Guia de Produto REX521
Guia de Produto REX521
Guia de Produto REX521
Product Guide
Feeder Protection Relay REX 521
1MRS752177-MBG
Issued: 20.11.2001
Status: Updated
Version: F/15.02.2006
Data subject to change without notice
General The protection relay REX 521 is designed for protection relay is provided with energizing
protection, control, measuring, and supervi- inputs for conventional current and voltage
sion in medium voltage networks. Typical transformers. Also a hardware version with
applications include incoming and outgoing inputs for current and voltage sensors is
feeders as well as substation protection. The available.
Design The protection relay is based on a multipro- and informs the user via indication messages.
cessor environment. The human-machine Modern technology is applied both in hard-
interface (HMI)1 including an LCD display ware and software solutions.
with different views makes the local use easy
The protection relay is part of the ABB Sub-
1. HMI is referred to as MMI in the relay and in the station Automation system and extends the
Relay Setting Tool.
functionality and flexibility of the concept
further.
3
Feeder Protection Relay REX 521
1MRS752177-MBG
CBFP 3 49F
62 3I I0
0 I 79 I0
LO 86 3I
CBFP 62
REX 521 B01
LO 86
Fig. 1 Block diagram of B01
REX 521 B02
4
Feeder Protection Relay REX 521
1MRS752177-MBG
U0 CBFP 62
5
Feeder Protection Relay REX 521
1MRS752177-MBG
Features (cont´d) • Three-phase power and energy measure- • Synchro-check/voltage-check function with
ment one stage
• Calculation of the accumulated electric • Supervision function for energizing current
breaker wear of the circuit breaker (CB) input circuit
• Transient disturbance recorder • Supervision function for energizing voltage
input circuit
• Trip-circuit supervision
• Current waveform distortion measurement
• Delayed trip output for the circuit-breaker
failure protection (CBFP) function • Voltage waveform distortion measurement
• Automatic reclosing 1...5 shots • Three-phase current measurement
• Circuit breaker control with indication • Neutral current measurement
• Lockout function • Three phase voltage measurements
• Object indication • Residual voltage measurement
• Logic control position selector • System frequency measurement
• User-configurable I/Os • Three-phase power and energy measure-
ment
• Interlocking
• Calculation of the accumulated electric
• User-configurable alarm LEDs
breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
3I> 67 MCS1 000
• Trip-circuit supervision
TCS
3I > 50/51 • Delayed trip output for the circuit-breaker
CBCM 0 I failure protection (CBFP) function
I0 > 67N
3I~harm R • Automatic reclosing 1...5 shots
f</f> 81U/81O
3U~harm • Circuit breaker control with indication
3I2f> 68
• Lockout function
I> 46
• Object indication
3 49F I0
3I P • Logic control position selectorUser-config-
urable I/Os
0 I 79
3U U0 Q • Interlocking
CBFP */62
• User-configurable alarm LEDs
LO 86
f pf E
REX 521 H02
3I > 50/51 MCS 000
7
Feeder Protection Relay REX 521
1MRS752177-MBG
8
Feeder Protection Relay REX 521
1MRS752177-MBG
Features (cont´d) • Calculation of the accumulated electric • Supervision function for energizing current
breaker wear of the circuit breaker (CB) input circuit
• Transient disturbance recorder • Supervision function for energizing voltage
input circuit
• Trip-circuit supervision
• Current waveform distortion measurement
• Delayed trip output for the circuit-breaker
failure protection (CBFP) function • Voltage waveform distortion measurement
• Circuit breaker control with indication • Three-phase current measurement
• Lockout function • Neutral current measurement
• Object indication • Three phase voltage measurements
• Logic control position selector • Residual voltage measurement
• User-configurable I/Os • System frequency measurement
• Interlocking • Three-phase power and energy measure-
ment
• User-configurable alarm LEDs
• Calculation of the accumulated electric
breaker wear of the circuit breaker (CB)
3I > 50/51 MCS 000
• Transient disturbance recorder
TCS
I 0> 50N/51N • Trip-circuit supervision
CBCM 0 I
3I2f 68 • Delayed trip output for the circuit-breaker
3I~harm R failure protection (CBFP) function
U 0> 59N
3U~harm • Circuit breaker control with indication
3U> 59
• Lockout function
3I I0 P
3U< 27 • Object indication
CBFP */62 • Logic control position selector
3U U0 Q
LO 86 • User-configurable I/Os
• Interlocking
3 49 f pf E
• User-configurable alarm LEDs
TCS
U 0> 59N
Standard configuration H06:
CBCM 0 I
• Three-phase non-directional overcurrent 3U> 59
protection with two stages 3I~harm R
3U< 27
• Three-phase overvoltage protection with 3U~harm
two stages f</f> 81U/81O
• Three-phase undervoltage protection with 3I I0 P
CBFP 62
two stages
• Residual overvoltage protection with three LO 86 U0
3U Q
stages
• Underfrequency or overfrequency protec- f pf E
tion with two stages REX 521 H06
9
Feeder Protection Relay REX 521
1MRS752177-MBG
11
Feeder Protection Relay REX 521
1MRS752177-MBG
I 0> 50N/51N
TCS • Three phase voltage measurements
CBCM 0 I • Residual voltage measurement
3I2f 68
3I~harm R • System frequency measurement
U 0> 59N
3U~harm • Three-phase power and energy measure-
3U> 59 ment
3I I0 P • Calculation of the accumulated electric
3U< 27
breaker wear of the circuit breaker (CB)
CBFP */62
3U U0 3U_B • Transient disturbance recorder
LO 86 • Trip-circuit supervision
f</f> 81U/81O Q f pf • Delayed trip output for the circuit-breaker
failure protection (CBFP) function
0 I 79
E • Automatic reclosing 1...5 shots
• Circuit breaker control with indication
Fig. 13 Block diagram of H09
• Lockout function
• Object indication
Note! The standard configuration H09 is
available only with the voltage transformer • Logic control position selector
(VT) HW version. VTs are used to measure
phase-to-earth voltages. • User-configurable I/Os
• Interlocking
Standard configuration H50:
• Three-phase non-directional overcurrent • User-configurable alarm LEDs
protection with three stages.
• Three-phase directional overcurrent pro-
3I> 50/51 MCS 000
tection with two stages
I0> 50N/51N TCS
• Directional earth-fault protection with two
stages 3I2f 68
CBCM 0 I
stages 3I> 67 f pf E
• Three-phase transformer inrush and motor U1<
start-up current detector U2> 27,47,59
U1>
12
Feeder Protection Relay REX 521
1MRS752177-MBG
13
Feeder Protection Relay REX 521
1MRS752177-MBG
Applications Several standard configurations are available The H03 standard configuration is designed
for the protection relay. Refer to the REX 521 to be used in single busbar systems using one
“Technical Reference Manual, Standard Con- circuit-breaker for selective non-directional
figurations” for more detailed information. short-circuit protection, non-directional time-
overcurrent protection, directional earth-fault
The B01 standard configuration for REX 521 protection and automatic reclosing with syn-
is designed to be used in single busbar sys- cro- and voltage-check functionality.
tems using one circuit breaker for selective
short-circuit, time overcurrent and earth-fault The H04 standard configuration is designed
protection of radial isolated neutral networks, to be used in single busbar systems using one
solidly earthed networks, resistant earthed circuit-breaker for selective non-directional
networks and resonant earthed networks. short-circuit protection, non-directional time-
overcurrent protection, directional and non-
The B02 standard configuration is designed directional earth-fault protection and auto-
to be used in single busbar systems using one matic reclosing.
circuit-breaker for selective short-circuit pro-
tection, time-overcurrent protection, earth- The H05 standard configuration is designed
fault protection and automatic reclosing. The to be used in single busbar systems using one
configuration can be used in different types of circuit-breaker for selective non-directional
networks such as radial isolated neutral net- short-circuit protection, non-directional time-
works, solidly earthed networks, resistant overcurrent protection, non-directional earth-
earthed networks and resonant earthed net- fault protection, overvoltage protection, und-
works. ervoltage protection, residual overvoltage
protection and thermal overload protection
The M01 standard configuration is designed for devices.
to be used in single busbar systems using one
circuit-breaker for selective short-circuit, The H06 standard configuration is designed
time overcurrent and directional earth-fault to be used in single busbar systems using one
protection of radial isolated neutral networks, circuit-breaker for selective non-directional
solidly earthed networks, resistant earthed short-circuit protection, non-directional time-
networks and resonant earthed networks. overcurrent protection, overvoltage protec-
tion, undervoltage protection, residual over-
The M02 standard configuration is designed voltage protection, underfrequency protection
to be used in single busbar systems using one and overfrequency protection.
circuit-breaker for selective short-circuit pro-
tection, time-overcurrent protection, direc- The H07 standard configuration is designed
tional earth-fault protection and automatic for protection of large or medium-size three-
reclosing. The configuration can be used in phase AC motors in circuit-breaker controlled
different types of networks such as of radial motor drives. Due to the large number of pro-
isolated neutral networks, solidly earthed net- tective functions integrated, the relay pro-
works, resistant earthed networks and reso- vides a complete protection against motor
nant earthed networks. damage caused by electrical faults. The H07
configuration can also be applied to other
The H01 standard configuration is designed objects needing thermal overload protection,
to be used in single busbar systems using one such as power transformers. It can also be
circuit-breaker for selective directional and used in applications requiring overcurrent
non-directional short-circuit protection, protection, under or overvoltage protection
directional time-overcurrent protection, and/or directional or non-directional earth-
directional earth-fault protection and auto- fault protection.
matic reclosing with syncro- and voltage-
check functionality. The H08 standard configuration is designed
to be used in single busbar systems using one
The H02 standard configuration is designed circuit-breaker for selective non-directional
to be used in single busbar systems using one short-circuit protection, non-directional time-
circuit-breaker for selective directional and overcurrent protection, non-directional earth-
non-directional short-circuit protection, fault protection, overvoltage protection, und-
directional and non-directional time-overcur- ervoltage protection, residual overvoltage
rent protection, directional earth-fault protec- protection and thermal overload protection
tion and automatic reclosing. for devices. The protection is based on phase-
14
Feeder Protection Relay REX 521
1MRS752177-MBG
Applications (cont´d) to-earth voltages. In addition, phase-to-phase protection, undervoltage protection, residual
voltages are available in the measurement overvoltage protection, underfrequency pro-
view. tection, over-frequency protection and auto-
matic reclosing.
The H09 standard configuration for REX 521
is designed to be used in single busbar sys- The H51 standard configuration for REX 521
tems using one circuit breaker for selective is designed for protection of large or medium-
non-directional short-circuit protection, non- size three-phase AC motors in circuit breaker
directional time-overcurrent protection, non- controlled motor drives. Due to the large
directional earth-fault protection, overvolt- number of protective functions integrated, the
age protection, undervoltage protection, relay provides a complete protection against
residual overvoltage protection, underfre- motor damage caused by electrical faults.
quency protection, overfrequency protection
and automatic reclosing. The H51 configuration can be applied to
other objects that need the thermal overload
The H50 standard configuration for REX 521 protection (such as power transformers). It
is designed to be used in single busbar sys- can also be used in applications requiring
tems by using one circuit breaker for selective overcurrent protection, directional overcur-
non-directional short-circuit protection, rent protection, under/overvoltage protec-
directional and non-directional time-overcur- tion, directional or non-directional earth-fault
rent protection, directional and/or non-direc- protection, underfrequency protection and/or
tional earth-fault protection, overvoltage overfrequency protection.
15
Feeder Protection Relay REX 521
1MRS752177-MBG
REX521xMxxx
REX521xBxxx
REX521xHxxx
REX521xSxxx
Transformer modules (MIM) 1 1 1 1
Transformers
• Current transformers 1/5 A 4 4 4 1
• Current transformers 0.2/1 A 1 1 1
• Voltage transformers 100 V 1 4 1
Sensor channels
• Current sensor inputs 3
• Voltage sensor inputs 3
Main CPU modules 1 1 1 1
6 x 16 character display
Digital inputs 9
IRF outputs 1
16
Feeder Protection Relay REX 521
1MRS752177-MBG
Design, software Functionality is available as part of the stan- Functions available for use in the different
dard configurations B01, B02, M01, M02, standard configurations are listed below.
H01, H02, H03, H04, H05, H06, H07, H08,
H09, H50 and H51.
Standard configurations B01 B02 M01 M02 H011 H02 H03 H04 H05 H06 H07 H0823 H0923 H502 H512
ANSI
IEC FB name
device
symbol (CD-ROM)
number
Protection
3I> 51-1 NOC3Low x x x x x x x x x x x x x x
3I>> 51-2 NOC3High x x x x x x x x x x x x x x
3I>>> 51-3 NOC3Inst x x x x x x x x x x x x x
Io> 51N-1 NEF1Low x x x4 x x x x x x
Io>> 51N-2 NEF1High x x x4 x x x x x x
Io>>> 51N-3 NEF1Inst x x x4 x x x
Io>-->5 67N-1 DEF2Low x x x x x x x x x
Io>>-->5 67N-2 DEF2High x x x x x x x x x
Io>>>-->5 67N-3 DEF2Inst x x x x x x
3I>--> 67-1 DOC6Low x x6 x x
3I>>--> 67-2 DOC6High x x6 x x
3U> 59-1 OV3Low x x x x x x x
3U>> 59-2 OV3High x x x x x x
3U< 27-1 UV3Low x x x x x x x
3U<< 27-2 UV3High x x x x x x
3I2f> 68 Inrush3 x x x x x x x x x x x x
Iub> 46 CUB3Low x x x x x x x x
3Ith> 49F TOL3Cab x x x x x x x x
O-->I 79 AR5Func x x x x x x x x
Uo> 59N-1 ROV1Low x x x x x x
Uo>> 59N-2 ROV1High x x x x x
Uo>>> 59N-3 ROV1Inst x x x x
f1 81-1 Freq1St1 x x x x x x x
f2 81-2 Freq1St2 x x x x
SYNC1 25-1 SCVCSt1 x x
Is2t n< 48 MotStart x x
3I() 46R PREV3 x x
I2> 46-1 NPS3Low x x
I2>> 46-2 NPS3High x
3I< 37-1 NUC3St1 x
FUSEF 60 FuseFail x x
3Ithdev> 49M/G/T Tol3Dev x x x x
U1U2<>_1 47-1 PSV3St1 x x x
Control functions
I<->O CB1 COCB1 COCB1 x x x x x x x x x x x x x x x
I<->O IND1 COIND1 COIND1 x x x x x x x x x x x x x x x
I<->O IND2 COIND2 COIND2 x x x x x x x x x x x x x x x
17
Feeder Protection Relay REX 521
1MRS752177-MBG
Standard configurations B01 B02 M01 M02 H011 H02 H03 H04 H05 H06 H07 H0823 H0923 H502 H512
ANSI
IEC FB name
device
symbol (CD-ROM)
number
I<->O IND3 COIND3 COIND3 x7 x7
I<->O POS COLOCAT COLOCAT x x x x x x x x x x x x x x x
ALARM1-8 ALARM1-8 MMIALAR1-8 x x x x x x x x x x x x x x x
Measurement
3I 3I MECU3A x x x x x x x x x x x x x x x
Io Io MECU1A x x x x x x x x x x x x x x x
Uo Uo MEVO1A x x x x x x x x x x x x x
DREC DREC MEDREC x x x x x x x x x x x x x x x
3U 3U MEVO3A x x x x x x x x x x x
3U_B 3U_B MEVO3B x x
f f MEFR1 x x x x x x x x x x x
PQE PQE MEPE7 x x x x x x x x x x x
AI1 AI1 MEAI1 x x
Condition monitoring
CB wear1 CB wear1 CMBWEAR1 x x x x x x x x x x x x x x x
TCS1 TCS1 CMTCS1 x x x x x x x x x x x x x x x
MCS 3I MCS 3I CMCU3 x x x x x x x x x x x x x x x
MCS 3U MCS 3U CMVO3 x x x x x x x x x x x
TIME1 TIME1 CMTIME1 x x
Power quality monitoring
PQ 3Inf PQ 3Inf PQCU3H x x x x x x x x x x x x x x x
PQ 3Unf PQ 3Unf PQVO3H x x x x x x x x x x x
Standard
SWGRP SWGRP SWGRP x x x x x x x x x x x x x x x
1
H01 available only as sensor version
2
Available only as VT version
3
VTs are used to measure phase-to-earth voltages, calculated phase-to-phase voltages are shown by 3U_B
4Configured fixedly to the Io (1/5 A) channel or Ios if selected
5
Can be used as Io>, Io>> and Io>>> or Uo>, Uo>> and Uo>>> function block with some limitations
6
3I>-> and 3I>>-> cannot be set to operate as 3I>, 3I>> or 3I>>>
7
Motor status indication
Note: Calculated Uo (Uos) is used in the Sen- For more information, see REX 521 Techni-
sor versions of H01 and H03 configurations. cal Reference Manual, Standard Configura-
Calculated Io (Ios) is available in H01-H05, tions.
H08, H09 and H50 configurations.
18
Feeder Protection Relay REX 521
1MRS752177-MBG
Technical data
Table 3: Energizing inputs
Rated frequency 50.0/60.0 Hz
Current inputs rated current 0,2 A/1 A/5 A
Thermal withstand continuously 1.5 A/4 A/20 A
capability for 1 s 20 A/100 A/500 A
dynamic current withstand, half-wave value 50 A/250 A/1250 A
input impedance <750 mΩ/<100mΩ/
<20 mΩ
Voltage inputs rated voltage 100 V/110 V/115
V/120 V (parametri-
zation)
voltage withstand, continuous 2 x Un (240 V)
burden at rated voltage <0.5 VA
Sensor inputs voltage range RMS 9.4 V RMS
voltage range peak ± 12 V
input impedance >4.7 MΩ
input capacitance <1 nF
19
Feeder Protection Relay REX 521
1MRS752177-MBG
20
Feeder Protection Relay REX 521
1MRS752177-MBG
21
Feeder Protection Relay REX 521
1MRS752177-MBG
22
Feeder Protection Relay REX 521
1MRS752177-MBG
23
Feeder Protection Relay REX 521
1MRS752177-MBG
24
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
*) - I
X4.1
+
ACFail Mains 1
X1.1
2
TempAlarm -
L1 L3
P1 S1 5
IRF 4
S2 3
P2 8
7
S1
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
2 **)
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
DATA B
10
*) Power flow direction
**) The jumper is not assembled by default when
the protection relay is delivered
A051916
25
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
*) - I
da dn X4.1
+
ACFail Mains 1
X1.1
Source 2
TempAlarm -
L1 L3
P1 S1 5
IRF 4
S2 3
18
P2 100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
2
**)
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
DATA B
10
A051917
26
Feeder Protection Relay REX 521
1MRS752177-MBG
Terminal diagram of the REX 521: High, excluding H08 and H09
L1 L3
A
0 -
+
Q0
N
n
*) - I
a
da dn X4.1
+
ACFail Mains 1
X1.1
27 VT4 U31**) 2
100V TempAlarm -
25
L1 L3 24 VT3
P1 S1 100V U23 5
22 IRF 4
21 VT2
100V U12
S2 19 3
P2 18
100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
***)
2
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
10 DATA B
A051918
27
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
n
*) - I
a
da dn X4.1
+
ACFail Mains 1
X1.1
27 VT4 U3 2
100V TempAlarm -
25
L1 L3 24 VT3
P1 S1 100V U2 5
22 IRF 4
21 VT2
100V U1
S2 19 3
P2 18
100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
2
**)
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
10 DATA B
A051919
28
Feeder Protection Relay REX 521
1MRS752177-MBG
X4.1
+
ACFail Mains 1
X1.1
27 2
TempAlarm -
25
24
5
22 IRF 4
21
19 3
18 VT1
100V U0 *) 8
16 7
15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
11 5A
I0 10
10 11
9
8
7 SO2 9
6 12
5 13
4
3
2
1 PO1
14
Sensor VD3 15
Voltage input, U3 X2.1
DIFF
Sensor RS3
Current input, IL3 X2.4 PO3
DIFF
Sensor RS2
Current input, IL2 X2.5
DIFF
HSPO1
X4.2 TCS1 1
5 DI1
6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
DATA B
10
29
Feeder Protection Relay REX 521
1MRS752177-MBG
Ordering infor- When ordering REX 521 protection relays, Each protection relay has a specific order
mation specify the following: number that identifies the protection relay
type as well as the hardware and the software
• order number as described in the figure below. The order
number is labelled on the marking strip on the
• quantity
front panel of the relay delivered, for example,
• additional language Order No: REX521GMHPSM01G..
• optional Chinese front panel (Order No:
1MRS121025)
REX521GMHPSM01G XX
Configuration revision
Configuration name: B01, B02, M01, M02, H01, H02, H03, H04, H05,
H06, H07, H08, H09, H50, H51
Rear communication: S=SPA/IEC/Modbus/DNP 3.0
L=SPA/IEC/Modbus/DNP 3.0/LON
Optical connectors for rear communication: P = plastic-fibre
G = glass-fibre
Power supply: H = PS_87H, L = PS_87L
Type of hardware: B = Basic, M = Medium, H = High, S = High sensor
Revision
A051925
Accessories
Semi-flush mounting kit 1MRS050254
Wall mounting kit 1MRS050240
Rack mounting kits:
Enclosure size (x 19”): Mounting kit order number:
1/2 + 1/3 1MRS050241 and 1MRS050238
1/3 1MRS050258
1/3 + 1/3 1MRS050241 and 1MRS050377
1/3 + 1/3 + 1/4 1MRS050241 (2 pcs) and 1MRS050381
1/4 + 1/4 + 1/3 1MRS050241 (2 pcs) and 1MRS050382
1/3 + 1/4 1MRS050609 and 1MRS050241
Connection cable for front
panel connector 1MKC950001-2
30
Feeder Protection Relay REX 521
1MRS752177-MBG
Ordering information Configuration, setting and SA system • CAP 505 Relay Configuration Tool;
(cont´d) tools CAP 505 v. v.2.4.0 or later
The following tool versions are needed to • LIB 500 Library for MicroSCADA Pro;
support the new functions and features of LIB 500 v.4.2-1 or later
Release Q1/2006 revisions of REX 521:
• LIB 510 Library for MicroSCADA Pro;
• CAP 501 Relay Configuration Tool; LIB 510 v.4.2-1 or later
CAP 501 v.2.4.0 or later
• SMS 510 v.1.3.0 or later
31
Feeder Protection Relay REX 521
1MRS752177-MBG
32
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, FINLAND
Tel +358 10 22 11
Fax +358 10 224 1094
www.abb.com/substationautomation