Burner Data Sheet
Burner Data Sheet
Burner Data Sheet
OPTIMIZED
PROCESS
FURNACES, INC.
3995 S. SANTA FE / BOX 706
CHANUTE, KS 66720-0706
PHONE (620) 431-1260
FAX (620) 431-6631
REV. DATE
0 1/14/05
ZEECO BURNER DATA SHEETS
Revision Table
Rev # Issue Description of Revision Rev Date Name
Confidential Property of Zeeco. To be returned upon request and used only in reference to contracts
or proposal of this company. Reproduction of this print or unauthorized use of this Document is prohibited.
04910-7 SO14619
• Burners Optimized Process Furnaces, Inc. TBA
• Flares BP Columbia Vertical Cylindrical
• Incinerators Colombia Rev. 0
• Combustion Systems Raw Gas, Conventional Emissions SHEET 1 OF 5
ZEECO BURNER DATA SHEETS
Rev. Rev.
GENERAL INFORMATION
Customer Name Optimized Process Furnaces, Inc.
End User Name BP Columbia
Jobsite Colombia
FURNACE DATA / SITE CONDITIONS
Furnace Tag Number TBA Plant Site Elevation Above Sea Level, ft 1352
Type of Furnace Vertical Cylindrical Ambient Air Temperature (°F) 70
Refractory Thickness, in 8 Minimum Relative Humidity 0%
Heater Steel Thickness, in 0.25 Normal Relative Humidity 50%
Type of Draft Natural Maximum Relative Humidity 100%
Direction of Firing Vertical, Up Heater Height (to convective sec.), ft 56.0
Mounting Direction Vertical, Up Tube Circle Diameter (ft) 24.8
Heater Length, ft 0.0
PROCESS DATA Gas
Maximum Heat Release (MM BTU/hr) 17.500 Available Combustion Air dP (in H2O) 0.660
Normal Heat Release (MM BTU/hr) 14.000 Combustion Air Temperature (°F) 70
Minimum Heat Release (MM BTU/hr) 3.500 Furnace Temperature (°F) 1575
Turndown 5.00 Combustion Test Required
Available Fuel Pressure (psig) 25
Design Excess Air 15%
Confidential Property of Zeeco. To be returned upon request and used only in reference to contracts
or proposal of this company. Reproduction of this print or unauthorized use of this Document is prohibited.
04910-7 SO14619
• Burners Optimized Process Furnaces, Inc. TBA
• Flares BP Columbia Vertical Cylindrical
• Incinerators Colombia Rev. 0
• Combustion Systems Raw Gas, Conventional Emissions SHEET 2 OF 5
ZEECO BURNER DATA SHEETS
.
FUEL GAS CHARACTERISTICS OFF GAS CHARACTERISTICS
LHV (BTU/lb)
S.G. @ 60°F
TEMP (°F)
API GRAVITY @ 60°F
NITROGEN (wt%)
VANADIUM (PPM)
SULFUR (wt%)
CATALYST PRESENT
GENERAL OIL TYPE
Confidential Property of Zeeco. To be returned upon request and used only in reference to contracts
or proposal of this company. Reproduction of this print or unauthorized use of this Document is prohibited.
04910-7 SO14619
• Burners Optimized Process Furnaces, Inc. TBA
• Flares BP Columbia Vertical Cylindrical
• Incinerators Colombia Rev. 0
• Combustion Systems Raw Gas, Conventional Emissions SHEET 3 OF 5
ZEECO BURNER DATA SHEETS
EMISSIONS COMMENTS
4-1 The above listed UHC emissions are based upon UHC being defined as free "methane" as the result of incomplete combustion due
to the supplied combustion equipment as stated in these data sheets.
4-2 The above listed VOC emissions are based upon VOC being defined as free "propane" as the result of incomplete combustion due to
the supplied combustion equipment as stated in these data sheets.
4-3 The above listed Particulate emissions are based upon Particulate being defined as free "ethane" as the result of incomplete combustion
due to the supplied combustion equipment as stated in these data sheets. This excludes ash, sand and heavy metals in the fuel oil.
4-4 NOx guarantees are based on the furnace temperature, combustion air temperature, excess combustion air and the fuel gas compositions
as specified the Zeeco Burner Data Sheets.
4-5 The emissions guarantees above are for operation between maximum and normal heat release.
4-6 The emissions guarantees as stated above are based upon operation with the % excess air, temperature, furnace temperature,
and fuel temperatures as stated in these data sheets.
4-7 See Notes & Clarifications section for more information concerning noise emissions.
4-8 See Notes & Clarifications section for more information concerning the above emissions guarantees.
4-9 Zeeco takes exception to any SOx guarantees since SOx production is based upon the amount of Sulfur in the fuel stream and the
equilibrium conditions in the furnace.
4-10 The above listed predictions & guarantees are based on the lower heating value 'LHV' of the fuel(s).
4-11 All ppmv and/or mg/Nm3 guarantees are corrected to 3% O2 dry basis.
Confidential Property of Zeeco. To be returned upon request and used only in reference to contracts
or proposal of this company. Reproduction of this print or unauthorized use of this Document is prohibited.
04910-7 SO14619
• Burners Optimized Process Furnaces, Inc. TBA
• Flares BP Columbia Vertical Cylindrical
• Incinerators Colombia Rev. 0
• Combustion Systems Raw Gas, Conventional Emissions SHEET 4 OF 5
ZEECO BURNER DATA SHEETS