Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Power Quality Improvement in A Grid Integrated Solar PV System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/323507016

Power quality improvement in a grid integrated solar PV system

Conference Paper · March 2017


DOI: 10.1109/ITCOSP.2017.8303144

CITATIONS READS

2 1,334

3 authors:

C.Shiva Eee Ratakonda Bhavani


Sethu Institute of Technology Gokaraju Rangaraju Institute of Engineering & Technology
2 PUBLICATIONS   2 CITATIONS    7 PUBLICATIONS   19 CITATIONS   

SEE PROFILE SEE PROFILE

Rathina PRABHA N.
Mepco Schlenk Engineering College
19 PUBLICATIONS   50 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Performance Analysis of STATCOM with Different Loading Conditions View project

All content following this page was uploaded by C.Shiva Eee on 18 September 2018.

The user has requested enhancement of the downloaded file.


2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , O PTIMIZATION AND SIGNAL P ROCESSING

Power Quality Improvement in a Grid


Integrated Solar PV System
C.Shiva R.Bhavani N.Rathina Prabha
PG scholar, Dept. of EEE Asst Professor (Sr.Gr), Associate Professor, Dept. of EEE
Mepco Schlenk Engineering Dept. of EEE Mepco Schlenk Engineering
College Sivakasi, Tamilnadu, Mepco Schlenk Engineering College Sivakasi, Tamilnadu,
India. College Sivakasi, Tamilnadu, India
shiva220593@gmail.com India. nrpeee@mepcoeng.ac.in
bavanir@mepcoeng.ac.in

Abstract - At present, Power Quality is one of the key them, the solar energy is the main spotlight of the energy
elements, which influences the economy of a nation. that can be developed and to be consumed. PV production
Due to rising of population utility supplies excess is renowned as main methodological data and the
power to meet the increasing demand of the predicting technology, because of its prevalence upon
consumers. To maintain the pollution and the global environmental defence [1]. Inverter topology is the
warming within the particular level alternate sources leading topology of PV grid. As the crossing point devices
of energy have used which devolops the pollution less across solar cells and the grid, inverter plays a crucial
environment. To overcome those issues non- piece in developing and consuming the new energy
conventional energy come into picture. The whole schemes, disturbing the financial side and consistency of
performance of the electrical utility can be improved the photovoltaic (PV) grid generation system openly. To
by the usage of non-conventional energy resources. get better PV grid inverter work transmission and
There are different forms of Renewable Energy consummation excellence is the sudy to be focused in
Resource (RES) are available. Among them solar upcoming era[2-4].
energy is mostly used because it is abundantly
available in nature. In addition it has lot of advantages
such as no air pollution, no fuel cost, noiseless and low
maintenance. Integrating solar power to the grid has
adverse effect on the power quality in the grid. In a
few PV based framework, the inverter is a key
segment which is responsible for the control of power
stream between the dc source, and loads or lattice.
This paper describes the difficulties and issues in the
area of power quality the due to the integration of
solar power in to grid are to be analysed. The Shunt
Active Power Filter (SAPF) with PI controller is to be Fig. 1. Block diagram of proposed system
designed to enhance power quality in the grid
integrated solar system. Grid Connected solar PV system is a kind of electrical
inverter that alters DC current from PV module into
Keywords: Solar PV system, Converter, Inverter, Fuzzy alternating current (AC). When the PV system is
logic, Power quality, Shunt active power filters. associated to the grid, it can transmit the extra energy to
the grid after satisfying the limited demand. But when the
I.INTRODUCTION demand is more than the generation, extra energy is
obtained from the grid. Thus PV energy acts as another
Requirement of energy for the human is escalating step by source of electricity. The PV system, considered in this
step due to globalisation and industrialization. In work, aims to relocate electrical power from PV panel to
harmony with the above case, since the twentieth century, the grid. Firstly, DC-DC Converter is used to boosts PV
nations across the world are enchanting process, but the voltage to a higher level than the peak of grid voltage [5].
main problem is to solving the prevention of energy Power converters are used for interfacing the RES to
getting extinct and to forfending our environment from power system. When the power converters are utilized,
pollution by amending newer technology in the field of they introduces the harmonics in the system. Conversely,
energy. Expanding the fresh and non-conventional energy, the increased use of sensitive electronic circuits in the
for purpose of obtaining them and maintaining tham at a industries and household jointly with privatization and
constant growth rate is the vital task. In the middle of rivalry in electric energy systems, pose the power quality

448 978-1-5090-4777-2/17/$31.00 ©2017 IEEE


2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , O PTIMIZATION AND SIGNAL P ROCESSING

improvement as one of the key problems in electrical related to the integrated configuration are hurdles for its
industry. Harmonics causes distortion of source voltage, broad utilization. Use of electrolytic capacitors can reduce
addition loss due to unwanted current flowing in the the life span is also a downside for this access. Since the
source. And also it may guide to misoperation of relays, module-integrated inverter is implemented on the rear of
mains and other control units. So it is necessary to reduce the PV array casing should maintain unsympathetic
the harmonics there a many techniques to reduce the circumstances and excess temperature. The duration of
effect of harmonics [6, 7]. One of those methods is to use electrolytic capacitors, which has shorter span than other
SAPF which produce harmonic current of equal apparatus and deeply depends upon operational
magnitude and opposite polarity to that of the harmonic temperature, becomes the key barrier to expanding the life
current produced in the system such that it cancels the span of PV unit production.
harmonic current in the system. It has a high speed
response and flexibility in operation as it contains the In this article, a dc PV generation crossing point is in view
power electronic devices. of proposed as a compensatory answer for AC module
idea. Employing the significance of the ac module theory,
Shunt Active Power Filter (SAPF) is proficient of dc interfaced PV production systems are cheap and has
concurrently compensates the harmonics, current distort, higher effectiveness because of less transformation stages
and injecting the power produced by non conventional from source to stack. Additionally, consistency point are
resources [8-10]. The SAPF is a voltage source inverter transmitted by eradicating the shorter lifespan of
(VSI), is related to the load. Shunt Active Power Filter electrolytic capacitors in the PV circuit. Therefore PV cell
can keep the current balanced and sinusoidal after can be modelled as a current source which generate
remuneration for different load conditions. The DC to AC current IL. The current flows in the reverse path and which
power conversion is the result of power switching devices, is caused by a voltage between the terminals. The series
[11]. The output waveforms are consequently prepared up resistance (Rs) is due to the fact that solar cell is perfect
of distinct values, producing the output which are more insulator. The shunt resistance (Rsh) is due to leakage of
oscillatory rather the filtered ones . The capacity to deliver current from 1 terminal to the other due to underprivileged
close sine waveforms around the key recurrence is insulation. In an ideal solar cell, Rs=0 and Rsh=∞. The
directed by the regulation technique tyrannical when and simplified equivalent circuit of solar PV cell is shown in
how long the power values can become active in nature. the Fig.1
General techniques, include the pulse width modulation,
fuzzy control based technique is used. The design
scheme and configuration of these devices is based on
combination of traditional power system components and
power electronic elements [12, 13]. In this project, the
difficulties and issues involved in the zone of power
quality due to the integration of solar power in to grid are
to be analysed. The suitable fuzzy control technique is to
be designed and modelled to get better power quality in Fig. 2. Equivalent circuit of PV cell
the grid integrated solar system.
The characteristic equation of Photovoltaic cell is
II. PV GENERATION
q(V IRs )
Advancement in the field of solar energy leading to the I I pv I s exp 1
AkTc
cheaper rate of PV cells and the rates are decreasing day
by day, though they are advancing but solar energy is I IL Id I sh
costing higher among the other available sources. Due to
the higher cost, solar powered system can be setting up Where,
with the help of funds given by the government. I = Output current of PV panel (A)
Effectiveness and rate are vital driven factors on the PV IL =Current generated by PV cell (A)
merchadise. The effectiveness of the PV circuit is ID =Current through diode (A)
moderately high and the unit rate is cheap due to its high Ish=Current through shunt resistor (A)
power capacity. Yielding the energy will be improved by Rs =Series Resistance(R)
and security issues will eradicated by appending the Q =Electron charge (1.6 x 10-19C)
stimulant at the back of the segment so consumers are K=Boltzmann’s constant (1.381 x 10-23J/K)
uncovered to high dc voltage. Establishment gets to be T=Junction temperature (K)
distinctly simpler by assign the ac unit scheme, yielding N=Diode ideality factor (1~2)
effectiveness can be kept at peak even in variance
condition. But it is relatively expensive and less effective

449
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , O PTIMIZATION AND SIGNAL P ROCESSING

The PV cell power is P = V.I The inductor current detoirates until the next cycle. The
energy stored in inductor L flows through the load. The
Where, V= PV panel output voltage . total of vitality put away in the inductor during ON time
I =PV panel output current. and the supply current will courses through the load
resistor (RL) and the capacitor (C) when switch is OFF.
TABLE 1 PARAMETERS OF PV MODULE Thus the voltage across the load is (VIN +VL).The
proposed converter is designed with the specifications
Parameters Values shown in Table 2 then modelled using MATLAB shown
Rs 0.62 Ω in Fig 3(a).
Is 3.8 A
Rsh 250.57 Ω TABLE 2 DESIGN SPECIFICATION OF CONVERTER
Voc 21 V
Ig 1.13 A Parameters Values
N 1.3 Input voltage (Vs ) 21.1 V
Tc 298 Output voltage (V0) 230V
N 36 Switching Frequency 20khz
Duty Cycle (α) 0.9
Table 1 shows the Parameters for the Solar PV panel. Inductance(L) 0.8 mH
From the specifications the experimental operation had Capacitor(C) 9.1 μF
been done. Resistor(R) 500 Ω

III. DC TO DC CONVERTER WITH PI The oscillations from the boost converter are rectified by
CONTROLLER using PI controller. The converter outputs with and
without PI controller are shown in Fig 3(b, c).
DC to DC converters at this time used is Boost converter,
where input voltage (DC) is a smaller than output voltage
(DC).That means boost converter output is higher than the
PV input. Hence, boost converter is required for the PV
system with PI controller to boost-up the voltage of the
PV system. DC-DC Converters are used for dc-input
voltage which is then converted to desired dc-output
voltages where the magnitude of the output voltage may
differ than the input voltage magnitude. Normally, DC-
DC converters are classified into three types namely:
buck, boost and buck-boost Converter and here boost
converter is preferred as we need to step up the PV output.
DC-DC converters are also useful for noise separation and
power bus regulation. The DC-DC boost converter
contains an inductor, capacitor, diode and a MOSFET.
Based on the switch duty cycle the output voltage may Fig 3a) Circuit diagram of converter with PI controller
change. Generally transformer can step up the voltage, but
there may be losses in the transformer. So to overcome
this loss and to get desired output voltage DC-DC
converters is used. The converter operates in two modes,
in the first mode begins when transistor M1 is switched
lying on at time t=0. The input current ascent and flows
through inductor L and transistor M1.

The inductor and MOSFET form a closed path when


MOSFET is ON. The current flows through the inductor
(L1) and the energy is stored in inductor when the switch
is ON. Virtually there is no current flowing through the Fig 3 b) Output Voltage and current waveform of
load at the initial stage. And the second mode begins when converter with PI controller
transistor M1 be switched off at time t=t1. The input
current now breeze through L, C, load, and diode Dm.

450
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , O PTIMIZATION AND SIGNAL P ROCESSING

procurement and control frameworks.

Fig 3 c) Output waveform of converter without PI


controller.
Fig. 4. Inverter topology
IV SAPF WITH FUZZY LOGIC
CONTROLLER It can be actualized in equipment, programming, or a
collection of together. FL gives undemanding technique to
A Shunt Active Filter (SAPF) is the bidirectional current touch base at an unequivocal conclusion based upon
converter with six switches having combination of both obscure, uncertain, loose, loud, or missing info data.. FL
switching network and filter-components. Structure of this approach imitates how a man would decide, just
power filter is dependent on the control technique of VSI significantly quicker. The fuzzy controller is based on the
having a capacitor for the purpose of DC energy storage following rules.
and the inverter output has been connected to Non-linear
load consists of diode bridge rectifier with a RL-load. In
each of the switches the diodes are connected in back to
back arrangement with the IGBTs to permit current flow
in either direction. For compensation of reactive power
the PV interconnected shunt APF injects real PV power to
a distribution line at PCC and also reduces harmonic in
load currents caused by nonlinear loads by injecting
compensating current. This filter is connected in shunt
that means in parallel with the nonlinear load. This SAPF
has ability of detecting the harmonic current caused by the
nonlinear loads and then injects a current of equal
magnitude and opposite in phase with the non-linear load
current which is called compensating current to reduce the
harmonics present in load currents due to Non-linear load. Fig. 5. Fuzzy rules
Hence, the resulting current is in form of a fundamental
frequency sinusoidal current which is drawn at PCC in V POWER QUALITY ISSUES
distribution network. VSI is one of the DC source has tiny
or trifling impedance. At the end of the day VSI has In modern years, there has been a better prominence and
hardened DC voltage source at its info terminals. At anxiety for the quality of power delivered to factories,
present CSI is sustained with customizable current from a business organisations and habitations. This is due to the
DC asset of high impedance, (i.e.) from a solid DC current increasing convention of harmonic-creating nonlinear
source. In a CSI bolstered with firm current source, yield loads such as ASD, switched sort power supplies, arc
current waves are not influenced by the load. A 3 phase furnaces, electronic fluorescent lamp ballasts etc. Power
inverter, which is the most normally utilized topology in quality can be defined, as the revision of driving and
motor drives. The control procedure is like the control of establishing electronic frameworks so as to keep up the
the 1 phase inverter, with the exception of that the veracity of the power supplied to the system. IEEE
reference signals for the adjusted legs have a phase shift criterion 1159 defines power quality to the model of
of 120 in lieu of 180 for the 1 phase inverter. powering and grounding perceptive equipment in an
approach that is appropriate for the operation of that
Fuzzy logic deals with ambiguity in engineering by apparatus. In the IEEE 100 Legitimate Dictionary of IEEE
attaching level of certainty to answer a logic question. FL criterion terms, Power quality is defined as the idea of
is a critical unriddle charge framework technique that fits powering and grounding electronic apparatus in a way
execution in framework running from straightforward that is fitting to the function of that apparatus and well-
little, installed smaller scale controllers to huge, arranged, matched with the assertion wiring system and other
multi-channel PC or workstation-based information

451
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , O PTIMIZATION AND SIGNAL P ROCESSING

coupled apparatus. Superior power quality, however, is the grid along with harmonic compensation. The THD of
not easy to define because what is superior power quality an inverter voltage is reduced to 0.37%. The simulation
to a refrigerator motor may not be good sufficient for model of grid connected PV system is shown in Fig 6a.
current delicate computers and other sensitive loads. The final outcome shows reduction of harmonics in the
Harmonic trouble come commonly from apparatus with a inverter while interfacing to the grid. This is achieved by
non-linear voltage/current features. These days a connecting a shunt active power filter.
substantial piece of mechanical, business and local
burdens is non-direct, making the alteration intensity on
the low-voltage supply network a serious concern. As
time goes on, additional and greater gear is being utilized
that makes sounds in power frameworks. On the other
hand, new and more apparatus is being used that is
tending to failure due to harmonics. Computers,
communication apparatus, and other power systems are
vulnerable to misoperation due to the effects of
harmonics. Due to the effect of harmonics, the electric
motors has AC misfortunes in the center and copper Fig 6 b) Output waveform of Inverter voltage without
windings. This can bring about center scalding, winding SAPF.
heating, torque fluctuation, and failure of efficiency in the
motors. Harmonics may resulting, increase in perceptible
sound from engines and transformers and can energize
mechanical resonances in electric engines and their heaps.

VI PROPOSED SYSTEM
The proposed system comprises of a 3 phase AC source of
voltage 415 V and 50 Hz frequency to a nonlinear RLC
load through a source and line combined reactance of
50mH/Phase. The R Load on the DC side of Boost
converter is about 20ohm. The boost converter is Fig 6 c) Output waveform of Inverter voltage with SAPF
energized through the solar PV system of 21V and
produced an output of 230V. The simulation results of the
proposed 3 phase inverter based SAPF compensation. The
Figure 6 c, d, e shows the 3 phase voltage and current
waveforms after compensation.

Fig 6 d) Output waveform of grid voltage with SAPF

Fig 6 a) Circuit diagram of Grid connected with SAPF.

The 3 phase compensating currents of 3 phase inverter


based SAPF compensates the load current harmonics and Fig 6 e) Output waveform of current with SAPF.
thus the source current approached to sinusoidal is
exposed in Figure 6e Thus, the 3 phase inverter based The following figure shows the THD of an inverter. The
SAPF successfully injects the power from solar panel into figure 7 and table 2 describes the THD level of inverter

452
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , O PTIMIZATION AND SIGNAL P ROCESSING

and grid with SAPF. REFERENCES


[1]. Carrasco JM, Franquelo LG, Bialasiewicz JT, Galván E,
Guisado RCP, Prats MÁM, . ―Power electronic systems
for the grid integration of renewable energy sources.
IEEE Trans Ind Electron, vol. 53, no.4, pp. 1002–16,
2006.
[2]. Renders B, De Gusseme K, Ryckaert WR, Stockman K,
Vandevelde L, Bollen MHJ, ―Distributed generation for
mitigating voltage dips in low-voltage distribution
grids‖, IEEE Trans Power Deliv, vol. 23, no.3, pp. 1581–
8, 2003.
[3]. Singh Mukhtiar, Chandra Ambrish, Varma Rajiv K.,
―Grid interconnection of renewable energy sources at the
distribution level with power-quality improvement
features‖, IEEE Trans Power Deliv, vol. 26, no. 1, pp.
Fig 7 a) THD of inverter with SAPF 307–15, 2011.
[4]. S. B. Kjaer, J. K. Pedersen, and F. Blaabjerg, "A review
of single-phase grid-connected inverters for photovoltaic
modules," Industry Applications, IEEE Transactions on,
vol. 41, pp. 1292-1306, 2005.
[5]. Czarnecki LS. ―Power related phenomena in three-phase
unbalanced systems‖, IEEE Trans Power Deliv, vol. 10,
no.3, pp. 1168–76, 1995.
[6]. Pai Fu Sheng, Hung Shyh-Iier, ―Design and operation of
power converter for micro turbine powered distributed
generator with capacity expansion capability‖, IEEE
Trans Energy Convers, vol. 3, no.1, pp. 110–6, 2003.
[7]. Khanh Loc Nguyen, Seo Jae-Jin, Kim Yun-Seong, Won
Dong-Jun, ―Power management strategies for a grid-
connected PV-FC hybrid system‖, IEEE Trans Power
Fig 7b) THD of grid with SAPF Deliv, vol. 25, no. 3, pp. 1874–82, 2011.
[8]. Jang Jyh-shing Roger, Sun Chuen-Tsai, Mizutani Eiji,
TABLE 3 THD COMPARISON ―Neuro-fuzzy and soft computing—a computational
approach to learning and machine intelligence‖. Prentice-
SYSTEM THD without THD with SAPF Hall; 1997.
SAPF (%) (%) [9]. Bhuvaneswari G, Nair MG, ―Design, simulation, and
Grid 33.7 0.32 analog circuit implementation of a three-phase shunt
Inverter 32.4 0.37 active filter using the I cos U algorithm‖, IEEE Trans
Power Deliv, vol. 23, no. 2, pp. 1222–35, 2008.
[10]. Graovac Dusan, Katic Vladimir A, Rufer Alfred, ―Power
VII CONCLUSION quality problems compensation with universal power
quality conditioning system‖, IEEE Trans Power Deliv,
In this paper the issues and difficulties involved due to the vol. 22, no. 2, pp. 968–97, 2008.
Grid integration of Solar PV System was completely [11]. Enslin JHR, Heskes PJM, ―Harmonic interaction
analysed. The harmonics present in this proposed system between a large number of distributed power inverters
was efficiently eliminated using SAPF. Comparison with and the distribution network‖, IEEE Trans Power
other conventional techniques shows that FUZZY Electron, vol. 19, no. 6, pp. 1586–93, 2014.
controlled SAPF limit the total percent of THD. Voltage [12]. Jintakosonwit P, Fujita H, Akagi H, Ogasawara S,
―Implementation and performance of cooperative control
effectively to an attainable level. This prototype affords
of shunt active filters for harmonic damping throughout a
reliability in feeding the load. This prototype also supplies power distribution system‖, IEEE Trans Ind Appl, vol.
the active power indispensable during the unreliable grid 39, no.2, pp. 556–64, 2013.
operation all the way through the solar energy linked at [13]. Milands MI, Cadavai ER, Gonzalez FB, ―Comparison of
the DC side of the SAPF. The obtained results prove that control strategies for shunt active power filters in three
the proposed model animatedly performs the THD of phase four wire system‖, IEEE Trans Power Electron,
source voltages at inverter and Grid is reduced. vol. 22, no. 1, pp. 229–36, 2007.

453

View publication stats