1001.C12 GEN93 SLD Rev00 2018-06-12 DRAFT
1001.C12 GEN93 SLD Rev00 2018-06-12 DRAFT
1001.C12 GEN93 SLD Rev00 2018-06-12 DRAFT
TABLE OF CONTENT:
M M
M M
-Q1 -Q3
145kV – SF6 145kV – SF6
2000A – 31,5kA 2000A – 31,5kA
M M
M
M M
M
M M
M
M
-Q2 -Q4
132 / 11 kV 132/ 11 kV
35 MVA (40MVA) - YNd5 15 MVA (20MVA) - YNd5
+/- 8x 1,25% OLTC +/- 8x 1,25% OLTC
ONAN (ONAF) ONAN (ONAF)
uk = 8% uk = 8%
page 2 page 2
Remark:
Substation / Power supply to the Steelplant is up to the power
supplying company. The Steelplant requires 2 incoming lines
(Medium Voltage) for operation.
Customer-ID 1001
TITLE KEYWORD:
DEFINITION POWER SUPPLY =
DATE NAME
General Single Line Layout INCOMING LINE 132KV
CHECKED xx.xx.2018 ---
DATE NAME
DRAWING-NO.:
4310 Rheinfelden, REVISION VERSION SHEET OF
TAYBAH Steel Pakistan (PVT.), LTD. / Pakistan 1001.C12_GEN93_SLD_Rev00
DRAWN 11.06.2018 G. Arbogast Rev.00 Suisse 0 - 002 5
0 1 2 3 4 5 6 7 8 9
page 1 page 1
Note: Incoming Cable to be specified by the Power supplying Company (Diameter, No of cable,…)
- A01
MV Main Distribution – DIRTY BUS - A06
MV Auxiliary Distribution - CLEAN BUS
M
1250A
M
2500A
630A 630A 630A 630A 630A xxxA xxxA xxxA xxxA xxxA xxxA xxxA xxxA xxxA
M M M M M M M M
xxxA
M M M M M M M
Meltshop Meltshop Meltshop FTP BaP #1 BaP #2 WTP WTP+CAP RM+RHF Spare
Tech. Units Auxiliaries Caster Services Services
Switchgear Room
CA
M 1250A
Transformer Room
7314(2x 3657)kVA 7314(2x 3657)kVA
M
xxkV ± 2.5x7.5% xxkV ± 2.5x7.5%
1150V 1150V
Description Abbrev. Feeder Recommended Remark
Vcc12 / 13%
Dd0y11
Vcc12 / 13%
Dd0y11
FEEDER No. Dist. Transformer
[kVA]
5 MVA Meltshop Technological MSP TU 07 1600 IF1‐LV + IF2‐LV, LMF‐LV, MHS‐LV, FTP‐LV,
7314(2x 3657)kVA 7314(2x 3657)kVA
12MW xxkV ± 2.5x7.5% xxkV ± 2.5x7.5%
Power Supply 1150V 1150V
Units Loads to be verified by Supplier
Vcc12 / 13% Vcc12 / 13%
Dd0y11 Dd0y11
IF No.1 Meltshop Auxiliaries MSP Aux 08 1600 MSP Crane and Auxiliaries MSP TU; Scrap Yard Crane (Loads to be verified
by Supplier); Sockets. Lighting MSP, HVAC, …
12MW Meltshop Caster CKB 00 1600 CKB, CK Crane, CK Auxiliaries, CK Services, Loads to be verified by Supplier
Power Supply
page 2
M
- Axx - Axx 2500A
Recommended
Description FEEDER Feeder Absorbed [kW] Remark
Dist. Transformer [kVA]
Cooling Bed, Bundling area, Auxiliary, Crane, Lighting, HVAC to be verified and
Rolling Mill Auxiliaries & Switchboard 03 1600
detailed by Supplier
Rolling Mill Main Drive Reversing Mill 04 3200 / 2x 1600 @0,72kV Technological Load to be verified and detailed by Supplier
Rolling Mill other Main Drives 05 3200 / 2x 1600 @0,72kV Technological Load to be verified and detailed by Supplier
Spare 06 Spare breaker
Power Factor Correction 07 For Rolling Mill Main Drives
Customer-ID 1001
TITLE KEYWORD:
SINGLE LINE DIAGRAM
DATE NAME
General Single Line Layout 11kV Distribution Rolling Mill
CHECKED
DATE NAME
DRAWING-NO.:
4310 Rheinfelden, REVISION VERSION SHEET OF
TAYBAH Steel Pakistan (PVT.), LTD. / Pakistan 1001.C12_GEN93_SLD_Rev00
DRAWN 11.06.2018 G. Arbogast Rev.00 Suisse 0 - 004 5
0 1 2 3 4 5 6 7 8 9