Daikin VRV3 PDF
Daikin VRV3 PDF
Daikin VRV3 PDF
Service Manual /
R-410A RX(Y)MQ4·5·6PVE
RX(Y)MQ4·5·6PVE
R-410A
Heat Pump 50/60Hz
Si34-603
Cooling Only 50/60Hz
July
R-410A
Heat Pump / Cooling Only
50/60Hz
1. Introduction .............................................................................................v
1.1 Safety Cautions ........................................................................................v
1.2 PREFACE ............................................................................................... ix
Part 5 Function............................................................................ 47
1. Operation Mode ....................................................................................48
2. Basic Control.........................................................................................49
2.1 Normal Operation ...................................................................................49
2.2 Compressor PI Control...........................................................................50
2.3 Electronic Expansion Valve PI Control...................................................51
2.4 Cooling Operation Fan Control...............................................................52
3. Special Control......................................................................................53
3.1 Startup Control .......................................................................................53
3.2 Oil Return Operation ..............................................................................54
3.3 Defrosting Operation ..............................................................................56
3.4 Pump-down Residual Operation ............................................................57
3.5 Restart Standby......................................................................................58
3.6 Stopping Operation ................................................................................59
Table of Contents i
Si34-603
ii Table of Contents
Si34-603
Index ............................................................................................. i
iv Table of Contents
Si34-603 Introduction
1. Introduction
1.1 Safety Cautions
Cautions and Be sure to read the following safety cautions before conducting repair work.
Warnings The caution items are classified into “ Warning” and “ Caution”. The “ Warning”
items are especially important since they can lead to death or serious injury if they are not
followed closely. The “ Caution” items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an
electrical shook.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas discharges during the repair work, do not touch the
discharging refrigerant gas.
The refrigerant gas can cause frostbite.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
v
Introduction Si34-603
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
vi
Si34-603 Introduction
Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
vii
Introduction Si34-603
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get
Caution an unexpected result or has to restart (part of) a procedure.
Warning
viii
Si34-603 Introduction
1.2 PREFACE
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2006 VRVIII-S series Heat Pump / Cooling
Only System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVIII-S series R-410A
Heat Pump / Cooling Only System.
July, 2006
ix
Introduction Si34-603
x
Si34-603
Part 1
General Information
General Information 1
Model Names of Indoor/Outdoor Units Si34-603
FXDQ-
NVET 20N 25N 32N 40N 50N 63N — — — VE *1
Ceiling Mounted FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M
Built-In Type
Ceiling Suspended
Cassette Type FXUQ — — — — — — 71MA 100MA 125MA V1
Connection Unit
BEVQ- — — — — — — 71MA 100MA 125MA VE *1
M(A)
Note:FXDQ has following 2 Series, as shown below.
FXDQ-P, N(A)VET: without Drain Pump (For General, Asia: except for EU, China and Australia)
FXDQ-P, N(A)VE: with Drain Pump
BEV unit is required for each indoor unit.
*1 VE:1φ, 220~240V, 50Hz, 1φ, 220V, 60Hz
V1:1φ, 220~240V, 50Hz
Outdoor Units
Series Model Name Power Supply
2 General Information
Si34-603 External Appearance
2. External Appearance
2.1 Indoor Units
Ceiling Mounted Cassette Type (Double Flow) Ceiling Suspended Type
FXCQ20M FXHQ32MA
FXCQ25M FXHQ63MA
FXCQ32M FXHQ100MA
FXCQ40M
FXCQ50M
FXCQ63M
FXCQ80M
FXCQ125M
Ceiling Mounted Cassette Type (Multi Flow) Wall Mounted Type
FXFQ25M FXAQ20MA
FXFQ32M FXAQ25MA
FXFQ40M FXAQ32MA
FXFQ50M FXAQ40MA
FXFQ63M FXAQ50MA
FXFQ80M FXAQ63MA
FXFQ100M
FXFQ125M
Ceiling Mounted Cassette Corner Type Floor Standing Type
FXKQ25MA FXLQ20MA
FXKQ32MA FXLQ25MA
FXKQ40MA FXLQ32MA
FXKQ63MA FXLQ40MA
FXLQ50MA
FXLQ63MA
General Information 3
Capacity Range Si34-603
3. Capacity Range
Outdoor Units
Capacity Range 4HP 5HP 6HP
RX(Y)MQ 4P 5P 6P
No of Indoor
Units to be 6 8 9
Connected
Total Capacity
Index of Indoor 50~130 62.5~162.5 70~182
Units to be
Connected
Indoor Units
Capacity Range 0.8HP 1HP 1.25HP 1.6HP 2HP 2.5HP 3.2HP 4HP 5HP
Capacity Index 20 25 31.25 40 50 62.5 80 100 125
Ceiling Mounted
Cassette Type FXCQ 20M 25M 32M 40M 50M 63M 80M — 125M
(Double Flow)
Ceiling Mounted
Cassette Type FXFQ — 25M 32M 40M 50M 63M 80M 100M 125M
(Multi Flow)
Ceiling Mounted
Cassette Corner Type FXKQ — 25MA 32MA 40MA — 63MA — — —
Ceiling Mounted
Duct Type FXMQ — — — 40MA 50MA 63MA 80MA 100MA 125MA
Ceiling Suspended
Type FXHQ — — 32MA — — 63MA — 100MA —
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA — — —
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — —
Concealed Floor
Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — —
Ceiling Suspended
Cassette Type FXUQ — — — — — — 71MA 100MA 125MA
4 General Information
Si34-603
Part 2
Specifications
1. Specifications ..........................................................................................6
1.1 Outdoor Units ...........................................................................................6
1.2 Indoor Units ............................................................................................10
Specifications 5
Specifications Si34-603
1. Specifications
1.1 Outdoor Units
Heat Pump 50/60Hz <RXYMQ-PVE>
Model Name RXYMQ4PVE RXYMQ5PVE
kcal / h 9,600 12,000
1 Cooling Capacity Btu / h 38,200 47,800
kW 11.2 14.0
kcal / h 10,800 13,800
2 Heating Capacity Btu / h 42,700 54,600
kW 12.5 16.0
Casing Color Ivory White Ivory White
Dimensions: (H×W×D) mm 1,345×900×320 1,345×900×320
Heat Exchanger Cross Fin Coil Cross Fin Coil
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m³/h 19.36 19.36
Comp. Number of Revolutions r.p.m 6,480 6,480
Motor Output×Number kW 2.5×1 3.0×1
of Units
Starting Method Direct on line Direct on line
Type Propeller Fan Propeller Fan
Motor Output W 70×2 70×2
Fan
Air Flow Rate m³/min 106 106
Drive Direct Drive Direct Drive
Connecting Liquid Pipe mm φ9.5 (Flare Connection) φ9.5 (Flare Connection)
Pipes Gas Pipe mm φ15.9 (Flare Connection) φ15.9 (Flare Connection)
Machine Weight kg 125 125
Safety Devices High Pressure Switch, Fan Driver Overload Protector, High Pressure Switch, Fan Driver Overload Protector,
Inverter Overload Protector, Fusible Plugs, Fuse Inverter Overload Protector, Fusible Plugs, Fuse
Defrost Method Reverse cycle defrosting Reverse cycle defrosting
Capacity Control % 24~100 24~100
Refrigerant Name R-410A R-410A
Refrigerant Charge kg 4.0 4.0
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator DAPHNE FVC68D DAPHNE FVC68D
Oil Charge Volume L 1.5 1.5
Standard Accessories Installation Manual, Operation Manual, Clamps Installation Manual, Operation Manual, Clamps
Drawing No. C: 4D052608
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference cfm=m³/min×35.3
: 0m.
6 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference cfm=m³/min×35.3
: 0m.
Specifications 7
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m. kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
8 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m. kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Specifications 9
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
10 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications 11
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
12 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications 13
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
14 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Specifications 15
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
16 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Specifications 17
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
18 Specifications
Si34-603 Specifications
Slim Ceiling Mounted Duct Type (PVE: with Drain Pump PVET: without Drain Pump)
Model FXDQ20PVE FXDQ25PVE FXDQ32PVE
FXDQ20PVET FXDQ25PVET FXDQ32PVET
kcal/h 2,000 2,500 3,200
1 Cooling Capacity (19.5°CWB) Btu/h 7,800 9,900 12,600
kW 2.3 2.9 3.7
2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
kcal/h 2,200 2,800 3,400
3 Heating Capacity Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm 200×900×620 200×900×620 200×900×620
Coil (Cross Rows×Stages×Fin Pitch mm 2×12×1.5 2×12×1.5 2×12×1.5
Fin Coil) Face Area m² 0.176 0.176 0.176
Model — — —
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × Number W 62×1 62×1 62×1
Fan of Units
Air Flow Rate (H/L) m³/min 9.5/7.5 9.5/7.5 10.5/8.5
External Static Pressure Pa 44-15 5 44-15 5 44-15 5
Drive Direct Drive Direct Drive Direct Drive
Temperature Control Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat
for Cooling and Heating for Cooling and Heating for Cooling and Heating
Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene
Air Filter Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection)
Piping Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Connections
Drain Pipe mm VP20 VP20 VP20
(External Dia. 26 Internal Dia. 20) (External Dia. 26 Internal Dia. 20) (External Dia. 26 Internal Dia. 20)
Machine Weight (Mass) kg 26 26 26
6 Sound Level (H/L) dBA 33/29 33/29 33/29
Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Operation Manual, Operation Manual, Operation Manual,
Installation Manual, Warranty, Installation Manual, Warranty, Installation Manual, Warranty,
Standard Accessories Drain Hose, Sealing Pads, Clamps, Drain Hose, Sealing Pads, Clamps, Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting, Washers, Insulation for Fitting, Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate, Clamp Metal, Washer Fixing Plate, Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter Screws for Duct Flanges, Air Filter Screws for Duct Flanges, Air Filter
Drawing No. 3D052136
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Specifications 19
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard -Low static pressure”.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
20 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard -Low static pressure”.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Specifications 21
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard”.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
22 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure-Standard".
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Specifications 23
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure-Standard".
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
24 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications 25
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length:7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
26 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications 27
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
28 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications 29
Specifications Si34-603
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
30 Specifications
Si34-603 Specifications
Notes:
Conversion Formulae
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m. kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
cfm=m³/min×35.3
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications 31
Specifications Si34-603
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Conversion Formulae
difference: 0m.
kcal/h=kW×860
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level Btu/h=kW×3412
difference: 0m. cfm=m³/min×35.3
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
32 Specifications
Si34-603 Specifications
BEV Units
Model BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE
Power Supply 1 Phase 50Hz 220~240V 1 Phase 50Hz 220~240V 1 Phase 50Hz 220~240V
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm 100×350×225 100×350×225 100×350×225
Sound Absorbing Thermal Insulation Material Flame and Heat Resistant Foamed Flame and Heat Resistant Foamed Flame and Heat Resistant Foamed
Polyethylene Polyethylene Polyethylene
Indoor Liquid Pipes 9.5mm (Flare Connection) 9.5mm (Flare Connection) 9.5mm (Flare Connection)
Unit Gas Pipes 15.9mm (Flare Connection) 15.9mm (Flare Connection) 15.9mm (Flare Connection)
Piping
Connection Liquid Pipes 9.5mm (Flare Connection) 9.5mm (Flare Connection) 9.5mm (Flare Connection)
Outdoor
Unit Suction Gas Pipes 15.9mm (Flare Connection) 15.9mm (Flare Connection) 15.9mm (Flare Connection)
Machine Weight (Mass) kg 3.0 3.0 3.5
Installation manual, Gas piping Installation manual, Gas piping Installation manual, Gas piping
Standard Accessories connections, Insulation for fitting, connections, Insulation for fitting, connections, Insulation for fitting,
Sealing material, Clamps Sealing material, Clamps Sealing material, Clamps
Drawing No. 4D045387A 4D045387A 4D045388A
Specifications 33
Specifications Si34-603
34 Specifications
Si34-603
Part 3
List of Electrical and
Functional Parts
Model
Parts Name Symbol FXCQ FXCQ FXCQ FXCQ FXCQ FXCQ FXCQ FXCQ Remark
20MVE 25MVE 32MVE 40MVE 50MVE 63MVE 80MVE 125MVE
Wired Remote BRC1C62
Remote Controller
Controller Option
Wireless Remote BRC7C62
Controller
AC 220~240V 50Hz
1φ10W 1φ15W 1φ20W 1φ30W 1φ50W 1φ85W
Fan Motor M1F
Thermal protector 135°C : OFF
Thermal Fuse 152°C — 87°C : ON
Motors
AC220-240V (50Hz) AC220V (60Hz)
Drain Pump M1P PLD-12230DM
Thermal Fuse 145°C
Model
Parts Name Symbol FXKQ FXKQ FXKQ FXKQ Remark
25MAVE 32MAVE 40MAVE 63MAVE
Wired Remote BRC1C62 Option
Remote Controller
Controller Wireless Remote BRC4C61
Controller
AC 220~240V 50Hz
Model
Parts Name Symbol FXDQ FXDQ FXDQ FXDQ FXDQ FXDQ Remark
20N(A)VE(T), 25N(A)VE(T), 32N(A)VE(T),
PVE(T) PVE(T) PVE(T) 40N(A)VE(T) 50N(A)VE(T) 63N(A)VE(T)
Wired Remote
Controller BRC1C62
Remote Option
Controller Wireless Remote BRC4C62
Controller
AC 220~240V 50Hz
Model
Parts Name Symbol FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ Remark
20MVE 25MVE 32MVE 40MVE 50MVE 63MVE 80MVE 100MVE 125MVE
Wired Remote BRC1C62
Remote Controller
Controller Option
Wireless Remote BRC4C62
Controller
AC 220~240V 50Hz
Model
Parts Name Symbol FXMQ FXMQ FXMQ FXMQ FXMQ FXMQ Remark
40MAVE 50MAVE 63MAVE 80MAVE 100MAVE 125MAVE
Wired Remote
Controller BRC1C62
Remote Option
Controller Wireless Remote
Controller BRC4C62
AC 220~240V 50Hz
Fan Motor M1F 1φ100W 1φ160W 1φ270W 1φ430W
Motors Thermal protector 135°C : OFF 87°C : ON
Model
Parts Name Symbol FXHQ FXHQ FXHQ Remark
32MAVE 63MAVE 100MAVE
Wired Remote BRC1C62 Option
Remote Controller
Controller
Wireless Controller BRC7E63W
AC 220~240V/220V 50Hz/60Hz
Fan Motor M1F 1φ63W 1φ130W
Thermal protector 130°C : OFF 80°C : ON
Motors
Capacitor for Fan Motor C1R 3.0µF-400V 9.0µF-400V
Swing Motor M1S MT8-L[3P058751-1]
AC200~240V
Model
Parts Name Symbol FXAQ FXAQ FXAQ FXAQ FXAQ FXAQ Remark
20MAVE 25MAVE 32MAVE 40MAVE 50MAVE 63MAVE
Wired Remote BRC1C62
Remote Controller
Option
Controller Wireless Remote BRC7E618
Controller
AC 220~240V 50Hz
Fan Motor M1F 1φ40W 1φ43W
Motors Thermal protector 130°C : OFF 80°C : ON
Model
Parts Name Symbol FXLQ FXLQ FXLQ FXLQ FXLQ FXLQ Remark
20MAVE 25MAVE 32MAVE 40MAVE 50MAVE 63MAVE
Wired Remote BRC1C62
Remote Controller
Controller Option
Wireless Remote BRC4C62
Controller
AC 220~240V 50Hz
Fan Motor M1F 1φ15W 1φ25W 1φ35W
Motors
Thermal protector 135°C : OFF 120°C : ON
Capacitor for Fan Motor C1R 1.0µF-400V 0.5µF-400V 1.0µF-400V 1.5µF-400V 2.0µF-400V
Model
Parts Name Symbol FXNQ FXNQ FXNQ FXNQ FXNQ FXNQ Remark
20MAVE 25MAVE 32MAVE 40MAVE 50MAVE 63MAVE
Wired Remote
Controller BRC1C62
Remote
Controller Option
Wireless Remote
Controller BRC4C62
AC 220~240V 50Hz
Fan Motor M1F 1φ15W 1φ25W 1φ35W
Motors
Thermal protector 135°C : OFF 120°C : ON
Capacitor for Fan Motor C1R 1.0µF-400V 0.5µF-400V 1.0µF-400V 1.5µF-400V 2.0µF-400V
Model
Parts Name Symbol Remark
FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
Wired Remote
Controller BRC1C62
Remote Option
Controller Wireless Remote
Controller BRC7C528W
AC 220~240V 50Hz
Fan Motor M1F 1φ45W 1φ90W
Thermal protector 130°C Thermal protector 130°C : OFF 83°C : ON
Motors
Drain Pump M1P AC220-240V (50Hz) AC220V (60Hz)
PJV-1426
Part 4
Refrigerant Circuit
Refrigerant Circuit 43
Refrigerant Circuit Si34-603
1. Refrigerant Circuit
1.1 RX(Y)MQ4 / 5 / 6P
No. in
refrigerant Symbol Name Major Function
system
diagram
Inverter compressor is operated on frequencies between 36 Hz and 195 Hz by using
A M1C Inverter compressor (INV) the inverter.
31 steps
D M1F Inverter fan Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
M2F speed by using the inverter.
E Y1E Electronic expansion valve While in heating operation, PI control is applied to keep the outlet superheated degree
(Main: EV1) of air heat exchanger constant.
F Y3E Electronic expansion valve Pl control is applied to keep the outlet superheated degree of subcooling heat
(Subcool: EV3) exchanger constant.
G Y2S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
H Y3S Solenoid valve (Unload circuit Used to the unloading operation of compressor.
SVUL)
M Y1S Four way valve Used to switch the operation mode between cooling and heating.
N S1NPH High pressure sensor Used to detect high pressure.
O S1NPL Low pressure sensor Used to detect low pressure.
HP pressure switch (For INV In order to prevent the increase of high pressure when a malfunction occurs, this
P S1PH compressor) switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.
In order to prevent the increase of pressure when abnormal heating is caused by fire
S — Fusible plug or others, the fusible part of the plug is molten at a temperature of 70 to 75°C to
release the pressure into the atmosphere.
Pressure regulating valve 1 This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
T — (Receiver to discharge pipe) resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
1 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2 R2T Thermistor (INV discharge used to detect discharge pipe temperature, make the temperature protection control of
pipe: Tdi) compressor, and others.
3 R3T Thermistor used to detect suction pipe temperature, keep the suction superheated degree
(Suction pipe1: Ts1) constant in heating operation, and others.
Thermistor (Heat exchanger Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
4 R4T deicer: Tb) operation, and others.
Thermistor
5 R5T (Suction pipe2: Ts2) Used to the calculation of an internal temperature of compressor etc.
6 R6T Thermistor (Subcooling heat Used to control of subcooling electronic expansion valve.
exchanger gas pipe: Tsh)
7 R7T Thermistor Used to detect refrigerant over charge in check operation, and others.
(Liquid pipe: Tl)
44 Refrigerant Circuit
Si34-603 Refrigerant Circuit
G
N
D
M
D
P
E
H
S
A
F
C : 3D052627A
Refrigerant Circuit 45
Functional Parts Layout Si34-603
THERMISTOR (SUCTION 2)
R5T
(MARKING COLOR:GREEN)
46 Refrigerant Circuit
Si34-603
Part 5
Function
1. Operation Mode ....................................................................................48
2. Basic Control.........................................................................................49
2.1 Normal Operation ...................................................................................49
2.2 Compressor PI Control...........................................................................50
2.3 Electronic Expansion Valve PI Control...................................................51
2.4 Cooling Operation Fan Control...............................................................52
3. Special Control......................................................................................53
3.1 Startup Control .......................................................................................53
3.2 Oil Return Operation ..............................................................................54
3.3 Defrosting Operation ..............................................................................56
3.4 Pump-down Residual Operation ............................................................57
3.5 Restart Standby......................................................................................58
3.6 Stopping Operation ................................................................................59
4. Protection Control .................................................................................60
4.1 High Pressure Protection Control...........................................................60
4.2 Low Pressure Protection Control............................................................61
4.3 Discharge Pipe Protection Control .........................................................62
4.4 Inverter Protection Control .....................................................................63
5. Other Control.........................................................................................64
5.1 Demand Operation .................................................................................64
5.2 Heating Operation Prohibition ................................................................64
6. Outline of Control (Indoor Unit) .............................................................65
6.1 Drain Pump Control................................................................................65
6.2 Louver Control for Preventing Ceiling Dirt..............................................67
6.3 Thermostat Sensor in Remote Controller...............................................68
6.4 Freeze Prevention ..................................................................................70
6.5 View of Operations of Swing Flaps ........................................................71
6.6 Electronic Expansion Valve Control .......................................................72
6.7 Hot Start Control (In Heating Operation Only)........................................72
Function 47
Operation Mode Si34-603
1. Operation Mode
Operation in
stop mode
Malfunction/
Standby
Indoor unit stop or
Startup control thermostat OFF
• Cooling startup Pump-down
control residual
• Heating startup Indoor unit thermostat ON
operation
control
Malfunction/Standby
Cooling or heating
operation
Malfunction/
Standby
No
Defrost IN Yes
Defrosting operation
conditions are met.
No
Operation Yes
mode change
No Note:
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
(V3152)
48 Function
Si34-603 Basic Control
2. Basic Control
2.1 Normal Operation
Cooling Operation
Actuator Operation Remarks
Used for high pressure protection control, low
pressure protection control, discharge pipe
Compressor Compressor PI control temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan Cooling fan control
Four way valve OFF
Main electronic expansion valve (EV1) 480 pls
Subcooling electronic expansion valve PI control
(EV3)
Hot gas bypass valve (SVP) OFF This valve turns on with low pressure protection
control.
Heating Operation
Actuator Operation Remarks
Used for high pressure protection control, low
pressure protection control, discharge pipe
Compressor Compressor PI control temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan STEP 7 or 8
Four way valve ON
Main electronic expansion valve (EV1) PI control
Subcooling electronic expansion valve PI control
(EV3)
This valve turns on with low pressure protection
Hot gas bypass valve (SVP) OFF control.
Function 49
Basic Control Si34-603
[Cooling operation]
Controls compressor capacity to adjust Te to Te : Low pressure equivalent saturation temperature
achieve target value (TeS). (°C)
Te setting (Set in Set-up mode 2) TeS : Target Te value
(Varies depending on Te setting, operating
L M (Normal) H frequency, etc.)
(factory
setting)
3 6 9
[Heating operation]
Controls compressor capacity to adjust Tc to Tc : High pressure equivalent saturation temperature
achieve target value (TcS). (°C)
Tc setting TcS : Target Tc value
L M (Normal) H (Varies depending on Tc setting, operating
(factory frequency, etc.)
setting)
43 46 49
RXYMQ4 · 5 · 6P
STn INV(Fullload) INV(Unload) STn INV(Fullload) INV(Unload) STn INV(Fullload) INV(Unload)
1 36.0Hz 11 80.0Hz 21 140.0Hz
2 39.0Hz 12 86.0Hz 22 146.0Hz
3 43.0Hz 13 92.0Hz 23 152.0Hz
4 47.0Hz 14 98.0Hz 24 158.0Hz
5 52.0Hz 15 104.0Hz 25 164.0Hz
6 52.0Hz 57.0Hz 16 110.0Hz 26 170.0Hz
7 57.0Hz 64.0Hz 17 116.0Hz 27 175.0Hz
8 62.0Hz 71.0Hz 18 122.0Hz 28 180.0Hz
9 68.0Hz 78.0Hz 19 128.0Hz 29 185.0Hz
10 74.0Hz 20 134.0Hz 30 190.0Hz
31 195.0Hz
∗ Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Selection of full load operation to/from unload operation is made with the unload circuit solenoid valve
(Y3S=SVUL). The full load operation is performed with the SVUL set to OFF, while the unload operation is
performed with the SVUL set to ON.
50 Function
Si34-603 Basic Control
Function 51
Basic Control Si34-603
Pc<2.75MPa Pc>3.24MPa
PI control
Lapse of 20 sec.
PI control
-1 step on Hold the +1 step on
current step on
outdoor unit fan outdoor unit fan outdoor unit fan
PI control Lapse of 20 sec.
Fan Steps
52 Function
Si34-603 Special Control
3. Special Control
3.1 Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
Thermostat ON
Outdoor unit fan STEP7 Ta<20°C: OFF +1 step/15 sec. (when Pc>2.16MPa)
Ta≥20°C: STEP4 -1 step/15 sec. (when Pc<1.77MPa)
Four way valve (20S1) Holds OFF OFF
Main electronic expansion 0 pls 480 pls 480 pls
valve (EV1)
Subcooling electronic 0 pls 0 pls 0 pls
expansion valve (EV3)
Hot gas bypass valve OFF OFF OFF
(SVP)
Subcooling electronic
expansion valve (EV3) 0 pls 0 pls 0 pls
Function 53
Special Control Si34-603
Take the current step as the 52 Hz Full load Same as the “oil return
Compressor upper limit. (→ Low pressure constant operation” mode.
control)
Outdoor unit fan Fan control (Normal cooling) Fan control (Normal cooling) Fan control (Normal cooling)
Four way valve OFF OFF OFF
Main electronic expansion valve
(EV1) 480 pls 480 pls 480 pls
• 3 min. • 3 min.
Ending conditions 20 sec. or • Ts - Te<5°C or • Pe<0.6MPa
• HTdi>110°C
54 Function
Si34-603 Special Control
* From the preparing oil-returning operation to the oil-returning operation, and from the oil-
returning operation to the operation after oil-returning, the compressor stops for 1 minute to
reduce noise on changing of the four way valve.
Function 55
Special Control Si34-603
* From the preparing operation to the defrost operation, and from the defrost operation to the
operation after defrost, the compressor stops for 1 minute to reduce noise on changing of the
four way valve.
56 Function
Si34-603 Special Control
Function 57
Special Control Si34-603
58 Function
Si34-603 Special Control
Function 59
Protection Control Si34-603
4. Protection Control
4.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
Pc>3.64MPa
When occurring 10 times within 60
High pressure minutes, HPS is activated without high
standby pressure standby, thus outputting the
malfunction code "E3".
[In heating operation]
High-pressure drop
Pc>3.04MPa
High pressure not limited
Pc: HP pressure sensor detection value
Pc<2.89MPa
Pc>3.64MPa
When occurring 10 times within 60
High pressure minutes, HPS is activated without high
standby pressure standby, thus outputting the
malfunction code "E3".
60 Function
Si34-603 Protection Control
Pe<0.25MPa Pe>0.39MPa
Low pressure
Hot gas SVP = OFF
limited
Pe<0.15MPa Pe>0.30MPa
36Hz Unload
Pe<0.07MPa
or • Ts-Teg<8deg
&
• Pe>0.06MPa
Pe< 0.07MPa
Function 61
Protection Control Si34-603
[INV compressor]
or HTdi>135˚C
36 Hz Unload HTdi>120˚C for 10 min. or more.
62 Function
Si34-603 Protection Control
Not limited
Limited
Status quo
Not limited
•Tfin<75 ˚C
Tfin≥78˚C & •INV upper limit frequency=max Hz
Limited
Status quo
Tfin≤75˚C
continues for 3 min. Without conditions
INV upper limit frequency:
1-step up from current
compressor frequency
Tfin≥83˚C
Function 63
Other Control Si34-603
5. Other Control
5.1 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting”.
[Demand 1 setting]
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%
Other protection control functions have precedence over the above operation.
64 Function
Si34-603 Outline of Control (Indoor Unit)
6.1.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
∗ 1. The objective of residual operation is to completely drain any moisture adhering to the fin of
the indoor unit heat exchanger when the thermostat goes off during cooling operation.
6.1.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF:
Function 65
Outline of Control (Indoor Unit) Si34-603
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.1.4 When the Float Switch is Tripped and “AF” is Displayed on the
Remote Controller:
Note: If the float switch is tripped five times in succession, a drain malfunction is determined to have
occurred. “AF” is then displayed as operation continues.
66 Function
Si34-603 Outline of Control (Indoor Unit)
Existing position
P0
P1
P2
P3
P4
P1 P1
P0' P2
P2
P3 P1' P4 P0''
P4 P1''
P4 P2'
P2''
P3'
P4' P4'' P3''
Draft
prevention P0 P1 P2 P3 P4 Same as existing position
position
Range of direction adjustment
Function 67
Outline of Control (Indoor Unit) Si34-603
Cooling If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
And, assuming suction temperature has changed from 30°C to 18°C (F → A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F → D).
Remote controller thermostat sensor is used for temperatures from 25°C to 21°C (D → B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B → A).
68 Function
Si34-603 Outline of Control (Indoor Unit)
Heating When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesn’t become cold by widening the range in which thermostat sensor in remote
controller can be used so that suction temperature is higher than the preset temperature.
And, assuming suction temperature has changed from 28°C to 18°C (D → A):
Remote controller thermostat sensor is used for temperatures from 28°C to 23°C (D → B).
Body thermostat sensor is used for temperatures from 23°C to 18°C (B → A).
Function 69
Outline of Control (Indoor Unit) Si34-603
70 Function
Si34-603 Outline of Control (Indoor Unit)
Function 71
Outline of Control (Indoor Unit) Si34-603
LL
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
OFF
setting
Po (Horizontal)
72 Function
Si34-603
Part 6
Test Operation
Test Operation 73
Test Operation Si34-603
1. Test Operation
1.1 Procedure and Outline
Follow the following procedure to conduct the initial test operation after installation.
Check on refrigerant piping ¡ Is pipe size proper? (The design pressure of this product is
4.0MPa.)
¡ Are pipe insulation materials installed securely?
Liquid and gas pipes need to be insulated. (Otherwise causes
water leak.)
¡ Are respective stop valves on liquid and gas line securely open?
74 Test Operation
Si34-603 Test Operation
On completion of test operation, LED on outdoor unit PC board displays the following.
H3P ON: Normal completion
H2P and H3P ON: Abnormal completion →Check the indoor unit remote controller for
abnormal display and correct it.
Malfunction code
In case of an alarm code displayed on remote controller:
Malfunction
Nonconformity during installation Remedial action
code
The shutoff valve of an outdoor unit is left
closed. Open the gas-side shutoff valve and the liquid-side shutoff valve.
E3 Recalculate the required amount of refrigerant from the piping
Refrigerant overcharge. length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
The shutoff valve of an outdoor unit is left
closed. Open the gas-side shutoff valve and the liquid-side shutoff valve.
UA If no dedicated indoor unit is being used. Check the indoor unit. If it is not a dedicated unit, replace the
indoor unit.
The shutoff valve of an outdoor unit is left
closed. Open the gas-side shutoff valve and the liquid-side shutoff valve.
UF
If the right indoor unit piping and wiring are Make sure that the right indoor unit piping and wiring are properly
not properly connected to the outdoor unit. connected to the outdoor unit.
If the interunit wiring has not be connected Make sure the interunit wiring is correctly attached to terminals
UH or it has shorted. (X2M) F1/F2 (TO IN/D UNIT) on the outdoor unit circuit board.
Test Operation 75
Test Operation Si34-603
76 Test Operation
Si34-603 Test Operation
Indoor unit If ON button is pushed during operation described above, the “UH”
malfunction indicator blinks.
(Returns to normal when automatic setting is complete.)
Indoor unit If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when
automatic setting is complete.)
1.2.3 When an Indoor Unit or Outdoor Unit has been Added, or Indoor or
Outdoor Unit PC Board has been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit Test lamp H2P .... ON
Can also be set during operation described above.
Indoor unit If ON button is pushed during operation described above, the “UH” or “U4”
malfunction indicator blinks. (Returns to normal when automatic setting is
complete.)
Test Operation 77
Outdoor Unit PC Board Layout Si34-603
Caution Cover electric parts with an insulating sheet during inspection to prevent electric shock.
78 Test Operation
Si34-603 Field Setting
3. Field Setting
3.1 Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
CODE NO. 3 4
1 7 TEST
6 5 2
(V0292)
1. When in the normal mode, press the “ ” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ ” button ().
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), push the “ ” button () and select the INDOOR UNIT NO to be set. (This
operation is unnecessary when setting by group.)
4. Push the “ ” upper button () and select FIRST CODE NO.
5. Push the “ ” lower button () and select the SECOND CODE NO.
6. Push the “ ” button () once and the present settings are SET.
7. Push the “ ” button () to return to the NORMAL MODE.
(Example)
If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,
HEAVY, SET MODE NO. to “10” FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.
Test Operation 79
Field Setting Si34-603
1. When in the normal mode, push the “ ” button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the “ ” button.
3. Pushing the “ ” button, select the first code No.
4. Pushing the “ ” button, select the second code No.
5. Push the timer “ ” button and check the settings.
6. Push the “ ” button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.
80 Test Operation
Si34-603 Field Setting
Test Operation 81
Field Setting Si34-603
Notes : 1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
82 Test Operation
Si34-603 Field Setting
Ceiling mounted cassette type Slim Ceiling Ceiling Ceiling Wall Floor Concealed Ceiling
Ceiling mounted mounted suspended mounted standing Floor suspended
Multi flow Double Corner mounted built-in duct type type type type standing cassette
flow type duct type type type type
FXFQ FXCQ FXKQ FXDQ FXSQ FXMQ FXHQ FXAQ FXLQ FXNQ FXUQ
Filter sign { { { { { { { { { { {
Test Operation 83
Field Setting Si34-603
Setting Table
Mode No. Setting Switch No. Setting Position No. Setting
01 Long-Life Filter
10 (20) 1 02 Ultra-Long-Life Filter (1)
03 —
F2 T1 T2
Forced stop
Input A
Setting Table
Setting Table
Mode No. First Code No. Second Code No. Setting
01 LL Fan Speed
12(22) 3
02 Set Fan Speed
84 Test Operation
Si34-603 Field Setting
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Test Operation 85
Field Setting Si34-603
Setting Table
Second Code
Mode No. First Code No. No. Setting
Setting Table
Setting Mode No. First Code No. Second Code No.
Down-flow operation: Yes 01
13 (23) 3
Down-flow operation: No 02
86 Test Operation
Si34-603 Field Setting
Setting Table
Mode No. First Code No. Second Code No. Setting
01 Upward (Draft
prevention)
13 (23) 4 02 Standard
03 Downward (Ceiling
soiling prevention)
Air flow rate switching at discharge grille for field air flow rate switching
When the optional parts (high performance filter, etc.) is installed, sets to change fan speed for
securing air flow rate.
Follow the instruction manual for the optional parts to enter the setting numbers.
Test Operation 87
Field Setting Si34-603
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
SETTING MODE
TEST
3
5 4
2,6
Note:
For wireless remote controller, see the following.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
88 Test Operation
Si34-603 Field Setting
BRC7C Type Group No. setting by wireless remote controller for centralized control
BRC7E Type 1. When in the normal mode, push “ ” button for 4 seconds or more, and operation then
BRC4C Type enters the “field set mode.”
2. Set mode No. “00” with “ ” button.
3. Set the group No. for each group with “ ”“ ” button (advance/backward).
4. Enter the selected group numbers by pushing “ ” button.
5. Push “ ” button and return to the normal mode.
Centoral Remote
Controller
Indoor/Outdoor Outdoor/Outdoor Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
RC
Group Control by Remote Contoller
1-00 Main RC RC Sub RC
(autmatic unit address)
1-01 1-02
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
No Remote Controller
RC
1-03 (V0917)
1-04
Caution When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
Test Operation 89
Field Setting Si34-603
90 Test Operation
Si34-603 Field Setting
How to Select Whether operation by remote controller will be possible or not for turning on/off, controlling
Operation Mode temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
Example
ON by remote OFF by remote
Temperature Operation mode Control
controller controller OFF by control by setting by mode is "1."
(Unified ON by (Unified OFF by remote remote controller remote controller
central remote central remote controller
controller) controller)
↓ ↓ ↓ ↓ ↓
Rejection Rejection Rejection Acceptance Acceptance (VL069)
Acceptance 0
Rejection
ON/OFF control Rejection 10
impossible by Rejection
(Example) Acceptance
remote controller Acceptance (Example) 1(Example)
(Example)
Rejection (Example) Rejection 11
Acceptance 2
Rejection
OFF control only Rejection (Example) Rejection 12
possible by
remote controller Acceptance 3
Acceptance
Rejection 13
Acceptance 4
Rejection
Rejection 14
Centralized
Acceptance 5
Acceptance
Rejection 15
Acceptance Acceptance
Acceptance 6
Rejection
Rejection 16
Individual Acceptance
Acceptance 7 ∗1
Acceptance
Rejection 17
Acceptance 8
Rejection
Timer operation Acceptance Acceptance Rejection 18
possible by (During timer at ON (During timer at ON
remote controller position only) position only) Acceptance 9
Acceptance
Rejection 19
Do not select “timer operation possible by remote controller” if not using a remote controller.
Operation by timer is impossible in this case.
∗1. Factory setting
Test Operation 91
Field Setting Si34-603
92 Test Operation
Si34-603 Field Setting
Caution DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adapter
Test Operation 93
Field Setting Si34-603
Push and hold the BS1 (Normal) Push the BS1(MODE button)
(MODE button) for 5 seconds. one time.
Setting mode 2 Setting mode 1 Monitor mode
On Off Blinking
(Set): Select mode with BS2 (SET button) in each selection step.
Press BS1 (MODE button) for more than 5 sec. Setting mode 1 Press BS1(MODE button).
(Initial condition)
Press BS1
(MODE button).
(V2762)
94 Test Operation
Si34-603 Field Setting
a. “Setting mode 1”
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor
unit (factory set).
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group
with the master unit.
• COOL/HEAT selection (SLAVE)················Used to select COOL or HEAT by outdoor unit group
with the slave unit.
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
8 ON
7 OFF
9 Blink
Push the RETURN (BS3) button to Pushing the RETURN (BS3) button will return the system to the initial condition of
determine the setting. "Setting mode 1".
Test Operation 95
Field Setting Si34-603
96 Test Operation
Si34-603 Field Setting
Test Operation 97
Field Setting Si34-603
98 Test Operation
Si34-603 Field Setting
Lower 4 digits:
12 Number of terminal blocks 9 7 7 8 8 7 7 upper
Lower 4 digits:
13 Number of terminal blocks 9 7 7 8 8 7 8 lower
<Confirmation on setting contents> Contents of malfunction (the Malfunction
14
latest) 8 7 7 8 8 8 7 code table
Push the RETURN (BS3) button to
Contents of malfunction Refer to page
display different data of set items. 15
(1 cycle before) 8 7 7 8 8 8 8 124.
Contents of malfunction
16 (2 cycle before) 8 7 8 7 7 7 7
20 Contents of retry (the latest) 8 7 8 7 8 7 7
21 Contents of retry (1 cycle before) 8 7 8 7 8 7 8
22 Contents of retry (2 cycle before) 8 7 8 7 8 8 7
Lower 2 digits:
Normal judgment of outdoor units 87 Abnormal
25
PC board 9 7 8 8 7 7 8 78 Normal
Push the RETURN (BS3) button and
77 Unjudgment
switches to the initial status of
“Monitor mode”. The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
∗ Push the MODE (BS1) button and Setting item 0 Display contents of “Various setting”
returns to “Setting mode 1”. EMG operation / ON 9 7 7 8 7 7 7
backup operation
(V2765) setting OFF 9 7 7 7 7 7 7
Defrost select setting Short 9 7 7 7 8 7 7
Medium 9 7 7 7 9 7 7
Long 9 7 7 7 7 7 7
Te setting H 9 7 7 7 7 8 7
M 9 7 7 7 7 9 7
L 9 7 7 7 7 7 7
Tc setting H 9 7 7 7 7 7 8
M 9 7 7 7 7 7 9
L 9 7 7 7 7 7 7
Test Operation 99
Field Setting Si34-603
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and
confirm the data for each setting.
Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
977 7979
The number of terminal blocks for No. 12 and 13 is expressed as
64 16
No.12 128 32 an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
977 7997 In d the address for No. 12 is 0101, the address for No. 13 is
4 1 0110, and the combination of the two is 01010110 (binary
No.13 8 2 number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
See the preceding page for a list of data, etc. for No. 0 - 25.
c Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to IN (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
d Set Cool / Heat Separately for Each Outdoor Unit System by Cool/Heat Switching Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to OUT (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
When the low noise operation is carried out automatically at night (The external control
adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
Image of operation
When the normal demand operation is carried out. (Use of the external control adapter
for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Image of operation
(V3082)
{: ON z: OFF 9: Blink
c d e
Setting Setting Setting No. indication Setting No. indication Setting Setting contents indication (Initial setting)
No. contents contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External NO
low noise / { z z z z z z { z z { { z z (Factory { z z z z z 9
Demand set)
setting
YES { z z z z 9 z
22 Night-time OFF
low noise { z { z { { z (Factory { z z z z z z
setting setting)
Mode 1 { z z z z z 9
Mode 2 { z z z z 9 z
Mode 3 { z z z z 9 9
26 Night-time { z { { z { z PM 8:00 { z z z z z 9
low noise
start setting PM 10:00
(Factory { z z z z 9 z
setting)
PM 0:00 { z z z 9 z z
27 Night-time { z { { z { { AM 6:00 { z z z z z 9
low noise
end setting AM 7:00 { z z z z 9 z
AM 8:00
(Factory { z z z 9 z z
setting)
29 Capacity Low noise
precedence precedence
setting
{ z { { { z { (Factory
{ z z z z z 9
setting)
Capacity
precedence
{ z z z z 9 z
30 Demand 60 % of
setting 1 { z { { { { z rated power { z z z z z 9
consumption
70 % of
rated power
consumption { z z z z 9 z
(Factory
setting)
80 % of
rated power { z z z 9 z z
consumption
32 Normal OFF
demand { z z z z z z (Factory { z z z z z 9
setting setting)
ON { z z z z 9 z
Setting mode indication section Setting No. indication section Set contents indication section
[Operation procedure]
c In “Setting Mode 2” with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. “TEST
OPERATION” and “UNDER CENTRALIZED CONTROL” are displayed on the remote
controller, and the indoor / outdoor unit operation is prohibited.
After setting, do not cancel “Setting Mode 2” until completion of refrigerant recovery
operation.
d Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
e Press Mode button “BS1” once and reset “Setting Mode 2”.
[Operating procedure]
c In “Setting Mode 2” with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. “TEST
OPERATION” and “UNDER CENTRALIZED CONTROL” are displayed on the remote
controller, and the indoor / outdoor unit operation is prohibited.
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d Use the vacuum pump to perform vacuuming operation.
e Press Mode button “BS1” once and reset “Setting Mode 2”.
Completion
Part 7
Troubleshooting
1. Symptom-based Troubleshooting .......................................................113
2. Troubleshooting by Remote Controller ...............................................116
2.1 The INSPECTION / TEST Button.........................................................116
2.2 Self-diagnosis by Wired Remote Controller .........................................117
2.3 Self-diagnosis by Wireless Remote Controller .....................................118
2.4 Operation of the Remote Controller’s Inspection /
Test Operation Button ..........................................................................120
2.5 Remote Controller Service Mode .........................................................121
2.6 Remote Controller Self-Diagnosis Function .........................................123
3. Troubleshooting by Indication on the Remote Controller ....................130
3.1 “A0” Indoor Unit: Error of External Protection Device ...........................130
3.2 “A1” Indoor Unit: PC Board Defect.........................................................131
3.3 “A3” Indoor Unit: Malfunction of Drain Level Control System (33H) ......132
3.4 “A6” Indoor Unit: Fan Motor (M1F) Lock, Overload...............................134
3.5 “A7” Indoor Unit: Malfunction of Swing Flap Motor (MA) .......................135
3.6 “A9” Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (20E) ........................................................137
3.7 “AF” Indoor Unit: Drain Level above Limit..............................................139
3.8 “AJ” Indoor Unit: Malfunction of Capacity Determination Device ..........140
3.9 “C4” Indoor Unit: Malfunction of Thermistor (R2T)
for Heat Exchanger ..............................................................................141
3.10 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes..........142
3.11 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air.........143
3.12 “CA” Indoor Unit: Malfunction of Thermistor for Discharge Air...............144
3.13 “CJ” Indoor Unit: Malfunction of Thermostat Sensor in
Remote Controller ................................................................................145
3.14 “E1” Outdoor Unit: PC Board Defect ......................................................146
3.15 “E3” Outdoor Unit: Actuation of High Pressure Switch ..........................147
3.16 “E4” Outdoor Unit: Actuation of Low Pressure Sensor ..........................149
3.17 “E5” Compressor Motor Lock ................................................................151
3.18 “E7” Malfunction of Outdoor Unit Fan Motor..........................................152
3.19 “E9” Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y3E)...............................................153
3.20 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature ..................155
3.21 “F6” Outdoor Unit: Refrigerant Overcharged.........................................156
3.22 “H9” Outdoor Unit: Malfunction of Thermistor (R1T) for Outdoor Air.....157
3.23 “J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R2T) ....158
3.24 “J5” Outdoor Unit: Malfunction of Thermistor (R3T, R5T) for
Suction Pipe 1, 2 ..................................................................................159
3.25 “J6” Outdoor Unit: Malfunction of Thermistor (R4T) for
Outdoor Unit Heat Exchanger ..............................................................160
3.26 “J7” Outdoor Unit: Malfunction of Thermistor (R7T) for
Outdoor Unit Liquid Pipe ......................................................................161
3.27 “J9” Outdoor Unit: Malfunction of Subcooling Heat
Exchanger Gas Pipe Thermistor (R6T) ................................................162
Troubleshooting 111
Si34-603
112 Troubleshooting
Si34-603 Symptom-based Troubleshooting
1. Symptom-based Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start operation at all. Blowout of fuse(s) Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s) • If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
ON
Knob
Tripped
OFF
Circuit breaker
Troubleshooting 113
Symptom-based Troubleshooting Si34-603
114 Troubleshooting
Si34-603 Symptom-based Troubleshooting
Troubleshooting 115
Troubleshooting by Remote Controller Si34-603
Normal
mode
Press Inspection/Test Operation button once.
Press Inspection/Test Operation
Or after 30 minutes
button once.
After 10 seconds
116 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
ON/OFF button
Inspection display
Malfunction code
Inspection/Test button
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or
more will clear the failure history indication shown above. In this case, on the codes display,
the malfunction code will blink twice and then change to “00” (=Normal), the Unit No. will
change to “0”, and the operation mode will automatically switch from check mode to normal
mode (displaying the set temperature).
Troubleshooting 117
Troubleshooting by Remote Controller Si34-603
The upper digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
*2 Number of beeps
Continuous beep : Both upper and lower digits matched. (Malfunction code confirmed)
2 short beeps : Upper digit matched.
1 short beep : Lower digit matched.
5. Press the MODE selector button.
The right “0” (lower digit) indication of the malfunction code flashes.
6. Malfunction code lower digit diagnosis
Press the UP or DOWN button and change the malfunction code lower digit until the
continuous malfunction code matching buzzer (*2) is generated.
118 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
The lower digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
Troubleshooting 119
Troubleshooting by Remote Controller Si34-603
120 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
Troubleshooting 121
Troubleshooting by Remote Controller Si34-603
Mode Function Contents and operation method Remote controller display example
No
Malfunction Display malfunction hysteresis.
40 hysteresis display The history No. can be changed with the Unit 1
button.
Malfunction code 40
2-U4
Malfunction code
Hystory No: 1 - 9
(VE007) 1: Latest
Individual setting Set the fan speed and air flow direction by each
44 unit
Unit 1
Select the unit No. with the time mode
Code
button. Set the fan speed with the
button. 44
1 3
Set the air flow direction with the button.
Fan speed 1: Low Air flow direction
3: High P0 - P4
(VE010)
122 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
Operation lamp
ON/OFF button
(VL050)
Troubleshooting 123
Troubleshooting by Remote Controller Si34-603
8: ON 7: OFF 9: Blink
Malfunction Operation Inspection Unit No. Malfunction contents Page
code lamp display Referred
Indoor Unit A0 9 9 9 Error of external protection device 130
A1 9 9 9 PC board defect, E2 PROM defect 131
A3 9 9 9 Malfunction of drain level control system (S1L) 132
A6 9 9 9 Fan motor (M1F) lock, overload 134
A7 8 9 9 Malfunction of swing flap motor (MA) 135
A9 9 9 9 Malfunction of moving part of electronic expansion 137
valve (20E)
AF 8 7 9 Drain level about limit 139
AJ 9 9 9 Malfunction of capacity setting 140
C4 9 9 9 Malfunction of thermistor (R2T) for heat exchange 141
(loose connection, disconnection, short circuit, failure)
C5 9 9 9 Malfunction of thermistor (R3T) for gas pipes (loose 142
connection, disconnection, short circuit, failure)
C9 9 9 9 Malfunction of thermistor (R1T) for air inlet (loose 143
connection, disconnection, short circuit, failure)
CJ 8 9 8 Malfunction of thermostat sensor in remote controller 145
Outdoor Unit E1 9 9 9 PC board defect 146
E3 9 9 9 Actuation of high pressure switch 147
E4 9 9 9 Actuation of low pressure sensor 149
E5 9 9 9 Compressor motor lock 151
E6 9 9 9 Standard compressor lock or over current —
E7 9 9 9 Malfunction of outdoor unit fan motor 152
E9 9 9 9 Malfunction of moving part of electronic expansion 153
valve (Y1E, Y2E)
F3 9 9 9 Abnormal discharge pipe temperature 155
F6 9 9 9 Refrigerant overcharged 156
H3 8 7 9 Failure of high pressure switch —
H4 9 9 9 Actuation of low pressure switch —
H7 9 9 9 Abnormal outdoor fan motor signal —
H9 9 9 9 Malfunction of thermistor (R1T) for outdoor air (loose 157
connection, disconnection, short circuit, failure)
J2 9 9 9 Current sensor malfunction —
J3 9 9 9 Malfunction of discharge pipe thermistor (R31~33T) 158
(loose connection, disconnection, short circuit,
failure)
J5 9 9 9 Malfunction of thermistor (R3T, R5T) for suction pipe 159
(loose connection, disconnection, short circuit,
failure)
J6 9 9 9 Malfunction of thermistor (R4T) for heat exchanger 160
(loose connection, disconnection, short circuit,
failure)
J7 9 9 9 Malfunction of receiver outlet liquid pipe thermistor (R7T) 161
J9 9 9 9 Malfunction of subcooling heat exchanger gas pipe 162
thermistor (R5T)
JA 9 9 9 Malfunction of discharge pipe pressure sensor 163
JC 9 9 9 Malfunction of suction pipe pressure sensor 164
L0 9 9 9 Inverter system error —
L1 9 9 9 Malfunction of PC board 165
L4 9 9 9 Malfunction of inverter radiating fin temperature rise 166
L5 9 9 9 DC output overcurrent of inverter compressor 167
L8 9 9 9 Inverter current abnormal 168
L9 9 9 9 Inverter start up error 169
124 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
8: ON 7: OFF 9: Blink
Malfunction Operation Inspection Unit No. Malfunction contents Page
code lamp display Referred
Outdoor Unit LA 9 9 9 Malfunction of power unit —
LC 9 9 9 Malfunction of transmission between inverter and 170
control PC board
P1 9 9 9 High voltage of capacitor in main inverter circuit. 171
P4 8 9 8 Malfunction of inverter radiating fin temperature rise 172
sensor
System U0 8 7 9 Low pressure drop due to refrigerant shortage or 173
electronic expansion valve failure
U1 9 9 9 Reverse phase / open phase —
U2 9 9 9 Power supply insufficient or instantaneous failure 175
U3 9 9 9 Check operation is not completed. 177
U4 9 9 9 Malfunction of transmission between indoor and 178
outdoor units
U5 9 9 9 Malfunction of transmission between remote 180
controller and indoor unit
U5 7 8 7 Failure of remote controller PC board or setting 180
during control by remote controller
U7 9 9 9 Malfunction of transmission between outdoor units —
U8 9 9 7 Malfunction of transmission between main and sub 181
remote controllers (malfunction of sub remote controller)
U9 9 9 9 Malfunction of transmission between indoor unit and 182
outdoor unit in the same system
UA 9 9 9 Improper combination of indoor and outdoor units, 184
indoor units and remote controller
UC 8 8 8 Address duplication of central remote controller 185
UE 9 9 9 Malfunction of transmission between central remote 186
controller and indoor unit
UF 9 9 9 Refrigerant system not set, incompatible wiring / 188
piping
UH 9 9 9 Malfunction of system, refrigerant system address 189
undefined
Central UE 9 9 9 Malfunction of transmission between central remote 190
Remote controller and indoor unit
Controller
and M1 8 or 7 9 9 Central remote controller PC board defect 191
Schedule Schedule timer PC board defect
Timer M8 8 or 7 9 9 Malfunction of transmission between optional 192
controllers for centralized control
MA 8 or 7 9 9 Improper combination of optional controllers for 193
centralized control
MC 8 or 7 9 9 Address duplication, improper setting 195
Heat 64 8 7 9 Indoor unit’s air thermistor error —
Reclaim 65 8 7 9 Outside air thermistor error —
Ventilation
68 8 7 9 Malfunction of HVU —
6A 8 7 9 Damper system alarm —
6A 9 9 9 Damper system + thermistor error —
6F 8 7 9 Malfunction of simple remote controller —
94 9 9 9 Internal transmission error —
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting 125
Troubleshooting by Remote Controller Si34-603
126 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
8: ON 7: OFF 9:Blink
Malfunction Confirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3 Confirmation of malfunction 4
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
E1 9 7 7 9 9 9 7 7 7 9 9 8 7 7 7 7 7 9 8 8 7 7 9 9
E3 9 7 7 9 9 9 7 7 7 7 9 7 7
E4 9 7 9 7 7 9 7 7 7 7 9 7 7
E5 9 7 9 7 9 9 7 7 7 7 9 7 7
E7 9 7 9 9 9 9 7 7 7 7 9 7 9 ∗1
9 7 7 7 9 9 7 9
E9 9 9 7 7 9 9 7 7 7 7 9 7 7
9 7 7 7 7 9 9 7
H9 9 9 7 7 9 9 7 7 7 7 9 7 7 ∗1
F3 9 7 9 7 9 9 7 7 9 9 9 7 7 7 7 9 7 7 ∗1
F6 9 7 9 9 7 9 7 7 7 7 9 7 7 9 9
J3 9 7 9 9 7 9 7 7 9 9 9 7 7 7 7 9 7 7
J5 9 7 9 7 9 9 7 7 7 7 9 7 7
9 7 7 7 7 9 7 9
J6 9 7 9 9 7 9 7 7 7 7 9 7 7
∗1
J7 9 7 9 9 9 9 7 7 7 7 9 7 7
J9 9 9 7 7 9 9 7 7 7 7 9 7 7
JA 9 9 7 9 7 9 7 7 7 7 9 7 7
JC 9 9 9 7 7 9 7 7 7 7 9 7 7
L1 9 7 9 9 9 9 7 7 7 9 9 7 7 7 7 9 7 7 7 7
9 7 7 7 9 9 7 7 7 7 9 7 7 7 9
9 7 7 7 9 9 7 7 7 7 9 7 7 9 7
9 7 7 7 9 9 7 7 7 7 9 7 7 9 9
9 7 7 7 9 9 7 7 7 7 9 7 9 7 7
L4 9 7 9 7 7 9 7 7 7 7 9 7 7
L5 9 7 9 7 9 9 7 7 7 7 9 7 7
L8 9 9 7 7 7 9 7 7 7 7 9 7 7
9 7 7 7 7 9 7 9
9 7 7 7 7 9 9 7
9 7 7 7 9 9 7 7 ∗1
L9 9 9 7 7 9 9 7 7 7 7 9 7 7
9 7 7 7 7 9 7 9
9 7 7 7 7 9 9 7
LC 9 9 9 7 7 9 7 7 7 7 9 7 9
Troubleshooting 127
Troubleshooting by Remote Controller Si34-603
<Monitor mode>
Contents of malfunction Malfunction
To enter the monitor mode, push the code
MODE (BS1) button when in Open phase/Power supply imbalance Imbalance of inverter power supply P1
“Setting mode 1”. voltage
Faulty temperature sensor of inverter Faulty thermistor of inverter fin P4
radiation fin
Gas shortage Gas shortage alarm U0
Abnormal power supply voltage Insufficient Inverter voltage U2
Faulty charge of capacitor in main inverter circuit
<Selection of setting item> Malfunction due to SP-PAM overvoltage
Push the SET (BS2) button and set Malfunction due to P-N short circuit
the LED display to a setting item. No implementation of test-run U3
Push the RETURN (BS3) button Erroneous field setting System transmission malfunction UA
once to display "First digit" of Overconnection malfunction of indoor units
malfunction code. Malfunction of field setting
Refrigerant abnormal
Connection error (BP unit)
Faulty system malfunction Wiring error (Auto-address error) UH
Conflict in wiring and piping, no setting Conflict in wiring and piping UF
for system
<Confirmation of malfunction 2>
Push the SET (BS2) button once to Detail
display "Second digit" of malfunction description
code. on next
page.
128 Troubleshooting
Si34-603 Troubleshooting by Remote Controller
8: ON 7: OFF 9:Blink
Malfunction Confirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3 Confirmation of malfunction 4
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
P1 9 9 7 7 7 9 7 7 7 9 9 7 7 7 7 9 7 7
∗1
P4 9 7 9 7 7 9 7 7 7 7 9 7 7
U0 9 9 7 7 9 9 7 7 7 7 9 7 7 7 7 9 7 7 9 9
U2 9 7 7 9 7 9 7 7 7 7 9 7 7
∗1
9 7 7 7 7 7 9
9 7 7 7 7 9 7 7 9 7
9 7 7 7 7 9 7 7 7 9
U3 9 7 7 9 9 9 7 7 7 7 9 7 7 9 9
9 7 7 7 7 9 7 9 9 9
U4 9 7 9 7 7 9 7 7 7 7 9 7 7 9 9
9 7 7 7 7 9 7 9 9 9
U9 9 9 7 7 9 9 7 7 7 7 9 7 7 9 9
UA 9 9 7 9 7 9 7 7 7 7 9 7 7 9 9
9 7 7 7 7 9 7 9 9 9
9 7 7 7 7 9 9 7 9 9
9 7 7 7 9 9 7 7 9 9
9 7 7 9 7 9 7 9 9 9
UH 9 9 7 9 9 9 7 7 7 7 9 7 7 9 9
UF 9 9 9 9 9 9 7 7 7 7 9 7 7 9 9
Troubleshooting 129
Troubleshooting by Indication on the Remote Controller Si34-603
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
External
protection device is
connected to terminals T1 YES
Actuation of external protection
and T2 of the indoor device.
unit terminal
block.
NO
ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been YES
set to external protection Change the second code No. to
device input (second "01" or "02" .
code No. 03)
by remote
controller.
NO
Indoor unit PC board replacement.
(V2776)
130 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
Conditions supply is turned off.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Does
YES
the system return External factor other than
to normal? malfunction (for example,
noise etc.).
NO
Troubleshooting 131
Troubleshooting by Indication on the Remote Controller Si34-603
Malfunction When rise of water level is not a condition and the float switch goes OFF.
Decision
Conditions
132 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to NO circuit connector is NO
X8A (or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The float
switch contact is
forming a short circuit Becomes NO
YES normal when X8A (or X15A) of
(continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited
NO YES
Loose connection of connector.
The voltage
of terminals Y1
and Y2 or X25A is NO
220~240 V (within Replace indoor unit PC board.
5minutes of resetting
the power
supply).
YES
Replace the drain pump or
check for dirt, etc.
(V2778)
Troubleshooting 133
Troubleshooting by Indication on the Remote Controller Si34-603
Method of Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Detection
Malfunction When number of turns can’t be detected even when output voltage to the fan is maximum
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
wiring from the fan
motor securely connected NO
Connect the wiring and turn on
to connectors on the again.
indoor unit PC
board?
YES
Wiring
between the
indoor unit PC board and YES
Fix the wiring and turn on again.
fan motor is
disconnected.
NO
YES
Does the fan motor run? Replace the indoor unit PC board.
NO
Replace the fan motor.
(V2779)
134 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
Decision motor is energized for a specified amount of time (about 30 seconds).
Conditions
Troubleshooting 135
Troubleshooting by Indication on the Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
Indoor unit
is a model equipped NO
with a swing flap Replace indoor unit PC board.
function
YES
The swing
motor works when YES The connector NO
the power supply is turned is connected to X9A (or X15A) of Connect the connector to X9A
off and then back the indoor unit PC and turn on again.
on. board.
NO YES
YES
YES
When
the air flow
direction flap's cam
mechanism is disconnected NO
from the swing motor, Replace swing motor.
operation is normal
when turned
on again.
YES
Take the cam mechanism
apart, reassemble and turn on
again.
(V2780)
136 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
electronic
expansion valve is NO
connected to X7A of the After connecting, turn the power
indoor unit PC supply off and then back on.
board.
YES
Normal
when coil check
(∗1) of the moving part of NO
Replace the moving part of the
the electronic expansion electronic expansion valve.
valve is
checked.
YES
NO
If you turn the power supply off
and turn on again, and it still does
not help, replace the indoor unit
PC board.
(V2781)
Troubleshooting 137
Troubleshooting by Indication on the Remote Controller Si34-603
∗1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × { × { ×
Approx. Approx.
300Ω 150Ω
2. Yellow × { × {
Approx. Approx.
300Ω 150Ω
3. Orange × { ×
Approx.
150Ω
4. Blue × {
Approx.
150Ω
5. Red ×
6. Brown
{: Continuity
×: No continuity
138 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of Water leakage is detected based on float switch ON/OFF operation while the compressor is in
Malfunction non-operation.
Detection
Malfunction When the float switch changes from ON to OFF while the compressor is in non-operation.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Field drain
piping has a defect such as YES
Modify the drain piping.
upward sloping.
NO
A humidifier
unit (optional accessory) YES
Check if the humidifier unit is
is installed on the leaking.
indoor unit.
NO
Defect of indoor unit PC board.
(V2782)
Troubleshooting 139
Troubleshooting by Indication on the Remote Controller Si34-603
Method of Capacity is determined according to resistance of the capacity setting adaptor and the memory
Malfunction inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
Detection is determined.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The indoor NO
unit PC board was replaced Replace the indoor unit PC board.
with a replacement
PC board.
YES
The indoor
unit is a model that
requires installation of a NO
capacity setting adaptor Replace the indoor unit PC board.
when replacing the
PC board.
YES
Install a capacity setting adaptor.
(V2783)
140 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction
Detection
Malfunction When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to X12A NO
Connect the thermistor and turn
of the indoor unit PC on again.
board.
YES
Resistance
is normal when
measured after NO
disconnecting the thermistor Replace the thermistor (R2T).
(R2T) from the indoor
unit PC board
(3.5kΩ~
360kΩ)
YES
Replace the indoor unit PC board.
(V2784)
Troubleshooting 141
Troubleshooting by Indication on the Remote Controller Si34-603
Method of Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Detection
Malfunction When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector is NO
connected to X11A of Connect the thermistor and turn
the indoor unit PC on again.
board.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
Replace the thermistor (R3T).
(R3T) from the indoor
unit PC board.
(0.6kΩ~
360kΩ)
YES
Replace the indoor unit PC board.
(V2785)
142 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of Malfunction detection is carried out by temperature detected by suction air temperature
Malfunction thermistor.
Detection
Malfunction When the suction air temperature thermistor becomes disconnected or shorted while the unit is
Decision running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector NO
is connected to X13A Connect the thermistor and turn
of the indoor unit on again.
PC board.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO Replace the thermistor (R1T).
(R1T) from the indoor
unit PC board.
(7.2kΩ~
112kΩ)
YES
Replace the indoor unit PC board.
(V2786)
Troubleshooting 143
Troubleshooting by Indication on the Remote Controller Si34-603
Method of Malfunction detection is carried out by temperature detected by discharge air temperature
Malfunction thermistor.
Detection
Malfunction When the discharge air temperature thermistor becomes disconnected or shorted while the unit
Decision is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector NO
is connected to the indoor Connect the thermistor and turn
unit PC board. on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO Replace the thermistor.
from the indoor unit
PC board.
(7.2kΩ~
112kΩ)
YES
Replace the indoor unit PC board.
(V2786)
144 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of Malfunction detection is carried out by temperature detected by remote controller air
Malfunction temperature thermistor. (Note1)
Detection
Malfunction When the remote controller air temperature thermistor becomes disconnected or shorted while
Decision the unit is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is "CJ" YES
displayed on the remote Replace remote controller.
controller?
NO
External factor other than
equipment malfunction.
(for example, noise etc.)
(V2787)
Note: In case of remote controller thermistor malfunction, unit is still operable by suction air thermistor
on indoor unit.
Troubleshooting 145
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
Conditions supply is turned off.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
146 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Detection
Malfunction Error is generated when the HPS activation count reaches the number specific to the operation
Decision mode.
Conditions (Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 3.0MPa
Troubleshooting 147
Troubleshooting by Indication on the Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the NO
three points above Rectify defective points, if any.
OK?
YES
· Mount a pressure gauge on the high-pressure service port.
· Connect the Service Checker.
· Reset the operation using the remote controller,
and then restart the operation.
NO YES
Are the
characteristics of the high NO
Replace the high pressure sensor.
pressure sensor normal?
(See *1.)
YES
Is the
pressure detected with NO
the PCB normal? Replace the main PCB.
(See *2.)
YES
· The high pressure sensor is normal, and the pressure detected with the PCB is also normal.
· The high pressure has really become high.
(4) Red
High
(3) Black
pressure
sensor
(2)
Micro controller
A/D input (1) White
Make measurement of DC
voltage between these wires.
148 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RXYMQ4~6P
Models
Method of Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Detection
Malfunction Error is generated when the low pressure is dropped under specific pressure.
Decision Operating pressure:0.07MPa
Conditions
Troubleshooting 149
Troubleshooting by Indication on the Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the stop NO
Open the stop valve.
valve open?
YES
Mount a pressure gauge on the low-pressure service port.
Connect the Service Checker.
Reset the operation using the remote controller, and then
restart the operation.
Are the
characteristics of the NO
low pressure sensor Replace the low pressure sensor.
normal?
(See *1.)
YES
Is the
pressure detected NO
with the PCB Replace the main PCB.
normal?
(See *2.)
YES
· The low pressure sensor is normal, and the pressure
detected with the PCB is also normal.
· The low pressure has really become low.
*1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on page 233.)
*2: Make a comparison between the low pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
+5V
Connector for low pressure sensor
(Blue)
(4) Red
150 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Inverter PC board takes the position signal from UVW line connected between the inverter and
Malfunction compressor, and the malfunction is detected when any abnormality is observed in the phase-
Detection current waveform.
Malfunction This malfunction will be output when the inverter compressor motor does not start up even in
Decision forced startup mode.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
Is the stop valve open? Open the stop valve.
YES
NO
YES
Does low or
high pressure vary YES
even instantaneously when
restarting
compressor?
NO
Replace the compressor.
(V2793)
Troubleshooting 151
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction of fan motor system is detected according to the fan speed detected by hall IC
Malfunction when the fan motor runs.
Detection
Malfunction When the fan runs with speed less than a specified one for 6 seconds or more when the fan
Decision motor running conditions are met
Conditions When malfunction is generated 4 times, the system shuts down.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector YES
of fan motor is Connect the connector.
disconnected.
NO
Is there any YES
obstacle around Remove the obstacle.
the fan?
NO
YES
Check No. 3
Check on connector of fan
motor (Refering to
information on page 204)
Are the
resistances between pins NO
Replace the fan motor of
above judgment?
outdoor unit.
YES
Replace outdoor unit PC
board.
152 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Malfunction Error is generated under no common power supply when the power is on.
Decision
Conditions
Troubleshooting 153
Troubleshooting by Indication on the Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Return to normal? External factor other than
malfunction (for example, noise
NO etc.).
Electronic
expansion valve is
connected to X21A and NO
After connecting, turn the power
X22A of outdoor unit off and then back on again.
PC board
(A1P).
YES
Normal
when coil
check (∗1) of the moving NO
part of the electronic Replace the moving part of the
expansion valve is electronic expansion valve.
checked.
YES
NO
Replace outdoor unit PC board
(A1P).
(V3067)
(Orange) 1
(Red) 2
Measuring points
(Yellow) 3 1-6
2-6
(Black) 4
3-6
5 4-6
(Gray) 6
(V3067)
154 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Abnormality is detected according to the temperature detected by the discharge pipe
Malfunction temperature sensor.
Detection
Malfunction When the discharge pipe temperature rises to an abnormally high level
Decision When the discharge pipe temperature rises suddenly
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Discharge
pipe temperature is YES
120˚C or higher when the Refrigerant shortage, compression
unit stop by defect, etc. Defect of the
malfunction. refrigerant system.
NO
Pull out the discharge pipe
thermistor from the outdoor
PCB, and then make
measurement of resistance
using a multiple meter.
Are
the characteristics
of the discharge pipe NO
Replace the discharge pipe
thermistor normal? thermistor.
(3.5~400KΩ)
∗
YES
Replace outdoor unit PC board
(A1P).
(V3068)
Troubleshooting 155
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Excessive charging of refrigerant is detected by using the heat exchanging deicer temperature
Malfunction during a check operation.
Detection
Malfunction When the amount of refrigerant, which is calculated by using the heat exchanging deicer
Decision temperature during a check run, exceeds the standard.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
above thermistor NO
installed on pipes Install thermistor correctly.
correctly?
YES
Remove the heat exchanging
deicer thermister from the
outdoor PCB and measure
resistance with a tester.
Is the
characteristic of the NO
above thermistor Replace thermistor.
normal?
YES
Refrigerant overcharged.
(V2797)
156 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Detection
Malfunction When the outside air temperature thermistor has short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector is
connected to X11A of NO
Connect the connector and turn on
outdoor PC board again.
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
Replace the thermistor (R1T).
(R1T) from the outdoor
unit PC board.
(3.5kΩ to
360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3070)
Troubleshooting 157
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected from the temperature detected by discharge pipe temperature
Malfunction thermistor.
Detection
Malfunction When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to NO
outdoor unit Connect the thermistor and turn
PC board on again.
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
Replace the thermistor (R2T).
R2T from the outdoor
unit PC board.
(5.0kΩ~
640kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3072)
158 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected from the temperature detected by the thermistor for suction pipe 1, 2.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the thermistor for suction pipe 1, 2 are detected.
Decision
Conditions
Supposed Defect of thermistor (R3T, R5T) for outdoor unit suction pipe
Causes Defect of outdoor unit PC board (A1P)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
of the thermistor for
suction pipe1, 2 is NO
connected to outdoor Connect the thermistor and turn
unit PC board on again.
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO Replace the thermistor (R3T, R5T).
(R3T, R5T) from the
outdoor unit PC
board. (3.5kΩ ~
360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3073)
Troubleshooting 159
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to outdoor NO
Connect the thermistor and turn
unit PC board
(A1P). on again.
YES
Resistance
is normal when
measured after NO
disconnecting the thermistor Replace the thermistor (R7T).
(R7T) from the outdoor
unit PC board.
(3.5kΩ~
360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3074)
160 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected from the temperature detected by the liquid pipe thermistor.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to outdoor NO
Connect the thermistor and turn
unit PC board
(A1P). on again.
YES
Resistance
is normal when
measured after NO
disconnecting the thermistor Replace the thermistor (R7T).
(R7T) from the outdoor
unit PC board.
(3.5kΩ~
360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3074)
Troubleshooting 161
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected according to the temperature detected by subcooling heat exchanger
Malfunction gas pipe thermistor.
Detection
Malfunction When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is
the connector
for subcooling heat
exchanger gas pipe NO
Connect connector and operate
thermistor connected to unit again.
outdoor unit
PC board
(A1P)?
YES
Is the
resistance
measured after
removing the thermistor NO
(R6T) from outdoor unit PC Replace thermistor (R6T).
board normal?
(3.5 kΩ to
360 kΩ)
(V3075)
162 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Detection
Malfunction When the high pressure sensor is short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The high
pressure sensor is
connected to X17A of NO
Connect the high pressure sensor
outdoor unit PC and turn on again.
board (A1P).
YES
The
relationship
between the ∗1
VH and high pressure
is normal (see ∗2) when YES
voltage is measured between Replace outdoor unit PC board
X17A pins (1) and (3) of (A1P).
outdoor unit PC
board (A1P)
(see ∗1).
Troubleshooting 163
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Malfunction When the low pressure sensor is short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The low
pressure sensor is NO
connected to X18A (blue) Connect low pressure sensor
of outdoor unit PC
board (A1P). property and restart system.
YES
The
relationship
between the ∗1
VL and low pressure is
normal (see ∗2) when voltage YES
is measured between X18A pins Replace outdoor unit PC board
(2) and (3) of outdoor unit (A1P).
PC board (A1P)
(see ∗1).
NO
Replace the low pressure sensor.
(V2808)
164 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Detect malfunctions by current value during waveform output before compressor startup.
Malfunction Detect malfunctions by current sensor value during synchronized operation at the time of
Detection startup.
Detect malfunctions using an SP-PAM series capacitor overvoltage sensor.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Does YES
it return normally? It is believed that
external factors (noise,
etc.) other than failure
caused the malfunction.
NO
Troubleshooting 165
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Malfunction When the temperature of the inverter radiation fin increases above 83°C.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The radiator
fin temperature is supposed YES
Faulty heat radiation of power unit
to have risen to 83°C • Air suction opening blocked
or more. • Dirty radiator fin
• High outdoor temperature
NO
Is the
connector X111A of
the fin thermistor properly NO
Properly connect.
connected to the
outdoor PCB?
YES
Turn ON the power supply,
and then press the remote
controller check button once.
Is the
malfunction code "P4" YES
displayed on the remote To "P4" troubleshooting
controller?
NO
Does the
malfunction code "L4" YES
recur when the unit starts Replace the outdoor PCB (A1P)
operation? as well.
NO
Continue operation.
166 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Compressor inspection
NO
Disconnect the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
Inverter
output
voltage check
Inverter output
voltage is not balanced. YES
Replace the inverter unit.
(Normal if within ±5V Must
be measured when
frequency
is stable.
NO
There is YES
instantenious power Correct power supply.
drop.
NO
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V2812)
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
Troubleshooting 167
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
secondary
current of the inverter is YES
higher than 24.9A, Compressor overload
260 sec. for Inspection of the compressor and
each phase.
refrigerant system is required.
NO
Compressor
inspection The YES
compressor's coil is Replace the compressor.
disconnected.
NO
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
Inverter
output
voltage check
Inverter output voltage
is not balanced NO
Replace outdoor unit PC board
(Normal if within ±5V). Must
(A1P).
be measured when
frequency
is stable.
YES
After turning NO
on again, "L8" blinks Reset and restart.
again.
YES
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V3184)
168 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The difference
between high and low NO
pressure when starting Unsatisfactory pressure
is above equalization
0.2MPa. Check refrigerant system.
YES
Disconnect the connection
between the compressor and
inverter. Make the power
transistor check mode ON by
service mode.
Inverter
output
voltage check
Inverter output voltage
is not balanced. NO
(Normal if within ±5V) Must
Replace outdoor unit PC board
be measured when
(A1P).
frequency
is stable.
YES
After turning NO
on again, "L9" blinks Reset and restart.
again.
YES
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V2814)
Troubleshooting 169
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Check the communication state between inverter PC board and control PC board by micro-
Malfunction computer.
Detection
Supposed Malfunction of connection between the inverter microcomputer and outdoor control
Causes microcomputer
Defect of outdoor unit PC board
Defect of noise filter
External factor (Noise etc.)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
microcomputer
monitor (green) on the YES
Replace outdoor unit PC board
outdoor unit PC board (A1P).
(A1P) is
blinking.
NO
The voltage
between red and YES
white of X1A on the inverter Replace outdoor unit PC board
unit is the power supply (A1P).
voltage.
170 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Malfunction is detected according to the voltage waveform of main circuit capacitor built in the
Malfunction inverter.
Detection
Malfunction When the aforementioned voltage waveform becomes identical with the waveform of the power
Decision supply open phase.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the "C4" NO
properly connected? If not connected, connect the "C4".
YES
Replace the outdoor unit PC board
(A1P).
Troubleshooting 171
Troubleshooting by Indication on the Remote Controller Si34-603
Applicable RX(Y)MQ4~6P
Models
Method of Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Detection
Malfunction When the resistance value of thermistor becomes a value equivalent to open or short circuited
Decision status.
Conditions Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
End
172 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Short of gas malfunction is detected by discharge pipe temperature thermistor and low pressure
Malfunction saturation temperature.
Detection
Troubleshooting 173
Troubleshooting by Indication on the Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
Resistance
is normal when
measured with the
thermistor (R3T) for NO
suction pipe1 disconnected Replace the thermistor.
from the outdoor
unit PC
board.
∗1
YES
Is the NO
low pressure sensor Replace the low pressure
correct? sensor.
YES
Replace the outdoor unit PC
board (A1P).
(V2819)
174 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Method of Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction When the abnormal voltage of main circuit capacitor built in the inverter and abnormal power
Decision supply voltage are detected.
Conditions
Troubleshooting 175
Troubleshooting by Indication on the Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
power supply voltage NO
Correct power supply
200~240V ±10%?
YES
Is the
P-N resistance not less than NO
Field factors
several hundred of
ohms?
YES
Check No.3 ∗ NO
Is the resistance Replace the fan motor
above standard
value?
YES
NO
Replace the inverter PC board
(A1P).
(S2605)
176 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Applicable RX(Y)MQ4~6P
Models
Malfunction Malfunction is decided when the unit starts operation without check operation.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has the
check operation NO
performed on Outdoor Press the BS4 on PC board on the
unit PC board? master outdoor unit for 5 seconds
or more to execute check
YES operation.
Troubleshooting 177
Troubleshooting by Indication on the Remote Controller Si34-603
Method of Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
Causes or wrong wiring
Outdoor unit power supply is OFF
System address doesn’t match
Defect of outdoor unit PC board
Defect of indoor unit PC board
178 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has
the indoor
or outdoor unit PC
board been replaced,
or has the indoor - outdoor YES
Push and hold the RESET
or outdoor - outdoor unit button on the master outdoor
transmission wiring unit PC Board for 5 seconds.
been ∗ The unit will not operate for
modified? up to 12 minutes.
NO
All
indoor unit Is indoor
remote controllers of the NO - outdoor and outdoor - YES Replace the indoor unit PC
same refrigerant system outdoor unit transmission board.
display wiring normal?
"U4."
NO Fix the indoor/outdoor unit
YES
transmission wiring.
Reset the power supply.
The
Outdoor voltage between
unit PC board NO terminals L1 and N of the NO
microcomputer monitor outdoor unit PC board Supply 220~240 V.
(HAP) blinks. is 220~240 V.
YES
YES
The fuse on YES
the outdoor unit's PC Replace the fuse.
board is burnt.
NO
The
secondary voltage NO
of the transformer is about Replace the transformer.
22~24 V.
YES
Replace outdoor unit PC
NO Operation board (A1P).
ready lamp (H2P) is
blinking.
YES
Lamp does YES
not go off for 12 minutes Push and hold the RESET
or more. button on the outdoor unit PC
board for 5 seconds.
NO
Is
indoor - outdoor
and outdoor - outdoor unit NO
Fix the indoor/outdoor unit
transmission wiring transmission wiring.
normal?
YES
Replace the outdoor unit PC
board (A1P).
(V3187)
Troubleshooting 179
Troubleshooting by Indication on the Remote Controller Si34-603
Method of In case of controlling with 2-remote controller, check the system using microcomputer is signal
Malfunction transmission between indoor unit and remote controller (main and sub) is normal.
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Using SS1 of
YES both remote controllers YES
2-remote controllers Set one remote controller to
control. is set to "MAIN." "SUB"; turn the power supply
NO off once and then back on.
NO
Operation
All indoor NO returns to normal when NO
PC board microcomputer the power is turned off Replace indoor unit PC
monitors blink. momentarily. board.
YES YES
There is possibility of
malfunction caused by noise.
Check the surrounding area
Multi-core and turn on again.
cableis used for the YES
indoor unit remote controller Switch to double-core
transmission independent cable.
wiring. replacement
NO
Defect of remote controller PC
board or indoor unit PC board.
Replace whichever is
defective.
(V2823)
180 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of In case of controlling with 2-remote controller, check the system using microcomputer if signal
Malfunction transmission between indoor unit and remote controller (main and sub) is normal.
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Troubleshooting 181
Troubleshooting by Indication on the Remote Controller Si34-603
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
182 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
"U9" YES
has been displayed for 2 Re-diagnose by display after
minutes or more. passage of 2 minutes or more.
NO
The "UA"
display blinks on the
remote controllers of other YES
Refer to failure diagnosis for "UA"
units within the same malfunction code.
refrigerant
system.
NO
The "A1"
display blinks on
the remote controllers of YES
Refer to failure diagnosis for "A1"
other units within the malfunction code.
same refrigerant
system.
NO
The "A9"
display blinks on
the remote controllers of YES
other units within the Refer to failure diagnosis for "A9"
same refrigerant malfunction code.
system.
NO
The "U4"
display blinks on
the remote controllers of YES
Refer to failure diagnosis for "U4"
other units within the malfunction code.
same refrigerant
system.
NO
Refer to failure diagnosis for "U5"
malfunction code.
(V2826)
Troubleshooting 183
Troubleshooting by Indication on the Remote Controller Si34-603
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the outdoor
P.C. board replaced YES
The refrigerant classification has
to spare parts PC not been set yet.
board?
NO
The total
of indoor units
displaying "UA" and
indoor units connected to the NO There are too many indoor units
same refrigerant system is within the same refrigerant
within connectable system.
number of
unit∗
YES
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds.
NO
Does a malfunction occur? Normal
YES
Does the
refrigerant type of indoor NO
Matches the refrigerant type of
and outdoor unit indoor and outdoor unit.
match?
YES
Replace outdoor unit PC board
(A1P).
(V3169)
∗ The number of indoor units that can be connected to a single outdoor unit system depends on
the type of outdoor unit.
184 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Optional
controllers for
centralized control are YES
Address duplication of central
connected to the remote controller
indoor unit. The setting must be changed so
that the central remote control
address is not duplicated.
NO
Replace indoor unit PC board.
(V2828)
Troubleshooting 185
Troubleshooting by Indication on the Remote Controller Si34-603
Method of Microcomputer checks if transmission between indoor unit and centralized remote controller is
Malfunction normal.
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Malfunction of transmission between optional controllers for centralized control and indoor
Causes unit
Connector for setting master controller is disconnected.
Failure of PC board for centralized remote controller
Defect of indoor unit PC board
186 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has
an indoor unit once YES
connected been remove Reset power supply
or its address simultaneously for all optional
changed? controllers for centralized
control.
NO
Is
the power supply
turned on for indoor units NO
Turn indoor unit's power
displaying supply.
malfunction?
YES
Is
transmission wiring NO
disconnected or Fix the wiring correctly.
wired incorrectly?
YES
Is
transmission with Is the group NO
NO No. of malfunctioning
all indoor units Set the group No.
malfunctioning? indoor units set? correctly.
YES YES
Replace indoor unit PC
board.
Is
the transmission
wiring with the master NO
controller disconnected Fix the wiring correctly.
or wired
incorrectly?
YES
Is the
master controller's
connector for setting NO
Connect the connector
master controller correctly.
disconnected?
YES
Replace the central PC
board.
(V2829)
Troubleshooting 187
Troubleshooting by Indication on the Remote Controller Si34-603
Method of On check operation, the number of indoor units in terms of transmission is not corresponding to
Malfunction that of indoor units that have made changes in temperature.
Detection
Malfunction The malfunction is determined as soon as the abnormality aforementioned is detected through
Decision checking the system for any erroneous connection of units on the check operation.
Conditions
Supposed Improper connection of transmission wiring between indoor-outdoor units and outdoor-
Causes outdoor units
Failure to execute check operation
Defect of indoor unit PC board
Stop valve is left in closed
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Is the Is indoor
NO -outdoor and outdoor- YES
check operation Replace indoor unit PC board.
carried out? outdoor unit transmission
wiring normal?
YES
NO
Is
indoor - outdoor NO
and outdoor - outdoor unit After fixing incorrect wiring,
transmission wiring push and hold the RESET
normal? button on the master outdoor
unit PC board for 5 seconds.
YES ∗ The unit will not run for up to
12 minutes.
Note: Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
188 Troubleshooting
Si34-603 Troubleshooting by Indication on the Remote Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed Improper connection of transmission wiring between outdoor unit and outdoor unit outside
Causes control adaptor
Defect of indoor unit PC board
Defect of outdoor unit PC board (A1P)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is Does
electricity a malfunction
being introduce for occur even after 12
the first time after YES minutes elapses from the NO
installationor after an indoor Normal
time when electricity is
or outdoor unit PC introduced to indoor
board has been and outdoor
replaced? units?
NO YES
Is
indoor - outdoor and NO
outdoor - outdoor unit After fixing incorrect wiring,
transmission wiring push and hold the RESET
normal? button on the master outdoor
unit PC board for 5 seconds.
YES ∗ The unit will not run for up to
12 minutes.
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
NO
Does a malfunction occur? Normal
YES
Does
a "UH" malfunction occur NO
Replace indoor unit PC board.
for all indoor units in
the system?
YES
Replace outdoor unit PC
board (A1P).
(V2831)
Troubleshooting 189
Troubleshooting by Indication on the Centralized Remote Controller Si34-603
Method of Microcomputer checks if transmission between indoor unit and central remote controller is
Malfunction normal.
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Malfunction of transmission between optional controllers for centralized control and indoor unit
Causes Connector for setting master controller is disconnected.
Failure of PC board for central remote controller
Defect of indoor unit PC board
Troubleshooting Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has
an indoor unit once YES
connected been remove Reset power supply
or its address simultaneously for all optional
changed? controllers for centralized
control.
NO
Is the
power supply turned NO
on for indoor units displaying Turn indoor unit's power
malfunction? supply.
YES
Is
transmission wiring NO
disconnected or wired Fix the wiring correctly.
incorrectly?
YES
YES YES
Replace indoor unit PC
board.
Is the
transmission wiring
with the master controller NO
Fix the wiring correctly.
disconnected or wired
incorrectly?
YES
Is the
master controller's
connector for setting NO
Connect the connector
master controller correctly.
disconnected?
YES
Replace the central PC board.
(V2832)
190 Troubleshooting
Si34-603 Troubleshooting by Indication on the Centralized Remote Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting 191
Troubleshooting by Indication on the Centralized Remote Controller Si34-603
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has a once
connected optional
controller for centralized YES
Reset power supply
control been disconnected simultaneously for all optional
or its address controllers for centralized control.
changed?
NO
Is
the power supply
turned on for all optional NO
Turn on power supply for all
controllers for optional controllers for centralized
centralized control.
control?
YES
Is
the reset switch
of all optional controllers NO
for centralized control set Set reset switch to "normal."
to ''normal?''
YES
Is
transmission wiring YES
disconnected or wired Fix the wiring correctly.
incorrectly?
NO
The PC board of one of the
optional controllers for centralized
control is defective. Try turning
on/off using each optional
controllers for centralized control,
and replace the PC board of the
one that is unable to control the
indoor unit.
(V2833)
192 Troubleshooting
Si34-603 Troubleshooting by Indication on the Centralized Remote Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting 193
Troubleshooting by Indication on the Centralized Remote Controller Si34-603
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Cannot be used in
Is combination with a wiring
the wiring adaptor for YES adaptor for electrical
electrical appendices appendices. Remove the
connected? wiring adaptor for electrical
appendices and reset the
NO power supply for all optional
controllers for centralized
control simultaneously.
Are
there two Arrange so that the
or more optional connector for setting master
controllers for centralized YES control is connected to one
control connected with the controller for centralized
connector for setting control and reset the power
master supply for all optional
control? controllers for centralized
control simultaneously.
NO Disconnect the connector for
setting master control from
Reset the power supply for the master controller,
all optional controllers for connect to another optional
centralized control controller for centralized
simultaneously. control and simultaneously
If the malfunction is still not cleared: reset all optional controllers
for centralized control again.
The controller connected by
the connector for setting
master control when the
malfunction is cleared is
defective and must be
replaced.
(V2834)
194 Troubleshooting
Si34-603 Troubleshooting by Indication on the Centralized Remote Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are two
or more centralized YES
remote controllers Disconnect all centralized
connected? remote controllers except one
and reset the power supply of
the centralized remote
NO controller.
Troubleshooting 195
Troubleshooting by Indication on the Unified ON/OFF Controller Si34-603
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
196 Troubleshooting
Si34-603 Troubleshooting by Indication on the Unified ON/OFF Controller
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is a
malfunction YES
code displayed on the Diagnose the cause with the
remote controller? air conditioner's failure
diagnosis manual.
NO
Has a
once connected
indoor unit been removed YES
Reset power supply for all
or its address optional controllers for
changed? centralized control
simultaneously.
NO
Is the
power supply for
the indoor unit displaying NO
Turn the power supply of the
a malfunction indoor unit on.
turned
on?
YES
Is
transmission wiring YES
disconnected or wired Fix the wiring correctly.
incorrectly?
NO
Is Is
transmission NO the group NO
with all indoor units No. of malfunctioning Set the group No.
malfunctioning? indoor units correctly.
set?
YES YES
Is the Replace indoor unit PC board.
transmission
wiring with the master NO
controller disconnected or Fix the wiring correctly.
wired incorrectly?
YES
Is the
master
controller's connector for YES
setting master controller Connect the connector
disconnected. correctly.
NO
Replace the central PC board.
(V2841)
Troubleshooting 197
Troubleshooting by Indication on the Unified ON/OFF Controller Si34-603
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
198 Troubleshooting
Si34-603 Troubleshooting by Indication on the Unified ON/OFF Controller
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has a once
connected optional
controller for centralized YES
control been disconnected Reset power supply
or itsaddress simultaneously for all optional
changed? controllers for centralized
control.
NO
Is the
power supply
turned on for all NO
optional controllers for Turn on power supply for
centralized all optional controllers for
control? centralized control.
YES
Is the
reset switch
of all optional controllers NO
for centralized Set reset switch to
control set to "normal."
"normal"?
YES
Is
transmission wiring YES
disconnected or wired Fix the wiring correctly.
incorrectly?
NO
Is Is the
a central remote central remote YES
YES controller or schedule
controller or schedule timer Refer to failure diagnosis for
connected? timer displaying a central remote controller or
malfunction? schedule timer.
NO
NO
Is the setting
Are of the unified
two or more unified YES ON / OFF controller's NO
ON / OFF controllers switch for setting Correct the setting of the
connected? each address unified ON / OFF controller's
duplicated? switch for setting each
NO address and reset the power
supply of the unified ON /
YES OFF controller.
2A
(V2842)
Troubleshooting 199
Troubleshooting by Indication on the Unified ON/OFF Controller Si34-603
2A
Is the
wiring adaptor for YES
electrical appendices Cannot be used in
connected? combination with a wiring
adaptor for electrical
NO appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Is a schedule timer YES Is a data station YES
Schedule timer and data
connected? connected? station cannot be used in
combination. Disconnect
NO NO either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
Is a parallel interface Schedule timer and parallel
connected? interface cannot be used in
combination. Disconnect
NO either the schedule timer or
parallel interface and reset the
power supply for all optional
Is the controllers for centralized
schedule timer's control simultaneously.
YES
individual/combined Disconnect the schedule
connector timer's individual / combined
connected? connector and reset the power
supply for all optional
NO controllers for centralized
control simultaneously.
Are
there two or
more optional
controllers for centralized YES
control connected with the Arrange so that the connector
connector for setting for setting master control is
master connected to one controller for
control? centralized control and reset
the power supply for all
NO optional controllers for
centralized control
Reset the power supply simultaneously.
for all optional controllers
for centralized control
simultaneously.
200 Troubleshooting
Si34-603 Troubleshooting by Indication on the Unified ON/OFF Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed Central control address (group No.) is not set for indoor unit.
Causes Improper address setting
Improper wiring of transmission wiring
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the central
control address (group No.) NO Set by remote controller the
set for the central control address for all
indoor unit? indoor units connected to the
central control line.
YES
Is the switch NO
for setting each address Set the switch for setting each
set correctly? address correctly and
simultaneously reset the power
YES supply for all optional controllers
Is
the transmission YES
wiring disconnected or Fix the wiring correctly.
wired incorrectly?
NO
Replace the PC board of the
unified ON/OFF controller.
(V2844)
Troubleshooting 201
Troubleshooting by Indication on the Unified ON/OFF Controller Si34-603
[In cooling] ←Is the suction air temperature not more than
High suction air Short circuit
46°C?
temperature
High suction of outdoor unit High ambient temperature ←Is the outdoor temperature not more than 46°C?
air
temperature
of the High suction Short circuit ←Is the suction air temperature not more than 27°C?
condenser air temperature
of indoor unit High ambient temperature ←Is the indoor temperature not more than 27°C?
←Is the connector properly connected?
Faulty suction air thermistor of indoor unit Are the thermistor resistance characteristics normal?
[In heating]
High suction air temperature of outdoor unit ←Is the outdoor temperature not more than 16?CWB?
Faulty outdoor temperature thermistor of outdoor unit ←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation Dirty condenser
in condensing ←Is the heat exchanger clogged? (In cooling)
capacity
Mixing of non-condensable gas ←Is air or else mixed in the refrigerant system?
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
*2: In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(For details, refer to “Electronic Expansion Valve Control” on page 72.)
C: SDK04009
202 Troubleshooting
Si34-603 Troubleshooting by Indication on the Unified ON/OFF Controller
*1: For details of the compressor capacity control while in cooling, refer to “Compressor PI Control” on page 50.
*2: The “low pressure protection control” includes low pressure protection control and hot gas bypass control. For details, refer to page 61.
*3: In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (For details, refer to page 72.)
*4: In heating, the outdoor unit electronic expansion valve (EV1) is used for “superheated degree control of outdoor unit heat exchanger”.
(For details, refer to page 51.)
C: SDK04009
Troubleshooting 203
Troubleshooting by Indication on the Unified ON/OFF Controller Si34-603
1 White
Measurement point Judgment
2 Orange 1-4 1MΩ or more
2-4 100kΩ or more
3 Brown
3-4 100Ω or more
GND 4-7 100kΩ or more
4 Blue
7 Red
204 Troubleshooting
Si34-603
Part 8
Appendix
1. Piping Diagrams..................................................................................206
1.1 Outdoor Unit .........................................................................................206
1.2 Indoor Unit............................................................................................207
2. Wiring Diagrams..................................................................................210
2.1 Outdoor Unit .........................................................................................210
2.2 Field Wiring ..........................................................................................212
2.3 Indoor Unit............................................................................................213
3. Option List ...........................................................................................226
3.1 Option List of Controllers......................................................................226
3.2 Option List of Outdoor Unit...................................................................228
4. Example of Connection .......................................................................229
5. Thermistor Resistance / Temperature Characteristics........................231
6. Pressure Sensor .................................................................................233
7. Method of Replacing the Inverter’s Power Transistors Modules.........234
Appendix 205
Piping Diagrams Si34-603
1. Piping Diagrams
1.1 Outdoor Unit
RX(Y)MQ4 / 5 / 6PVE
3D052628
206 Appendix
Si34-603 Piping Diagrams
Fan
(2)
(3)
Liquid piping connection port
(Flare connection)
(1)
Filter Electronic Filter
expansion valve
DU220-602J
(mm)
Capacity GAS Liquid
20 / 25 / 32 / 40 / 50M(A) φ12.7 φ6.4
63 / 80 / 100 / 125M(A) φ15.9 φ9.5
Appendix 207
Piping Diagrams Si34-603
FXDQ
4D043864H
208 Appendix
Si34-603 Piping Diagrams
FXUQ + BEVQ
Indoor Unit
4D037995F
Connection Unit
4D034127B
Appendix 209
Wiring Diagrams Si34-603
2. Wiring Diagrams
2.1 Outdoor Unit
2.1.1 Heat Pump
RXYMQ4 / 5 / 6PVE
3D051730D
210 Appendix
Si34-603 Wiring Diagrams
3D051731C
Appendix 211
Wiring Diagrams Si34-603
3D052597
212 Appendix
Si34-603 Wiring Diagrams
3D039556A
Appendix 213
Wiring Diagrams Si34-603
3D039557A
214 Appendix
Si34-603 Wiring Diagrams
3D039600A
Appendix 215
Wiring Diagrams Si34-603
3D039564C
216 Appendix
Si34-603 Wiring Diagrams
3D045500C
Appendix 217
Wiring Diagrams Si34-603
3D049604A
218 Appendix
Si34-603 Wiring Diagrams
3D039561A
Appendix 219
Wiring Diagrams Si34-603
3D039620B
220 Appendix
Si34-603 Wiring Diagrams
3D039801D
Appendix 221
Wiring Diagrams Si34-603
3D034206C
222 Appendix
Si34-603 Wiring Diagrams
3D039826D
Appendix 223
Wiring Diagrams Si34-603
3D044973A
224 Appendix
Si34-603 Wiring Diagrams
3D044901B
Appendix 225
Option List Si34-603
3. Option List
3.1 Option List of Controllers
Operation Control System Optional Accessories
Type FXDQ-N(A) FXLQ-MA
No. FXCQ-M FXFQ-M FXKQ-MA FXUQ-MA FXSQ-M FXMQ-MA FXHQ-MA FXAQ-MA
Item FXDQ-P FXNQ-MA
Remote Wireless BRC7C62 BRC7E61W BRC4C61 BRC4C62 BRC7C528W BRC4C62 BRC7E63W BRC7E618 BRC4C62
1 controller Wired BRC1C62
2 Wired remote controller
with weekly schedule timer BRC1D61
Simplified remote Note 8 Note 8 Note 8
3 — — —
controller BRC2C51 BRC2C51 BRC2C51
Remote controller for
4 — BRC3A61 — BRC3A61 — BRC3A61
hotel use
5 Adaptor for wiring KRP1B61 KRP1B59 KRP1B61 KRP1B56 — KRP1B61 KRP1C-3 — KRP1B61
Wiring adaptor for
6-1 KRP2A61 KRP2A62 KRP2A61 KRP2A53 KRP2A62 KRP2A61 KRP2A62 KRP2A61 KRP2A61
electrical appendices (1)
Wiring adaptor for
6-2 KRP4A51 KRP4A53 KRP4A51 KRP4A54 KRP4A53 KRP4A51 KRP4A52 KRP4A51 KRP4A51
electrical appendices (2)
7 Remote sensor KRCS01-1 — KRCS01-1
Installation box for Note 2, 3 Note 2, 3 Note 4, 6 Note 5 Note 3 Note 2, 3
8 — KRP1B97 — —
adaptor PC board KRP1B96 KRP1D98 KRP1B101 KRP4A91 KRP1C93 KRP4A93
9 Central remote controller DCS302CA61
Electrical box with earth
9-1 KJB311A
terminal (3 blocks)
10 Unified on/off controller DCS301BA61
Electrical box with earth
10-1 KJB212A
terminal (2 blocks)
Noise filter (for
10-2 electromagnetic interface KEK26-1
use only)
11 Schedule timer DST301B(A)61
External control adaptor
12 for outdoor unit (Must be DTA104A6 DTA104A61 — DTA104A61 DTA104A61
installed on indoor units) DTA104A61 2 DTA104A53 DTA104A62 DTA104A61
13
Interface adaptor for — — — — Note 7 — — — —
SkyAir-series DTA102A52
Note:
1. Installation box (No.8) is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box (No. 8) is necessary for second adaptor.
6. Installation box (No. 8) is necessary for each adaptor.
7. This adaptor is required when connecting with optional controller for centralized control.
8. BRC2A51 is also available.
Various PC Boards
No. Part name Model No. Function
KRP1B56
KRP1B57
1 Adaptor for wiring KRP1B59 PC board when equipped with auxiliary electric heater in the indoor unit.
KRP1B61
KRP1C3
Up to 1024 units can be centrally controlled in 64 different groups.
2 DIII-NET Expander Adaptor DTA109A51 Wiring restrictions (max. length: 1000m, total wiring length: 2000m, max. number of
branches: 16) apply to each adaptor.
System Configuration
No. Part name Model No. Function
Up to 64 groups of indoor units (128 units)can be connected, and ON/OFF, temperature
1 Central remote controller DCS302CA61 setting and monitoring can be accomplished individually or simultaneously. Connectable up
to “2” controllers in one system.
Up to 16 groups of indoor units (128 units) can be turned, ON/OFF individually or
2 Unified ON/OFF controller DCS301BA61 simultaneously, and operation and malfunction can be displayed. Can be used in
combination with up to 8 controllers.
3 Schedule timer DST301BA61 Programmed time weekly schedule can be controlled by unified control for up to 64 groups
of indoor units (128 units). Can turn units ON/OFF twice per day.
Unification adaptor for computerized
4 DCS302A52 Interface between the central monitoring board and central control units
control
5 Interface adaptor for SkyAir-series DTA102A52 Adaptors required to connect products other than those of the VRV System to the high-
6 Central control adaptor kit DTA107A55 speed DIII-NET communication system adopted for the VRV System.
To use any of the above optional controllers, an appropriate adaptor must be installed on
7 Wiring adaptor for other air-conditioner DTA103A51 the product unit to be controlled.
DIII-NET Up to 1,024 units can be centrally controlled in 64 different groups.
8 Expander adaptor DTA109A51 Wiring restrictions (max. length : 1,000m, total wiring length : 2,000m, max. number of
branches : 16) apply to each adaptor.
9 Mounting plate KRP4A92 Fixing plate for DTA109A51
Note:
Installation box for adaptor must be procured on site.
226 Appendix
Si34-603 Option List
Controller
Controller
DIII-NET
1-1 Hardware plus DCS601A52 • Additional 64 groups (10 outdoor units) is possible.
adaptor
Option
1-2 P.P.D. DCS002C51 • P.P.D.: Power Proportional Distribution function
Software • Monitors and controls the air conditioning system using the Internet
1-3 Web DCS004A51
and Web browser application on a PC.
1-4 Electrical box with earth terminal (4blocks) KJB411A • Wall embedded switch box.
128 units DAM602B52
256 units DAM602B51
Manager III
Number of units to be DAM602B51x2 Air conditioner management system (featuring minimized engineering)
intelligent
2 512 units
connected that can be controlled by personal computers.
768 units DAM602B51x3
1024 units DAM602B51x4
P.P.D. DAM002A51 • P.P.D.: Power Proportional Distribution function
2-1 Option Software
ECO. DAM003A51 Software for energy-saving control.
2-2 Optional DIII Ai unit DAM101A51 Analog input for "sliding temperature" function (to reduce cold shock) for
intelligent Manager EC021.
Interface unit to allow communications between VRV and BMS.
2 Interface for use in BACnet® Operation and monitoring of air-conditioning systems through BACnet®
Communication
3 DMS502A51
communications.
Line
3-1 Optional DIII board DAM411A1 Expansion kit, installed on DMS502A51, to provide 3 more DIII-NET
communication ports. Not usable independently.
Expansion kit, installed on DMS502A51, to provide 16 more wattmeter
3-2 Optional Di board DAM412A1 pulse input points. Not usable independently.
Interface unit to allow communications between VRV and BMS.
4 3 Interface for use in LONWORKS DMS504B51 Operation and monitoring of air-conditioning systems through
LONWORKS communication.
Enables ON/OFF command, operation and display of malfunction; can be used
5 Basic unit DPF201A51
in combination with up to 4 units.
interface
Parallel
Temperature
6 DPF201A52 Enables temperature measurement output for 4 groups; 0-5VDC.
Contact/Analog signal
measurement units
7 Temperature setting units DPF201A53 Enables temperature setting input for 16 groups; 0-5VDC.
8 Unification adaptor for computerized DCS302A52 Interface between the central monitoring board and central control units
control
Wiring adaptor for electrical Simultaneously controls air-conditioning control computer and up to 64 groups of
9-1 KRP2A53, 61, 62
appendices (1) indoor units.
Wiring adaptor for electrical To control the group of indoor units collectively, which are connected by the
9-2 appendices (2) KRP4A51-54 transmission wiring of remote controller.
External control adaptor for outdoor DTA104A53, 61, Cooling/Heating mode change over. Demand control and Low noise control are
13 unit (Must be installed on indoor units.) 62 available between the plural outdoor units.
Notes:
1. PPD does not support Connection Unit Series.
2. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-
Conditioning Engineers (ASHRAE).
3. LONWORKS is a registered trade mark of Echelon Corporation.
Appendix 227
Option List Si34-603
Refnet header
(MAX. 4 branch) (MAX. 8 branch)
Piping
228 Appendix
Si34-603 Example of Connection
4. Example of Connection
Example of connection Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
(Connection of 8 indoor units
Outdoor unit REFNET joint (A-G) Outdoor unit REFNET joint (A • B) Outdoor unit Refnet header
Heat pump system)
i
a a
A B
a b c d e f g k
b j
A B C D E F G
H1
P H1 Refnet header 7 8 H1
h i j k l m n H2 g
1 2 3 4 5 6 7 H2 c d e f g h b c d e f h i
1 2 3 4 5 6 1 2 3 4 5 6 7 H2
8
8
Indoor units (1-8) Indoor units (1-8) Indoor units (1-8)
Pipe length between outdoor and indoor units ≤ 150m
Actual pipe length
Maximum Example unit 8: a + b + c + d + e + f + g + p ≤ 150m Example unit 6: a + b + h ≤ 120m, unit 8: a + i + k ≤ 150m Example unit 8: a + i ≤ 150m
allowable Between outdoor and indoor units Equivalent length Equivalent pipe length between outdoor and indoor units ≤ 175m (assume equivalent pipe length of refnet joint to be 0.5m, that of refnet header to be 1m, calculation purposes)
length
Total extension length Total piping length from outdoor unit to all indoor units ≥10m, ≤ 300m
Allowable Between outdoor and indoor units Difference in height Difference in height between outdoor and indoor units (H1) ≤ 50m (Max 40m if the outdoor unit is below)
height
length Between indoor and indoor units Difference in height Difference in height between adjacent indoor units (H2) ≤ 15m
Pipe length from first refrigerant branch kit (either refnet joint or refnet header ) to indoor unit ≤ 40m
Allowable length after the branch Actual pipe length
Example unit 8: b + c + d + e + f + g + p ≤ 40m Example unit 6: b + h ≤ 40m, unit 8:i + k ≤ 40m Example unit 8: i ≤ 40m
Refrigerant branch kit selection Use refnet joint from the following table. How to select the refnet header
Refrigerant branch kits can only be Outdoor unit capacity type Refrigerant branch kit name • Choose from the following table below the REFNET header according
used with R-410A. to the number of units on the system.
RX(Y)MQ4,5, 6 type KHRP26M22T
Outdoor unit capacity type Refrigerant branch kit name
KHRP26M22H (Max. 4 branch)
RX(Y)MQ4, 5, 6 type
KHRP26M33H (Max. 8 branch)
Pipe size selection Piping between outdoor unit and refrigerant branch kit Piping between refrigerant branch kits Between refrigerant branch kit and indoor unit
〈Caution on selecting connection pipes〉 • Match to the size of the connection piping on the outdoor unit. • Use the pipe size from the following table. • Pipe size for direct connection to indoor unit must be the
• When the equivalent piping length between the outdoor unit and the indoor unit is same as the connection size of indoor unit.
90 m or more, make sure to use a thicker pipe as the main pipe on the gas side. Outdoor unit connection pipe size (Unit: mm) Connection pipe size (Unit: mm) Indoor unit connection pipe size (Unit: mm)
When the air-conditioning ability is reduced due to the refrigerant piping distance,
a thicker pipe may be used also as the main pipe. Piping size Piping size (outer diameter × minimum thickness) Piping size
Outdoor unit (outer diameter × minimum thickness) Indoor unit (outer diameter × minimum thickness)
capacity type capacity type
[Gas side] Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe
RXYMQ4,5 type φ15.9 → φ 19.1 φ 15.9 × 1.0 φ 15.9 × 1.0 φ 9.5 × 0.8
RX(Y)MQ4,5 20 · 25 · 32 · φ 12.7 × 0.8 φ 6.4 × 0.8
RXYMQ6 type φ19.1 → φ 22.2
type φ 19.1 × 1.0 * 40 · 50 type
The first refrigerant φ 9.5 × 0.8
RX(Y)MQ6 φ 19.1 × 1.0 63 · 80 · 100 ·
branching kit φ 15.9 × 1.0 φ 9.5 × 0.8
type φ 22.2 × 1.0 * 125 type
Main pipe
Outdoor unit * When the size is larger
Enlarge
Indoor unit
Caution) In brazing connection in the size increase area in the piping, use a different-
diameter joint for connection. (The different-diameter joint should be arranged
in the local field.)
The connection area is located near the outdoor unit (usually after the first
bending outside the unit).
How to calculate the additional refrigerant to be charged Example for refrigerant branch using refnet joint and refnet header
Additional refrigerant to be charged R (Kg) Total length (m) Total length (m)
R= of liquid piping ×0.054 + of liquid piping ×0.022 The piping a: 9.5 × 30m d: 9.5 × 13m g: 16.4 × 10m j : 16.4 × 10m
R should be rounded off in units of 0.1Kg. size at φ9.5 size at φ6.4 lengths are as b: 9.5 × 10m e: 6.4 × 10m h: 16.4 × 20m k: 16.4 × 19m
at right c: 09.5 × 10m f : 6.4 × 10m i : 9.5 × 10m
R= 73 0.054 + 69 0.022 = 5.46
Appendix 229
Example of Connection Si34-603
230 Appendix
Si34-603 Thermistor Resistance / Temperature Characteristics
Appendix 231
Thermistor Resistance / Temperature Characteristics Si34-603
Outdoor Unit
Thermistors for
Discharge Pipe
(R2T)
(kΩ)
T°C 0.0 0.5 T°C 0.0 0.5 T°C 0.0 0.5
0 640.44 624.65 50 72.32 70.96 100 13.35 13.15
1 609.31 594.43 51 69.64 68.34 101 12.95 12.76
2 579.96 565.78 52 67.06 65.82 102 12.57 12.38
3 552.00 538.63 53 64.60 63.41 103 12.20 12.01
4 525.63 512.97 54 62.24 61.09 104 11.84 11.66
5 500.66 488.67 55 59.97 58.87 105 11.49 11.32
6 477.01 465.65 56 57.80 56.75 106 11.15 10.99
7 454.60 443.84 57 55.72 54.70 107 10.83 10.67
8 433.37 423.17 58 53.72 52.84 108 10.52 10.36
9 413.24 403.57 59 51.98 50.96 109 10.21 10.06
10 394.16 384.98 60 49.96 49.06 110 9.92 9.78
11 376.05 367.35 61 48.19 47.33 111 9.64 9.50
12 358.88 350.62 62 46.49 45.67 112 9.36 9.23
13 342.58 334.74 63 44.86 44.07 113 9.10 8.97
14 327.10 319.66 64 43.30 42.54 114 8.84 8.71
15 312.41 305.33 65 41.79 41.06 115 8.59 8.47
16 298.45 291.73 66 40.35 39.65 116 8.35 8.23
17 285.18 278.80 67 38.96 38.29 117 8.12 8.01
18 272.58 266.51 68 37.63 36.98 118 7.89 7.78
19 260.60 254.72 69 36.34 35.72 119 7.68 7.57
20 249.00 243.61 70 35.11 34.51 120 7.47 7.36
21 238.36 233.14 71 33.92 33.35 121 7.26 7.16
22 228.05 223.08 72 32.78 32.23 122 7.06 6.97
23 218.24 213.51 73 31.69 31.15 123 6.87 6.78
24 208.90 204.39 74 30.63 30.12 124 6.69 6.59
25 200.00 195.71 75 29.61 29.12 125 6.51 6.42
26 191.53 187.44 76 28.64 28.16 126 6.33 6.25
27 183.46 179.57 77 27.69 27.24 127 6.16 6.08
28 175.77 172.06 78 26.79 26.35 128 6.00 5.92
29 168.44 164.90 79 25.91 25.49 129 5.84 5.76
30 161.45 158.08 80 25.07 24.66 130 5.69 5.61
31 154.79 151.57 81 24.26 23.87 131 5.54 5.46
32 148.43 145.37 82 23.48 23.10 132 5.39 5.32
33 142.37 139.44 83 22.73 22.36 133 5.25 5.18
34 136.59 133.79 84 22.01 21.65 134 5.12 5.05
35 131.06 128.39 85 21.31 20.97 135 4.98 4.92
36 125.79 123.24 86 20.63 20.31 136 4.86 4.79
37 120.76 118.32 87 19.98 19.67 137 4.73 4.67
38 115.95 113.62 88 19.36 19.05 138 4.61 4.55
39 111.35 109.13 89 18.75 18.46 139 4.49 4.44
40 106.96 104.84 90 18.17 17.89 140 4.38 4.32
41 102.76 100.73 91 17.61 17.34 141 4.27 4.22
42 98.75 96.81 92 17.07 16.80 142 4.16 4.11
43 94.92 93.06 93 16.54 16.29 143 4.06 4.01
44 91.25 89.47 94 16.04 15.79 144 3.96 3.91
45 87.74 86.04 95 15.55 15.31 145 3.86 3.81
46 84.38 82.75 96 15.08 14.85 146 3.76 3.72
47 81.16 79.61 97 14.62 14.40 147 3.67 3.62
48 78.09 76.60 98 14.18 13.97 148 3.58 3.54
49 75.14 73.71 99 13.76 13.55 149 3.49 3.45
50 72.32 70.96 100 13.35 13.15 150 3.41 3.37
232 Appendix
Si34-603 Pressure Sensor
6. Pressure Sensor
PH = 1.38V-0.69 PH : Detected Pressure [High Side] MPa
PL = 0.57V-0.28 PL : Detected Pressure [Low Side] MPa
Detected Pressure PH : High pressure (MPa) VH : Output Voltage [High Side] VDC
VL : Low pressure (MPa) VL : Output Voltage [Low Side] VDC
V : Voltage (V)
Appendix 233
Method of Replacing the Inverter’s Power Transistors Modules Si34-603
Inverter PC board
234 Appendix
Si34-603 Method of Replacing the Inverter’s Power Transistors Modules
The following abnormalities are also doubted besides the PC board abnormality.
1 Faulty compressor (ground fault, ground leakage)
1 Faulty fan motor (ground leakage)
Appendix 235
Method of Replacing the Inverter’s Power Transistors Modules Si34-603
236 Appendix
Si34-603
Part 9
Precautions for New
Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................238
1.1 Outline ..................................................................................................238
1.2 Refrigerant Cylinders............................................................................240
1.3 Service Tools........................................................................................241
Temperature Steam pressure Density Specific heat at constant Specific enthalpy Specific entropy
( ) (kPa) (kg/m3 ) pressure (kJ/kgK) (kJ/kg) (kJ/KgK)
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Cylinder
Siphon tube
Refrigerant can be charged in liquid state with cylinder in
upright position.
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same way as any other high-pressure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releases gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
Tool compatibility
Compatibility
Tool HFC HCFC Reasons for change
R-410A R-407C R-22
2Do not use the same tools for R-22
Gauge manifold and R-410A.
Charge hose ✕ 2Thread specification differs for
R-410A and R-407C.
Charging cylinder ✕ { 2Weighting instrument used for HFCs.
Gas detector { ✕ 2The same tool can be used for HFCs.
Vacuum pump 2To use existing pump for HFCs,
(pump with reverse flow { vacuum pump adaptor must be
preventive function) installed.
Weighting instrument {
2Seal material is different between
Charge mouthpiece ✕ R-22 and HFCs.
2Thread specification is different
between R-410A and others.
Flaring tool (Clutch type) { 2For R-410A, flare gauge is necessary.
Torque wrench { 2Torque-up for 1/2 and 5/8
Pipe cutter {
Pipe expander {
Pipe bender {
Pipe assembling oil ✕ 2Due to refrigerating machine oil
change. (No Suniso oil can be used.)
Refrigerant recovery
device Check your recovery device.
Refrigerant piping See the chart below. 2Only φ19.1 is changed to 1/2H material
while the previous material is "O".
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
* O: Soft (Annealed)
H: Hard (Drawn)
1. Flaring tool
Flare gauge
Specifications
2 Dimension A
Unit:mm
Tube O.D. A +0−0.4
Nominal size
Do Class-2 (R-410A) Class-1 (Conventional)
1/4 6.35 9.1 9.0
3/8 9.52 13.2 13.0
1/2 12.70 16.6 16.2
5/8 15.88 19.7 19.4
3/4 19.05 24.0 23.3
Differences
2 Change of dimension A
Dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
2. Torque wrench
Specifications
2 Dimension B Unit:mm
Nominal size Class-1 Class-2 Previous
1/2 24 26 24
5/8 27 29 27
No change in tightening torque
No change in pipes of other sizes
Differences
2 Change of dimension B
Only 1/2", 5/8" are extended
Dimension B
Specifications
2 Discharge speed z Maximum degree of vacuum
50 l/min (50Hz) Select a vacuum pump which is able to keep
60 l/min (60Hz) the vacuum degree of the system in excess of
2 Suction port UNF7/16-20(1/4 Flare) –100.7 kPa (5 torr – 755 mmHg).
UNF1/2-20(5/16 Flare) with adapter
Differences
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
4. Leak tester
Specifications
2 Hydrogen detecting type, etc.
2 Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2 Offers high rust resistance and stability over long period of time.
Differences
2 Can be used for R-410A and R-22 units.
Specifications
2 High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
2 Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
2 1/4" → 5/16" (2min → 2.5min)
2 No oil is used in pressure test of gauges.
→ For prevention of contamination
2 Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
2 Change in pressure
2 Change in service port diameter
Specifications
2 Working pressure 5.08 MPa (51.8 kg/cm2)
2 Rupture pressure 25.4 MPa (259 kg/cm2)
2 Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
2 Pressure proof hose
2 Change in service port diameter
2 Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
2 Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
2 The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Specifications
2 High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2 Measurement is based on weight to prevent change of mixing ratio during charging.
10.Charge mouthpiece
Specifications
2 For R-410A, 1/4"→ 5/16" (2min → 2.5min)
2 Material is changed from CR to H-NBR.
Differences
2 Change of thread specification on hose connection side (For the R-410A use)
2 Change of sealer material for the HFCs use.
Index
A Electrical and Functional Parts
A0 .........................................................................130 Outdoor Unit ................................................... 36
A1 .........................................................................131 Electronic Expansion Valve PI Control .................. 51
A3 .........................................................................132 Error of External Protection Device ..................... 130
A6 .........................................................................134 Excessive Number of Indoor Units ...................... 184
A7 .........................................................................135
A9 .........................................................................137 F
Abnormal Discharge Pipe Temperature ...............155 F3 ........................................................................ 155
About Refrigerant R-410A ....................................238 F6 ........................................................................ 156
Actuation of High Pressure Switch .......................147 Fan Motor (M1F) Lock, Overload ........................ 134
Actuation of Low Pressure Sensor .......................149 Field Setting .......................................................... 79
Address Duplication of Field Setting from Outdoor Unit ............................. 92
Central Remote Controller ............................185 Field Setting from Remote Controller .................... 79
Address Duplication, Improper Setting .................195 Filter Sign Setting .................................................. 84
AF .........................................................................139 Freeze Prevention ................................................. 70
AJ .........................................................................140 Functional Parts Layout ........................................ 46
Applicable Range of Field Setting ..........................83
Auto Restart after Power Failure Reset .................85 H
H9 ........................................................................ 157
C Heating Operation Prohibition ............................... 64
C4 .........................................................................141 High Pressure Protection Control .......................... 60
C5 .........................................................................142 High Voltage of Capacitor in
C9 .........................................................................143 Main Inverter Circuit ..................................... 171
CA ........................................................................144
Centralized Control Group No. Setting ...................88 I
Check for causes of drop in low pressure ............203 Improper Combination of Optional Controllers for
Check for causes of rise in high pressure ............202 Centralized Control ...................................... 193
Check Operation ....................................................75 Inverter Compressor Abnormal ........................... 167
Check Operation not Executed ............................177 Inverter Current Abnormal ................................... 168
CJ .........................................................................145 Inverter Protection Control .................................... 63
Compressor Motor Lock .......................................151 Inverter Start up Error ......................................... 169
Compressor PI Control ...........................................50
Contents of Control Modes ....................................90 J
Cool / Heat Mode Switching .................................101 J3 ........................................................................ 158
Cooling Operation Fan Control ..............................52 J5 ........................................................................ 159
J6 ........................................................................ 160
D J7 ........................................................................ 161
Defrosting Operation ..............................................56 J9 ........................................................................ 162
Demand Operation .................................................64 JA ........................................................................ 163
Detailed Explanation of Setting Modes ..................84 JC ........................................................................ 164
Discharge Pipe Protection Control .........................62
Display “Under Host Computer Integrate Control” L
Blinks (Repeats Double Blink) ......................201 L1 ........................................................................ 165
Display “Under Host Computer Integrate Control” L4 ........................................................................ 166
Blinks (Repeats Single Blink) ........................198 L5 ........................................................................ 167
Drain Level above Limit ........................................139 L8 ........................................................................ 168
Drain Pump Control ................................................65 L9 ........................................................................ 169
LC ........................................................................ 170
E Louver Control for Preventing Ceiling Dirt ............. 67
E1 .........................................................................146 Low Pressure Drop Due to Refrigerant Shortage or
E3 .........................................................................147 Electronic Expansion Valve Failure .............. 173
E4 .........................................................................149 Low Pressure Protection Control .......................... 61
E5 .........................................................................151
E7 .........................................................................152 M
E9 .........................................................................153 M1 ....................................................................... 191
M8 ....................................................................... 192
MA ....................................................................... 193
Index i
Si34-603
ii Index
Si34-603
C L
Centralized Control Group No. Setting ...................88 Louver Control for Preventing Ceiling Dirt ............. 67
BRC1C Type ...................................................88 Low Pressure Drop Due to Refrigerant Shortage or
BRC4C Type ...................................................89 Electronic Expansion Valve Failure ............. 173
BRC7C Type ...................................................89 Low Pressure Protection Control .......................... 61
BRC7E Type ....................................................89
Group No. Setting Example .............................89 M
Check for causes of drop in low pressure ............203 Malfunction of Capacity Determination
Check for causes of rise in high pressure ............202 Device .......................................................... 140
Check for Fan Motor Connector ...........................204 Malfunction of Discharge Pipe Thermistor
Check Operation ....................................................75 (R2T) ............................................................ 158
Check Operation not Executed ............................177 Malfunction of Drain Level Control System
Check Work Prior to Turn Power Supply On ..........74 (33H) ............................................................ 132
Compressor Motor Lock .......................................151 Malfunction of High Pressure Sensor .................. 163
Contents of Control Modes ....................................90 Malfunction of Inverter Radiating Fin
How to Select Operation Mode ........................91 Temperature Rise ........................................ 166
Cooling Operation Fan Control ..............................52 Malfunction of Inverter Radiating Fin
Temperature Rise Sensor ............................ 172
D Malfunction of Low Pressure Sensor .................. 164
Display “Under Host Computer Integrate Control” Malfunction of Moving Part of Electronic
Blinks (Repeats Double Blink) ......................201 Expansion Valve (20E) ................................ 137
Display “Under Host Computer Integrate Control” Malfunction of Moving Part of Electronic Expansion
Blinks (Repeats Single Blink) ........................198 Valve (Y1E, Y3E) ......................................... 153
Display of sensor and address data .....................122 Malfunction of Outdoor Unit Fan Motor ............... 152
Drain Level above Limit .......................................139 Malfunction of Subcooling Heat Exchanger Gas
Drain Pump Control ...............................................65 Pipe Thermistor (R6T) ................................. 162
When the Float Switch is Tripped and “AF” is Malfunction of Swing Flap Motor (MA) ................ 135
Displayed on the Remote Controller ...66 Malfunction of System, Refrigerant System
When the Float Switch is Tripped During Heating Address Undefined ...................................... 189
Operation ............................................66 Malfunction of Thermistor (R1T) for
When the Float Switch is Tripped while the Outdoor Air ................................................... 157
Cooling Thermostat is OFF ................65 Malfunction of Thermistor (R1T) for
When the Float Switch is Tripped while the Suction Air .................................................... 143
Cooling Thermostat is ON ..................65 Malfunction of Thermistor (R2T) for
Heat Exchanger ........................................... 141
E Malfunction of Thermistor (R3T) for Gas Pipes ... 142
Error of External Protection Device ......................130 Malfunction of Thermistor (R3T, R5T) for
Excessive Number of Indoor Units .......................184 Suction Pipe 1, 2 .......................................... 159
Malfunction of Thermistor (R4T) for
F Outdoor Unit Heat Exchanger ...................... 160
Fan Motor (M1F) Lock, Overload .........................134 Malfunction of Thermistor (R7T) for
Freeze Prevention ..................................................70 Outdoor Unit Liquid Pipe .............................. 161
Functional Parts Layout .........................................46 Malfunction of Thermistor for Discharge Air ........ 144
Malfunction of Thermostat Sensor in Remote
H Controller ..................................................... 145
High Pressure Protection Control ...........................60 Malfunction of Transmission between Central
High Voltage of Capacitor in Remote Controller and Indoor Unit .............. 186
Main Inverter Circuit ......................................171 Malfunction of Transmission between Centralized
Remote Controller and Indoor Unit .............. 190
O
Operation Lamp Blinks .........................................196
Operation Mode .....................................................48
Operation of the Remote Controller’s Inspection /
Test Operation Button ...................................120
Outdoor Unit PC Board Layout ..............................78
P
PC Board Defect ................................. 131, 146, 191
Piping Diagrams ...................................................206
Power Supply Insufficient or Instantaneous
Failure ...........................................................175
Pressure Sensor ..................................................233
R
Refrigerant Circuit ..................................................44
Refrigerant Overcharged .....................................156
Remote Controller Self-Diagnosis Function .........123
Remote Controller Service Mode .........................121
S
Self-diagnosis by Wired Remote Controller .........117
Self-diagnosis by Wireless Remote Controller .....118
Setting of Low Noise Operation and Demand
Operation ......................................................103
Image of operation .........................................104
Setting of Refrigerant Additional Charging
Operation ......................................................107
Check Operation ............................................109
Simplified Remote Controller .................................81
BRC2C51 ........................................................81
System is not Set yet ...........................................188
T
Thermostat Sensor in Remote Controller ...............68
Cooling ............................................................68
Heating ............................................................69
Torque wrench .....................................................243
Troubleshooting by Remote Controller ................116
Turn Power On .......................................................74
W
Weigher for refrigerant charge .............................246
Wired Remote Controller ........................................79
Wireless Remote Controller - Indoor Unit ..............80
BRC4C type .....................................................80
Service Manual /
R-410A RX(Y)MQ4·5·6PVE
RX(Y)MQ4·5·6PVE
R-410A
Heat Pump 50/60Hz
Si34-603
Cooling Only 50/60Hz
July