Efficiency 91%
High reliability - field proven design of 350,000 hours/40 years MTBF
Extremely high power density - convection cooled
Real measured power factor over 0.98
Sine wave input current to EN60555, EN61000-3, IEC1000-3
Front panel adjustment of key variables
EMC - Complies with European and USA standards
Temperature compensation of float voltage
Silent in operation
TECHNICAL SPECIFICATION
Input
Environmental
Output Current Limit Current limit characteristic is constant current between 100%
and 110% of rated current down to 70% voltage then a current
fold back to minimal current at short circuit. Automatic recovery
to normal operation on the removal of the overload
Overvoltage An output overvoltage in excess of the overvoltage setting
results in the unit latching into output shutdown. Reset is by
disconnection of the AC input supply. There are two settings for
overvoltage in both the Float and Boost/Equalise modes.
The first operates when unit is supplying current (on load) and
ensures that should a unit’s output voltage exceed the
overvoltage exceed the overvoltage setting in a paralleled
system only the faulty rectifier will shutdown.
The other setting is load independent and is fixed above the on
load setting enabling the unit to shutdown regardless of output
current
Thermal Protection Automatic shutdown on thermal overload with automatic reset
when acceptable temperatures are re-established
Reverse Polarity Blows external distribution fuse (HRC to BS88) or external type
2 circuit breaker. Optional facility on 24V units.
Standards
Due to our policy of continuous product development and modernisation, Specifications may differ slightly
from those given.