12 MGDP I 1045 0 (Spec For WHCP)
12 MGDP I 1045 0 (Spec For WHCP)
12 MGDP I 1045 0 (Spec For WHCP)
20298-00-EJ12-101
Project Title
TABLE OF CONTENTS
1.0 INTRODUCTION ................................................................................................... 4
1.1 General............................................................................................................................................ 4
1.2 Scope............................................................................................................................................... 4
1.3 Definitions....................................................................................................................................... 4
1.4 Abbreviations ................................................................................................................................. 5
1.5 Environmental Conditions ............................................................................................................ 5
2.0 CODES AND STANDARDS ................................................................................. 7
3.0 SCOPE OF SUPPLY............................................................................................. 8
4.0 FUNCTIONAL REQUIREMENTS ......................................................................... 8
4.1 General............................................................................................................................................ 8
4.2 Operating Philosophy.................................................................................................................... 8
4.3 Opening / Closing Times ............................................................................................................... 9
4.4 Opening and Closing Sequence................................................................................................... 9
4.5 Interlock, Shutdown & Override Requirements ........................................................................ 10
4.6 Choke Valve Operation................................................................................................................ 11
4.7 Indications & Controls................................................................................................................. 11
5.0 DESIGN & CONSTRUCTION ............................................................................. 13
5.1 Panel Construction ...................................................................................................................... 13
5.2 Hydraulic System ......................................................................................................................... 15
5.3 Main Reservoir ............................................................................................................................. 16
5.4 Hydraulic Pumps.......................................................................................................................... 17
5.5 Accumulators ...............................................................................................................................18
5.6 SCSSV Return Tank / Hydraulic Quick Exhaust ....................................................................... 19
5.7 Hydraulic Components................................................................................................................ 19
5.8 Instruments & Electrical Components....................................................................................... 20
5.9 Junction Boxes ............................................................................................................................ 21
5.10 Power Supply ...............................................................................................................................22
5.11 Nameplates & Labeling................................................................................................................ 23
6.0 INSPECTION & TESTING .................................................................................. 23
7.0 INSTALLATION, PRE-COMMISSIONING AND COMMISSIONING .................. 24
8.0 DOCUMENTATION............................................................................................. 24
9.0 QUALITY ASSURANCE / QUALITY CONTROL................................................ 25
10.0 SPARE PARTS & SPECIAL TOOLS.................................................................. 25
VECO Doc. No. 20298-00-EJ12-101
Project Title
1.0 INTRODUCTION
1.1 General
PETRONAS CARIGALI (Pakistan) Ltd. (PCPL) is undertaking the development of Mehar
Gas Field in Mehar Block (Block 2767-1) located in Sindh and Balochistan Provinces of
Pakistan.
Mehar Block is located in the Kirthar Fold belt area, in the Middle Indus Basin. Mehar
field is located about 190 km west of Sukkur and 400 km north of Karachi in Sindh
province (distances by road). The environment is arid and the terrain is mountainous.
Mazarani gas field, operated by PPL is situated about 25 km to the north, while
Zamzama gas field operated by BHP is situated about 70 km to the north of Mehar Field.
Mehar field consists of Pab and Ranikot formations. The wells will be connected to the
new GPF through a Gathering System. There will be a total of 6 wells (3 Wells from the
North and 3 Wells from the South). 3 Wells will be producing in Phase-1 and 3 Wells in
Phase-2 (future). ME-1 well is from PAB reservoir. ME-2 wells is from Ranikot reservoir.
Wells, ME-3, ME-4, ME-5 and ME-6 are dual completion.
PCPL intends to develop the Mehar Field by installing a Gathering System, Gas
Processing Facility (GPF) and Product Storage & Loading Facilities. The field facilities
will be developed in two phases, Phase-I and Phase-2.
Phase-1 development will cater for 55 MMSCFD of gas production and Phase-2 will
cater to 80 MMSCFD of gas production. The expected condensate production rate is
6600 BPD in Phase-I increasing to 7000 BPD in Phase-2.
1.2 Scope
This specification covers the basic minimum requirements for the Wellhead Hydraulic
Control Panel for the Mehar Gas development project.
1.3 Definitions
1.4 Abbreviations
HP High Pressure
LP Low Pressure
MP Medium Pressure
Wellhead facilities, Gathering stations and Gas Processing Facility (GPF) area has been
tentatively selected at a location about 190 km west of Sukkur and 300 km north of
Karachi in Sindh Province. The environment is arid the terrain is mountain.
Elevation Above Mean Sea Level (GPF) : 54m (Site-IV) / 56m (Site-l)
Codes, specifications and standards referred to within this specification, form a part of
the requirements of this specification in a manner and to the extent specified within
those codes and standards.
Unless otherwise specified, the latest edition or revision to these codes specifications,
and standards in force at the time of request for quotation and/or Purchase Order shall
apply.
No deviations from the Codes and Standards listed in this document will be allowed
unless such deviations are clearly identified in the bids, with the reasoning. In addition,
they must be approved in writing by COMPANY.
Where only British standards are quoted, other internationally acceptable codes and
standards may be put forward in lieu for COMPANY approval. All the applicable codes
and standards shall be of the latest edition at the time of order.
Each well head hydraulic control panel package shall include the following as a
minimum:
• Well head hydraulic control panel including all required power, indications,
controls, and protections as detailed in the subsequent sections of this
specification;
• Controller / PLC to incorporate WHCP logic, for design and specification of PLC
PCPL document no. 12-MGDP-I-1046 shall be referred;
• Four (4) field mounted Low-Pressure fusible Plugs through separate headers
• All other tools/accessories that are not specifically mentioned, but are required to
deliver a fully operational system.
4.1 General
Proposed well head facilities are shown on P&ID drawings and the layout drawings
developed for this project. WHCP will provide for actuation of the following:
• SCSSV;
• SSV-Master Valve.
The operation of Xmas tree valves shall be by hydraulic power supply. These valves
shall be controlled through electrical solenoid valves installed in the WHCP. WHCP
shall be provided with SIL2 PLC.
VECO Doc. No. 20298-00-EJ12-101
Project Title
Panel shall have in-service / wire line diverter valve and provision for connection of wire
line unit, to operate each of these valves.
The overall well shutdown time is within 45 seconds from the activation of the trip device.
Each hydraulic supply line to these valves shall include throttling valves for adjusting the
actuation time. VENDOR shall provide provision to adjust opening / closing time from
panel.
The actuator shall be spring to close type. Typical actuator volume is 1500cc (HOLD).
The control system shall be designed by the VENDOR to comply with the timing
indicated above.
Opening sequence shall be LOCAL MANUAL only (by initiation of panel push buttons).
Valves shall open in the following sequence with adjustable time delays:
VECO Doc. No. 20298-00-EJ12-101
Project Title
It shall not be possible to open valve when the respective ESD situation is not healthy.
Closing sequence for total well shutdown shall be automatic in the following order with
adjustable time delay:
• Hydraulic operated SSV-Master valve (typically after 30 sec of wing valve closing)
A facility shall be provided to allow “out of sequence closing & opening” of the SSV and
SCSSV and shall be tagged Rigless Operation ON/OFF. When selected ON, the valve
shall be able to operate from the Wellhead hydraulic control panel only. This shall
incorporate a key locked mechanical local command override to prevent remote
operation of the SCSSV and SSV during wireline operation. This override shall prevent
any remote operation (i.e. well ESD) in order to avoid cutting of wireline. The key locked
wireline overrides shall be provided with a proximity switch and wired to RTU interface
junction boxes to indicate the override position. A common alarm will be sent to PMCS
from RTU. The following only shall be capable of overriding the wire–line lockout.
VECO Doc. No. 20298-00-EJ12-101
Project Title
• Fire at wellhead.
In addition to ESD push button on the panel, three (3) ESD push button stations shall be
installed at main gate, Xmas tree and launcher. The hand stations shall be supplied by
VENDOR & mounted on stand pipe by CONTRACTOR.
Panel shall control wellhead choke valve using stepping action. For this hydraulic oil
distribution to the choke valve shall be provided. Pulsed output signal from RTU shall be
interfaced with the panel. The choke valve shall also be able to be controlled remote
from PMCS console by pulsed signal. This pulsed signal shall control the stepping
function with sufficient dwell time between each step to ensure full cylinder retraction.
Choke Valve position indicator (a 4-20 mA position feedback) shall be interfaced with the
hydraulic panel. Choke valve position shall also be interfaced with RTU. Hydraulic
supply pressure to choke valve shall meet the choke valve actuator output torque
requirement.
Panel shall control SCSSV and SSV-Master valve. Panel shall control the 2 valves, with
normally pressurized hydraulic signals through hydraulic tubing. The regulator knob for
all pressure regulators shall be located on the faceplate of the Panel.
Following parameters shall be indicated locally on the panel front, using local gauges (as
a minimum):
• Hydraulic Pump A discharge pressure;
• Hydraulic Pump B discharge Pressure;
• HP Hydraulic Header Pressure (HP);
• MP Hydraulic Header Pressure (MP);
• LP Hydraulic Header Pressure (LP);
• Fusible Plugs Loop Pressure;
• Hydraulic Pressure to SCSSV;
• Hydraulic Pressure to SSV-Master valve;
• Hydraulic Pressure to SSV-Wing valve;
• Main Hydraulic Reservoir Level;
VECO Doc. No. 20298-00-EJ12-101
Project Title
Following electric devices shall be installed on the panel front for local control, as a
minimum. These signals shall be wired to RTU interface junction boxes:
• OPEN & CLOSE Pushbuttons, one set each for SCSSV & SSV;
• Start & Stop push button, one set each for Hydraulic Pumps A & B;
• ESD pushbutton;
• Lamp for ESD station activation with reset PB;
• Local / Remote selector switch to allow remote operation from the RTU panel;
• Override Switch, one each for SCSSV and SSV (for in-service / wire line
diverter valve);
• OPEN and CLOSE indication for SCSSV (by monitoring the hydraulic control line
using a pressure transmitter);
a. The panel shall be complete with isolation valves, relief valves, check valves,
hydraulic control valves, pilot valves, lubricators, filters, pumps, pressure
regulators, ESD push buttons, tubing, fittings, pressure gauges, etc as required for
smooth trouble free and safe operation of the well.
b. Panel shall have SS316L cabinet weatherproof to IP-65 as a minimum with front &
rear access doors. Panel may be of welded construction with proper considerations
for the environment corrosion where it is to be installed.
c. Panel shall be suitable for Area Classification Zone 2 Gr IIA / IIB, T3 and
approved.
e. Panel shall be provided with a perplex glass window on the front. All the doors and
windows shall be provided with mechanical door stoppers, pad-lockable handle
arrangement with three-point locking mechanism as a minimum. Door shall have
pocket for holding drawings. The panel rear door shall be designed with allowable
clearance 700 mm at the back of the opening.
f. Imperial tube sizes and double compression ferrule fittings with NPT threads in
316L SS shall be used for all panel tube work. Liquid sealant shall be applied to all
VECO Doc. No. 20298-00-EJ12-101
Project Title
g. All tubing, fittings and other components shall be designed for pressure rating of
10,000 psi;
h. The base of the panel shall be fitted with an enclosed drip tray to collect any
spillage of oil. The tray shall be sloped and fitted with 1”, ANSI 150#, RF flange
connection to facilitate draining from one corner.
i. The panels shall have proper lighting arrangement and auxiliary power socket. The
supply voltage for auxiliary socket shall be 24 VDC.
j. A rain canopy shall be provided over the panel for access under adverse weather
conditions. A sunshade shall be provided such that the panel is shaded for most of
the day. Canopy shall have a minimum extension of 18” from the panel edge to
provide shade to the operator.
k. Panel shall be provided with adequate corner supporting legs of 250 mm height,
suitable for installation and bolting on concrete foundation.
l. Lifting “Pad Eyes” fabricated of 316 SS, shall be provided at the ends of the panel.
Each pad eye shall be capable of lifting the entire weight of the fully assembled
panel. Special lifting arrangement if any shall be foreseen by the VENDOR and
provided accordingly.
m. A minimum of two numbers of external earthing bosses shall be provided for the
panel.
o. Well head hydraulic control panel and all field mounted equipment shall be painted
suitable to environment condition.
p. Panel, junction boxes and hydraulic reservoir shall be painted suitable for the
environmental conditions.
q. Each hydraulic line on the bulkhead shall have isolation valve accessible from
outside. All the bulkheads shall be tagged.
r. Components inside the panel shall be suitable for the continuous operating
temperature that may arise due to heat generated within and also ambient
conditions.
s. Panel shall have an inside lamp suitable for hazardous area. It shall not be
interlocked with the door switch; instead manual switch shall be provided.
VECO Doc. No. 20298-00-EJ12-101
Project Title
• Hydraulic accumulators;
b. Hydraulic system shall be designed to provide power for the SCSSV and for SSV-
Master. VENDOR shall provide details of hydraulic thrust required for SCSSV &
SSV according to well shut in pressure i.e. 370 barg (5400 Psig). A pressure
reducing valve shall supply the lower pressure system from the pump discharge
and shall be protected by a relief valve;
• Operation of SCSSV;
e. Each hydraulic output line (SCSSV and SSV) shall be provided with pressure
regulator and pressure relief valve;
f. Four (4) low-pressure fusible plugs shall be installed around well head. Fusible
plugs shall have a melting point of 255°F;
g. Each hydraulic supply line to two (2) valves and fusible plugs shall have its own
pressure regulator, knob of which shall be located on the faceplate of the panel
front. Vendor shall also provide adjustable regulation range;
h. All regulators shall have auto drain (bleeding) facility and drain line shall be routed
back to the hydraulic reservoir;
VECO Doc. No. 20298-00-EJ12-101
Project Title
i. There shall be a “in sequence and out of sequence” switch on the panel. Logic
shall be such that, in out-of-sequence mode only panel ESD push button shall be
active bypassing all other ESD;
j. Panel shall also have well start & stop push button. This push button will operate
the logic in sequence when “Local-Remote” switch is in “Local” position;
k. All three (3) valves shall have open/close indication lamps on the panel front;
l. Hydraulic system startup from zero pressure to operating pressure shall be within
10 minutes. Pump capacity shall be selected based on this;
m. Accessibility of the components inside the panel is very important and vendor shall
ensure that good accessibility for maintenance and operations;
n. The type of hydraulic fluid will be decided later. All WHCP hydraulic components
and tubing shall be suitable for the service. VENDOR shall include for the supply of
the first fill quantity of hydraulic oil in suitable containers for transportation to the
construction site. VENDOR shall supervise the partial filling of the system, with
sufficient hydraulic fluid retained in secure containers for shipping with the modules
for replenishment of the system following the hook-up of the wells.
a. The main hydraulic reservoir shall have a capacity of 100 liters, minimum.
VENDOR shall calculate and design adequate capacity of the main reservoir,
based on the actual swept volume of the valves actuators and the requirements of
operation. The VENDOR is solely responsible for co-ordination with the
CONTRACTOR for obtaining actual actuator swept volumes for all valves;
b. The main reservoir shall be fabricated from AISI 316 SS and shall be equipped
with the following:
VECO Doc. No. 20298-00-EJ12-101
Project Title
• Magnetic plug located in the base of the reservoir to trap iron and steel
particles;
c. The level transmitter shall be D/P type. The level transmitter body, internal and
enclosure shall be in 316 SS. Level gauges shall be fitted with automatic and
manual shut-off valves to prevent loss of fluid due to accidental gauge glass
breakage. Also it should be possible to change the gauge glass without draining
the reservoir;
d. The main reservoir shall be engraved or labeled with the following level marks
adjacent to the level gauges:
e. The LSH, LSL and LSLL shall be set accordingly in RTU logic, for alarming and
interlock functions. The low-level switch shall be activated (set point) when the
level is approximately 100 mm above the section line. Switch functions shall be
derived from transmitter;
f. The MP return lines from the Xmas tree quick opening valves shall have ¾”
connections and are piped with ¾” OD tube to the main reservoir;
g. Hydraulic reservoir shall have filling, drain and level gauge located outside the
panel;
h. Breather vent of the hydraulic reservoir shall be extended outside away from the
panel and shall not be kept below the canopy.
• The hydraulic pump shall operate automatically. The pump run / stop status shall
be made available to RTU. Running hours of each pump shall also be recorded.
• Hydraulic Hand Pump shall be used to manually pump up the hydraulic system to
put the safety in service. This hand pump shall be used to re-open the valve
following a trip.
• It should be possible to isolate, reset, repair and test each pump independently.
Hydraulic pump suction pipe work shall have an OD of 10 mm, minimum.
5.5 Accumulators
The accumulator size shall be optimized to act as a buffer and to cater for temperature
variation during day and night.
a. Accumulator shall be designed to ASME section VIII, DIV-1 or BS5500 with the
design pressure identical to the hydraulic pressure circuits and temperature at
149°F. It shall be provided with pressure vessel code stamps;
b. Accumulator shall be bladder type, painted Stainless Steel. It shall be provided with
316 SS isolation valve and shall be mounted in the vertical position, on separate
skid to allow easy handling and maintenance;
c. Each accumulator shall be provided with a pressure gauge to indicate the pre-
charge pressure;
g. Accumulators shall be located outside the panel for easy lifting and charging;
There is a risk of the hydraulic fluid being contaminated by the process fluid, in the
SCSSV circuit. Hence, the fluid from the SCSSV pilot solenoids shall be returned to a
dedicated SCSSV return tank. (The fluid return from the quick dump valve of the
SCSSV, installed at Xmas tree actuator shall be returned to a vent pipe located close to
the Xmas tree).
a. The minimum capacity of the SCSSV return tank shall be 10 liters minimum.
During detailed engineering VENDOR shall calculate exactly the required tank
capacity and design accordingly;
b. This return tank shall be equipped with a level gauge. This tank shall be fitted with
an overflow connection. This tank shall not vent within the control panel, but vent
outside and a flame arrestor shall be installed;
c. Provision shall be made to permit the SCSSV return tank contents to be drained to
the main reservoir after examination for contamination. In an event of
contamination of this return tank, it shall be possible to flush / drain the tank and
tubing for the same with isolation valve shall be provided, up to the main reservoir.
A tank top mounted duplex filter with visual indication for clogging shall be provided
on the return line to the main reservoir;
e. The hydraulic fluid return from quick-exhaust valve on SSV actuators shall be
individually piped back to the main reservoir on the wellhead panel.
The hydraulic fluid return from quick exhaust valve on SCSSV actuator shall be
terminated near the wellhead and be connected to a 4”x 12’, 316 SS vent pipe with an oil
collection facility. The height of the pipe shall be at least 10 ft above the Xmas tree and
be equipped with flame arrestor. VENDOR shall design the vent pipe and shall supply it
loose for installation by CONTRACTOR
a. The wellhead hydraulic control system shall utilise suitable components, which are
field proven for hydraulic service in identical application. All components shall be of
AISI 316 SS, suitably rated for the service pressure;
b. Pumps, flow control valves, accumulators, solenoid valves, pressure relief valves,
regulators, gauges, transmitters and switches, shall be from client approved Sub-
VENDOR List;
e. All tubing within panel and modules shall be of annealed seamless 316L SS, with
sizes of, ½" and wall thickness 0.083”. Tubing wall thickness shall be suitable for
the maximum hydraulic pressure i.e. PSV setting on the main supply header.
f. All external tubing shall be same as of internal tubing with 2 mm thick UV resistant
PVC coating. All tubes run under-ground shall be single piece and joint free for its
entire length.
g. Tubing size, pilots, quick exhaust valve etc., shall be designed to meet the closing
time for the distance (minimum 246 ft) between the well head hydraulic control
panel & the master/wing/sub-surface safety valves as per the layouts;
h. All tube fittings shall be of SWAGELOK, 316 stainless steel, double ferrule, and
double compression type;
a. All the instruments shall be weatherproof to IP65 as per IEC 60529 and per IEC
60079. For the purpose of standardization following philosophy shall be followed:
b. All transmitters shall be 2 wires, 4~20 mA DC HART transmitters. Body & wetted
parts material shall be 316L SS as a minimum;
c. All the solenoids shall be spring return type. The solenoid valves and pilot valves
shall be of auto reset type. Solenoid coils shall be LOW POWER, high temperature
(class H insulation) moulded and encapsulated type suitable for continuous duty at
rated voltage (24V DC +10, -15%). Solenoids shall have suitably rated suppression
diodes connected across the coil.
Body and enclosure material, shall be 316 SS with suitably sized NPT connections
for tubing and ISO M20 entry for cabling;
d. Solenoid valve must be high-pressure direct acting. Pilot solenoids are not
acceptable;
VECO Doc. No. 20298-00-EJ12-101
Project Title
e. The pressure gauge shall be full safety pattern, incorporating blowout and safety
glass. The casing, wetted parts material shall be SS316L as a minimum;
f. Emergency Stop push buttons shall be stay-put type with RED actuator provided
with a shroud to avoid accidental actuation. It shall comply with requirements of
IEC & EN standards. Normally Closed contact (open on actuation) shall be wired to
the junction box;
g. START / STOP, OPEN / CLOSE push button shall be momentary type. Colour of
the actuator shall be GREEN for START / OPEN and RED for STOP / CLOSE
push button. Normally Open contact (close on actuation) for start and normally
closed contact for stop shall be wired to the junction box for these push buttons;
h. Color of the indicating lamps shall be GREEN for RUN / OPEN status and RED for
TRIP / CLOSE / POWER ON status indication.
j. All supply/installation of interconnecting cables from the power supply input within
the system shall be by VENDOR.
k. Cable glands associated with the internal junction boxes shall be EEx’d’
compression type (inner, outer sheaths & armour clamp) manufactured from brass
with nickel plating. Cable glands shall be supplied in metric (ISO) thread and
complete with PVC shroud/sleeve, earth tag and lock nuts.
a. All signals to / from Wellhead hydraulic control panel to RTU shall be wired to the
junction boxes located at one side of the panel. Junction boxes shall be accessible
from outside the panel. All internal wiring / cabling to these junction boxes shall be
done at factory;
c. Separate junction boxes shall be provided for analog (4~20 mADC) signals, digital
signals (contacts, limit switches, pushbuttons, selector switches), FGS signals and
solenoid valves. If signals are combined in one junction box, signals shall be
segregated based on separate terminal strips;
d. Junction box shall be provided with removable gland plate at the bottom with
proper sealing at the cable entries. Sufficient free space shall be made available
for easy wiring & maintenance;
VECO Doc. No. 20298-00-EJ12-101
Project Title
g. No more than two conductors shall be connected to any one terminal. If more than
two conductors must be terminated at the same point, terminations shall be made
on as many terminals as necessary and terminals interconnected with special
jumpers specially designed for this purpose;
h. All terminals shall be marked i.e. provided with suitable markers for identification.
Terminal markers shall be pre-printed from manufacturer and not hand written;
i. All internal cabling / wiring shall below smoke zero halogen type with suitable cross
section (not less than 0.5 mm2). If stranded copper wire is applied, wire ends at
terminal points shall be provided with suitable type wire crimp pins/lugs and
markers;
j. Colour code and marking of wires shall be as per VENDOR’S standards. All power
wiring shall be clearly marked with reference codes and/or tag numbers with
permanent wire marker;
k. Junction boxes shall be located completely outside the panel without any cutout on
the panel i.e. no portion of junction box shall be inside the panel.
The power supply for the wellhead control panel shall be 24 VDC, -10%, +15%, negative
earthed. This will be fed from the SOLAR array power system, supplied by others.
a. External power supply terminals shall generally be suitable for 2C x 95 mm2 cable
(to be confirmed by VENDOR). VENDOR shall provide separate terminal box to
terminate large size cable.
b. Panel shall be provided with isolators for each individual incoming power feeder.
The isolators shall be installed in the terminal boxes. The terminal boxes shall be
provided with a single switch for isolating the incoming power of both pumps. This
switch shall be accessible externally, without opening the terminal box. The
terminal box shall be supplied with un-drilled plate for cable glands.
c. The power supply to the solenoids shall be 24 VDC and will be provided from the
RTU.
d. VENDOR shall provide detailed power consumption calculation and submit it to the
CONTRACTOR for approval, stating all assumptions made concerning leakage
rates both internal and external to his scope of supply.
VECO Doc. No. 20298-00-EJ12-101
Project Title
e. There are two types of calculations involved. The first one is for the power
consumption of cold start or after a power shutdown. The second is the daily
consumption to account for leakages.
f. Since the solar power generation is critical, it is important that the hydraulic safety
system employs low power consumption design. Hence, due consideration shall be
given to avoid over sizing.
Well head hydraulic control panel and all field mounted equipment shall be tagged with a
stainless steel tag. Nameplate shall be provided under each item on the front and major
components inside the panel.
Nameplate shall be laminated plastic, engraved in English with black lettering on a white
background. Nameplate shall be secured with self-tapping screws or adhesive.
Nameplate size on the panel front shall be uniform and letter height shall be such that
service description can be read from the distance.
The well head hydraulic control panel shall be subjected to inspection by COMPANY. It
is a prior requirement to any final inspection that the drawings/relevant documents be
certified/ approved in advance by COMPANY where appropriate.
The inspection & testing shall be in accordance with the approved “Inspection & test
plan”. It shall cover the following as a minimum.
• Calibration checks.
VECO Doc. No. 20298-00-EJ12-101
Project Title
VENDOR shall conduct integrated FAT (panel & RTU system) for both wells. COMPANY
will witness one of them.
Acceptance of shop test shall not constitute a waiver of requirements to meet this field
test under specified conditions and final guarantee for material design, workmanship and
performance.
Flushing of hydraulic lines from WHCP to well head valves shall be part of VENDOR’S
scope. As the RTU is being supplied by others, Integrated Testing at site (100%
functional testing) shall be part of VENDOR’S scope.
8.0 DOCUMENTATION
• Project Schedule;
• Bill of material, specifications, data sheets & catalogs for all the components;
• Final Dossier;
Vendor proposed quality system shall fully satisfy ISO 9001/2000 QMS Requirements.
The VENDOR and the Sub-vendors shall be ISO certified. VENDOR shall provide a
specific Quality Plan (QP) within 2 weeks of order award for COMPANY review and
approval. VENDOR shall provide the following to COMPANY for approval:
• The source of material supply for all parts and components including the country
of origin and place of manufacturing, assembly and testing;
• Sub-vendors and contractors list and these shall be from COMPANY approved
list.
VENDOR shall include with the bid the recommended spare parts for start-up,
commissioning and two (2) years of operation.
VENDOR shall also provide special tools and tackles, if any, for operation and
maintenance of the WHCP.
VECO Doc. No. 20298-00-EJ12-101
Project Title
Vendor shall provide additional equipment, if any, to boost the pressure available from
nitrogen cylinders, which is in the range of 2000-3000 psig (VENDOR to confirm the
requirment).
11.0 GUARANTEE
The VENDOR shall ensure that the material and accessories provided is his standard
product regularly manufactured, tested and serviced in accordance with the Codes and
Standards, defined in this document.
Any material or part thereof covered by this specification that shows evidence of
deterioration, contamination or corrosion within the guarantee period shall be considered
the result of failure to comply with the requirements and the intent of this specification
and shall be replaced on site at no extra cost to the Owner.