High Performance Air Conditioning

VRF inverter multi-system air-conditioning products

50Hz
09KX01E-A-0

4")

History of Technologies
more efficient , more sophisticated

KX2

KX4

KX6
(8~12HP)

New Line Up

Contents
Introduction Outdoor units Indoor units Control systems Service and maintenance Further information 4~13 14~29 30~57 58~62 63 64~69

4")

Product Line Up

<Outdoor units>
from 11.2kW up to 136.0kW(24models)
1 Outdoor unit type
Capacity Model Index

4HP 11.2

5HP 14.0

6HP 15.5

8HP 22.4

10HP 28.0

12HP 33.5

14HP 40.0

16HP 45.0

18HP 50.4

20HP 56.0

22HP 61.5

24HP 68.0

2 Outdoor units type


Capacity Model Index

26HP 73.5

28HP 80.0

30HP 85.0

32HP 90.0

34HP 96.0

36HP

38HP

40HP

42HP

44HP

46HP

48HP

101.0 106.5 113.0 118.0 123.5 130.0 136.0

4HP FDC112KXEN6 FDC112KXES6

5HP FDC140KXEN6 FDC140KXES6

6HP FDC155KXEN6 FDC155KXES6 1-phase 3-phase

8HP FDC224KXE6

10HP FDC280KXE6

12HP FDC335KXE6

12HP FDC335KXE6-K 20HP FDC560KXE6

14HP FDC400KXE6 20HP FDC560KXE6-K

16HP FDC450KXE6 22HP FDC615KXE6

18HP FDC504KXE6 24HP FDC680KXE6

26HP 12+14

28HP 14+14

30HP 14+16

32HP 16+16

34HP 16+18

36HP 18+18

FDC735KXE6 FDC800KXE6 FDC850KXE6 FDC900KXE6 FDC960KXE6 FDC1010KXE6 FDC335KXE6-K FDC400KXE6 FDC400KXE6 FDC450KXE6 FDC450KXE6 FDC504KXE6 FDC400KXE6 FDC400KXE6 FDC450KXE6 FDC450KXE6 FDC504KXE6 FDC504KXE6 38HP 18+20 40HP 20+20 42HP 20+22 44HP 22+22 46HP 22+24 48HP 24+24

FDC1065KXE6 FDC1130KXE6 FDC1180KXE6 FDC1235KXE6 FDC1300KXE6 FDC1360KXE6 FDC504KXE6 FDC560KXE6 FDC560KXE6-K FDC615KXE6 FDC615KXE6 FDC680KXE6 FDC560KXE6 FDC560KXE6 FDC615KXE6 FDC615KXE6 FDC680KXE6 FDC680KXE6
1.FDC335KXE6(12HP), FDC560KXE6-K, FDC615KXE6(22HP) & FDC680KXE6(24HP)are applied 3D compressor. 2.FDC335KXE6-K & FDC560KXE6-K are only used for combining with other models.

<Indoor units>
Wide variety of 15 types 77 models
A range of 15 types of exposed or concealed indoor units, in wide capacities, 77 indoor models. The best selection of indoor units for many kinds of rooms and preference can be available from our full lineup.

Indoor units lineup


Type

15 types 77 models
Capacity Model Index FDT 0.8HP 22 1HP 1.25HP 1.6HP 28 36 45 2HP 56 2.5HP 3.2HP 71 90 4HP 112 5HP 140 6HP 160 8HP 224 10HP 280

4way

4way Compact (600 x 600) Ceiling Cassette

FDTC

2way

FDTW

1way Compact

FDTQ

1way High Static Pressure Low/Middle Static Pressure Duct Connected Low Static Pressure (Ultra thin) Compact & Flexible

FDTS

FDU

FDUM

FDQS

FDUH

Wall Mounted

FDK

Ceiling Suspended

FDE

with casing Floor Standing without casing

FDFL

FDFU

OA Processing unit

FDU-F

Type Fresh Air Ventilation and Heat Exchange unit SAF

Air flow M3/h

250

350

500

800

1000

R410A

1. High Efficiency
The industry's highest COP levels
We have cleared the class A standard, the highest energy saving level, with our high COP (Coefficient Of Performance).

EER in Cooling
COP 4.5 4.0 3.5 3.0 2.5 4 5 6

CLASS

COP in Heating

CLASS

4.00 3.36 3.29

4.00

3.2
3.46 3.41 3.55 3.47 3.42 3.34

COP 4.5 4.0 3.5 3.0 2.5

4.33 3.71 3.72

4.15

3.6
3.84 3.71 3.84 3.82 3.74 3.75

10

12

14

16

18

20

HP

10

12

14

16

18

20

HP

(ISO-T1 conditions)

Power Consumption[kW] *COP = Capacity[kW] /range ensures reduced running costs and reduced environmental impact. COP across the KX6 *

2. Compact Design
4~6HP
Volume

35% reduced
Weight

1FAN

34% reduced
Previous Model
H1300 x W970 x D370mm 125kg / 0.47m3
Transportation Becomes much easier Easier to hide behind the fence

New Model
H845 x W970 x D370mm 82kg / 0.30m3

(Harmonic Appearance)

8~12HP
Volume

2FAN

47% reduced
Weight

10% reduced
Previous Model
H1690 x W1350 x D720mm 245kg / 0.97m3
Transportation Becomes much easier

New Model
H1675 x W1080 x D480mm 221kg / 0.52m3 (FDC224KXE6)

High efficiency and compact design are realized applying the various advanced functions 4~6HP
Compact High Efficient Heat Exchanger New Inverter Control
Vector Inverter Control system

Compact high efficiency Heat Exchanger


Optimizing relationship of the air flow velocity & fin pattern Improvement of air distribution Maximizing efficiency of heat exchanger Heat Exchanger

New Twin Rotary Compressor

DC Fan Motor
Compact & High efficiency

KX4

KX6

Optimum New Refrigerant System Control

8~12HP
New DC Fan motor
Compact & High efficiency

New Inverter Control


Compact & Vector Inverter Control system

Downsized accumulator

Receiver in fan section 3D-Scroll Compressor (12HP)

14~48HP
DC Fan Motor Expansion of Heat Exchanger Tetrahedral structure of Heat Exchanger

Double tube

New Inverter Control

3D-Scroll Compressor (22,24HP)

R410A

3D Scroll Compressor
Unit start up speed in heating mode drastically improved for lower outdoor temperature operation.

Present scroll
Same height Fixed scroll

3D scroll
Lower at the inside Higher at the outside

2-Dimension compression

Orbital scroll

3-Dimension compression

High strength due to the lower teeth inside

Downsizing High Efficiency High Endurance

3D scroll compressor has the different height scroll at the outside and the inside. A high compression ratio is improved by compressing the refrigerant both radially and axially. 3-Dimension Compression has been realized with a much higher efficiency even if compression ratio is high.

The strength of the scroll is improved by reducing the height of the inner wrap, which receives a heavy load.

New Inverter Control (Vector control)


New Inverter Control has applied new advanced technology of Vector control and has realized high efficiency. Smooth operation from low speed to high speed Smooth Sine Voltage Wave form are attained Energy efficiency is further improved in low speed range

Compact Integrated PCB


Control Box size reduction PCB size reduced by 50 % Control PCB: Single-sided board Double-sided board Inverter PCB: Power transistor size reduction New Superlink system control New Design method applied Control PCB

Optimum Refrigerant System Control


We have improved refrigeration circuit from our long experience and have realized following Optimum Refrigerant System Control. Optimum heat exchanger refrigerant distribution Advanced refrigerant liquid return protection control system High speed system control by new Superlink system Use of larger diameter for suction piping and discharge piping and redesigned of double tube KX4 KX6

DC Fan Motor
Employment of DC fan motor has enabled to realize an excellent efficiency of approximate 60% higher than previous models.
Rotor(Squirrel Cage made of conductor) Stator (coil) Rotor(made of permanent magnet) Stator (coil)

Long-chorded 3 propeller fan with serration


Fan blade design adapted from MHI's aerospace division - with serrated edges that deliver increased air volume with less power input. Serration

3. Design Flexibility
Increased indoor unit connection capacity
KX6 series(4~34HP) can connect indoor unit capacity up to 150~200% from 130% of previous models. If the connection capacity of indoor units is more than 100%, capacity of each indoor unit may be affected by connection capacity ratio.

Capacity connection
HP 4~12 14,16 18~34 36~48 KX4 130% 130% 130% 130% HP 4~12 14,16 18~34 36~48 KX6 150% 200% 160% 130%

In case that capacity connection is more than 130%, additional charge of refrigerant is required on site.

KX6 14,16HP unit

KX4 130% capacity connection

KX6 200% capacity connection

More connectable indoor units


KX6 enable more connectable indoor units (per kW), compared with former model KX4.
80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0

Number of connectable indoor unit

KX6

KX4

4 5 6

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

48 HP

Control Systems
KX6 series offer wide variation of control system and provide the best solution. [KX6 Control system units with "New" SUPERLINK- ]
Classification Type Model Connectable Indoor units (Maximum) Electric power calculation

Individual controller

Wired Wireless Push buttons Touch screen

Center Console PC windows interface units BMS interface BACnet units Lonworks

RC-E3 RCN-T-36W-E etc. SC-SL1N-E SC-SL2N-E SC-SL3N-AE SC-SL3N-BE SC-WGWN-A SC-WGWN-B SC-BGWN-A SC-BGWN-B SC-LGWN-A

1 1 16 64 128 128 128(64x2) 128(64x2) 128(64x2) 128(64x2) 96(48x2)

R410A

Long Pipe Length


Piping length has extended max height difference between indoor units from 4m to 18m and enables us to put indoor unit on extra three floors. As a result of the adoption of thinner refrigerant piping and refrigerant volume reductions, the industry's longest 160 m actual piping length or 1000m total piping length is realized.

8~12HP
Total length: 510m
Outdoor unit To the first branch: max 130m
Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 4m 18m

14~48HP
Max: 10m

Total length: 510 1000m

Outdoor unit

Max: 0.4m

Indoor unit

To the first branch: max 130m From the first branch to the furthest * indoor unit: 40m 90m

Max: 5m

Indoor unit

Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m 18m

From the first branch to the furthest indoor unit: 40m 90m

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Furthest indoor unit: 160m

Furthest indoor unit: 160m


* The difference in length from the first branch must be within 40m.

(1)Divide up the refrigerant system into independent refrigeration circuit systems in case required additional refrigerant on site is 50kg or more for 14~24HP and 100kg or more for 26~48HP. (2)In case indoor unit connection capacity is 130% or more or total piping length is 510m or more, additional charge of refrigerant and oil on site is required. Refer to our Installation Manual for details.

Easy Transportation & Installation


Due to realization of significant reduction in size and foot print which is one of the smallest in the industry, transportation in an elevator made for six persons (Width:1400mm, Depth:850, Open area:800mm) is possible, eliminating cost of a crane and reducing labor.
1,400 Transportation in an elevator made for six persons

8~12HP
H1,675 x W1,080 x D480 850

Easy transportation

800

KX6(14~48HP) is portable and the uniform reduced footprint allows neat, continuous installation.

1350mm

1350mm

1350mm

10

Range of Operation
KX6 series permits a system design considering a heating range operation under a low temperature condition up to -20C from -15C of previous model and a cooling range operation under -15C from -5C of that.

-20C
-15C

Heating NEW
previous

+15.5C

-15C
-5C

Cooling NEW
previous

+43C

-20 -10 0 10 20 30 40 For the capacities under low temperature conditions, refer to technical manual.

50

New remote control for all indoor units


Applying nonpolar 2-core in new remote control line, it is very convenient for installation including renewal case.

Max length of electrical wiring


The wiring must be a 2-core shielded cable size 0.75mm2 to 1.25mm2. The max length of 2-core can be 1500m from 1000m of previous models.

previous

New previous

!-core

-core

m

#m

New

4. Serviceability
Easy Service
Quick and easy access to service parts by separation of compartments.

Check Operation (8~48HP)


Closing of Service valve, crossing connection of refrigerant piping and electrical wiring, proper operation of EEV (Electrical Expansion Valve) can be checked automatically in cooling operation. This check operation can be done at 0~43C outdoor temperature and 10~32C indoor temperature by use of outdoor unit dip switch. The check should be done in one refrigerant system. It takes 15~30 minutes and avoids frequent failure by preventing careless mistakes during installation. dip switch
Blower compartment

Mechanical compartment

11

R410A

Monitoring Function
KX6 series includes new feature to assist with servicing and trouble shooting. Various data can be monitored through 3-degit display on the outdoor unit PCB. Detailed fault diagnosis and operation history memory via 7-segment display. Equipped with RS232C for connection directly to your PC monitoring and service tasks made simple with our service software (Mente PC). all KX6 series

4~6HP

8~48HP

3 Layer Construction (14~48HP)


Thanks to improvement of control box structure from 4 to 3 layer construction and by use of hinged lays, service and maintenance has been made much easier for inverter components.

Back-up Operation
In, 2-compressor module, in the event of the compressor failure, the system will keep operating with good compressor. In combined module, in the event that one unit has a failure, the system will keep operating with another unit.

Keeping operation

Compressor failed
Inverter

Reduced Refrigerant Volume


To use the new refrigerant R410A, KX6 series have adopted thinner diameter refrigerant pipes, which will help reduce piping work cost.

Blue Fin
Due to application of blue coated fins (KS101) for the heat exchanger of new outdoor unit, corrosion resistance has been improved compared to current models.

Outdoor unit
KX6 HP Liquid piping Gas piping 4 15.88 5 6 9.52 19.05 8 22.22 10 12 25.4[28.58] 14 16 12.7 18 28.58 20 22 24 26 28 31.8[34.92] 30 15.88 32 34 36 38 40 38.1[34.92] 42 19.05 44 46 48 [ ]: Pipe sizes applicable to European installations are shown in parentheses.
1" 11/8" 11/4" 13/8" 11/2" 13/4" 2"

Blue Fin

KX6 R410A
9.52 22.22

Liquid piping

Refrigerant charge amount check function


(1)It is supplementary function. Weight of refrigerant charge amount should be measured in any case. (2)In case check result is not satisfied, it is necessary to take countermeasure. (3)Even in case check result is ok, it might vary with different temperature conditions. So that only one time check can not cover every temperature condition. For the safety sake it is recommended to check refrigerant charge amount continuously every year. (4)Refer to operation manual for details.

Gas piping

ex.10HP

mm 9.52 12.7 15.88 19.05 22.22 25.4 28.58 31.8 34.92 38.1 44.5 50.8 inch 3/8" 1/2" 5/8" 3/4" 7/8"

12

KX6 heat pump systems


KX6 heat pump systems operate with 2 inter-connecting pipes, thus commonly referred to as a '2-pipe system'. These systems provide either a heating or cooling operation to all indoor units and are suitable for a wide range of applications from an individual apartment (with "Micro KX", 1/phase system) to an entire multi storey building, especially where there are significant open plan areas to be controlled. The range starts with a 11.2kW cooling capacity, up to the largest capacity single outdoor unit in the industry (24hp) with 68.0kW cooling capacity. Outdoor units can also be twinned providing up to 48HP/136.0kW on a single system. The KX6 range has a total piping length of 1000m (14HP+) and the furthest indoor unit can be connected up to 160m (8HP+) from the outdoor unit.

Fixed Cooling mode/fixed heating mode (summer/winter switch): It is possible to fix the operational mode of the system (either cooling or heating) using a switch (SW3-7) on the outdoor unit PC board - this enables the building user to decide the operation of the system (e.g. cooling only in summer/heating only in winter), to avoid unnecessary energy wastage. It is also possible to wire the control switch to a remote location (inside the building) to a control room, or even linked to an ambient thermostat.

13

4")

Outdoor units Heat pump systems 4, 5, 6hp (11.2kW~15.5kW)


Model No. FDC112KXEN6 FDC140KXEN6 FDC155KXEN6 FDC112KXES6 FDC140KXES6 FDC155KXES6 Nominal Cooling Capacity 11.2kW (1phase) 14.0kW (1phase) 15.5kW (1phase) 11.2kW (3phase) 14.0kW (3phase) 15.5kW (3phase)

Blue Fin

The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas. Connect up to 8 indoor units/up to 150% capacity. High efficiency with COP (in cooling) up to 4.0. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 100m and a maximum pipe run of 70m.

Total length: 100m


Outdoor unit Height difference
30m(outdoor unit above) 15m(outdoor unit below)

Range of operation
50

+43C
40

30

Indoor unit
20

Cooling
Max height
+15.5C

Indoor unit

difference between indoor units: 15m

10

Heating
-10

Furthest indoor unit: 70m

-15C
-20

-20C

* The total length of 9.52mm(3/8") liquid piping must be 50m or less

Specifications
Item Nominal horse power Power source Nominal capacity Model

FDC112KXEN6
4HP 11.2 12.5 2.80 2.89 13.5-12.4 14.1-12.9

FDC140KXEN6
5HP 1 Phase 220-240V, 50Hz 14.0 16.0 4.17 4.31 20.6-18.9 21.5-19.7

FDC155KXEN6
6HP 15.5 16.3 5 4.71 4.38 23.3-21.3 21.9-20.1

FDC112KXES6
4HP 11.2 12.5 2.80 2.89 4.5-4.1 4.7-4.3

FDC140KXES6
5HP 3 Phase 380-415V, 50Hz 14.0 16.0 4.17 4.31 6.9-6.3 7.2-6.6

FDC155KXES6
6HP 15.5 16.3 4.71 4.38 7.8-7.1 7.3-6.7

Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating Exterior dimensions mm HxWxD Net weight kg Refrigerant charge kg R410A dB(A) Cooling/Heating Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units

845x970x370 82 5.0 52/54 53/55 53/56 9.52(3/8") 15.88(5/8") 50~150 6 8 8 6 8 8 52/54 53/55 53/56

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

14

Dimensions
All measurements in mm.

L2
Intake

L3

Intake

L4 L1
40 100 36 51

outlet Service space

B
Terminal block

Minimum installation space

B A
845

A
F

110

242

279

195

10

195

55

50

50 52 27 50

C
970

50

15

110

E
190 60 20 40 60 580 200 60 15 15 55 103

410

370

38

150

C
20 40 262 388

50

70

40

VIEW A

15

50

Mark A B C D E F

Item Service valve connection (gas side) Service valve connection (liquid line) Pipe/cable draw-out port Drain discharge port Anchor bolt hole Cable draw-out port 15.88 (5/8") (flare) 9.52 (3/8") (flare) 4 places 20 x 3 places M10 x 4 places 30 x 3 places L1 L2 L3 L4

I
Open 300 150 5

II
Open 5 300 5

II
500 Open 150 5

1m overhead clearance required

Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The unit name plate is attached on the lower right corner of the front panel.

15

4")

Outdoor units Heat pump systems 8, 10, 12hp (22.4kW~33.5kW)


Model No. FDC224KXE6 FDC280KXE6 FDC335KXE6 Nominal Cooling Capacity 22.4kW 28.0kW 33.5kW

Blue Fin

The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.

Connect up to 22 indoor units/up to 150% capacity. High efficiency with COP (in cooling) up to 4.0. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 510m and a maximum pipe
run of 160m.

Total length: 510m


To the first branch: max 130m

Range of operation Outdoor unit


50

+43C

Indoor unit

Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 18m
-10

40

30

Cooling
20

+15.5C

From the first branch to the furthest indoor unit: 90m Furthest indoor unit: 160m

Indoor unit

10

Indoor unit

Heating
-20C

-20

-20C

Specifications
Item Nominal horse power Power source Nominal capacity Model

FDC224KXE6
8HP 22.4 25.0 5.60 6.03 9.25-8.47 9.85-9.02 221 58/58 9.52(3/8") 19.05(3/4") 15

FDC280KXE6
10HP 3 Phase 380V-415V, 50Hz 28.0 31.5 5 8.09 8.21 13.22-12.10 13.41-12.28 1675x1080x480 11.5 59/60 22.22(7/8") 50~150 19

FDC335KXE6
12HP 33.5 37.5 9.82 10.12 15.87-14.53 16.36-14.98 224 61/61 12.7(1/2") 25.4(1") [28.58(1 1/8")] 22

Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Operating Cooling A current Heating HxWxD Exterior dimensions mm Net weight kg R410A Refrigerant charge kg Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

16

Dimensions
All measurements in mm.

L2
Intake

L3

Intake

L4
L1
Outlet

Minimum installation space

69 51

Service space

43 60 120

Terminal block

1675

69

B A G

A
553 640(8.10HP) 634(12HP)

20

159 194

174 84

84

F
1080

51

54 14

159 84

35

35

67 42

50

14

54 51

55

55

E
19 39

195

690 50

195

E
30 30

989

701 461 421 141 241 321 361

520 480

105

Mark A B C D E F G

Item Service valve connection of the attached connecting pipe (gas side) Service valve connection (liquid side) Pipe/cable draw-out hole Drain discharge hole Anchor bolt hole Cable draw-out hole Connecting position of the local pipe. (gas side)

19 39

FDC224KXE6

FDC280KXE6

55

FDC335KXE6

19.05 (3/4") (Flare) 9.52 (3/8") (Flare) 20 x 4places M10 x 4places 30 x 2places (front) 45 (side) 30 x 2places (back) 19.05 (3/4")(Brazing)

19.05 (3/4") (Flare) 9.52 (3/8") (Flare) 20 x 4places M10 x 4places 30 x 2places (front) 45 (side) 30 x 2places (back) 22.22 (7/8")(Brazing)

19.05 (3/4") (Flare) 12.7 (1/2") (Flare) 20 x 4places M10 x 4places 30 x 2places (front) 45 (side) 30 x 2places (back) 25.4 (1")(Brazing)

Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The model name label is attached on the lower right corner of the front. (7) Connect the Service valve with local pipe by using the pipe of the attachment.(Gas side only) (8) Mark shows the connecting position of the local pipe.(Gas side only)

II
Open 5 300 5

II
1500 Open 300 5

L1 L2 L3 L4

Open 300 300 5

17

4")

Outdoor units Heat pump systems 14, 16hp (40.0kW~45.0kW)


Model No. FDC400KXE6 FDC450KXE6 Nominal Cooling Capacity 40.0kW 45.0kW

Blue Fin

The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.

Connect up to 40 indoor units/up to 200% capacity. High efficiency with COP (in cooling) up to 3.6. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.

Uniform footprint of models (14,16hp) allows continuous side-by-side installation

Total length: 1000m


To the first branch: max 130m

Outdoor unit Range of operation Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m
50

+43C
40

Indoor unit

30

From the first branch to the furthest indoor unit: 40m Furthest indoor unit: 160m

Indoor unit

Cooling
20

+15.5C

10

Indoor unit

Heating
-10

-20

-20C

-20C

Specifications
Item Nominal horse power Power source Nominal capacity Model

FDC400KXE6
14HP 3 Phase 380-415V, 50Hz 40.0 45.0 8 11.27 11.73 18.4-16.9 19.6-17.9 1690x1350x720 317 11.5 59.5/60 12.7(1/2") 25.4(1") [28.58(1 1/8")] 50~200 36

FDC450KXE6
16HP 45.0 50.0 12.97 13.10 21.1-19.3 21.719.9

Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Operating Cooling A current Heating HxWxD Exterior dimensions mm Net weight kg R410A Refrigerant charge kg Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units

62.5/62.5 28.58(1 1/8") 40

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

18

Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185

Rear

C 594 232
Anchor bolt positions for I

Anchor bolt positions for F, J

296.7 140 240 295 22 174 720

K B

58.5

19

Dimensions of refrigerant pipe connection (plan)

F I

I F

726

647

85

57

95 140.5

141

75 142.5 234

58.5

19

Air intake

G
148 410 352 158 530 342 235

1690 797.8

126.2

720

1350

Drain pipe 175

7-segment display inspection port 682 Signal wire terminal block Terminal block for power cable connection

K B A C (front)
166 169 211 259 291.6

120

22

80.5 71

C (right)

C (rear)

L
44.7

84

D (left)

104.9

95

90

D (right)

86.5 220 180 550 180 214

D (front)

Mark A B C D F G H K* L

Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.

Intake

Installation example
Dimensions

L2

L3

Wall height H3 L4

1 500 10 100 10 1500

2 Open 200 300 Open

Intake
Wall height H2

Intake
Wall height H4 Wall height H1

88 50 M10 x 4 places 45 x 3 places 20 x 6 places 3/8 flare 180 x 44.7

L1 L2 L3 L4 H1 H2 H3 H4

Service space

Intake

Installation space 2m overhead clearance required

No restrictions No restrictions 1000 No restrictions No restrictions

*14 + 16HP models only

Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination. (For 14,16Hp only)

When more than one unit is installed


Wall height H3

Installation example
Dimensions

A 500 10 100 10 0 0 1500

L1

20

Instruction plate

6 86.1

172

172

80

B Open 200 300 Open 400 400 No restrictions

L3
Wall height H2 Wall height H4

L1
L6 L4

L2

L5

L2 L3 L4 L5 L6 H1 H2 H3 H4

L1 (Unit front side)


Wall height H2

No restrictions No restrictions 1000 No restrictions

No restrictions No restrictions

19

4")

Heat pump systems 18, 20, 22, 24hp (50.4kW~68.0kW)


Model No. FDC504KXE6 FDC560KXE6 FDC615KXE6 FDC680KXE6 Nominal Cooling Capacity 50.4kW 56.0kW 61.5kW 68.0kW

Blue Fin

The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.

Connect up to 49 indoor units/up to 160% capacity. High efficiency with COP (in cooling) up to 3.4. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.

Uniform footprint of all models (from 8hp~24hp) allows continuous sideby-side installation

Total length: 1000m


To the first branch: max 130m

Range of operation Outdoor unit


50

+43C

Indoor unit

Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m
-10

40

30

Cooling
20

+15.5C

From the first branch to the furthest indoor unit: 40m Furthest indoor unit: 160m

Indoor unit

10

Indoor unit

-5C

Heating

-20

-20C

Specifications
Item Nominal horse power Power source Nominal capacity Model

FDC504KXE6
18HP 50.4 56.5 14.73 15.12 24.1-22.0 25.2-23.1 341

FDC560KXE6
20HP

FDC615KXE6
22HP

FDC680KXE6
24HP 68.0 73.0 24.98 19.08 40.3-36.9 31.6-29.0 355

3 Phase 380-415V, 50Hz 56.0 63.0 8 16.79 16.79 27.4-25.1 28.0-25.7 2048x1350x720 11.5 61.5/62.0 63.0/63.5 12.7(1/2") 28.58(1 1/8") 50~200 36 40 50~160 44 49 64.5/64.0 65.0/65.0 20.37 18.48 33.1-30.3 30.7-28.1 61.5 69.0

Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Operating Cooling A current Heating HxWxD Exterior dimensions mm Net weight kg R410A Refrigerant charge kg Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

20

Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185 Rear Dimensions of refrigerant pipe connection (plan)

C 594 232
Anchor bolt positions for I

Anchor bolt positions for F, J

296.7 140 240 295 22 174 720

K B

58.5

F I

I F

19

726

647

85

57

95 140.5

141

75 142.5 234

58.5

19

Air intake

G
148 410 352 158 530 342 235

2048

1155.8

126.2

720

1350

Drain pipe

7-segment display inspection port 682 Signal wire terminal block 175 Terminal block for power cable connection

K B A C (front)
166 169 211 259 291.6

120

22

80.5 71

C (right)

C (rear)

L
44.7

84

D (left)

80

104.9

95

90

D (right)

86.5 220 180 550 180 214

D (front)

Mark A B C D F G H K L

Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.

Intake

Installation example
Dimensions

L2

L3

Wall height H3 L4

1 500 10 100 10 1500

2 Open 200 300 Open

Intake
Wall height H2

Intake
Wall height H4 Wall height H1

100 50 M10 x 4 places 45.3 x 3 places 20.5 x 3 places 9.52 flare 180 x 44.7

L1 L2 L3 L4 H1 H2 H3 H4

Service space

Intake

Installation space 2m overhead clearance required

No restrictions No restrictions 1000 No restrictions No restrictions

Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.

L1

20

Instruction plate

6 86.1

172

172

21

4")

Heat pump combination systems 26, 28, 30, 32hp (73.5kW~90.0kW)


Model No. FDC735KXE6 (FDC335+FDC400) FDC800KXE6 (FDC400x2) FDC850KXE6 (FDC400+FDC450) FDC900KXE6 (FDC450x2) Nominal Cooling Capacity 73.5kW 80.0kW 85.0kW 90.0kW

Blue Fin

The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.

Connect up to 65 indoor units/up to 160% capacity. High efficiency with COP (in cooling) up to 3.6. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.

Uniform footprint of all models (from 8hp~24hp) allows continuous side-byside installation

Total length: 1000m


To the first branch: max 130m

Range of operation Outdoor unit


50

+43C

Indoor unit

Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m
-10

40

30

Cooling
20

+15.5C

From the first branch to the furthest indoor unit: 40m Furthest indoor unit: 160m

Indoor unit

10

Indoor unit

-5C

Heating

-20

-20C

Specifications
Item Combination (FDC) Nominal horse power Power source Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Operating A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units Nominal capacity Model

FDC735KXE6
335KXE6-K 400KXE6 26HP 73.5 82.5 20.21 20.66 32.9-30.2 34.4-31.4

FDC800KXE6

FDC850KXE6

FDC900KXE6
450KXE6 450KXE6 32HP 90.0 100.0 25.94 26.20 42.2-38.6 43.4-39.8

53

400KXE6 400KXE6 400KXE6 450KXE6 28HP 30HP 3 Phase 380-415V, 50Hz 80.0 85.0 90.0 95.0 16 22.54 24.24 23.46 24.83 36.8-33.8 39.5-36.2 39.2-35.8 41.3-37.8 1690x2700x720 317x2 11.5x2 15.88(5/8") 31.8(1 1/4") [34.92(1 3/8")] 50~160 58 61

65

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

22

Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185

Rear

C 594 232
Anchor bolt positions for I

Anchor bolt positions for F, J

296.7 140 240 295 22 174 720

K B

58.5

19

Dimensions of refrigerant pipe connection (plan)

F I

I F

726

647

85

57

95 140.5

141

75 142.5 234

58.5

19

Air intake

G
148 410 352 158 530 342 235

1690 797.8

126.2

720

1350

Drain pipe 175

7-segment display inspection port 682 Signal wire terminal block Terminal block for power cable connection

K B A C (front)
166 169 211 259 291.6

120

22

80.5 71

C (right)

C (rear)

L
44.7

84

D (left)

104.9

95

90

D (right)

86.5 220 180 550 180 214

D (front)

Mark A B C D F G H K L

Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.

88 50 M10 x 4 places 45 x 3 places 20 x 6 places 3/8" flare 180 x 44.7

Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.

20

Instruction plate

6 86.1

172

172

80

23

4")

Heat pump combination systems 34, 36, 38, 40, 42, 44, 46, 48hp (96.0kW~136.0kW)
Model No. FDC960KXE6 (FDC450+FDC504) FDC1010KXE6 (FDC504x2) FDC1065KXE6 (FDC504+FDC560) FDC1130KXE6 (FDC560x2) FDC1180KXE6 (FDC560+FDC615) FDC1235KXE6 (FDC615x2) FDC1300KXE6 (FDC615+FDC680) FDC1360KXE6 (FDC680x2) Nominal Cooling Capacity 96.0kW 101.0kW 106.5kW 113.0kW 118.0kW 123.5kW 130.0kW 136.0kW

Blue Fin

The KX6 heat pump 2-pipe systems offer high performance VRF for applications that
require either cooling only or heating only, ideal for open plan areas. Connect up to 80 indoor units/up to 130% (960KXE6:160%) capacity.

High efficiency with COP (in cooling) up to 3.5. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum pipe run of 160m.
Total length: 1000m
To the first branch: max 130m Range of operation Outdoor unit
50

+43C

Indoor unit

Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m
-10

40

30

Cooling
20

+15.5C

From the first branch to the furthest indoor unit: 40m Furthest indoor unit: 160m

Indoor unit

10

Indoor unit

-5C

Heating

-20

-20C

Specifications
Item Combination (FDC) Nominal horse power Power source Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Operating Cooling A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units Nominal capacity Model

FDC960KXE6 FDC1010KXE6 FDC1065KXE6 FDC1130KXE6 FDC1180KXE6 FDC1235KXE6 FDC1300KXE6 FDC1360KXE6


450KXE6 504KXE6 34HP 96.0 108.0 27.70 28.22 45.2-41.3 46.9-43 341+317 15.88(5/8") 34.92(1 3/8") 50~130 66 69 504KXE6 504KXE6 36HP 101.0 113.0 29.46 30.24 48.2-44.0 50.4-46.2 504KXE6 560KXE6 38HP 106.5 119.5 31.52 31.91 51.5-47.1 53.2-48.8 341x2 560KXE6 560KXE6 560KXE6 615KXE6 40HP 42HP 3 Phase 380-415V, 50Hz 113.0 118.0 127.0 132.0 16 33.58 37.16 33.58 35.27 54.8-50.2 60.5-55.4 56-51.4 58.7-53.8 2048x2700x720 360+340 11.5x2 615KXE6 615KXE6 44HP 123.5 138.0 40.74 36.96 66.2-60.6 61.4-56.2 615KXE6 680KXE6 46HP 130.0 142.0 45.35 37.56 73.4-67.2 62.3-57.1 355x2 680KXE6 680KXE6 48HP 136.0 146.0 49.96 38.16 80.6-73.8 63.2-58.0

19.05(3/4")

69

59

62

72

76

80

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

24

Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185 Rear Dimensions of refrigerant pipe connection (plan)

C 594 232
Anchor bolt positions for I

Anchor bolt positions for F, J

296.7 140 240 295 22 174 720

K B

58.5

F I

I F

19

726

647

85

57

95 140.5

141

75 142.5 234

58.5

19

Air intake

G
148 410 352 158 530 342 235

2048

1155.8

126.2

720

1350

Drain pipe

7-segment display inspection port 682 Signal wire terminal block 175 Terminal block for power cable connection

K B A C (front)
166 169 211 259 291.6

120

22

80.5 71

C (right)

C (rear)

L
44.7

84

D (left)

80

104.9

95

90

D (right)

86.5 220 180 550 180 214

D (front)

Mark A B C D F G H K L

Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.

100 50 M10 x 4 places 45.3 x 3 places 20.5 x 3 places 9.52 flare 180 x 44.7

Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.

20

Instruction plate

6 86.1

172

172

25

4")

KX6 refrigerant piping


Installation of Interconnecting Pipework Mitsubishi KX6 equipment is manufactured to the highest standards of quality and reliability. It is imperative the method of installation and the materials used are also to high standards, to ensure trouble free operation and long term reliability. The interconnecting pipework must be installed by a competent and trained engineer. Refrigeration quality copper tube must be used, soft copper coils or half-hard straight lengths. The refrigeration quality tube must be soft drawn seamless high grade copper pipe. The copper tube must be selected taking into account the higher operating pressures of R410A refrigerant, and that high pressures will occur throughout the system because of the reverse cycle operation. All pipework material used should be EN12735 European standard. The supplied branch pipe kits, must be used to make connections to indoor units, and the supplied manifold kits must be used to make connections between outdoor units (where applicable); it is not permitted to use standard fittings such as elbows, tees etc. The branch pipes shall be installed in accordance with the manufacturers instructions, allowing unrestricted flow of refrigerant, and in accordance with European standard E378:2000. All brazed joints shall be made with dry nitrogen purge to ensure the prevention of oxidisation to the internal surface of the copper pipes. The ingress of moisture, dirt and any other contaminants to the interior of the copper pipes, and air conditioning units, must be prevented during the installation procedure. After the installation of pipework, prior to the connection of the outdoor units, and sealing of insulation joints, the pipework must be pressure tested for leakage, using dry nitrogen. The pipe ends must be crimped and brazed, and a suitable service valve connection will need to be fitted (supplied by installer). Pipe Insulation The refrigeration pipework must be insulated with close cell Class O fire performance with a minimum wall thickness of 13mm. Additional Refrigerant Additional R410A refrigerant only shall be used, and must be charged by weight only, using electronic scales. The amount of additional refrigerant must be accurately calculated from the manufacturers data, based on the length and diameter of each section of the liquid refrigerant pipework of the system.

Single outdoor unit piping examples:

Piping arrangement using header

HEAD8-371-1

FDC335KXE6 Liquid pipe

90

90

56

56

36

36

36

36

Gas pipe

Piping arrangement using branch pipe kits

56

56

36

36

36

112

112

112

26

KX6 refrigerant piping


Outdoor unit (HP) Liquid pipe Gas pipe Liquid pipe Gas pipe Branch pipes Furthest indoor unit =<90m Furthest indoor unit =>90m 8 10 12 14 16 18 12.7 28.58 12.7 22.22 28.58 Header pipe 20 9.52 19.05 22.22

Pipe sizes applicable to European installations.


22 24 26 28 30 32 34 36 38 40 42 44 46 48
mm 9.52 12.7 15.88 19.05 22.22 25.4
Horizontally

inch 3/8" 1/2" 5/8" 3/4" 7/8" 1"

mm 31.8 38.1 44.5 50.8

inch 11/4" 11/2" 13/4" 2"

15.88 34.92 15.88 19.05 34.92

19.05 22.22

28.58 11/8" 34.92 13/8"

Good
Floor

DIS-22-1/DIS-180-1

HEAD6-180-1R
No Good
Vertically

Combination outdoor unit manifold


Floor

No

Floor

DIS-540-2/DIS-371-1

DOS-2A-1

Floor

Combination outdoor unit piping examples:

Piping arrangement using branch pipe kits


Oil equalisation pipe Outdoor unit branch pipe set (DOS-2A-1)

112

112

90

90

90

140

140

140

Piping arrangement using header


Oil equalisation pipe Outdoor unit branch pipe set (DOS-2A-1)

Outdoor unit's branching piping Outdoor unit 2 units (for 735~1360) Branch piping set DOS-2A-1

HEAD8-540-2

Indoor unit's first branching piping Total capacity of indoor units ~179 180~370 371~539 540~ Branch piping set DIS-22-1 DIS-180-1 DIS-371-1 DIS-540-2 Header set Model HEAD4-22-1 HEAD6-180-1 HEAD8-371-1 HEAD8-540-2 Branches Max 4 branches Max 6 branches Max 8 branches Max 8 branches

112

112

90

90

90

140

140

140

27

4")

KX6 electrical wiring power supply


KX6 new design includes greatly simplified wiring requirements utilising a polarity-free two wire control loop connecting the indoor units. Power wiring Cables can be laid through the front, right, left or bottom of the outdoor unit casing. Separate power supplies should be used for the outdoor unit (3/phase) and the indoor units (1/phase). Only control wiring is connected from outdoor to indoor unit.

Outdoor unit power supply: 3 phase 4 wiring 380-415V

Distributed, separate power supply system

Earth leakage breaker (Impulse withstanding type) Circuit breaker for cabling Grounding wire

Outdoor unit

A Power cable (Main Power cable)[4 cores] B Signal wire (Super Link wire)[2 cores] C Power cable (Indoor unit power cable)
[2 cores]

D Remote control cord A B B


[2 cores]

C
Circuit breaker for cabling Earth leakage breaker

Indoor unit

D R R R R R R
Remote control unit

Indoor unit power supply: Single phase 220-240V

CAUTION
If the earth leakage breaker is exclusively for ground fault protection, then you will need to install a circuit breaker for wiring work.

KX6 outdoor unit mechanical compartment

Electrical component box Outdoor unit power supply terminal block

28

KX6 electrical wiring control wiring


1. The control wiring is 5 Volt DC, non-polarised, two wire connection notated as A1 and B1. This AB wiring connects outdoor unit to indoor unit and indoor unit to indoor unit. 2. This wiring must be a 2-core shielded cable size 0.75mm2 or 1.25mm2.
~1000m 1000~1500m 0.75mm2 YES YES 1.25mm2 YES NO
(1) When one outdoor unit is used Outdoor signal line terminal block

A1

B1

Indoor and outdoor signal line do not have a polarity. Any of the connections in the following illustration can be made.

A1
Indoor signal line terminal block

A B

A1 B1

A B

B1

(2) When plural outdoor units are used

3. We recommend only one end of the shield of the cable is connected to ground (earth) at one of the outdoor units. At all other terminal connections on the same network, connect all the shields together and electrically insulate them. This will prevent accidental grounding at 2 points and eliminate any electrical noise.

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

Network connector

A1B1 A2B2
Indoor unit

A1B1 A2B2

A1B1 A2B2
Indoor unit

A1B1 A2B2

A B

A B

4. When plural outdoor units are used, .Connect the signal cable between indoor Refrigerant pipe Indoor unit Indoor unit and outdoor units and the signal cable A A between outdoor units belonging to the B B same refrigerant line to A1 and B1. .Connect the signal line between outdoor Signal line units on different refrigerant lines to A2 and B2. (a) The maximum number of indoor units that can be connected in a system is 128 and it is possible to configure outdoor units and/or indoor units as an outdoor or indoor unit group connected with each other with two wires. 5. For current specification of 2-core (AB) wiring, please consult your MHI dealer. (b) The signal wires can also be connected using the method shown below.
(3) The signal lines can also be connected using the method shown below.

Important
Outdoor unit Outdoor unit Outdoor unit Outdoor unit

Loop wiring prohibited

Outdoor unit

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

The signal lines cannot form a loop, so the wirings shown as in the diagram are prohibited.
Indoor unit Indoor unit Indoor unit Indoor unit

Indoor unit

Indoor unit

Indoor unit

Remote control wiring specifications


1. For interconnecting wiring between the remote control and indoor units (XY wiring) use 2-core shielded cable size 0.3mm2. The maximum length of 2-core cable is 600 metres. Where the 2-core wiring exceeds 100m, use the wire size detailed on the table opposite. 2. Be sure to ground (earth) only one end of the shield of the cable. When connecting more than one indoor unit to a remote control, we recommend the shield of the cable is connected to ground (earth) at the first indoor unit only. At all subsequent terminal connections on the same loop, connect all the shields together and electrically insulate them. This will prevent accidental grounding at 2 points and eliminate any electrical noise. 3. For current specification of 2-core (XY) wiring, please consult your dealer.
Remote control Wires can be connected across different refrigerant systems when wired within 1 Superlink system

Length (m) 100 to 200 To 300 To 400 To 600

Wire size 0.5mm2 x 2 core 0.75mm2 x 2 core 1.25mm2 x 2 core 2.0mm2 x 2 core

Outdoor unit No.49

A
Indoor unit

A
Indoor unit

A
Indoor unit

A
Indoor unit

29

4")

Indoor units Ceiling Cassette -4wayFDT


Model No. FDT28KXE6A FDT36KXE6A FDT45KXE6A FDT56KXE6A FDT71KXE6A FDT90KXE6A FDT112KXE6A FDT140KXE6A FDT160KXE6A
Wireless remote control RCN-T-36W-E (option)
The thinnest design

Individual flap control system

According to room temperature conditions, four directions of air flow can be controlled by individual flap as preferred. As individual flap control is available even after installation, installation area became wider than before.

Thanks to new design of heat exchanger changed from 2 parts to 1 part, the height of indoor unit is reduced drastically. Furthermore applying DC fan motors to FDT models, the highest energy efficiency level, reduction of weight and significant compact design are realized.
270mm

Shape of Heat exchanger

Previous

New

365mm

Due to optimization of outlet design of air flow with our new advanced technology, sufficient air flow is secured and long reach of air flow is realized.
Previous New

246
mm
FDT28~71

298
mm
FDT112~160

reduction!!

9%

reduction!!

18%

for person who is far from the indoor unit

for both persons who are feeling hot or cold

can cool both the kitchen and the guests

Specifications
Item Model FDT28KXE6A Nominal cooling capacity kW 2.8 Nominal heating capacity kW 3.2 Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Panel Air filter, Qty Remote control Liquid line:6.35(1/4") Installation data Refrigerant piping size mm(in) Gas line:9.52(3/8") Accessories

FDT36KXE6A
3.6 4.0 0.03-0.03 0.03-0.03

FDT45KXE6A
4.5 5.0

FDT56KXE6A
5.6 6.3

FDT71KXE6A

FDT90KXE6A FDT112KXE6A FDT140KXE6A FDT160KXE6A


9.0 10.0 11.2 12.5 14.0 16.0 16.0 18.0

7.1 8.0 1 Phase 220-240V, 50Hz 0.04-0.04 0.10-0.10 0.04-0.04 0.10-0.10

Hi:33 Me:31 Lo:30 Unit:246x840x840 Panel:35x950x950 Unit:22 Panel:5.5 Hi:18 Me:16 Lo:14 Unit:24 Panel:5.5

Hi:40 Me:37 Lo:35

0.14-0.14 0.14-0.14 Hi:42 Me:40 Lo:37 Hi:43 Me:41 Lo:38

Unit:298x840x840 Panel:35x950x950 Unit:27 Panel:5.5 Hi:27 Me:24 Lo:20 Hi:30 Me:27 Lo:23

Possible T-PSA-36W-E Pocket Plastic net x1 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-T-36W-E Liquid line:6.35(1/4") Gas line:12.7(1/2") Mounting kit, Drain hose Liquid line:9.52(3/8") Gas line:15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

30

Dimensions
All measurements in mm.

FDT28KXE6A, 36KXE6A, 45KXE6A, 56KXE6A, 71KXE6A

FDT90KXE6A, 112KXE6A, 140KXE6A, 160KXE6A

31

4")

Ceiling Cassette -4way Compact (600x600mm)FDTC


Model No. FDTC22KXE6A FDTC28KXE6A FDTC36KXE6A FDTC45KXE6A FDTC56KXE6A

Wireless remote control RCN-TC-24W-ER (option)

CLEARERAIR FLOW
295~325

New shape & angled louvre re-directs the air current away from the ceiling, to reduce ceiling stains
INSTALLATION WORKABILITY

Condensate drain pump included as standard

For wireless control simply insert the infra-red receiver kit on a corner of the panel

600 or less (Max. Drain up) 248 Opening for exit wiring

Ultra slim design at just 248mm above the ceiling

Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Panel Air filter, Qty Remote control Installation data Refrigerant piping size mm(in) Unit:14 Panel:3.5 Hi:9.5 Me:8.5 Lo:8

FDTC22KXE6A
2.2 2.5

FDTC28KXE6A
2.8 3.2 0.03-0.03 0.03-0.03

FDTC36KXE6A
3.6 4.0 1 Phase 220-240V, 50Hz

FDTC45KXE6A
4.5 5.0 0.04-0.04 0.04-0.04

FDTC56KXE6A
5.6 6.3

Hi:35 Me:33 Lo:32

Hi:38 Me:36 Lo:34 Unit:248x570x570 Panel:35x700x700

Hi:40 Me:38 Lo:36

Hi:45 Me:42 Lo:39

Unit:15 Panel:3.5 Hi:10 Me:9 Lo:8 Hi:11 Me:10 Lo:9 Not possible TC-PSA-24W-ER Pocket Plastic net x1 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-TC-24W-ER Liquid line:6.35(1/4") Gas line:12.7(1/2")

Hi:13 Me:11.5 Lo:10

Liquid line:6.35(1/4") Gas line:9.52(3/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

32

Dimensions
All measurements in mm.

33

4")

Ceiling Cassette -2wayFDTW


Model No. FDTW28KXE6 FDTW45KXE6 FDTW56KXE6 FDTW71KXE6 FDTW90KXE6 FDTW112KXE6 FDTW140KXE6

Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Panel Air filter, Qty Remote control

FDTW28KXE6
2.8 3.2

FDTW45KXE6
4.5 5.0 0.09-0.10 0.09-0.10 Hi:39 Me:34 Lo:32

FDTW56KXE6
5.6 6.3

FDTW71KXE6

FDTW90KXE6

FDTW112KXE6
11.2 12.5 0.18-0.20 0.18-0.20 Hi:44 Me:38 Lo:37

FDTW140KXE6
14.0 16.0 0.20-0.24 0.20-0.24 Hi:45 Me:41 Lo:39

7.1 9.0 8.0 10.0 1 Phase 220-240V, 50Hz 0.10-0.11 0.12-0.13 0.10-0.11 0.12-0.13 Hi:41 Me:36 Lo:35 Hi:41 Me:37 Lo:36 Unit:342x1054x620 Panel:8x1300x680

Unit:287x817x620 Panel:8x1055x680 Unit:18 Panel:7 Unit:19 Panel:7 Hi:14 Me:12 Lo:10

Unit:357x1524x620 Panel:8x1770x680 Unit:38 Panel:11 Hi:28 Me:25 Lo:23 Hi:32 Me:28 Lo:24 TW-PSA-44W-E Pocket Plastic net x2 (Washable)

Unit:26 Panel:9 Hi:16 Me:13 Lo:11 Hi:19 Me:16 Lo:12 Possible TW-PSA-24W-E TW-PSA-34W-E Pocket Plastic net x1 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2")

Liquid line:6.35(1/4") Installation data Refrigerant piping size mm(in) Gas line:9.52(3/8")

Liquid line:9.52(3/8") Gas line:15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

Dimensions
All measurements in mm.

FDTW28KXE6, 45KXE6, 56KXE6

FDTW71KXE6, 90KXE6

FDTW112KXE6, 140KXE6

Dimension Table
model FDTW28,45,56KXE6 FDTW71,90KXE6 FDTW112,140KXE6 a 127 127 137 b 47 50 50 c 98 95 110 d 91 88 103 e 1055 f 965 g 214 226 241 h 405 410 410 i 234 284 299

Unit:mm

j 155 155 170

1300 1210 1770 1680

34

Ceiling Cassette -1wayFDTS


Model No. FDTS45KXE6 FDTS71KXE6

Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Panel Air filter, Qty Remote control Installation data Refrigerant piping size mm(in)

FDTS45KXE6
4.5 5.0 1 Phase 220-240V, 50Hz 0.09-0.11 0.09-0.11 Hi:43 Me:38 Lo:36 Unit:194x1040x650 Panel:10x1290x770 Unit:27 Panel:6 Hi:14 Me:12 Lo:10 Possible TS-PSA-29W-E Pocket plastic net x2 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2")

FDTS71KXE6
7.1 8.0 0.12-0.15 0.12-0.15 Hi:44 Me:38 Lo:36 Unit:194x1300x650 Panel:10x1500x770 Unit:31 Panel:7 Hi:18 Me:15 Lo:12 TS-PSA-39W-E Pocket plastic net x3 (Washable) Liquid line:9.52(3/8") Gas line:15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

Dimensions
All measurements in mm.

Dimension Table
model FDTS45KXE6 FDTS71KXE6 a b c d e f g h i j k m n o

Unit:mm

60 1230 990 555 435 180 115 940 235 205 125 920 245 1200 1290 345 45 1440 1250 675 575 145 100 1200 200 70 110 1180 210 1410 1500 475

35

4")

Ceiling Cassette -1way CompactFDTQ


Model No. FDTQ22KXE6 FDTQ28KXE6 FDTQ36KXE6
Fits into standard 600 x 600 ceiling

Comfortable effective cooling for small rooms,


with low fan speed air flow at just 5.4m3/min.

Holes for tapping screws


Max.Drain up

Fresh air opening for ducting (Knock out) 250

295~325 63

600 or less

Optional wide panel shown for solid ceiling

210

Condensate drain pump included as standard

Ultra slim design at just 250mm above the ceiling

Specifications
Model Item FDTQ22KXE6 FDTQ28KXE6 FDTQ36KXE6 Direct blow panel Duct panel Direct blow panel Duct panel Direct blow panel Duct panel Panel Name Panel mode (Option) TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER Nominal cooling capacity kW 2.2 2.8 3.6 Nominal heating capacity kW 2.5 3.2 4.0 Power source 1 Phase 220-240V, 50Hz Cool 0.04-0.05 0.04-0.05 0.04-0.05 Power consumption Heat kW 0.04-0.05 0.04-0.05 0.04-0.05 Sound pressure level dB(A) Hi:38 Lo:33 Hi:42 Lo:39 Hi:38 Lo:33 Hi:42 Lo:39 Hi:38 Lo:33 Hi:42 Lo:39 250x570x570 250x570x570 250x570x570 Exterior dimensions Unit mm HxWxD 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 Panel Net weight kg Unit:19 Panel:2.5 Unit:19 Panel:3 Unit:19 Panel:2.5 Unit:19 Panel:3 Unit:19 Panel:2.5 Unit:19 Panel:3 Unit:19 Panel:2.5 Unit:19 Panel:3 Unit:19 Panel:2.5 Unit:19 Panel:3 Unit:19 Panel:2.5 Unit:19 Panel:3 Air flow (Standard) CMM Hi:7 Lo:5.4 Hi:7 Lo:6.5 Hi:7 Lo:5.4 Hi:7 Lo:6.5 Hi:7 Lo:5.4 Hi:7 Lo:6.5 Outside air intake Possible Air filter, Qty Pocket Plastic net x1 (Washable) Remote control wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Installation data Refrigerant piping size mm(in) Liquid line:6.35(1/4") Gas line:9.52(3/8") Liquid line:6.35(1/4") Gas line:12.7(1/2")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

36

35

285

Dimensions
All measurements in mm.
Direct blow panel (TQ-PSA-15W-E) Direct blow panel (TQ-PSB-15W-E)

Duct panel (QR-PNA-14W-ER)

Duct panel (QR-PNB-14W-ER)

* In case of Direct blow panel

Dimension Table
model TQ-PSA-15W-E TQ-PSB-15W-E a 625 780 b 514 514 c 650 650

Unit:mm

Dimension Table
model QR-PNA-14W-ER QR-PNB-14W-ER a 625 780 b 650 650

Unit:mm

d 580 580

c 580 580

37

4")

Duct Connected -High Static PressureFDU


Model No. FDU71KXE6 FDU90KXE6 FDU112KXE6 FDU140KXE6

Dimensions
All measurements in mm.

FDU71KXE6

FDU90KXE6, 112KXE6, 140KXE6

Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Available Static pressure Pa Outside air intake Air filter, Qty Remote control Installation data Refrigerant piping size mm(in)

FDU71KXE6
7.1 8.0 0.29-0.32 0.27-0.30 Hi:41 Lo:37 295x850x650 40 Hi:25 Lo:20

FDU90KXE6
9.0 10.0 1 Phase 220-240V, 50Hz 0.35-0.39 0.34-0.38 Hi:42 Lo:37

FDU112KXE6
11.2 12.5 0.39-0.45 0.34-0.39 Hi:42 Lo:38 350x1370x650

FDU140KXE6
14.0 16.0

Hi:43 Lo:39

63 Hi:34 Lo:27 Standard 50, Max 130 Possible(on Return duct) Procure locally wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Liquid line:9.52(3/8") Gas line:15.88(5/8")

Hi:42 Lo:33.5

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

38

Duct Connected -High Static PressureFDU


Model No. FDU224KXE6 FDU280KXE6

Fan control kit (100~200Pa) U-FCRA(option)

Dimensions
All measurements in mm.

Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Available Static pressure Pa Outside air intake Air filter, Qty Remote control Installation data Refrigerant piping size mm(in)

FDU224KXE6
22.4 25.0 1 Phase 220-240V, 50Hz 0.94-1.03 0.86-0.90 Hi:51 360x1570x830 92 Hi:51 Standard 100, Max 200 Possible(on Return duct) Procure locally wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Liquid line:9.52(3/8") Gas line:19.05(3/4")

FDU280KXE6
28.0 31.5 0.96-1.05 0.88-0.96 Hi:52

Hi:68

Liquid line:9.52(3/8") Gas line:22.22(7/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

39

4")

Duct Connected -Low/Middle Static PressureFDUM


Model No. FDUM22KXE6 FDUM28KXE6 FDUM36KXE6 FDUM45KXE6 FDUM56KXE6 FDUM71KXE6 FDUM90KXE6 FDUM112KXE6 FDUM140KXE6

Filter kit
UM-FL1E : for 22~56 UM-FL2E : for 71, 90 UM-FL3E : for 112, 140 (option)

LOW NOISE

Specifications
Model FDUM22KXE6 FDUM28KXE6 FDUM36KXE6 FDUM45KXE6 FDUM56KXE6 FDUM71KXE6 FDUM90KXE6 FDUM112KXE6 FDUM140KXE6 Item Nominal cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 Nominal heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 Power source 1 Phase 220-240V, 50Hz Cool 0.09-0.11 0.11-0.13 0.14-0.16 0.15-0.17 0.16-0.19 0.24-0.28 0.28-0.32 Power consumption Heat kW 0.09-0.11 0.11-0.13 0.14-0.16 0.15-0.17 0.16-0.19 0.24-0.28 0.28-0.32 Sound pressure level dB(A) Hi:33 Me:31 Lo:28 Hi:34 Me:31 Lo:28 Hi:35 Me:32 Lo:29 Hi:36 Me:33 Lo:30 Hi:37 Me:35 Lo:32 Hi:38 Me:36 Lo:33 Exterior dimensions mm HxWxD Net weight 33 kg Air flow (Standard) CMM Hi:10 Me:9 Lo:8 Available Pa Static pressure Outside air intake Air filter, Qty Remote control Installation data Refrigerant piping size mm(in) Liquid line:6.35(1/4") Gas line:9.52(3/8") 299 x 750 x 635 34 Hi:12 Me:11 Lo:10 Hi:14 Me:12 Lo:11 Standard:50 Max:85 Possible Procure locally wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2") Liquid line:9.52(3/8") Gas line:15.88(5/8") 299 x 950 x 635 350 x 1370 x 635

40 59 Hi:18 Me:16 Lo:14 Hi:20 Me:18 Lo:15 Hi:28 Me:25 Lo:22 Hi:34 Me:31 Lo:27 Standard:60 Max:85

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

Dimensions
All measurements in mm.

FDUM22KXE6

40

FDUM28KXE6, 36KXE6, 45KXE6, 56KXE6

FDUM71KXE6, 90KXE6

FDUM112KXE6, 140KXE6

41

4")

Duct Connected(Ultra thin) -Low Static PressureFDQS


Model No. FDQS22KXE6 FDQS28KXE6 FDQS36KXE6 FDQS45KXE6 FDQS56KXE6

Filter kit
QS-FL1E (option)

Ultra thin design

180mm

Ultra thin design at just 30kg in weight means quick, easy and neat installation in various kinds of room types.

600mm Drain Pump

600mm

Drain can be discharged upwards by 600mm from the unit bottom. It allows a piping layout with a high degree of freedom depending on the installation location.

Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Air filter, Qty Available Static pressure Pa Remote control Installation data Refrigerant piping size mm(in)

FDQS22KXE6
2.2 2.5 0.06-0.07 0.06-0.07

FDQS28KXE6
2.8 3.2

FDQS36KXE6

FDQS45KXE6

FDQS56KXE6
5.6 6.0 0.08-0.09 0.08-0.09

3.6 4.5 4.0 5.0 1 Phase 220-240V, 50Hz 0.07-0.08 0.07-0.08 Rear air return Hi:37 Me:35 Lo:33 Bottom air return Hi:43 Me:41 Lo:39 180 x 940 x 580

27 Hi:9 Me:8 Lo:7.5

28 Hi:9 Me:8 Lo:7.5 Not possible Procure locally Standard:15, Max:30 wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Hi:11 Me:10 Lo:9

Liquid line:6.35(1/4") Gas line:9.52(3/8")

Liquid line:6.35(1/4") Gas line:12.7(1/2")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

42

Dimensions
All measurements in mm.

43

R410A

Duct Connected (Compact & Flexible) FDUH


Model No. FDUH22KXE6 FDUH28KXE6 FDUH36KXE6

Drain up kit
(600mm)

UH-DU-E(option)

Compact and thin size, light weight

Installation Flexibility
570mm

Our leading high technology has realized the best solution for air conditioning in hotels with compact and thin size units and high energy efficiency. In addition, weight is only 20kg.
Quiet operation

257 mm

Control box and drain piping can be installed on both side of the unit and air intake to the unit is available from bottom or back side. Our highest technology can satisfy diverse installation requirements.
Control box

530m

The lowest sound level in the industry can ensure comfortable stay and rest in hotels.
Drain piping

Remote control
Simple remote control
Considering specialized usage in hotel rooms, control buttons are limited only to minimum required functions such as ON/OFF, mode, temperature setting and fan speed. It is really simple and easy to use.

NEW
Wired

RCH-E3
(option)

Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions HxWxD mm Net weight kg Air flow (Standard) CMM Available static pressure Pa Air filter, Q'ty Remote control Installation data mm(in) Refrigerant piping size

FDUH22KXE6
2.2 2.5

FDUH28KXE6
2.8 3.2 1 Phase 220-240V, 50Hz 0.050-0.055/0.053 0.050-0.055/0.053 HI: 33 Me: 30 Lo: 27 257x570x530 20 HI: 7 Me: 6.5 Lo: 6 30 Procure locally wired:RCH-E3,RC-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:9.52(3/8")

FDUH36KXE6
3.6 4.0

Gas line:12.7(1/2")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

44

Dimensions
All measurements in mm.
30.8 32.5 83.3 53
Symbol A B C1,C2 D E F Model Gas piping Liquid piping Drain piping Hole for wiring Suspension bolts Inspection hole Duct dimension Content FDUH22KXE6,28KXE6 9.52 38"Flare 6.35 14"Flare FDUH36KXE6 12.7 12"Flare

100 145

Holes for tapping screws

12-4

32 27.6

150

150 494

150

32 27.6

Supply air duct

VP20(I.D.20, O.D.26) Note2 30 M10 635X890Note3

Duct dimension

30.8

145.6
Air outlet

Drain hose piece Standard Accessory Installed on site Note 4

575.2 273 66.4

Suspension bolts pitch Space for installation and service

32.5

255.8 21 40

C1 A B

66 95.3

30.8 66

F
610

156.8

Suspension bolts pitch

488

Control box Note 4

530

62.1

C2

890 600 100


Unit:mm

D68
549.2

Holes for tapping screws

12-4

21

188.5 148.5

38.2

Air inlet

32 27.5

150

150 494.2 574

150

32 27.5

G
Bottom plate Able to be located on the back side

View G
In case of Bottom air intake
Holes for tapping screws

30 28.3

37.6

160 200

30

30

12-4

28.5

Air inlet

198.2

160

After bottom plate is replaced to back side

View G

30

Air inlet

E
Notes The model name label is attached on the fan case inside the air return grille. Prepare the connecting socketVP20on site. As for drain piping, it is possible to choose C1 or C2 When control box is located on the reverse side, Installation space should be modified to new location. Contorl box and Drain hose piece are able to be relocated on the reverse side.

Simple remote control


150 50.5

50.5

150

150

18.2

537.6

120

70

15

45

4")

Wall Mounted FDK


Model No. FDK22KXE6 FDK28KXE6 FDK36KXE6 FDK45KXE6 FDK56KXE6 FDK71KXE6

FDK22~56

coming soon
Wireless remote control
FDK71

RCN-K-E : FDK22~56 RCN-K71-E : FDK71 (option)

INNOVATIVE DESIGN

INSTALLATION WORKABILITY

New FDK models adopt the air flow design that's proven to minimise resistance in a CFD analysis to achieve uniform air conditioning to the furthest corners of the room.
259

The new slimmer design allows easy & neat installation even in tight spaces.

Fast

Slow

Colors in the figure show the air speed.

IMPROVED MAINTAINABILITY

Also included is a new easy clean mechanism where the front panel is opened/closed simply from the bottom to easily access the detachable filters.

Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Air filter, Qty Remote control Installation data Refrigerant piping size mm(in)

FDK22KXE6
2.2 2.5

FDK28KXE6
2.8 3.2 0.05 0.04

FDK36KXE6

FDK45KXE6

FDK56KXE6
5.6 6.3 0.05 0.05

FDK71KXE6
7.1 8.0 0.09 0.09 Hi:47 Me:43 Lo:39 318 x 1098 x 248 15.5 Hi:21 Me:18 Lo:15

3.6 4.5 4.0 5.0 1 Phase 220-240V, 50Hz

Hi:35 Me:33 Lo:31

Hi:39 Me:35 Lo:31 298 x 840 x 259 12

Hi:42 Me:37 Lo:33

Hi:46 Me:42 Lo:37

Hi:8 Me:7 Lo:6

12.5 13 Hi:10 Me:9 Lo:7 Hi:11 Me:9 Lo:7 Hi:14 Me:12 Lo:10 Not possible Polypropylene net x2 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-K-E (for FDK22~56), RCN-K71-E (for FDK71) Liquid line:6.35(1/4") Gas line:12.7(1/2")

Liquid line:6.35(1/4") Gas line:9.52(3/8")

Liquid line:9.52(3/8") Gas line:15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

46

Dimensions
All measurements in mm.

FDK22~56KXE6

FDK71KXE6

47

4")

Ceiling Suspended FDE


Model No. FDE36KXE6A FDE45KXE6A FDE56KXE6A FDE71KXE6A FDE112KXE6A FDE140KXE6A

Wireless remote control RCN-E-E(option)

Small Light-weight Quiet Sleek, intelligent design


INSTALLATION WORKABILITY NEW SLIM DESIGN

Up Rear

210mm
Right

Refrigerant piping can be routed in three directions (rear, up, right) & drain piping in left or right directions, allowing free layout to meet installation conditions.

Slim and sleek design starting at just 28kgs in weight means quick, easy & neat installation.

Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Outside air intake Air filter, Qty Remote control Installation data Refrigerant piping size mm(in)

FDE36KXE6A
3.6 4.0

FDE45KXE6A
4.5 5.0 0.04-0.05 0.04-0.05 Hi:39 Me:38 Lo:36 210 x 1070 x 690 28 Hi:11 Me:9 Lo:7

FDE56KXE6A

FDE71KXE6A

FDE112KXE6A
11.2 12.5 0.12-0.14 0.11-0.13 Hi:44 Me:41 Lo:39

FDE140KXE6A
14.0 16.0 0.14-0.15 0.13-0.14 Hi:46 Me:44 Lo:43

5.6 7.1 6.3 8.0 1 Phase 220-240V, 50Hz 0.08-0.09 0.07-0.08 Hi:41 Me:39 Lo:37 210 x 1320 x 690 37 Hi:18 Me:14 Lo:12 Not possible Pocket Plastic net x2 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-E-E

250 x 1620 x 690 49 Hi:26 Me:23 Lo:21 Hi:29 Me:26 Lo:23

Liquid line:6.35(1/4") Gas line:12.7(1/2")

Liquid line:9.52(3/8") Gas line:15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

48

Dimensions
All measurements in mm.

C1,C2
10 290 (Suspension bolts pitch) 135 68 5 410

FDE36KXE6A, 45KXE6A, 56KXE6A


24 1022 (Suspension bolts pitch) 24

D
145
52

40

B A
108

Note) The slope of drain piping inside the unit must take decline of 10mm.

53

40

990 1070

40

690 195 235 271

15 20 100

60

C1,C2

Air supply

Drain hose piece (Accessory, 0.3m) (Installed on site)

Symbol A B C 1,2 D E F G

Content Gas piping Liquid piping Drain piping Hole for suspension bolt Back cutout Top cutout Hole for drain piping (for left back)

31

12.7 (1/2") (Flare) 6.35 (1/4") (Flare) VP20 (I.D.20) (M10 or M8) PE cover Plate cover (Knock out)

173

210

215

53 109

27

MITSUBISHI HEAVY INDUSTRIES,LTD

Space for installation and service

Position of top cutout and back cutout

27

20

12

175

19

Hole for drain piping (for left)

308

100 or more

300 or more

F
150 or more 5 or more
Right side cutout

G E
Note(1)The model name label is attached on the fan casing inside the air return grille.

C2
76 Air return grille

75

A C1

110 135

Obstacle Make a space of 4000 or more between the units when installing more than one.

Remove the cutout using side cutter or similar tool.

C1,C2

FDE71KXE6A
24 1272 (Suspension bolts pitch) 24

290 (Suspension bolts pitch) 135 68 5 410

D
145 52

40

B A
108

Note)The slope of drain piping inside the unit must take decline of 10mm.
Symbol A B C 1,2 D E F G Content Gas piping Liquid piping Drain piping Hole for suspension bolt Back cutout Top cutout Hole for drain piping(for left back)

10

53

40

1240 1320

40

690 195 235 271

15 20 100

60

Air supply

1 2 Drain hose piece (Accessory, 0.3m) (Installed on site)

C ,C

15.88 (5/8") (Flare) 9.52 (3/8") (Flare) VP20 (I.D.20) (M10 or M8) PE cover Plate cover (Knock out)

173

210

215

53 109

27

MITSUBISHI HEAVY INDUSTRIES,LTD

Space for installation and service

Position of top cutout and back cutout

27

31

20

12

175

19

Hole for drain piping (for left)

308

100 or more

300 or more

F
150 or more 5 or more
Right side cutout

G E
Note(1)The model name label is attached on the fan casing inside the air return grille.

C2
76

75

Air return grille

A C1

110 135

Obstacle
Make a space of 4500 or more between the units when installing more than one.

Remove the cutout using side cutter or similar tool.

C1,C2

FDE112KXE6A, 140KXE6A
24 1572 (Suspension bolts pitch) 24

290 (Suspension bolts pitch) 135 68 5 410

D
145 52

250

255

40

B A
108

Note) The slope of drain piping inside the unit must take decline of 10mm.

10

53

40

1540 1620

40

690 195 235 271

15 20 100

60

C1,C2

Symbol A B C1,2 D E F G

Content Gas piping Liquid piping Drain piping Hole for suspension bolt Back cutout Top cutout Hole for drain piping (for left back)

15.88 (5/8") (Flare) 9.52 (3/8") (Flare) VP20 (I.D.20) (M10 or M8) PE cover Plate cover (Knock out)

173

53 109

27

Air supply

Drain hose piece (Accessory, 0.3m) (Installed on site)

MITSUBISHI HEAVY INDUSTRIES,LTD

Space for installation and service

Position of top cutout and back cutout

27

31

20
300 or more 308 100 or more

0 12

175

19

Hole for drain piping (for left)

F
150 or more 5 or more Right side cutout

G E
Note(1)The model name label is attached on the fan casing inside the air return grille.

C2

75 76 Air return grille

A C1

110 135

Obstacle
Make a space of 5000 or more between the units when installing more than one.

Remove the cutout using side cutter or similar tool.

49

4")

Floor Standing (with casing) FDFL Floor Standing (without casing) FDFU
Model No. FDFL28KXE6 FDFL45KXE6 FDFL71KXE6 FDFU28KXE6 FDFU45KXE6 FDFU56KXE6 FDFU71KXE6

FDFL

FDFU (concealed type)

Compact design at 630mm height

Wider airflow for optimum comfort

Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cool Power consumption Heat kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Air filter, Qty Remote control

FDFL28KXE6
2.8 3.2

FDFL45KXE6
4.5 5.0

FDFL71KXE6
7.1 8.0

FDFU28KXE6
2.8 3.2 1 Phase 220-240V, 50Hz

FDFU45KXE6
4.5 5.0

FDFU56KXE6
5.6 6.3

FDFU71KXE6
7.1 8.0

Hi:41 Me:38 Lo:36

0.09-0.10 0.09-0.10 Hi:43 Me:41 Lo:40 630x1481x225

Hi:41 Me:38 Lo:36

0.09-0.10 0.09-0.10 Hi:43 Me:41 Lo:40 630x1077x225 630x1362x225 32 Hi:18 Me:15 Lo:12

630x1196x225 32 Hi:12 Me:11 Lo:10 Hi:14 Me:12 Lo:10

40 25 Hi:14 Me:12 Lo:10 Hi:12 Me:11 Lo:10 Hi:18 Me:15 Lo:12 Polypropylene net x1 (Washable) wired:RC-E3, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2")

Liquid line:6.35(1/4") Liquid line:6.35(1/4") Liquid line:9.52(3/8") Liquid line:6.35(1/4") Installation data Refrigerant piping size mm(in) Gas line:9.52(3/8") Gas line:12.7(1/2") Gas line:15.88(5/8") Gas line:9.52(3/8")

Liquid line:9.52(3/8") Gas line:15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

50

Dimensions
All measurements in mm.

FDFL

Dimension Table
model FDFL28KXE6, 45KXE6 FDFL71KXE6 a 786 1071 b 1196 1481 c 750 1035

Unit:mm

d 806 1091

FDFU

Dimension Table
model FDFU28KXE6, 45KXE6, 56KXE6 FDFU71KXE6 a 786 1071 b 810 1095 c 722 1007 d 750 1035

Unit:mm

e 806 1091

51

4")

Outdoor Air Processing unit FDU-F


Model No. FDU500FKXE6 FDU850FKXE6 FDU1300FKXE6 FDU1800FKXE6
Fan control kit (100~200Pa) U-FCRB(option)

Air conditioning and intake of outdoor air are in the same system

Outdoor Air processing unit can be connected in a KX6 system as one of indoor unit series and can create fresh and comfortable air supply together from our high advanced technology.

KX6 outdoor unit

indoor unit Outdoor Air Processing unit air conditioning

indoor unit office outside air supply corridor refresh room, rest room

Compact design

Compact design at just 360mm in height, high static pressure of 200Pa and the industry's lowest noise level can meet various kind of installation location for office, refresh room, restroom and kitchen of restaurant etc.

exhaust air

supply air outdoor air supply air

outdoor air

(1) This unit is the specific unit for processing the outdoor air temperature closer to the room temperature. For conditioning the room temperature a dedicated air-conditioner is required additionally. (2) This unit monitors the outdoor air temperature and controls thermostat ON/OFF at the setting temperature by the remote controller, which indicates the outdoor air temperature for controlling thermostat ON/OFF. When thermostat is turned OFF, the operation is changed to the fan mode so that unprocessed outdoor air will be blown into the room directly. Therefore place the air outlet port or orient the air outlet direction not to blow air directly to persons in the room, especially in the small room such as a restroom and/or sanitary hot water supplying room. (3) It is strictly prohibited to monitor the room temperature by switching to the thermistor at remote controller side and/or the optional remote thermistor. Otherwise dew formation at air outlet port and/or dew dripping may occur during cooling operation due to the lower outdoor air temperature. Therefore keep the remote controller of this unit in place closer to the administrator so as not to be touched it freely by the end user. (4) Dehumidifying operation with this unit is prohibited. (5) When handing over this unit to the end user, make sure to explain sufficiently about the foregoing cautions, the installation place and usage of remote control for this unit and the location of the air outlet.

52

Connectivity with KX6 series


FDU-F series are connectable to 8~48HP KX6 outdoor units, not connectable to 4~6HP. 8 ~ 48 HP : Yes , 4 ~ 6 HP : No

Combination with KX6 series


case A are connected with KX6 outdoor units and max quantity of FDU-F is 2 units.
In case both of OA processing units In case OA processing units only

Combination
The total capacity of FDU-F is 50~100% of outdoor capacity

B and dedicated air-conditioner


are connected with KX6 outdoor unit.

The total capacity of FDU-F and dedicated air-conditioners is 50~100% of outdoor capacity and max quantity of FDU-F should be below 30% of outdoor unit capacity.

[A]
10HP FDU850FKXE6 (5HP) FDU850FKXE6 (5HP)

[B]
18HP

Less than 30%

FDU850FKXE6 (5HP)

6HP

6HP

Concept (Difference between FDU-F and SAF)


SAF is the energy recovery ventilation unit which can recover heat energy from exhaust air to supply air and "has no air processing function, but FDU-F is air processing unit which can treat the supply air closer to room temperature by cooling or heating in connection with KX6 refrigerant system and exhaust air is discharged to outside of the room.

FDU-F OA Processing units


Outside

Exhaust Air Air Supply

Direct Expansion Heat Exchanger

SAF
Outside

Air Supply Exhaust Air

53

4")

Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Power Cool kW consumption Heat Sound pressure level dB(A) Exterior dimension mm HxWxD Net weight kg Air flow (Standard) CMM CMH Available static pressure Pa Remote control Installation data mm Refrigerating piping size (in)

FDU500FKXE6
9.0 4.2 0.11 0.11 43 360x820x830 48 8.5 510

FDU850FKXE6
14.0 7.0

FDU1300FKXE6
22.4 10.9

FDU1800FKXE6
28.0 14.8 0.31 0.31 51 360x1570x830

1 Phase 220-240V, 50Hz 0.16 0.16 46 360x1200x830 62 14 840 82 22 1320 Max:200 wired:RC-E3 wireless:RCN-KIT3-E Liquid line:9.52(3/8") Gas line:19.05(3/4") 0.27 0.27 48

84 30 1800

Liquid line:9.52(3/8") Gas line:15.88(5/8")

Liquid line:9.52(3/8") Gas line:22.22(7/8")

1. Cooling capacity is measured at 33CDB/28CWB (68%RH) and heating capacity is measured at 0CDB/2.9CWB under OA processing mode. 2. Operation range of outdoor air temperature is 20C-40CDB in cooling, and 0C-24CDB in heating. 3. Indicated sound level value is measured in anechoic chamber. Actual operation value may become higher due to the surrounding conditions 4. Indicated sound level values are measured at 200Pa static pressure. Indicated air flow volume is measured at 200Pa static pressure. 5. Total connection capacity of dedicated air conditioning units and OA processing units should be within 50% to 100% of the outdoor unit capacity. Total connection capacity of OA processing units should not exceed 30% of outdoor unit capacity. 6. OA processing unit can be used alone, but connecting number of OA processing units should not exceed two (2). The connection capacity of OA processing units should be within 50% to 100% of outdoor unit capacity. 7. When optional fan control kit (U-FCRB) is used and operated at 100Pa static pressure, the sound level value becomes 5dB(A) lower than the above indicated value.

Dimensions
All measurements in mm.

FDU500FKXE6

Suspension bolts pitch

(Inner size of duct flange)

Suspension bolts pitch

Control box

12-M5 screw

Duct connection port for outdoor air inlet Above

12-M5 screw

Port for air outlet

(Inner size of duct flange) Installation space

(Below suspension bolt pitch)

Below

(Inner size of duct flange)

Installation space

Installation space

or more

or more

or more

Plan view

or more

Front view

Symbol

Content

Slab Ceiling Service space or more Piping space (Service from below) (Service from side and below)

(Service from side)

54

or more

Gas piping Liquid piping Drain piping connection Power supply wiring connection Suspension bolt Inspection Opening Inspection Opening

(Inner size of duct flange)

FDU850FKXE6

Suspension bolts pitch

(Inner size of duct flange)

Suspension bolts pitch

Control box

16-M5 screw

Duct connection port for outdoor air inlet Above

12-M5 screw

Port for air outlet

(Below suspension bolt pitch)

Below

(Inner size of duct flange)

or more

or more

Front view

or more

Plan view Installation space

Installation space or more Installation space Slab Ceiling

(Inner size of duct flange)


Symbol Content

(Service from side)

or more Piping space

(Service from below)

(Service from side and below)

FDU1300FKXE6, FDU1800FKXE6
Suspension bolts pitch

Suspension bolts pitch

or more

Service space

Gas piping Liquid piping Drain piping connection Power supply wiring connection Suspension bolt Inspection Opening Inspection Opening

(Inner size of duct flange)

Control box Duct connection port for outdoor air inlet Above 20-M5 screw Port for air outlet

20-M5 screw

(Below suspension bolt pitch)

Below

(Inner size of duct flange)

Installation space or more or more Installation space Slab Ceiling or more Piping space (Service from side) (Service from below) or more Service space Service space (Service from side and below) Front view or more or more Plan view

(Inner size of duct flange)

Symbol

Content

Gas piping Liquid piping Drain piping connection Power supply wiring connection Suspension bolt Inspection Opening Inspection Opening

(Inner size of duct flange)

(Inner size of duct flange)

55

4")

Fresh Air Ventilation and Heat Exchange unit SAF-E4


Model No. SAF250E4 SAF350E4 SAF500E4 SAF800E4 SAF1000E4

Re; Building Regulations Part L2


The Part L2 (April 2006) regulations limit the amount of electrical/gas power to be used to provide heating or cooling in commercial buildings. Therefore the building designer needs to select energy efficient heating/cooling equipment, and to minimise energy losses through ventilation systems. The SAF recovers heat energy which would otherwise be exhausted to atmosphere, and uses this energy to warm the air entering the building. The reverse happens in warmer climates, where the exhausted cool air is used to partially cool the incoming air.
Structure (SAF1000E4)
Plate heat exchanger Damper Exhaust Air

Capturing this waste energy, means the heating/ cooling requirements of the building are reduced, so smaller size plant can be selected, savings can be made in long term energy consumption, and carbon emissions are reduced. The inclusion of the SAF energy recovery ventilation units in the building design, will reduce the total amount of carbon emissions.

Principle of operation (simple ventilation) FREE COOLING


outdoor indoor Supply Air

Principle of operation (heat exchanging) ENERGY RECOVERY


Exhaust Air outdoor indoor Supply Air

EA (Exhaust Air)

RA (Room Air)

27deg Outside Air 10deg

10deg Room Air 27deg e.g. For cooling in winter time

33deg Outside Air 35deg

29deg Room Air 27deg

OA (Outside Air)

SA (Supply Air)

Specifications
Item Model Power source Exterior dimensions mm Height x Width x Depth Exterior appearance Power input W Running current A Enthalpy Cooling exchange UHi efficiency Heating Temperature exchange efficiency Enthalpy Cooling exchange Hi efficiency Heating Temperature exchange efficiency Enthalpy Cooling exchange Lo efficiency Heating Temperature exchange efficiency Motor & Qty kW Air handling equipment Fan type & Qty UHi Air flow Hi m3/h Lo UHi Available static pressure Hi Pa Lo

SAF250E4
270x882x599 99-114 0.46-0.48 63 70 63 70 66 73 77 0.02x2 250 250 170 90 80 37

SAF350E4
170x882x804 124-137 0.59-0.60 66 69 66 69 69 71 77 0.044x2 350 350 280 95 65 42

SAF500E4
1 Phase 220-240V, 50Hz 270x962x904 Galvanised steel sheet 169-188 0.79-0.81 62 67 75 62 67 75 77 67 75 0.062x2 Sirocco fan x 2 500 500 370 105 70 38 Protection for element (Washable) PS400

SAF800E4
388x1322x884 309-359 1.48-1.50 65 71 65 71 68 74 76 0.117x2 800 800 650 140 110 70

SAF1000E4
388x1322x1135 360-399 1.85-1.93

Capacity

68 73 76 0.137x2 1000 1000 810 90 55 35

Air filter

Out take intake air Exhaust air

56

Dimensions
All measurements in mm.

SAF250E4,350E4,500E4

SAF800E4

SAF1000E4

Installation reference
Pipe Hood Outside Intake Duct Ceiling Suspension Bolt Supply Air Duct

SA
(Supply Air)

RA
(Room Air)

OA

(Outside Air) Exhaust Air

EA

Room Intake Duct Heat Insulation Material Exhaust Air Duct

Inside Supply Opening (Supply/Exhaust Air Grill)

Room Intake Opening (Supply/Exhaust Air Grill)

Dimension table
NO.
1 2 3 4 5 6 7 8 9 10 11

Unit:mm

Name
Frame Adaptor Electrical Equipment Box Inspection Cover Fan Motor Heat Exchange Element Filter Damper Damper Motor Ceiling Suspension Fixture

Quantity
1 4 1 1 2 2 2 2 1 1 4

Material
Zinc-plated steel ABS Resin Zinc-plated steel ABS Resin

Remarks

Model
SAF250E4 SAF350E4 SAF500E4

a
142 162 202

b
810 810 890

c
599 804 904

d
315 480 500

e
655 860 960

Model
SAF250E4 SAF350E4 SAF500E4

f
219 219 246

g
164 164 210

h
144 144 194

i
882 882 962

j
95 95 107

Flame Retardant Paper + Plastic Air to air Heat Exchanger Non-woven Cloth Collection Efficiency Gravimetric Method 82%

Zinc-plated Steel

Note(1) An inspection port is needed for cleaning the heat exchanger and filter 1 or 2 times a year.

57

R410A

Control Systems <Individual control>


Remote Control line up
indoor unit wired all models remote control RC-E3 RCH-E3 wireless indoor unit FDT FDTC FDE remote control RCN-T-36W-E RCN-TC-24W-ER RCN-E-E indoor unit FDK22~56 FDK71 others remote control RCN-K-E RCN-K71-E RCN-KIT3-E

Wired remote control with weekly timer (option)


RC-E3
The RC-E3 controller enables extensive access to service and maintenance technical data combined with easy to use functions and a clear LCD display. Run hour meters to facilitate maintenance checking RC-E3 stores operation data when an anomaly occurs and indicates the error on the LCD. It also displays cumulative operation hours of the air conditioner and compressor since commissioning. Room temperature controlled by the remote control sensor The temperature sensor is housed in the top section of the remote control unit. This arrangement has improved the sensitivity of the remote control units sensor, which permits more finely controlled air conditioning. Weekly timer function as standard RC-E3 provides (as a standard feature) a weekly timer, which allows one-week operation schedules to be registered. A user can specify up to four times a day to start/stop the air conditioner. (Temperature setting is also possible with the timer). Timer operation Changeable range
Upper limit Lower limit 20~30C(effective for heating operation) 18~26C(effective for non-heating operation)

Changeable set temperature ranges RC-E3 allows the upper and lower limits of a set temperature range to be specified separately. By adjusting a set temperature range, you can ensure energy saving air conditioning by avoiding excessive cooling or heating.

Simple remote control (option)


RCH-E3 (wired)

NEW

Considering specialized usage in hotel rooms, control buttons are limited only to minimum required functions such as ON/OFF, mode, temperature setting and fan speed. It is really simple and easy to use.

Up to 16 units It can control up to 16 units individually, with pressing the AIR CON No. button. AUTO restart This function allows starting the air conditioner automatically when power supply is restored after power failure or by turning on the power switch.

Wireless remote control (option)


For wireless control simply insert the infra-red receiver kit on a corner of the panel

Thermistor (option)
RCN-KS-E, RCN-K71-E

RCN-T-36W-E, RCN-TC-24W-ER

RCN-E-E

NEW

NEW

RCN-KIT3-E

SC-THB-E3
In case sensor in the indoor units or the remote control sensor can not sense the room temperature correctly, or individual remote control in each room is not required but only censor is required (as when center control system is in place), install SC-THB-E3 at proper place in the rooms.

coming soon

58

<Control System>
SUPERLINKMHI has now combined simplicity of installation with our highly sophisticated Superlink- control system, to offer building owners and occupiers a comprehensive control and management system, while providing complete commissioning and service maintenance assistance for installers and service engineers. The Superlink- network utilises two wire, non-polar cable - for further details of wiring. Superlink- is an advanced high speed data transmission system that can connect up to 128 indoor units and 32 outdoor units as a network. MHI offers a wide range of control options for the Superlink- network to suit any application large or small, as well as connection to new or existing building management systems. Individual MHI split systems can also be integrated on to the Superlink- network using SC-ADN-E.

Multi-KX6 outdoor units "Micro KX"

Multi-KX6 indoor units

Centre Control SC-SL2N-E


Capable of control and monitoring up to 64 indoor units. All operational functions, plus enable/disable connected remote control. Individual On/Off Control

KX6 Outdoor units

Multi-KX6 indoor units

SC-WGWN-A/B PC Control Interface


KX6 twined Outdoor units

Centre Control SC-SL3N-AE/BE

Multi-KX6 indoor units with individual room control

Centre Control SC-SL2N-E

3-core + earth cable for connecting indoor and outdoor units

3-core cable for connecting indoor and outdoor units

3-core cable for connecting indoor and outdoor units

3-core + earth cable for connecting indoor and outdoor units SRK/SRF-ZIXseries SC-BIKN-E

Wireless remote control SC-ADN-E SC-ADN-E SC-ADN-E SC-ADN-E

One-to-one

Wireless

59

4")

<Central Control>
SC-SL1N-E
Start/stop control of up to 16 indoor units either individually or collectively. Simple centralised control. 1. The SC-SL1N-E is connected to the Superlinknetwork via 2-core, non-polar wires (AB connection). 2. It will monitor and control the start/stop function of up to 16 units, with the sixteen operation button. 3. The unit or group numbers in operation or in need of service are displayed with an LED. 4. Collective start/stop is also available through the simultaneous on/off button. 5. Up to 12 SC-SL1N-E units can be connected to a Superlink- network (consisting of up to 128 indoor units). 6. If a power failure occurs, the SC-SL1N-E will resume the operation of the system according to a stored operation condition, once power is restored. 7. This central control can be connected anywhere on the Superlink- network, at indoor units as well as outdoor units. This can substantially reduce the amount of electrical installation work. This feature is common to both SC-SL1N-E and SC-SL2N-E controls.

Example of control by a centre control SC-SL1N-E

SL1N-E

More than one unit (up to 16) can be controlled for individual or collective start/stop operation and indication of unit statuses such as in operation or in need of service. Outer dimensions: H120 x W120 x D15+62*mm. 62* is the measurement including the part contained in a recess.

SC-SL2N-E
Central control of up to 64 indoor units including weekly timer function as standard. 1. The SC-SL2N-E is connected to the Superlinknetwork via 2-core, non-polar wires (AB connection). 2. It will monitor and control the start/stop function of up to16 units, or 16 groups of units, with the sixteen operation buttons. 3. It also monitors and controls the following functions for individual units, groups of units or the complete network: operation mode, set point temperature, return air temperature, louvre position, error code. 4. The unit or group numbers in operation or in need of service are displayed with an LCD. 5. Collective start/stop is also available through the simultaneous on/off button. 6. If a power failure occurs, the SC-SL1N-E will resume the operation of the system according to a stored operation condition, once power is restored. 7. The SC-SL2N-E can be connected to an external timer to facilitate timed on/off cycles. 8. The number of SC-SL1N-E and SC-SL2N-E units connected to one network are detailed on the table below. 9. This central control can be connected anywhere on the Superlink- network, at indoor units as well as outdoor units. This can substantially reduce the amount of electrical installation work. This feature is common to both SC-SL1N-E and SC-SL2N-E controls.

Example of control by a centre control SC-SL2N-E

SL1N-E

An SC-SL2N-E performs the start/stop control, monitoring and mode setting of up to 64 units. It is a high quality air conditioner control system that allows up to 64 indoor units to be freely grouped into 1 to 16 groups. It allows not only the start/stop control but also the monitoring, display of operation statuses such as in operation or in need of service and mode setting such as switching of operation modes of connected units collectively, by group or individually. Outer dimensions: H215 x W120 x D25+35*mm. 35* is the measurement including the part contained in a recess.

Combination of Center Control and BMS interface unit


SC-SL1N-E SC-SL2N-E SC-SL3N-AE/BE SC-WGWN-A/B SC-BGWN-A/B SC-LGWN-A SC-SL1N-E Yes( 1) Yes( 1) Yes( 1) Yes( 2) Yes( 2) Yes( 2)

Yes:connectable No:not connectable

SC-SL2N-E Yes( 1) Yes( 1) Yes( 1) Yes( 2) Yes( 2) Yes( 2)


network 2 5-8 3-4 0 4

SC-SL3N-AE/BE Yes( 1) Yes( 1) Yes( 1) Yes( 2) Yes( 2) Yes( 2)

SC-WGWN-A/B Yes( 2) Yes( 2) Yes( 2) No No No

SC-BGWN-A/B Yes( 2) Yes( 2) Yes( 2) No No No


network SC-SL2N-E 0-1

SC-LGWN-A Yes( 2) Yes( 2) Yes( 2) No No No

( 1) Number of units in combination of SC-SL1N-E, SC-SL2N-E and SC-SL3N-AE/BE


SC-SL3N-AE/BE SC-SL2N-E SC-SL1N-E Connectable number of controls in one superlink0 1 0 1-2 3-4 5-8 0-2 5-8 0-2 3-4 12 8 4 0 8 0 8 4

( 2) Number of units in combination of SC-WGWN-A/B, SC-BGWN-A/B, SC-LGW-A, SC-SL3N-AE/BE, SC-SL2N-E and SC-SL1N-E
Connectable number of controls in one superlinkSC-WGWN-A/B or SC-BGWN-A/B or SC-LGWN-A 1 SC-SL1N-E 0-4 SC-SL3N-E-AE/BE 0-1

Regarding previous Superlink, refer to Technical Manual '06 SC-T-111, '08 SC-T-119.

Regarding previous Superlink, refer to Technical Manual '06 SC-T-111, '08 SC-T-119.

60

SC-SL3N-AE/BE
MHI introduces the full colour touch screen central control SC-SL3NAE/BE, with 7 inch interactive LCD display. Offers control, monitoring, scheduling and service/maintenance functions for up to 128 indoor units. Indoor units can be controlled, scheduled, monitored and interrogated either individually, as groups or as blocks of groups with the following functions:

Indoor unit 128 units

SLA3R-BX Control Box (option)

NEW
Collective stop signal input

In case SC-SL3N-AE/BE is fixed in the wall, use SLA3R-BX as optional parts.


Electric wires Beam of building Inner wall Central Control Fix the SLA3R-BX to the beam in the building

40

more than 105mm

SLA3R-BX

Control Run/Stop Mode (cool/heat/fan) Set temperature Operation permitted/prohibited Fan speeds Air direction Filter reset Filter sign Maintenance (1, 2 or back-up) Breakdown

Monitoring Operating state Mode Set temperature Room temperature Operation enabled Fan speed Air direction

Scheduling Yearly schedule Today's schedule Special day schedule

Administration/Service Block definition Group definition Unit definition Time and date setting Alarm history Energy consumption calculation period Energy consumption cumulative operation time Demand control Emergency stop Power failure recovery control

Electric power calculation function:


(for SC-SL3N-BE only) SC-SL3N-BE gives outputs as electric power consumption kW data -each indoor unit, each group, each SUPERLINK- system and each power pulse system- and uses USB memory. The data can be edited by using the software that comes with the unit. Item
Power supply Power consumption External dimensions (Height x Width x Depth) Net weight Number of connectable units (indoor units) LCD touch panel SL (Superlink) signal inputs Inputs Gas, Power pulse input* Emergency stop signal input* Demand signal input* Outputs

Model

SC-SL3N-AE/SC-SL3N-BE
0 ~ 40oC 1 Phase 100-240V 50/60Hz 18W 162mm x 240mm x 108mm 2.0kg up to 128 units Colour LCD, 7 inches wide 3 systems 8-point pulse width 100ms or more 1 point non-voltage a contact input continuous input (closed, forced stop) 1 point non-voltage a contact input continuous input (closed, demand control) 1 point maximum rated current 40mA, 24 V During full stop; Open. If even one unit is operating; Closed 1 point maximum rated current 40mA, 24 V Normal; closed. If even one unit is abnormal; Open

Ambient temperature during use

SC-SL3N-BE
Method of data saving Calculation software Air-conditioner power proportional distribution pulse input Connecting indoor units number (Maximum) USB Standard 8 systems 128

Simultaneous operation output Simultaneous error output

* The receiving side power supply is DC 12V (10mA). The air conditioning charges calculations of this unit are based on OIML, the international standard. * In case embodying in a wall, please be sure to special box SLA3R-BX (option).

61

4")

<PC windows central control>


SC-WGWN-A/SC-WGWN-B
Production by order

(SC-WGWN-B is with electric power calculation function)


Control and monitoring of up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) centralised to a network PC using the Superlink- web gateway. Simple installation is assured with no special software requirements, operation is via Internet Explorer. A low power embedded CPU and compact flash ROM ensure a large storage capacity with high reliability (no moving parts such as a PC fan, etc). An IP address filter function combined with three-level user authentication check also ensures security.
SUPERLINK- No. 1 system
48 cells
Internet Explorer

Additional engineering service cost etc. is required. Please consult your dealer when using this central control.

64 units

HUB Ethernet 10 BASE-T/ 100BASE-TX pulse 48 cells SC-ADN-E

SUPERLINK- No. 2 system


64 units

Watt meter pulse input

P1 P2 P3 P4 (in case of SC-WGWN-B)

Cell

PC requirements: Windows 2000 or Windows XP. Monitor resolution 1024 x 768. Web browser requirements: Internet Explorer 6.0 or later.

<BMS interface unit>


SC-BGWN-A/SC-BGWN-B (BACnet gateway)
(SC-BGWN-B is with electric power calculation function)
SC-BGWN-A/B is an interface device that converts MHIs Superlink- communication data to BACnet code. Control and monitoring functions of the a/c system for up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) can be integrated to a central control point via the building management system network.
SUPERLINK- No. 1 system 48 cells Ethernet 10 BASE-T/100BASE-TX BACnet I/P Protocol. 64 units

Production by order

Network for lighting Emergency sensor network


pulse

48 cells SC-ADN-E

SUPERLINK- No. 2 system 64 units

Cell

Watt meter pulse input

P1 P2 P3 P4 (in case of SC-BGWN-B)

Additional engineering service cost etc. is required. In case of SC-BGWN-B, communication test by qualified person regarding electric cost calculation function is required before commissioning. Please consult your dealer when using this gateway.

SC-LGWN-A (LonWorks gateway)


SUPERLINK- No. 1 system 48 units

Production by order

SC-LGWN-A is an interface device that converts MHIs Superlink- communication data to LonWorks code. Control and monitoring functions of the a/c system for up to 96 indoor units can be integrated to a central control point via the building management system network.

SUPERLINK- No. 2 system LonWorks network (FTT-10) Network for lighting SC-ADN-E 48 units

Emergency sensor network

Additional engineering service cost etc. is required. Please consult your dealer when using this gateway.

62

KX6 Service/maintenance and monitoring


The design of the outdoor units separates the air flow compartment from the mechanical compartment, allowing easy access to serviceable parts by simply removing the panel. This design also means that the base plate of the air flow compartment acts as a drain tray connected to a drain pipe that runs through the mechanical compartment, so a simple connection of a drain hose to the base of the unit is all that is required, no need for a separate drain tray to be installed. Service maintenance and trouble shooting tasks can be carried out easily via the wired remote controller, as well as a cooling test operation to assist commissioning. The outdoor unit control box is also equipped with a switch to invoke a 'test-run' mode. This function can be used to help detect any installation errors, indoor/outdoor unit matching errors, EEV and valve operation. A 'pump-down' switch on the PCB allows refrigerant to be recovered with the compressor protected. All outdoor unit PCBs are also equipped with a 7-segment digital display for detailed operation history and fault finding. Operation data is stored for the 30 minute period preceding a fault occurring and details are displayed on the 7-segment reading.
Air flow chamber

Mechanical chamber

Outdoor unit PCB 7-segment display

Automatically produced test-run report


6

Operation data storage during servicing

Operation data storage when a fault occurs

Method of connecting Mente PC in the combination Multi system

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

63

KX4
4")

KX4 Outdoor units Heat pump systems 8, 10, 12hp (22.4kW~33.5kW)


Model No. FDCA224HKXE4D FDCA280HKXE4D FDCA335HKXE4D Nominal Cooling Capacity 22.4kW 28.0kW 33.5kW

Production by order Superlink models (not Superlink- models) The KX4 heat pump 2-pipe systems offer high performance VRF
for applications that require either cooling only or heating only.

Uniform footprint of all models allows continuous side-by-side installation

Connect up to 20 indoor units/up to 130% capacity. High efficiency with COP (in cooling) from 3.6 to 3.9.

Total length: 510m


To the first branch: max 130m

Outdoor unit Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m
-10

Range of operation
50

Indoor unit

+43C
40

Air

discharge duct

From the first branch to the furthest indoor unit: 40m Furthest indoor unit: 160m

Indoor unit

30

Cooling
20

+15.5C

*Up to 50 Pa outside inside

10

Indoor unit

-5C

Heating
louvre

Air
outdoor unit

-20

-20C

In case an outdoor unit is installed inside the building and outdoor exhaust air is discharged to outside the building through duct system, these units have necessary minimum external static pressure (50Pa).

Specifications
Item Nominal horse power Power source Nominal capacity Model

FDCA224HKXE4D
8HP 22.4 25.0 5.70 5.98 9.6-8.8 9.6-8.8

FDCA280HKXE4D
10HP 3 Phase 380V-415V, 50Hz 28.0 31.5 5 8.26 8.06 13.6-12.4 13.3-12.4 1690x1350x720 245 11.5 57/58 9.52(3/8") 22.22(7/8") 20~114 16

FDCA335HKXE4D
12HP 33.5 37.5 9.53 9.84 15.5-14.2 16.3-14.9

Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Operating Cooling A current Heating HxWxD Exterior dimensions mm Net weight kg R410A kg Refrigerant charge Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity control Number of connectable indoor units

57/57 19.05(3/4") 27~126 13

60.5/61 12.7(1/2") 19~117 20

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

64

Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185

Rear

C 594 232
Anchor bolt positions for I

Anchor bolt positions for F, J

296.7 140 240 295 22 174 720

K B

58.5

19

Dimensions of refrigerant pipe connection (plan)

F I

I F

726

647

85

57

95 140.5

141

75 142.5 234

58.5

19

Air intake

G
148 410 352 158 530 342 235

1690 797.8

126.2

720

1350

Drain pipe 175

7-segment display inspection port 682 Signal wire terminal block Terminal block for power cable connection

K B A C (front)
166 169 211 259 291.6

120

22

80.5 71

C (right)

C (rear)

L
44.7

84

D (left)

104.9

95

90

D (right)

86.5 220 180 550 180 214

D (front)

Mark A B C D F G H K* L

Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.

Intake

Installation example
Dimensions

L2

L3

Wall height H3 L4

1 500 10 100 10 1500

2 Open 200 300 Open

Intake
Wall height H2

Intake
Wall height H4 Wall height H1

88 50 M10 x 4 places 45 x 3 places 20 x 6 places 3/8" flare 180 x 44.7

L1 L2 L3 L4 H1 H2 H3 H4

Service space

Intake

Installation space 2m overhead clearance required

No restrictions No restrictions 1000 No restrictions No restrictions

*14 + 16HP models only

Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation.

When more than one unit is installed


Wall height H3

Installation example
Dimensions

A 500 10 100 10 0 0 1500

L1

20

Instruction plate

6 86.1

172

172

80

B Open 200 300 Open 400 400 No restrictions

L3
Wall height H2 Wall height H4

L1
L6 L4

L2

L5

L2 L3 L4 L5 L6 H1 H2 H3 H4

L1 (Unit front side)


Wall height H2

No restrictions No restrictions 1000 No restrictions

No restrictions No restrictions

65

4")

Mitsubishi Heavy Industries KX6/further information


Mitsubishi Heavy Industries operates a continuous CSR (Corporate Social Responsibility) policy, with a role to realise a sustainable society through its various areas of business.

Creed
We strongly believe that the customer comes first and that we are obliged to be an innovative partner to society. We base our activities on honesty, harmony, and a clear distinction between public and private life. We shall strive for innovative management and technological development from an international perspective.

Reason for Instituting the Creed


In Japan there are many enterprises with their own creeds which simply represent their management concept. Mitsubishi Heavy Industries, Ltd. has a creed of this type, also. It was instituted in 1970 on the basis of the policy advocated by Koyata Iwasaki, president of Mitsubishi Goshi Kaisha in the 1920s, to indicate the essential attitude of the company, the mental attitude of the employees, and the future directions of the company. The reason for instituting the present creed is so that all of us can call to mind our one hundred years of tradition, and strive for further development in the future.
Issued 1 June 1970
Contribution to Society through Company Business Environment, Human Rights and Labour

MHIs creed was established based on The Three Corporate Principles shared by the Mitsubishi Group from the companys beginnings. In the spirit of this creed, MHI continues its efforts to fulfil its three corporate social responsibilities (CSRs): corporate governance and compliance, the environment, human rights and labour, and contribution to society through business activities.

Corporate Governance and Compliance

Contribution to Society through Company Business


Power & Energy Transportation & Security

MISSION
Supply all areas of the world with highly efficient, clean energy

MISSION
VISION
MHI, a premier global organization.
MHI is a global enterprise with a vision for sustainable growth, living up to the trust of customers with outstanding technology, and helping people worldwide lead safe and fulfilling lives. A company with expertise in all modes of transportation, from land and sea to air and space, and in the defence sector

Environment & Society

Industries

MISSION
Help people lead fulfilled lives

MISSION
Support manufacturing activities worldwide

66

The KX6 product range has been developed in compliance with the Mitsubishi Heavy Industries Policy on the Environment.

In order to make the sustainable development of society possible, a basic policy on environmental matters has been established.
Pursuant to the express provision of Section 1 of its creed that We strongly believe that customers come first and that we are obligated to be an innovative partner to society, MHI shall, as a matter of primary importance, strive, through its R&D, manufacturing and other business activities, to play a useful role in the development of society. To this end, while remaining aware that a business enterprise is a member of society, MHI shall endeavour, in all aspects of its business activities, to reduce the burden on the environment and shall concentrate and fully utilise its technological capabilities for the development of technologies and products that will protect the environment, thus contributing to the establishment of a society in which sustainable development is possible.

In order to realise its basic policy, MHI has set the following seven conduct guidelines.
1. Recognise that environmental protection is top priority in the companys operations, and encourage the entire company in its endeavours to protect and improve the environment. 2. Define roles and responsibilities regarding environmental protection by developing and maintaining a corporate organisation designated for environmental protection, and create and implement corporate policies and procedures on environmental matters. 3. Endeavour to reduce the burden on the environment by preventing pollution, saving resources, saving energy, reducing waste, reusing materials, and recycling in all aspects of the companys business activities in R&D, designing, procurement of materials, manufacturing, transportation, use, service and disposal. 4. Endeavour to develop and provide advanced, highly reliable, unique technologies and products that contribute to solving environmental and energy problems. 5. Comply with national and local environmental laws and regulations, beyond mere compliance by enacting, implementing and evaluating voluntary standards where necessary, and to endeavour to continuously improve and promote environmental protection activities by establishing environmental goals and targets. 6. Endeavour to protect the environments of foreign countries by carefully examining the consequences of the companys overseas business operations and the exportation of its products, and to become actively involved in technological co-operation overseas in areas of environmental protection. 7. Provide environmental training and other programs to enhance the environmental awareness of all company employees, and take steps to expand public relations activities, such as providing environment-related information to the public and social contribution activities.

Number of offices/plants and employees by region (Consolidated) as of June, 2008

Europe
Major subsidiaries 13

Russia
Overseas offices & representatives 1

North, Central & South America Japan


Head office & domestic offices 9 6 9 129 Research & development centres Works 7 39 Major domestic subsidiaries Major subsidiaries 24

Asia
Overseas offices & representatives Major subsidiaries

Oceania
Major subsidiaries 1

67

global activity
On the land and sea, in the sky and even in space, MHIs stage of operations is expanding limitlessly. We manufacture more than 700 different products which support various industrial and civil activities in both domestic and international markets. Ships, steel structures, power systems, machinery for both industrial and general use, air-conditioners, pollution reduction and environmental control systems, aerospace systems the MHI product lines which create rich and comfortable living environments, are as harmonious as an orchestra. What creates this harmony is MHIs general technological expertise developed over more than a century of hard work. We are highly esteemed in the world for providing high quality products through untiring technological research and development. From new energy development and environmental concerns to the exploration of space, with the advent of the 21st century MHI is confronting a variety of issues to ensure the realisation of a society in which there is harmony between mankind and technology.

Ultra-High Steel Stacks Refuse Incineration Plants Night Soil Treatment Plants Electrostatic Precipitators Flue Gas Desulfurization System Fluidized Incinerators CFC Collecting Equipment

Crude Oil Storage Barges LNG Tanks Boilers & Turbines Oil Production Plants Contra-Rotating Propellers Thermal Power Plants Combined Cycle Plants Fuel Cells Water Turbines Wind Turbines Geothermal Power Plants PWR Nuclear Power Plants Uranium Enrichment Equipment FBRs Co-Generation Systems

Spillway Radial Gates Steel Bridges Penstocks Desalination Plants Physical Distribution Equipment Engines

RESO

C LO

S URCE

Unloader & Container Cranes Mechanical Parking Facilities Integrated Automated Storage Systems Rubber & Tyre Machinery Skyrails Monorail Cars New Transportation Systems Passenger Boarding Bridges

Toll Collection Machine Systems Forklift Trucks Helicopters Aircraft Railway Maintenance Equipment LNG Carrier Container Ships

AL

V EN

TR

AN

VE DE P LO
TA TIO

SP

IRO

/ENER

OR

NM EN

M T EN
N

GY

68

Chemical Plants Wind Tunnel/Experiment Equipment Casting Machines Strip Mill Cement Plant Stepless Variable Speed Gears Industrial Robots Injection Moulding Machines Pulp & Paper Machinery Corrugation Machines Box Making Machines Machine Tools

Ceiling Recess Packaged Air Conditioners Automotive Air Conditioners Residential Use Split Air Conditioners Refrigeration Units Dry Cleaning Machines Food Machinery Cruise Ships Multi-purpose Dome Stage Machinery Systems

Cable Layer Printing Machinery

Oceanographic Research Ships Deep Submergence Research Vehicles Communications Satellite Rockets Space Transportation Rockets & Engines

YLE

EST

ST

EM

INDUS T

IN FO RM

SU RE

V DE

LEI

EL

E PM

AT

NT

N EFE

CE

Submarines Naval Vessels Jet Fighters Helicopters Missiles Tanks & Infantry Fighting Vehicles

RIAL

/LIF

IO

SY

69

Before starting use


Heating performance
The heating performance values (kW) described in catalog are the values obtained by operating at an outdoor temperature of 7 C and indoor temperature of 20 C as set forth in the ISO Standards. As the heating performance decreases as the outdoor temperature drops, if the outdoor temperature is too low and the heating performance is insufficient, use other heating appliances as well.

Refrigerant leakage
The refrigerant (R410A) used for Air conditioner is non-toxic and inflammable in its original state. However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.

Indication of sound values


The sound values are the values (A scale) measured in a chamber such as an anechoic chamber following the ISO Standards. In the actual installation state, the value is normally larger than the values given in the catalog due to the effect of surrounding noise and echo. Take this into consideration when installing.

Use in snowy areas


Take the following measures when installing the outdoor unit in snowy areas.

Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake port or enter and freeze in the outdoor unit.

Use in oil atmosphere


Avoid installing this unit in as atmosphere where oil scatters or builds up, such as in a kitchen or machine factory. If the oil adheres to the heat exchanger, the heat exchanging performance will drop, mist may be generated, and the synthetic resin parts may deform and break.

Snow piling
In areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.

Automatic defrosting device


If the temperature is low, and the humidity is high, frost will stick to the heat exchanger of the outdoor unit. If use is continued, the heating performance will drop. The "Automatic defrosting device" will function to remove this frost. After heating for approx, three to ten minutes, it will stop, and the frost will be removed. After defrosting, hot air will be blown again.

Use in acidic or alkaline atmosphere


If this unit is used in acidic atmosphere such as hot spring areas having high level of sulfuric gases or in alkaline atmosphere including ammonia or calcium chloride, places where the exhaust of the heat exchanger is sucked in, or at coastal areas where the unit is subject to salt breezes, the outer plate or heat exchanger, etc., will corrode. Please ask a dealer or specialist when you use an air conditioner in places differing from a general atmosphere.

Servicing the air-conditioner


After the air-conditioner is used for several seasons, dirt will build up in the air-conditioner causing the performance to drop. In addition to regular servicing, we recommend the maintenance contract (charged for) by a specialist.

Use in places with high ceilings


If the ceiling is high, install a circulator to improve the heat and air flow distribution when heating.

Safety Precautions
Air-conditioner usage target
The air-conditioner described in this catalog is a dedicated cooling/heating device for human use. Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc. This could cause the quality of the items to drop, etc. Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur.

Installation
Always commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires. Make sure that the outdoor unit is stable in installation. Fix the unit to stable base.

Usage place
Do not install in places where combustible gas could leak or where there are sparks. Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.

Before use

, Always read the "User s Manual" thoroughly before starting use.

Japan Head Office:


Mitsubishi Heavy Industries Ltd 16-5 2-Chome Kounan Minato-ku Tokyo 108-8215, Japan www.mhi.co.jp Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001 Certified ISO 14001

ISO 14001

Certificate 04104 1998 0813 E5 BIWAJIMA PLANT


Mitsubishi Heavy Industries, Ltd. Air-conditioning & Refrigeration Systems Headquarters

MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO., LTD.

Mitsubishi Heavy Industries-Haier (Quingdao) Air-conditioners Co.,Ltd.

BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd. Air-conditioning & Refrigeration Systems Headquarters

MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO.,LTD.

Mitsubishi Heavy Industries-Haier (Quingdao) Air-conditioners Co.,Ltd.

HB91-09KX01E-A-0

December 2008(2B)R

Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.