for
rectifier/bypass input
S 3‐phase (L1, L2, and L3), neutral, and ground connection for load
output
The nominal input/output voltages are:
S 120/208 or 127/220 Vac
Output overcurrent protection and disconnect switch must be provided
by others.
Figure 37 through Figure 39 beginning on page 53 show the oneline
diagrams.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 41
VERSION 2 WALL-MOUNTED BYPASS SWITCH

WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS
installation and initial startup. Risk of electrical shock.

To hardwire the bypass cabinet:

1. Verify that the electrical connections to the installation site have


been properly installed.

2. A wall-mounted, user‐supplied, readily‐accessible disconnection


device must be incorporated in the input wiring.

Compare the circuit breaker ratings to the ones in Table 3 on


page 47.

3. Switch off utility power to the distribution point where the bypass
cabinet and UPS will be connected. Be absolutely sure there is no
power.

4. Determine your equipment's grounding requirements according to


your local electrical code.

5. Unfasten the bypass cabinet front door latch and swing the door
open (see Figure 28).

6. Follow the instructions on the inside of the door to open or remove


the front cover (see Figure 28 and Figure 29).

42 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 2 WALL-MOUNTED BYPASS SWITCH

Front Cover

Door Latch

Door

Figure 28. Version 2 Bypass Cabinet Front Door and Cover

Internal
Cover
Front Cover

Figure 29. Version 2 Bypass Cabinet Front Cover Open

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 43
VERSION 2 WALL-MOUNTED BYPASS SWITCH

7. Remove the internal cover to gain access to the breakers (see


Figure 30).

Internal
Cover

Figure 30. Version 2 Bypass Cabinet Internal Cover

44 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 2 WALL-MOUNTED BYPASS SWITCH

8. Punch holes for the conduit (AC input, UPS output, load connection,
and maintenance bypass contact wires) using a Greenlee punch or
similar device.

9. Verify that the bypass breaker is in the OFF position (see Figure 31).

10. Mount the bypass cabinet to the wall and install the conduit.

Figure 31. Version 2 Bypass Cabinet Bypass Breaker

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 45
VERSION 2 WALL-MOUNTED BYPASS SWITCH

11. Verify that the UPS battery circuit breaker is in the OFF position
(see Figure 32).

12. Remove the UPS wiring access cover and one of the conduit
landing plates and retain.

13. Punch two holes in the conduit landing plate for the input and
output conduit using a Greenlee punch or similar device.

Battery Circuit Breaker

UPS Wiring
Access Cover

Conduit Landing Plates

Figure 32. UPS Rear View (3-High Shown)

46 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 2 WALL-MOUNTED BYPASS SWITCH

14. Hardwire the UPS input terminations.

See Table 3 for specifications and Figure 33 for a detailed view of


the UPS terminal block.

NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral
will void the warranty. If the optional input transformer is installed, an input neutral is not
required.
NOTE The Eaton 9355 UPS is a single-feed UPS only.

Table 3. UPS Terminal Block Wiring


10 kVA Wire Feeder Circuit L1, L2, L3, N Ground Tightening Conduit Size2, 3
System Voltage Function Breaker Rating Wire Size1 Wire Size1 Torque (Number of Conduits)
208 Input 45A 6 AWG 10 AWG
120 lb in
1.00” conduit (1)
220 45A 8 AWG 10 AWG (13.5 Nm)

208 Output 8 AWG 10 AWG


120 lb in
1.00” conduit (1)
220 8 AWG 10 AWG (13.5 Nm)

15 kVA Wire Feeder Circuit L1, L2, L3, N Ground Tightening Conduit Size2, 3
System Voltage Function Breaker Rating Wire Size1 Wire Size1 Torque (Number of Conduits)
208 Input 60A 4 AWG 10 AWG 1.25” conduit (1)
120 lb in
220 60A 4 AWG 10 AWG (13.5 Nm) 1.25” conduit (1)
208 Output 6 AWG 10 AWG
120 lb in
1.00” conduit (1)
220 6 AWG 10 AWG (13.5 Nm)
1 Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code
Table 310‐16. Code may require a larger AWG size than shown in this table because of temperature, number of
conductors in the conduit, or long service runs. Follow local requirements.
2 Per NEC article 300‐20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be
run in the same conduit as the phase conductors.
3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG
ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW, THHW, THW‐2.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 47
VERSION 2 WALL-MOUNTED BYPASS SWITCH

Maintenance
Bypass
Contacts

TB2

Ground

Figure 33. UPS Terminal Block (3-High Shown)

48 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 2 WALL-MOUNTED BYPASS SWITCH

15. Hardwire the output terminations from the UPS to the bypass
cabinet (see Figure 34).

Neutral

Ground

Line 1
Line 2
Line 3

Figure 34. Version 2 Bypass Cabinet UPS Output to Bypass Wiring

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 49
VERSION 2 WALL-MOUNTED BYPASS SWITCH

16. Hardwire the load to the bypass cabinet (see Figure 35).

17. Route the maintenance bypass wires through the conduit to the
UPS terminal block (see Figure 33 on page 48).

Connect the black and the red wires from the terminal block on the
Tie Cabinet to TB2 on the UPS.

NOTE The maintenance bypass contacts are normally-open. To ensure proper bypass
operation, DO NOT use the blue wire (it is normally-closed).

18. Replace the UPS wiring access cover and conduit landing plate.

50 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 2 WALL-MOUNTED BYPASS SWITCH

Line 1 Line 2 Line 3

Neutral

Ground

Maintenance Bypass
Wiring to UPS TB2

Figure 35. Version 2 Bypass Cabinet Load Connections

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 51
VERSION 2 WALL-MOUNTED BYPASS SWITCH

19. Wire the AC input to the bypass breaker (see Figure 36).

Line 1

Line 2

Line 3

Figure 36. Version 2 Bypass Cabinet Bypass AC Input Wiring

20. Verify the phase rotation for each UPS and the bypass input.

21. Reinstall the internal cover.

22. Reinstall the bypass cabinet front cover.

23. Continue to “Stabilizing the Cabinet” on page 55 to complete the


UPS installation.

52 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
VERSION 2 WALL-MOUNTED BYPASS SWITCH

Red Wire
(open when breaker is open)
Black Wire
225A Breaker (common)
Auxiliary Contacts
Blue Wire
225A (closed when breaker is open)

Bypass Input
80A (4X) LOAD
From UPS 1 Output

Not Used

Not Used

Not Used

Figure 37. Version 2 Bypass Cabinet Bypass Wiring Diagram – without Maintenance Isolation Switch (MIS)

Red Wires
(open when breaker is open)
Black Wires
225A Breaker (common)
Auxiliary Contacts
Blue Wires
(closed when breaker is open)
225A

Bypass Input
110A
80A (4X) LOAD
From UPS 1 Output
MIS
Not Used 225A

Not Used

Not Used

Figure 38. Version 2 Bypass Cabinet Bypass Wiring Diagram – with MIS

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 53
VERSION 2 WALL-MOUNTED BYPASS SWITCH

Figure 39. UPS with Input Isolation Transformer and Version 2 Wall Mounted Bypass Cabinet Wiring Diagram

54 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 7 Stabilizing the Cabinet

NOTE For seismic installations, you MUST order and install an Eaton 9355 UPS seismic kit;
do not use the following instructions.
NOTE For non-seismic installations, you MUST install the stabilizing bracket on all 3-high
cabinets. The stabilizing bracket is optional for 2-high cabinets.

To stabilize the cabinet(s):

1. Lower the leveling feet to prevent the cabinet from rolling.

Figure 40. Lowering the Leveling Feet

2. Attach the stabilizing bracket to the bottom of the cabinet rear panel
using the retained hardware from the shipping pallet according to
the cabinet configuration:

S For one cabinet, see Figure 41.


S For two cabinets, see Figure 42.
S For three cabinets, see Figure 43.

NOTE No more than three cabinets can be attached together. For four cabinets, use two of
the two-cabinet installations. For five cabinets, use one three-cabinet and one two-cabinet
installation.

3. Use the holes and slots in the bottom of the bracket to attach the
cabinet to the flooring if desired.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 55
STABILIZING THE CABINET

4. Continue to one of the following sections:

S “Extended Battery Module Installation” on page 59 to install


optional EBMs.

S “Communication” on page 63 to install UPS communication


options, such as X-Slot cards or remote emergency power-off
(REPO).

S “Operation” on page 81 to start up the UPS.

NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the
correct number of EBMs (see page 91).

M4 Screws

Figure 41. Stabilizing Bracket with One Cabinet

56 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
STABILIZING THE CABINET

M4 Screws

Figure 42. Stabilizing Bracket with Two Cabinets

M4 Screws

Figure 43. Stabilizing Bracket with Three Cabinets

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 57
STABILIZING THE CABINET

58 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 8 Extended Battery Module Installation

NOTE A maximum of 22 battery strings can be installed in one configuration, including


UPS batteries (4 EBM-64 models or 3 EBM-96 models). UPS-32 models contain 2 strings;
UPS-64 models contain 4 strings; EBM-64 models contain 4 strings; and EBM-96 models
contain 6 strings.
NOTE For non-seismic installations, you MUST install the stabilizing bracket on all 3-high
cabinets. The stabilizing bracket is optional for 2-high cabinets.

To install the optional Extended Battery Module (EBM):

1. Position the EBM adjacent to the next cabinet.

2. Verify that all battery circuit breakers are in the OFF position (see
Figure 44).

3. Remove the two ground straps from the EBM rear panel.

4. Install one ground strap between the UPS and EBM rear panels as
shown in Figure 44.

5. If additional EBMs are installed, attach another ground strap


between the first and second EBM as shown in Figure 44. Repeat
for each additional EBM.

6. Plug the EBM cable into the UPS battery connector.

7. If additional EBMs are installed, plug the EBM cable of the second
cabinet into the battery connector on the first EBM. Repeat for each
additional EBM.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 59
EXTENDED BATTERY MODULE INSTALLATION

EBM Battery
Circuit Breaker
Rear Ground Strap

UPS Battery Connector


EBM Battery Connector

UPS Battery Circuit Breaker

EBM Cable

Figure 44. Typical EBM Installation (2-High Cabinets Shown)

60 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
EXTENDED BATTERY MODULE INSTALLATION

8. Remove the top front covers of all cabinets.

9. Install the remaining ground straps between each cabinet (see


Figure 45).

10. Reinstall the top front covers removed in Step 8.

Hang the top edge of the cover on the cabinet first, then lower the
bottom edge and snap into place.

11. Continue to one of the following sections:

S “Communication” on page 63 to install UPS communication


options, such as X-Slot cards or remote emergency power-off.

S “Operation” on page 81 to start up the UPS.

NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the
correct number of EBMs (see page 91).

Front Ground Strap

Figure 45. Front Ground Strap Installation (2-High Cabinets Shown)

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 61
EXTENDED BATTERY MODULE INSTALLATION

62 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 9 Communication

This section describes the:


S DB-9 communication port
S X-Slot cards
S Remote Monitor Panel and Industrial Relay Card (IRC)
S Power Management Software
S Remote emergency power-off (REPO)
S Relay output contacts
S Programmable signal inputs
Figure 46 shows the location of the communication options and control
terminals on the UPS.

X-Slot Communication Bay #1

Signal Input 1
1
X-Slot Communication Bay #2 2

1
Signal Input 2 2
1
REPO (normally open) 2
1
REPO (normally closed) 2

DB-9 Communication Port


1
2
Relay Output Contacts 3

Figure 46. Communication Options and Control Terminals

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 63
COMMUNICATION

Installing Communication Options and Control Terminals


To access and install the communication options and control terminals:

1. Remove the front covers of all cabinets, starting with the top
cabinet.

Press and release the handle latch at the bottom of each cover and
then lift the cover up and off the cabinet (see Figure 47).

Figure 47. Removing the Front Covers

2. Install the appropriate X-Slot card and/or necessary cable(s) into the
top cabinet (see Figure 46 and Figure 48).

64 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

Figure 48. Installing Communication Cables

3. On the bottom cover (and also the middle cover if 3-high), remove a
knockout tab in the top edge of the cover for each cable:

With wire cutters, cut either side of the tab and twist down to
remove the tab (see Figure 49).

Figure 49. Removing Knockout Tabs

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 65
COMMUNICATION

4. Route the cable(s) to the approximate location of the cover access


holes.

5. Connect the cables to the appropriate location.

See “Communication Options” on page 67 or “Control Terminals”


on page 76 for detailed information.

6. Reinstall the front covers, starting with the bottom cabinet (see
Figure 50).

Hang the top edge of the cover on the cabinet first, then lower the
bottom edge and snap into place. Verify that the cables fit in the
access holes in the covers.

Figure 50. Reinstalling the Front Covers

7. Continue to “Operation” on page 81 to start up the UPS.

NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the
correct number of EBMs (see page 91).

66 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

Communication Options
The Eaton 9355 UPS has serial communication capabilities through the
DB-9 communication port or through an X-Slot card in one of the
available bays. In addition, the power management software can be
installed and used to communicate with the UPS via one of the serial
communication connections.
The UPS supports two serial communication devices according to the
following table:

Independent Multiplexed

X-Slot 1 X-Slot 2 DB-9 Communication Port

Any X-Slot card Any X-Slot card except the Eaton Not in use
Modem Card
Any X-Slot card Eaton Relay Interface Card Available
Powerware Hot Sync CAN Bridge Card
Any X-Slot card Not in use Available

NOTE You can configure relays, signal inputs, and the serial port baud rate through the
front panel menus (see Table 9 on page 84).

DB-9 Communication Port


To establish communication between the UPS and a computer, connect
your computer to the UPS communication port using the supplied
communication cable.
When the communication cable is installed, power management
software can exchange data with the UPS. The software polls the UPS
for detailed information on the status of the power environment. If a
power emergency occurs, the software initiates the saving of all data
and an orderly shutdown of the equipment.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 67
COMMUNICATION

The cable pins are identified in Figure 51 and the pin functions are
described in Table 4. See Figure 46 on page 63 for the communication
port location.

5
9
4
8
3
7
2
6
1

Figure 51. Communication Port

Table 4. Communication Port Pin Assignment


Pin Number Signal Name Function Direction from the UPS

2 TxD Transmit to external device Out

3 RxD Receive from external device In

5 GND Signal common (tied to chassis) —

X-Slot Cards
X-Slot cards allow the UPS to communicate in a variety of networking
environments and with different types of devices. The Eaton 9355 UPS
has two available communication bays for any X-Slot card, including:
S ConnectUPSt-X Web/SNMP Card - has SNMP and HTTP capabilities
as well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It has a built-in
switching hub that allows three additional network devices to be
connected to the network without the requirement of additional
network drops. In addition, a Environmental Monitoring Probe can be
attached to obtain humidity, temperature, smoke alarm, and security
information.
S Relay Interface Card - has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On
bypass.
S Modbus® Card - allows you to continuously and reliably monitor the
UPSs in your Building Management System (BMS).

68 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

S Industrial Relay Card - is used to indicate the operating status of the


UPS using the customer's monitoring equipment and to connect an
optional RMP. The IRC uses four isolated normally-open or
normally-closed dry relay contacts to indicate the UPS status. Normal,
Bypass, Battery, and Alarm mode can be monitored (see page 74 for
more information).
S Multi-Server Card - has six serial communication ports that can
communicate simultaneously with other computers using power
management software (provided on the Software Suite CD).
S Modem Card - provides out-of-band remote notification and
monitoring using modem communication directly to cell phones and
pagers.
S Single-Port Card - connects to the Expansion Chassis to enable
multiple communication options or to a PC for power management
control.
S ConnectUPS-MX SNMP Card - has Ethernet, modem, and SNMP
capabilities.
S USB Card - connects to a USB port on your computer.

NOTE The Eaton 9355 UPS does not detect plug-and-play hardware. Before installing the
USB Card, set the UPS baud rate to 1200 through the front panel (see Table 9 on page 84).

See Figure 46 on page 63 for the location of the two X-Slot


communication bays.

ConnectUPS-X Web/SNMP Card Multi-Server Card

Relay Interface Card Modem Card

Modbus Card Single-Port Card

Industrial Relay Card ConnectUPS-MX SNMP Card

USB Card

Figure 52. Optional X-Slot Cards

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 69
COMMUNICATION

Remote Monitor Panel


The optional RMP can be installed to monitor the operation of the UPS
from virtually any location within your facility, up to 152.4m (500 ft) from
the UPS. You can surface‐mount an RMP on a desktop or on a wall,
wherever you have a serial interface line. Figure 53 shows an RMP.
Figure 54 shows the enclosure dimensions and cable exit openings.

Cable Exit Opening for 1/2” Conduit


or Provided Strain Relief Horn Silence Button

Figure 53. Remote Monitor Panel

70 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

Cable Exit Openings


for 1/2” Conduit or
Provided Strain Relief
(3 places)

Mounting Slots
(6 places)

NOTE Matches mounting holes on a single- or


Dimensions are in mm [inches] double-gang electrical box.

Figure 54. RMP Dimensions

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 71
COMMUNICATION

To install an RMP:

NOTE If mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud
within the wall. Do not use hollow wall anchors. The RMP can also be mounted to a single-
or double-gang electrical box.

1. If wall mounting, securely mount the RMP. Continue to Step 2.

If desk mounting, install the provided bumpers to the bottom of the


RMP enclosure. Proceed to Step 3.

2. Install 1/2” conduit from the RMP to the IRC through the cable exit
openings (see Figure 54). Proceed to Step 4.

3. Install wiring from the RMP to the IRC using the cable listed in
Table 5 and the provided strain relief bushings in the cable exit
openings in the IRC (see Figure 56) and the RMP.

4. Connect the wiring between the RMP and the IRC plug‐in terminal
blocks using terminations shown in Table 5. See Figure 55 and
Figure 56 for plug‐in terminal block locations.

Table 5. RMP Wire Terminations


From RMP Terminal To IRC Terminal Remarks

J1-1 J1-1

J1-3 J1-3

J1-4 J1-4 Use Beldon 8690 060 or


equivalent cable
J1-5 J1-5

J1-6 J1-6

5. Install the IRC into an open X-Slot communication bay (see


Figure 48 on page 65).

72 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

6. To check the operation of the RMP, ensure that the UPS is


supplying the load via the inverter or bypass. If the indicators on the
RMP show the appropriate status, then it is operating correctly.

If the RMP is not operating correctly, check the wiring, the fuse on
the IRC, and the plug‐in terminal blocks for proper seating. If all
connections are secure but the RMP still does not operate
correctly, replace the fuse. If this does not correct the problem,
contact your service representative for verification that the RMP is
working correctly.

Plug-in Terminal Block J1


to Industrial Relay Card

NOTE Conduit and wiring


supplied by the customer. The
maximum distance between
the RMP and the UPS is not to
exceed 152.4m (500 ft).

Figure 55. RMP Top Internal View

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 73
COMMUNICATION

Industrial Relay Card


The IRC uses normally-open or normally-closed dry relay contacts to
indicate the UPS status as listed in Table 6. Figure 56 shows an IRC.

Plug-in Terminal Block J1 to RMP

Plug-in Terminal Block J2


Cable Exit Opening for 1/2” Conduit from Relay Contacts
or Provided Strain Relief to Customer Monitoring Equipment

Figure 56. Industrial Relay Card

1. Verify that the UPS is turned off and all power sources are
removed.

2. Install wiring from the IRC to the monitoring equipment using 1/2”
conduit through the cable exit opening in the IRC (see Figure 56).

3. Connect wiring between the IRC and the monitoring equipment


using terminations shown in Table 6. See Figure 56 for plug‐in
terminal block locations.

4. Install the IRC into an open X-Slot communication bay (see


Figure 48 page 65).

5. To check the operation of the IRC, ensure that the UPS is supplying
the load via the inverter or bypass. If the indicators on the
customer's monitoring equipment show the appropriate status,
then it is operating correctly.

If the IRC is not operating correctly, check the wiring, the fuse on
the IRC, and the plug‐in terminal blocks for proper seating. If all
connections are secure but the IRC still does not operate correctly,
replace the fuse. If this does not correct the problem, contact your
service representative for verification that the IRC is working
correctly.

74 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

Table 6. IRC Wire Terminations


IRC Terminal Function Remarks

J2-1 NC

J2-2 COM Normal mode


J2-3 NO

J2-4 NC

J2-5 COM Bypass mode


J2-6 NO

J2-7 NC

J2-8 COM Battery mode


J2-9 NO

J2-10 NC

J2-11 COM Alarm mode


J2-12 NO

NOTE Maximum contact rating: 250 Vac, 30 Vdc @ 5A; Wire range: 16–24 AWG

Power Management Software


Each Eaton 9355 UPS ships with power management software and an
interface cable. To begin installing power management software, see
the instructions accompanying the Software Suite CD.

NOTE Use only the supplied communication cable to connect the UPS to your computer.

Power management software provides up-to-date graphics of UPS


power and system data and power flow. It also gives you a complete
record of critical power events, and it notifies you of important UPS or
power information. If there is a power outage and the Eaton 9355 UPS
battery power becomes low, power management software can
automatically shut down your computer system to protect your data
before the UPS shutdown occurs.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 75
COMMUNICATION

Control Terminals
The cables should be connected to the control terminals with a mating
connector. Input and output terminals have a functional isolation from
terminal to terminal. They are connected to the UPS chassis through
individual 1 MΩ resistors.

2 + Polarity
Signal Input 1 (programmable)
1 – Polarity

2 + Polarity
Signal Input 2 (programmable)
1 – Polarity
UPS
Connectors 2
(see Figure 46 on REPO Normally Open
page 63) 1

2
REPO Normally Closed
1

3 Common
2 Normally Closed Relay Output
1 Normally Open

Figure 57. External Control Terminal Connections

NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or
other mechanical control is preferred.

76 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

Remote Emergency Power-off


REPO is used to shut down the UPS from a distance. This feature can
be used for shutting down the load and the UPS by thermal relay, for
instance in the event of room overtemperature. When REPO is
activated, the UPS shuts down all converters, de-energizes all system
relays, trips the battery circuit breaker, and fully powers down within
10-15 seconds.
There are two REPO positions that may be used, normally-open or
normally-closed.
The pins on the normally-closed REPO connector are connected
together. When this connection is open, the logic circuitry completely
shuts down the UPS, thus preventing the power from supplying the
load.
If the use of normally-closed REPO operation is desired, replace the
connector with a normally-closed external switch (see Figure 46 on
page 63).
If the use of normally-open REPO operation is desired, connect a
normally-open external switch (see Figure 46 on page 63).

NOTE To restart the UPS, reconnect the REPO connector pins and turn on the UPS
manually. The pins must be shorted to keep the UPS running. Maximum resistance is 10 ohm.
NOTE Leave the REPO connector installed in the REPO port on the UPS rear panel even if
the REPO function is not needed.

CAUTION
S The REPO must not be connected to any utility connected circuits. Reinforced insulation
to the utility is required. The REPO switch must have a minimum rating of 24 Vdc and
20 mA.
S To ensure the UPS stops supplying power to the load during any mode of operation, the
input power must be disconnected from the UPS when the emergency power-off function
is activated.

REPO Connections

Wire Function Terminal Wire Size Rating Suggested Wire Size

REPO L1
12–22 AWG
18 AWG (0.82 mm2)
L2 (4–0.32 mm2)

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 77
COMMUNICATION

Relay Output Contacts


The UPS incorporates a programmable relay output with potential free
contacts for remote alarm indications (see Figure 46 on page 63). An
additional four relay outputs can be obtained with the X-Slot compatible
Relay Interface Card.

WARNING
The relay output contacts must not be connected to any utility connected circuits. Reinforced
insulation to the utility is required. The relay output contacts must have a maximum rating of
30 Vac/1A and 60 Vdc/2A nominal values.

Programmable Signal Inputs


The UPS incorporates two programmable signal inputs (see Figure 46 on
page 63). Use of non-polar (relay) control input is recommended. The
pins must be shorted with maximum resistance of 10 ohm in order to
activate the specific input.

NOTE See Figure 57 on page 76 for the polarity and verify these connections if polarity
control is required.

The default and programmable settings for the signal inputs are shown
in Table 7.

78 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
COMMUNICATION

Table 7. Programmable Signal Inputs


Signal Description

Disable Bypass Operation If active, the automatic transfer to the static bypass is prevented.

Charger Off If active, the battery charge function is disabled. In a utility power outage, the
discharge of batteries is supported.
Remote ON/OFF If active, the UPS output turns off regardless of the mode of operation.
Auxiliary power, fan, communication, and rectifier/battery charger remain
functional. Restart is initiated immediately when this signal is inactive.

Request Bypass If active, the UPS transfers to bypass if the bypass voltage, frequency, and
synchronization are all okay.
Request Normal If active, the UPS transfers to inverter operation if not prohibited by REPO or an
alarm condition.
Force Bypass If active, the UPS is forced to static bypass operation regardless of the bypass
status.
External Battery Breaker Status If active, the UPS knows that the batteries are disconnected.

Building Alarm 1–6 These alarms can be activated separately or at the same time with other
building alarms.
Not in Use Default

Shutdown If active, the UPS shuts down immediately.

Delayed Shutdown If active, the UPS shuts down after a user-configured delay time. Default
shutdown delay is 120 seconds. The UPS automatically restarts when the
signal changes to inactive.

Normal/Bypass If active, the UPS transfers to bypass if okay. If inactive, the UPS transfers to
the inverter when possible.
On Generator If active, the UPS knows that input is fed from the generator. Bypass is
disabled; the automatic battery test is disabled.
External Transformer This option is not used.
Overtemperature

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 79
COMMUNICATION

80 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 10 Operation

This chapter contains information on how to use the Eaton 9355 UPS,
including front panel operation, UPS startup and shutdown, and
configuring the UPS for Extended Battery Modules (EBMs).

Control Panel Functions


The UPS has a four-button graphical LCD with backlight. It provides
useful information about the UPS itself, load status, events,
measurements, and settings (see Figure 58).

Power On Indicator (green)


On Battery Indicator (yellow)
Bypass Indicator (yellow)
Alarm Indicator (red)

Control Buttons
for the LCD Menu Options

Figure 58. Eaton 9355 UPS Control Panel

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 81
OPERATION

The following table shows the indicator status and description.

Indicator Status Description

On The UPS is operating normally.

Green Flashing S The UPS is starting up or is shut down and waiting for power to return.
S A new information message is active.
S Bypass is not available.

Off The UPS is turned off and will not turn on automatically.

On The UPS is in Battery mode.

Yellow

On The UPS is in Bypass mode.

Yellow
On The UPS has an active alarm.

Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 105 for
Red additional information.

Changing the Language


Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.

Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the button to enter a submenu. Press the button
to select an option. Press the ESC button to cancel or return to the
previous menu.

82 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
OPERATION

The following table shows the basic menu structure.

Table 8. Menu Map for Display Functions


Main Menu Submenu Display Information or Menu Function

UPS Status UPS off / System normal / UPS supporting load / UPS on battery / UPS on
bypass / Active alarm list / Battery status
Event Log Displays up to 127 events and alarms

Measurements Output L-N and L-L / Current / Frequency / Power

Battery Voltage / Current / Runtime

Input L-N and L-L / Current / Frequency

Bypass L-N and L-L / Frequency

Control Go to Bypass Mode Transfers the UPS to internal Bypass mode


When this command is active, the option changes to Go to Normal Mode.
Start Battery Test Initiates a battery test

Display Test Four different selectable tests for the front panel functions: the LEDs cycle
through, the alarm beep sounds, the backlight turns off and on, and the
pixels scroll through to test the LCD.
Settings User Settings See Table 9 for detail.

Service Settings This screen is password-protected.

Identification UPS Type / Part Number / Serial Number / Firmware / Display / CAN Bridge

Turn UPS ON/OFF ON and OFF Options

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 83
OPERATION

User Settings
The following table displays the options that can be changed by the
user.

NOTE Changes to the output voltage or frequency options should be made before turning
on the UPS; otherwise, the changes do not take effect.

Table 9. User Settings

Description Available Settings Default Setting

Set Date and Time Set Month


Date: mm/dd/yyyy 01/01/2003
Time: 24:00 00:00

Display Contrast Adjust contrast with up/down arrow buttons Moderate

Change Language Select Language: <English> English


Elegir idioma <Español>
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or Alarm 1: empty
[X-Slot 2-1/2/3/4] X-Slots (1 or 2)
Setup: [Battery Low] [On Battery] [On #1: UPS ok
Bypass] [UPS ok] [custom] [empty] #2: On Bypass
#3: Summary Alarm
#4: On Battery

Signal Inputs [empty] [Logic] <empty>


(see “Programmable Signal Inputs” on
page 78)

Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv] 19200


Speed: [19200] [9600] [2400] [1200]
Modem Config Modem Installation <Not Installed>

Set Modem Call Events Event #0


Call modem: no
Set Modem Init String ATZ0

Set Modem Call Command None

Set Modem Communication Password None

Start Screen Eaton logo Eaton logo


Mimic screen
User Password Enabled/Disabled Disabled
If Enabled is selected, the password is USER.

84 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
OPERATION

Table 9. User Settings (continued)

Description Available Settings Default Setting

Audible Alarms Normal Sound/Disabled Normal Sound

Battery Charging ABM cycling/constant ABM cycling

Automatic Battery Tests Enabled/Disabled Enabled


Enabled automatically runs the battery test
once a month.

Full Power Battery Test Enabled/Disabled Enabled

Number of Battery Strings 0 through 22 2 strings for UPS-32 models


(see “Configuring the UPS for EBMs” on 4 strings for UPS-64 models
page 91)

Battery Capacity 1 through 65535 watts per cell 34 W/cell

Battery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell

Set Nominal Output Voltage Output: 120V/208V


[120V/208V] [127V/220V]
Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%

Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%

Nominal Output Frequency 50 Hz or 60 Hz 60 Hz

Synchronization Enabled/Disabled Enabled

Synchronization Window ±0.5 through ±3.0 Hz ±2.0 Hz


(0.1 Hz increments)
Unsynchronized Transfer to Bypass Allowed/Not Allowed Not Allowed

Output Frequency Slew Rate 0.1 though 5 hertz per second 0.5 Hz/s
(0.1 Hz increments)
Usage of Bypass Enabled/Disabled Enabled

Transfer to Bypass When Overload After a delay/Immediately After a delay

Automatic Start Delay -1 through 32767 seconds 0s


(-1 means disabled)
Control Commands from X-Slot1 Allowed/Disabled Allowed

Control Commands from X-Slot2/Serv Allowed/Disabled Allowed

X-Slot Signal Input Activation Delay 0 through 65 seconds 5s

Input signal delayed shutdown delay 1 through 65535 seconds 120s

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 85
OPERATION

Table 9. User Settings (continued)

Description Available Settings Default Setting

Site Wiring Fault Notice Enabled/Disabled Enabled

Reset Custom Event Settings 0 through 32 Total: 0/32

Auto Output Configuration Enabled/Disabled Enabled for initial startup


Disabled after initial startup

Initial Startup
Startup and operational checks must be performed by an authorized
Eaton Customer Service Engineer, or the warranty terms as specified on
page 109 become void. This service is offered as part of the sales
contract for the UPS. Contact service in advance (usually a two-week
notice is required) to reserve a preferred startup date.

UPS Startup
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS
installation and initial startup. Risk of electrical shock.

Verify that UPS installation has been carried out correctly and the UPS
ground has been connected.
Select one of the following startup options:

Startup Option Section

Normal mode “Normal Mode Startup” on page 87


Battery mode “Starting the UPS on Battery“ on page 88
Bypass mode “Internal Bypass Startup” on page 89
UPS maintenance bypass “UPS Maintenance Bypass Startup” on
page 90
Wall-mounted maintenance bypass “Wall-Mounted Maintenance Bypass
Startup” on page 90
Parallel UPS configuration Refer to the Eaton 9355 Parallel UPS
(10/15 kVA) User's Guide.

86 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
OPERATION

Normal Mode Startup


To start up the UPS when the load is de-energized:

1. If an optional wall-mounted bypass cabinet is installed, proceed to


Step 2; otherwise, proceed to Step 4.

2. Verify the wall mounted bypass is transferred to UPS mode (see


“Using the Wall-Mounted Bypass Cabinet” on page 97.

3. Proceed to Step 4.

4. Verify that the internal maintenance bypass switch is in the UPS


position (see Figure 59 on page 95).

5. If an optional isolation transformer is installed, switch the input


circuit breaker to the ON position (see Figure 12 on page 21).

6. Switch on utility power where the UPS is connected.

7. Wait for the front panel LCD to illuminate.

The indicator flashes.

8. Remove the breaker tie from all battery circuit breakers.

9. Switch all battery circuit breakers to the ON position.

The indicator stops flashing.

10. Press any button on the front panel display to activate the menu
options.

11. Press the button on the front panel display and then press the
button to select the TURN UPS ON/OFF menu.

12. Select the TURN UPS ON option. Press and hold the button for
three seconds, until the UPS stops beeping.

The indicator illuminates. The UPS is now powering the load.

If the indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 87
OPERATION

Starting the UPS on Battery


NOTE Before using this feature, the UPS must have been powered by utility power at least
once.

To start the UPS on battery when the load is de-energized:

1. If an optional wall-mounted bypass cabinet is installed, proceed to


Step 2; otherwise, proceed to Step 4.

2. Verify the wall mounted bypass is transferred to UPS mode (see


“Using the Wall-Mounted Bypass Cabinet” on page 97.

3. Proceed to Step 4.

4. Verify that the internal maintenance bypass switch is in the UPS


position (see Figure 59 on page 95).

5. Switch all battery circuit breakers to the ON position.

NOTE Leave the battery circuit breaker(s) in the ON position during this operation. If you
need to cancel this operation, wait until the front panel LCD illuminates before switching the
battery circuit breaker(s) off.

6. Wait for the front panel LCD to illuminate.

7. Press any button on the front panel display to activate the menu
options.

8. Within three minutes, press the button on the front panel display
and then press the button to select the TURN UPS ON/OFF
menu.

9. Select the TURN UPS ON option. Press and hold the button for
three seconds, until the UPS stops beeping.

The UPS starts in Battery mode within two minutes and supplies
battery power to your equipment.

88 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
OPERATION

Internal Bypass Startup


To start the UPS when load is powered by internal bypass:

1. If an optional wall-mounted bypass cabinet is installed, proceed to


Step 2; otherwise, proceed to Step 4.

2. Verify the wall mounted bypass is transferred to Bypass mode (see


“Using the Wall-Mounted Bypass Cabinet” on page 97.

3. Proceed to Step 4.

4. Verify that the maintenance bypass switch is in the SERVICE


position (see Figure 59 on page 95).

5. If an optional isolation transformer is installed, switch the input


circuit breaker to the ON position (see Figure 12 on page 21).

6. Switch on utility power where the UPS is connected.

7. Wait for the front panel LCD to illuminate.

The indicator flashes.

The UPS starts and transfers to Bypass mode. This may take up to
1 minute.

The indicator flashes while transferring to bypass then goes out


with the illuminating to indicate the UPS is operating in Bypass
mode. The load is now powered by utility power.

The display indicates On Manual/Maintenance Bypass.

8. To switch to Normal mode from internal Bypass mode, transfer the


wall mounted bypass to Bypass mode (see “Using the
Wall-Mounted Bypass Cabinet” on page 97 and rotate the internal
maintenance bypass switch to the UPS position.

The indicator illuminates to indicate the UPS is operating in UPS


mode. The load is now powered by UPS.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 89
OPERATION

UPS Maintenance Bypass Startup


To start the UPS in maintenance bypass:
1. Verify that the maintenance bypass switch is in the BYPASS
position (see Figure 59 on page 95).

2. If an optional isolation transformer is installed, switch the input


circuit breaker to the ON position (see Figure 12 on page 21).

3. Switch on utility power where the UPS is connected.

The load is now powered by utility power.

4. To transfer the load to the UPS, see “Using the UPS Maintenance
Bypass Switch” on page 95.

Wall-Mounted Maintenance Bypass Startup


To start the UPS in maintenance bypass (wall-mounted operation):

1. Verify that the bypass breaker is in the OFF position (see Figure 20
on page 32 or Figure 31 on page 45).

2. Switch on utility power where the wall-mounted bypass cabinet is


connected.

3. Switch the bypass breaker to the ON position.

The load is now powered by utility power.

4. To transfer the load to the UPS, see “Using the Wall-Mounted


Bypass Cabinet” on page 97.

90 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
OPERATION

Configuring the UPS for EBMs


To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:

1. Press any button on the front panel display to activate the menu
options.

2. Using the button, scroll to the Settings menu.

3. Press the button twice to select the User Settings menu.

4. Using the button, scroll to the Number of Battery Strings option


and press the button.

5. Use the or buttons to select the number of strings according to


your UPS configuration:

All 2-High UPS and EBM Cabinets* Number of Strings

UPS + 1 EBM 6

UPS + 2 EBMs 10

UPS + 3 EBMs 14

UPS + 4 EBMs 18

All 3-High UPS and EBM Cabinets* Number of Strings

UPS + 1 EBM 10

UPS + 2 EBMs 16

UPS + 3 EBMs 22

* UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.


UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.

6. Press the button to save the setting.

7. Press the ESC button until the Eaton logo appears.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 91
OPERATION

UPS Shutdown
To shut down the UPS:

1. Press any button on the front panel display to activate the menu
options.

2. Press the button on the front panel display and then press the
button to select the TURN UPS ON/OFF menu.

3. Press the button to select the TURN UPS OFF option.

4. Press and hold the button for three seconds, until the UPS stops
beeping.

The UPS stops supplying power to the load.

5. Switch the UPS battery circuit breaker to the OFF position.

The UPS disconnects from the batteries and is on logic power only.

6. Switch off utility power where the UPS is connected.

92 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 11 UPS Maintenance

This section explains how to:


S Care for the UPS and batteries
S Recycle used batteries or UPS
S Use the maintenance bypass switch

UPS and Battery Care


For the best preventive maintenance, keep the area around the UPS
clean and dust‐free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
77°F (25°C).

NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of
service life varies, depending on the frequency of usage and ambient temperature.
Batteries used beyond expected service life will often have severely reduced runtimes.
Replace batteries at least every 5 years to keep units running at peak efficiency.

Storing the UPS and Batteries


When storing the UPS and optional cabinets, the following requirements
should be met:
S Verify that the battery circuit breaker is in the OFF position.
S Avoid temperature and humidity extremes. To maximize battery life,
the recommended storage temperature is 59°F (15°C) to 77°F (25°C).
S If you store the UPS for a long period, recharge the batteries every
10 months by applying utility power. The batteries charge to 80%
capacity in approximately 3 hours. However, it is recommended that
the batteries charge for 48 hours after long-term storage.
S Check the battery recharge date on the shipping carton label. If the
date has expired and the batteries were never recharged, do not use
the UPS. Contact your service representative.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 93
UPS MAINTENANCE

When to Replace Batteries


When the indicator flashes and the LCD panel displays Battery
Failure, the batteries may need replacing. Contact your service
representative to order new batteries.
Change the batteries approximately every five years.

Recycling the Used Battery or UPS


Contact your local recycling or hazardous waste center for information
on proper disposal of the used battery or UPS.

WARNING
S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal requirements.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.

CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
lead‐acid batteries and must be disposed of properly. For more information, contact your
local recycling/reuse or hazardous waste center.

CAUTION
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.

94 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS MAINTENANCE

Using the UPS Maintenance Bypass Switch


The UPS maintenance bypass switch is located on the back of the UPS
(see Figure 59).
The maintenance bypass switch is used to bypass the UPS during
maintenance or servicing. The switch provides a wrap-around bypass
without shutting down the load. The SERVICE position on the switch
allows a service engineer to apply power to the UPS input and verify its
operation while the load is powered through bypass.

Figure 59. Maintenance Bypass Switch

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 95
UPS MAINTENANCE

To transfer the load from the UPS to maintenance bypass:

1. Set the system to internal Bypass mode:

S Using the button on the front panel display, scroll to the Control
menu option and press the button.

S Press the button to select the Go to Bypass Mode option.

The indicator illuminates and the indicator extinguishes,


indicating the UPS system is operating in Bypass mode.

2. Turn the maintenance bypass switch to the BYPASS position.

The battery circuit breaker trips, and the UPS is now bypassed, with
the load powered by utility power.

3. The UPS automatically shuts down.

To transfer the load from maintenance bypass to the UPS:

1. Turn the maintenance bypass switch to the SERVICE position.

The UPS starts up in Bypass mode, with the load still powered by
utility power.

2. Switch the UPS input and battery circuit breakers to the ON


position.

NOTE Wait until the indicator illuminates before proceeding to Step 3; otherwise,
power to the load may be lost.

3. Turn the maintenance bypass switch to the UPS position to return


to Normal mode.

The UPS is now powering the load.

96 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
UPS MAINTENANCE

Using the Wall-Mounted Bypass Cabinet


To transfer the load from the UPS to maintenance bypass:

1. Transfer the UPS to Bypass mode:

S Press any button on the front panel display to activate the menu
options.

S Using the button on the front panel display, scroll to the Control
menu option and press the button.

S Press the button to select the Go to Bypass Mode option.

The indicator illuminates and the indicator extinguishes,


indicating the UPS system is operating in Bypass mode.

2. Switch the bypass breaker (may be designated MBP or CBP) in the


wall-mounted bypass cabinet to the ON position.

3. If present, switch the maintenance isolation breaker (MIS) on the


wall-mounted bypass cabinet to the OFF position; otherwise,
switch the UPS breakers (may be designated MOB or UPS) on the
wall-mounted bypass cabinet to the OFF position.

The UPS is now bypassed, with the load powered by utility power.

To transfer the load from maintenance bypass to the UPS mode:

1. If the UPS was powered off, continue to Step 2.

If the UPS is already in Bypass mode, proceed to Step 6.

2. Switch on utility power where the UPS is connected.

3. Wait for the front panel LCD to illuminate.

The indicator flashes.

4. Switch all battery circuit breakers to the ON position.

The indicator stops flashing.

The UPS starts and transfers to Bypass mode. This may take up to
1 minute.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 97
UPS MAINTENANCE

The indicator flashes while transferring to bypass then goes out


with the illuminating to indicate the UPS is operating in Bypass
mode.

The display indicates On Manual/Maintenance Bypass.

5. Verify voltage is present on the UPS output by checking that an


output voltage reading present on the front panel LCD display.

The load is now powered by utility power.

6. If present, switch the maintenance isolation breaker (MIS) on the


wall-mounted bypass cabinet to the ON position; otherwise, switch
the UPS breakers (may be designated MOB or UPS) on the
wall-mounted bypass cabinet to the ON position.

7. Switch the bypass breaker (may be designated MBP or CBP) in the


wall-mounted bypass cabinet to the OFF position.

The UPS is now powering the load in Bypass mode.

8. Transfer the UPS to Normal mode:

S Press the button to select the Go To Normal Mode option.

S Press the ESC button until the Eaton logo appears.

The UPS is now powering the load in Normal mode.

98 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 12 Specifications

This section provides the following specifications:


S Model list
S Dimensions and weights
S Environmental and safety specifications
S Technical specifications
S Model specifications
S Battery specifications
S Battery runtimes

Table 10. Model List


UPS Description Power Rating

9355-10-32 2-high: UPS with one battery section 10 kVA, 9 kW


3-high: UPS with one battery and one isolation transformer section
9355-10-64 3-high: UPS with two battery sections 10 kVA, 9 kW

9355-15-32 2-high: UPS with one battery section 15 kVA, 13.5 kW


3-high: UPS with one battery and one isolation transformer section
9355-15-64 3-high: UPS with two battery sections 15 kVA, 13.5 kW

Extended Battery
Description
Module (EBM)

EBM-64 2-high: two battery sections

EBM-96 3-high: three battery sections

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 99
SPECIFICATIONS

Table 11. Dimensions and Weights


Dimensions (H W D) Weight

2-High UPS 32.2” 12” 33.5” (81 30 85 cm) 381 lb (173 kg)

3-High UPS-32 47.8” 12” 33.5” (121.5 30 85 cm) 587 lb (266 kg)

3-High UPS-64 47.8” 12” 33.5” (121.5 30 85 cm) 619 lb (281 kg)

2-High EBM 32.2” 12” 30.3” (81 30 77 cm) 480 lb (218 kg)

3-High EBM 47.8” 12” 30.3” (121.5 30 77 cm) 710 lb (322 kg)

Table 12. Environmental and Safety Specifications


Operating Temperature 50°F to 104°F (10°C to 40°C)
Optimal battery performance: 77°F (25°C)
Transit Temperature -13°F to 131°F (-25°C to 55°C)

Storage Temperature 32°F to 77°F (0°C to 25°C)


Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Ventilation Front air intake, forced air, two fans, positive pressurization,
temperature UPS-monitored
Altitude 9,843 ft (3,000m) operating without derating
32,810 ft (10,000m) during transportation
Relative Humidity 5–95% noncondensing

Audible Noise <56 dBA at 1 meter distance, typical loads


<62 dBA for heavy load, high ambient or high altitude, on battery
Surge Suppression ANSI C62.41 Category B3

Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;

Agency Markings cULus

EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003

100 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
SPECIFICATIONS

Table 13. Technical Specifications


Technology Online, double‐conversion topology with static bypass switch and
3‐position maintenance bypass switch.
Frequency independent operation.

Input Voltage Range 75/130–144/249 Vac per phase

Input Power Factor >0.99 at full load nominal line conditions

Input Rated Voltage 120/208 or 127/220 Vac three-phase

Isolation Transformer Input 480V or 600V ±20%


Voltage Range 60 Hz only
Input Frequency Range 45–65 Hz

Input Rated Frequency 50/60-Hz selectable, auto‐configuring

Output Voltage Regulation ±1% static, Phase to Neutral


±2% static, Phase to Phase
±5% dynamic at 100% resistive load change
Response time <1 ms

Output Voltage Distortion <2% THD linear load


<5% THD non‐linear load
Output Frequency 50/60-Hz selectable or auto‐configuring

Output Frequency Synchronization to line


Regulation

Output Overload 101–110% for 10 minutes


111–125% for 60 seconds
126–149% for 5 seconds
>150% for 300 milliseconds

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 101
SPECIFICATIONS

Table 14. Model Specifications

10 kVA Model

Output Voltage (Line–Line) 208 208 208 220

Output Voltage (Line–Neutral) 120 120 120 127

Input Voltage 208 480 (with input 600V (with input 220
isolation isolation
transformer) transformer)

Input Current 32.2A 16A 13.3A 30.5A

Output Current 27.8A 27.8A 27.8A 26.2A

Output kVA 10 10 10 10

Output kW 9 9 9 9

Efficiency (Minimum) 89% 83% 83% 89%

Heat Rejection [BTU/hr (kg-cal/hr)] 3798 (956) 6294 (1585) 6294 (1585) 3798 (956)

15 kVA Model

Output Voltage (Line–Line) 208 208 208 220

Output Voltage (Line–Neutral) 120 120 120 127

Input Voltage 208 480 (with input 600 (with input 220
isolation isolation
transformer) transformer)

Input Current 48A 24A 20A 45.7A

Output Current 41.6A 41.6A 41.6A 39.4A

Output kVA 15 15 15 15

Output kW 13.5 13.5 13.5 13.5

Efficiency (Minimum) 90% 85% 85% 90%

Heat Rejection [BTU/hr (kg-cal/hr)] 5122 (1290) 8134 (2048) 8134 (2048) 5122 (1290)

102 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
SPECIFICATIONS

Table 15. Battery Specifications


Battery Type 9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float
service life at 25°C (77°F), voltage 192 Vdc (96 cells per string)
Number of Strings Maximum of 22 strings per full configuration, including UPS batteries
(4 EBM-64 cabinets or 3 EBM-96 cabinets, plus UPS batteries)
UPS-32: 2 strings; UPS-64: 4 strings
EBM-64: 4 strings; EBM-96: 6 strings

Battery Replacement Must be replaced by a qualified service technician

Charger Service configurable 0.5–34A per string, with overall maximum of 34A (limited by input
current). Default: 3.4A per string
Charging Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage
after full load discharge
External battery: no more than 10x discharge time to 90% usable capacity at nominal line
voltage after full load discharge

Start-on-Battery Allows start of UPS without utility input

Performance ABM technology increases battery service life, optimizes recharge time, and provides a
warning before the end of useful battery life
Protection Extended Battery Module output protected by 100A circuit breaker

Table 16. Battery Runtimes (in Minutes) at Full Load


2-High Cabinets

32 Internal UPS
Load (1) EBM-64 (2) EBM-64 (3) EBM-64 (4) EBM-64
Batteries

15 kVA/13.5 kW 4 23 43 65 88
10 kVA/9 kW 8 37 69 106 144
3-High Cabinets

64 Internal UPS
Load (1) EBM-96 (2) EBM-96 (3) EBM-96
Batteries

15 kVA/13.5 kW 13 43 76 113
10 kVA/9 kW 22 69 124 184
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 103
SPECIFICATIONS

104 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 13 Troubleshooting

The Eaton 9355 is designed for durable, automatic operation and also
alerts you whenever potential operating problems may occur. Usually
the alarms shown by the control panel do not mean that the output
power is affected. Instead, they are preventive alarms intended to alert
the user. Use the following troubleshooting chart to determine the UPS
alarm condition.

Typical Alarms and Conditions


The following table describes typical alarms and conditions; check the
Event Log through the control panel for a list of active alarms. If an alarm
appears with a service code, please contact the Help Desk (see
page 107).

Alarm or Condition Possible Cause Action

On Battery A utility failure has occurred and the The UPS is powering the equipment with battery
UPS is in Battery mode. power. Prepare your equipment for shutdown.

LED is on.
1 beep every second.
Battery Low The battery is running low. Five minutes or less of battery power remains
(depending on load configuration and battery
charge). Save your work and turn off your
equipment.
LED is on. When utility power is restored, the UPS restarts
Continuous beep for automatically, provides power to the load, and
10 seconds. charges the battery.

Battery Breaker The UPS does not recognize the Verify the battery circuit breaker is in the ON
internal batteries. position. If the condition persists, contact your
service representative.
LED is on.
1 beep every second.
Overload Power requirements exceed the UPS Remove some of the equipment from the UPS. The
capacity (greater than 100% of UPS continues to operate, but may switch to
nominal; see page 101 for specific Bypass mode if the load increases. The alarm
LED is on. output overload ranges). resets when the condition becomes inactive.
1 beep every second.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 105
TROUBLESHOOTING

Alarm or Condition Possible Cause Action

Overtemperature UPS internal temperature is too high Turn the maintenance bypass switch to the
or the fan has failed. SERVICE position. Otherwise, shut down the UPS.
Clear vents and remove any heat sources. Allow
LED is on. the UPS to cool. Ensure the airflow around the UPS
1 beep every second. is not restricted.
If the alarm disappears, turn the maintenance
bypass switch back to the UPS position.
If the condition persists, contact your service
representative.

Battery test failed The batteries need service. Contact your service representative.

The UPS does not start. The main utility breaker is off. Verify that the main utility breaker is on.

If an optional isolation transformer is Verify that the isolation transformer input circuit
installed, the input circuit breaker is breaker is on.
off.

The remote emergency power-off Reset the REPO switch and restart the UPS. Verify
(REPO) switch is active or the REPO that the REPO connector is present.
connector is missing.
Power is not available at The UPS is in Standby mode. Supply power to the connected equipment: Press
the UPS output any button on the front panel display to activate the
receptacles. menu options. Press the button on the front panel
display and then press the button to select the
TURN UPS ON/OFF menu. Press the button to
select the TURN UPS ON option; press the
button. Press and hold the button for three
seconds, until the UPS stops beeping.

The UPS does not The batteries need charging or Apply utility power for 48 hours to charge the
provide the expected service. batteries. If the condition persists, contact your
backup time. service representative.

Battery circuit breakers are in the OFF Switch all battery circuit breakers to the ON
position. position.

Silencing the Alarm


Before silencing an alarm, check the alarm condition and perform the
applicable action to resolve the condition.
Press any button on the front panel display to silence the alarm. If the
alarm status changes, the alarm beeps again, overriding the previous
alarm silencing.

106 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
TROUBLESHOOTING

Service and Support


If you have any questions or problems with the UPS, call your Local
Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.

United States: 1-800-843-9433


Canada: 1-800-461-9166 ext 260
All other countries: Call your local service representative

Please have the following information ready when you call for service:
S Model number
S Serial number
S Firmware version number
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 107
TROUBLESHOOTING

108 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality
Chapter 14 Warranty

Limited Factory Warranty


Eaton 9355 UPS Products
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton (“Eaton”).
LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original end-user (the “End-User”)
of the Eaton 9355 UPS Products (the “Product”) and cannot be transferred. This Warranty applies even in the event
that the Product is initially sold by Eaton for resale to an End-User.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants,with the terms of this Warranty, that the Eaton
three-phase UPS electronics, Eaton-built accessories, and Eaton -built battery cabinets (individually and collectively,
the ”Warranted Items”) are free from defects in material and workmanship.
For Product installed (and currently located) in the fifty (50) United States and the District of Columbia, if, in the
opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or
replace such defective Warranted Item (including the costs of providing diagnosis, service, and labor [“labor
coverage”]). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such
other location as determined by Eaton. Any parts that are replaced may be new or reconditioned. All parts replaced
by Eaton shall become the property of Eaton.
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the
opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or
replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item
will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton. Any
parts that are replaced may be new or reconditioned. All parts replaced by Eaton shall become the property of
Eaton.
LIMITED WARRANTY PERIOD:
The period covered by this Warranty for Product installed (and currently located) in the fifty (50) United States and
the District of Columbia is ninety (90) days from the date of Product purchase for labor coverage and twelve (12)
months from the date of Product purchase or eighteen (18) months from the date of Product shipment, whichever
occurs first, for the refurbishment/replacement of parts.
The period covered by this Warranty for Product installed (and currently located) outside the fifty (50) United States
and the District of Columbia is ninety twelve (12) months from the date of Product purchase or eighteen (18)
months from the date of Product shipment, whichever occurs first, for the refurbishment/replacement of parts.
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the ”trickle charge” of batteries no
later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory;
(c) neglect, accident, fire, flood, lightning, vandalism, acts of God, Customer's neglect, abuse, misuse,
misapplication, incorrect installation; (d) repair or alteration not authorized in writing by Eaton personnel or
performed by an authorized Eaton Customer Service Engineer or Agent; or (e) improper testing, operation,
maintenance, adjustment, or any modification of any kind not authorized in writing by Eaton personnel or performed
by an authorized Eaton Customer Service Engineer or Agent.

Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality 109
WARRANTY

This Warranty is not valid: if the Product's serial numbers have been removed or are illegible. Any Warranted Items
repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty
subject to all the terms thereof. Labor warranty is not provided for Product located outside of the fifty (50) United
States or the District of Columbia. Any equipment, parts, or materials included in the Product and not
manufactured by Eaton are warranted solely by the manufacturer of such equipment, parts, or materials and are
not included as part of this Warranty. Batteries are not warranted by Eaton.
THIS WARRANTY IS THE END-USER'S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO OTHER
EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED).
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special, or consequential
damages of any kind or type whatsoever, or based on any claim or cause of action, however denominated. Eaton
shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In
no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
END-USER'S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must register the
product warranty (via mail or online at www.eaton.com/PQ/Register); use the Product in a normal way; follow the
Product's user's guide; and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Eaton's obligations under this Warranty are expressly conditioned upon receipt by Eaton of
all payments due to it (including interest charges, if any). During such time as Eaton has not received payment of
any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton
shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run
and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Warranty, including without limitation site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses, or labor of Eaton representatives outside the terms of this Warranty will be borne
by the End-User.
OBTAINING WARRANTY SERVICE: In the USA, call the Eaton Customer Reliability Center 7x24 at 800-843-9433.
Outside of the USA, call your local Eaton sales or service representative. For comments or questions about this
Warranty, write to the Customer Quality Representative, 8609 Six Forks Road, Raleigh, North Carolina 27615 USA.

110 Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev F www.eaton.com/powerquality

You might also like