CS3000 Service v6 E5 09 1 E
CS3000 Service v6 E5 09 1 E
CS3000 Service v6 E5 09 1 E
Salwico CS3000
Service manual
Ver. 6
çConsilium
The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error
or damage resulting from the usage of this document.
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: cmab.got@consilium.se
Internet: www.consilium.se
Service Manual CS3000 Contents i
Contents
About this manual ..................................................................................................... ii
Chapter Control Unit gives a general description on how the Control unit
works.
Chapter The Circuit Board of the Control Unit describes the functions of the
Control unit’s circuit board.
For information regarding the Central unit’s various circuit boards refer to The
Circuit Boards of the Central Unit chapter.
DIP switch settings for all different parts of the CS3000 system are listed in
the DIP Switch Settings appendix.
The fault codes for CS3000 version 4 and 6 are listed in the Fault Codes
CS3000 Version 4 and Fault Codes CS3000 Version 6 appendixes
respectively.
For a more detailed description of the system refer to the CS3000 Reference
Manual.
Set address
(Access level 4)
Each control unit in the system must have a unique address in the interval 217
- 232. The control unit number must correspond with the number defined in
the Definition program. The control unit address must be set after the system
definition is downloaded and the system is restarted.
• Press F4 (MENU) until SERVICE is displayed on line 4.
• Press F1 (SERVICE).
• Press F1 (ADDRESS).
• Enter the address for the control unit. The address interval is 217 - 232.
Handling
Fuses
Function
Block diagram
1. Data buffer
The data bus is buffered before entering/leaving the board.
2. Address decoder
The address decoder selects the different blocks. The address decoder is
controlled by the control unit board.
3. Regulator
The regulator converts power voltage to 5 VDC.
4. Expansion
Future expansion possibilities. Not used.
5. Board ID
The control unit board reads the IKK-4 ID.
6. Inputs
Reads all external inputs.
7. Outputs
Controls the four transistor outputs.
8. Buzzer
An external buzzer may be connected via a transient protected output. The
buzzer will be parallel connected to the fire alarm and the fault buzzer on the
control unit board.
9. Barrier
The RS 232 communication is protected against transients before entering the
control unit board.
11. Barrier
The power supply voltage output is protected against external transients.
Technical data
Board size: 145 x 107 mm
General
The loop processor board SPK-2 controls and supervises two detector loops with
analogue and addressable detectors. The detectors are constantly polled in order to
detect faults or changes in alarm status. Detector-initiated alarms are also
recognised and verified. The events are reported to the LPK-2 and proper hardware
signals are then activated.
Handling
Indications
Model 1 There are nine LEDs on the front panel of the board.
No 1 (green) when lit:proper voltage supply.
No 2 (yellow) when lit:fault in loop #1.
No 3 (red) when lit:fire alarm in loop #1.
No 4 (yellow) when lit:fault in loop #2.
No 5 (red) when lit:fire alarm in loop #2.
No 6 (yellow) when lit:local processor failure
No 7 (in service mode) will flash synchronously with the central unit’s
communication with the loop-PCB.
No 8, 9 (in service mode) will flash synchronously with polling of the
loop-units
Model 2 & 3 There are eight LEDs on the front panel of the board.
No 1 (green) when lit:proper voltage supply.
No 2 (yellow) when lit:local processor failure.
No 3, 4 (green) (in service mode) will flash synchronously with polling of the
loop-units
No 5 (yellow) when lit:fault in loop #1.
No 6 (red) when lit:fire alarm in loop #1.
No 7 (yellow) when lit:fault in loop #2.
No 8 (red) when lit:fire alarm in loop #2.
Fuse
The battery voltage is fused. If the fuse is blown a signal is activated in the back
plane. The fuse is accessible on the front panel of the board, and can be used for
disconnecting the power.
Fuse ratings:
Model 1 & 2: 1 AT 5x20 mm
Model 3: 1.6 AT 5x20 mm
Setting the address
The address of loop #1 of the board is set with a DIP-switch (SW1), with 8
switches. Bit #1 is set with SW1-1, and bit #8 with SW1-8. The address of loop #2
is automatically set by the system to the next consecutive value.
Set the address of each SPK-2 according to the definition in the Definition
program.
Restarting the board
Remove the fuse from the board to disconnect the power. When the fuse is put back
on, the board is restarted.
Replacing the board
To replace the SPK-2 follow these steps:
1. Disconnect the power by removing the fuse.
WARNING!
The power must be disconnected before the board is removed.
Function
Block diagram Model 1 & Model 2
NB! In the diagram blocks 8 - 14 are doubled, one set for each detector loop.
1. Power supply
Power supply for processor, memory and logic of the loop processor board.
2. Control logic
Control logic for activation and blocking of hardware signals to the back plane.
LEDs for indication of status and communication are also controlled in this block.
3. LED indications
LEDs for indicating status of fire, fault, communication and voltage.
4. Drivers
Drivers for adapting hardware signal to the back plane.
5. CPU/Memory/watchdog
This is the main block of the SPK-2 board. The CPU controls both of the detector
loops and the communication with the LPK-2. The memory circuits contain the
programme code, default data for the detectors and status information. The
watchdog supervises the processor and checks for hang-ups in the programme
execution.
6. Address switch
The 8-bit address of the SPK-2, i.e. the loop number, is set with the DIP switch.
7. LPK communication
Interface for back plane communication.
8. DC/DC converter
The DC/DC-converter converts the battery voltage from the back plane to 30 VDC,
for the detector loops.
9. Signal filter
Signal filter for the communication signals.
10. Communication direction switch
For closed loops the choice of direction for the communication is made with this
switch.
11. Disconnection switch
With this switch the entire detector loop may be disconnected.
12. Barrier
Barrier for protecting the loops against incoming transients.
13. Basic-Alarm detection
Circuit for the detection of a basic-alarm.
14. Transmitter/receiver
Transmitter, receiver and interface for the processor bus.
15. Buses
The control signal bus contains signals to control the reading and writing of devices
connected to the address bus and the data bus.
DC/DC converter
Power is taken from the back plane and converted via a galvanically isolated
DC/DC converter into 35V. The 35V is used to power feed the loops and is also
converted to 5V for the logic. The voltage feed is fused.
Control logic
Signals in the back plane for fuse fault, voltage fault and prim-alarm. All signals
are galvanically isolated between SPK-2 and the back plane.
LEDs
Indicating status of the system. Some LEDs are active only in service mode.
CPU, memory and watchdog
The CPU controls and supervises the communication on both loops and also
communicates with the LPK. The memory contains program code with initial
values for the loop units and also gives status information. The watchdog
supervises the CPU and activates a reset signal to the CPU in case of malfunction.
Address switch
An 8-pole DIP-switch deciding the physical address of the board.
RS485 LPK communication
One asyncronous channel of the processor is used for communication with the
LPK. These signals are adapted to the RS485 levels and are galvanically separated
from the back plane.
Service plug
RS232 channel used for service, debugging and downloading of code.
Earth fault measurement
Measuring positive and negative earth faults. Since the board is galvanically
separated from the rest of the system, the measurement is a local indication of earth
faults from the loops. Earth fault is not measured when the board is used for
connection of GSK.
Loop : EMC protection
Protecting the electronics from various EMC disturbances.
Loop: Short circuit protection
Contains two parts, one part automatically disconnecting the loop power when the
current consumption exceeds allowed limit and one part which is used to control
the power feed to the primary and/or secondary side of the loop.
Loop: Line power
Feeding the loop with correct DC voltage and current and adapting the loop to the
signalling used on IDA and NOSE loops.
Loop: Current measurement
Measuring the DC current which is fed to the loop.
Loop: Signal filter
Separating and filtering out IDA/NOSE communication from the DC supply
voltage on the loop.
Loop: Line modem
Sending and receiving IDA/NOSE communication. Communication with the
processor via serial channel.
Jumpers Model 3
JP2 JP4
JP1 JP3
JP1 Must always be strapped in normal operation. The strap enables the
watchdog.
JP2 Never strapped during normal operation.
JP1 and JP2 are only strapped differently during production when the card is
programmed the first time.
Model 3
Board size: Single Europe board, 100 x 160 mm
Front panel: Anodised aluminium, width 6 TE(30.1 mm)
Salwico LPK-2
The battery voltage is fused. If the fuse is blown a signal is activated in
the back plane. The fuse is accessible on the front panel of the board,
and can be used for disconnecting the power.
Fuse rating: 1 A 5x20 mm
Model 1 Model 2
Function
Block diagram
BACK PLANE
1 FUSE
DC/DC
24 VDC
CONVERTER
TX/RX 6
INT.COM. TX/RX
3 2 LOOP (SPK)
LED- DIR
INDICATIONS
CPU 8 TX SYSTEM
SYSTEM
MEMORY TX/RX LOOP 1
COM. LOOP RX
WATCH-DOG
TX/RX 7 (CSM/LPK)
4 LOOP
ADDRESS COM. CONTR. SWITCH
SWITCH SYSTEM 8 TX SYSTEM
COM. LOOP LOOP 2
RX
TX/RX (CSM/LPK)
5 ADDRESS/DATA/CONTROL 9
REAL TIME DATA/ADDRESS
CLOCK BUFFERS
10
BACK PLANE
SIGNALS
11
BLOCK BASIC
ALARM
RELAY 12
OUTPUTS
1. DC/DC converter
The DC/DC circuit converts the battery voltage of the back plane to 5 VDC,
which is supplied to all logical circuits on the board.
2. CPU/Memory/Watchdog
This is the main block of the LPK-board. The CPU uses the memory circuits for
executing the programme code. There is also a non-erasable memory containing
the system configuration and the external controls. The watchdog supervises the
processor and checks that there are no hang-ups in the programme execution.
3. LED indications
One green LED indicates that the board is power supplied. If the watchdog is
activated (possible fault in the board), a yellow LED is lit, indicating system
fault. Furthermore there are two LEDs (one yellow and one red) indicating fault
and alarm in the central unit. Finally there are two green LEDs that are used for
service purposes.
4. Address switch
With the DIP switch the 8-bit address of the LPK is set.
5. Real time clock
The real time clock is keeping track of the time in the system. The clock has
built-in registers for seconds, minutes, hours, days, week-day, month and year
(including leap-years). The real time clock is reset from the control panel.
6. Internal communication loop (RS485)
The internal communication loop is connected to all SPKs in the same rack
system. All SPKs are polled and supervised via this loop.
7. Loop switch
The loop switch changes the communication channel from one external loop to
the other.
8. System communication loop (RS422)
This block contains the communication with control units and other central
units.
9. Data/address buffers
All bus connections going from the back plane are buffered in special buffer
circuits.
10. Back plane signals
Certain hardware signals in the back plane are read by the LPK after a voltage
conversion.
11. Basic-alarm
The basic-alarm function is activated if a SPK or the LPK is faulty and therefore
incapable of transmitting an alarm. This board will block the basic-alarm
function if the processor is in proper working order.
12. Fire brigade output
Two relay outputs for connection to the fire brigade. The alarm relay is
programmable and the other relay is activated when there are not muted faults in
the system.
Technical data
Board size: Single Europe board, 100 x 160 mm.
Front panel: Anodised aluminium, width 6 TE (30.1 mm).
Indications
The LED on the front panel of the board is lit every time the board is polled.
F1 F2 Fuses
F3 F4
There are 14 fuses on the front panel..
F5 F6
Jumper "PLUS"
With this jumper the pulse type can be altered. In the left position the pulse is
internally generated, in the right position the pulse comes from an external
source.
Switch S9
This switch is found on the front panel and is used for resetting the basic-
alarm.
Switch SW1
SW1-1, SW1-2, SW1-3 (B1, B2, B3)
"ON" : Steady signal to corresponding alarm bell output.
"OFF": Pulsed signal to corresponding alarm bell output.
SW1-7 (GA)
"ON" : Signal in step with the signal on the GA-input.
"OFF": Pulsing signal
Replacing the board
To replace the ARK-2 follow these steps:
1. Shut down the central by removing the fuses F3-F6 on the KE-2 rectifier.
WARNING!
The power must be disconnected before the board is removed.
Function
Block diagram
BACK PLANE
PTC
ALARM DEVICE 5
2 FUSE
DC/ DC FAULT BARRIER
CONVERTER
POWER SUPPLY 6
FUSE
FAULT BARRIER
FAULT
1 DET.
7
RELAY OUTPUT
3
PANEL CONTROL
LED SIGNALS 8
FIRE/ FAULT
PTC
OUTPUT
9 11
GA - RELAY
EPLD/ PI OUTPUT
GA
LOGIC
4 GA INPUT 12
PANEL GA INTERM. INPUT 13
SWITCH
10
DIP
SWITCH
16
OPTO ISOL.
uP BUS 17
1. EPLD/PIO
The EPLD/PIO includes I/O-circuit to the microprocessor and a programmable
circuit for all output, input and supervising functions on the board.
2. DC/DC-converter
The DC/DC-circuit converts the battery voltage of the back plane to 5 VDC,
which is fed to circuits on the board.
3. Panel-LED
The panel-LED is flashing when the board is being polled by the LPK.
4. Panel-switch
The panel-switch is used for manually resetting the alarm devices after a basic-
alarm.
5. Alarm device output
Three programmable, fused and fault-supervised alarm device outputs.
6. Power supply output
Two fused and fault supervised outputs for power supply to external devices.
7. Relay output
Three programmable, fused and potential free relay outputs.
8. Fire/fault output
One current-sinking programmable output for FIRE and one for FAULT.
9. GA-logic
The GA-logic controls the GA-output and the alarm device outputs depending
on the GA-input and pulsed output selection.
10. DIP-switch
The DIP-switch is used for setting a continuous/intermittent function of the
outputs 5 and 7 above.
11. GA-relay output
One fused and potential free relay output, which follows the GA-input.
12. GA-input
Input for connection of GA push button.
13. GA intermittent signal output
Input for connection of external intermittent signal for the GA.
14. External fuse fault input
Input for indication of fuse fault in external devices.
15. BASIC-ALARM input
16. Opto-isolated inputs
Four opto-isolated inputs for external signals.
17. Micro processor bus
Connection of micro processor bus to the LPK.
Technical data
Board size: Two joined single Europe board, 100 x 160 mm.
Front panel: Anodised aluminium, width 6 TE (30.1 mm).
Ambient temperature: -10° to +70°C.
Ambient humidity: 96% Rh.
Input power: Uin : 24 VDC (-20% - + 25%).
Current consumption: Iin nom: 30 mA
Iin max: 80 mA.
Inputs
Four opto isolated with common +
Input voltage: Uin max: 35 VDC
Input current Iin : 8 mA at Uin = 24 V
OneDG, 2880 ohm relay coil for 24 VDC, activated when low
Input voltage: Uin max: 35 VDC
Activation of relay: Uactmax: 7.2 VDC
One external intermittence, 10 kohm pull-up to +24 V, activated when low
Input voltage: Uin max: 35 VDC
One external fuse fault, 10 kohm pull-up to +24 V, activated when low
Input voltage: Uin max: 35 VDC
Outputs
Two power outputs, 24 VDC, Imax : 2 A
Three fault supervised, programmable alarm outputs, 35 VAC, Imax : 2 A
Three change-over, programmable relay outputs, 35 VAC, Imax. : 2 A
One change-over relay output for GA, Imax. : 2 A
Two open-collector outputs, PTC-protected, one programmable and one
activated at not muted fault in the central unit, Umax. : 24 V, Isink max.: 100 mA
Indications
There are two LEDs on the front panel of the board.
Function
Block diagram
BACK PLANE
1 2
+5V
DC/DC
CONVERTER
FUSE FAULT
SUPERVISION
POWER FAULT
4 5
3 ADDRESS BUS
LED CONTROL ADDRESS
INDICATOR LOGIC BUFFER
STATUS REGISTER
DATA
BUFFER
DATA BUS
8 8 8
INPUT BUFFER INPUT BUFFER INPUT BUFFER
9 9 9 9 9 9
4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO-
ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED
INPUTS INPUTS INPUTS INPUTS INPUTS INPUTS
INPUT CONNECTOR
1. DC/DC converter
The DC/DC circuit converts the battery voltage of the back plane to 5 VDC,
which is supplied to all logical circuits on the board. Should the voltage
disappear, a signal is activated in the back plane.
2. Supervision
The battery voltage is fused. If the fuse is blown a signal is activated in the
back plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
3. LED indications
On the front panel are two green LEDs for indicating 5V power and normal
polling.
4. Control logic
The control logic is used for decoding the address bus and for generating
signals to read/write the status register and read the input buffers.
5. & 6. Buffers
The address bus, the data bus and the control signals are buffered before
entering the board.
7. Status register
The status register is a read/write register. On reset the status is zeroed. Thus it
is possible to check the function of the board.
8. Input buffers
The signals on the inputs are buffered before entering the data bus.
9. Opto-isolated inputs
The inputs are divided into six groups, where each group has a common return
conductor. The inputs are protected by transient suppressors. Each input is
equipped with an LED that is lit when the input is active. These LEDs are not
visible from the front panel.
Technical data
Board size: Single Europe board, 100 x 160 mm.
Front panel: Anodised aluminium, width 6 TE (30.1 mm).
Inputs
24 opto isolated, transient protected in six groups with common return
conductor.
Input voltage: Uin max: 35 VDC.
Input current: Iin : 10 mA at Uin = 24 V.
Activated input: Iin min: 1.3 mA
Deactivated input: Iin max: 0.1 mA
Indications
In the front panel of the board are two LEDs.
Fuse
The battery voltage is fused. If the fuse is blown a signal is activated in the
back-plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
Fuse rating: 250 mAT 5x20 mm
Salwico UTK-2
Function
Block diagram
BACK PLANE
1 2
+5V
DC/DC
SUPERVISION
CONVERTER
FUSE FAULT
POWER FAULT
4
5
3
LED CONTROL ADDRESS
INDICATOR LOGIC BUFFER
10
STATUS REGISTER
DATA
CONTROL BUS
BUFFER
DATA BUS
7 8 7 8 7 8
OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT
STATUS LATCH STATUS LATCH STATUS LATCH
9 9 9 9 9 9
4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO-
ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED
OUTPUTS OUTPUTS OUTPUTS OUTPUTS OUTPUTS OUTPUTS
OUTPUT CONNECTOR
1. DC/DC converter
The DC/DC circuit converts the battery voltage of the back plane to 5 VDC,
which is supplied to all logical circuits on the board. Should the voltage
disappear, a signal is activated in the back-plane.
2. Supervision
The battery voltage is fused. If the fuse is blown a signal is activated in the
back-plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
3. LED indications
On the front panel are two green LEDs for indicating 5V power and normal
polling.
4. Control logic
The control logic is used for decoding the address bus and for generating
selection signals for read buffers and output buffers.
5. & 6. Buffers
The address bus, the data bus and the control signals are buffered before
entering the board.
7. Output status
The value written to the outputs can be read, to check the function of the
board.
8. Output latch
The output latches also functions as drive circuits for the opto switches.
9. Opto-isolated outputs
The outputs are divided into six groups, where each group has a common
positive conductor. The load is connected between the output and ground.
Each output is protected by a varistor and a freewheel diode for inductive
loads.
Technical data
Board size: Single Europe board, 100x160 mm
Front panel: Anodised aluminium, width 6 TE (30.1 mm)
Jumpers
The jumpers are factory set (as in the picture) for source output on all lines.
SOURCE SINK
Output group configuration. 4 outputs per group
Indications
There are nine LEDs on the front panel of the board.
No 1 (green) when lit: proper voltage supply.
No 2 (red) when lit: fire alarm in section #1
No 3 (yellow) when lit: fault in section #1
1 No 4 (red) when lit: fire alarm in section #2
3
2
No 5 (yellow) when lit: fault in section #2
4 5
6 7 No 6 (red) when lit: fire alarm in section #3
8 9 No 7 (yellow) when lit: fault in section #3
No 8 (red) when lit: fire alarm in section #4
No 9 (yellow) when lit: fault in section #4
Fuse
The battery voltage is fused. If the fuse is blown a signal is activated in the
back plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
Salwico GSK-2
Fuse rating: 2 AT 5x20 mm
Function
Block diagram
1 2
+5V
3 VOLTAGE STAB FUSE FAULT
AND
ADDRESS
SUPERVISION
SWITCH +12V
VOLTAGE FAULT
4 5
IDA SECTION 1
8
7 FIRE,FAULT 9 10
TEST AND INHIBIT
AND STATUS LOGIC BARRIER
TRANSMITTER/ DETECTION
RECEIVER
OFF
SECTION 2
8
7 FIRE,FAULT 9 10
TEST AND INHIBIT
AND STATUS LOGIC BARRIER
DETECTION
OFF
DIGITAL 16
OUTPUTS
CONTROL
LOGIC
D/A CONV. SECTION 3
8
2
7 FIRE,FAULT 9 10
2 TEST AND INHIBIT
AND STATUS LOGIC BARRIER
ANALOG 2
DETECTION
INPUTS 2
OFF
6 SECTION 4
8
LED 8
MONITOR 7 FIRE,FAULT 9 10
TEST AND INHIBIT
AND STATUS LOGIC BARRIER
DETECTION
OFF
1. Voltage stabiliser
The board has a local voltage stabiliser for 5 VDC power and 12 VDC power.
The 5 VDC is supplied to all logical circuits on the board. The presence of
both powers is indicated by an LED. If one of the voltages should disappear, a
signal is activated in the back-plane.
2. Supervision
The battery voltage is fused. If the fuse is blown a signal is activated in the
back-plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
3. Address switch
The address of the first section is set with this switch. The other three sections
automatically receive the next three consecutive addresses.
4. IDA
Alarm signals, fault signals and status information are collected by two IDA-
circuits, which communicate with the central unit. The IDA-circuits also
controls the sections.
5. Control logic
Alarms and faults are latched in the GSK-2 board and at reset from the control
unit the section is turned on and off again. Common fire alarms and cable
break fault signals are also generated in the GSK-2. The alarm and fault
signals are added which gives an analogue signal, enabling the IDA to give an
auto-alarm.
6. LED indications
Fire alarm and fault indication are indicated on the front panel by one LED
each per section.
7. Fire, fault and status detection
Fire alarms and faults are detected by two comparators. The signals are filtered
before reaching the comparators. The status signal is an analogue signal that is
used to indicate the status of the section, if it is "on", "off" or has disconnected
smoke detectors.
8. Test and inhibit logic
When the disconnect smoke detector function is activated the output voltage to
the sections is lowered to 12 VDC.
9. Electrical isolation
Each section can be electrical isolated from the central unit by a double relay.
10. Barrier
Each section output is protected against transients and hf-interference.
Technical data
Board size: Single Europe board, 100x160 mm.
Front panel: Anodised aluminium, width 6 TE (30.1 mm).
Outputs
Four supervised for connection of sections with conventional digital detectors.
Output voltage: Uin : 24 VDC (-20% -- + 25%).
Output current: Iout : 2.4 mA at Uin = 24 V.
Fire alarm: Iout min: 17 mA
Broken connection: Iout max: 0.8 mA
Indications
There are ten green LEDs on the front panel of the board.
No 1 when lit: proper voltage supply.
No 2 when lit: the board is properly polled.
No 3 when lit: RS232 channel #2 sending.
1 2 No 4 when lit: RS232 channel #2 receiving.
3 4
6
No 5 when lit: RS232 channel #2, RTS active.
5
7 8 No 6 when lit: RS232 channel #2, CTS active.
9 10 No 7 when lit: RS485 channel #1 sending.
No 8 when lit: RS485 channel #1 receiving.
No 9 when lit: RS485 channel #2 sending.
No 10 when lit: RS485 channel #2 receiving.
Fuse
The battery voltage is fused. If the fuse is blown a signal is activated in the
Salwico RS232K-2
back plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
Fuse rating: 250 mAT 5x20 mm
Function
Block diagram
BACK PLANE
1 2
+5V
DC/DC
CONVERTER
FUSE FAULT
SUPERVISION
POWER FAULT
4 5 ADDRESS BUS
CONTROL ADDRESS
LOGIC BUFFER
6
DATA BUS
DATA
BUFFER
7 8
9 10 12 13
14
14
11
1. DC/DC converter
The DC/DC circuit converts the battery voltage of the back plane to 5 VDC,
which is supplied to all logical circuits on the board. Should the voltage
disappear, a signal is activated in the back-plane.
2. Supervision
The battery voltage is fused. If the fuse is blown a signal is activated in the
back-plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
3. LED Indications
The 5 V voltage and proper polling are indicated by green LEDs. Send and
receive for both the RS485 channels as well as send and receive and two
control signals for one of the RS232 channels are also indicated by green
LEDs.
4. Control logic
The address bus is decoded and selection signals for the two double serial
channels are generated.
5. & 6. Buffers
The address bus, the data bus and the control signals are buffered before
entering the board.
7. & 8. DUART circuits
Two of the DUARTs are for the RS232 channels and two is for the RS485
channels. All parameters, such as baud-rate, parity, etc., are programmable.
9. & 10. RS232 adaptation
Adaptations of the signals from 5 V logic to RS232 logic and vice versa. The
signals from one channel are connected to a D-sub header on the front panel
and the other are connected to the back plane.
11. RS232 D-SUB HEADER
Male 9-pin D-sub header on the front panel with IBM PC/AT pin-standard.
12. & 13. RS485 adaptation
Adaptations of the signals from 5 V logic to RS485 logic and vice versa. The
signals from both channels are connected to the back plane.
14. Line protection
The line protector includes resistors for level definition of the line when not in
use. Line protection with zener diodes and varistors.
Technical data
Indications
There are ten green LEDs on the front panel of the board.
No 1 when lit: proper voltage supply.
No 2 when lit: the board is properly polled.
No 3 when lit: RS232 channel #1 sending.
1 2 No 4 when lit: RS232 channel #1 receiving.
3 4
6
No 5 when lit: RS232 channel #2, sending.
5
7 8 No 6 when lit: RS232 channel #2, receiving.
9 10 No 7 when lit: RS485 channel #1 sending.
No 8 when lit: RS485 channel #1 receiving.
No 9 when lit: RS485 channel #2 sending.
No 10 when lit: RS485 channel #2 receiving.
Fuse
The battery voltage is fused. If the fuse is blown a signal is activated in the
Salwico KPK-2
back plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
Fuse rating: 250 mAT 5x20 mm
Setting the address
The address of the board is set with a DIP-switch (SW1), two switches. The
recommended address and DIP-switch setting are provided in Appendix A.
Function
Block diagram
1. DC/DC converter
The DC/DC circuit converts the battery voltage of the back plane to 5 VDC,
which is supplied to all logical circuits on the board. Should the voltage
disappear, a signal is activated in the back-plane. The DC/DC converter aslso
supplies the serial port drivers with electric isolated power.
2. CPU/Memory/Watch-dog
Contains processor, memory, watch-dog and digital circuitry to provide system
function.
3. LED Indications
The 5 V voltage and proper polling are indicated by green LEDs. Send and
receive for both the RS485 channels as well as send and receive for the RS232
channels are also indicated by green LEDs. The serial channels can also be
enabled/disabled by the CPU.
4. DUART circuits
Two of the DUARTs are for the RS232 channels and two is for the RS485
channels. All parameters, such as baud-rate, parity, etc., are programmable.
Contains processor two serial ports which is connected to the RS485
tranceivers. The DUART also control certain I/O on the board.
5. Fuse fault
The battery voltage is fused. If the fuse is blown a signal is activated in the
back-plane. The fuse is accessible on the front panel of the board, and can be
used for disconnecting the power.
6. & 7. RS232 adaptation
Adaptations of the signals from 5 V logic to RS232 logic and vice versa. The
signals from one channel are connected to a D-sub header on the front panel
and the other are connected to the back plane.
8. & 9. RS485 adaptation
Adaptations of the signals from 5 V logic to RS485 logic and vice versa. The
signals from both channels are connected to the back plane.
10. & 11. Buffers
The address bus, the data bus and the control signals are buffered before
entering the board.
12. Board address
Selects the board address.
13. RS232 D-SUB HEADER
Male 9-pin D-sub header on the front panel with IBM PC/AT pin-standard.
Technical data
Rack CSR-3200
General
All PCBs in the central unit are mounted in a rack with a back plane. The back
plane supplies all the PCBs with power and channels for communication
between them. The rack has room for 14 PCBs. If needed, several racks can be
inter-connected. The rack fits into a standard 19" cabinet.
Handling
Reserved PCB locations
Certain slots in the rack are reserved for special purposes.
The relay board ARK-2 must be placed in slot #1 of the first rack and is the
only board allowed in this slot. If there are more than one rack inter-connected,
slot #1 in the other racks must be empty.
The alarm processor board LPK-2 must be placed in slot #2 of the first rack
and all boards communicating with the LPK-2 via the address and data bus
must be in the same rack. If there are more than one rack inter-connected, slot
#2 in the other racks may be used for other purposes.
If the interface board GSK-2 is used it may be placed in any available slot,
with the above exceptions. In this case a loop processor board SPK-2 must be
placed in the last slot (#14) of one of the racks.
Settings
The only necessary setting on the rack is made when an interface board GSK-2
shall be used for the connection of sections with conventional digital detectors.
In this case a SPK-2 board in slot #14 will be using the internal IDA-loop, and
therefore the two jumpers S01 and S02 must be set in their upper positions.
These two jumpers are normally set in their lower positions by the factory.
Function
Each board occupies 30 mm of the width of the rack. The slots in each rack are
numbered #1 - #14.
If more than one rack shall be inter-connected, this is done with flat cables
connected to headers on the rear side of the racks.
In order to prevent noise from loads connected to the relay board ARK-2 from
interfering with other boards, the power to the rack is divided in two separate
channels, one supplying the relay board and one for the rest of the rack.
Technical data
Type: Standard 19"
Height: 4 U (177 mm)
Depth: 215 mm
Number of slots: 14, each 6 TE width (30.1 mm)
Ambient temperature: -10°C -- +70°C
Humidity: 96 % Rh
Input power: Unom : 24 VDC (-20% -- + 25%)
Indications
There are seven LEDs on the front panel of the power unit.
Fuses
There are six fuses on the front panel.
WARNING!
When starting up the central first insert fuses F3+F4, and then F5+F6
in that order.
Technical data
Mains/emergency voltage: 230 V +10%/-15%
Mains/emergency frequence: 50-60 Hz
Output current : Imin: 0.1 A
Imax: 20 A*
Output voltage: Uout: 23 - 26 VDC
Urip: ± 0.2 VDC
*
Output current is of higher priority than battery charging current. If the
output current exceeds 8 A the battery charging current will decrease. The
battery charging current is equal to zero when the output current is equal to
20 A.
Battery charging
Charging current: Icharge: 0 - 10 A**
Charging voltage: Ucharge: 21.5 - 34.0 ± 0.2 VDC
**
The charging current and the charging voltage can be set individually for
the different charging phases. The charging current can be set between 0-10
A and the charging voltage can be set between 21 - 34 VDC.
The address set on the DIP sitch must correspond to the address specified in the
Definition program .
INK-2
Address Hex.
CC
RS232K-2 board 1
Address Hex.
E0
RS232K-2 board 2
Address Hex.
80
UTK-2 board 1
Address Hex.
B0
UTK-2 board 2
Address Hex.
B4
UTK-2 board 3
Address Hex.
B8
UTK-2 board 4
Address Hex.
BC
UTK-2 board 5
Address Hex.
C4
UTK-2 board 6
Address Hex.
C8
KPK-4 board 1
ON Address Hex.
100
KPK-4 board 2
ON Address Hex.
200
The word FAULT is displayed on the first line of the display together with a fault
code followed by the section number and the address for the section unit causing the
problem, if the system has this information. Additional text is displayed on line two, if
provided. A few fault codes can not be displayed with all this information. These fault
codes are marked with an asterisk (*) in the summary below.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
5 SECTION(S) MISSING
The main central unit is missing a section after cold start.
Cause Remedy
6 ADDITIONAL SECTION(S)
An additional section has been found by the central unit after cold start.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
22 NO ANSWER
No polling answer from a section unit.
Cause Remedy
24 WRONG STATUS
Incorrect answer from the section unit.
Cause Remedy
25 WRONG ID
The software does not recognise the ID of a section unit.
Cause Remedy
Cause Remedy
41 SECTION BOOTING
A section in the system has generated a boot signal.
Cause Remedy
42 BOOT DISABLED
A section unit was disconnected by the system during the initialisation.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
81 MAINS FAULT
Mains power failure.
Cause Remedy
83 FUSE FAULT
A fuse in the central unit is blown. Different messages are displayed depending
on the location of the fuse.
Cause Remedy
84 VOLTAGE FAULT
Too low voltage in the system.
Cause Remedy
85 I/O-FAULT
An I/O-board is faulty or missing.
Cause Remedy
Cause Remedy
93 FUSE/CABLE FAULT
A fuse in the central unit is blown or there is a cable break. Different messages
are displayed depending on the location of the fuse.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
One of the system loops, a Mend the cable. See Cable break
detector loop or a conventional at the end of this chapter.
loop is faulty.
Cause Remedy
Cause Remedy
Short circuit on detector loop See Short circuit at the end of this
chapter.
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
Cause Remedy
Cause Remedy
Cause Remedy
Earth fault between positive See Earth fault at the end of this
terminal and earth. chapter.
Cause Remedy
Earth fault between negative See Earth fault at the end of this
terminal and earth. chapter.
Cause Remedy
Too low system voltage from the Test the rectifier and measure the
power unit. voltage.
Too low voltage: → Exchange the
rectifier.
Normal voltage: → Exchange the
IOK-4 board.
Cause Remedy
Too high system voltage from Test the rectifier and measure the
power unit. voltage.
Too high voltage: → Exchange the
rectifier.
Normal voltage: → Exchange the
IOK-4 board.
Cable break
No answer from any section unit
− The cable is broken before the first section unit on a single ended loop.
− The cable is broken before the first section unit at least once and it is also broken
after the last section unit, if the loop is a double ended loop.
Earth fault
• Check the earth fault circuit, change it if it is faulty.
• If the circuit is working properly, check the loops one by one.
• Disconnect the loops one by one, see Disconnection, Electric isolation of a loop.
Short circuit
No answer from any section unit
Search for the short circuit between the central unit and the short circuit
isolator.
Proceed as follows when you want to locate an earth fault. Divide the cable in two
halves, locate the earth fault on one of the halves. Thereafter divide this part of the
cable into two halves. Continue to divide the cable into halves until you have found
the earth fault. If you are using a multimeter use the diode tester range.
Fuses
Check the fuses on the boards included in the system. The fuses are mounted on the
front panels on the following boards: ARK-2, GSK-2, INK-2, KPK-4, LPK-2,
RS232K-2, SPK-2 and UTK-2. The fuses to the IKK-4 are mounted on the board
itself.
* The central unit is not working properly. Indicator No. 1 (green) is not lit.
FIRE IN SYSTEM
There is a fire alarm in the system and the LPK board is not answering.
Cause Remedy
Cause Remedy
3 MISSING CENTRAL
The main central unit is missing a sub-central after cold start.
Cause Remedy
4 ADDITIONAL CENTRAL
The central unit found an additional sub-central unit after cold start.
Cause Remedy
5 LOOP(S) MISSING
The main central unit is missing a loop after cold start.
Cause Remedy
6 ADDITIONAL LOOP(S)
The central unit found an additional loop after cold start.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
The loop has not been defined properly at Redefine the loop.
the installation.
Cause Remedy
Cause Remedy
Cause Remedy
Bad communication with one or several Exchange the loop unit if the
loop units. condition remains or returns.
22 NO ANSWER
The loop unit doesn't answer.
Cause Remedy
Cause Remedy
25 UNKNOWN ID
The software does not recognise the ID of a loop unit.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Loop modem cannot transmit. Turn off the power, wait for 5
minutes, then restart the system.
Faulty loop unit. Search for the faulty unit by
interval-halving and replace the
unit.
29 COMMUNICATION ERROR
A loop unit has sent a wrong checksum.
Cause Remedy
Two loop units have the same address. Check the addresses of the units
and set correct adresses.
Loop unit faulty. Exchange the unit.
Cause Remedy
The LPK in the main central unit is not The LPK is faulty. Replace it.
answering.
Cable break in the system loop. Check the cable.
41 BOOTED
A loop in the system has generated a boot signal.
Cause Remedy
42 BOOT DISABLED
A loop unit was disconnected by the system during the initialisation.
Cause Remedy
Cause Remedy
44 ILLEGAL ADDRESS
The received address does not correspond with the sent address.
Cause Remedy
Cause Remedy
The loop unit has no active outputs. Error Download new set-up data.
in the site set-up.
Cause Remedy
Cause Remedy
Cause Remedy
The communication between the loop units Localize the faulty unit and replace
is interrupted either because a hanging for it. Localization can be done e.g. by
more than 20 seconds on a certain unit or interval-halving technique.
because a polling cycle takes too long
time.
The fault can appear when a command is
given to set outputs for a particular loop
unit.
81 MAINS FAULT
Mains power failure.
Cause Remedy
Example:
FAULT (81) 1 POWER MAINS FAULT
Mains power failure in the power unit.
83 FUSE FAULT
A fuse in the central unit is blown. Different messages are displayed depending
on the location of the fuse.
Cause Remedy
A fuse is blown. In the display is shown Exchange the fuse. See Fuses at the
which fuse is blown. end of this chapter.
84 LOW VOLTAGE
Too low voltage in the system.
Cause Remedy
85 I/O-FAULT
An I/O-board is faulty or missing.
Cause Remedy
Cause Remedy
93 FUSE/CABLE FAULT
A fuse in the central unit is blown or there is a cable break. Different messages
are displayed depending on the location of the fuse.
Cause Remedy
A fuse is blown in the central unit. Exchange the fuse. See Fuses at the
end of this chapter.
Cable break. Mend the cable. See Cable break at
the end of this chapter.
Example:
FAULT (93) EXT.ALARM 9 FUSE/CABLE FAULT
A fuse blown or a cable break in external alarm device 9.
Cause Remedy
A fuse is blown in the central unit. Exchange the fuse. See Fuses at
the end of this chapter.
Cable break. Mend the cable. See Cable break at
the end of this chapter.
Cause Remedy
The alarm function in the detector does not Exchange the detector.
work.
Cause Remedy
Cause Remedy
Cause Remedy
One of the system loops, a detector loop or Mend the cable. See Cable break at
a conventional loop is faulty. the end of this chapter.
Example:
FAULT (121) EXT.COMM 2 CABLE BREAK
The cable break is in system loop no 2. The fault can only be reset when the
central is allowed to communicate on the loop. This message can only emanate
from the central unit itself.
Cause Remedy
Cause Remedy
Short circuit on detector loop See Short circuit at the end of this
chapter.
Cause Remedy
Cause Remedy
Cause Remedy
Earth fault between positive terminal and See Earth fault at the end of this
earth. chapter.
Cause Remedy
Earth fault between negative terminal and See Earth fault at the end of this
earth. chapter.
Cause Remedy
Too low system voltage from the power Test the rectifier and measure the
unit. voltage. If necessary exchange the
rectifier.
Cause Remedy
Too high system voltage from power unit. Test the rectifier and measure the
voltage. If necessary exchange the
rectifier.
Cause Remedy
Cause Remedy
Cause Remedy
A door is still open one minute after the Check the door.
instruction to close it was sent.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
There is no response from the door- Check the door-holder relay and its
holding relay. cable.
Cause Remedy
Cause Remedy
Cause Remedy
Check for a cable break on positive lead. Mend the cable break.
A tripped short circuit isolator can cause Check the short circuit isolators.
this fault.
Cause Remedy
Check for a cable break on negative lead. Mend the cable break.
A tripped short circuit isolator can cause Check the short circuit isolators.
this fault.
Cause Remedy
Check the ID setting of the faulty unit. Set a correct value on the DIP-
switch of the unit.
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
Cause Remedy
The battery charger is unable to charge the Check the battery charger and the
battery. battery.
Cause Remedy
Cause Remedy
Check the offending units against Set correct addresses for the units,
drawings. with the DIP-switches.
Cause Remedy
Cable break
No answer from any loop unit
• The cable is broken before the first loop unit on a single ended loop.
• The cable is broken before the first loop unit at least once and it is also
broken after the last loop unit, if the loop is a double ended loop.
Earth fault
• Check the earth fault circuit, change it if it is faulty.
• If the circuit is working properly, check the loops one by one.
• Disconnect the loops one by one, see Disconnection, Electric isolation of a
loop.
Short circuit
No answer from any loop unit
• Search for the short circuit between the central unit and the short circuit
isolator.
Proceed as follows to locate an earth fault. Divide the cable in two halves and locate
the earth fault on one of the halves. Thereafter divide this part of the cable into two
halves. Continue dividing the cable into halves until the earth fault has been found. If
you are using a multimeter use the diode tester range.
Fuses
Check the fuses on the boards included in the system. The fuses are mounted on the
front panels on the following boards: ARK-2, GSK-2, INK-2, KPK-4, LPK-2,
RS232K-2, SPK-2 and UTK-2. The fuses to the IKK-4 are mounted on the board
itself.
* The central unit is not working properly. Indicator No. 1 (green) is not lit.