Fundamentals Diagonestics Aux Xfo Excitation Loss Power Swing Detection System Protection Power System Analysis ABB
Fundamentals Diagonestics Aux Xfo Excitation Loss Power Swing Detection System Protection Power System Analysis ABB
Fundamentals Diagonestics Aux Xfo Excitation Loss Power Swing Detection System Protection Power System Analysis ABB
ABB
TEST REPORT
Asea Brown Boveri Ltda.
Report No.
Page 1 of 15
Factory: Asea Brown Boveri Ltda. Test Department:
Calle16 # 15-124 La Popa Dosquebradas
(Risaralda-Colombia)
ISO 9001 - ISO 14001 – OHSAS 18001 Date
of Issue:
Issued by:
Signature: ___________________________________
Approved by:
Signature: _________________________________
Tests Room Engineer Quality Manager
Customer: Test Object: Serial No.:
Customer Ref.:
Customer Specification:
Highest Rated Power:
Voltage:
Highest Rated Current:
BIL:
Connection:
Phase Displacement:
Frequency:
Cooling Condition(s):
Oil Temp. Rise:
Winding Temp. Rise:
ABB Reference:
Product Reference:
Order No.:
Name Plate No.:
Inspection and Test Plan:
Performed and Approved Tests:
Voltage Ratio
Winding Resistance
No Load Losses
Load Losses
Efficiency
Regulation
Applied Voltage
Induced Voltage
Insulation Resistance
Insulation Capacitance
Temperature Rise
Current Transformer Test
Applied Standards:
Witnessed by:
Comments:
ABB
TEST REPORT
Voltage Ratio
Report No.
Page 3 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
First Terminals:
Second Terminals:
Phase Displacement:
Tap Position Rated Voltage (kV) Measured Ratio
First
Terminals
Second
Terminals
First
Terminals
Second
Terminals
U-PN
x-z
V-PN
y-x
W-PN
z-y
Calculated
Ratio
(with
Multiplier)
Maximum
Difference
(%)
Remarks: Was checked the polarity and phase deviation.
ABB
TEST REPORT
Winding Resistance
Report No.
Page 4 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Reference Temperature:
Tested Terminal Names:
Average Oil Temperature:
Tap Resistance Between Terminals (W )
Positions U-PN V-PN W-PN
Average
Resistance
(W /Phase)
Resistance at
Reference Temp.
(W /Phase)
1
2
3
4
5
Reference Temperature:
Tested Terminal Names:
Average Oil Temperature:
Tap Resistance Between Terminals (W )
Positions x-y y-z z-x
Average
Resistance
(W /Phase)
Resistance at
Reference Temp.
(W /Phase)
-
ABB
TEST REPORT
No Load Losses
Report No.
Page 5 of 15
Serial No.:
1 Corrected to Sinusoidal Wave
Test Date: Test Engineer: Test Department:
Supplied Terminals: Tap:
1st O pen Terminals: Tap:
2nd Open Terminals: Tap:
Power Base: Rated Power:
Average Oil Temperature:
Measured Values Guaranteed
Vappl.
. xVmean
Vrms
1 11
1.11xVmean
(kV)
Vrms
(kV)
IA
(A)
IB
(A)
IC
(A)
Losses
(kW)
Losses1
(kW)
Current Losses
(kW)
Current
ABB
TEST REPORT
Load Losses
Report No.
Page 6 of 15
Serial No.:
1 Corrected to Reference Temperature
2 Corrected to Instrument Error
Test Date: Test Engineer: Test Department:
Supplied Terminals: Reference Temperature:
1st Shorted Terminals: Power Base:
2nd Shorted Terminals:
Connection Measured Corrected1 Guaranteed
Tap Positions
Supplied 1st
Shorted
2nd
Shorted
Supplied
Winding
Vrated
(kV)
Temp.
(°C)
Voltage
(kV)
Current
(A)
Losses
(kW)
Imp.
(%)
Losses
(kW)
Imp.
(%)
ABB
TEST REPORT
Efficiency
Report No.
Page 7 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Test Condition:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
0.80 0.80 0.80 0.80
1st Load Factor
Terminals
2nd
Terminals 25 % 50 % 75 % 100 %
Test Condition:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
0.90 0.90 0.90 0.90
1st Load Factor
Terminals
2nd
Terminals 25 % 50 % 75 % 100 %
Test Condition:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
1.00 1.00 1.00 1.00
1st Load Factor
Terminals
2nd
Terminals 25 % 50 % 75 % 100 %
ABB
TEST REPORT
Regulation
Report No.
Page 8 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
1st
Terminals
2nd
Terminals
1.00 0.90 0.80
ABB
TEST REPORT
Applied Voltage
Report No.
Page 9 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Frequency (Hz):
Supplied Terminals Voltage (kV) Duration (s)
ABB
TEST REPORT
Induced Voltage
Report No.
Page 10 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Tap Position For HV Terminals:
Supplied Terminals:
Frequency (Hz):
Tested Terminals Grounded Terminals Voltage (kV) Duration (s) P.D. Measured
ABB
TEST REPORT
Insulation Resistance
Report No.
Page 11 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Test Condition:
Applied Voltage:
Terminals Time
Tested Grounded Guard
Temp.
(°C)
Measured
Ratio 15s 30s 45s
Time
1m 0s 2m 0s 3m 0s 4m 0s 5m 0s 6m 0s 7m 0s 8m 0s 9m 0s
Tiempo
10m 0s
Remarks: Values in M -ohm
Test Condition:
Applied Voltage:
Terminals Time
Tested Grounded Guard
Temp.
(°C)
Measured
Ratio 15s 30s 45s
Time
1m 0s
Remarks: Values in M -ohm
ABB
TEST REPORT
Insulation Capacitance
Report No.
Page 12 of 15
Serial No.:
Fp(20) = Fp(T) / K
Doble:
Fp(20) = Power Factor corrected to 20C
Fp(T) = Power Factor measured at T degrees
K = Correction Factor (from Table below)
T (C) 10 15 20 25 30 35 40 45 50 55 60 65 70
K: BIL < 750 kV 0.8 0.9 1.0 1.12 1.25 1.4 1.55 1.75 1.95 2.18 2.42 2.7 3.0
K: BIL >= 750 kV 1.01 0.99 1.00 1.02 1.05 1.08 1.12 1.17 1.23 1.31 1.41 - -
ANSI:
T (C) 10 15 20 25 30 35 40 45 50 55 60 65 70
K 0.8 0.9 1.0 1.12 1.25 1.4 1.55 1.75 1.95 2.18 2.42 2.7 3.0
Test Date: Test Engineer: Test Department:
Applied Voltage for Capacitance:
Applied Voltage for Power Factor:
Equipment Type:
No Test Tested Grounded Guard (UST) Capacitance
[ pF ]
Power Factor
at 20 C (%)
ABB
TEST REPORT
Lightning Impulse
Report No.
Page 13 of 15
Serial No.:
1 Legend:
ANSI: Reduced Full-Wave RFW IEC: Reduced Full-Impulse RFI
Full-Wave FW Full-Impulse FI
Reduced Chopped Wave RCW Reduced Chopped Impulse RCI
Chopped Wave CW Chopped Impulse CI
Reduced Front-of-Wave RFoW
Front-of-Wave FoW
Test Date: Test Engineer: Test Department:
Test
Type 1
Tested
Terminal
Required
Voltage
(kV)
Test Voltage
(kV)
Tap
Position
Impulse
Shape
(m s)
Oscillogram
Number
ABB
TEST REPORT
Lightning Impulse
Report No.
Page 14 of 15
Serial No.:
1 Legend:
ANSI: Reduced Full-Wave RFW IEC: Reduced Full-Impulse RFI
Full-Wave FW Full-Impulse FI
Reduced Chopped Wave RCW Reduced Chopped Impulse RCI
Chopped Wave CW Chopped Impulse CI
Reduced Front-of-Wave RFoW
Front-of-Wave FoW
Test Date: Test Engineer: Test Department:
ABB
TEST REPORT
Current Transformer Test
Report No.
Page 15 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Checkup
Position Name Taps Measured Ratio Power
(VA)
Class Measured
Ratio
Measured
RatioPower system protection philosophy
TEST REPORT
Table Of Contents
Report No.
Page 2 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Voltage Ratio ......................................................................................................................................3
Winding Resistance ............................................................................................................................4
No Load Losses ..................................................................................................................................5
Load Losses ........................................................................................................................................6
Efficiency...........................................................................................................................................7
Regulation...........................................................................................................................................8
Applied Voltage ..................................................................................................................................9
Induced Voltage ................................................................................................................................ 10
Insulation Resistance ........................................................................................................................ 11
Insulation Capacitance...................................................................................................................... 12
Lightning Impulse ............................................................................................................................ 13
Current Transformer Test ................................................................................................................. 15
ABB
TEST REPORT
Asea Brown Boveri Ltda.
Report No.
Page 1 of 15
Factory: Asea Brown Boveri Ltda. Test Department:
Calle16 # 15-124 La Popa Dosquebradas
(Risaralda-Colombia)
ISO 9001 - ISO 14001 – OHSAS 18001 Date of Issue:
Issued by:
Signature: ___________________________________
Approved by:
Signature: