Safety Relays - PSR-SCP-24DC/FSP/2X1/1X2 - 2986960: Your Advantages
Safety Relays - PSR-SCP-24DC/FSP/2X1/1X2 - 2986960: Your Advantages
Safety Relays - PSR-SCP-24DC/FSP/2X1/1X2 - 2986960: Your Advantages
com/us/products/2986960
Safe coupling relay for SIL 3 high and low demand applications, connects digital output signals to the I/O, 2
enabling current paths, 1 signal contact, module for safe state off applications, integrated test pulse filter, plug-in
screw connection, width: 17.5 mm
Your advantages
Narrow 17.5 mm housing
Up to SIL 3 according to IEC 61508
Forcibly guided contacts according to EN 50205
Easy proof test according to IEC 61508 thanks to integrated signal contact
Long service life thanks to filtering of controller test pulses
Two enabling current paths
Couples digital output signals from failsafe controllers to I/O devices (valves, etc.) for electrical isolation and power adaptation
GTIN
GTIN 4046356520911
Weight per Piece (excluding packing) 180.000 g
Custom tariff number 85364900
Country of origin Germany
Technical data
Note
Utilization restriction 1
03/27/2019 Page 1 / 7
https://www.phoenixcontact.com/us/products/2986960
Ambient conditions
Ambient temperature (operation) -20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude ≤ 2000 m (Above sea level)
Input data
Rated control circuit supply voltage US 24 V DC -15 % / +10 %
Rated control supply current IS typ. 55 mA
Power consumption at US typ. 1.32 W
Inrush current max. 100 mA
Typ. starting time with Us 50 ms
Typical release time 50 ms
Recovery time 1s
Operating voltage display 1 x yellow LED
Protective circuit Surge protection Suppressor diode, 33 V (A1 - A2)
Maximum switching frequency 0.5 Hz
Filter time max. 5 ms (at A1 in the event of voltage dips at Us)
max. 2 ms (Test pulse width; high test pulse at A1/A2)
≥ 100 ms (Test pulse width; high test pulse at A1/A2)
Test pulse rate = 80 x Test pulse width
max. 5 ms (Test pulse width; low test pulse at A1/A2)
≥ 50 ms (Test pulse rate; low test pulse at A1/A2)
Test pulse rate = 15 x Test pulse width
Output data
Contact type 2 enabling current paths
1 confirmation current path
Contact material AgCuNi, + 0.2 µm Au
Maximum switching voltage 250 V AC/DC (N/O contact / N/C contact, observe the load curve)
Minimum switching voltage 15 V AC/DC (N/O contact / N/C contact)
Limiting continuous current 5 A (N/O contact, pay attention to the derating)
100 mA (N/C contact)
Maximum inrush current 5 A (N/O contact)
03/27/2019 Page 2 / 7
https://www.phoenixcontact.com/us/products/2986960
General
Electromechanical relay with forcibly guided contacts in accordance with
Relay type
EN 50205
Nominal operating mode 100% operating factor
Net weight 186.5 g
Mounting position any
Mounting type DIN rail mounting
Degree of protection IP20
IP54
Min. degree of protection of inst. location IP54
Housing material PBT
Housing color yellow
Connection data
Connection method Screw connection
pluggable Yes
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
03/27/2019 Page 3 / 7
https://www.phoenixcontact.com/us/products/2986960
03/27/2019 Page 4 / 7
https://www.phoenixcontact.com/us/products/2986960
0
SF
1
BATF
2
DC5V
FRCE
RUN
3
4
K1
5
RUN-P
6
STOP 7
RUN 31 32
STOP A1 A2
MRES
0
K2
1
2
3
4
5
Power
PSR-FSP/2X1
6
7
23 24
13 14 A2 14 24 32
Circuit diagram
24V DC
SIS / FS-PLC
24V 0V DO DO DI
0V GND
L
K1
K2
A1 13 23 31 K1
PSR-...-24DC/FSP/2X1/1X2 K2
A2 14 24 32
M
K1 24V DC
K2
Circuit diagram
24V DC
SIS / FS-PLC
24V 0V DO DO DI K1
0V GND
K2
L L
K1 K3 M
K2 K4
A1 13 23 31 A1 13 23 31
K3
PSR-...-24DC/FSP/2X1/1X2 PSR-...-24DC/FSP/2X1/1X2
A2 14 24 32 A2 14 24 32 K4
K1 24V DC K3
M
K2 K4
N N
03/27/2019 Page 5 / 7
https://www.phoenixcontact.com/us/products/2986960
ETIM
UNSPSC
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / EAC / UL Listed / cUL Listed / EAC / Functional Safety / GL / EAC
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
03/27/2019 Page 6 / 7
https://www.phoenixcontact.com/us/products/2986960
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
Functional Safety
968/EZ 365.05/16
EAC
EAC-Zulassung
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
RU C-
EAC
DE.A*30.B.01082
Functional Safety
968/EZ 365.05/16
GL
http://exchange.dnv.com/tari/ 13979-15HH
EAC
EAC-Zulassung
03/27/2019 Page 7 / 7