VRV-3W Service Manual
VRV-3W Service Manual
VRV-3W Service Manual
Service
Manual
Water Cooled
Heat Pump / Heat Recovery
R-410A 50 / 60Hz
RWEYQ8-30PY1, RWEYQ10-30PYL, RWEYQ10-30PTL
Si30-813_A
Water Cooled
Heat Pump/Heat Recovery
R-410A 50Hz/60Hz
ED Reference
For items below, please refer to Engineering Data.
No. Item ED No. Page Remarks
P. 14-15, 30-31, 48-49,
1 Indoor Unit Specification ED30-942 66, 80-81, 102-104, 130,
142, 156-157, 170-173,
190-191, 208, 220, 230
Outside Unit
2 Specification ED30-942 P. 244-247
1. Introduction .............................................................................................v
1.1 Safety Cautions ........................................................................................v
1.2 Used Icons .............................................................................................. ix
1.3 Preface .....................................................................................................x
i Table of Contents
Si30-813_A
Table of Contents ii
Si30-813_A
Table of Contents iv
Introduction Si30-813_A
1. Introduction
1.1 Safety Cautions
Cautions and Be sure to read the following safety cautions before conducting repair work.
Warnings The caution items are classified into “ Warning” and “ Caution”. The “ Warning”
items are especially important since they can lead to death or serious injury if they are not
followed closely. The “ Caution” items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates the item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates the prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates the action that must be taken, or the instruction.
The instruction is shown in the illustration or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
If the refrigerant gas leaks during the repair work, ventilate the area. The
refrigerant gas may generate toxic gases when it contacts flames.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment may
cause an electrical shock or fire.
v
Si30-813_A Introduction
Warning
Be sure to wear a safety helmet, gloves, and a safety belt when working at a
high place (more than 2 m). Insufficient safety measures may cause a fall
accident.
In case of R-410A refrigerant models, be sure to use pipes, flare nuts and tools
for the exclusive use of the R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious accident
such as a damage of refrigerant cycle as well as an equipment failure.
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Be sure to turn OFF the power switch and unplug the power cable when
cleaning the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down enough
before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
vi
Introduction Si30-813_A
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it may cause an electrical shock,
excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow the local
technical standards related to the electrical equipment, the internal wiring
regulations, and the instruction manual for installation when conducting
electrical work.
Insufficient power circuit capacity and improper electrical work may cause an
electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the terminal
cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause
an electrical shock, excessive heat generation or fire.
Do not mix air or gas other than the specified refrigerant (R-410A / R-22) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair it
before charging the refrigerant. After charging refrigerant, make sure that there
is no refrigerant leak.
If the leaking point cannot be located and the repair work must be stopped, be
sure to perform pump down and close the service valve, to prevent the
refrigerant gas from leaking into the room. The refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such as fan
and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation site has
sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment may fall and cause injury.
vii
Si30-813_A Introduction
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert
the plug into a power outlet securely.
If the plug has dust or loose connection, it may cause an electrical shock or fire.
Be sure to install the product correctly by using the provided standard For unitary type
installation frame. only
Incorrect use of the installation frame and improper installation may cause the
equipment to fall, resulting in injury.
Be sure to install the product securely in the installation frame mounted on the For unitary type
window frame. only
If the unit is not securely mounted, it may fall and cause injury.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections may cause excessive heat generation,
fire or an electrical shock.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding may cause an electrical shock.
viii
Introduction Si30-813_A
Caution
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 MΩ or higher.
Defective insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Defective drainage may cause the water to enter the room and wet the furniture
and floor.
Be sure to install the packing and seal on the installation frame properly. For unitary type
If the packing and seal are not installed properly, water may enter the room and only
wet the furniture and floor.
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get
Caution an unexpected result or has to restart (part of) a procedure.
Warning
ix
Si30-813_A Introduction
1.3 Preface
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's water cooled VRV System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of water cooled VRV System.
August, 2011
After Sales Service Division
x
Si30-813_A
Part 1
General Information
1. Model Names of Indoor/Outside Units ....................................................2
1.1 Indoor units...............................................................................................2
1.2 Outside units ............................................................................................3
2. External appearance ...............................................................................4
2.1 Indoor units...............................................................................................4
2.2 Outside Units............................................................................................5
3. Combination of Outside Units .................................................................6
4. Capacity Range.......................................................................................7
1 General Information
Si30-813_A Model Names of Indoor/Outside Units
BS units
Series Model name Power supply
100P 160P 250P V1
Heat recovery BSVQ
36P 60P — VJU
Note: No compatibility between BSVQ-M.
Centralized BS units
Series Model name Power supply
Heat recovery BSV 4Q100P 6Q100P V1
General Information 2
Model Names of Indoor/Outside Units Si30-813_A
VE: 1 phase, 220-240/220V, 50/60Hz VJU: 1 phase, 208-230V, 60Hz YL: 3 phase, 380V, 60Hz
V1 : 1 phase, 220-240V, 50Hz Y1 : 3 phase, 380-415V, 50Hz TL : 3 phase, 220V, 60Hz
3 General Information
Si30-813_A External appearance
2. External appearance
2.1 Indoor units
Ceiling mounted cassette (Round flow) type Wall mounted type
FXFQ25PVE FXAQ20MAVE
FXFQ32PVE FXAQ25MAVE
FXFQ40PVE FXAQ32MAVE
FXFQ50PVE FXAQ40MAVE
FXFQ63PVE FXAQ50MAVE
FXFQ80PVE FXAQ63MAVE
FXFQ100PVE
FXFQ125PVE
Ceiling mounted cassette (Compact multi flow) type Floor standing type
FXZQ20MVE FXLQ20MAVE
FXZQ25MVE FXLQ25MAVE
FXZQ32MVE FXLQ32MAVE
FXZQ40MVE FXLQ40MAVE
FXZQ50MVE FXLQ50MAVE
FXLQ63MAVE
Ceiling mounted cassette (Double flow) type Concealed floor standing type
FXCQ20MVE FXNQ20MAVE
FXCQ25MVE FXNQ25MAVE
FXCQ32MVE FXNQ32MAVE
FXCQ40MVE FXNQ40MAVE
FXCQ50MVE FXNQ50MAVE
FXCQ63MVE FXNQ63MAVE
FXCQ80MVE
FXCQ125MVE
Slim ceiling mounted duct type Heat Reclaim Ventilator (VKM series)
FXDQ20PBVE / FXDQ20PBVET VKM50GAV1 / VKM50GAMV1
FXDQ25PBVE / FXDQ25PBVET VKM80GAV1 / VKM80GAMV1
FXDQ32PBVE / FXDQ32PBVET VKM100GAV1 / VKM100GAMV1
FXDQ40NBVE / FXDQ40NBVET with DX coil (GA)
FXDQ50NBVE / FXDQ50NBVET with DX coil and humidifier (GAM)
FXDQ63NBVE / FXDQ63NBVET
with a Drain Pump (VE)
without a Drain Pump (VET)
General Information 4
External appearance Si30-813_A
8, 10 HP
RWEYQ16, 18, 20P
16, 18, 20 HP
RWEYQ24, 26, 28, 30P
5 General Information
Si30-813_A Combination of Outside Units
60Hz
10 HP 1 –
General Information 6
Capacity Range Si30-813_A
4. Capacity Range
Outside Units
50Hz
60Hz
Combination Single outside unit Double outside units Triple outside units
Capacity range 10 HP 20 HP 30 HP
RWEYQ 10P 20P 30P
Capacity index 250 500 750
Total capacity index of indoor units to be 125 250 375
connected ~ ~ ~
325 650 975
Connectable capacity 50-130% of the rated capacity of the outside unit
Max. number of connectable indoor units 16 32 36
Max. number of connectable BS units 16 32 36
7 General Information
Si30-813_A Capacity Range
Indoor Units
Capacity range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250
Ceiling mounted
cassette FXFQ — 25P 32P 40P 50P 63P — 80P 100P 125P — — —
(Round flow) type
Ceiling mounted
cassette (Compact FXZQ 20M 25M 32M 40M 50M — — — — — — — —
multi flow) type
Ceiling mounted
cassette FXCQ 20M 25M 32M 40M 50M 63M — 80M — 125M — — —
(Double flow) type
Ceiling mounted
cassette corner type FXKQ — 25MA 32MA 40MA — 63MA — — — — — — —
Ceiling mounted
duct type FXMQ — — — — — — — — — — — 200MA 250MA
Ceiling suspended
type FXHQ — — 32MA — — 63MA — — 100MA — — — —
Wall mounted type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — —
Floor standing type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — —
Concealed floor
standing type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — —
Ceiling suspended
cassette type FXUQ — — — — — — 71MA — 100MA 125MA — — —
General Information 8
Si30-813_A
Part 2
Refrigerant Circuit
1. Refrigerant Circuit .................................................................................10
1.1 Outside Unit............................................................................................10
1.2 Indoor Unit..............................................................................................12
1.3 BS Unit ...................................................................................................13
2. Functional Parts Layout ........................................................................14
3. Refrigerant Flow for Each Operation Mode...........................................16
3.1 In Case of Heat Pump Connection.........................................................16
3.2 In Case of Heat Recovery Connection
(Single Outside Unit Installation) ............................................................19
9 Refrigerant Circuit
Si30-813_A Refrigerant Circuit
1. Refrigerant Circuit
1.1 Outside Unit
RWEYQ8P, 10P
No. in
Refrigerant Electric Name Major Function
System Symbol
Diagram
Inverter compressor is operated on frequencies between 52 Hz and 230
A M1C Inverter compressor Hz by using the inverter. The number of operating steps is as follows.
RWEYQ8P, 10P: 22 steps
In cooling: High pressure control
In heating or simultaneous cooling/heating operation:
B Y1E Electronic expansion valve (Main) • When the heat exchanger is used as the evaporator : SH control
• When the heat exchanger is used as the condenser : High pressure
control
C Y3E Electronic expansion valve (Subcooling) PI control is applied to keep the outlet superheated degree of
subcooling heat exchanger constant.
D Y1S Solenoid valve (Hot gas) Used to prevent the low pressure from transient falling.
E Y2S Solenoid valve (Oil return of water heat Used to collect the refrigerant oil from water heat exchanger.
exchanger)
Used to maintain high pressure while in cooling at low water
F Y3S Solenoid valve (Receiver gas charging) temperature. And also used to prevent the accumulation of refrigerant in
non-operating outside units in the case of multiple outside unit system.
G Y4S Solenoid valve (Receiver gas discharging) Used to collect refrigerant to receiver.
Changes the operation into cooling, heating or simultaneous cooling/
H Y5S Four way valve (Main) heating operation.
Solenoid valve (Non-operating unit liquid Used to prevent the accumulation of refrigerant in non-operating outside
I Y6S pipe closing) units in the case of multiple outside unit system.
J Y7S Four way valve (Sub) Changes the water heat exchanger into condenser or evaporator.
K S1NPH High pressure sensor Used to detect high pressure.
L S1NPL Low pressure sensor Used to detect low pressure.
In order to prevent the increase of high pressure when an error occurs,
M S1PH High pressure switch this switch is activated at high pressure of 4.0 MPa or more to stop the
compressor operation.
In order to prevent the increase of pressure when abnormal heating is
N – Fusible plug caused by fire or others, the fusible part of the plug is molten at a
temperature of 70 - 75°C to release the pressure into the atmosphere.
Pressure regulating valve (Liquid pipe to This valve opens at a pressure of 4.0 MPa or more for prevention of
O – pressure increase, thus resulting in no damage of functional parts due to
discharge pipe) the increase of pressure in transportation or storage.
• Used for outside unit fan speed control.
1 R1T Radiation fin thermistor • Used for inverter radiation fin temperature control.
• Used for pressure difference control.
Used to detect suction pipe temperature, keep the suction superheated
2 R2T Suction pipe thermistor degree constant in heating, and others.
3 R3T Discharge pipe thermistor Used to detect discharge pipe temperature, make the temperature
protection control of compressor, and others.
4 R4T Heat exchanger gas pipe thermistor Used to detect gas pipe temperature of water heat exchanger.
Used to detect gas pipe temperature on the evaporating side of sub-
5 R5T Subcooling heat exchanger outlet pipe cooling heat exchanger, keep the superheated degree at the outlet of
thermistor
subcooling heat exchanger constant, and others.
Used to detect receiver outlet liquid pipe temperature, prevent the drift
6 R6T Receiver outlet liquid pipe thermistor between outside units while in heating in the case of multiple outside
unit system, and others.
Refrigerant Circuit 10
Refrigerant Circuit Si30-813_A
Solenoid valve
G
SV Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter
N Filter Filter
B Water
Heat exchanger inlet
SV
Subcooling
Plate heat
C Solenoid valve exchanger
I
Check valve
O Water
Service outlet
port
Pressure
regulating
valve Capillary Capillary
tube tube
Filter Four way valve
H
∗
Solenoid valve Four way valve
J
SV
Check
F
valve
Check valve
Strainer
separator
Gauge port
1/4" flare connection
Oil
K
High pressure
Filter S1NPH
sensor
M
S1PH
High pressure
switch
D
Capillary
A
SV
tube L
S1NPL
Solenoid
valve Gauge port Compressor
Low pressure 1/4" flare connection
sensor INV.
Filter
Stop valve (With service port on on-site piping side φ7.9mm flare connection)
11 Refrigerant Circuit
Si30-813_A Refrigerant Circuit
Fan
R1T
R2T
A
Filter Electronic Filter
expansion valve
4D024460E
FXDQ FXUQ
Gas side
Liquid side
R2T Filter A Filter
R1T
R1T
Fan
R3T Field piping φ9.5 C1220T-O
To
Filter Field piping φ15.9 C1220T-O Outside unit
R2T
Indoor heat exchanger
Indoor unit
4D060927A
4D037995J
Refrigerant Circuit 12
Refrigerant Circuit Si30-813_A
1.3 BS Unit
BSVQ100, 160, 250PV1
No. in
Refrigerant Electric
System Symbol Name Major Function
Diagram
A Y4E Electronic expansion valve Opens while in heating or all indoor units are in cooling. (Max : 760pls)
B Y5E Electronic expansion valve Opens while in cooling. (Max : 760pls)
C Y2E Electronic expansion valve Opens while in heating or all indoor units are in cooling. (Max : 480pls)
D Y3E Electronic expansion valve Opens while in cooling. (Max : 480pls)
In simultaneous cooling and heating, it is used to subcooling liquid
E Y1E Electronic expansion valve refrigerants when an indoor unit downstream of this BS unit is in
heating. (Max : 480pls)
Used to bypass high pressure gas to low pressure side to protect
F — Capillary tube “Refrigerant accumulation” in dual pressure gas pipes.
E Electronic
Double pipe heat Expansion Valve
exchanger (EVSC) Filter
F Capillary tube
A Electronic
Dual gas pipe
Expansion Valve connection port
(EVH)
Filter
B Electronic
Expansion Valve
(EVL)
13 Refrigerant Circuit
Si30-813_A Functional Parts Layout
Gauge port
Receiver Compressor
Refrigerant Circuit 14
Functional Parts Layout Si30-813_A
Top View
Front View
15 Refrigerant Circuit
Si30-813_A Refrigerant Flow for Each Operation Mode
Outside Unit
Solenoid valve
SV Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
inlet
Heat exchanger
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
Refrigerant Circuit 16
Refrigerant Flow for Each Operation Mode Si30-813_A
B. Heating Operation
Indoor Unit ON (Heating) + Thermo. ON Indoor Unit OFF (Heating) Indoor Unit ON (Heating) + Thermo. OFF
High temp. High pressure gas Heat exchanger Heat exchanger Heat exchanger
High temp. High pressure liquid
Low temp. Low pressure gas
Low temp. Low pressure liquid
Outside Unit
Solenoid valve
SV Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
inlet
Heat exchanger
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
17 Refrigerant Circuit
Si30-813_A Refrigerant Flow for Each Operation Mode
Outside Unit
Solenoid valve
SV Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
inlet
Heat exchanger
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
Refrigerant Circuit 18
Refrigerant Flow for Each Operation Mode Si30-813_A
BS Unit
exchanger
exchanger
exchanger
Capillary tube
Capillary tube
Capillary tube
EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC
Outside Unit
Solenoid valve
SV
Filter Fusible
plug Electronic
Receiver
Water
Heat exchanger
inlet
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
19 Refrigerant Circuit
Si30-813_A Refrigerant Flow for Each Operation Mode
B. Heating Operation
Indoor Unit ON (Heating) + Thermo. ON Indoor Unit ON (Heating) + Thermo. OFF Indoor Unit OFF (Heating)
High temp. High pressure gas Heat exchanger Heat exchanger Heat exchanger
High temp. High pressure liquid
Low temp. Low pressure gas
Low temp. Low pressure liquid
BS Unit
exchanger
exchanger
exchanger
Capillary tube
Capillary tube
Capillary tube
EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC
Outside Unit
Solenoid valve
SV
Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
Heat exchanger
inlet
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
SV Electronic
expansion valve
Solenoid valve Capillary
tube
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
Refrigerant Circuit 20
Refrigerant Flow for Each Operation Mode Si30-813_A
C. Heating and simultaneous cooling/heating operation (When the outside water cooled heat exchanger is used
as condenser.)
Indoor Unit ON (Cooling) + Thermo. ON Indoor Unit ON (Cooling) + Thermo. ON Indoor Unit ON (Heating) + Thermo. ON
High temp. High pressure gas Heat exchanger Heat exchanger Heat exchanger
High temp. High pressure liquid
Low temp. Low pressure gas
Low temp. Low pressure liquid
BS Unit
exchanger
exchanger
exchanger
Capillary tube
Capillary tube
Capillary tube
EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC
Filter Filter
Outside Unit
Solenoid valve
SV
Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
Heat exchanger
inlet
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
SV Electronic
expansion valve
Solenoid valve Capillary
tube
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
21 Refrigerant Circuit
Si30-813_A Refrigerant Flow for Each Operation Mode
D. Heating and simultaneous cooling/heating operation (When the outside water cooled heat exchanger is used
as evaporator.)
(In case there are indoor units operating with cooling thermostat “ON”.)
Indoor Unit ON (Cooling) + Thermo. ON Indoor Unit ON (Heating) + Thermo. ON Indoor Unit ON (Heating) + Thermo. ON
High temp. High pressure gas Heat exchanger Heat exchanger Heat exchanger
High temp. High pressure liquid
Low temp. Low pressure gas
Low temp. Low pressure liquid
BS Unit
exchanger
exchanger
exchanger
Capillary tube
Capillary tube
Capillary tube
EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC
Filter Filter
Outside Unit
Solenoid valve
SV
Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
Heat exchanger
inlet
Sub cooling
SV
Plate heat
Solenoid valve exchanger
Check valve
SV Electronic
expansion valve
Solenoid valve Capillary
tube
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
Refrigerant Circuit 22
Refrigerant Flow for Each Operation Mode Si30-813_A
(Normal operation) (Oil return opening degree) (Oil return opening degree)
BS Unit
exchanger
exchanger
exchanger
Capillary tube
Capillary tube
Capillary tube
EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC EVL EVLS EVH EVHS EVSC
Filter Filter
Outside Unit
Solenoid valve
SV
Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
Heat exchanger
inlet
Sub cooling
SV
Plate heat
Solenoid valve exchanger
SV
Check valve Electronic
expansion valve
Solenoid valve Capillary
tube
Check valve
Water
Service outlet
port
Pressure
regulating Capillary
valve Capillary tube
Four way valve tube
Filter
Check
valve
Check valve
Strainer
separator
Gauge port
Oil
Capillary
SV
tube
S1NPL
Solenoid Compressor
valve Low pressure Gauge port
sensor 1/4” flare connection INV.
Filter
4D048290C
23 Refrigerant Circuit
Si30-813_A
Part 3
Remote Controller
1. Remote Controller .................................................................................25
1.1 Wired Remote Controller........................................................................25
1.2 Wireless Remote Controller ...................................................................33
1.3 Service Mode .........................................................................................36
1.4 Inspection Mode .....................................................................................40
Remote Controller 24
Remote Controller Si30-813_A
1. Remote Controller
1.1 Wired Remote Controller
1.1.1 Names and Functions
BRC1C Type
5 12 4 2 1
3
7 hr
9
C L H
hr NOT 11
6 TEST AVAILABLE
10
8 13
14 21
20
TEST
19
16 15 17 18 22
25 Remote Controller
Si30-813_A Remote Controller
BRC1D Type
3P107422-3D
Remote Controller 26
Remote Controller Si30-813_A
29 PROGRAMMING BUTTON
This button is a multi-purpose button.
Depending on the previous manipulations of the user,
the programming button can have various functions.
3P107422-3D
27 Remote Controller
Si30-813_A Remote Controller
BRC1E61
1. Operation mode
selector button
4. Up button
5. Down button
6. Right button
7. Left button
9. Operation lamp
8. ON/OFF button
3. Menu/Enter button
3. Menu/Enter button
Used to indicate the main menu.
Used to enter the setting item selected.
5. Down button (Be sure to press the part with the symbol )
Used to lower the set temperature.
The next items on the lower side will be highlighted.
(The highlighted items will be scrolled continuously when the button is kept pressed.)
Used to change the item selected.
Remote Controller 28
Remote Controller Si30-813_A
6. Right button (Be sure to press the part with the symbol )
Used to highlight the next items on the right-hand side.
Each screen is scrolled in the right-hand direction.
Home leave settings are enabled with this button kept pressed for at least 4 seconds.
7. Left button (Be sure to press the part with the symbol )
Used to highlight the next items on the left-hand side.
Each screen is scrolled in the left-hand direction.
Home leave settings are enabled with this button kept pressed for at least 4 seconds.
8. ON/OFF button
Press this button and system will start.
Press this button again and system will stop.
10.Cancel button
Used to return to the previous screen.
29 Remote Controller
Si30-813_A Remote Controller
M
Set the switch to SUB.
S
BRC1E61
The designation of the main and sub remote controllers can be swapped. Note that this change requires
turning the power OFF and then ON again.
Basic screen
Select "Main
is displayed. remote controller"
Press and or "Sub remote
Press
hold Cancel controller" using
Cancel
button for 4 the /
button
seconds or (Up/Down) buttons,
once.
more. and then press
Select "Main/sub changeover" Menu/Enter button.
Press Menu/Enter
Field setting and press Menu/Enter button. Item 2 is button.
Item 2 is
menu is displayed. displayed.
Press Cancel button.
displayed.
Remote Controller 30
Remote Controller Si30-813_A
BRC1C Type
Mode No.
Group No.
UNIT NO.
Field
SETTING Setting
Mode
TEST
2
4 3
1,5
BRC1D Type
Mode No.
Group No.
Field
Setting
Mode
2
4 3
1,5
Note:
For setting group No. of heat reclaim ventilator and wiring adaptor for other air conditioners, etc., refer to
the operation manual attached.
Notice
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to
keep the installation table with the operation manual for maintenance.
31 Remote Controller
Si30-813_A Remote Controller
BRC1E61
In order to conduct the centralized remote control using the centralized remote controller and the unified ON/
OFF controller, Group No. settings should be made by group using the operating remote controller.
Make Group No. settings for centralized remote control using the operating remote controller.
(1) <Basic screen>
Press and hold Cancel button for 4 seconds or more.
Field setting menu is displayed.
Note:
For setting group No. of heat reclaim ventilator and wiring adaptor for other air conditioners, etc., refer to
the operation manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to
keep the installation table with the operation manual for maintenance.
Remote Controller 32
Remote Controller Si30-813_A
3
1-2
H M L
DOWN 10
C ON OFF
6 UP
TEMP
FAN H M L TIME 11
4
C
hr. UP
9 DOWN
hr. FAN
2 13
RESERVE CANCEL
hr.
5 TIMER 12
TEST hr.
MODE 15
7
SWING 14
16
TEST
TEST 17
Figure 1
3P107422-11J
33 Remote Controller
Si30-813_A Remote Controller
Remote Controller 34
Remote Controller Si30-813_A
1
Wireless address
2
2
switch (SS2)
3
3
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller should be set
to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the receiver to SUB.
MAIN/SUB S S
switch (SS1) M M
35 Remote Controller
Si30-813_A Remote Controller
3 4 Mode
First
Code No.
1 2 7 TEST
5 3
6
UNIT No.
CODE SETTING
Error history 1: Newest
3: Oldest
∗ "00" displayed for 4 and subsequent.
Remote Controller 36
Remote Controller Si30-813_A
Service Setting
Mode No.
Unit No. Mode No. Field Setting Mode
Second Unit NO. 5
Field
Code No. 5
SETTING Setting
3 4 Mode
First
Code No.
1 2 6 TEST
Second Code No.
5 3
5
First Code No.
1, 2, 6
SETTING
44 Individual Setting Sets fan speed and airflow direction for
each unit individually when using group Fan 1: Low
speed 3: High
control. 0: Upper
Settings are made using the “airflow
direction adjust” and “fan speed adjust”
UNIT No. 4: Lowest
buttons.
CODE SETTING
UNIT No.
CODE SETTING
37 Remote Controller
Si30-813_A Remote Controller
1.3.2 BRC1E61
Operating the remote controller allows service data to be acquired and various services to be set.
Basic
screen is
displayed.
Press Press Cancel
Cancel Press and hold Cancel button button.
button for 4 seconds or more.
once.
Field setting
menu is
displayed.
Remote Controller 38
Remote Controller Si30-813_A
39 Remote Controller
Si30-813_A Remote Controller
Unit 0
Error code L0
Inspection
Inspection mode Inspection mode
Press the Inspection/test button once.
Unit 0
Error code L0
Inspection
Error code blinks when an error occurs.
071
FJJ
–––
AA1
Test operation
Test operation mode
Press the Inspection/test button once.
Note:
Inspection mode is not available for BRC1E61.
Remote Controller 40
Si30-813_A
Part 4
Function and Control
1. Function General...................................................................................42
1.1 Operation Mode......................................................................................42
2. Basic Control.........................................................................................43
2.1 Normal Operation ...................................................................................43
2.2 Indoor Unit Operation Mode Detail.........................................................44
2.3 Compressor Control ...............................................................................45
2.4 Electronic Expansion Valve Control .......................................................47
2.5 Heat Exchange Mode in Heating or Simultaneous Cooling/
Heating Operation ..................................................................................48
3. Special Control......................................................................................50
3.1 Startup Control .......................................................................................50
3.2 Oil Return Operation ..............................................................................52
3.3 Oil Return Operation of Water Heat Exchanger .....................................54
3.4 Pump down Residual Operation Control ................................................55
3.5 Refrigerant Drift Prevention....................................................................57
3.6 Standby ..................................................................................................58
3.7 Stopping Operation ................................................................................59
4. Protection Control .................................................................................61
4.1 High Pressure Protection Control...........................................................61
4.2 Low Pressure Protection Control............................................................62
4.3 Discharge Pipe Protection Control .........................................................64
4.4 Inverter Protection Control .....................................................................65
4.5 Cooling Fan Control ...............................................................................66
5. Other Control.........................................................................................67
5.1 Outside Unit Rotation .............................................................................67
6. Outline of Control (Indoor Unit) .............................................................68
6.1 Drain Pump Control................................................................................68
6.2 Thermostat Control.................................................................................70
6.3 Electronic Expansion Valve Control .......................................................73
6.4 Hot Start Control (In Heating Only) ........................................................73
6.5 Freeze-up Prevention.............................................................................74
6.6 List of Swing Flap Operations ................................................................75
1. Function General
1.1 Operation Mode
System stopping function
NO • Restart standby
Thermostat ON
• Crankcase heater control
YES
Startup control
• Cooling startup control
• Heating startup control • Pump down residual operation
• Pressure equalization
startup control
Normal operation
YES
Thermostat OFF
• Cooling operation
• Heating operation NO
• Cooling/Heating simultaneous
operation
Abnormal stop Determination
• BS unit & Indoor unit operation • Abnormal stop
condition
• Sub unit stopping function
• Compressor control NO
• Electronic expansion valve control
• Heat exchanger mode control
Cooling/Heating YES
• Pressure equalization control
mode change
Protection control
NO
• High pressure protection control
• Low pressure protection control
• Discharge pipe protection control IN Oil return operation
Oil return
• Cooling oil return operation
• Inverter protection control condition
• Heating oil return operation
• Refrigerant drift prevention
NO
NO
2. Basic Control
2.1 Normal Operation
Actuator Function
Parts Name Electric
Symbol Normal heating or normal cooling/
Normal cooling heating simultaneous operation
PI control, High pressure protection, PI control, High pressure protection,
Compressor M1C Low pressure protection, Discharge Low pressure protection, Discharge
pipe temperature protection control, pipe temperature protection control,
Inverter protection control Inverter protection control
Inverter cooling fan M1F, M2F Inverter cooling fan control Inverter cooling fan control
Four way valve (Main) Y5S OFF ON
Heat exchanger mode control
Four way valve (for heat Y7S OFF (In case of heating and simultaneous
exchanger) cooling/heating operation)
Electronic expansion valve Heat exchanger mode control Heat exchanger mode control
(Main) Y1E (In case of cooling operation) (In case of heating and simultaneous
cooling/heating operation)
Electronic expansion valve
(Subcooling) Y3E Y3E control Y3E control
Hot gas bypass solenoid valve Y1S Protection control Protection control
Water heat exchanger oil return Water heat exchanger oil return
solenoid valve Y2S OFF control
Receiver gas charging solenoid Y3S Receiver pressurising control Receiver pressurising control and
valve drift protection control
Receiver gas discharge
solenoid valve Y4S OFF Drift protection control
Note: ∗1: The switch for the BS unit is operated when pressure equalization control turns on after
cooling/heating mode of other indoor unit is changed or on the timing of oil returns.
∗2: If Y3S: ON, depend on indoor control (200 pulse).
If Y3S: OFF, 0 pulse.
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to achieve TeS.
Te setting
L M (Normal) H
(factory setting)
3 6 7 8 9 10 11
[Heating operation]
Controls compressor capacity to adjust Tc to achieve TcS.
Tc setting
L M (Normal) H
(factory setting)
43 46 49
3 6 7 8 9 10 11
Tc setting
L M (Normal) H
(factory setting)
43 46 49
[Heating operation]
To lower the discharge pipe temperature when the discharge pipe temperature is over 95°C,
makes PI control of the electronic expansion valve (Y3E) to keep the superheated degree of the
outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger. (When
the discharge pipe temperature is lower than 95°C, Y3E opening is 0 pulse.)
SH = Tsh -Te
Master unit
Four way valve for heat exchanger (Y7S) ON
(For the application of heat exchanger) (Evaporator)
Content of the control of electronic expansion valve Control of heat exchange
(Y1E) capacity balance
3. Special Control
3.1 Startup Control
This startup control provides the following control to reduce the compressor load resulting from
liquid return or else during compressor startup, and also determine the position of four way
valves.
3.1.1 Startup Control in Cooling
Both master and slave units operate same time for changing four way valve position → Normal
operation after completion.
Pc: Value detected by high pressure sensor
Pe: Value detected by low pressure sensor
Thermostat ON
Indoor unit fan M1F, M2F Indoor unit control Indoor unit control
Indoor unit electronic expansion valve Y1E 0 pulse 0 pulse → Initial opening
Ending condition 1 minute Max. 5 minutes
Pressure Equalization
Parts Name Electric Symbol Control before Start-up Starting Control
Indoor unit
electronic expansion Y1E — —
valve (Heating)
[Starting condition]
Tg: Gas pipe temperature of water heat exchanger
Te: Low pressure equivalent saturation temperature
After a certain continuous period of time has passed under the following conditions, oil return
operation starts.
• Y7S = ON (Water heat exchanger is an evaporator.)
& • Tg – Te > 10°C
• Elapse of a certain period of time
Compressor M1C 52 Hz
Electric
Parts Name Symbol Master Unit Operation Slave Unit Operation
Electronic expansion valve (Main) Y1E Y7S = OFF: 2000 pulse 0 pulse
Y7S = ON: 0 pulse
Electronic expansion valve Y3E 0 pulse 0 pulse
(Subcooling)
Hot gas bypass solenoid valve Y1S ON OFF
Water heat exchanger oil return
solenoid valve Y2S OFF OFF
3.6 Standby
3.6.1 Restart Standby
Forced standby is performed to prevent frequent repetition of ON/OFF of the compressor, and
to equalize pressure in the refrigerant system.
Electric
Parts Name Symbol Actuator Function
Compressor M1C 0 Hz
Inverter cooling fan M1F, M2F OFF
Four way valve (Main) Y5S Holding
Four way valve (for heat exchanger) Y7S Holding
Electronic expansion valve (Main) Y1E 0 pulse
Electronic expansion valve (Subcooling) Y3E 0 pulse
Hot gas bypass solenoid valve Y1S OFF
Water heat exchanger oil return solenoid valve Y2S OFF
Receiver gas charging solenoid valve Y3S OFF
Receiver gas discharge solenoid valve Y4S OFF
Non-operation unit liquid pipe stop solenoid valve Y6S ON
Indoor unit fan (Cooling) M1F, M2F Remote controller setting
Indoor unit electronic expansion valve (Cooling) Y1E All indoor electronic expansion valve : 0 pulse
Indoor unit fan (Heating) M1F, M2F Indoor unit control
Indoor unit electronic expansion valve (Heating) Y1E All indoor electronic expansion valve : 0 pulse
BS unit Holding
Ending condition 4 minutes
Note:
Master Slave
∗1 Mode A or B operation unit unit
The changeover operation for mode A and B is performed for the reason that the required
refrigerant amount varies depending on the indoor unit operation capacity.
Note:
Master Slave
∗1 Mode A or B operation unit unit
The changeover operation for mode A and B is performed for the reason that the required
refrigerant amount varies depending on the indoor unit operation capacity.
4. Protection Control
4.1 High Pressure Protection Control
This high pressure protection control prevents the activation of protection devices due to
abnormal increase of high pressure and to protect compressors against the transient increase
of high pressure.
Pc: High pressure sensor detection value for each outside unit
[In cooling]
Normal operation
Frequency control
Pc < 3.23 MPa
Compressor upper limit down 3 steps/10 seconds INV. upper limit up 1 step/30 seconds
Compressor 52Hz
Pc ≥ 3.63 MPa
Less than 2 times When occurring 3 times within 30
within 30 minutes minutes, high pressure switch is activated
High pressure standby
without high pressure standby, and the
error code “E3” is displayed.
Normal operation
Frequency control
Compressor down 7 steps/10 seconds
Pc ≥ 3.63 MPa
When occurring 3 times within 30
minutes, high pressure switch is activated
High pressure standby without high pressure standby, and the
Less than 2 times within
error code “E3” is displayed.
30 minutes
[In cooling]
Pe: Value detected by low pressure sensor
Normal operation
Compressor 52Hz
Normal control
Compressor 52Hz
Normal operation
Compressor 52 Hz
[INV. compressor]
HTdi: Value of INV. compressor discharge pipe temperature compensated with outdoor air
temperature
Normal operation
Compressor 62Hz
Not limited
∗1 ∗2
Inverter current < ∗1 RWEYQ8-30PY1 13.5A 17A
Inverter &
current > ∗1 INV. upper limit frequency = 230 Hz RWEYQ10-30PYL 13.5A 17A
RWEYQ10-30PTL 24.0A 25.1A
Normal operation
Tfin ≤ 81˚C
for continues 3 minutes
Compressor upper limit down Compressor upper limit up
1 step/15 seconds 1 step/1 minute
Tfin ≥ 84˚C
[Details]
Control the cooling fan by each outside unit.
· 52C1 = ON
& · Tfin > 50˚C
OR · Tfin is defective
· 52C1 = OFF
OR · Tfin < 30˚C
& · Tfin is normal
5. Other Control
5.1 Outside Unit Rotation
In the case of multi outside unit system, this outside unit rotation prevents the compressor from
burning out due to unbalanced oil level between outside units.
Example) The following diagram shows outside unit rotation in combination of 3 outside units.
Starting
control Oil return operation
Normal operation Normal operation
A
Outside unit
rotation Priority Priority Priority
2 3 1
Note: ∗ “Master unit”, “slave unit 1” and “slave unit 2” in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are
different from “master unit” and “slave unit” for control.)
The outside unit connected the control wires (F1 and F2) for the indoor unit should be
designated as master unit.
Consequently, The LED display on the main PCB for “master unit”, “slave unit 1” and “slave
unit 2” do not change. (Refer to the P.79.)
6.1.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
OFF
Float switch
ON
ON
Drain pump
OFF
6.1.2 When the Float Switch is Tripped during Cooling OFF by Thermostat:
Enters error treatment if the float switch is not reset within 5 minutes.
ON
Thermostat Remote controller displays "A3" and the system stops.
(running)
OFF
OFF
Float switch
ON
ON
Drain pump
OFF
∗1
Thermostat ON
(running) Remote controller displays "A3"
OFF
ON
Float switch Reset
OFF
ON
Drain pump
OFF
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.1.4 When the Float Switch is Tripped and “AF” is Displayed on the
Remote Controller:
Enters error treatment if the
float switch is not reset
within 5 minutes.
ON
Remote "AF" display (running) Remote controller displays "A3"
controller display OFF
OFF
Float switch
ON
1st time 2nd time 3rd time 4th time 5th time
ON
Drain pump
OFF
5 sec.
∗1 ∗1 ∗1 ∗1 ∗1 ∗1 ∗1
∗2 ∗3
34
Cooling
32
30
28
Room temperature thermistor
22
20
Suction air
12 14 16 18 20 22 24 26 28 30 32 34 temperature (˚C)
28
Heating
26
24
Suction air
Room temperature
Suction air thermistor thermistor
thermistor
22
Room temperature Suction air
Suction air thermistor thermistor thermistor
20
18
16
15 Suction air
12 14 16 18 20 22 24 26 28 30 32 34 temperature (˚C)
While in a single remote controller group control, the suction air thermistor is only used for this
control.
Furthermore, while in heating, cassette-mounted indoor units conduct the thermostat control by
a value compensated by –2°C for the value detected with the suction air thermistor. (Through
field settings, the thermostat differential setting can be changed from 1°C to 0.5°C. For details
on the changing procedure, refer to P.87.)
Tro: Suction air temperature at the time of starting the dry operation
Tr: Temperature detected with the suction air thermistor
Tr < Tro –1ºC
Furthermore, while in dry operation mode, fans operate at "L" tap, stops for a period of 6
minutes while the thermostat is OFF, and then return to operation at "L" tap. (This control
prevents a rise in indoor temperature while in thermostat OFF mode.)
12 4 Differential value while in "AUTO" 0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C
operation mode
: Factory setting
Cooling thermostat ON
Cooling thermostat OFF
Display change
Cooling → Heating
Display change
Heating → Cooling
3°C
(D
2 +2)°C
LL
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
OFF
setting
Po (Horizontal)
Starting condition: Temperature is –1°C or less for total of 40 minutes, or temperature is –5°C or
less for total of 10 minutes.
Ending condition: Temperature is +7°C or more for 10 minutes continuously
10 minutes
Part 5
Test Operation
1. Test Operation ......................................................................................77
1.1 Procedure and Outline ...........................................................................77
2. Field Setting from Remote Controller....................................................82
2.1 Wired Remote Controller........................................................................82
2.2 Wireless Remote Controller ...................................................................85
2.3 Simplified Remote Controller..................................................................86
2.4 Setting Contents and Code No. for Indoor Units ....................................87
3. Field Setting from Outside Unit PCB.....................................................97
3.1 Location of DIP Switch and BS Button ...................................................97
3.2 Setting by DIP Switches .........................................................................98
3.3 Setting by BS Buttons ..........................................................................100
3.4 Setting Mode 1 .....................................................................................101
3.5 Setting Mode 2 .....................................................................................102
3.6 Monitor Mode .......................................................................................105
3.7 Detailed Explanation of Setting Modes ................................................107
4. Emergency Operation .........................................................................124
4.1 Restrictions for Emergency Operation .................................................124
4.2 In the Case of Multi Outside Unit System.............................................124
Test Operation 76
Test Operation Si30-813_A
1. Test Operation
1.1 Procedure and Outline
Follow the following procedure to conduct the initial test operation after installation.
Check on air tight test and { Is the air tight test and vacuum drying carried out as per
vacuum drying installation manual?
Carry out field setting on { For field settings, refer to “Field Settings” on and after P.98.
outside unit PCB After the completion of field settings, set to “Setting mode 1”.
In case of multi outside unit connection, carry out the field settings
on master unit. (The setting on slave unit is not effective.)
77 Test Operation
Si30-813_A Test Operation
k: ON h: OFF l: Blink
Micro C/H selection
computer MODE TEST Low
LED display (Factory normal IND Master Slave noise Demand Multi
setting) monitor
HAP H1P H2P H3P H4P H5P H6P H7P H8P
1 outside unit installation l h h k h h h h h
Outside unit Master l h h k h h h h k
multi Slave1 l h h h h h h h l
installation(*) Slave2 l h h h h h h h h
* The outside unit connected the control wires (F1 and F2) for the indoor unit should be
designated as master unit. The other outside unit not connected the control wires will be slave
unit.
Indoor unit If ON button is pressed during operation described above, the “UH” error
indicator blinks.
(Returns to normal when automatic setting is complete.)
Indoor unit If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when
automatic setting is complete.)
3. When an Indoor Unit or Outside Unit Has Been Added, or Indoor or Outside Unit PCB
Has been Changed
Be sure to press and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outside unit address, etc.)
Status
Outside unit Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit If ON button is pressed during operation described above, the “UH” or “U4” error
indicator blinks. (Returns to normal when automatic setting is complete.)
Caution When the 400 volt power supply is applied to "N" phase by mistake,
replace Inverter PCB (A2P) and control transformer (T1R, T2R) in
switch box together.
Test Operation 78
Test Operation Si30-813_A
79 Test Operation
Si30-813_A Test Operation
Figure 1
81 Test Operation
Si30-813_A Field Setting from Remote Controller
1 7 TEST
6 5 2
1. When in the normal mode, press the “ ” button for 4 seconds or more, and the Field
TEST
Test Operation 82
Field Setting from Remote Controller Si30-813_A
2.1.2 BRC1E61
<Basic screen>
<Field setting menu screen> 4 In the case of setting per indoor unit
(2) during group control (When Mode No.
such as 20 , 21 , 22 , 23 , 25 are
selected), highlight the unit No. and
select “Indoor unit No.” to be set by
using (Up/Down) button. (In the
case of group total setting, this
operation is not needed.)
In the case of individual setting per
indoor unit, current settings are
displayed. And, Second Code No.
“ - ” means no function.
Press Menu/Enter button.
5 Highlight Second Code No. of the First
Code No. to be changed, and select
<Field setting screen>
desired “Second Code No.” by using
In the case of individual In the case of group total (Up/Down) button. Multiple identical
setting per indoor unit setting mode number settings are available.
(3) (3) In the case of group total setting, all
(4) (5) of Second Code No. which may be
set are displayed as “ ∗ ”.
(5) “ ∗ ” is changed to Second Code
No. to be set. And, Second Code
No. “ - ” means no function.
83 Test Operation
Si30-813_A Field Setting from Remote Controller
CAUTION
z When an optional accessory is installed on the indoor unit, settings of the indoor
unit may be changed. See the manual of the optional accessory.
z For field setting details of the outside unit, see installation manual attached to the
outside unit.
Test Operation 84
Field Setting from Remote Controller Si30-813_A
UP button
Mode No.
Field setting mode DOWN button
RESERVE button
First code No.
MODE button
Second code No.
INSPECTION/TEST button
Setting
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
85 Test Operation
Si30-813_A Field Setting from Remote Controller
Mode No.
First
Code No.
Unit No.
Second
Code No.
Test Operation 86
Field Setting from Remote Controller Si30-813_A
Note: 1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
∗2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
4. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
∗5. If the setting mode to “Equipped”, heat reclaim ventilator fan conducts the fan residual
operation by linking to indoor unit.
∗6. • The FXMQ20·25·32PVE cannot be set to 110-200Pa.
• The FXMQ40PVE cannot be set to 180 or 200Pa.
• The FXMQ50·63·80·100·125PVE cannot be set to 30Pa.
• The FXMQ140PVE cannot be set to 30Pa and 150-200Pa.
87 Test Operation
Si30-813_A Field Setting from Remote Controller
Mode No. First Code Second Standard Long Life Ultra Long Setting
No. Code No. Filter Filter Life Filter
Contamination
01 200 hrs. 2,500 hrs. 10,000 hrs. Light
10 (20) 0
02 100 hrs. 1,250 hrs. 5,000 hrs. Contamination
Heavy
Selection of Thermistor
Select the thermistor to control room temperature.
Mode No. First Code No. Second Code No. Thermistor that controls room temperature
Room temperature thermistor in remote
01 controller and suction air thermistor for
indoor unit
10 (20) 2
02 Suction air thermistor for indoor unit
Room temperature thermistor in remote
03 controller
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and room temperature thermistor in remote controller.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the room
temperature thermistor in remote controller.
Test Operation 88
Field Setting from Remote Controller Si30-813_A
Airflow Adjustment
Make settings in either method (a) or method (b) as explained below. (FXMQ140PVE cannot be
selected method (a). Please select method (b).)
(a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is automatically adjusted to the rated
quantity.
(1) Check that power supply wiring to the air conditioner is completed along with duct
installation. If a closing damper is installed in the air conditioning system, make sure that
the closing damper is opened. Furthermore, check that the air filter as a field supply is
attached to the air passage on the suction side.
(2) If there are a number of air outlets and inlets, adjust the throttles so that the airflow rate of
each air outlet and inlet will coincide with the designed airflow rate. At that time, operate
the air conditioner in “fan operation mode”. To change the airflow rate, press and set the
airflow adjustment button of the remote controller to HH, H, or L.
(3) Make settings for airflow automatic adjustment. After setting the air conditioner to “fan
operation mode”, stop the air conditioner, go to “field setting mode”, select “mode No. 21”
(11 in the case of group settings), set the setting “first code No.” to 7, and set the setting
“second code No.” to 03.
Return to normal mode after these settings, and press the ON/OFF operation button.
Then the operation lamp will be lit and the air conditioner will go into fan operation for
airflow automatic adjustment. Do not adjust the throttles of the air outlets or inlets during
automatic adjustment of the air conditioner. After the air conditioner runs approximately
1~8 minutes, the air conditioner will finish airflow adjustment automatically, the operation
lamp will be turned OFF, and the air conditioner will come to a stop.
(4) After the air conditioner stops operating, check with “mode No. 21” on an indoor unit
basis that 02 is set for the “second code No.” in the table below. If the air conditioner
does not stop operating automatically or the “second code No.” is not 02, repeat steps
from (3). If the outside unit is not turned ON, U4 or UH will be displayed. This display is
not problematic, because this function is set for the indoor unit. Continue setting the
function.
After setting this function, be sure to turn ON the outside unit before the test operation of
the outside unit.
CAUTION
z If there is any change after airflow adjustment in the ventilation paths (e.g., the duct and air
outlet), be sure to make airflow auto adjustment again.
z Consult your Daikin representative if there is any change in the ventilation paths (e.g., the
duct and air outlet) after the test operation of the outside unit is finished or the air
conditioner is moved to another place.
(b) Select external static pressure with remote controller check that 01 (OFF) is set for the
“second code No.” in “mode No. 21” for airflow adjustment on an indoor unit basis in the
table below. The “second code No.” is set to 01 (OFF) at factory setting. Change the “second
code No.” as shown in external static pressure settings on P.93 according to the external
static pressure of the duct to be connected.
(1) The “second code No.” is set to 07 (an external static pressure of 100 Pa) at factory
setting. (FXMQ40 · 50 · 63 · 80 · 100 · 125 · 140PVE)
The “second code No.” is set to 02 (an external static pressure of 50 Pa) at factory
setting. (FXMQ20 · 25 · 32PVE)
Mode No. First Code No. Second Code No. Airflow Adjustment
01 OFF
11 (21) 7 02 Completion of airflow adjustment
03 Start of airflow adjustment
89 Test Operation
Si30-813_A Field Setting from Remote Controller
First Second
Mode No. Code No. Code No. Operation by Input of The Signal A
Thermostat Switching
Differential value during thermostat ON/OFF control can be changed. (For details, refer to "6.2.2
Thermostat Control while in Normal Operation" on P.71.)
Mode No. First Code No. Second Code No. Differential Value
01 1ºC
12(22) 2
02 0.5ºC
Test Operation 90
Field Setting from Remote Controller Si30-813_A
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned ON again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning OFF the main power switch
during the unit is in operation, and turning ON the switch again after the
work is completed start the unit operation (the fan rotates).
FXHQ
Mode No. First Code No. Second Code Setting Ceiling Height
No.
01 Standard • All round outlet ≤ 3.2 m
13 (23) 0 02 High Ceiling 3.2 - 3.6 m
03 Higher Ceiling 3.6 - 4.2 m
91 Test Operation
Si30-813_A Field Setting from Remote Controller
FXUQ
First Second Ceiling Height
Mode Code Code Setting
No. No. No. 4-way Outlets 3-way Outlets 2-way Outlets
01 Standard ≤ 2.7 m ≤ 3.0 m ≤ 3.5 m
13 (23) 0 02 High Ceiling ≤ 3.0 m ≤ 3.5 m ≤ 3.8 m
03 Higher Ceiling ≤ 3.5 m ≤ 3.8 m —
01 F: 4-direction airflow
13 (23) 1 02 T: 3-direction airflow
03 W: 2-direction airflow
01 Upward (Draft
prevention)
13 (23) 4 02 Standard
03 Downward (Ceiling
soiling prevention)
∗ Some indoor unit models are not equipped with draft prevention (upward) function.
Test Operation 92
Field Setting from Remote Controller Si30-813_A
93 Test Operation
Si30-813_A Field Setting from Remote Controller
01 Individual operation of
humidifier
15 (25) 3 Interlocked operation
02 between humidifier and
drain pump
Test Operation 94
Field Setting from Remote Controller Si30-813_A
95 Test Operation
Si30-813_A Field Setting from Remote Controller
Selection of Select whether to accept or to reject the operation from the remote controller regarding the operation,
Control Mode No. stop, temperature setting and operation mode setting, respectively, and determine the particular
control mode from the rightmost column of the table below.
(Example)
The control
mode is “ 1 ”.
[Rejection] [Rejection] [Rejection] [Acceptance] [Acceptance]
C: 3P171361-1
Test Operation 96
Field Setting from Outside Unit PCB Si30-813_A
(3) BS button H1P H2P H3P H4P H5P H6P H7P H8P
BS1 BS2 BS3 BS4 BS5
1
2
1 2 3 4 1 2 3 4
DS3
DS1 DS2
A B C F1 F2 F1 F2 Q1 Q2
Indoor − Outside − Multi
C/H selector Outside unit Outside unit outside unit
(3) BS button
Used to change mode.
97 Test Operation
Si30-813_A Field Setting from Outside Unit PCB
Caution DIP switch setting after changing the main PCB (A1P) to spare PCB
When you change the main PCB (A1P) to spare PCB, please carry out the following setting.
Initial Condition
ON ON
Overseas OFF OFF
1 2 3 4 1 2 3 4
DS1 DS2
DS1-4 — —
ON Except Japan
DS2-1 Japan/Except
Japan setting OFF Japan
DS2-2 8 10
DS2-2 ON OFF
DS2-3 HP setting
DS2-3 OFF ON
DS2-4 DS2-4 OFF OFF
Domestic
Test Operation 98
Field Setting from Outside Unit PCB Si30-813_A
BSVQ100PV1
BSVQ100PV13 ON
BSVQ100PV18(A)(B) Set DS1-3 to ON.
BSVQ100PV19 OFF
1 2 3 4 1 2 3 4
BSVQ36PVJU
BSVQ160PV1
BSVQ160PV13 ON
BSVQ160PV18(A)(B) Set DS1-4 to ON.
BSVQ160PV19 OFF
1 2 3 4 1 2 3 4
BSVQ60PVJU
BSVQ250PV1
ON
BSVQ250PV13
Set DS1-3 and DS1-4 to ON.
BSVQ250PV18(A)(B) OFF
BSVQ250PV19 1 2 3 4 1 2 3 4
99 Test Operation
Si30-813_A Field Setting from Outside Unit PCB
Press BS1 (MODE) for more than 5 sec. Setting mode 1 Press BS1(MODE) once.
(Initial condition)
4 Number of units for Sets the number of units for sequential starting.
sequential starting
Indoor unit forced Allows forced operation of indoor unit fan while unit is
<Selection of setting items> 5 fan H stopped. (H tap)
Press the SET button (BS2) and set 6 Indoor unit forced Allows forced operation of indoor unit.
the LED display to a setting item operation
shown in the table on the right. 8 Te setting Target evaporating temperature for cooling
↓
Press the RETURN button (BS3) 9 Tc setting Target condensing temperature for heating
and decide the item. (The present 12 Demand setting Reception of demand signal
setting condition is blinked.)
13 AIRNET address Sets address for AIRNET.
Additional
20 refrigerant charge Carries out additional refrigerant charge operation.
operation setting
Refrigerant
21 collection mode Sets to refrigerant collection mode.
setting
Interlock error
26 display setting Sets interlock error display
<Selection of setting conditions>
Power transistor Used for service diagnosis of DC compressor. Since the
Press the SET button (BS2) and set check mode waveform of inverter is output without wiring to the
to the setting condition you want. 28 ∗Check after compressor, it is convenient to probe whether the trouble
↓ disconnection of
Press the RETURN button (BS3) comes from the compressor or PCB.
compressor wires
and decide the condition.
Changes target value of power consumption when
30 Demand setting 1 demand control 1 is input.
k: ON h: OFF l: BLINK
Setting Item Setting Condition
No. C/H Selection Low LED Display
MODE TEST Demand
Setting Item Noise Contents
H1P H2P IND
H3P
Master Slave
H4P H5P H6P
H7P
∗ Factory setting
Address 0 khhhhhh ∗
1
Cool / Heat
k h h h h h k
Binary number 1 khhhhhk
Unified address (6 digits) ~
31 khkkkkk
Address 0 khhhhhh ∗
2 Demand address k h h h h k h
Binary number 1 khhhhhk
(6 digits) ~
31 khkkkkk
1 unit khhhhhk
4
Number of units for
sequential starting k h h h k h h 2 units khhhhkh
3 units khhhhkk
5 Indoor forced fan H k h h h k h k
Normal operation khhhhhk ∗
Indoor forced fan H khhhhkh
6
Indoor forced
k h h h k k h
Normal operation khhhhhk ∗
operation Indoor forced operation khhhhkh
Low (“L” tap) khhhhhk
Normal (“M” tap) khhhhkh ∗
High khhhhkk
8 Te setting k h h k h h h High khhhkhh
High (“H” tap) khhhkhk
High khhhkkh
High khhhkkk
Low khhhhhk
9 Tc setting k h h k h h k Normal (factory setting) khhhhkh ∗
High khhhkhh
12 Demand setting k h h k k h h
Demand: NO khhhhhk ∗
Demand: YES khhhhkh
Address 0 khhhhhh ∗
13 AIRNET address k h h k k h k
Binary number 1 khhhhhk
(6 digits) ~
63 khkkkkk
Additional refrigerant
20 operation setting k h k h k h h
Refrigerant charging: OFF khhhhhk ∗
Refrigerant charging: ON khhhhkh
21 Refrigerant recovery k h k h k h k
Refrigerant recovery: OFF khhhhhk ∗
mode setting Refrigerant recovery: ON khhhhkh
26 Interlock
error
k h k k h k h
OFF khhhhhk ∗
display setting ON khhhhkh
28 Power
transistor
k h k k k h h
OFF khhhhhk ∗
check mode ON khhhhkh
60 % demand khhhhhk
30 Demand setting 1 k h k k k k h 70 % demand khhhhkh ∗
80 % demand khhhkhh
32 Continuous
demand
k k h h h h h
OFF khhhhhk ∗
setting ON khhhhkh
Emergency
operation OFF khhhhhk ∗
(Master unit with
38 multi outside unit k k h h k k h
system is inhibited to
operate.)
Master unit operation: Inhibited khhhhkh
k: ON h: OFF l: BLINK
Setting Item Setting Condition
No. C/H Selection Low LED Display
MODE TEST Demand
Setting Item Noise Contents
H1P H2P IND
H3P
Master
H4P
Slave
H5P H6P
H7P
∗ Factory setting
khhhhhk ∗
Emergency
operation OFF
39
(Sub unit 1 with multi
outside unit system k k h h k k k
is inhibited to
operate.)
Slave unit 1 operation:
Inhibited khhhhkh
khhhhhk ∗
Emergency
operation OFF
40
(Sub unit 2 with multi
outside unit system k k h k h h h
is inhibited to
operate.)
Slave unit 2 operation:
Inhibited khhhhkh
Press the SET button (BS2) and set 6 Number of connected BS units l h h h k k h
the LED display to a setting item.
7
Number of connected zone units
(excluding outside and BS unit) l h h h k k k
8 Number of outside units l h h k h h h
9 Number of connected BS units l h h k h h k Lower 4 digits:
upper (∗4)
Note:
∗1. The numbers in the "No." column represent the number of times to press the
∗ Press the MODE button (BS1) and
returns to “setting mode 1”. SET (BS2) button.
∗2. Display contents of “Various setting”
LED Display
H1P H2P H3P H4P H5P H6P H7P
Operation /backup operation ON l h h k h h h
setting
OFF l h h h h h h
Te setting L l h h h h h h
M l h h h h l h
H ~ l h h h h k h
Tc setting L l h h h h h h
M l h h h h h l
H l h h h h h k
Tc: High pressure equivalent saturation temperature
Te: Low pressure equivalent saturation temperature
∗3. Data such as addresses and number of units is expressed as binary numbers.
The No. 1 cool/heat unified address is expressed as a binary number consisting of the
lower 6 digits. (0 - 63)
(Example 1)
In (Example 1) the address is 010110 (binary number), which
translates to 16 + 4 + 2 = 22 (base 10 number). In other words, the
16 4 1
32 8 2 address is 22.
∗4. The number of connected BS units for No.9 and 10 / the number of terminal blocks for No.
12 and 13 is expressed as an 8-digit binary number, which is the combination of 4 upper,
and 4 lower digits respectively. (0 - 128)
(Example 2)
In (Example 2) the address for No. 12 is 0101, the address for No.
13 is 0110, and the combination of the 2 is 01010110 (binary
64 16 number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
No.12 128 32
number). In other words, the number of terminal block is 86.
4 1
No.13 8 2
(1) Set Cool / Heat Separately for Each Outside Unit System by Indoor Unit Remote Controller
z It does not matter whether or not there is outside - outside unit wiring.
z Set outside unit PCB DS1-1 to IN (factory setting).
z Set cool/heat switching to IND (individual) for “Setting mode 1” (factory setting).
IN I
Remote Remote
controller controller
(2) Set Cool/Heat Separately for Each Outside Unit System by Cool / Heat Selector
z It does not matter whether or not there is outside - outside unit wiring.
z Set outside unit PCB DS1-1 to OUT (factory setting).
z Set cool/heat switching to IND (individual) for “Setting mode 1” (factory setting).
DIP SW.
DS1-1 IN I
Remote Remote
controller controller
(3) Set Cool / Heat for more than Single Outside Unit System Simultaneously in Accordance with Unified
Master Outside Unit by Indoor Unit Remote Controller
z Install the external control adaptor for outside unit on either the outside-outside, indoor-
outside transmission line.
z Set outside unit PCB DS1-1 to IN (factory setting).
z In setting mode 1, set the outside unit you want to give cool/heat selection permission to as
the group master, and set the other outside units as group slave units.
z Set the outside unit external control adaptor SS1 to BOTH (factory setting) or C/H, and SS2
to OFF (factory setting).
z When multiple external control adaptors are used and cool/heat is selected for each external
control adaptor, use "setting mode 2" and set DS1 and DS2 on the external control adaptors
and the unified heat/cool address on the outside unit main PCB to the same address No.
(For details, refer to the following page.)
DEMAND
DEMAND
L.N.O.P.
MODE
L.N.O.P.
MODE
TEST
TEST
OFF ON
IN I IN I
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
CENTRAL TERMINAL
C/H NO. ADDRESS
L.N.O.P.
C/H SELECT
MODE
MODE
L.N.O.P.
C/H SELECT
Multi
Multi
TEST
TEST
IN I IN I
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
To indoor unit
(4) Set Cool/Heat for more than Single Outside Unit System Simultaneously in Accordance with Unified
Master Outside Unit by Cool / Heat Selector
z Install the external control adaptor for outside unit on either the outside-outside, indoor-
outside transmission line.
z Mount the COOL/HEAT selector to the master outside unit for the unified control.
Set the DS1-1 on the PCB of master outside unit to OUT.
z In setting mode 1, set the outside unit you want to give cool/heat selection permission to as
the group master, and set the other outside units as group slave units.
z When multiple external control adaptors are used and cool/heat is selected for each external
control adaptor, use "setting mode 2" and set DS1 and DS2 on the external control adaptors
and the unified heat/cool address on the outside unit main PCB to the same address No.
(For details, refer to the following page.)
DEMAND
DEMAND
L.N.O.P.
MODE
L.N.O.P.
MODE
TEST
TEST
OFF ON
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
CENTRAL TERMINAL
C/H NO. ADDRESS
Cool/Heat
selector To indoor unit To indoor unit
L.N.O.P.
C/H SELECT
L.N.O.P.
MODE
MODE
C/H SELECT
Multi
Multi
TEST
TEST
IN I IN I
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
To indoor unit
Address setting for (3) and (4) (Set lower 5 digits with binary number.) [No.0 to No.31]
Address Outside unit PCB LED External control adaptor for outside unit
No. Set with setting mode 2 DS2 DS1
No 0 kh hhhhh
0 0
No 1 kh hhhhk
1 1
No 2 kh hhhkh
2 2
No 3 kh hhhkk
3 3
No 4 kh hhkhh
4 4
~
No 30 kh kkkkh
30 30
No 31 kh kkkkk
31 31
(5) Set cool/heat at all outside unit systems simultaneously for each outside unit external control adaptor
by using the centralized remote controller.
z Install the outside unit external control adaptor (optional accessory) onto the outside-outside,
indoor-outside, or indoor-indoor transmission line.
z Use "setting mode 1" and set all outside units to SLAVE.
z Set the outside unit external control adaptor SS1 to BOTH (factory setting) or C/H and set SS2 to ON.
z Use "setting mode 2" and set DS1 and DS2 on the outside unit external control adaptors and
the unified heat/cool address on the outside unit main PCB to the same address. (The
factory setting addresses are all "0".)
L.N.O.P.
DEMAND
L.N.O.P.
DEMAND
MODE
L.N.O.P.
DEMAND
MODE
C/H SELECT
TEST
C/H SELECT
TEST
MODE
C/H SELECT
TEST
for outside unit CENTRAL IND IND MASTER SLAVE IND MASTER SLAVE
C/H
MASTER SLAVE
SELECTOR
OFF ON
IN I IN I IN I
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
CENTRAL TERMINAL
C/H ADDRESS
NO.
L.N.O.P.
DEMAND
DEMAND
MODE
L.N.O.P.
C/H SELECT
MODE
TEST
C/H SELECT
TEST
OFF ON
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
DEMAND
DEMAND
L.N.O.P.
MODE
C/H SELECT
MODE
TEST
C/H SELECT
TEST
OFF ON
IN I IN I
C/H SELECTOR I-O O-O OUT-MULTI C/H SELECTOR I-O O-O OUT-MULTI
CENTRAL TERMINAL
C/H NO. ADDRESS
Setting of Address
In binary, set the address number (middle 2 digits) and terminal No. (last 3 digits) of the external
control adaptor (DIP switches) and outside unit main PCB (LED lamps).
Address Terminal External control adaptor for outside unit Outside unit main PCB LED
No. No. DS2 DS1 Set with setting mode 2
Central Terminal
No. 0 No. 0 kh hh hhh
0 0 0 0
No. 0 No. 1 kh hh hhk
0 1 0 1
No. 0 No. 2 kh hh hkh
0 2 0 2
No. 0 No. 3 kh hh hkk
0 3 0 3
~
~
~
No. 2 No. 5 kh kh khk
2 5 2 5
~
~
No. 3 No. 6 kh kk kkh
3 6 3 6
No. 3 No. 7 kh kk kkk
3 7 3 7
as same
as same
k ON h OFF
Upper Lower
(ON) (OFF)
(part shows knob)
COOL/HEAT selector
Note: • This setting is read into the micro-computer when turning ON the power supply.
• Be sure to make the setting before turning ON the power supply.
• Be sure to close the El. compo. box lid after setting.
In case of the indoor unit connect as the cool only unit, it wire
the terminal F1 F2 of the last BS unit.
OUT/D.BS
F1 F2 F1 F2
IN/D OUT/D.BS
F1 F2 F1 F2
Final BS unit
1st unit Final unit
To the indoor unit where
the selection of heating Cooling Only
and cooling is available.
CONTROLLER
CONTROLLER
A A A
REMOTE
REMOTE
REMOTE
F1 F2 F1 F2 B F1 F2 F1 F2 B F1 F2 F1 F2 B
IN/D OUT/D.BS C IN/D OUT/D.BS C IN/D OUT/D.BS C
Demand 2 The compressor operates at Short circuit "2" and "C". Set item No. 32 to "Demand 2".
approx. 40% or less of rating.
Demand 3 Forced thermostat OFF. Short circuit "3" and "C".
*: However the demand operation does not occur in the following operation modes.
Startup control Oil return operation
Defrosting operation Pump down residual operation
If carrying out demand input, connect the adaptor’s terminals as shown below.
F1 X
F2 X
P3 X
P4 X
External control X X X X X X
adaptor for 1 2 3 C Low
outside unit Demand noise
A. When the demand operation is carried out by external contact (with the use of the
external control adaptor for outside unit).
1. Connect external control adaptor for outside unit and short-circuit terminals as required
(Refer above figure).
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of demand
operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the normal demand operation is carried out. (Use of the external control
adaptor for outside unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of alternate demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Setting mode indication section Setting No. indication section Set contents indication section
Additional
charge Turn OFF the power.
without
compressor
operation Charge through service port of
liquid stop valve.
YES
Is all refrigerant charged?
NO
Open discharge gas, liquid,
suction gas stop valve.
YES
Is all refrigerant charged? Open liquid stop valve.
NO
Note: ∗ The stop valve operations are different from Heat Pump and Heat Recovery connection, refer
to following page for detail.
Caution Refrigerant cannot be charged until field wiring has been completed.
Refrigerant may only be charged after performing the leak test and the vacuum drying.
When charging a system, care shall be taken that its maximum permissible charge is never
exceeded, in view of the danger of liquid hammer.
Charging with an unsuitable substance may cause explosions and accidents, so always ensure
that the appropriate refrigerant (R-410A) is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when charging refrigerant.
This outside unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Determine the amount of refrigerant to be added by referring to the table, write it down on
the included “Added Refrigerant” plate and attach it to the rear side of the front cover.
Note: refer to the example of connection for the amount to be added.
Additional refrigerant charge procedure (1)-normally
Charge the refrigerant to the liquid pipe in its liquid state. Since R-410A is a mixed
refrigerant, its composition changes if charged in a state of gas and normal system operation
would no longer be assured.
Make sure to use installation tools you exclusively use on R-410A installations to withstand
the pressure and to prevent foreign materials from mixing into the system.
1. Before charging, check whether the tank has a siphon attached or not.
How to charge with a siphon attached tank.
Charge with the tank upright.
There is a siphon tube
inside, so there is no need
to turn the tank upside-down.
2. After the vacuum drying is finished, charge the additional refrigerant in its liquid state
through the liquid stop valve service port.
Taking into account following instructions:
Check that gas and liquid stop valves are closed.
Stop the compressor and charge the specified weight of refrigerant.
(If the outside unit is not in operation and the total amount cannot be charged, follow the
Additional refrigerant charge procedure (2) shown next page.)
R-410A
Valve A
Refrigerant
Nitrogen
tank
With
a siphon
R-410A
Valve A
Refrigerant
tank
Nitrogen
With
a siphon
Valve B
Stop valve service port
To indoor
units / BS units
Measuring instrument
Vacuum pump Dotted lines represent
onsite piping
Shaft
Hexagon hole
Cap
The main
body seal
Service port
Remove the cap and turn Never remove Remove the cap and turn
the valve counter clockwise the partition flange the valve counter clockwise
with the hexagon wrenches for any reason. with the hexagon wrenches
until it stops. until it stops.
Discharge Discharge
gas side Liquid side gas side Liquid side
Full close on
the suction gas Suction
gas side Suction
side gas side
[Operation state]
• Compressor frequency : Normal cooling PI control, upper limit 177Hz
• Y5S, Y7S, four way valve: OFF Y1E, electronic expansion valve: Normal cooling control
• Indoor unit electronic expansion valve (All unit): 1024 pulse Y3E: 0 pls
• Indoor unit fan: H tap
[Operation procedure]
(1) In setting mode 2 with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective electronic expansion valve of indoor and outside units are fully
opened. (H2P turns to display “TEST OPERATION” (blinks), “TEST OPERATION” and “IN
CENTRALIZED CONTROL” are displayed on the remote controller, and the operation is
prohibited.
(2) Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detail.)
(3) Press Mode button “BS1” once and reset “Setting Mode 2”.
[Operating procedure]
(1) With Setting Mode 2 while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to
ON. The electronic expansion valves of indoor and outside units fully open and some of
solenoid valves open.
(H2P blinks to indicate the test operation, and the remote controller displays "Test
Operation" and "In Centralized control", thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
(2) Use the vacuum pump to perform vacuuming operation.
(3) Press Mode button “BS1” once and reset “Setting Mode 2”.
3~5 minutes
Step 3 Stability waiting operation
10 minutes
Step4~6 Judgement function
• Stop valve close check
• Wrong wiring check
• Refrigerant over change check
• Piping length check
3 minutes
Completion
: Normal completion
: Abnormal completion
Note: Be sure to disconnect the compressor wiring when conducting the check operation mentioned
above.
When the output voltage is approx. 100~200 V (10 Hz) and the voltage balance between
phases U-V, V-W, W-U is within ±5%, the inverter PCB is normal.
4. Emergency Operation
If the compressor cannot operate, this control inhibits any applicable compressor or outside unit
from operating to perform emergency operation only with the operative compressor or outside
unit.
Caution
"For making a compressor unable to operate due to error, etc., be sure to conduct the
work with emergency operation setting.
Never execute work such as disconnection of the power cable from magnet contact
switch.
(Otherwise, other normal compressors may be defective.)
∗ Because the units will be operated in the combination with which oil pressure
equalization between compressors cannot be performed.
Note : Reset the power supply during the outside unit is stopping to cancel the
automatic backup operation forcibly.
Part 6
Service Diagnosis
1. Symptom-based Troubleshooting .......................................................128
2. Troubleshooting by Remote Controller ...............................................131
2.1 The INSPECTION / TEST Button.........................................................131
2.2 Procedure of Self-diagnosis by Remote Controller ..............................131
2.3 Error Codes and Description ................................................................135
2.4 Error Code Indication by Outside Unit PCB .........................................137
2.5 Error of External Protection Device ......................................................139
2.6 PCB Abnormality ..................................................................................140
2.7 Drain Level Control System (S1L) Abnormality....................................141
2.8 Fan Motor Lock, Overload....................................................................143
2.9 Abnormal Indoor Fan Motor .................................................................144
2.10 Swing Flap Motor Abnormality .............................................................150
2.11 Abnormal Power Supply Voltage..........................................................152
2.12 Electronic Expansion Valve Coil Abnormality / Dust Clogging .............153
2.13 Electronic Expansion Valve Coil Abnormality.......................................155
2.14 Drain Level above Limit........................................................................157
2.15 Capacity Determination Device Abnormality ........................................158
2.16 Transmission Error (between Indoor Unit PCB and Fan PCB) ............159
2.17 Thermistor Abnormality ........................................................................161
2.18 Combination Error (between Indoor Unit PCB and Fan PCB)..............162
2.19 Thermistor Abnormality ........................................................................163
2.20 Humidity Sensor System Abnormality ..................................................164
2.21 Abnormal Room Temperature Thermistor in Remote Controller..........165
2.22 PCB Abnormality ..................................................................................166
2.23 Earth Leakage by Leak Detection PCB Assy .......................................167
2.24 High Pressure Abnormality
(Detected by the High Pressure Switch) ..............................................169
2.25 Actuation of Low Pressure Sensor .......................................................172
2.26 Inverter Compressor Motor Lock..........................................................174
2.27 Electronic Expansion Valve Coil Abnormality.......................................176
2.28 Discharge Pipe Temperature Abnormality ...........................................178
2.29 Refrigerant Overcharged......................................................................180
2.30 Water System Abnormality...................................................................182
2.31 Thermistor System Abnormality ...........................................................184
2.32 High Pressure Sensor Abnormality ......................................................185
2.33 Low Pressure Sensor Abnormality .......................................................187
2.34 Inverter Radiation Fin Temperature Rise Abnormality .........................189
2.35 Momentary Overcurrent of Inverter Compressor..................................190
2.36 Overcurrent Abnormality of Inverter Compressor.................................192
2.37 Inverter Compressor Startup Error .......................................................194
2.38 Transmission Error (between Inverter and Main PCB).........................196
2.39 Inverter Over-Ripple Protection............................................................198
2.40 Inverter Radiation Fin Thermistor Abnormality.....................................200
2.41 Defective Field Setting after Replacing Main PCB or
Defective Combination of PCB.............................................................201
1. Symptom-based Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start operation at all. Blowout of fuse(s) Turn OFF the power supply and
then replace the fuse(s).
Cutout of breaker(s) • If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
ON
Knob
Tripped
OFF
Circuit breaker
Normal
mode
Press INSPECTION/TEST Operation button
Press INSPECTION/TEST Operation
once.
button once.
Or after 30 minutes
After 10 seconds
ON/OFF button
Error code
INSPECTION/TEST button
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in service mode, holding down the ON/OFF button for a period of 5 seconds or more will clear the
error history indication shown above. In this case, on the codes display, the error code will blink twice and
then change to “00” (= Normal), the Unit No. will change to “0”, and the operation mode will automatically
switch from service mode to normal mode (displaying the set temperature).
Operation lamp
Error code
Applicable
model names
The upper digit of the code changes as shown below when the UP and DOWN
buttons are pressed.
Normal status
Enters inspection mode from
normal status when the INSPECTION/
TEST button is pressed.
If no button is pressed
for 1 minute, equipment
returns to normal status.
3
Press
MODE
When MODE selector selector
button is pressed or button.
no button is pressed
for 1 minute, equipment
returns to normal status.
If no button is pressed
for 1 minute, equipment
returns to normal status.
Page
Error code Contents of Error Referred
System U0 Refrigerant shortage alert 202
U1 Reverse phase, open phase 204
U2 Power supply insufficient or instantaneous failure 205
U3 Check operation is not executed 207
U4 Transmission error (between indoor and outside units) 208
U5 Transmission error (between remote controller and indoor unit) 210
U7 Transmission error (between outside units) 211
U8 Transmission error (between main and sub remote controllers) 217
U9 Transmission error (between indoor and outside units in the same system) 218
UA Improper combination of indoor, BS and outside units 219
UC Address duplication of centralized control equipment 224
UE Transmission error (between centralized control equipment and indoor unit) 225
UF System is not set yet 228
UH System error, refrigerant system address undefined 229
The system operates for error codes indicated in black squares, however, be sure to check and repair.
Method of Error Detect open or short circuit between external input terminals in indoor unit.
Detection
Error Decision When an open circuit occurs between external input terminals with the remote controller set to
Conditions "external ON/OFF terminal".
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
External
protection device is
connected to terminals T1 YES
and T2 of the indoor unit Actuation of external protection
terminal block. device.
NO
ON/OFF
input from
outside (mode No.
12, first code No. 1) has YES
been set to external Change the second code No. to
protection device input "01" or "02" .
(second code No.
03) by remote
controller.
NO
Replace the indoor unit PCB.
Error Decision When data could not be correctly received from the E²PROM
Conditions E²PROM: Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned OFF.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Applicable FXFQ, FXZQ, FXCQ, FXKQ, FXDQ, FXMQ, FXHQ (Option), FXMQ200·250MA (Option),
Models FXAQ (Option)
Error Decision When rise of water level is not a condition and the float switch goes OFF
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float
switch contact Becomes
is forming a short YES normal when X8A NO
circuit. (continuity check or X15A of the indoor unit Replace the indoor unit PCB.
with X8A or X15A PCB is short
disconnected) circuited.
NO YES
Loose the connection of
connector.
The drain
pump is connected NO
to X25A or terminals Y1 Connect the drain pump and
and Y2 of the indoor turn ON again.
unit PCB.
YES
The
drain pump YES
works when the power Check the drain piping for
supply is reset for the clogging or upward slope, etc.
indoor unit.
NO
The
voltage of
terminals Y1
and Y2 or X25A is NO
220~240 V (within 5 Replace the indoor unit PCB.
minutes of resetting
the power
supply).
YES
Method of Error This error is detected if there is no revolutions detection signal output from the fan motor.
Detection
Error Decision When no revolutions can be detected even at the maximum output voltage to the fan
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
wiring from the fan
motor securely connected to NO
connectors X4A and X27A on Connect the connector correctly.
the indoor unit (At this time, check for any
PCB? defective connector contact or
broken wires.)
YES
NO
Replace the indoor unit PCB.
Method of Error Detection of abnormal fan revolutions with the signal from the fan motor.
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
Are the
harness from the fan
motor and the harness of NO
Connect properly.
A1P fan motor (fixed to
X20A) connected
properly?
YES
YES
Does
the resistance
NO
between pins satisfy the Replace the fan motor.
judgement
criteria?
YES
Are
high-power PCB
NO
(A1P) and low-power PCB Connect properly.
(A2P) connected
properly?
YES
Replace the indoor unit PCB.
Red U
Black W
2.9.2 FXMQ50~140P
Remote A6
Controller
Display
Applicable FXMQ50~140P
Models
Method of Error Detection from the current flow on the fan PCB.
Detection Detection from the RPM of the fan motor in operation.
Detection from the position signal of the fan motor.
Detection from the current flow on the fan PCB when the fan motor starting operation.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
There is
a foreign matter YES
Remove the foreign matter.
around the fan.
NO
The fan
motor connectors (X1A YES
and X2A) of the fan PCB (A2P) are Connect correctly.
disconnected.
NO
The connectors
between the indoor unit YES
PCB (A1P) and the fan PCB Connect correctly.
(A2P) are
disconnected.
NO
The fuse
(F3U, white) on the NO
fan PCB (A2P) has no Replace the fan
continuity. PCB (A2P).
YES
The fan
can be moved
lightly by hand after the fan NO
motor connector of the fan Replace the fan motor.
PCB (A2P) is
removed.
YES
The
resistance between
the power supply wire YES
terminals of the fan motor and motor Replace the fan motor.
frame (metal part) is 1 MΩ
or below.
NO
A
resistance
The
resistors among U, V, YES
and W are unbalanced or short- Replace the fan motor.
circuited.
NO
Between
VCC and GND YES
terminals, and between GND and Replace the fan motor.
HW, HV, or HU terminals are
short-circuited.
NO
The HAP
lamp of the indoor
unit PCB (A1P) blinks and YES
Replace the fan PCB
the HAP lamp of the fan (A2P).
PCB (A2P) is
OFF.
NO
Replace the fan motor.
4 4 Pink Vcc
3 White V 3 Orange Hw
2 2 Blue HV
1 Black W 1 Yellow HU
R ed
<FXMQ50~140PVE>
Measuring P oints J udgement
White
B lack - R ed 3.5ǡr
B lack - White 3.5ǡr
B lack
Si30-813_A Troubleshooting by Remote Controller
Method of Error Utilizes ON/OFF of the limit switch when the motor turns.
Detection
Error Decision When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing
Conditions flap motor is energized for a specified amount of time (about 30 seconds).
∗ Error code is displayed but the system operates continuously.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
Indoor
unit is a model NO
equipped with a swing Replace the indoor unit PCB.
flap function
YES
The limit NO
switch functions Replace the swing motor.
normally.
YES
YES
When
the airflow
direction flap-cam
mechanism is NO
disconnected from the swing Replace the swing motor.
motor, operation is
normal when
turned ON
again.
YES
Take the cam mechanism
apart, reassemble and turn ON
again.
Applicable FXMQ20-140P
Models
Method of Error The error is detected by checking the input voltage of fan motor.
Detection
Error Decision When the input voltage of fan motor is 150V or less, or 386V or more.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check the condition of the
power supply.
Check if power supply
voltage is 220V - 240V
± 10%.
Check if there is power
open phase or defective
wiring.
Check if power supply
voltage unbalance is
within 6V.
There are
problems on the YES
condition of power supply Correct any fault.
described above.
NO
YES
Error is displayed again? Check and correct each wiring.
NO
Applicable FXFQ
Models
Method of Error Check the coil condition of electronic expansion valve by using micro-computer.
Detection Check the dust clogging condition of electronic expansion valve main body by using micro-
computer.
Error Decision Pin input for electronic expansion valve coil is abnormal when initializing micro-computer.
Conditions Either of the following conditions is seen/caused/ occurs while the unit stops operation.
z Temperature of suction air (R1T) – temperature of liquid pipe of heat exchanger (R2T) >
8°C.
z Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Troubleshooting
NO
When power is supplied. Replace the electronic expansion
valve main body.
YES
Electronic
expansion valve is NO
connected to X7A Shut the power supply OFF after
of indoor unit connection and then restart.
PCB.
YES
Check (∗1) of
electronic expansion NO
Replace the electronic expansion
valve coil indicates valve coil.
normal.
YES
NO
When restarting the operation after
shutting the power supply OFF
does not work, replace the indoor
unit PCB.
1) White
Method of Error Use a micro-computer to check the electronic expansion valve for coil conditions.
Detection
Error Decision When the pin input of the electronic expansion valve is not normal while in the initialization of
Conditions the micro-computer.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
electronic
expansion valve is NO
connected to X7A of After connecting, turn OFF the
the indoor unit power supply and then turn the
PCB. power ON.
YES
Normal when
(∗1) the electronic NO
expansion valve coil is Replace the electronic expansion
checked. valve coil.
YES
NO
If you turn OFF the power supply
and turn ON again, and it still does
not help, replace the indoor unit
PCB.
Note: ∗1: Coil check method for the electronic expansion valve
Discount the electronic expansion valve from the PCB and check the continuity between the
connector pins.
(Normal)
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × { × { ×
Approx. Approx.
300Ω 150Ω
2. Yellow × { × {
Approx. Approx.
300Ω 150Ω
3. Orange × { ×
Approx.
150Ω
4. Blue × {
Approx.
150Ω
5. Red ×
6. Brown
{: Continuity
× : No continuity
1 White
Applicable FXFQ, FXZQ, FXCQ, FXKQ, FXDQ, FXMQ-P, FXMQ-MA, FXHQ, FXAQ, FXUQ
Models
Method of Error Water leakage is detected based on float switch ON/OFF operation while the compressor is in
Detection non-operation.
Error Decision When the float switch changes from ON to OFF while the compressor is in non-operation
Conditions ∗ Error code is displayed but the system operates continuously.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Field drain
piping has a defect such YES
Modify the drain piping.
as upward sloping.
NO
A humidifier
unit (optional YES
accessory) is installed Check if the humidifier unit is
on the indoor leaking.
unit.
NO
Replace the indoor unit PCB.
Method of Error Capacity is determined according to resistance of the capacity setting adaptor and the memory
Detection inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Error Decision When the capacity code is not saved to the PCB, and the capacity setting adaptor is not
Conditions connected
When a capacity that does not exist for that unit is set.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
indoor unit PCB was NO
replaced with a spare Replace the indoor unit PCB.
PCB.
YES
The
capacity
setting adaptor need NO
to be installed when Replace the indoor unit PCB.
replacing the PCB.
YES
Install a capacity setting adaptor.
Applicable FXMQ20~140P
Models
Method of Error Check the condition of transmission between indoor unit PCB (A1P) and fan PCB (A2P) using
Detection micro-computer.
Error Decision When normal transmission is not carried out for certain amount of time.
Conditions
Supposed Connection error of the connecter between indoor unit PCB (A1P) and fan PCB (A2P)
Causes Defective indoor unit PCB (A1P)
Defective fan PCB (A2P)
External factor, such as instantaneous power failure
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
connector
between indoor unit NO
PCB (A1P) and fan PCB Connect the connector accurately.
(A2P) accurately
connected?
(∗1)
YES
Under
above field setting NO
mode, second code No. is Replace the indoor unit PCB (A1P).
"01".
YES
Error is YES
displayed again? Replace the fan PCB (A2P).
NO
Note: ∗1: Pull out and insert the connecter once and check it is accurately connected.
∗2: Method to check transmission part of indoor unit PCB.
(1) Turn OFF the power and remove the connecter X70A of indoor unit PCB (A1P).
(2) Short circuit X70A.
(3) After turning ON the power, check below numbers under field setting remote control.
(Confirmation: Second code No. at the condition of first code No. 21 on mode No. 41)
↓
Determination 01: Normal
Other than 01: Transmission defect on indoor unit PCB
∗ After confirmation, turn OFF the power, take off the short circuit and connect X70A back to
original condition.
Error Decision When the thermistor becomes disconnected or shorted while the unit is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the YES
thermistor normal? Normal (The error is caused by
defective contact.)
NO
CHECK 11 NO
5 kΩ to 90 kΩ Replace the thermistor (∗1).
YES
Replace the indoor unit PCB.
Applicable FXMQ20~140P
Models
Method of Error Check the condition of transmission with fan PCB (A2P) using indoor unit PCB (A1P).
Detection
Error Decision When the communication data of fan PCB (A2P) is determined as incorrect
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the type of NO
fan PCB (A2P) correct? Replace it with the correct fan
PCB (A2P).
YES
YES
Was
the correct
capacity setting NO
adaptor installed when Install the correct capacity
replacing it with a setting adaptor.
spare PCB?
YES
After establishing
transmission for indoor and
outside, diagnose the
operation again.
Applicable FXMQ20~140P
Models
Error Decision When the thermistor becomes disconnected or shorted while the unit is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the YES
thermistor normal? Normal (The error is caused by
defective contact.)
NO
CHECK 11 NO
Replace the thermistor (∗1).
5 kΩ to 90 kΩ
YES
Replace the indoor unit PCB.
Applicable FXFQ
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
Is "CC" displayed
YES
on the remote Replace the humidity sensor
controller? (∗2) PCB (A2P).
(∗3)
NO
Note: ∗1: To delete the history, the ON/OFF button of the remote controller must be pressed and
held for 5 seconds in the check mode.
∗2: To display the code, the Inspection/Test Operation button of the remote controller must be
pressed and held in the normal mode.
∗3: If "CC" is displayed even after replacing the humidity sensor PCB assy (A2P) and taking the
steps ∗1 and 2, replace the indoor unit PCB assy (A1P).
Method of Error The error is detected by temperature detected by room temperature thermistor in remote
Detection controller. (∗1)
Error Decision When the room temperature thermistor in remote controller becomes disconnected or shorted
Conditions while the unit is running
∗ Error code is displayed but the system operates continuously.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Error is YES
displayed again? Replace the remote
controller.
NO
External factor (Noise, etc.)
Note: ∗1: In case of room temperature thermistor in remote controller error, unit is still operable by
suction air thermistor on indoor unit.
Method of Error Abnormality is detected under the communication conditions in the hardware section between
Detection the indoor unit and outside unit.
Error Decision When communication conditions in the hardware section between the indoor unit and heat
Conditions source unit is abnormal
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Does it return normally? Check the following parts and
continue operation
• Check noise, etc.
NO • Check whether foreign
particles attach to the terminal
of the main PCB (X1M).
Foreign
particles are attached YES
Remove the foreign particles
on the terminal (X1M) of and restart operation.
the main PCB.
NO
Replace the outside unit
main PCB.
Error Decision Leakage is detected under the conditions outside of the scope of high pressure sensor
Conditions operation.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check for
power supply voltage. NO
Voltage between phases: Onsite causes.
380 to 415V Make proper wire
connections without open
YES
phase, erroneous
Check connections, or erroneous
for any wiring order of phases.
errors in the R-, S-, and T- Wiring error
phase electric wiring in the outside Correct the connection at
unit power (including the location of the wiring
auxiliary power).
error.
Check
the compressor for Insulation fault
insulation using a megger Replace the defective part.
tester.
Check the
whole product for Insulation fault
insulation resistance using a Replace the defective part.
megger tester.
Check the
connectors of the high Disconnected
pressure sensor line for any Securely connect the
disconnection. connectors.
Check the
earth leakage detection YES
PCB (A4P) for any broken Replace the earth leakage
wire in it. detection PCB (A4P).
NO
Reinstall all wirings.
Check
whether there is
continuity between both X3A No continuity *1
ends of the earth leakage
Replace the earth leakage
detection PCB detection PCB (A4P).
(A4P).
Check whether
there is continuity between both No continuity
ends of high pressure
Replace the high pressure
switch. switch.
Normal
It is supposed that ground leakage occurs due to temporary liquid back or accumulation of refrigerant.
This phenomenon can occur when power fails while in operation or is cut off for an extended period of time.
*1: It is normal that there is no continuity between both ends of X3A when the power supply turns OFF and for
a period of 9 seconds at maximum after the power supply turns ON.
Method of Error The error is detected by the protection device circuit that detects continuity at high pressure
Detection switch.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the 3 NO
points above OK? Rectify the defective points, if
any.
YES
• Mount a pressure gauge on the high pressure service port.
• Connect the Service Checker.
• Reset the operation using the remote controller, and then
restart the operation.
Is the
Does the
YES high pressure NO
emergency stop due
switch operating value Replace the high pressure
to error "E3" recur?
(4.0 MPa) switch.
normal?
NO YES
Are the
characteristics
of the high pressure NO
Replace the high pressure sensor.
sensor normal?
(∗1)
YES
SERVICE CHECKER
Connect the service checker to compare the "high pressure" value and the
actual measurement value by pressure sensor (∗2) by using the service
checker.
Are the
"high pressure"
value and the actual NO
measurement value by Replace the outside unit main
pressure sensor PCB.
the same?
YES
• The high pressure sensor is normal and the pressure detected with the
main PCB is also normal.
• The high pressure or field piping pressure has really become high.
CHECK 1 : Remove the causes by which the high pressure or field piping
pressure has become high.
Note: ∗1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge. (As to the voltage of the pressure sensor, make measurement of voltage at
the connector and then convert it pressure.)
∗2: Make measurement of voltage of the pressure sensor.
+5V Connector for high
pressure sensor (red)
(3) Black
(2)
Micro-computer
(1) White
A/D input
Method of Error Judge the pressure detected by a low pressure sensor with the outside unit main PCB.
Detection
Error Decision When low pressure drops while the compressor is in operation
Conditions Operation pressure: 0.07 MPa
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Mount a pressure gauge on the low pressure
service port.
Reset the operation using the remote controller,
and then restart the operation.
Are the
characteristics NO
of the low pressure Replace the low pressure sensor.
sensor normal?
(∗1)
YES
SERVICE CHECKER
Connect the service checker to compare the "low pressure" value and the
actual measurement value by pressure sensor (∗2) by using the service
checker.
Are
the "low
pressure" value
and the actual NO
measurement valve by Replace the outside unit
pressure sensor main PCB.
the same?
YES
• The low pressure sensor is normal and the pressure detected with the
main PCB is also normal.
• The low pressure has really become low.
CHECK 2 : Remove the causes by which the low pressure has become low.
Note: ∗1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector
and then convert it pressure.)
∗2: Make measurement of voltage of the pressure sensor.
(4) Red
(3) Black
Micro-computer
A/D input (2) White
(1)
Method of Error Inverter PCB takes the position signal from UVW line connected between the inverter and
Detection compressor, and the error is detected when any abnormality is observed in the phase-current
waveform.
Error Decision This error will be output when the inverter compressor motor does not startup even in forced
Conditions startup mode.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the connection NO
of UVW phase order Ensure correct connection.
correct? W
YES U
Power OFF
Is the wiring NO V
the same as in the electric Ensure correct connection.
wiring diagram? Check if the wiring has
any error in mistake for
YES inverter compressor.
The insulation
resistance of the compressor is YES
low (not more than 100kW). Replace the compressor.
NO
The
compressor coil has YES
disconnection of wires.
NO
Restart and
check the operation. Check NO
if the condition occurs again. Conclude the work
There is a possibility of defective
pressure equalizing.
YES Check the refrigerant circuit.
Power ON
Is the
start mode in the YES
high differential pressure Defective of pressure equalizing
(not less than 0.5 Check the refrigerant circuit.
MPa)?
NO
CHECK 4 NO
Power OFF Is the power transistor Replace the inverter PCB (A2P).
normal?
YES
Restart
Power ON and check if the NO
error occurs again. Continue the operation.
(There is a possibility of
instantaneous power failure etc.)
YES
Power OFF Replace the inverter PCB
(A2P).
Restart
and check if the NO
Power ON error occurs again. Continue the operation.
YES
Replace the inverter compressor.
+ The inverter PCB is not
defective.
Return the inverter PCB to
original position.
Method of Error Check the continuity of electronic expansion valve coil (Y1E)
Detection
Error Decision No current is detected in the common (COM [+]) when the power supply is ON.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Return to normal? External factor (Noise, etc.)
NO
Check the electronic expansion valve corresponding to the error code “E9” in the monitor mode.
{ When confirmation of error 3 shows as follows:
→ Electronic expansion valve for main (Y1E)
{ When confirmation of error 3 shows as follows:
→ Electronic expansion valve for subcooling (Y3E)
{ Explanation of “ ” Master unit
Slave unit 1
Slave unit 2
System
The connector of
outside unit PCB (A1P) for NO
Ensure correct connection.
electronic expansion valve
is connected.
YES
YES
Replace the outside unit PCB
(A1P).
Note: ∗1: Make measurement of resistance between the connector pins, and then make sure the
resistance falls in the range of 40 to 50Ω.
1 Orange
2 Red
Measuring points Judgement criteria
3 Yellow 1-6
2-6
4 Black 40~50Ω
3-6
5 4-6
COM[+] 6 Gray
Method of Error The error is detected according to the temperature detected by the discharge pipe temperature
Detection sensor.
Error Decision When the discharge pipe temperature rises to an abnormally high level (135°C or more)
Conditions When the discharge pipe temperature rises suddenly (120°C or more continues 10 minutes)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the discharge NO
pipe thermistor Replace the discharge pipe
property normal? thermistor.
(∗1)
YES
Service Checker
Connect the service checker to compare the
temperature of discharge pipe by using service
checker with actual measurement value of discharge
pipe thermistor. CHECK 11
Is the temperature
of discharge pipe by
using service NO
checker same with Replace the outside unit
actual measurement main PCB (A1P).
value of discharge
pipe thermistor?
YES
Note: ∗1: Compare the resistance value of discharge pipe thermistor and the value based on the
surface thermometer.
Method of Error The error is detected according to the temperature detected by the discharge pipe temperature
Detection during check operation
Error Decision When the discharge pipe temperature drops during check operation
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the thermistor NO
mounted properly? Mount the thermistor properly
before operation.
YES
Is it normal? NO
Replace the thermistor if it
CHECK 11 functions abnormally before
operation.
YES
NO
Error is displayed Continue the operation.
again?
YES
There is a possibility that there are other causes of
refrigerant overfilling.
Method of Error Detect abnormalities using the thermistor on the heat exchanger gas side.
Detection Detect turned OFF interlock circuit.
(When interlock setting is provided.)
Error Decision When temperature on the heat exchanger gas side (R4T) drops remarkably with the
Conditions minimum operation step (52 Hz) of the compressor
With interlock setting provided, when interlock circuit is turned OFF
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Clogged
water piping
system (mixing in of YES
Remove the clog.
foreign matters, solenoid
valve for water
use)
NO
Is the
amount of water
NO
of heat exchanger 50 l/ Secure the enough water.
minute or more?
YES
NO
Is the
connection
between the
thermistor on the heat NO
exchanger gas side (R4T) and Connect the connector properly.
the low pressure sensor
(S1NPL)
proper?
YES
Are
characteristics
of the thermistor on
the heat exchanger gas side NO
(R4T) and the low pressure sensor Replace the thermistor/sensor if
(S1NPL) normal? any of its characteristics are
CHECK 11 abnormal.
YES
NO
The
power transistor is
NO
normal? Replace the inverter PCB
CHECK 4 concerned.
YES
Connect the relay cable to the
compressor, and the restart
the operation.
Error is displayed NO
again? Continue the operation.
YES
Replace the outside unit
main PCB.
Method of Error The error is detected according to the temperature detected by each individual thermistor.
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO Connect correctly.
Is it normal?
YES
YES
Method of Error The error is detected from the pressure detected by the high pressure sensor.
Detection
Error Decision When the high pressure sensor is short-circuit or open circuit
Conditions (Not less than 4.22MPa or 0.01MPa or less)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
characteristics of
the high pressure
sensor normal? (Make a NO
comparison between the Replace the high pressure sensor.
voltage characteristics
(∗1) and the gauge
pressure.)
YES
If the
PCB
pressure detection
normal? (Make a
comparison between the NO
Replace the outside unit PCB.
checker pressure data and
the voltage
characteristics
(∗1).)
YES
Reset the operation, and then
restart the outside unit.
Are the
characteristics of the NO
Replace the high pressure sensor.
high pressure sensor
normal?
YES Replace the outside unit PCB.
X32A
High pressure sensor
(4) Red
(2)
Method of Error The error is detected from pressure detected by low pressure sensor.
Detection
Error Decision When the low pressure sensor is short circuit or open circuit
Conditions (Not less than 1.77MPa or -0.01MPa or less)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
characteristics of
the low pressure
sensor normal? (Make a NO
Replace the low pressure sensor.
comparison between the
voltage characteristics
(∗1) and the gauge
pressure.)
YES
If
the PCB
pressure
detection normal?
(Make a comparison NO
between the checker Replace the outside unit PCB.
pressure data and the
voltage
characteristics
(∗1).)
YES
Reset the operation, and then
restart the outside unit.
Are the
characteristics of the NO
Replace the low pressure sensor.
low pressure sensor
normal?
YES Replace the outside unit PCB.
X45A
Low pressure sensor
(4) Red
Error Decision When the temperature of the inverter radiation fin increases above 87°C
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The radiation
fin of the inverter PCB YES
concerned exceeded Defective radiation from the power unit
a temperature of • Blocked air suction port
87°C. • Stained radiation fin
• High outdoor air temperature
NO
Turn OFF the power supply,
and then make measurement
of resistance of the radiation
fin thermistor.
Is the thermistor NO
resistance normal? Replace the thermistor.
CHECK 11
YES
Connect and disconnect the
connector (X111A) for the
radiation fin thermistor, and
then properly connect it.
Error is
displayed again when YES
the power supply Replace the inverter PCB.
turns ON to start the
compressor?
NO
Continue the operation.
z It is supposed that the radiation
fin temperature became high due
to some field factors. In this
connection, check the following
points:
• Stained radiation fin
• Airflow obstructed with dirt or
foreign matters
• Damage to fan impellers
• Too high outdoor air
temperature
Method of Error Error is detected from current (∗1) flowing in the power transistor
Detection ∗1 PY1, PYL: 32A
PTL: 59.1A
NO
Is the stop valve open? Open the stop valve.
YES
Are the
compressor lead NO
Replace the compressor
wires normal?
lead wires.
YES
NO
Compressor YES
coils are disconnected. Replace the inverter
compressor.
NO
CHECK 4 NO
Is the power transistor Replace the inverter PCB
normal? (A2P).
YES
Failure occurs NO
Power ON again after restarting the Continue the operation.
unit. (
YES
(Momentary power failure
is possible.
Method of Error Error is detected from the current flowing in the power transistor
Detection
YES
Are the
compressor NO
lead wires Replace the compressor
normal? lead wires.
YES
YES
Power OFF
Is the insulation
resistance of the YES
Replace the inverter
compressor 100kΩ compressor.
or less?
NO
CHECK 4 NO
Is the power transistor Replace the inverter
normal? PCB (A2P).
YES
Error is displayed NO
Continue the operation.
again?
YES
Is the
pressure difference
between high pressure and NO
low pressure before Defective pressure
restarting 0.2MPa equalizing in the
or below? refrigerant circuit.
YES
Inspection of the
compressor.
Method of Error Error is detected based on the signal waveform of the compressor
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Is a right amount of NO
Charge a right amount of
refrigerant charged? refrigerant.
YES
YES
Refrigerant
is melting in refrigerant
oil. (The unit is out of YES
Cancel the melting state of
power supply for more refrigerant.
than 6 hours.)
NO
Is the
insulation resistance of NO
the compressor more Cancel the melting state of
than 100kΩ? refrigerant.
YES
NO
Correct the wiring then supply the
power to restart.
Troubleshooting
Refrigerant
is melting in refrigerant NO
oil. (The unit is out of Cancel the melting state of
power supply for more refrigerant.
than 6 hours.)
YES
Is the insulation
resistance of the NO
Replace the inverter compressor.
compressor 100kΩ
or more?
YES
NO
CHECK 4
Check if the NO
Replace the compressor inverter
power transistor PCB (A2P).
is normal.
YES
Method of Error Check the communication state between inverter PCB and main PCB by micro-computer.
Detection
Error Decision When the transmission is not carried out in a specified period of time or longer
Conditions
Supposed Incorrect transmission wiring between the inverter PCB and outside unit main PCB
Causes Defective outside unit main PCB (transmission section)
Defective inverter PCB
Defective noise filter
External factor (Noise, etc.)
Defective inverter compressor
Defective fan motor
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
connectors of
the main PCB and NO
inverter PCB all securely Properly connect the connectors.
connected?
(∗1)
YES
YES
The INV.
compressor has YES
insulation resistance of not Replace the INV. compressor
more than (M1C).
100kΩ.
NO
The fan
motor has insulation YES
resistance of not more Replace the fan motor.
than 1MΩ.
NO
The
micro-
computer normal NO
monitor (green) of the main Not the "LC" error. Check the error
PCB (A1P) is code again.
blinking.
YES
The micro-
computer normal NO
monitor (green) of the Replace the inverter PCB (A2P).
inverter PCB (A2P) is
blinking.
YES
NO
Continue the operation.
(It is supposed that the error
results from causes such as
instantaneous power failure.)
Note: ∗1: Disconnect the connector once, then reconnect it and check that it is securely connected.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Imbalance in
supplied voltage is YES YES
Open phase? Open phase
in excess of 6 V. Normalize the field cause.
(∗1)
NO NO
Repair power supply
voltage imbalance.
Parts or wiring defect
Is the voltage After turning the power supply
imbalance applied YES OFF, check and repair the
to the inverter in main circuit wiring or parts.
excess of 6 V? (1) Loose or disconnected
(∗2) wiring between power
supply and inverter
(2) K1M contact disposition,
NO <When voltage monitoring is possible:> fusion or contact is poor.
(3) Loose or disconnected
Using a device capable of noise filter
constant recording of power
supply voltage record power
supply voltage between 3
phases (R-S,
S-T, R-T) for about 1
continuous week.
Explanation for users ∗In accordance with "notification of inspection results" accompanying spare parts.
Be sure to explain to the user that
Give the user a copy of "notification of inspection results" and leave there is a "power supply imbalance"
it up to him to improve the imbalance. for which DAIKIN is not responsible.
Note: ∗1: Measure voltage at the X1M power supply terminal block.
∗2: Measure voltage at terminals R, S and T of the diode module inside the inverter PCB while
the compressor is running.
Method of Error Resistance of radiation fin thermistor is detected during the compressor stops.
Detection
Error Decision When the resistance value of thermistor becomes a value equivalent to open or short-circuited
Conditions status
Error is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the thermistor NO
resistance value Replace the INV. PCB.
normal?
YES
The INV.
compressor's YES
insulation resistance Replace the INV.
is not more than compressor (M1C).
100kΩ.
NO
NO
Continue the operation.
Method of Error This error is detected according to communications with the INV. PCB.
Detection
Error Decision Make judgement according to communication data on whether or not the type of the INV. PCB
Conditions is correct.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
type of the NO
compressor inverter PCB Replace it with the
(A2P) correct? correct compressor
inverter PCB.
YES
Is the type
of the fan inverter PCB NO
Replace it with the
(A2P) correct? correct fan inverter
PCB.
YES
Is the
setting of DIP switches NO
when replace the main Set the DIP switches
PCB correct? correctly.
(After setting: Reset the
YES power supply)
Does the
preparation indication NO
lamp (H2P) on the main Rectify the connection
PCB turn OFF? wiring.
YES
Replace the outside
unit main PCB.
Method of Error Detect refrigerant shortage based on the temperature difference between low pressure
Detection equivalent saturation temperature or suction pipe and heat exchanger temperature.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
Is the low pressure NO characteristics of NO
0.1MPa or less? (∗1) low pressure sensor Replace the low pressure
normal? (∗2) sensor.
YES YES
In heating
Reset the operation using the remote controller then restart.
Note: ∗1: Check the low pressure value by using pressure gauge in operation.
∗2: Compare the actual measurement value by pressure sensor with the value by the pressure
gauge.
(To gain actual measurement value by pressure sensor, measure the voltage at the
connector [between (2)-(3)] and then convert the value into pressure referring to P.240.)
∗3: Compare the thermistor resistance value with the value on the surface thermometer.
Method of Error The phase of each phase are detected by reverse phase detection circuit and right phase or
Detection reverse phase are judged.
Error Decision When a power supply is reverse phase, or T phase is open phase
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
There
is an open
phase at the
power supply (T phase) YES
terminal section (X1M) of Fix the open phase. Requires
the outside unit. inspection of field power supply
section.
NO
Operation is
normal if one place of YES
power supply line phase Reverse phase.
is replaced. Countermeasure of the problem is
completed by phase replacement.
NO
Replace the outside unit PCB
(A1P).
Method of Error Detection of voltage of main circuit capacitor built in the inverter PCB and power supply voltage
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check if power
supply voltage is 200 to NO Correct the power
240V? supply voltage.
YES
Is the
resistance between
NO
terminals P and N more Replace the INV. PCB
than hundreds of (A2P).
ohms?
YES
Turn ON again.
The voltage is NO
Replace the INV. PCB
190 V or more. (A2P).
YES
Is the YES
connection wiring Replace the connection
defective? wire.
NO
To diagnosis error
code "P1".
Error Decision The error is decided when the unit starts operation without check operation.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has the
check operation NO
performed on outside Press the BS4 on PCB on the
unit PCB? master outside unit for 5 seconds
or more to execute check
YES operation.
Method of Error Micro-computer checks if transmission between indoor and outside units is normal.
Detection
Error Decision When transmission is not carried out normally for a certain amount of time
Conditions
Supposed Indoor to outside, outside to outside transmission wiring F1, F2 disconnection, short circuit
Causes or wrong wiring
Outside unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outside unit main PCB
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check if
indoor unit
PCB or outside unit
PCB has been replaced. YES
Or check if indoor-outside, Press the RESET button on the
outside-outside main PCB of the master outside
transmission wires unit. Keep pressing for 5 seconds
has been or more. (Operation does not start
modified.
for a maximum 12 minutes.)
NO
Do all
the indoor Are the
remote controllers indoor-outside,
NO outside-outside YES
within the same Replace the indoor unit PCB.
refrigerant circuit transmission wires
display “U4”? normal?
YES NO
Correct the transmission wires.
Reset the power supply.
Does Is the
the normal
condition monitor for NO voltage between NO
the micro-computer (HAP) R, S terminals on the Correct the voltage (220-240V).
on the outside unit outside unit PCB
PCB blink? 220-240V?
YES YES
Does
the LED in
preparation mode NO Is the fuse on the YES
(H2P) on the outside outside unit PCB Replace the fuse.
unit PCB blink? blown?
YES NO
The
secondary voltage NO
of the transformer is Replace the transformer.
about 22V.
YES
Replace the outside unit PCB
(A1P).
Lights
do not go out YES
for 12 minutes or Press the RESET button on the
more. main PCB of the outside unit main
PCB. Keep pressing for 5 seconds
NO or more.
Are the
indoor-outside, NO
outside-outside Correct the transmission wires.
transmission wires
normal?
YES
Replace the outside unit main
PCB.
Method of Error Micro-computer checks if transmission between indoor unit and remote controller is normal.
Detection
Error Decision When transmission is not carried out normally for a certain amount of time.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Is it normal? Normal
NO
There is possibility of error
caused by noise. Check the
surrounding area and turn ON
again.
Error Decision When transmission is not carried out normally for a certain amount of time
Conditions
Supposed Improper connection of transmission wiring between outside unit and external control
Causes adaptor for outside unit.
Improper cool/heat selection
Improper cool/heat unified address (outside unit, external control adaptor for outside unit)
Defective outside unit PCB (A1P)
Defective external control adaptor for outside unit
Improper connection of transmission wiring between outside units
Defective fuse of outside unit compressor
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check 3 Check 4
Go on to the Diagnosis Flow 1
(Defective transmission caused
when the external control adaptor
for outside unit is mounted)
Check 3 Check 4
Go on to the Diagnosis Flow 2
(Transmission alarm given when
the external control adaptor for
outside unit is mounted)
Check 3 Check 4
Go on to the Diagnosis Flow 3
(Abnormal transmission between
the master unit and the slave unit 1)
Check 3 Check 4
Go on to the Diagnosis Flow 4
(Abnormal transmission between
the master unit and the slave unit 2)
Check 3 Check 4
Go on to the Diagnosis Flow 5
(Defective auto address of the
slave units 1 and 2)
Check 3 Check 4
Go on to the Diagnosis Flow 6
(Erroneous manual address
settings of the slave units 1 and 2)
Check 3 Check 4
Go on to the Diagnosis Flow 7
(Connection of four or more
outside units to the same circuit)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Diagnosis Flow 1
Confirmation of error 3 Confirmation of error 4
Check if
any disconnection or
connection error is detected in NO
connecting wires with external Correct the connecting wiring
control adaptor for outside with the external control adaptor
unit. for outside unit.
YES
YES YES
Replace the outside unit main
PCB.
Check if the
Check if the normal power supply wire for the
condition monitor LED for the NO NO
external control adaptor for Connect the power supply wire
external control adaptor for outside unit is connected to 5V for the external control adaptor
outside unit blinks. supply line. for outside unit to 5V supply
line.
YES YES
Replace the PCB of the external
control adaptor for outside unit.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Diagnosis Flow 2
Confirmation of error 3 Confirmation of error 4
NO
Cool/Heat selection C/H SELECT of the external
is unified. control adaptor for outside unit
is set to “IND”.
YES
YES
Troubleshooting
Diagnosis Flow 3
Confirmation of error 3 Confirmation of error 4
Check the
connection status of
connecting wires of the outside multi NO
to SLAVE 1. Check if the wiring is Replace the outside unit main
disconnected or is about to PCB of the SLAVE 1.
be disconnected.
YES
Diagnosis Flow 4
Confirmation of error 3 Confirmation of error 4
Check
the connection status
of connecting wires of the outside NO
multi to SLAVE 2. Check if the wiring is Replace the outside unit main
disconnected or is about to be PCB of the SLAVE 2.
disconnected.
YES
Check the
connection status of the
connecting wires of outside multi. Check NO
if the wiring has any connection error Replace the outside unit main
or broken, or is about to be PCB.
disconnected.
YES
Troubleshooting
Diagnosis Flow 6
Confirmation of error 3 Confirmation of error 4
Check
the connection
status of one of the connecting NO
wires of outside multi. Check if Replace the outside unit main
the wiring is broken or PCB.
disconnected.
YES
Correct the connecting wires of the
outside multi and then reset the
power supply.
Diagnosis Flow 7
Confirmation of error 3 Confirmation of error 4
In the
connection status NO
of the outside multi, check if Replace the outside unit main
more than 4 outside units
are connected. PCB.
YES
Method of Error In case of controlling with 2-remote controller, check the system using micro-computer if signal
Detection transmission between indoor unit and remote controller (main and sub) is normal.
Error Decision When transmission is not carried out normally for a certain amount of time
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Method of Error Detect the error signal for the other indoor units within the circuit by outside unit PCB.
Detection
Error Decision When the error decision is made on any other indoor unit within the system concerned.
Conditions
Troubleshooting
YES
Method of Error A difference occurs in data by the type of refrigerant between indoor, BS and outside units.
Detection The number of indoor units is out of the allowable range.
Signal transmission between indoor, BS and outside units is abnormal.
Error Decision The error decision is made as soon as either of the abnormalities aforementioned is detected.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Confirmation of Confirmation of
error 3 error 4
To Diagnosis Flow 1
Confirmation of Confirmation of
error 3 error 4
To Diagnosis Flow 2
Confirmation of Confirmation of
error 3 error 4
To Diagnosis Flow 3
Confirmation of Confirmation of
error 3 error 4
To Diagnosis Flow 4
Confirmation of Confirmation of
error 3 error 4
To Diagnosis Flow 5
Confirmation of Confirmation of
error 3 error 4
To Diagnosis Flow 6
Troubleshooting
Diagnosis Flow 1
Confirmation of Confirmation of
error 3 error 4
The
number of
indoor units
connected to the same YES Replace the main PCB of the
refrigerant circuit system outside unit.
should not more
than 64
units.
NO
Diagnosis Flow 2
Confirmation of Confirmation of
error 3 error 4
Check
if the refrigerant
type of the outside unit YES Replace the main PCB of the
corresponds to that of outside unit.
the indoor
unit.
NO
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Diagnosis Flow 3
Confirmation of Confirmation of
error 3 error 4
YES YES
YES
Diagnosis Flow 4
Confirmation of Confirmation of
error 3 error 4
Is the wiring
between the outside NO Correct the wiring.
unit and BS unit
correct?
YES
Troubleshooting
Diagnosis Flow 5
Confirmation of Confirmation of
error 3 error 4
Is the wiring
NO Correct the wiring.
between the BS units
correct?
YES
Diagnosis Flow 6
Confirmation of Confirmation of
error 3 error 4
Is the wiring
NO Correct the wiring.
between the indoor and BS
unit correct?
YES
Method of Error The principal indoor unit detects the same address as that of its own on any other indoor unit.
Detection
Error Decision The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Troubleshooting
Method of Error Micro-computer checks if transmission between indoor unit and centralized control equipment is
Detection normal.
Error Decision When transmission is not carried out normally for a certain amount of time
Conditions
Supposed Transmission error between optional controllers for centralized control and indoor unit
Causes Connector for setting main controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Defective PCB for centralized remote controller
Defective indoor unit PCB
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check
the indoor unit for
which “UE” is displayed. Is YES
the transmission error “UE” Continued to A (on the
caused on all indoor following page)
units?
NO
Is the
power supply of
the indoor unit on which NO Make sure there are no
the “UE” occurred, hazardous situations, and then
turned ON? turn the power ON.
YES
Has the
setting of
centralized control group NO Can the setting of YES
No. been made with the indoor centralized control group Make correct setting of the
unit on which the “UE” No. be made? centralized control group No.
occurred?
YES NO
For
VRV
systems, can the
setting of centralized NO
control group No. be made in Check outside units to which
one and the same the refrigerant system is
refrigerant connected.
system?
Was the
YES
centralized control NO
group No. for indoor unit Check whether or not there are
changed? no problems with the
transmission wiring length,
branch numbers, types of
YES cables and wires, number of
units connected, and others. If
no problems, replace the indoor
unit PCB.
Check the
transmission
wiring between
centralized control
equipment for any broken wire. Abnormal Correct the wiring.
For details, refer to information
in the “Procedure for
checking broken
wires”
section.
Normal
Check the
transmission
wiring between main
centralized control
equipment for any broken wire. Abnormal Correct the wiring.
For details, refer to information
in the "Procedure for
checking broken
wires" section.
Normal
Has the
main centralized
control equipment setting NO Correct the connection of the
connector been connector.
connected?
YES
Is the
voltage between
the terminals F1 (+) and NO Replace the centralized control
F2 (-) in the range of equipment.
15.2 to 17.6
VDC?
YES
Method of Error On check operation, the number of indoor units in terms of transmission is not corresponding to
Detection that of indoor units that have made changes in temperature.
Error Decision The error is determined as soon as the abnormality aforementioned is detected through
Conditions checking the system for any erroneous connection of units on the check operation.
Supposed Improper connection of transmission wiring between indoor-outside units and outside-
Causes outside units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Is indoor-
Is the check operation NO outside and outside- YES
Replace the indoor unit PCB.
carried out? outside unit transmission
wiring normal?
YES NO
Is indoor -
outside and outside - NO
outside unit transmission After fixing the incorrect wiring,
wiring normal? press the RESET button on the
master outside unit PCB for 5
seconds.
YES ∗ The unit will not run for up to
12 minutes.
Error Decision The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Supposed Improper connection of transmission wiring between indoor-outside units and outside-
Causes outside units
Defective of indoor unit PCB
Defective of outside unit main PCB
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is Does
electricity being an error occur
introduce for the first YES even after 12 minutes
time after installation or after elapses from the time when NO Normal
an indoor or outside unit electricity is introduced to
PCB has been indoor and outside
replaced? units?
YES
NO
Is indoor - outside
and outside - outside unit NO After fixing the incorrect wiring,
transmission wiring press the RESET button on the
normal? (*1) master outside unit PCB for 5
seconds.
YES ∗ The unit will not run for up to
12 minutes.
Disconnect the
outside-outside unit
transmission wiring to YES Install the DIII-NET extension
create the one-system status,
adaptor.
and then check whether
or not the system
is normal.
NO
Does a “UH”
error occur for all indoor NO Replace the indoor unit PCB.
units in the system?
YES
Note: ∗1: Check the correct wiring “indoor-outside” and “outside-outside” by Installation Manual.
∗2: What is Auto Address?
This is the address automatically assigned to indoor units and outside units after initial
power supply upon installation, or after executing rewiring (Keep pressing the RESET
button for more than 4 seconds).
2.56 Check
CHECK 1 Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
[In cooling] Short circuit ← Is the suction air temperature not more
High suction air than 43°C?
temperature of
High suction indoor unit High outdoor air temperature ← Is the outdoor air temperature not more
air than 43°C?
temperature
of the High suction air Short circuit ← Is the suction air temperature not more
condenser temperature of than 27°C?
indoor unit High outdoor air temperature ← Is the indoor temperature not more than 27°C?
← Is the connector properly connected?
Defective suction air thermistor of indoor unit Are the thermistor resistance
[In heating] characteristics normal?
High suction air temperature of outside unit ← Is the outdoor air temperature not more
than 16°CWB?
Defective outdoor air temperature thermistor of outside unit ← Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
Degradation in Dirty condenser
condensing ← Is the heat exchanger clogged? (In cooling)
capacity
Mixing of non-condensable gas ← Is air or else mixed in the refrigerant system?
∗1: In cooling, it is normal if the outside unit electronic expansion valve is fully open.
∗2: In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(For details, refer to “Electronic Expansion Valve Control”.)
∗1: For details of the compressor capacity control while in cooling, refer to “Compressor PI Control”.
∗2: The “low pressure protection control” includes low pressure protection control and hot gas bypass control.
∗3: In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”.
∗4: In heating, the outside unit electronic expansion valve (EVM) is used for “superheated degree control of
outside unit heat exchanger”.
Superheat due to
Compressor shaft damage
overheat Superheat due to
defective compressor
Indoor unit Defective valve coil ← Check if coil resistance and insulation are
electronic expansion normal.
[In cooling mode] valve failure Defective valve body
If the indoor unit
electronic Defective thermistor for ← Check if the connector is connected properly.
expansion valve indoor unit gas pipe Check if the thermistor resistance property is
is excessively
normal.
throttled. (∗3) Defective control
Defective thermistor for
indoor unit liquid pipe ← Check if the connector is connected properly.
Defective Check if the thermistor resistance property is
superheated normal.
degree Defective control PCB
control.
Outside unit Defective valve coil ← Check if coil resistance and insulation are
electronic expansion normal.
valve failure Defective valve body
[In heading
mode] If the Defective low pressure ← Check if the voltage property is normal.
outside unit sensor
electronic Defective thermistor for
Defective control ← Check if the connector is connected properly.
expansion valve suction pipe Check if the thermistor resistance property is normal.
is excessively
throttled. (∗4) Defective control PCB ← Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.
Refrigerant ← Refer to CHECK 7
shortage ← Does the piping length fall in the permissible range?
Irregular piping length
∗1: Refer to “Low pressure protection control” for hot gas bypass control.
∗2: Refer to “Subcooling electronic expansion valve control”.
∗3: “Superheating temperature control” in cooling mode is conducted by indoor unit electronic expansion valve.
∗4: Superheating temperature control in heating mode is conducted by outside unit electronic expansion valve (EVM).
∗5: Judgement criteria of superheat operation:
(1) Suction gas superheating temperature: 10 degrees and over. (2) Discharge gas superheating temperature: 45 degrees
and over, except for immediately after starting and drooping control, etc..
(Use the above stated values as a guide. Depending on the other conditions, the unit may be normal despite the values
within the above scope.)
Defective indoor Defective valve coil ←Does the valve coil have normal
unit electronic resistance and insulation?
(Refer to information in the CHECK 11
[Cooling] expansion valve Defective valve body section.)
Indoor unit
electronic Defective indoor unit
expansion ←Is the connector correctly connected?
gas pipe thermistor Are the thermistor resistance
valve opens
Defective characteristics normal?
too much. (∗1)
control Defective indoor unit ←Is the connector correctly connected?
Defective control liquid pipe thermistor Are the thermistor resistance
of superheated characteristics normal?
degree Defective control PCB
Defective outside Defective valve coil ←Does the valve coil have normal
unit electronic resistance and insulation?
(Refer to information in the CHECK 11
expansion valve Defective valve body section.)
Wet operation [Heating] Defective power pressure sensor ←Are the voltage characteristics normal?
Outside unit
electronic Defective ←Is the connector correctly connected?
expansion
Defective suction pipe thermistor
control Does the thermistor have normal
valve opens too resistance characteristics?
much. (∗2) Defective control PCB ←Is the pressure reading of the service
checker corresponding to the actual
measurement of the sensor?
∗1: "Superheated degree control" in cooling is exercised with the indoor unit electronic expansion valve.
∗2: "Superheated degree control" in heating is exercised with the outside unit electronic expansion valve (EV1).
∗3: Guideline of superheated degree to judge as wet operation
Suction gas superheated degree: Not more than 3°C; Discharge gas superheated degree: Not more than
15°C, except immediately after compressor starts up or is running under drooping control.
(Use the values shown above as a guideline. Even if the superheated degree falls in the range, the compressor
may be normal depending on other conditions.)
Cooling
High pressure
drooping control
Frequency comes to
High pressure the minimum level.
gradually rises with
increase in frequency.
Subcooled degree
becomes higher.
(Liquid connection
High pressure pipe temperature
lowers.)
(Low pressure is
maintained at a
constant level.)
Low pressure
Low pressure rises
due to reduced
compressor output.
Frequency
(Degree of overcharge)
Proper quantity Higher degree of overcharge
Cooling
The opening degree of the indoor unit Fan control is activated for high
electronic expansion valve becomes larger. pressure protection under
cooling control at low outdoor
Either of the electronic expansion air temperature, i.e., the fan is
valves becomes fully open. hunting at high pressure.
Frequency comes to the minimum level.
High pressure
To maintain low
pressure, frequency
drops due to the
capacity control.
Heating
The opening degree of the outside unit electronic expansion valve becomes larger.
The outside unit electronic expansion valve fully opens and frequency increases.
Discharge pipe or low pressure drooping control
Frequency comes to
High pressure the minimum level.
(High pressure is
maintained at a
constant level.)
Low pressure
Frequency
∗ In case of construction during rainy reason, if dew condensation occurs in the piping due
to extended construction period, or rainwater or else may enter the piping during
construction work:
652
High Pressure (PH)
580
507
435
362
290
217
145
72
-72
Part 7
Procedure for Mounting /
Dismounting of Switch Box
1. Procedure for Mounting / Dismounting of Switch Box.........................242
1.1 Procedure for Dismounting...................................................................242
1.2 Procedure for Mounting........................................................................242
Side panel
Switch box support leg
High
voltage
wiring
Low
voltage
wiring
Screw/Unscrew
the mounting screws.
Connect/Disconnect
the wirings.
Part 8
Appendix
1. Piping Diagrams..................................................................................245
1.1 Outside Units........................................................................................245
1.2 Indoor Unit............................................................................................246
1.3 BS Units ...............................................................................................248
2. Wiring Diagrams..................................................................................251
2.1 Outside Unit..........................................................................................251
2.2 Outside Unit Field Wiring......................................................................254
2.3 BS Unit .................................................................................................258
2.4 Air Treatment Equipment .....................................................................261
2.5 Indoor Unit............................................................................................265
3. Example of Connection .......................................................................279
4. Precautions for New Refrigerant (R-410A) .........................................281
4.1 Outline ..................................................................................................281
4.2 Refrigerant Cylinders............................................................................283
4.3 Service Tools........................................................................................284
Appendix 244
Piping Diagrams Si30-813_A
1. Piping Diagrams
1.1 Outside Units
RWEYQ8PY1 / RWEYQ10PY1
RWEYQ10YL / RWEYQ10TL
Solenoid valve
SV Filter Fusible
plug Electronic
Receiver
Heat exchanger pipe expansion valve
Filter Filter Filter
Water
inlet
Heat exchanger
SV
Subcooling
Plate heat
Solenoid valve exchanger
Check valve
Water
Service outlet
port
Pressure
regulating
valve Capillary Capillary
tube tube
Filter Four way valve
SV
Check
valve
Check valve
Strainer
separator
Gauge port
1/4" flare connection
Oil
High pressure
Filter S1NPH
sensor
High pressure
S1PH
switch
Capillary
SV
tube
S1NPL
Solenoid
valve Gauge port Compressor
Low pressure 1/4" flare connection
sensor INV.
Filter
Stop valve (With service port on on-site piping side φ7.9mm flare connection)
4D048290C
245 Appendix
Si30-813_A Piping Diagrams
Fan
4D024460E
FXDQ
Gas side
Liquid side
Filter Filter
Fan
4D060927A
Appendix 246
Piping Diagrams Si30-813_A
FXUQ + BEVQ
Indoor unit
Indoor unit
4D037995J
Connection Unit
4D034127B
247 Appendix
Si30-813_A Piping Diagrams
1.3 BS Units
BSVQ100, 160, 250PV1
Electronic
Double pipe heat Expansion Valve
exchanger (EVSC) Filter
Capillary tube
Electronic
Gas pipe Expansion Valve
connection port (EVHS)
Filter
Electronic
Expansion Valve HP/LP gas pipe
(EVH) connection port
Filter
Electronic
Expansion Valve
(EVL)
4D057985B
Appendix 248
Appendix 249
Liquid pipe
connection port
exchanger
connection port
Capillary tube
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
connection port
Suction gas pipe
Liquid pipe
Electronic Expansion
Valve (EVL)
connection port
connection port
HP/LP gas pipe
exchanger
connection port
Capillary tube
Electronic Expansion
Filter Valve (EVHS)
Liquid pipe
Electronic Expansion
Filter
connection port
Valve (EVH)
Electronic Expansion
Valve (EVLS) Filter
Liquid pipe
Electronic Expansion
Valve (EVL)
connection port
Electronic Expansion Valve
Double pipe heat Filter
(EVSC)
Gas pipe
exchanger
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
Liquid pipe
Electronic Expansion
Valve (EVL)
connection port
Electronic Expansion Valve
Double pipe heat Filter
(EVSC)
Gas pipe
exchanger
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
Electronic Expansion
Valve (EVL)
3D064148
BSV4Q100PV1
Si30-813_A Piping Diagrams
250 Appendix
Liquid pipe
connection port
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
connection port
Electronic Expansion
Valve (EVL)
Liquid pipe
connection port
HP/LP gas pipe
connection port
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Liquid pipe
Electronic Expansion
connection port
Valve (EVL)
connection port
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
Electronic Expansion
Valve (EVL)
Liquid pipe
connection port Electronic Expansion Valve
Double pipe heat (EVSC) Filter
Gas pipe exchanger
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
Electronic Expansion
Liquid pipe
Valve (EVL)
connection port
Electronic Expansion Valve
Double pipe heat (EVSC) Filter
exchanger
Gas pipe
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
Electronic Expansion
Valve (EVL)
Liquid pipe
connection port
Electronic Expansion Valve
Double pipe heat (EVSC) Filter
exchanger
Gas pipe
Capillary tube
connection port
Electronic Expansion
Filter Valve (EVHS)
Electronic Expansion
Valve (EVH) Filter
Electronic Expansion
Valve (EVLS) Filter
Electronic Expansion
Valve (EVL)
3D064149
BSV6Q100PV1
Piping Diagrams Si30-813_A
251
L1 L2 L3 N POWER SUPPLY
3/N ~ 380-415V 50Hz
2.1
A1P
Wiring Diagrams
K3R
K5R
K6R
K7R
K8R
K9R
K10R
K11R
K12R
K13R
Z1F X1A P> HAP H2P H4P H6P H8P
X1A S1PH X7A X9A X10A X11A X12A X13A X14A X15A X16A X17A
GRN E GRY GRY H1P H3P H5P H7P
X2A
GRY GRY BS1 BS2 BS3 BS4 BS5 S1NPL
X1M L1 L2 L3 N PNK ORG X45A
L11 L21 L31 N1 F1U X2A X3A
RWEYQ8PY1 / RWEYQ10PY1
RED
WHT
BLK
BLU
Y1S Y3S Y4S Y5S Y7S E1HC X46A
Outside Unit
Y6S Y2S
BLK
BLU
RED
X4A
WHT
M(1) (2) X2M
M
OFF 1234
M1F M2F 1~ 1~
T1A OPERATION OUTPUT
N=1 V1CP R3T R2T R4T R5T R6T NOTE)9 X26A
t˚ X1A Y1E
t˚ t˚ t˚ t˚ t˚ ∗ : ∗ IS CONNECTOR COLOR FOR PRINTED CIRCUIT BOARD. 6 6M
R1T A2P ∗ : ∗ IS CONNECTOR COLOR FOR COMPONENT.
2. Wiring Diagrams
WHT NOTE)5
P2
C66 C63 outdoor(Q1)(Q2)
+ + COOL HEAT COOL
T1R S2S S1S outdoor(F1)(F2) (3) (4) X3M
R50 R59 L1R HEAT FAN indoor(F1)(F2)
M1F M2F
+ - INTERLOCK
COOL/HEAT SELECTOR (OPTIONAL ACCESSORY) AXP NOTE)8
V2R A4P A2P
X11A A1P PRINTED CIRCUIT BOARD (MAIN) K10R MAGNETIC RELAY (OPERATION OUTPUT) (A1P) V1R DIODE BRIDGE (A2P)
Z1C A3P Z1C A2P PRINTED CIRCUIT BOARD (INV) K11R MAGNETIC RELAY (Y5S) (A1P) V2R POWER MODULE (A2P)
N=5 A3P PRINTED CIRCUIT BOARD (NOISE FILTER) K12R MAGNETIC RELAY (Y7S) (A1P) X1A, X3A CONNECTOR (Y1E, Y3E)
RED
WHT
BLK
A1P A4P PRINTED CIRCUIT BOARD (SUB) K13R MAGNETIC RELAY (E1HC) (A1P) X1M TERMINAL STRIP (POWER SUPPLY)
U V W X4M X1M BS1~5 BS BUTTON L1R REACTOR X1M TERMINAL STRIP (CONTROL) (A1P)
DETAIL OF M1C (MODE, SET, RETURN, TEST, RESET) M1C MOTOR (COMPRESSOR) X2M TERMINAL STRIP (OPERATION OUTPUT)
RED
WHT
BLK
W X1M X4M X2M X3M C63, C66 CAPACITOR M1F, M2F MOTOR (FAN, INVERTER COOLING) X3M TERMINAL STRIP (INTERLOCK)
U U V W DS1 DIP SWITCH PS SWITCHING POWER SUPPLY X4M TERMINAL STRIP (M1C)
MS EL. COMPO. BOX E1HC CRANKCASE HEATER Q1RP PHASE REVERSAL DETECT CIRCUIT (A1P) Y1E ELECTRONIC EXPANSION VALVE (MAIN)
V 3~ F1U FUSE (250V, 5A, B ) (A3P) R50,R59 RESISTOR Y3E ELECTRONIC EXPANSION VALVE (SUBCOOL)
NOTES) M1C F1U, F2U FUSE (250V, 10A, B ) (A1P) R95 RESISTOR (CURRENT LIMITING) Y1S SOLENOID VALVE (HOT GAS BYPASS)
H1P~8P PILOT LAMP (SERVICE MONITOR-ORANGE) (A1P) R1T THERMISTOR (FIN) (A2P) Y2S SOLENOID VALVE (OIL RECOVERY)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT. [H2P] PREPARE, TEST ------------------- FLICKERING R2T THERMISTOR (SUCTION) Y3S SOLENOID VALVE (RECEIVER PRESSURIZATION)
2. : FIELD WIRING. ERROR DETECTION ------------- LIGHT UP R3T THERMISTOR (M1C DISCHARGE) Y4S SOLENOID VALVE (RECEIVER GAS PURGE)
3. : TERMINAL STRIP : CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW) HAP PILOT LAMP (SERVICE MONITOR-GREEN) (A1P) R4T THERMISTOR (HEX GAS PIPE) Y5S SOLENOID VALVE (4 WAY VALVE) (MAIN)
4. WHEN USING THE OPTION ADAPTOR, REFER TO THE INSTALLATION MANUAL. K1M MAGNETIC CONTACT SWITCH (M1C) (A2P) R5T THERMISTOR (SUBCOOLING HEX) Y6S SOLENOID VALVE (LIQUID PIPE)
K1R MAGNETIC RELAY (A2P) R6T THERMISTOR (RECEIVER LIQ PIPE) Y7S SOLENOID VALVE (4 WAY VALVE) (HEAT EXCHANGER)
5. REFER TO THE INSTALLATION MANUAL, FOR CONNECTION WIRING TO INDOOR-OUTDOOR MAGNETIC RELAY (Y1S) (A1P) S1NPH NOISE FILTER (FERRITE CORE)
K3R PRESSURE SENSOR (HIGH) Z1C
TRANSMISSION F1 • F2, OUTDOOR-OUTDOOR TRANSMISSION F1 • F2, OUTDOOR-MULTI TRANSMISSION Q1 • Q2. K5R MAGNETIC RELAY (Y3S) (A1P) S1NPL PRESSURE SENSOR (LOW) Z1F NOISE FILTER (WITH SURGE ABSORBER)
6. REFER TO "SERVICE PRECAUTION" LABEL (ON EL. COMPO. BOX COVER), HOW TO USE BS1~BS5 AND DS1 SWITCH. K6R MAGNETIC RELAY (Y4S) (A1P) S1PH PRESSURE SWITCH (HIGH)
7. WHEN OPERATING, DON'T SHORT CIRCUIT FOR PROTECTION DEVICE. (S1PH) K7R MAGNETIC RELAY (M1F, M2F) (A1P) T1A CURRENT SENSOR (A4P) COOL/HEAT SELECTOR
8. BE SURE TO CONNECT AN INTERLOCK CIRCUIT BETWEEN THE TERMINAL (3)-(4) OF TERMINAL STRIP (X3M). K8R MAGNETIC RELAY (Y6S) (A1P) T1R TRANSFORMER (220 - 240V/20V) S1S SELECTOR SWITCH (FAN/COOL • HEAT)
K9R MAGNETIC RELAY (Y2S) (A1P) V1CP SAFETY DEVICES INPUT S2S SELECTOR SWITCH (COOL/HEAT)
9. INSTALL A HEAT SOURCE WATER PUMP OPERATION CIRCUIT BETWEEN THE TERMINAL (1)-(2) OF TERMINAL STRIP (X2M),
WHEN INTERLOCKING A HEAT SOURCE WATER PUMP AND SYSTEM OPERATION.
10. COOL/HEAT SELECTOR CANNOT BE CONNECTED WHEN OPERATING HEAT RECOVERY SYSTEM.
11. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK GRY : GRAY ORG : ORANGE.
3D061377E
Appendix
Si30-813_A
Appendix
Si30-813_A
L1 L2 L3 N POWER SUPPLY
RWEYQ10PYL
3/N~380V 60Hz
A1P
RED F1U X22A X23A X24A
A3P
L1 L2 L3 N BLU
BLK F2U Q1RP T1R NOTE) 4
K3R
K5R
K6R
K7R
K8R
K9R
K10R
K11R
K12R
K13R
Z1F HAP H2P H4P H6P H8P
X1A X1A S1PHP> X7A X9A X10A X11A X12A X13A X14A X15A X16A X17A
GRN E GRY GRY H1P H3P H5P H7P
X2A BS1 BS2 BS3 BS4 BS5
GRY GRY S1NPL
X1M L1 L2 L3 N PNK ORG X45A
L11 L21 L31 N1 F1U X2A X3A DS1 S1NPH
RED
WHT
BLK
BLU
Y1S Y3S Y4S Y6S Y2S
WHT RED Y5S Y7S E1HC ON X46A
X4A OFF
RED
WHT
BLK
BLU
M1F M M M2F
(1) (2) X2M 1234
1~ 1~ OPERATION OUTPUT
T1A NOTE) 9 X26A
N=1 V1CP R3T R2T R4T R5T R6T
t˚ ∗ :∗IS CONNECTOR COLOR FOR PRINTED CIRCUIT BOARD. 6 X1A 6Y1E
t˚ t˚ t˚ t˚ t˚ M
R1T ∗ :∗IS CONNECTOR COLOR FOR COMPONENT.
X2A X3A A2P
∗ :∗IS DISCRIMINATION COLOR FOR COMPONENT LEAD WIRE.
X10A X1A X28A
X1A X111A BLU
K1M 6 X3A 6Y3E
A4P X8A 1 X34A 1 X37A M
X21A X1M
V1R COOL/HEAT SELECTOR IN-OUT OUT-OUT OUT-MULTI WHT BLU WHT BLU
+ –
P1 A B C F1 F2 F1 F2 Q1 Q2 X47A
WHT K1R X25A
L1R PS
WHT R95 X4A NOTE)5
ORG
WHT
P2
C66 C63 outdoor (Q1) (Q2)
+ + COOL HEAT COOL S1S
T1R S2S outdoor (F1) (F2) (3) (4) X3M
R50 R59 L1R HEAT indoor (F1) (F2) FAN
M1F M2F
+ – COOL/HEAT SELECTOR (OPTIONAL ACCESSORY) INTERLOCK
AXP NOTE)8
V2R A4P A2P NOTE)10
X11A A1P
PRINTED CIRCUIT BOARD (MAIN) K10R MAGNETIC RELAY (OPERATION OUTPUT) (A1P) V1R DIODE BRIDGE (A2P)
Z1C A3P Z1C A2P
PRINTED CIRCUIT BOARD (INV) K11R MAGNETIC RELAY (Y5S) (A1P) V2R POWER MODULE (A2P)
N=5 PRINTED CIRCUIT BOARD (NOISE FILTER) K12R
A3P MAGNETIC RELAY (Y7S) (A1P) X1A, X3A CONNECTOR (Y1E, Y3E)
RED
WHT
BLK
A1P PRINTED CIRCUIT BOARD (SUB) K13R
A4P MAGNETIC RELAY (E1HC) (A1P) X1M TERMINAL STRIP (POWER SUPPLY)
U V W X4M X1M PUSH BUTTON SWITCH
BS1~5 L1R REACTOR X1M TERMINAL STRIP (CONTROL) (A1P)
DETAIL OF M1C (MODE, SET, RETURN, TEST, RESET) M1C MOTOR (COMPRESSOR) X2M TERMINAL STRIP (OPERATION OUTPUT)
RED
BLK
WHT
W X1M X4M X2M X3M C63, C66 CAPACITOR M1F, M2F MOTOR (FAN, INVERTER COOLING) X3M TERMINAL STRIP (INTERLOCK)
U U V W DS1 DIP SWITCH PS SWITCHING POWER SUPPLY X4M TERMINAL STRIP (M1C)
MS EL. COMPO. BOX
V E1HC CRANKCASE HEATER Q1RP PHASE REVERSAL DETECT CIRCUIT (A1P) Y1E ELECTRONIC EXPANSION VALVE (MAIN)
3~ F1U FUSE (250V, 5A, B ) (A3P) R50, R59 RESISTOR Y3E ELECTRONIC EXPANSION VALVE (SUB COOL)
M1C F1U, F2U FUSE (250V, 10A, B ) (A1P) R95 RESISTOR (CURRENT LIMITING) Y1S SOLENOID VALVE (HOT GAS BYPASS)
NOTES) H1P~8P PILOT LAMP (SERVICE MONITOR-ORANGE) (A1P) R1T THERMISTOR (FIN) (A2P) Y2S SOLENOID VALVE (OIL RECOVERY)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTSIDE UNIT. [H2P] PREPARE, TEST-------------------FLICKERING R2T THERMISTOR (SUCTION) Y3S SOLENOID VALVE (RECEIVER PRESSURIZATION)
MALFUNCTION DETECTION---LIGHT UP R3T THERMISTOR (M1C DISCHARGE) Y4S SOLENOID VALVE (RECEIVER GAS PURGE)
2. :FIELD WIRING HAP PILOT LAMP (SERVICE MONITOR-GREEN) (A1P) R4T THERMISTOR (HEX GAS PIPE) Y5S SOLENOID VALVE (4 WAY VALVE) (MAIN)
3. : TERMINAL STRIP : CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW) K1M MAGNETIC CONTACTOR (M1C) (A2P) R5T THERMISTOR (SUB COOLING HEX) Y6S SOLENOID VALVE (LIQUID PIPE)
4. WHEN USING THE OPTION ADAPTOR, REFER TO THE INSTALLATION MANUAL. K1R MAGNETIC RELAY (A2P) R6T THERMISTOR (RECEIVER LIQ PIPE) Y7S SOLENOID VALVE (4 WAY VALVE) (HEAT EXCHANGER)
5. REFER TO THE INSTALLATION MANUAL FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 · F2, K3R MAGNETIC RELAY (Y1S) (A1P) S1NPH PRESSURE SENSOR (HIGH) Z1C NOISE FILTER (FERRITE CORE)
OUTDOOR-OUTDOOR TRANSMISSION F1 · F2, OUTDOOR-MULTI TRANSMISSION Q1 · Q2. K5R MAGNETIC RELAY (Y3S) (A1P) S1NPL PRESSURE SENSOR (LOW) Z1F NOISE FILTER (WITH SURGE ABSORBER)
6. REFER TO "SERVICE PRECAUTION" LABEL (ON EL. COMPO. BOX COVER), HOW TO USE BS1~BS5 AND DS1 SWITCH. K6R MAGNETIC RELAY (Y4S) (A1P) S1PH PRESSURE SWITCH (HIGH)
7. WHEN OPERATING, DO NOT SHORT CIRCUIT FOR PROTECTION DEVICE. (S1PH) K7R MAGNETIC RELAY (M1F, M2F) (A1P) T1A CURRENT SENSOR (A4P) COOL/HEAT SELECTOR
8. BE SURE TO CONNECT AN INTERLOCK CIRCUIT BETWEEN THE TERMINAL (3)-(4) OF TERMINAL STRIP (X3M). K8R MAGNETIC RELAY (Y6S) (A1P) T1R TRANSFORMER (220V/20V) S1S SELECTOR SWITCH (FAN/COOL HEAT)
9. INSTALL A HEAT SOURCE WATER PUMP OPERATION CIRCUIT BETWEEN THE TERMINAL (1)-(2) OF K9R MAGNETIC RELAY (Y2S) (A1P) V1CP SAFETY DEVICES INPUT S2S SELECTOR SWITCH (COOL/HEAT)
TERMINAL STRIP (X2M), WHEN INTERLOCKING A HEAT SOURCE WATER PUMP AND SYSTEM OPERATION.
10. COOL/HEAT SELECTOR CANNOT BE CONNECTED WHEN OPERATING HEAT RECOVERY SYSTEM.
11. COLORS BLK: BLACK RED: RED BLU: BLUE WHT: WHITE PNK: PINK GRY: GRAY ORG: ORANGE
C: 3D061378C
252
Wiring Diagrams
253
POWER SUPPLY
RWEYQ10PTL
Wiring Diagrams
K3R
K5R
K6R
K7R
K8R
K9R
K10R
K11R
K12R
K13R
X7A X9A X10A X11A X12A X13A X14A X15A X16A X17A
HAP H2P H4P H6P H8P
GRN E1 Z1F S1PH P>
F1U X2A X2A GRY GRY H1P H3P H5P H7P
GRY GRY BS1 BS2 BS3 BS4 BS5 S1NPL
L1B L2B L3B PNK ORG X45A
X1M L1 L2 L3 X3A DS1 S1NPH
Y1S Y3S Y4S Y6S Y2S WHT RED Y5S Y7S E1HC ON X46A
RED
WHT
BLU
A4P X4A OFF
RED
WHT
BLU
M M (1) (2) X2M 1234
X2A M1F 1~ 1~ M2F OPERATION OUTPUT Y1E
T1A X1A
N=1 V1CP NOTE) 9 X26A
6 X1A 6 M
R3T R2T R4T R5T R6T
X3A ∗ : ∗IS CONNECTOR COLOR FOR PRINTED CIRCUIT BOARD.
t˚ t˚ t˚ t˚ t˚ Y3E
∗ : ∗IS CONNECTOR COLOR FOR COMPONENT.
A2P 6 X3A 6 M
∗ : ∗IS DISCRIMINATION COLOR FOR COMPONENT LEAD WIRE. X28A
L1 L2 L3 X1A WHT BLU WHT BLU
X1M
R1 X8A X21A 1 X34A 1 X37A COOL/HEAT SELECTOR IN-OUT OUT-OUT OUT-MULTI
K1M X25A A B C F1 F2 F1 F2 Q1 Q2 X47A
K84R
X4A
V2R
+ – PS NOTE)5
P1
ORG
WHT
WHT
L1R COOL HEAT COOL outdoor (Q1) (Q2)
S1S
WHT S2S outdoor (F1) (F2)
FAN
P2 +C1 HEAT (3) (4) X3M
indoor (F1) (F2)
X7A T1R COOL/HEAT SELECTOR (OPTIONAL ACCESSORY) INTERLOCK
R2 L1R NOTE)10 AXP NOTE)8
+ – M1F M2F
V1R t˚ R1T A1P
PRINTED CIRCUIT BOARD (MAIN) K12R MAGNETIC RELAY (Y7S) (A1P) X1A, X3A CONNECTOR (Y1E, Y3E)
A4P A2P PRINTED CIRCUIT BOARD (INV) K13R
A2P MAGNETIC RELAY (E1HC) (A1P) X1M TERMINAL STRIP (POWER SUPPLY)
U VW PRINTED CIRCUIT BOARD (NOISE FILTER) K84R
A3P MAGNETIC RELAY (LIMITING RESISTOR) (A2P) X1M TERMINAL STRIP (CONTROL) (A1P)
Z1C A3P Z1C PRINTED CIRCUIT BOARD (SUB) L1R
A4P REACTOR X2M TERMINAL STRIP (OPERATION OUTPUT)
N=4 X4M PUSH BUTTON SWITCH
BS1~5 M1C MOTOR (COMPRESSOR) X3M TERMINAL STRIP (INTERLOCK)
RED
WHT
BLU
(MODE, SET, RETURN, TEST, RESET) M1F, M2F MOTOR (FAN, INVERTER COOLING) X4M TERMINAL STRIP (M1C)
DETAIL OF M1C X4M U V W A1P C1 CAPACITOR PS SWITCHING POWER SUPPLY Y1E ELECTRONIC EXPANSION VALVE (MAIN)
W X1M DS1 DIP SWITCH Q1RP PHASE REVERSAL DETECT CIRCUIT (A1P) Y3E ELECTRONIC EXPANSION VALVE (SUB COOL)
RED
WHT
BLU
U UVW X1M X3M E1HC CRANKCASE HEATER R1 RESISTOR (LIMITING RESISTOR) (A2P) Y1S SOLENOID VALVE (HOT GAS BYPASS)
MS X2M F1U FUSE (250V, 5A, B ) (A3P) R2 RESISTOR (CURRENT SENSOR) (A2P) Y2S SOLENOID VALVE (OIL RECOVERY)
V 3~ R1T THERMISTOR (FIN) (A2P) Y3S SOLENOID VALVE (RECEIVER PRESSURIZATION)
EL. COMPO. BOX F1U, F2U FUSE (250V, 10A, B ) (A1P)
M1C H1P~8P PILOT LAMP (SERVICE MONITOR-ORANGE) (A1P) R2T THERMISTOR (SUCTION) Y4S SOLENOID VALVE (RECEIVER GAS PURGE)
[H2P] PREPARE, TEST-------------------FLICKERING R3T THERMISTOR (M1C DISCHARGE) Y5S SOLENOID VALVE (4 WAY VALVE) (MAIN)
NOTES) MALFUNCTION DETECTION---LIGHT UP R4T THERMISTOR (HEX GAS PIPE) Y6S SOLENOID VALVE (LIQUID PIPE)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTSIDE UNIT. HAP PILOT LAMP (SERVICE MONITOR-GREEN) (A1P) R5T THERMISTOR (SUB COOLING HEX) Y7S SOLENOID VALVE (4 WAY VALVE) (HEAT EXCHANGER)
2. : FIELD WIRING K1M MAGNETIC CONTACTOR (M1C) (A2P) R6T THERMISTOR (RECEIVER LIQ PIPE) Z1C NOISE FILTER (FERRITE CORE)
3. : TERMINAL STRIP : CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW) K3R MAGNETIC RELAY (Y1S) (A1P) S1NPH PRESSURE SENSOR (HIGH) Z1F NOISE FILTER (WITH SURGE ABSORBER)
4. WHEN USING THE OPTION ADAPTOR, REFER TO THE INSTALLATION MANUAL. K5R MAGNETIC RELAY (Y3S) (A1P) S1NPL PRESSURE SENSOR (LOW) FIELD SUPPLIED PARTS NOTE) 8.
5. REFER TO THE INSTALLATION MANUAL FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 · F2, K6R MAGNETIC RELAY (Y4S) (A1P) S1PH PRESSURE SWITCH (HIGH) AXP INTERLOCK CIRCUIT
OUTDOOR-OUTDOOR TRANSMISSION F1 · F2, OUTDOOR-MULTI TRANSMISSION Q1 · Q2. K7R MAGNETIC RELAY (M1F, M2F) (A1P) T1A CURRENT SENSOR (A4P) CONNECTOR FOR OPTIONAL ACCESSORY NOTE) 4.
6. REFER TO "SERVICE PRECAUTION" LABEL (ON EL. COMPO. BOX COVER), HOW TO USE BS1~BS5 AND DS1 SWITCH. K8R MAGNETIC RELAY (Y6S) (A1P) T1R TRANSFORMER (220V/20V) X24A CONNECTOR (ADAPTER)
7. WHEN OPERATING, DO NOT SHORT CIRCUIT FOR PROTECTION DEVICE. (S1PH) K9R MAGNETIC RELAY (Y2S) (A1P) V1CP SAFETY DEVICES INPUT COOL/HEAT SELECTOR
8. BE SURE TO CONNECT AN INTERLOCK CIRCUIT BETWEEN THE TERMINAL (3)-(4) OF TERMINAL STRIP (X3M). K10R MAGNETIC RELAY (OPERATION OUTPUT) (A1P) V1R POWER MODULE (A2P) S1S SELECTOR SWITCH (FAN/COOL · HEAT)
9. INSTALL A HEAT SOURCE WATER PUMP OPERATION CIRCUIT BETWEEN THE TERMINAL (1)-(2) OF TERMINAL K11R MAGNETIC RELAY (Y5S) (A1P) V2R DIODE BRIDGE (A2P) S2S SELECTOR SWITCH (COOL/HEAT)
STRIP (X2M), WHEN INTERLOCKING A HEAT SOURCE WATER PUMP AND SYSTEM OPERATION.
10. COOL/HEAT SELECTOR CANNOT BE CONNECTED WHEN OPERATING HEAT RECOVERY SYSTEM.
11. COLORS BLK: BLACK RED: RED BLU: BLUE WHT: WHITE PNK: PINK GRY: GRAY ORG:ORANGE YLW: YELLOW
3D061376D
Appendix
Si30-813_A
2.2
Appendix
Si30-813_A
procured on the site must comply with the 7) Wiring shown are general points-of-connection guides only and are not intended for or
applicable local and national codes. to include all details for a specific installation.
2) Use copper conductors only. 8) Be sure to install the switch and the fuse to the power line of each equipment.
3) As for details, see wiring diagram. 9) Install the main switch that can interrupt all the power supply in an integrated manner
4) Install circuit breaker for safety. because this system consists of the equipment utilizing the multiple power supply.
5) All field wiring and components must be provided 10) If there exists the possibility of reversed phase, lose phase, momentary blackout or the
by licensed electrician. power goes on and off while the product is operating, attach a reversed phase protection
circuit locally.
Running the product in reversed phase may break the compressor and other parts.
L N L N L N L N L N L N L N L N
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)
(POWER LINE) (POWER LINE)
INDOOR UNITS INDOOR UNITS
RWEYQ8PY1 / RWEYQ10PY1 / RWEYQ16PY1 / RWEYQ18PY1 / RWEYQ20PY1 / RWEYQ24PY1
3D048824D
254
Wiring Diagrams
255
[Operation System : Heat Pump]
Notes 1) All wiring, components and materials to be procured on 6) Unit shall be grounded in compliance with the applicable local and national codes.
the site must comply with the applicable local and 7) Wiring shown are general points-of-connection guides only and are not intended for or to
national codes. include all details for a specific installation.
2) Use copper conductors only. 8) Be sure to install the switch and the fuse to the power line of each equipment.
Wiring Diagrams
3) As for details, see wiring diagram. 9) Install the main switch that can interrupt all the power supplies in an integrated manner
4) Install circuit breaker for safety. because this system consists of the equipment utilizing the multiple power supplies.
5) All field wiring and components must be provided by 10) If there exists the possibility of reversed phase, lose phase, momentary blackout or the
licensed electrician. power goes on and off while the product is operating, attach a reversed phase protection
circuit locally.
Running the product in reversed phase may break the compressor and other parts.
L N L N L N L N L N L N L N L N
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)
(POWER LINE) (POWER LINE)
3D052075A
Appendix
Si30-813_A
Appendix
Si30-813_A
2) Use copper conductors only. 8) Be sure to install the switch and the fuse to the power line of each equipment.
3) As for details, see wiring diagram. 9) Install the main switch that can interrupt all the power supply in an integrated manner
4) Install circuit breaker for safety. because this system consists of the equipment utilizing the multiple power supply.
5) All field wiring and components must be provided by 10) If there exists the possibility of reversed phase, lose phase, momentary blackout or the
licensed electrician. power goes on and off while the product is operating, attach a reversed phase
protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
When the power supply is suppled to When the power supply is connected
〈 each outside unit individually. 〉 〈 in series between the units. 〉
POWER SUPPLY POWER SUPPLY
L1 L2 L3 N L1 L2 L3 N
MAIN MAIN OUTSIDE UNITS
OUTSIDE UNITS
SWITCH SWITCH
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
[UNIT 1] [UNIT 2] [UNIT 3] [UNIT 1] [UNIT 2] [UNIT 3]
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
RWEYQ10PYL / RWEYQ20PYL / RWEYQ30PYL
L N L N L N L N L N L N
SWITCH SWITCH SWITCH SWITCH
SWITCH
SWITCH
FUSE 2 WIRES CABLE FUSE FUSE FUSE 2 WIRES CABLE FUSE FUSE
(POWER LINE) 2 WIRES CABLE (POWER LINE) 2 WIRES CABLE
2 WIRES CABLE BS UNITS (POWER LINE) BS UNITS (POWER LINE)
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
RWEYQ8PY1 / RWEYQ10PY1 / RWEYQ16PY1 / RWEYQ18PY1 / RWEYQ20PY1
(POWER LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (POWER LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
L N L N L N L N L N L N L N L N L N L N
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
SWITCH SWITCH
FUSE 2 WIRES CABLE FUSE FUSE FUSE FUSE FUSE 2 WIRES CABLE FUSE FUSE FUSE FUSE
2 WIRES CABLE (POWER LINE) 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE (POWER LINE) 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) INDOOR UNITS (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) INDOOR UNITS (POWER LINE) (POWER LINE) (POWER LINE)
COOLING ONLY UNIT COOLING ONLY UNIT
3D048823D
256
Wiring Diagrams
257
[Operation system: Heat Recovery]
Notes1) All wiring, components and materials to be procured 6) Unit shall be grounded in compliance with the applicable local and national codes.
on the site must comply with the applicable local and 7) Wiring shown are general points-of-connection guides only and are not intended for or
Wiring Diagrams
L N L N L N L N L N L N
SWITCH SWITCH SWITCH SWITCH
SWITCH SWITCH
FUSE 2 WIRES CABLE FUSE FUSE FUSE 2 WIRES CABLE FUSE FUSE
(POWER LINE) 2 WIRES CABLE (POWER LINE) 2 WIRES CABLE
2 WIRES CABLE BS UNITS (POWER LINE) BS UNITS (POWER LINE)
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (POWER LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
L N L N L N L N L N L N L N L N L N L N
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
SWITCH SWITCH
FUSE 2 WIRES CABLE FUSE FUSE FUSE FUSE FUSE 2 WIRES CABLE FUSE FUSE FUSE FUSE
2 WIRES CABLE (POWER LINE) 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE (POWER LINE) 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) INDOOR UNITS (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) INDOOR UNITS (POWER LINE) (POWER LINE) (POWER LINE)
COOLING ONLY UNIT COOLING ONLY UNIT
3D052074A
Appendix
Si30-813_A
2.3
Appendix
Si30-813_A
BS Unit
A1P PRINTED CIRCUIT BOARD Y2E ELECTRONIC EXPANSION VALVE (SUB DISCHARGE)
BSVQ100P / 160P / 250PV1
DS1, DS2 DIP SWITCH Y3E ELECTRONIC EXPANSION VALVE (SUB SUCTION)
F1U FUSE (T, 3.15A, 250V) Y4E ELECTRONIC EXPANSION VALVE (MAIN DISCHARGE)
HAP BLINKING LAMP Y5E ELECTRONIC EXPANSION VALVE (MAIN SUCTION)
(SERVICE MONITOR-GREEN) Z1C NOISE FILTER (FERRITE CORE)
PS SWITCHING POWER SUPPLY (A1P) CONNECTOR FOR OPTIONAL PARTS A1P
X1M TERMINAL STRIP (POWER) X2A CONNECTOR (WIRING EXTERNAL CONTROL X2A
X1M (A1P) TERMINAL STRIP (CONTROL) ADAPTOR FOR OUTDOOR UNIT)
NOTE)7.
X2M TERMINAL STRIP (C/H SELECTOR) X4A
6 DS1 DS2
Y1E M
Y1E ELECTRIC EXPANSION VALVE (SUB COOL)
HAP Y5E Y3E
NOTES) 1. THIS WIRING DIAGRAM APPLIES TO THE BS UNIT ONLY. X5A Y2E
6 Y4E
2. : TERMINAL STRIP, : CONNECTOR, : TERMINAL Y2E M PS Y1E
: FIELD WIRING, : PROTECTIVE EARTH
3. WHEN USING THE COOL/HEAT SELECTOR (OPTIONAL ACCESSORY), X6A BS UNIT TOP
6
CONNECT IT TO TERMINALS A, B AND C ON X2M. Y3E M
4. AS FOR WIRING TO THE IN/D UNIT (F1) · (F2) AND OUT/D UNIT (F1) · (F2)
ON X1M (A1P), REFER TO INSTALLATION MANUAL. X7A
6
5. SYMBOLS SHOW AS FOLLOWS. (BLU: BLUE RED: RED) Y4E M
6. USE COPPER CONDUCTORS ONLY.
7. DIP SWITCH (DS1 · 2) INITIAL SETTINGS ARE AS FOLLOWS. X8A NOTE)3. X1M F1U
6 TO IN/D TO OUT/D POWER SUPPLY
1234 1234 1234 1234 1234 1234 Y5E M X2M UNIT UNIT
ON ON ON ~220-240V
A B C F1 F2 F1 F2 X1A 50Hz
OFF OFF OFF
DS1 DS2 DS1 DS2 DS1 DS2
BSVQ100PV1 BSVQ160PV1 BSVQ250PV1 INDOOR
UNIT N
FOR USING DIP SWITCH (DS1 · 2), REFER TO INSTALLATION MANUAL BLU
OR "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER. L
OUTDOOR RED
Z1C
UNIT X1M
N=2
3D055928C
258
Wiring Diagrams
259
BSV4Q100PV1
Wiring Diagrams
NOTES) 1. THIS WIRING DIAGRAM APPLIES TO THE BS UNIT ONLY. 6. USE COPPER CONDUCTORS ONLY. A1P (UNIT A) PRINTED CIRCUIT BOARD (INDOOR UNIT A) X2M (A1P~A4P) TERMINAL STRIP (C/H SELECTOR)
2. : TERMINAL STRIP, : CONNECTOR 7. DIP SWITCH (DS1 · 2) INITIAL SETTINGS ARE AS FOLLOWS. A2P (UNIT B) PRINTED CIRCUIT BOARD (INDOOR UNIT B) X1M TERMINAL STRIP (POWER)
A3P (UNIT C) PRINTED CIRCUIT BOARD (INDOOR UNIT C) X2M-X7M TERMINAL STRIP (CONTROL)
: FIELD WIRING, : PROTECTIVE EARTH A4P (UNIT D) PRINTED CIRCUIT BOARD (INDOOR UNIT D) Y1E ELECTRONIC EXPANSION VALVE (SUB COOL)
1234 1234 ON
3. WHEN USING THE COOL/HEAT SELECTOR (OPTIONAL ACCESSORY), DS1, DS2 DIP SWITCH Y2E ELECTRONIC EXPANSION VALVE (SUB DISCHARGE)
CONNECT IT TO TERMINALS A, B AND C ON X2M (A1P~A4P). F1U FUSE (T, 3.15A, 250V) Y3E ELECTRONIC EXPANSION VALVE (SUB SUCTION)
DS1 DS2 OFF HAP BLINKING LAMP Y4E ELECTRONIC EXPANSION VALVE (MAIN DISCHARGE)
4. AS FOR WIRING TO THE X2M~X7M (CONTROL), (SERVICE MONITOR-GREEN) Y5E ELECTRONIC EXPANSION VALVE (MAIN SUCTION)
REFER TO INSTALLATION MANUAL. FOR USING DIP SWITCH (DS1 · 2), REFER TO INSTALLATION MANUAL PS SWITCHING POWER SUPPLY (A1P~A4P) Z1C NOISE FILTER (FERRITE CORE)
5. SYMBOLS SHOW AS FOLLOWS. (BLU: BLUE RED: RED) X1M (A1P~A4P) TERMINAL STRIP (CONTROL)
OR "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
3D063928B
Appendix
Si30-813_A
Appendix
Si30-813_A
BSV6Q100PV1
A1P (UNIT A) PRINTED CIRCUIT BOARD (INDOOR UNIT A) X1M (A1P~A6P) TERMINAL STRIP (CONTROL)
NOTES) 1. THIS WIRING DIAGRAM APPLIES TO THE BS UNIT ONLY. 6. USE COPPER CONDUCTORS ONLY. A1P (UNIT B) PRINTED CIRCUIT BOARD (INDOOR UNIT B) X2M (A1P~A6P) TERMINAL STRIP (C/H SELECTOR)
2. : TERMINAL STRIP, : CONNECTOR 7. DIP SWITCH (DS1 · 2) INITIAL SETTINGS ARE AS FOLLOWS. A1P (UNIT C) PRINTED CIRCUIT BOARD (INDOOR UNIT C) X1M TERMINAL STRIP (POWER)
A1P (UNIT D) PRINTED CIRCUIT BOARD (INDOOR UNIT D) X2M-X9M TERMINAL STRIP (CONTROL)
: FIELD WIRING, : PROTECTIVE EARTH
A1P (UNIT E) PRINTED CIRCUIT BOARD (INDOOR UNIT E) Y1E ELECTRIC EXPANSION VALVE (SUB COOL)
3. WHEN USING THE COOL/HEAT SELECTOR (OPTIONAL ACCESSORY), 1234 1234
ON A1P (UNIT F) PRINTED CIRCUIT BOARD (INDOOR UNIT F) Y2E ELECTRIC EXPANSION VALVE (SUB DISCHARGE)
CONNECT IT TO TERMINALS A, B AND C ON X2M (A1P~A6P). OFF DS1, DS2 DIP SWITCH Y3E ELECTRIC EXPANSION VALVE (SUB SUCTION)
DS1 DS2
4. AS FOR WIRING TO THE X2M~X9M (CONTROL), REFER TO F1U FUSE (T, 3.15A, 250V) Y4E ELECTRIC EXPANSION VALVE (MAIN DISCHARGE)
HAP FLASHING LAMP Y5E ELECTRIC EXPANSION VALVE (MAIN SUCTION)
INSTALLATION MANUAL. (SERVICE MONITOR-GREEN) Z1C
FOR USING DIP SWITCH (DS1 · 2), REFER TO INSTALLATION MANUAL NOISE FILTER (FERRITE CORE)
5. SYMBOLS SHOW AS FOLLOWS. (BLU: BLUE RED: RED) PS SWITCHING POWER SUPPLY (A1P~A6P)
OR "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
3D063929B
260
Wiring Diagrams
261
2.4
L N
POWER SUPPLY
220-240V S1H Note) 7
VKM80GAMV1
VKM50GAMV1
A3P
Wiring Diagrams
~ VKM100GAMV1
50Hz SS1 Note) 9 %H2O,
X4 X3 X2 X1 WHT
Note) 7
OFF ON
X2M X1M 1 2 X1M
X1M KFR KCR KHuR X20A
L N Y2 BLK BLK BLK
KHR 5 1 2 X1M
S1L
K8R
BLK Y1 3 BLU BLU
F2U WHT 7 RED RED
ADAPTOR PCB FOR WIRING WHT
(OPTIONAL ACCESSORIES) F2U YC K8R Y2S
EXTERNAL OUTPUT X1A
(KRP50-2) Note) 4 TERMINALS
X2A
8 WHT WHT
Tes10 WHT BLU
1 CONTACT R3T R4T R5T
R1T R2T Ry1 CAPACITY
2 Note) 8 Y1E M
Ry2 AC220-240V t˚ t˚ t˚ RED GRN
t˚ t˚ 3 A2P
RED
WHT
0.01~1.6A
A1P
RED
WHT
R S
X2M JC Note) 5 X3M
L N INPUT FROM F1U X16A X13A X12A X11A X9A X8A X7A PNK Note) 6
X12A X13A X9A X10A X11A SS1 T2 T2
NOR J2 OUTSIDE INPUT FROM OUTSIDE
Note) 10 H RED WHT
HAP M T1 T1
F1U J1 Note) 3
RED T2R RED HAP YLW
F2 F2
F2 ORG TO CONNECTION WIRING AND
T1R RED t˚ X3A F1 F1
F1 CENTRALIZED REMOTE CONTROLLER UNIT
X7A BLU
t˚ BLK P2 P2
P1
X18A BLK
K7R BLU BLU P1 P1
P2 X30A
K1R K2R K3R K4R K5R K6R BLU X1A
BLU X8A P1 P2
FC1 FH1 FM1 FL1 FC2 FH2 FM2 FL2 X3A X5A
BLU SS1
X1A X2A
Air Treatment Equipment
BLK
(OPTIONAL ACCESSORIES)
BLU
BLK
WHT
WHT
RED
RED
BLU
RED
RED
ORG
ORG
SS1 C1 C2
MSW S1Q
A3P A2P
YLW
WHT
YLW
WHT
Notes) 1. :TERMINAL BLOCK, ~
:TERMINAL, , :CONNECTOR, :SHORT CIRCUIT CONNECTOR
M1D
C1
T2R
C2
2. :FIELD WIRING
SS1 X17A X19A
T1R 3. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
A1P
RED
BLK
BLU
ORG
YLW
WHT
RED
BLK
BLU
ORG
YLW
WHT
INSTRUCTION MANUAL.
X3M
K8R
4. IN CASE USING WIRING ADAPTOR, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
X2M M M
X1M ~ M1F ~ M2F 5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FRESH UP CONTROL OPERATION CAN BE SELECTED BY
t˚ t˚
X11A CONTROL BOX F1UT F2UT REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE
A1P PRINTED CIRCUIT BOARD K7R MAGNETIC RELAY (M1D) (A1P) SS1 SELECTOR SWITCH SELECTED BY REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
A2P PRINTED CIRCUIT BOARD K8R MAGNETIC RELAY (S1L) (HUMIDISTAT INPUT) (A3P) 7. IN CASE INSTALLING A HUMIDISTAT S1H (LOCALLY PROCURED), REMOVE THE SHORT CIRCUIT WIRING BETWEEN (1) AND
A3P PRINTED CIRCUIT BOARD KCR, KFR MAGNETIC RELAY (A3P) T1R TRANSFORMER (220-240V / 22V) (2) AS SHOWN IN THE FIGURE RIGHT.
8. DO NOT REMOVE THE SHORT CIRCUIT CONNECTORS OF X8A AND X9A. THE UNIT WILL NOT RUN IF THEY ARE REMOVED.
(ADAPTOR FOR WIRING) KHR, KHuR MAGNETIC RELAY (A3P) T2R TRANSFORMER (220-240V / 22V)
9. SS1 (A3P) HAS ALREADY BEEN SET TO OFF AT FACTORY SET. HUMIDIFYING BECOMES IMPOSSIBLE , IF THE SETTING ARE
C1 · C2 CAPACITOR (M1F, M2F) M1D MOTOR (DAMPER MOTOR) X1M TERMINAL BLOCK (POWER SUPPLY) CHANGED.
F1U FUSE ( B , 10A, 250V) (A1P) M1F MOTOR (SUPPLY AIR FAN) X1M, X2M TERMINAL BLOCK (CONTROL) (A3P) 10. SS1 (A1P) HAS ALREADY BEEN SET TO "NOR". AT FACTORY SET. THE UNIT WILL NOT RUN IF THE SETTING ARE CHANGED.
F1U FUSE ( B , 5A, 250V) (A2P) M2F MOTOR (EXHAUST AIR FAN) X2M TERMINAL BLOCK (CONTROL) (A1P) 11. SYMBOLS SHOW AS FOLLOWS. (PNK: PINK WHT: WHITE YLW: YELLOW ORG: ORANGE BLU: BLUE BLK: BLACK RED: RED
F1U, F2U FUSE ( B , 5A, 250V) (A3P) R1T THERMISTOR (INDOOR AIR) X3M TERMINAL BLOCK (CONTROL) GRN: GREEN)
F1UT · F2UT THERMO SWITCH R2T THERMISTOR (OUTDOOR AIR) X17A, X19A CONNECTOR (RELAYING WIRE) 12. USE COPPER CONDUCTORS ONLY.
(152˚C) (M1F, M2F BUILT-IN) R3T THERMISTOR X20A CONNECTOR (RELAYING WIRE)
HAP LIGHT EMITTING DIODE (INLET AIR INTO COIL) Y1E ELECTRONIC EXPANSION VALVE
(SERVICE MONITOR-GREEN) (A1P) R4T, R5T THERMISTOR Y2S FEED WATER SOLENOID VALVE ADAPTOR PCB FOR WIRING Tes10 TERMINAL BLOCK X18A CONNECTOR (WIRING ADAPTOR FOR
HAP LIGHT EMITTING DIODE (LIQUID / GAS PIPE OF COIL) OPTIONAL ACCESSORIES (KRP50-2) (FOR EXTERNAL OUTPUT) ELECTRICAL APPENDICES) (A2P)
(SERVICE MONITOR-GREEN) (A2P) S1L FLOAT SWITCH (HUMIDIFIER) WIRED REMOTE CONTROLLER Ry1 MAGNETIC RELAY CONNECTOR FOR OPTIONAL PARTS LOCAL SUPPLIED PARTS
K1R~K3R MAGNETIC RELAY (M1F) (A1P) S1Q LIMIT SWITCH (DAMPER MOTOR) SS1 SELECTOR SWITCH (MAIN / SUB) (OPERATION / STOP) X11A CONNECTOR S1H HUMIDISTAT
K4R~K6R MAGNETIC RELAY (M2F) (A1P) SS1 SELECTOR SWITCH Ry2 MAGNETIC RELAY (ADAPTOR POWER SUPPLY) (A1P)
(FOR ESPECIALLY USE) (A1P) (FOR HUMIDIFIER OPERATION)
3D051310
Appendix
Si30-813_A
Appendix
Si30-813_A
L N
VKM80GAV1
VKM50GAV1
POWER SUPPLY
VKM100GAV1
220-240V
~
50Hz
X1M
L N
RED
WHT
0.01~1.6A
RED
WHT
A1P
R S
X2M JC Note) 5 X3M
L N SS1 INPUT FROM F1U X13A X12A X11A X9A X8A X7A PNK Note) 6
X12A X13A X9A X10A X11A NOR OUTSIDE T2 T2
Note) 8 H J2 WHT INPUT FROM OUTSIDE
HAP M
RED T1 T1
F1U J1 Note) 3
RED T2R RED HAP YLW
F2 F2
F2 ORG TO CONNECTION WIRING AND
T1R RED t˚ X3A F1
F1 F1 CENTRALIZED REMOTE CONTROLLER UNIT
X7A BLU
t˚ BLK P2 P2
P1
X18A BLK
K7R BLU BLU P1 P1
P2 X30A
K1R K2R K3R K4R K5R K6R BLU X1A
BLU P1 P2
X8A FC1 FH1 FM1 FL1 FC2 FH2 FM2 FL2 X3A X5A
BLU SS1
X1A X2A
X18A WIRED REMOTE CONTROLLER
(OPTIONAL ACCESSORIES)
WHT
WHT
RED
RED
BLK
BLK
BLU
BLU
RED
RED
ORG
ORG
C1 C2 S1Q
A2P MSW
YLW
WHT
YLW
WHT
~ Notes) 1. :TERMINAL BLOCK, :TERMINAL, , :CONNECTOR, :SHORT CIRCUIT CONNECTOR
C1
C2
T2R M1D 2. :FIELD WIRING
SS1 X17A X19A
A1P T1R 3. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
RED
BLK
BLU
ORG
YLW
WHT
RED
BLK
BLU
ORG
YLW
WHT
INSTRUCTION MANUAL.
X3M
X2M M M 4. IN CASE USING WIRING ADAPTOR, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
X1M ~ ~
t˚ M1F t˚ M2F 5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FRESH UP CONTROL OPERATION CAN BE SELECTED BY REMOTE
X11A CONTROL BOX F1UT F2UT CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE
SELECTED BY REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
7. DO NOT REMOVE THE SHORT CIRCUIT CONNECTORS OF X8A AND X9A. THE UNIT WILL NOT RUN IF THEY ARE REMOVED.
8. SS1 (A1P) HAS ALREADY BEEN SET TO "NOR". AT FACTORY SET. THE UNIT WILL NOT RUN IF THE SETTING ARE CHANGED.
9. SYMBOLS SHOW AS FOLLOWS. (PNK: PINK WHT: WHITE YLW: YELLOW ORG: ORANGE BLU: BLUE BLK: BLACK RED: RED
A1P PRINTED CIRCUIT BOARD K7R MAGNETIC RELAY (M1D) (A1P) T1R TRANSFORMER (220-240V / 22V) GRN: GREEN)
A2P PRINTED CIRCUIT BOARD M1D MOTOR (DAMPER MOTOR) T2R TRANSFORMER (220-240V / 22V) 10. USE COPPER CONDUCTORS ONLY.
C1 · C2 CAPACITOR (M1F, M2F) M1F MOTOR (SUPPLY AIR FAN) X1M TERMINAL BLOCK (POWER SUPPLY)
F1U FUSE ( B , 10A, 250V) (A1P) M2F MOTOR (EXHAUST AIR FAN) X2M TERMINAL BLOCK (CONTROL) (A1P)
F1U FUSE ( B , 5A, 250V) (A2P) R1T THERMISTOR (INDOOR AIR) X3M TERMINAL BLOCK (CONTROL)
F1UT · F2UT THERMO SWITCH R2T THERMISTOR (OUTDOOR AIR) X17A, X19A CONNECTOR (RELAYING WIRE)
(152˚C) (M1F, M2F BUILT-IN) R3T THERMISTOR X20A CONNECTOR (RELAYING WIRE)
HAP LIGHT EMITTING DIODE (INLET AIR INTO COIL) Y1E ELECTRONIC EXPANSION VALVE X18A CONNECTOR (WIRING ADAPTOR FOR
ADAPTOR PCB FOR WIRING Tes10 TERMINAL BLOCK
(SERVICE MONITOR-GREEN) (A1P) R4T, R5T THERMISTOR OPTIONAL ACCESSORIES (KRP50-2) (FOR EXTERNAL OUTPUT) ELECTRICAL APPENDICES) (A2P)
HAP LIGHT EMITTING DIODE (LIQUID / GAS PIPE OF COIL) WIRED REMOTE CONTROLLER MAGNETIC RELAY CONNECTOR FOR OPTIONAL PARTS
Ry1
(SERVICE MONITOR-GREEN) (A2P) S1Q LIMIT SWITCH (DAMPER MOTOR) SS1 SELECTOR SWITCH (MAIN / SUB) (OPERATION / STOP) X11A CONNECTOR
K1R~K3R MAGNETIC RELAY (M1F) (A1P) SS1 SELECTOR SWITCH Ry2 MAGNETIC RELAY (ADAPTOR POWER SUPPLY) (A1P)
K4R~K6R MAGNETIC RELAY (M2F) (A1P) (FOR ESPECIALLY USE) (A1P) (FOR HUMIDIFIER OPERATION)
3D051311
262
Wiring Diagrams
263
L N
50/60Hz Tes10
1 EXTERNAL OUTPUT TERMINALS
Ry1 CONTACT
X1M N R1T R2T 2 CAPACITY C1
L Ry2
3 AC200~240V X1M T1R
0.01~1.6A C2
t˚ t˚
RED
BLU
A1P SS1 X15A
L N
X12A X13A X9A X10A X11A A1P
X10A
F1U X9A
X2M JC
X2M
RED NOTE) 4
J2
INPUT FROM OUTSIDE
RED SS1 NOTE) 6 CONTROL BOX
T1R J1
NOR.
X7A H F2 NOTE) 3
t˚
M TO CONNECTION WIRING AND
F1 CENTRALIZED REMOTE CONTROLLER UNIT
X8A K1R K2R K3R K4R K5R K6R K7R P1
BLU
P2
BLU FC1 FH1 FM1 FL1 FC2 FH2 FM2 FL2 X5A X15A
X1A X2A X3A
P2 P1 WIRED REMOTE CONTROLLER
C1 C2
WHT
WHT
RED
RED
(OPTIONAL ACCESSORIES)
RED
BLK
BLU
ORG
SS1
RED
BLK
BLU
ORG
S1Q
YLW
WHT
YLW
WHT
MSW M1D
~
NOTE)
1. : TERMINAL, : CONNECTOR, : TERMINAL BLOCK
RED
BLK
BLU
ORG
RED
BLK
BLU
ORG
2. : FIELD WIRING
M M 3. IN CASE USING CENTRALIZED REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED MANUAL.
M1F ~ M2F ~
t˚ t˚ 4. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FRESH UP OR ON/OFF CONTROL OPERATION CAN BE SELECTED.
F1UT F2UT
L-RED N-BLU (CONTACT THAT CAN ENSURE THE MINIMUM APPLICABLE LOAD OF 12 V DC, 1mA)
A1P PRINTED CIRCUIT BOARD M2F MOTOR (EXHAUST FAN MOTOR) 5. IN CASE USING WIRING ADAPTOR, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED MANUAL.
C1 · C2 CAPACITOR (M1F · M2F) R1T THERMISTOR (INDOOR AIR) 6. SS1 (A1P) HAS BEEN ALREADY BEEN SET TO "NOR." AT FACTORY SET. THE UNIT WILL NOT RUN IF THE SETTING
ARE CHANGED.
F1U FUSE (250V, 10A, B ) R2T THERMISTOR (OUTDOOR AIR)
7. SYMBOLS SHOW AS FOLLOWS; BLK: BLACK, RED: RED, BLU: BLUE WHT: WHITE, YLW: YELLOW, ORG: ORANGE, GRN: GREEN.
F1UT · F2UT THERMAL FUSE (152˚C) S1Q LIMIT SWITCH (DAMPER MOTOR)
(M1F · M2F BUILT-IN) SS1 SELECTOR SWITCH X15A CONNECTOR (FOR EXTERNAL DAMPER) Tes10 TERMINAL BLOCK (FOR EXTERNAL OUTPUT)
K1R~K3R MAGNETIC RELAY (M1F) (FOR ESPECIALLY USE) OPTIONAL ACCESSORIES REMOTE CONTROLLER
K4R~K6R MAGNETIC RELAY (M2F) T1R TRANSFORMER (220-240V/22V) ADAPTOR FOR WIRING (KRP50-2) SS1 SELECTOR SWITCH (MAIN/SUB)
K7R MAGNETIC RELAY (M1D) X1M TERMINAL (POWER SUPPLY) Ry1 MAGNETIC RELAY (ON/OFF) OPTIONAL CONNECTOR
VAM150GJVE / VAM250GJVE / VAM350GJVE / VAM500GJVE / VAM650GJVE / VAM800GJVE /
M1D MOTOR (DAMPER MOTOR) X2M TERMINAL (CONTROL) Ry2 MAGNETIC RELAY X11A CONNECTOR
M1F MOTOR (AIR SUPPLY FAN MOTOR) X9A · X10A CONNECTOR (FOR KRP50-2) (HUMIDIFIER OPERATION) (ADAPTOR POWER SUPPLY)
3D041839A
Appendix
Si30-813_A
L N
Appendix
POWER SUPPLY
SINGLE PHASE
Si30-813_A
220-240/220V
ADAPTOR PCB FOR WIRING
50/60Hz TeS10 A2P L N
(OPTIONAL ACCESSORIES) EXTERNAL OUTPUT TERMINALS
(KRP50-2) Note) 5 1 CONTACT F2U
Ry1 CAPACITY
X1M L N 2 X3A
Ry2 AC200~240V
R1T R2T 3 0.01~1.6A
Ry1 Ry2 Ry3 Ry4 Ry5 Ry6
t˚ t˚
FC3 FH3 FM3 FL3 FC4 FH4 FM4 FL4
RED
BLU
A1P X1A
L N X12A X13A X9A X10A X11A SS1 NOTE) 6 C3 C4
RED
RED
BLK
BLU
ORG
BLK
BLU
ORG
NOR.
VAM1500GJVE / VAM2000GJVE
H
M J2 NOTE) 4
RED
INPUT FROM OUTSIDE
RED
BLK
BLU
ORG
RED
BLK
BLU
ORG
J1
RED NOTE) 3
T1R F2
X7A TO CONNECTION WIRING AND M M
t˚ ~ M3F ~ M4F
F1 t˚ t˚
CENTRALIZED REMOTE CONTROLLER UNIT F3UT F4UT
P1
X8A K7R K8R
BLU K1R K2R K3R K4R K5R K6R P2 C1
T1R
BLU FC1 FH1 FM1 FL1 FC2 FH2 FM2 FL2 X5A X8A X15A C2
X1A X2A X3A X4A SS1 X15A
P2 P1 A1P
C1 C2
SS1
RED
BLK
BLU
ORG
RED
BLK
BLU
ORG
X10A
WHT
WHT
RED
RED
WHT
WHT
RED
RED
YLW
WHT
YLW
WHT
X9A X2M
WIRED REMOTE CONTROLLER
(OPTIONAL ACCESSORIES)
RED
BLK
BLU
ORG
RED
BLK
BLU
ORG
S1Q S2Q C3 A2P
M M C4 X1M
M1F ~ M2F ~
t˚ t˚ M1D MSW M2D MSW
F1UT F2UT ~ ~
NOTE)
1. : TERMINAL, : CONNECTOR, : TERMINAL BLOCK CONTROL BOX
3D051412
264
Wiring Diagrams
265
2.5
N=1 N=1
Y1E ELECTRONIC EXPANSION VALVE R1T THERMISTOR (AIR) M
WHT
ORG
BRN
BLU
RED
WHT
ORG
BRN
BLU
RED
3D059890A
Appendix
Si30-813_A
Appendix
Si30-813_A
M1P MOTOR (DRAIN PUMP) H4P LIGHT EMITTING DIODE L NOTE)3 YLW F2 TRANSMISSION WIRING CENTRALIZED
M1S MOTOR (SWING FLAP) (DEFROST-ORANGE) L RED
SS1 SELECTOR SWITCH N N WHT ORG F1 REMOTE CONTROLLER
Q1M THERMAL PROTECTOR (M1F EMBEDDED) X1A T1R X3A
R1T THERMISTOR (AIR) (MAIN/SUB) X31A BLU P2 P2 R1T NOTE)2
GRN/YLW t˚ BLK P1
R2T THERMISTOR (COIL-LIQUID) SS2 SELECTOR SWITCH P1
R3T THERMISTOR (COIL-GAS) (WIRELESS ADDRESS SET) X30A X1M SS1
A1P A3P A4P
S1L FLOAT SWITCH CONNECTOR FOR OPTIONAL PARTS SS1 H1P C1
T1R TRANSFORMER (220-240V/22V) X16A CONNECTOR
KPR WIRED REMOTE
(ADAPTOR FOR WIRING) SS2 H2P BS1 CONTROLLER
V1TR TRIAC V1TR
H3P X4A
YLW
WHT
3D064843
266
Wiring Diagrams
267
Wiring Diagrams
INDOOR UNIT Q1M THERMO SWITCH WIRED REMOTE CONTROLLER H3P LIGHT EMITTING DIODE
A1P PRINTED CIRCUIT BOARD (M1F EMBEDDED) R1T THERMISTOR (AIR) (FILTER SIGN-RED)
C1R CAPACITOR (M1F) R1T THERMISTOR (AIR) SS1 SELECTOR SWITCH H4P LIGHT EMITTING DIODE
POWER SUPPLY
FXCQ20M / 25M / 32M / 63MVE
3D039558A
Appendix
Si30-813_A
Appendix
Si30-813_A
3D039559A
268
Wiring Diagrams
269
INDOOR UNIT
A1P PRINTED CIRCUIT BOARD
A2P TERMINAL BOARD
Wiring Diagrams
C1 CAPACITOR (M1F)
POWER SUPPLY
F1U FUSE ( B , 5A, 250V) ELECTRIC PARTS BOX
220-240V 220V
HAP LIGHT EMITTING DIODE ~ ~ X18A X16A
(SERVICE MONITOR-GREEN) 50Hz 60Hz
S1Q
K1R-K3R MAGNETIC RELAY (M1F) C1
KAR MAGNETIC RELAY (M1S) R1T R2T R3T S1L A2P
X1M A1P T1R X1M
L N X2M
KPR MAGNETIC RELAY (M1P) GRN/ t˚ t˚
A1P RED WHT YLW t˚ BLK
M1F MOTOR (INDOOR FAN) FC FH FL FLL
X4A L N
M1P MOTOR (DRAIN PUMP)
ORG BRN X13A X12A X11A
X9A X8A X16A
MOTOR (SWING FLAP) A2P RED BLK F1U
FXKQ25MA / 32MA / 40MA / 63MAVE
M1S
HAP
Q1M THERMO SWITCH (M1F EMBEDDED) YC
X3A X2A LL X18A X30A
X3A PNK
R1T THERMISTOR (AIR) X1A T2 T2 NOTE-4
T1R WHT
R2T·R3T THERMISTOR (COIL) RED GRY BLK ORG BRN T1 T1 INPUT FROM OUTSIDE
YLW
S1L FLOAT SWITCH F2 F2 NOTE-3
t˚ ORG
NOTE-5 F1 F1 TRANSMISSION WIRING
S1Q LIMIT SWITCH (SWING FLAP) X1A BLU
P2 P2 CENTRAL REMOTE
T1R TRANSFORMER (220-240V/22V) K1R K2R K3R KAR KPR BLK
P1 P1 CONTROLLER
X1M TERMINAL BLOCK (POWER) X2M
FC FH FL FLL X6A X7A
X2M TERMINAL BLOCK (CONTROL) X4A Y2 Y1
Y1E ELECTRONIC EXPANSION VALVE RED BLK ORG BRN
A2P
WIRED REMOTE CONTROLLER YC R1T
WHT P1P2
R1T X3A X2A LL RED WHT
THERMISTOR (AIR) M SS1
X1A MSW M
SS1 SELECTOR SWITCH (MAIN/SUB) ~ ~
RED GRY BLK ORG BRN Y1E WIRED REMOTE CONTROLLER
CONNECTOR FOR OPTIONAL PARTS M1S M1P (OPTIONAL ACCESSORY)
X16A CONNECTOR (ADAPTOR FOR WIRING) WHT M
C1 ~ Q1M
X18A CONNECTOR (WIRING ADAPTOR YLW M1F
FOR ELECTRICAL APPENDICES)
C: 3D039564C
Appendix
Si30-813_A
Appendix
A1P PRINTED CIRCUIT BOARD
Si30-813_A
C1 CAPACITOR (M1F)
F1U FUSE (F5A/250V)
HAP LIGHT EMITTING DIODE
(SERVICE MONITOR GREEN)
KPR MAGNETIC RELAY (M1P) R1T R2T R3T
M1F MOTOR (INDOOR FAN)
FXDQ20PB / 25PB / 32PB
3D060547A
270
Wiring Diagrams
271
A1P PRINTED CIRCUIT BOARD
C1 CAPACITOR (M1F)
F1U FUSE (F5A/250V)
Wiring Diagrams
R1T t˚ t˚ t˚
THERMISTOR (COIL-1) POWER A1P
R2T
SUPPLY X1M NOTE) 5
R3T THERMISTOR (COIL-2)
~220-240V~220V PNK T2 INPUT FROM
T1R TRANSFORMER (220V/22V) X13A X12A X11A X16A Z1C
50Hz 60Hz WHT T1 OUTSIDE
V1TR PHASE CONTROL CIRCUIT N=3
X2M YLW F2 TRANSMISSION
F1U X30A WIRING CENTRAL
X1M TERMINAL BLOCK L RED
L ORG F1
X2M TERMINAL BLOCK REMOTE CONTROLLER
N N BLU BLU P2 P2 R1T NOTE) 3
Y1E ELECTRONIC EXPANSION VALVE
X31A BLK P1 P1
Z1C · Z2C NOISE FILTER (FERRITE CORE) GRN SS1
WIRED REMOTE CONTROLLER /YLW WIRED REMOTE
THERMISTOR (AIR) X18A Z2C CONTROLLER
R1T
X1A T1R N=3
SS1 SELECTOR SWITCH (MAIN/SUB) X3A
t˚ X27A
FXDQ40NB / 50NB / 63NBVET (without Drain Pump)
Y1E
V1TR
YLW
WHT
X7A
X18A X16A RED M
~
BLK Q1M
X4A M1F
A1P HAP
X1M C1 X2M
Z1C
T1R
Z2C
NOTES) CONTROL BOX
1. : TERMINAL
, : CONNECTOR
2. : FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN
3D060548
Appendix
Si30-813_A
Appendix
Si30-813_A
INDOOR UNIT R1T THERMISTOR (SUCTION AIR) R1T R2T R3T R4T
A1P PRINTED CIRCUIT R2T THERMISTOR (LIQUID) M1P M ~ Z2C GRN
t˚ t˚ t˚ t˚ S1L
BOARD R3T THERMISTOR (GAS) GRN/YLW
POWER A1P YLW YLW
A2P PRINTED CIRCUIT R4T THERMISTOR SUPPLY NOTE) 5
BOARD (FAN) (DISCHARGE AIR) N=1 RED
F1U KPR X16A X18A X17A X13A X15A
A3P PRINTED CIRCUIT R5T THERMISTOR NTC
BOARD (CAPACITOR) (CURRENT LIMITING) L L X25A
C1, C2,C 3 CAPACITOR S1L FLOAT SWITCH N BLU PNK
N T2 INPUT FROM
F1U FUSE (T, 3.15A, 250V) V1R DIODE BRIDGE ~220-240V ~220V X27A PS WHT
50Hz 60Hz X1M Z1C T1 OUTSIDE NOTE) 3
F2U FUSE (T, 5A, 250V) V2R POWER MODULE YLW
X30A F2 TRANSMISSION
F3U FUSE (T, 6.3A, 250V) X1M TERMINAL STRIP HAP ORG
F1 WIRING
F4U FUSE (T, 6.3A, 250V) (POWER SUPPLY) FOR FXMQ50 • 63 • 80 • 100 • 125 • 140PVE(6) P2 CENTRAL REMOTE
BLU
3D058783E
272
Wiring Diagrams
273
Wiring Diagrams
FXMQ200MA / 250MAVE
3D039621D
Appendix
Si30-813_A
Appendix
Si30-813_A
3D039801D
274
Wiring Diagrams
275
Wiring Diagrams
BLU
WHT
BRN
RED
X1M
ORG
SIDE WHT WIRED REMOTE
FXAQ20MA / 25MA / 32MAVE / 40MA / 50MA / 63MAVE
3D060858A
Appendix
Si30-813_A
Appendix
Si30-813_A
3D039826G
276
Wiring Diagrams
277
INDOOR UNIT
Wiring Diagrams
1 RED
X18A EMERG. NORM. P1
X3A 1 P2 R1T
Q1M THERMO SWITCH (M1F EMBEDDED) P2
2
2 WHT X5A
R1T THERMISTOR (AIR) X10A X2A X1A X11A WIRED REMOTE
3 BLK SS1
3 X27A CONTROLLER
R2T THERMISTOR (COIL) A2P (NOTE 5)
C1
RyA MAGNETIC RELAY (M1A)
RyP X24A
RyP MAGNETIC RELAY (M1P)
YLW
WHT
V1TR X20A
GRN/YLW
S1Q LIMIT SWITCH (SWING FLAP) RC TC RED M
M X25A ~
S1L FLOAT SWITCH t˚ BLK Q1M
F1F2 BLU M
M1F
SS1 SELECTOR SWITCH (EMERGENCY) BLU ~ X29A
M1P RyA MSW
V1TR PHASE CONTROL CIRCUIT ~ M1S
X1M TERMINAL STRIP X14A S1Q
X2M TERMINAL STRIP X30A X33A X35A HAP HBP
X15A S1L
RC SIGNAL RECEIVER
X35A A2P C1
TC SIGNAL TRANSMISSION CIRCUIT SS1
WIRED REMOTE CONTROLLER A1P X1
X30A X2 M
M
R1T THERMISTOR (AIR)
X24A
SS1 SELECTOR SWITCH (MAIN/SUB) CONTROL BOX
RECEIVER/DISPLAY UNIT (ATTACHED TO WIRELESS REMOTE CONTROLLER)
A3P PRINTED CIRCUIT BOARD NOTES)
A4P PRINTED CIRCUIT BOARD 1. : TERMINAL
BS1 PUSH BUTTON (ON/OFF) : CONNECTOR
H1P LIGHT EMITTING DIODE (ON-RED) 2. : FIELD WIRING
3. THE BEV UNIT SHOWS AN OUTLINE. PLEASE REFER TO A WIRING DIAGRAM OF BEV UNIT PASTING IN DETAIL.
H2P LIGHT EMITTING DIODE (TIMER-GREEN)
4. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
H3P LIGHT EMITTING DIODE (FILTER SIGN-RED) INSTALLATION MANUAL.
H4P LIGHT EMITTING DIODE (DEFROST-ORANGE) 5. X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED.
SS1 SELECTOR SWITCH (MAIN/SUB) 6. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS
SS2 SELECTOR SWITCH (WIRELESS ADDRESS SET) AND CATALOGS, ETC. BEFORE CONNECTING.
CONNECTOR FOR OPTIONAL PARTS 7. CONFIRM THE METHOD OF SETTING THE SELECTOR SWITCH (SS1, SS2) OF WIRED REMOTE CONTROLLER AND WIRELESS
X24A CONNECTOR (WIRELESS REMOTE CONTROLLER) REMOTE CONTROLLER BY INSTALLATION MANUAL AND ENGINEERING DATA, ETC.
8. SYMBOLS SHOW AS FOLLOWS:
X30A CONNECTOR (INTERFACE ADAPTOR FOR SKY AIR SERIES)
RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW GRN : GREEN BLU : BLUE
X35A CONNECTOR (GROUP CONTROL ADAPTOR)
C: 3D044973A
Appendix
Si30-813_A
BEV UNIT POWER SUPPLY
Appendix
220-240V 220V
A1P PRINTED CIRCUIT BOARD ASSY
Si30-813_A
~ ~
A1P 50Hz 60Hz
A2P POWER SUPPLY PRINTED CIRCUIT
BOARD ASSY (220-240V/16V)
A2P X2A X1A RED
F1U FUSE ( B , 10A, 250V) L
X1A F1U
HAP LIGHT EMITTING DIODE BLU Z4F N
(SERVICE MONITOR-GREEN) Z2C
X2A X4A NE N=2
R3T THERMISTOR (GAS)
SS1 SELECTOR SWITCH (M/S) 1
X3A
X1M TERMINAL STRIP (POWER)
RED TO
BEVQ71MA / 100MA / 125MAVE
TO OUTDOOR UNIT
278
Wiring Diagrams
279
Example of connection Branch with REFNET joint Branch with REFNET joint and REFNET header Branch with REFNET header
REFNET joint (A-G) REFNET joint (A·B) a
(Connection of 8 indoor units Heat pump system) Example 1 Example 2 Example 3 REFNET header
a b c d e a m
(3-piping) (2-piping) A A
B C D E
Outside unit Single outside
HP/LP gas piping Indoor unit f n p b B5 n p
side Gas piping B1
i k l B2 B3 B4 REFNET header b d f h j l
Suction gas piping BS side unit system F G
r s B B1 B2 B3 B4 B5 B6
unit Liquid piping g m o q c e g i n o
Liquid piping h j c e g i k m
1 2 3 4 5 6 7 H2
Outside unit B1 B2 B3 B4 k l o 8 1 2 3 4 5 6 7
d f h j H2 H2
Outside unit H1 8 7 Outside unit H1 8
• Piping between outside unit and BS unit H1 1 2 3 4 5 6
HP/LP gas piping BS units Indoor units Heat recovery system Cooling only Indoor units Heat recovery system Cooling only BS units Indoor units Heat recovery system Cooling only
( B1 - B4 ) ( 1 - 8 ) ( 1 - 6 ) ( 7 · 8 ) BS units ( B1 - B5 ) ( 1 - 8 ) ( 1 - 4 , 7 · 8 ) ( 5 · 6 ) ( B1 - B6 ) ( 1 - 8 ) ( 1 - 6 ) ( 7 · 8 )
(Thick line): 3-piping Suction gas piping
Liquid piping REFNET joint (A-G) a m
Example 4 a
Example 5 REFNET header Example 6 a
b c d e A REFNET header BS units
• Piping between BS unit and indoor unit, A B C D E b B5 n p BS units ( B1 - B6 )
Gas piping f l n p ( B1 - B5 )
(Thin line): 2-piping Multi outside i k B
B1 B2 B3 B4 r s c Indoor units
Liquid piping g F G e g i b d j
o q l
Example of Connection
m B1 B2 B3 B4 k l o Indoor units B1 B2
f B3 h B4 B5 B6 ( 1 - 8 )
unit system j d h j 8 H2
n
First outside h 1 2 3 4 5 6 7 H2 f ( 1 - 8 ) c e g i k m
branch 8 1 2 3 4 5 6 7 4 5 6 o Heat recovery
[∗] 1 2 3 7 H2
u Heat recovery system
t REFNET joint (A·B) 8 system ( 1 - 6 )
In case of multi outside unit system, re-read the Outside unit H1 H1 ( 1 - 4 , 7 · 8 ) Outside
r s Cooling only
[outside unit] as [the first outside branch seen from the H3 Outside unit Cooling only unit H1
BS units Indoor units Heat recovery Cooling only ( 7 · 8 )
H3 ( 5 · 6 ) H3
indoor unit side].
And BS unit is not required.
( B1 - B4 ) ( 1 - 8 ) system ( 1 - 6 ) ( 7 · 8 )
Pipe length between outside (∗) and indoor units ≤ 120m
Actual pipe length
Between outside (∗) (Example 1,4) unit 8 : a + b + c + d + e + s ≤ 120m (Example 2,5) unit 6 : a + b + l ≤ 120m, 8 : a + m + n + p ≤ 120m (Example 3,6) unit 8 : a + o ≤ 120m
Maximum and indoor units Equivalent length Equivalent pipe length between outside (∗) and indoor units ≤ 140m (Note 1) (assume equivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, BSVP100,160 is 4 m and BSVP250 is 6m.)
allowable
length Total extension length Total piping length from outside unit (∗) to all indoor units ≤ 300m
u
Between outside branch and outside unit t
(In case of multi system) Actual pipe length Piping length from outside branch to outside unit ≤ 10m Equivalent length: max 13m
r s r ≤ 10m (Equivalent length ≤ 13m)
Allowable Between outside and indoor units Difference in height Difference in height between outside and indoor units (H1) ≤ 50m (Max 40m if the outside unit is below) u+s ≤ 10m (Equivalent length ≤ 13m)
height Between indoor and indoor units Difference in height Difference in height between indoor units (H2) ≤ 15m u+t ≤ 10m (Equivalent length ≤ 13m)
and from liquid gas pipe for liquid pipes.
length Between outside and outside units Difference in height Difference in height between outside unit (main) and outside unit (sub) (H3) ≤ 2m Outside unit
Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header ) to indoor unit ≤ 40m (Note 2)
Allowable length after the branch Actual pipe length
(Example 1,4) unit 8 : b + c + d + e + s ≤ 40m (Example 2,5) unit 6 : b + l ≤ 40m, 8 :m + n + p ≤ 40m (Example 3,6) unit 8 : o ≤ 40m
How to select REFNET joint: How to select REFNET header
Refrigerant branch kit selection • When using REFNET joints at the first branch counted from the outside unit side. • Select suitable one from the table below according to the total capacity of indoor units to be connected to the downstream of REFNET header.
Choose from the following table in accordance with the capacity of the outside unit. • Be careful that 250 type cannot be connected to the downstream of REFNET header.
Refrigerant branch kits can only be (Example 1,2,4,5 : REFNET joint A )
Refrigerant branch kit name
used with R-410A. Refrigerant branch kit name Indoor capacity index
Outside unit capacity type In case of 3-tube piping In case of 2-tube piping
Heat recovery system Heat pump system
< 200 KHRP26M22H, KHRP26M33H
RWEYQ8, 10 type KHRP25A33T KHRP26A33T KHRP25M33H
RWEYQ16-20 type KHRP25A72T + KHRP25M72TP KHRP26A72T 200 ≤ x< 290 KHRP26M33H
RWEYQ24-30 type KHRP25A73T + KHRP25M73TP KHRP26A73T + KHRP26M73TP 290 ≤ x< 640 KHRP25M72H+KHRP25M72HP KHRP26M72H
• For REFNET joints other than the first branch, select the proper branch kit model based on the total capacity index. 640 ≤ KHRP25M73H+KHRP25M73HP KHRP26M73H+KHRP26M73HP
3. Example of Connection
Refrigerant branch kit name How to select an outside branch kit (Needed when the outside unit type is RWEYQ20 or more.)
Indoor capacity index
In case of 3-tube piping In case of 2-tube piping • Select from the table below according to the number of outside units.
< 200 KHRP25A22T KHRP26A22T
200 ≤ x< 290 KHRP25A33T KHRP26A33T Number of units of outside unit Heat recovery system Heat pump system
290 ≤ x< 640 KHRP25A72T+KHRP25M72TP KHRP26A72T 2 unit BHFP26MA56 BHFP22MA56
640 ≤ KHRP25A73T+KHRP25M73TP KHRP26A73T+KHRP26M73TP 3 unit BHFP26MA84 BHFP22MA84
(Example 2,5) In case of REFNET Joint B , indoor units of 7 + 8 (Example 3,6) In case of REFNET Header,
Example of downstream indoor units (Example 1,4) In case of REFNET Joint C , indoor units of 5 + 6 + 7 + 8
(Example 2,5) In case of REFNET Header, indoor units of 1 + 2 + 3 + 4 + 5 + 6 indoor units of 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Piping between outside unit (∗) and refrigerant branch kit (part A) Piping between refrigerant branch kit and refrigerant branch kit/BS unit Piping between BS unit (refrigerant branch kit) and indoor unit
Pipe size selection Piping between outside branch and outside unit (part C) Piping between BS unit and refrigerant branching kit • Match to the size of the connection piping on the indoor unit.
• Match to the size of connection piping of outside unit (Unit: mm) • Select one from the table below according to the total capacity of indoor units to be Indoor unit connection piping size (Unit:mm)
Caution connected to downstream.
Piping size (outer diameter × Min. thickness) • For the gas piping size in case of 2-tube piping between refrigerant branching
The thickness of the pipes in the table shows the requirements of Japanese Capacity type Piping size (outer diameter × minimum
kit/BS unit and refrigerant branching kit, select the size of suction gas piping.
High Pressure Gas Control low. (As of Jan. 2003) of outside unit Suction gas pipe HP/LP gas pipe Liquid pipe wall thickness)
• The size of connection piping should not exceed the refrigerant piping size selected Indoor capacity type
The thickness and material shall be selected in accordance with local code. under the generic term of the system.
RWEYQ8 φ19.1 × 0.80 φ15.9 × 0.99 (Unit: mm) Gas pipe Liquid pipe
φ 9.5 × 0.80
RWEYQ10 φ22.2 × 0.80 φ19.1 × 0.80 Piping size (outer diameter × minimum wall thickness)
For a multi outside unit system, make the settings in accordance with 20, 25, 32, 40, 50 type φ12.7 × 0.80 φ6.4 × 0.80
RWEYQ16 φ12.7 × 0.80 Indoor capacity index
the following figure. φ28.6 × 0.99 φ22.2 × 0.80 Suction gas pipe HP/LP gas pipe Liquid pipe 63, 80, 100, 125 type φ15.9 × 0.99 φ9.5 × 0.80
RWEYQ18, 20 φ15.9 × 0.99
Piping between outside unit (∗) and refrigerant branch kit (part A) 200 type φ19.1 × 0.80
RWEYQ24 < 150 φ15.9 × 0.99 φ12.7 × 0.80 φ9.5 × 0.80
φ34.9 × 1.21 φ28.6 × 0.99 φ19.1 × 0.80 250 type φ22.2 × 0.80
Piping between outside branches (part B) RWEYQ26-30 150 ≤ x< 200 φ19.1 × 0.80 φ15.9 × 0.99 φ 9.5 × 0.80
200 ≤ x< 290 φ22.2 × 0.80
Piping between outside branch and outside unit (part C) Piping between outside branches (part B) φ19.1 × 0.80
290 ≤ x< 420 φ28.6 × 0.99 φ12.7 × 0.80
• Select the size from the following table based on the total capacity of the
outside unit to be connected to upstream (Unit: mm) 420 ≤ x< 640 φ28.6 × 0.99 φ15.9 × 0.99
640 ≤ x< 920 φ34.9 × 1.21 φ28.6 × 0.99
Piping size (outer diameter × Min. thickness) φ19.1 × 0.80
Total capacity 920 ≤ φ41.3 × 1.43
of outside unit Suction gas pipe HP/LP gas pipe Liquid pipe
Appendix
3P1538978P
Si30-813_A
Note 1. System Liquid pipe
When the equivalent pipe length between outside and indoor units is 80m or
RWEYQ8, 10PY1 φ9.5 → φ12.7
more, the size of main pipes on the liquid side (refer to figure 21) must be
RWEYQ16PY1 φ12.7 → φ15.9
increased according to the right table. RWEYQ18 ~ 24PY1 φ15.9 → φ19.1
Appendix
(Never increase suction gas pipe and HP/LP gas pipe.) RWEYQ26 ~ 30PY1 φ19.1 → φ22.2
Si30-813_A
Indoor unit
Increase only liquid pipe size
Note 2. Allowable length after the first refrigerant branch kit to indoor units is 40m or less, however it can be extended up to 90m if all the following conditions are satisfied. (In case of “Branch with REFNET joint”)
2. For calculation of Total extension length, the actual length of a+b×2+c×2+d×2+e×2+f×2+g×2 REFNET joint (A-G)
above pipes must be doubled. (except main pipe and the pipes + h + i + j + k + l + m + n + p ≤ 300 m
that are not increased)
a b c d e f g
A B C D E F G
3. Indoor unit to the nearest branch kit ≤ 40 m h, i, j....... p ≤ 40 m
p
4. The difference between The farthest indoor unit 8 h i j k l m n
1 2 3 4 5 6 7
[Outside unit to the farthest indoor unit] and [Outside unit to The nearest indoor unit 1 8
the nearest indoor unit] ≤ 40 m ( a + b + c + d + e + f + g + p ) - ( a + h ) ≤ 40 m Outside unit Indoor units ( 1 - 8 )
*If available on the site, use this size. Otherwise it can not be increased.
Example of Connection
280
3P153897-8P
Precautions for New Refrigerant (R-410A) Si30-813_A
281 Appendix
Si30-813_A Precautions for New Refrigerant (R-410A)
Temperature Steam pressure Density Specific heat at constant Specific enthalpy Specific entropy
(˚C) (kPa) (kg/m3 ) pressure (kJ/kgK) (kJ/kg) (kJ/KgK)
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Appendix 282
Precautions for New Refrigerant (R-410A) Si30-813_A
Cylinder
Siphon tube
Refrigerant can be charged in liquid state with cylinder in
upright position.
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high pressure gases. Be sure to follow the regulations.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same way as any other high pressure gases.
It should also be noted that high pressure vessels are equipped with safety devices that
releases gas when the outdoor air temperature reaches more than a certain level (fusible
plug melts) and when the pressure exceeds a certain level (spring-type safety valve
operates).
283 Appendix
Si30-813_A Precautions for New Refrigerant (R-410A)
Tool compatibility
Compatibility
Tool HFC HCFC Reasons for change
R-410A R-407C R-22
• Do not use the same tools for R-22 and
Gauge manifold R-410A.
Charge hose • Thread specification differs for R-410A
and R-407C.
Charging cylinder { • Weighting instrument used for HFCs.
Gas detector { • The same tool can be used for HFCs.
Vacuum pump • To use existing pump for HFCs,
(pump with reverse flow { vacuum pump adaptor must be
preventive function) installed.
Weighting instrument {
• Seal material is different between R-22
Charge mouthpiece and HFCs.
• Thread specification is different
between R-410A and others.
Flaring tool (Clutch type) { • For R-410A, flare gauge is necessary.
Torque wrench { • Torque-up for 1/2 and 5/8
Pipe cutter {
Pipe expander {
Pipe bender {
Refrigerant piping See the chart below. • Only φ19.1 is changed to 1/2H material
while the previous material is "O".
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
∗ O: Soft (Annealed)
H: Hard (Drawn)
Appendix 284
Precautions for New Refrigerant (R-410A) Si30-813_A
1. Flaring tool
Flare gauge
Specifications
• Dimension A
Unit: mm
+0
Tube O.D. A -0.4
Nominal size
Do Class-2 (R-410A) Class-1 (Conventional)
1/4 6.35 9.1 9.0
3/8 9.52 13.2 13.0
1/2 12.70 16.6 16.2
5/8 15.88 19.7 19.4
3/4 19.05 24.0 23.3
Differences
• Change of dimension A
Dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
285 Appendix
Si30-813_A Precautions for New Refrigerant (R-410A)
2. Torque wrench
Specifications
• Dimension B Unit: mm
Nominal size Class-1 Class-2 Previous
1/2 24 26 24
5/8 27 29 27
No change in tightening torque
No change in pipes of other sizes
Differences
• Change of dimension B
Only 1/2", 5/8" are extended
Dimension B
Specifications
• Discharge speed z Maximum degree of vacuum
50 l/min (50Hz) Select a vacuum pump which is able to keep
60 l/min (60Hz) the vacuum degree of the system in excess of
• Suction port UNF7/16-20(1/4 Flare) –100.7 kPa (5 torr – 755 mmHg).
UNF1/2-20(5/16 Flare) with adaptor
Differences
• Equipped with function to prevent reverse oil flow
• Previous vacuum pump can be used by installing adaptor.
Appendix 286
Precautions for New Refrigerant (R-410A) Si30-813_A
4. Leak tester
Specifications
• Hydrogen detecting type, etc.
• Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
• Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
• Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
• Offers high rust resistance and stability over long period of time.
Differences
• Can be used for R-410A and R-22 units.
Specifications
• High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
• Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
• 1/4" → 5/16" (2min → 2.5min)
• No oil is used in pressure test of gauges.
→ For prevention of contamination
287 Appendix
Si30-813_A Precautions for New Refrigerant (R-410A)
• Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
• Change in pressure
• Change in service port diameter
Specifications
• Working pressure 5.08 MPa (51.8 kg/cm2)
• Rupture pressure 25.4 MPa (259 kg/cm2)
• Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
• Pressure proof hose
• Change in service port diameter
• Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
• Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
• The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Appendix 288
Revision History
Month / Year Version Revised contents
12/2008 Si30-813 –
Organization: Organization:
DAIKIN INDUSTRIES, LTD. DAIKIN INDUSTRIES
AIR CONDITIONING MANUFACTURING DIVISION (THAILAND) LTD. All of the Daikin Group’s business
Scope of Registration: Scope of Registration: facilities and subsidiaries in Japan
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF THE DESIGN/DEVELOPMENT are certified under the ISO 14001
COMMERCIAL AIR CONDITIONING, HEATING, COOLING, AND MANUFACTURE OF AIR international standard for
REFRIGERATING EQUIPMENT, HEATING EQUIPMENT, CONDITIONERS AND THE environment management.
RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT COMPONENTS INCLUDING
JMI-0107 RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, JQA-1452 COMPRESSORS USED FOR THEM
COMPRESSORS AND VALVES.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
zSpecifications, designs and other content appearing in this brochure are current as of August 2011 but subject to change without notice.
Si30-813_A
Printed in Japan 08/2011 AK.K