11 KV Panel
11 KV Panel
11 KV Panel
12KV,800A,18.4KA,MULTI PANEL
(Incoming, Bus Coupler and Outgoing)
SHUNT TRIP, INDOOR TYPE
SCADA COMPATIBLE
SWITCHGEAR WITH MOTOR
OPERATED SPRING CLOSING
VACUUM CIRCUIT BREAKER
2.0 Scope of Work: This Specification covers the design and engineering, manufacture,
testing at the manufacturer‘s factory, painting, packing for transport, insuring, transportation by
road and delivery at destination point of 12 kV, 800 A, 18.4KA, Multi panel, shunt trip, Indoor
Type, motor operated, spring closing Vacuum Circuit Breaker having SCADA compatible
facilities and complete with all accessories as specified hereinafter.
Climatic condition: The equipment is required to operate satisfactorily under the following
site conditions:
3.1 Tropicalization
(a) All equipment must be designed for operations in the severe tropic climate conditions and
fully comply with climatic aging tests as per IEC 60932-class 2.
In choosing materials their finishes, due regard shall be given to the humid tropical
conditions under which the switchgear will be called upon to work. The manufacturer shall submit
details of his usual practice which have proven satisfactory for application to the parts of the
Switchgear panels, which may be affected by tropical conditions.
(i) Metals:
Iron and Steel are generally to be painted or galvanized as appropriate. Indoor parts may
alternatively have chromium or copper-nickel plates or other approved protective finish.
Small iron and steel parts (other than rustless steel) of all instruments and electrical equipment, the
cores of electromagnets and the metal parts of relays and mechanisms shall be treated in an
appropriate manner to prevent rusting.
The use of iron and steels shall be avoided in instruments and electrical relays wherever
possible. Steel screws shall be zinc, cadmium or chromium plated or where plating is not possible
owing to tolerance limitations, shall be of corrosion resisting steel. Instrument screws (except those
forming part of a magnetic circuit) shall be of brass or bronze. Springs shall be of non-rusting material,
e.g., phosphor-bronze or nickel silver, as far as possible.
(iii) Rubbers:
Neoprene and similar synthetic compounds, not subject to deterioration due to the climatic
conditions, shall be used for gaskets, sealing rings, diaphragms, etc.
3.2.1 General
a) The design, dimensions and materials of all parts shall be such that they will not suffer
damage under the most adverse conditions nor result in deflections and vibrations, which might
adversely affect the operation of the equipment. Mechanisms shall be constructed to avoid sticking
due to rust or corrosion.
b) The equipment and apparatus shall be designed and manufactured in the best and most
substantial and workmanlike manner with materials best suited to their respective purpose and
generally in accordance with up-to-date recognized standards of good practice.
c) Whenever possible, all similar parts, including spare parts, shall be made interchangeable.
Such parts shall be of the same materials and workmanship and shall be constructed to such
tolerances as to enable substitution or replacement by spare parts easily and quickly.
d) All equipment shall be designed to minimise the risk of fire and consequential damage, to
prevent ingress of vermin and dust and accidental contact with electrically energized or moving
parts. The switchgear panels shall be capable of continuous operation with minimum attention and
maintenance in the exceptionally severe conditions likely to be obtained in a tropical climate and
where the switchgear is called upon to frequently interrupt fault currents on the system and also
where the duty of operation is high.
a ) All steel castings and welding shall be stress-relieved by heat treatment before machining,
and castings shall be stress-relieved again after repair by welding.
b) Liberal factors of safety shall be used throughout, especially in the design of all parts
subject to alternating stresses or shocks.
The manufacturer shall provide all control, indication, alarm and protection devices and
all auxiliary equipment with wiring and interconnecting cable which are integral parts of
or are directly associated with or mounted on the switchgear panels to be supplied under
this tender. The design of protection and control schemes for the switchgear panels shall
be subject to approval of WBSEDCL.
b) Operation and control.
Interlocking devices shall be incorporated in the control circuit to ensure
safety, and proper sequence and correct operation of the equipment. The scheme will be finalised
during detailed engineering and drawing approval.
b) Particular care shall be taken during manufacture of busbar and fittings and
during subsequent handling to ensure smooth surface free from abrasion. All joints on the
busbar and the circuit within the switchgear board shall be silver or tin-plated to ensure good
electrical connection.
4.1 Enclosure Type Dead front, floor- standing, rigid welded steel frames fully
compartmentalized, Metal clad, Vermin Proof, suitable for
indoor installation and provision for bolting to the floor.
4.2 Enclosure degree of IP 5X for High Voltage compartment and IP4X for Low Voltage
protection compartment
4.3 Enclosure Material CRCA steel
4.4 Load bearing members Minimum 2.5 mm thick
4.5 Doors and covers Minimum 2.0 mm thick
4.6 Gland Plate (detachable 3.0mm MS detachable type for 3 core cable and aluminium
type) 5.0mm for single core cables. Cable compartment shall have
an anti vermin guard plate for protection against entry by rats,
rodents etc.
4.16 Fixing arrangement Concealed hinged Bolted with SS bolts and Neoprene rubber
i. Doors gasket , washer
ii. Covers
iii. Gasket
4.17 Required HV cable 550mm for 11KV
termination height in
the cable
4.18 compartment
Panel Base Frame Steel base frame as per manufacturer‘s standard.
4.19 Handle Removable bolted covers for cable chamber and busbar
chamber shall be provided with ―C‖ type handles
4.20 Prevention of Internal Arc Shall be type tested against internal arc as per provision in
IEC 62271-200. The Circuit Breaker, busbars and cable
compartments shall be provided with arc venting outlet. The
doors for the compartment shall be capable of withstanding
the effects of maximum internal arcing fault without being
blown off and causing danger to personnel and other
equipment. This should be proven by successful testing for
18.4 KA with duration 0.1 second as per relevant IEC
standard.
4.21 Test Terminal Block 13 Ways, 50A, 1100V with back connection. Dia of Entries
is 5 mm & overall dimension 250X50 mm, covered with
insulated cover. TTB should be suitable for 3 Phase 4 Wire
Energy Meter.
4.22 Multiway terminal Block Delinking type, Rail/Channel mounted, Terminal Connector
and low voltage wiring to be used in CT Circuit & Screw type for other Circuit. The
Terminal Blocks should be suitable for 2.5 sq.mm wire and
covered with insulated transparent cover. Pitch should be
minimum 8mm & 10mm for Screw type & Delinking type
connectors respectively.
The low voltage cable shall be enclosed in grounded
metal conduit when routed through a high voltage
compartment. Control wiring shall be neatly bundled and tie
wrapped where applicable. Wiring shall be protected from
rubbing against door flanges or other parts of the
enclosure.
4.23 Cable Tray Netted Metal cable Tray of suitable size at the rear side of
Switchgear, preferably running at the top along the panel
for carrying the signal cables for SCADA interface to be
provided.
4.24 Remote Terminal Box To be provided suitably at the back side of the panel for
termination of the following cables :
A . Main AC / DC
B . Inter trip from up stream
C . SCADA related terminations
D . Inter connection for Differential protection etc.
4.25.5 Operating mechanism Re-strike free, trip free both electrically and mechanically, with
electrical anti-pumping feature
One O-C-O operation possible after failure of power supply to
Local/Remote switch.
the spring charging motor.
Motor wound, spring, charged, stored energy type with
manual charging facility. One no. Breaker Truck operating handle
for every three panels needs to supply.
4.25.6 Trip and Closing Coil To be rated for substation DC voltage. Suitable for operation at
minimum operating voltage of 70% for tripping and 85% for
closing operation. Maximum Burden shall be about 250 watt for
each coil.
4.25.7 Truck The circuit breaker shall be mounted on an inbuilt carriage to
facilitate isolation and withdrawal of the breaker. Trolley of the
VCB should be horizontally isolated and there should be a
minimum ground clearance of 0.55 meter between thimble
point of cable termination and GL. There should be a
minimum clearance of 300 mm between any 11kV live bus
and GL.
Trolley should be detachable from panel without any additional
supporting trolley i.e. VCB trolley itself move on ground level.
4.26 Breaker Indications and
push buttons
4.29.2 Label for identification For bus side and cable side shutters
4.29.3 Warning label on shutters of Clearly visible label ―isolate elsewhere before earthing‖ be
incoming and other provided
connections
4.30 Breaker electrical
4.30.1 operation features
Trip coil supervision To be given for breaker close and open condition.
4.30.7 PT supply bus in all panels Fed normally by Bus PT with changeover facility.
4.30.8 Spring Charge Limit switch The circuit breaker shall be provided with motor operated spring
Aux. Contact Configuration charged closing. Spring charging by motor should be smooth
and hassle free and there should be nominal sound during
spring charging. Motor should be 230 Volt AC operated,
Tripping of the circuit breakers shall be through "Shunt trip" coils
rated for 30V DC auxiliary supply. It shall be possible to trip the
breaker manually in case of necessity.
4.30.9 Local/ Remote selector Switch should be 4 pole in each position, 2 way lockable and
switch stay put type.
5.1 Current Transformers Shall be cast resin type with insulation class of E or better.
Contact tips on primary side shall be silver plated. Correct
polarity shall be invariably marked on each primary and
secondary terminal.
Primary shall be wound or bar type, rigid, high conductivity
grade copper conductor. Unavoidable joints on the primary
conductor shall be welded type, preferably lap type. Current
density at any point shall not exceed 1.6 A/sq.mm. Suitable
insulated copper wire of electrolytic grade shall be used for CT
secondary winding. Multi ratio in CT shall be achieved by
reconnection of secondary winding tapping. The secondary
terminals shall have screw type terminals. The screw should
have sufficient length for connection of at least two nos wires
with plain and spring washers and minimum 10 mm clearance
between the adjacent screw.
6.2.0 Mounting Rail mounted on top of the Unit and connected on bus side.
It can be plugged into and withdraw from service by pulling
or pushing the PT by the handle provided on the PT. This
action traverses the PT along the rails and shall
automatically operate the spout shutters. The shutter drive
also forms a latch which holds the PT in the service position
and this latch shall be required to be released before PT can
be isolated.
Access to the PT and the reinforcement in the Panel for
allowing a person to stand on the Top should be provided.
Sealing arrangement of the PT with the carriage and
secondary fuses are to be provided.
Mounting of PT on the breaker truck is not acceptable.
7.7. Metallic cases of relays, Connected to the earth bus by independent copper wires of
instruments and other LT size not less than 2.5 sq mm with green colour insulation. For
panel mounted equipment this purpose LT compartment should have a clear designated
earth bus to which earth connections from all components are to
be connected.
7.8. CT & PT Secondary neutral Earthed at one place at the terminal blocks through links.
8.0 Indicating Meters Flush Mounted, back connected, dust proof with Industrial grade
―A‖ classification and conforms to IS:1248(1968)
8.1 CT operated Ammeter 3 no. Digital Ammeters to be provided in Incomer and Feeder
panels for measuring load current of each phases.
Display : 3 ½ -digit display,
Aux. Power: : 230 V AC
CTR: 600/1A for Incomer and 200/1A for Feeders.(Site
Selectable)
Accuracy Class: 1.0 or less.
Size : 96 X 48 mm.
8.2. Direct Ammeter 1 nos. Separate Digital Ammeter to be provided for
measuring heater current drawal in all the Panels.
Display : 3 ½ -digit display,
Aux. Power: : 230 V AC
Accuracy Class : 1.0 or less.
Size : 96 X 48 mm.
8.3. P T operated Voltmeter One no. Digital Voltmeter to be provided in Incomer Panels
for measurement of Phase to Phase system voltage, along with
a Voltage Selector Switch.
Display : 3 ½ -digit display,
Aux. Power: : 230 V AC
PTR : 11000 / 110 V
Accuracy Class : 1.0 or less.
Size : 96 X 48 mm.
8.4. Direct Voltmeter One no Analog DC Voltmeter to be provided in the Bus
Coupler panel for measurement of Control DC voltage.
9.0 Energy meter One Three Phase, Four Wire CT/PT operated, fully static
AMR compatible TRIVECTOR Energy Meter along with TTB to
be provided in all Incoming and outgoing breaker panels at its
upper most position in a separate metering chamber. Necessary
wiring to be provided with separate terminal block (suitable for
CT/PT connection) for Energy meter connection and as per
detailed technical specification attached in a separate sheet
(Annexure-F).
TTB to be installed in the metering chamber.
10.0 Multi functional Will be supplied by the Utility and to be fixed in the metering
Transducer chamber. Separate TB for connection should be provided.
Space required for Transducer fixing is 100X100mm.
11.0 Indication Flush mounted, insulated from 30V DC supply with appropriate
coloured lens. The lens shall be made of a material, which will
not be softened by the heat from the lamps.
11.1 Lamps High intensity, clustered LED type.
11.1.1 Breaker ON Red
11.1.2 Breaker Off Green
11.1.3 Spring Charged Blue
11.1.4 Auto trip Amber
11.1.5 Service position White
11.1.6 Signal Received from Remote White
12.0. Switches and push Flush mounted on LV compartment door, with shrouded
buttons terminals
12.1 TNC Control Switch with pistol Non Lockable spring return to normal position. Shall have
grip mechanical interlock to prevent accidental operation of the
switch. Terminals shall be screw type and indelibly marked.
2 nos. Contact each for Close and Open, 2 No. NAT,2 nos. NAC
and one for normal position contact is required.
12.2. Local / Remote selector 2 way, 4 poles in each position lockable and stay put type.
switch
12.3 Selector switch for voltmeter 4 Positions ( RY-YB-BR-OFF), 3 ways.
12.4. Toggle ON/Off switches For heater / illumination circuit
12.5 PT Selector switch 4 Position (PT1-PT2-PT3-OFF), 8 Poles in each position. Current
rating 16 Amps
12.6 Push button of IED(Relay) Wired up to specified DI contact of Relay.
Reset
12.7 Emergency trip push button Red colour with stay put, Current rating 10 Amps.
13.0 Internal wiring 450/750 V grade PVC insulated stranded flexible copper wire.
13.1. Wire Size 2.5 sq. mm for CT circuit, 1.5 sq mm for PT and 1.5 sq.
mm for control circuit, 4.0 sq. mm for Main, AC & DC and Bus
wiring.
i. A suitable wiring duct system firmly fixed on the panel
and having covers shall be installed for front to rear and inter
panel wiring to provide easy access for inspection and
replacement of the wires.
ii. Wiring between terminals of the various devices shall
be point to point. Splices or tee connection will not be
acceptable.
Iii. Facilities for short-circuiting the current transformer
secondary while the switchgear is in service shall be
provided.
iv. Wires shall be suitably bunched adequately supported
to prevent sagging. and it shall have sufficient clearance from
High voltage system.
v. Sufficient Bus wires shall be provided for
interconnecting with adjacent units both ways and also for
future connection.
13.2 Wiring Colour code
13.2.1 PT and CT Red Phase : Red, Yellow Phase : Yellow
Blue Phase : Blue, Neutral : Black.
13.2.2 DC Circuit Gray
13.2.3 AC Circuit Black
13.2.4 Earth Green
13.3 Ferrules At both ends of wire with same stated marking. Plastic ferrules
shall be used conforming IS. Interlocked type (one additional red
colour ferrule for all wires in trip circuit)
13.3.1.10 Spare contact circuit U1, U2, U3 .../ S1, S2, S3 .......
13.4 Lugs Tinned copper, pre-insulated, fork type and pin type as
applicable. Only Ring type is acceptable in CT &PT Circuit.
14.2. Terminal for CT & PT With provision for shorting with screw driver operated sliding
secondary leads link.
a ) CT shorting links shall be provided to short CT circuits
under live system condition.
b ) Isolation links shall be provided on the trip circuits, alarm
and on the VT circuits to allow easy isolation without
disconnecting the wires from TBs.
17.0 HT Cable Termination Cable entry from rear bottom side for Incomer and
Outgoing feeders .The cable termination shall be located at least
250 mm from the CT primary terminals. For Incomer, double
cable termination arrangement to be provided with two sets of
nut and bolts. Copper terminator strip of adequate size shall be
provided for termination of cables and shall have adequate
height inside to accommodate the heat shrinkable type indoor
cable termination.
18.0 Multi-core cable Incoming Panel- External DC supply from DCDB, External AC
termination box-- Purpose supply from ACDB, Remote Electrical Close and trip operation,
Inter trip operation from upstream 33 kV circuit, Breaker spare
aux. Contacts. Spare contacts of L/R Switch and Spring Charge
Limit Switch etc.
19.0 Operation Counter Each breaker shall be provided with operation counter.
20.0 Vacuum Interrupter Capable to withstand minimum 100 full short circuit operations at
26.3 kA as per test duty 1 to 5 of IEC-56. The continuous
Current rating should be more than 800A. Manufacturer‘s test
report/literature to be supplied along with tender in duplicate.
21.0 Insulated spacer It shall be made of insulated fibre glass materials shall be
provided in High voltage system, to protect from absorption of
moisture present in the air.
22.0 PT selection scheme Each Incoming and outgoing breaker panel shall be
provided with suitable manually operated selector switch having
break before make type contacts including necessary wiring for
selection of voltage from different PT secondary‘s available for
connection with energy meters.
Each panel should be provided with 3 PT scheme and
current rating of the PT Selector Switch should be minimum 16
Amp.
Voltmeter of incoming breaker panel shall be connected
directly from respective PT secondary of associated unit.
21.1.7 Relay contacts Shall make firmly without bounce and the relay mechanism shall
not be affected by panel vibration or external magnetic field.
21.1.8 Electromagnetic Compatibility Relay thermal rating shall be such that the fault clearance times
on any combination of current and time multiplier settings shall
not exceed the thermal withstand capability of the relay.
Compliant to EMC directives as per IEC.
21.1.9 Relays for auxiliary, Static or attracted armature type with short pickup time of less
supervision, trip and timer than 30 ms.
relays
21.1.10 Relay reset Self reset contacts except for Master Trip relays.
21.1.11 Operation indicators With hand reset operation indicators (flags) or LEDs with
Push buttons for resetting, for analyzing the cause of operation
21.2 Master Trip relay High Impedance and High speed relay flush mounted having
coil cut-off contact with at least 4NO and 4NC contact and
electrical reset facility capable to make, carry and break trip
coil current of Circuit Breaker and capable for future integration
with SCADA. It should be immune to capacitance discharge
currents and leakage current. Operating time should be less
than 20ms. Terminals shall be screw type to accommodate 1.5
sq. mm. Cable and located at the back of the relay. Terminals
shall be clearly marked. Contact configuration shall be drawn on
the relay casing.
21.3 Fault recording Relay shall have the facility for recording of various
parameters during a fault. It should be possible to set the
duration of record through settable pre fault and post fault time. It
should be possible to down load the data locally or from
SCADA remotely.
21.4 Auxiliary supply Operate on available 30 V. DC supply. To reduce the effect of
Electrolysis, relay coil shall be so connected such that they are
not continuously connected from the positive pole of the station
battery.
21.5 Test facility In built. Necessary test plugs shall be provided.
21.6 Protection in Incomer & 3 phase over current protection & Earth fault protection
Outgoing panel
21.7.1 For each breaker panel To be provided with anti pumping relay/contactor (94),
(plug-in type contactor will not be accepted)
21.7.2 Auxiliary relays, coupling To effect interlocks and to exchange signals of status &
relays, transducers etc. control from remote.
22.0 Additional Requirement The schematic diagram of control and indication circuit on a
durable sticker shall be fixed in a suitable place in Incomer and
feeder panels and Annunciation scheme in the Bus Coupler
panel.
The wiring arrangement, position of fuse, TBs etc, in the
panel should be such that each and every connection can be
accessed easily. Fuse tops can be opened /inserted easily.
Only ring type sockets should be used for wire termination in TB/
Relays/ Meters/TTB etc. Fork type socket can be used in
Annunciator only.
Separate switch to be used for cubicle light instead of Door
switch.
Circuit Label incorporating identification, information of
incoming/outgoing/bus coupler breaker shall be provided.
Connection diagram plates for the PT and CT shall be provided
as per provision in the relevant IS.
All name, rating , circuit label, connection diagram plate
shall be fixed with screws or by riveting instead of fixing by
adhesive.
23.0 Annunciation Scheme 6/8 Window Annunciator shall be provided in each panel
including Bus Coupler panel. It should be Microprocessor based
having inbuilt Accept/Reset/Test/Mute push buttons for trip and
non-trip functions. DC operated common Hooters shall be
provided in Bus Coupler breaker panel. It shall have provision of
inbuilt watch Dog and Fast fault indication with Trip (O/C , E/F
and other trip signals if any )and non-trip alarm i.e AC supply
fail, main DC supply fail at Bus Coupler. The functional details
and scheme will be decided during finalisation of drawings.
24.2 Space heater location Two nos. each in Breaker & HV cable compartment
to be mounted on an insulator.
24.3 Space heater Monitoring One AC Ammeter with 0-1.0Amp range shall be
provided in series with the heaters to monitor the current
drawal of the Heaters. Size :96x48mm.
25.0 Switch and sockets
25.1. Illumination Lamp For LV ,cable chamber & energy meter compartment
25.2. 240V AC, 5A Switch & socket In LV chamber
26.0 Name Plates and rating
plate of switchgear
26.2 Lettering Engraved, with white letters on black background, for use
inside the control compartment, a white label, engraved in
Black Letters and numbers shall be used. Each major
equipment shall be provided with a rating plate containing the
required information as specified in the relevant IEC standard.
26.3 Name plate for feeder On front and rear side of each panel giving feeder
description & number description. On the rear side the name plate shall be fixed on
the back cover.
Operating sequence
29.3 Paint shade RAL 7032 for external & internal surface
29.4 Paint thickness Minimum 80 microns
30.0 Type Test
30.1 Type Tests The product must be of type tested quality as per all tests in
IEC/Indian standards. Such tests shall be done at any NABL
accredited laboratory.
30.2 Type test report validity Last five years from due date of bid submission
period
A . Switchgear Panel (with circuit breaker installed)
30.3 Type test report to be a. Lightning Impulse Voltage withstand Test
submitted along with the bid b. H.V. dry 1 min power frequency withstand test
c. Short time and peak withstand current test
d. Short circuit test with basic duties
e . Single phase breaking capacity test.
f. Cable charging breaking current test
g. Temperature Rise test
h. IP Test
i. Internal Arc Test as per IEC 62271-200
j. Horizontal Acceleration due to seismic force (if
available)
B. Circuit Breaker
a. Mechanical Endurance Test as per M2 Class of
IEC
C. Current Transformer
a. Short Time Current Test
b. Impulse Voltage Withstand Test
c. Temperature Rise Test
D. Potential Transformer
a. Impulse Voltage Withstand Test
b. Temperature Rise Test
Copies of test certificates in respect of following
bought out items:-
a. Vacuum Interrupter.
b. Insulators
c. Bus Bar Material
d. Terminal connectors
e. KEMA / CPRI Certification for relay/IED i.r.o.
IEC61850 compliance
36.0 Routine & Acceptance All the switchgear panels shall be tested in accordance with
Test the requirement of IEC 62271-200.
Tests shall be carried out on the circuit breakers as per the
requirement of IEC 62271-100.
Current transformers and Voltage transformers shall be tested
in accordance with the requirement of IEC 60044-1, IS 2705
and IEC 6044-2, IS 3156 respectively. The Protection Relay
shall be tested in accordance with IEC 60255 & Energy Meter
shall be tested as per relevant IS.
All routine tests at manufacturer‘s works shall be carried
out and Test Reports are to be submitted to CE, P&C,
WBSEDCL.
a ) Dimensional Checks
Complete Switchgear Panel b) Operational Tests
test c) Primary Injection Tests
36.1 d) Calibration Tests on Relays and Instruments
e) Power frequency Withstand Test
f) Insulation Test
g) Contact resistance test of Primary joints
h) Power frequency Withstand Test on secondary Wiring
Routine tests.
18.4kA Circuit Breaker test a) Operation test.
( six copies of test report to be b) Dielectric Test on the main circuit.
36.2 submitted with Offer) c) Dielectric tests on controls and auxiliary circuits.
d) Measurement of resistance of the main circuit.
e) Timing test
f) Design and visual checks
g) Test Certificate for all resin cast/moulded components of
circuit breakers whose partial discharge measurement are
specified in the relevant IEC (No. 62271-100, Clause No.6.2.9)
Routine tests shall be carried out at the manufacturer‘s
Current Transformer Test plant as per the requirement of IEC 60044-1, IS 2705 as listed
( six copies of test report to be below:
36.3 submitted with Offer) i. Polarity test and verification of terminal markings test
ii. Ratio and phase angle error test(accuracy class;
composite error test)
iii. Power frequency tests on primary and secondary
windings
iv. Power frequency withstand tests between
sections(windings)
v. Inter-turn over voltage tests
vi. Partial discharge measurement
Protection Relay Tests a. Relay Pick-up test for all functions and phases
( six copies of test report to be b. Relay timing test for all functions and phases
submitted before with Offer) c. Conformance Test as per IEC 61850
36.5
-----------------------------------
ANNEXURE – A
1.0 Switchgear
1.1 Type Metal clad, air insulated with VCB type circuit
breaker
1.2 Service Indoor
1.3 Mounting Free standing, floor mounted
1.4 System voltage 11KV
1.5 Highest System voltage 12 KV
1.6 Frequency 50HZ, ± 3%
1.7 Phase 3
1.8
1.9 Rated current @ 50 DEG C ambient 800 Amp.
1.10 Short time rating for 3 sec. 18.4KA
1.11 Insulation level (PF rms / impulse 28 / 75 KV
peak)
1.12 System ground Solidly earthed
1.13 Enclosure degree of protection IP 5X for high and low voltage compartment
1.14 Bus bar – Main @ 50 DEG C 1600A, Current Density 1.6 Amp/sq.mm.(Max)
ambient
1.15 Material electrolytic copper, tinned /Silver plated
1.16 Bus Bar sleeve Full voltage sleeved with shrouds on joints
1.17 Bus identification Colour coded (R-Y-B)
1.18 Bus end connection To be capable to safely withstand stress due to
max. Short circuit current and thermal expansion.
Necessary provision to be made for testing current
transformer primary by removing insulated portion
without difficulty.
1.19 Temperature rise above Ambient 40DEG C for conventional joints, 55DEG C for
silver plated joints
1.20 Riser Bus electrolytic copper, tinned /Silver plated,
800A, Current Density 1.6 Amp/sq.mm.(Max)
1.21 For the design and erection of Busbars the following minimum clearance shall be observed
1.25 Hardware GI
1.27 Power and control cable entry From bottom for Power Cable. For control cables
through Remote Terminal Box installed at the
backside of the Panel.
2.0 Circuit Breaker
2.1 Type of isolation & Drawout Horizontal isolation & Horizontal Drawout.
3.2. Type Triple core, Dual ratio, Cast resin, Indoor type .
Marking on primary and secondary terminal as per
requirement of IEC 60044-1, IS 2705 and shall be
indelibly marked. The secondary terminals shall
have screw type terminals.
3.3. Class of insulation Class E or better
3.4. Ratio 600/400/1-1-1A
3.5. Number of secondary Three, Core 1 : Metering, Core 2 :Protection ,
Core 3 : Protection
3.6. Accuracy class Core 1 : 0.5, Core 2 : 5P15, Core 3 : PS.
4.2. Type Dual core, Dual ratio, Cast resin, Indoor type.
Marking on primary and secondary terminal as per
requirement of IEC 60044-1, IS 2705 and shall be
indelibly marked. The secondary terminals shall
have screw type terminals.
4.3. Class of insulation Class E or better
4.11 Name Plate of CT indelibly marked Name plate for the current transformer shall be
provided with all the required details as per IEC
60044-1, IS 2705 Standards, including :-
i) The manufacturer‘s name
ii) Serial number and a type designation
iii) Rated primary and secondary current
iv) Rated frequency
v) Rated output and corresponding accuracy
class for each secondary winding, including the
rated accuracy limit factor and Instrument
security factor for protection and metering
secondary windings respectively.
vi) The highest voltage of the equipment
vii) The rated Insulation level
viii) The rated short-time thermal current (Ith) and
the rated dynamic current
ix) Class of Insulation
x) Rated continuous thermal current
xi) Property Label – ― Property of WBSEDCL‖
xii ) Guranteed for 5 Years
5.9 Primary and secondary fuses HRC current limiting type, primary fuse
replacement shall be possible with VT in withdrawn
position
5.10 Voltage class 12KV
5.11 VA Burden 100 VA per phase
5.12 PT mounting Rail mounted on top of the Incomer Panel and
Primary connected on bus side. It can be plugged
into and withdraw from service by pulling or pushing
the PT by the handle provided on the PT. This
action traverses the PT along the rails and shall
automatically operate the spout shutters. The
shutter drive also forms a latch which holds the PT
in the service position and this latch shall be
required to be released before PT can be isolated.
Annexure - B
Standard Make of Relay and Fitments
VCB Panel Manufacturer should be the VCB Manufacturer.
Annexure-C
Legend of Devices associated with Multi panel Shunt trip vacuum Circuit Breaker
Annexure D
Sl Device Quantity
no.
Incomer Feeder Bus coupler
1. Numerical O/C & E/F Relay 1 No. 1 No. Nil
2. Trip Relay 1 No. 1 No. 1 No.
3. AC Supervision Relay Nil Nil 1 No.
4. Annuanciator 1 No. 1 No. 1 No.
5. AC Ammeter ( CT operated ) 3 No. 3 No. Nil
6. AC Voltmeter 1 No. Nil Nil
7. DC Voltmeter Nil Nil 1 No.
8. Ammeter ( Heater Ckt.) 1 No. 1 No. 1 No.
9. Current Transformer 3 No. 3 No. Nil
10. Potential Transformer 1 Set Nil Nil
11. Energy meter 1 No. 1 No. Nil
12. TTB 1 No. 1 No. Nil
13. Indicating Lamp 6 No. 6 No. 4 No.
14. MCB ( DC Ckt) 1 No. Nil 1 No.
15. MCB ( AC Ckt, 16 Amps) 1 No. Nil 1 No.
16. MCB ( Motor ckt.) 1 No. 1 No. 1 No.
17. 3 Position PT Selector Switch (16 Amps) 1 No. 1 No. Nil
18. Voltage Selector Switch 1 No. Nil Nil
19. Electronic Buzzer (DC Volt operated) Nil Nil 1 No.
20. Electronic Buzzer (AC Volt operated) Nil Nil 1 No.
21. Heater with controller 1 Set 1 Set 1 Set
22. T-N-C Switch 1 No. 1 No. 1 No.
23. Local – Remote Switch 1 No. 1 No. 1 No.
24. Push Button for Emergency Trip 1 No. 1 No. 1 No.
25. Push Button for Relay reset 1 No. 1 No. Nil
26. Spring Charging Handle 1 No. for every three Panel.
27. VCB Operating Handle 1 No. for every three Panel
28. HRC Fuse & Link As required As required As required
NB: The Bidder has to include list of other Items for the Equipment to meet our Technical requirement.
Annexure-G
1. General :
Office address
Factory address
2. Panel
Make
Application Standard
Rated Voltage
Highest Voltage
Normal Current
Frequency
Breaking Capacity
Making Capacity
AC Aux. Voltage.
DC Aux. Voltage
Trunk Panel in mm ( H x W x D )
3. Bus Bar
Material
Shape
Type of plating
Type of insulation
Colour Identification
Reference Standard.
Make
Material
Creepage distance
Make
Type
Reference Standard
Rated voltage
Highest voltage
Frequency
Normal Current
Breaking capacity
Making capacity
STC for 3 Sec.
Closing time
Opening time
Operating mechanism
6. Vacuum Bottle
Make
Rated voltage
Normal current
Breaking capacity
Making capacity
Contact material
Type of plating
Contact pressure
7. Current Transformer
Make
Reference Standard
Type
Voltage
Frequency
Insulation level
Class of insulation
Fixing Arrangement
8. Potential Transformer
Make
Reference Standard
Insulation level
Class of insulation
Type
Frequency
Winding connection
Ratio
Class of accuracy
Fixing position.
Fixing arrangement
Make
Type
Model no.
Ordering Code
Type
Model no.
Make
Type
Size
Basic CTR
Accuracy class
AC Aux. voltage
Fixing type.
Make
Type
Size
Current range
Accuracy class
AC Aux. voltage
Fixing type.
Make
Type
Size
PTR
Accuracy class
AC Aux. voltage
Fixing type.
Make
Type
Size
Accuracy class
Fixing type.
Make
Type
Model no.
Make
Type
Size
Make
Type
Contact configuration
AC Voltage rating.
Make
Type
No of contact ( NO + NC )
No of spare contact ( NO + NC )
AC Voltage rating.
Make
Type
Contact configuration
AC Voltage rating.
Make
Type
Rated AC Voltage
Rated wattage
Make
Type
Make
Type
Rated AC Voltage
Wattage
23. Thermostat
Make
Setting range
Make
Type
Make
Type
No of contact ( NO + NC )
No of spare contact ( NO + NC )
AC Voltage rating.
26. Annunciator
Make
No of window.
Aux voltage
Make
Type
28 PT selector switch
Make
Type
Current Rating
29 TTB
Make
Type
Size
30 Terminal Block
Make
Type
31 MCB
Make
Type
Make
Type
33 HRC Fuse
Make
Type
Make
Type
Voltage Grade
For CT & PT
Material
Shape
Size
Paint type
Paint shade
Paint thickness
Accessories
---------------------------------------
ANNEXURE-H
b. Withstanding capability of
Electromagnetic interference as per
relevant part of IEC 61850
17. Mounting
18. Watchdog
b. CT Ratio setting
c. Earth fault current with time delay IEC
Curves, 2nd stage for instantaneous
trip(less than 50 ms)
d. High set with delay
e. IEC Curves for all O/C and E/F have
user selectable?
20. a. No. of Digital Output Contacts
b. Contact rating
21. Mode of Time Synchronization
22. Type of Lugs and terminators
23. MTBF
24. Lifespan
25. Compliance to Type Test
26. Communication Port
a. Rear port- details
b. Front port-details
27. Whether Communication Ports are
native to the Relay
28. Protocol supported for Rear Port
ANNEXURE-J
04. Mounting
Date : Signature:
Name:
Designation:
Company Seal:
-----------------------------
ANNEXURE-E
Technical Specification for Non-directional over current and earth fault relay
1 Purpose and It is intended to automate the Switchgears specified in the scope of supply and use
application Communicable Numeric relays for Protection, Control, Metering and Status monitoring. This
specification is based on the understanding that an integrated Automation System along
with protections shall be provided and same shall have provisions for Integration with
SCADA system. All the feeders shall be remote controlled from Employer‘s SCADA and
from the local console of the numerical relays.
3. Processor feature Relay shall be completely Numerical with protective elements having software algorithm
based on sampling of analog inputs. Sampling Rate of Analog Signal: The sampling rate
should be 1000 Hz for 50 Hz signal or better for each analog channel. Hardware based
measurements shall not be acceptable.
4. Operational Philosophy The operation of Relay shall be possible both locally from the Switchgear and remote &
Local Work station. The local position shall be displayed in remote / local workstation and
remote operation shall be blocked if the switch is in Local. Clear control priorities shall
prevent initiation of operation of a single switch at the same time from more than one of the
various control levels and there shall be interlocks among various control levels. The priority
shall always be with the lowest enabled control level. Relay accuracy shall not be affected
by system frequency fluctuation.
6. Main measuring and All measurements should be in primary quantities. Minimum following displays are required
reporting feature in alpha numeric:-
1. Three phase (Positive sequence) current
2. Neutral(zero sequence) current
3. All the trips should have clear indication on the relay terminals
4. Resetting should be selectable as hand reset or auto reset.
5. The default relay LCD shall be user defined to display primary circuit loading.
7. Memory and Recording 1. The relay setting and programming should be stored in EEPROM so that during
Feature Aux. Power failure the said data is not lost.
2. Relay should have event log, trip log and DR record. All logs should go in to history.
3. All tripping of relay should initiate DR in auto without extra binary input. Triggering
of DR with binary input should be user configurable.
4. The last 2 fault DR records should be in flash memory and DR will not erase in case
of DC supply fail for more than 2 days.
5. Should be able to record at least 5 Oscillographic disturbances and 5 fault records
and 250 event records.
6. Minimum Four no. of latest trip log with cause of trip should be stored in memory
along with date and time stamping. The memory should not be lost with the
switching off of DC.
7. The relay should have fault-recording feature with current waveform and Digital
Input status. The fault waveform should consist of minimum four current waveforms
of three phase current and zero sequence current and DI status. Triggering time for
Pre and Post should have user selectable. This record should be in flash memory
for minimum 7(seven) days even after switching off the DC supply.
8. The fault should be date and time stamped.
9. Communication protocol IEC 61850.
8. Auxiliary Supply 30 V DC to - 25% to + 10%, 2 wire unearthed system. Necessary software shall be in-built
for proper shutdown and restart in case of power failure. Auxiliary supply burden will be
around 20Watt.
9. Rated CT/PT 5/1 Amp(User selectable) , CTs used to be protection class
secondary
10. Rated frequency 50 HZ +/- 3%
11. Ambient condition 1. Operating ambient temperature upto 55 Deg C
2. Operating Humidity upto 100 %
3. Relay shall meet the requirement for withstanding electromagnetic interference
according to relevant parts of IEC 61850. Failure of single component within the
equipment shall neither cause unwanted operation nor lead to a complete system
breakdown.
12. Module and Mounting 1. Relay should be flush mounted type
2. If module is draw-out type then it should have CT shorting facility of make before
break type.
3. Mounting in switchgears located in non AC rooms.
4. Galvanic isolation between field connection and relay hardware should be there.
13. Watchdog and self The relay should have facility to monitor the healthiness of its circuits and components by
monitoring own monitoring system. In case of any problems, the alarm should be generated by one of
the output contacts. The alarm as soft signal to be sent to SCADA system as well.
Necessary support documentation explaining the self diagnostic feature shall be furnished.
1. One potential free change over contact should be provided for start inhibit of relay.
2. All o/p contact should be freely programmable.
3. Rating of trip contacts:-
a) Contact durability>10K operation
b) 15 Amp make and carFry for 3 sec for trip contact
c) Make and carry for trip contacts L/R<=40ms
4. Rating of Alarm contacts:- 5 Amp make and carry continuously
for 5 sec.
Testing of Output relays through keypad on relay fascia and relay HMI software. Output
relay dwell time shall be user programmable or fixed at 100ms.
16. Relay software and 1. The relay should have native IEC 61850 Communication Protocol.
Man Machine Interface 2. Should have password protected key padlock.
3. Necessary software for relay setting , retrieving DR, event log, trip log should be
supplied by the Bidder. Necessary License is to be issued for WBSEDCL, if
required.
4. Bidder has to supply communication hardware for relay setting, DR downloading
from front port. This device should be compatible to USB/Ethernet port.
5. It shall be possible to transfer the data stored in the DFR to computer on
IEEE/COMTRADE format. The data format shall be compatible for dynamic
protection relay testing on relay test kit. COMTRADE data viewing software to be
provided.
6. Multiuser/Corporate license for installation on minimum 7 nos. of PCs.
17. Date and time Date and Time stamping with faults and record. The clock should be powered from internal
cell and should not required setting after every DC switching. The internal cell life minimum
5 years. Time synchronization by IRIG-B or SNTP. For time synchronization through SNTP
is to be provided from clock signal coming from RTU. In case of IRIG-B, time
synchronization will be done with GPS clock signal from GPS receiver located at substation.
18. Lugs and terminators All CT and PT terminals shall be provided as fixed (screwed) type terminals on the relay to
avoid any hazard due to loose connection leading to CT opening or any other loose
connection. Necessary amount of lugs should be supplied along with each relay for CT
connection and control wiring.
19. Manuals, Drawings and 1. The relays should be supplied with manuals with all technical and operating
Literature instructions.
2. All the internal drawings indicating the logics and block diagram details explaining
principle of operation should be given at the time of supply.
3. Mapping details shall be submitted in IEC format.
20. Assistance in As part of this offer, Bidder shall have to provide necessary support during integration of
commissioning relays with the third party SCADA system which will be commissioned in future.
1. Product maturity: The Bidder should mention the time period for which the product
is in the market
2. Expected production life
3. Hardware/Firmware change notification process. Upgrades to be provided free of
cost within the warranty period/5 years whichever is later, if needed.
4. Lifespan of standard tools and processes for relay configuration, querying and
integration.
24. Standards The relay should conform to the IEC255-5 or equivalent BS / ANSI for following:-
25. Communication Port 1. Two nos. IEC 61850 protocol compliant, 100 MBPS Ethernet RJ45/F.O port for
communication with SCADA system through two managed Ethernet Switches
operating in redundant mode. The communication shall be made in 1+1 mode
between individual IED to Switch, such that failure of one set of LAN shall not affect
the normal operation of SCADA. However, it shall be alarmed in SCADA.
2. Functioning of Relay shall not hamper to fault occurring any interconnected relay.
3. One Front port Ethernet RJ45/USB 2.0 for relay parameterization and configuration
etc. with the help of PC.
4. Relay should generate GOOSE message as per IEC 61850 standard for
interlocking and also ensure interoperability with third party relays.
26. Name Plate and Each IED shall be clearly marked with manufacturer‘s Name, type, serial no. and
marking electrical rating data. Name plates shall be made of anodized aluminium with white
engraving on black surface.
27. Performance Relays will be guaranteed for the period of five years from the date of last
Guarantee dispach.
Any problem in the said period should be attended free of charge
inclusive of repair/replacement of relays/ component (both H/W, S/W).
28. Type Test Dielectric Withstand Test—IEC 60255-5
High Voltage Impulse Test, class III --- IEC 60255-5(5kV peak, 1.2/50 micro Sec;3
Positive and 3 negative shots at interval of 5 Sec.)
DC Supply Interruption ---- IEC 60255-11
AC Ripple on DC supply ---- IEC 60255-11
Voltage Dips and Short Interruptions --- IEC 61000-4-11
High frequency Disturbance ---- IEC 60255-22-1, Class III
Fast Transient Disturbance ---- IEC 60255-22-4, Class-IV
Surge withstand capability ---- IEEE/ANSI C 37.90.1(1989)
Degree of Protection
Electromagnetic compatibility
Mechanical stress/vibration test
Temperature withstand
Type test reports for the above tests shall be submitted for the approval of WBSEDCL along
with Tender. Wherever the above mentioned standards and IEC 61850 overlap, the latter
will prevail.
30. Offer for relay Offer with all relevant documents for numerical relay may be submitted with different
make as per Annexure-B alongwith the Bid but after placement of order, drawing for
approval needs to be submitted with only one type of accepted offered relay.
2. Lugs suitable for current and control, wiring Qty as per Tender X Number
of TBs in relay + 20% extra.
N.B All the above tools/ Software should be compatible to WINDOWS XP/WINDOWS NT/WINDOWS 7
Operating System.
SCHEDULE – I
Company Seal :
Company Seal :
ANNEXURE-F
STANDARD
TECHNICAL SPECIFCATION
FOR
FOR
11 KV FEEDER METER
TECHNICAL SPECIFCATION FOR 3PHASE 4 WIRE CT, PT OPERATED 3PHASE LAG PLUS
LEAD ONLY FULLY STATIC AMR COMPATIBLE TRI-VECTOR ENERGY METERS FOR 11 KV
FEEDER.
1.0 SCOPE
Design, manufacturing, testing, supply and delivery of AC, 3 Phase, 4 Wire, CT,PT operated lag plus
lead only fully Static and AMR compatible Tri-Vector Energy Meters for measurement of different
electrical parameters listed elsewhere in the document including Active Energy (kWh/MWh), Reactive
Energy (kVArh/MVArh), Apparent Energy (kVAh/MVAh) etc.
2.0 APPLICATION
FEEDER METER – Category “A”
3.0 STANDARDS TO WHICH METERS SHALL COMPLY
IS-14697:1999(2004) Specification for AC Static Transformer operated Watt Hour & VAR-Hour meters
(class 0.5S);
IS-15959:2011 Data Exchange for Electricity Meter Reading Tariff & Load Control – Companion
Specification
IEC 62052-11 Electricity metering equipment (AC) –General requirements, tests and test conditions -
Part 11: Metering equipment;
IEC 62053-22 Electricity metering equipment (AC) –Particular requirements - Part-22: Static Meters
for Active Energy (Class 0.5S);
IEC 62053-23 Electricity metering equipment (AC) –Particular requirements - Part-23: Static Meters
for Reactive Energy;
IS 15707 Specification for Testing, evaluation, installation & maintenance of AC Electricity Meters-
Code of Practice.
Guidelines on ―Data Exchange for Electricity Meter Reading, Tariff and Load Control – Companion
Specification‖
IEC 62056-21 Electricity metering: Data exchange for meter reading, tariff and load control- Part 21:
Direct local data exchange
IEC 62056-31 Electricity metering: Data exchange for meter reading, tariff and load control -Part 31:
Local Area Network data exchange
IEC 62056-61 Electricity metering: Data exchange for meter reading, tariff and load control- Part 61:
Object identification system (OBIS)
The equipment meeting with the requirements of other authoritative standards, which ensure equal or
better quality than the standard mentioned above, also shall be considered; in case of conflict the
Guidelines on ―Data Exchange for Electricity Meter Reading, Tariff and Load Control – Companion
Specification‖ enclosed with this document as annexure shall prevail upon.
2 FREQUENCY 50 Hz ± 5%
4 SECONDARY VOLTAGE Suitable for operation from 110V Ph-Ph, (3P, 4W) 63.5V Ph -
RATING N
5 VOLTAGE VARIATION (-) 30% to (+) 20%
9 POWER CONSUMPTION The active and apparent power consumption, in each voltage
circuit, at reference voltage, reference temperature and
reference frequency shall not exceed 1. 5 W and 8 VA.
9.0 CONSTRUCTION
The case, winding, voltage circuit, sealing arrangements, registers, terminal block, terminal
cover & name plate etc. shall be in accordance with the relevant standards. The meter should be
compact & reliable in design, easy to transport & immune to vibration & shock involved in the
transportation & handling. The construction of the meter should ensure consistence performance
under all conditions especially during heavy rains / very hot weathers. The insulating materials used
in the meter should be non-hygroscopic, non-ageing & have tested quality.
The meter should comply latest technology such as Microcontroller or Application Specific
Integrated Circuit (ASIC) to ensure reliable performance. The mounting of the components on the
PCB should compulsorily be Surface Mounted Technology (SMT) type. Power supply component
may be of PTH type. The electronic components used in the meter should be of high quality and
there should be no drift in the accuracy of the meter for at least ten years. The circuitry of the meter
should be compatible with 16 Bit (or better) ASIC with compatible processor and meter should be
based on Digital measuring and sampling technique.
The meter should be housed in a safe, high grade, unbreakable, fire resistant, UV stabilized,
virgin Polycarbonate/ High grade engineering plastic/Thermosetting Plastic casing of projection
mounting type. The meter cover should be transparent, for easy reading of displayed parameters,
and observation of operation indicators. The meter base may or may not be transparent, but it
should not be black in colour. The meter casing should not change shape, size, and dimensions
when subjected to 200 hrs on UV test as per ASTMD 53. It should withstand 650 deg. C. glow wire
test and heat deflection test as per ISO 75.
Meters must be supplied with 2 (two) nos. manufacturers‘ seals between meter base and meter
cover at both the sides.
Both the communication port (Optical and RS 485 port) should have proper sealing
arrangement.
The bidder shall submit relevant documents (collected form Meter Manufacturer) regarding the
procurement of polycarbonate material. The polycarbonate material of only the following
manufacturers shall be used.
a) G.E. Plastics/Sabic: LEXAN 943A or LEXAN 143 or equivalent for Meter & Terminal cover,
and LEXAN 503R or 500R or equivalent for base.
d) MITSUBISHI : -Do-
e) TEJIN : -Do-
f) DUPONT : -Do-
The meter cover should be fixed to the meter base (case) with Unidirectional Screws, so that
the same cannot be opened by use of screwdrivers. The meter shall withstand external magnetic
influence as per latest amendments of CBIP Technical Report No. 304.
The terminals in the terminal block shall be of adequate length in order to have proper grip of
conductor with the help of screw adjustable metal plates to increase the surface of contact and reduce
the contact resistance. The screws shall have thread size not less than M 4 and head having 4-6mm.
diameters. The screws shall not have pointed ends at the end of threads. All terminals and
connecting screws should be of tinned/nickel plated brass material.
The internal diameter of terminal hole should be minimum 5.5 mm. The holes in the
insulating material shall be of sufficient size to accommodate the insulation of conductor also.
The meter shall be suitable designed for satisfactory operation under the hot and
hazardous tropical climate conditions and shall be dust and vermin proof. All the parts and surface,
which are subject to corrosion, shall either be made of such material or shall be provided with such
protective finish, which provided suitable protection to them from any injurious effect of excessive
humidity.
Fully assembled and finished meter shall under go ‗burn-in‘ test process for 24 Hours at 55
degree Celsius (Max. temperature to not exceed 60 degree Celsius) under base current (Ib) load
condition.
Test points should be provided to check the performance of each block/stage of the meter
circuitry.
RTC shall be synchronized with NPL time at the time of manufacture. Meters testing at
intermediate and final stage shall be carried out with testing instruments, duly calibrated with
reference standard, with traceability of source and date.
Meter shall have Scroll Lock facility to display any one desired parameter continuously
from display parameters.
Auto display cycling of each parameter should be minimum 10-12 Seconds. The time
between two auto display cycles shall be 100-120 sec. OBIS code in display is not required.
It should be possible to easily identify the single or multiple displayed parameters through
symbols/legend on the meter display itself or through display annunciation.
AUTO MODE:
i) LCD Test
i) Meter Sl No
The register shall be able to record and display starting from zero, for a minimum of 2500
hours, the energy corresponding to rated maximum current at reference voltage and unity power
factor. The register should not roll over in between this duration.
High resolution registers required in display min 4 digits (for kWh) and 6 digit (for MWh)
after decimal in case of Energy.
No decimal is required for main KWh, KVAh, KVarh (lag & lead) display. If display is in
MWH, digits after decimal may go up to KWH registration.
Push button mechanism should be of high quality and should provide trouble free service for
a long span of time. Up and Down scrolling facility should be there for Push Button Mode. If there is
separate button for MD reset, it should also have scrolling facility.
MD RESET OPTION
i) Billing Date at 00:00 Hrs of 1st day of the Month (Programmable)
ii) Push button
iii) By Authenticated Command from BCS through HHU or directly from PC/REMOTE
MD reset button should have proper sealing arrangement. Specific operation should be
available in downloading data.
16.0 PERFORMANCE UNDER INFLUENCE QUANTITIES
The meters performance under influence quantities shall be governed by IS 14697:1999
(2004). The accuracy of meter shall not exceed the permissible limits of accuracy as per standard IS
14697:1999(2004).
The clock day/date setting and synchronization shall only be possible through
password/Key code command from one of the following:
a) Hand Held Unit (HHU) or directly through BCS and this shall authentication from BCS
for individual meter.
b) From remote server through suitable communication network with authentication from
BCS.
The software should show electrical conditions existing at the time of reading the meter in
tabular forms as well as in graphical format (Phase diagram) i.e. Phase diagram is required for
voltage, current & PF only.
All the information about energy, maximum demand and their respective TOD register
readings, billing register readings and billing history readings should be shown in a manner which
user can understand quickly, preferably in tabular format.
All the load survey data should be available in numerical as well as graphical format. It
should also be possible to view this data in daily, weekly and monthly formats. The load survey graph
should show the respective values.
All the information about tamper events should be accompanied with date and time
stamping along with the ‗SNAPSHOT‘ (details) of the respective electrical conditions. This information
should be displayed in the sequence in which it happened, in cumulative format as well as in
summary format. The cumulative format should segregate a particular tamper information and
summary report should show count of tamper occurrence, restoration and the duration for which
meter has remained under tamper condition.
In BCS, tamper events must be followed as per Table 32-38 as per IS 15959. However,
final tamper logic will be given at the time of sample testing. Before issuing the purchase order bidder
has to confirm with letter to comply the said tamper logic. In display, first tamper occurrence & last
tamper occurrence & restoration with date & time and total tamper count must be available.
Facility to view data incorporating External multiplying factor due to Installed CTs & PT
should be provided.
The software should be capable of preparing CMRI to read the meter information or to
reconfigure the meter for change the setting of the meter as per IS 15959:2011.
The BCS should have the facility for ASCII conversion of all recorded meter data. There
should be user friendly approach for viewing meter data for the reading collected now or for the
reading collected in the past. All information about a particular consumer should be segregated and
available at one place so that locating any consumer's past data is easy. It should be possible to
locate/retrieve data on the basis of one of the following particulars:
a) Consumer ID/Number.
d) Location.
The BCS shall have multi level password for data protection and security. The first level
should allow the user to enter the system. The different software features shall be protected by
different passwords. The configuration of passwords should be user definable. The software installed
on one PC should not be copy-able on to another PC.
It is very important that the BCS has the feature to export available data to ASCII
format for integrating with the WBSEDCL billing system. Here again a wizard should be
available whereby user can select file format (for ASCII), what data to export, the field width
selection (whether 8 characters or 10 characters, to include decimal point or not, number of
digits after decimal point etc).
Help should be available with the software so that user can use all the features of the
software by just reading the Help contents.
The Fundamental Energy shall be logged in the meter memory and be capable of
downloading to the BCS through the HHU and be available for viewing at the BCS end.
The meter shall also store name plate details as given in the Table - 30 of IS 15959:2011
Both ports shall support the default and minimum baud rate of 9600 bps.
Optical Cord (i.e. Optical Port of Meter to PC) must be USB type.
Data downloading time from meter to HHU/PC should be within 2 min for meter data
(without load survey) and within 6 min for meter data with load survey.
The meters should work even in the presence of any two Potential wires.
Meter should work correctly irrespective of phase sequence.
Tamper details shall be stored in internal memory for retrieval by authorized personnel
through either of the following:
c) Direct by PC.
Meter should have a continuous and clear indication / annunciation in its display if top
cover is removed/open and even refixed (non roll over) and only cover open must be logged in BCS
without any restoration. Auto scroll display may be sacrificed for that COVER OPEN .
Minimum 400 numbers of events preferable (compartment wise) i.e. 200 no. events
for occurrences & 200 no. events for restoration with date & time and snapshot should be
available in the meter memory.
Final tamper Logic and threshold values as per our requirement will be supplied at
the time of Sample Testing. Before issuing the purchase order, Bidder has to confirm with
letter about compliance of the said Tamper Logic within stipulated period.
All the tamper information logged by the meter should be available in BCS with snapshot,
Date & Time as per Table 39 of IS 15959:2011 with occurrence and restoration.
Properly designed meter tamper logic with threshold value, should be provided and clearly
explained in the bid. The tamper logic should be capable of discriminating the system abnormalities
from source side and load side and it should not log / record tamper due to source side abnormalities.
The meter should be able to distinguish between HT PT fuse blowing and Single Phasing and record
the former.
The supplier shall keep the WBSEDCL informed in advance, about the
manufacturing program so that the arrangement can be made for inspection.
The representative / Engineer of the WBSEDCL attending the above testing shall carry out
testing as per relevant standards and issue test certificate approval to the manufacturer and give
clearance for dispatch.
Bidder (collected from Meter Manufacturer) shall furnish following information along with
his bid:
a) Organization structure of the manufacturer and his main sub-suppliers (PCBs, SMT
cards, CT/PT) with details of ‗QA‘ setup, overall workflow.
b) Copy of system manual showing ‗QAP‘ (Quality Assurance Plan) as actually practiced
during manufacturing and final testing.
c) List of raw materials and critical components (ASIC chip, crystal clock, memory
register Chip, transformers, optical ports etc.) with their suppliers and procurement details.
e) Procedure adopted for ‗In-situ‘ testing of PCBs, after placement of surface mounted
component, for quantitative parametric variation of tolerance by self or sub-contractor.
f) Testing and calibration facility, date of calibration of test bench, manpower data of bench
operators;
b) Running at no load
c) Starting current test
d) Limits of error
e) Dial Test
g) Repeatability of error
h) Transportation test
i) Tamper Test
j) Ageing Test
The Bidder (Meter Manufacturer) shall give a detailed list of bought out items with name of
the manufacturer and details about quality control.
34.0 GUARANTEE
Equipment (Meter & CMRI) supplied shall be guaranteed for a period of 5 years from the
date of last despatch. Bidders shall guarantee to replace the meters, which are found to be
defective/inoperative at the time of installation, or become inoperative/ defective during guarantee
period. Replacements shall be effected within 1 month from the date of intimation.
Necessary provision may be kept for fixing the utility seal also.
The manufacturers seal provided with the meter should be of high quality with tamper
proof features.
i ) 3-Phase 4-Wire 11 KV, - /1A. Class of Accuracy 0.5s – 2Nos. (Without Ultrasonic
welding)
ii ) Sample meters shall be submitted along with 1 no. ultrasonically welded (Proto
Type) case and cover. HHU, Power-Pack, Modem along with SIM Card if required, to
be brought at the time of testing of sample meters submitted against the tender.
Offer with all relevant documents for Energy Meter may be submitted with different
make as per Annexure-B alongwith the Bid but after placement of order, drawing for approval
needs to be submitted with only one type of accepted offered Energy Meter.
38.0 SCHEDULES:
The Bidder (collected from Meter Manufacturer) shall submit the following schedules (as
per Standard Format), which is part and parcel of the Specification.
Normally the offer should be as per Technical Specification without any deviation.
But any deviation from Specified Standards, Specified Test Requirement, Technical Specification felt
necessary to improve performance, efficiency and utility of equipment must be mentioned in the
‘Deviation Schedule’ with reasons of such deviation. Such deviation suggested may or may not be
accepted. Deviations not mentioned in Deviation Schedule will never be considered.
Schedule - A
SHEDULE-B
Sl. Component Make / Origin
No. Function / Feature
1 Current Element
2 Measurement /Computing chips
3 Memory chips
4 Display modules
5 Communication modules
6 Optical port
7 Power Supply
8 Electronic components
9 Mechanical parts
10 Battery
11 RTC / Micro controller
SCHEDULE-C
Pre-Qualification Conditions for HT Static Meters
SCHEDULE - D
Sl. LIST OF DOCUMENTS TO BE SUBMITTED
No. DURING SAMPLE SUBMISSION
Component Specifications:
The meters shall be designed and manufactured using SMT (Surface Mount
Technology) components, except for power supply components, LCD etc., which are PTH type.
All the material and electronic power components used in the manufacture of the meter shall be of
highest quality and reputed makes so as to ensure higher reliability, longer life and sustained
accuracy.
Sl. Component
Requirement Make / origin
no. Function / Feature
1. Current Element Current Transformer Any make or origin
conforming to
IS-2705
2. Measurement / The Measurement / computing chips USA:Analog Devices,
computing chips used in the meter should be with the AMS, Cyrus Logic,
Surface mount type. Atmel, SAMES, Texas
Instruments,Teridian,
Japan: NEC,Freescale,
Renesas,
Holland: Phillps
3. Memory chips The memory computing chips should not USA: National Semi
be affected by the external parameters like Conductor, Atmel,
sparking, high voltage spikes or SAMES, Texas
electrostatic discharges. Instruments,Teridian, ST
Japan: Hitachi, OKI,
Freescale, Renesas,
Holland / Korea: Phillps
4. Display modules The display modules should be well Singapore: Bonafied
protected from the external UV radiations. Technologies,
The display should be clearly visible over Korea: Advantek,
an angle of at least a cone of 70o.The Japan : Hitachi, SONY,
construction of the modules should be such Hijing,Truly
that the displayed quantity should not Semiconductor.
disturbed with the life of display. The
display should be TN type industrial grade
with extended temperature range.
IS 15959:2011
2. Current - IR 1.0.31.7.0.255 3
3. Current – IY 1.0.51.7.0.255 3
4. Current – IB 1.0.71.7.0.255 3
NOTES : -
The items at Sl No 5), 6) and 7) are for 3Ф / 4W system of measurement with NEUTRAL as
reference point.
Signed Power factor – (+ indicates lag) and (- indicates lead).
The parameters at Sl No 18) to 22) hold cumulative values at that instant from the date of
manufacturing or installation of meter as the case may be.
The above list is identified for the purpose of communication to HOST or HHU.
The utilities may choose, based on needs, additional parameters for display purpose ONLY.
Item at Sl No 21) refers to the Billing Period Counter
Item at Sl No 23) - Data type to be same as for attribute 2 of IC 8, Clock.
IS 15959:2011
Table 28 : Block Load Survey Parameters for Class C Meters (Required in Class A Meter)
NOTES : -
1 ) The parameters listed in this table are for load survey purpose and are logged as per
the block period time.
2 )The parameters at Sl No 2) to 9) are the average values during the block period time
and stored at the end of that time block.
3 )The parameters at Sl No 10) to 13) are the actual energy consumption during that time
block.
4 )Capture objects for 3 Ф / 4W are items at Sl No 1) to 7) and 10) to 13)
5 )Support for Selective access shall be as defined in Section 11.3
IS 15959:2011
Table 29 : Billing Profile Parameters for Class C Meters (Required in Class A Meter)
23. MD – kW 1.0.1.6.0.255 4 / 2 ,5
NOTES : -
1 ) The data are stored up to 6 billing cycles. The Billing profile is modeled as Profile
generic (IC: = 7) object with OBIS Code 1.0.98.1.0.255. The capture objects of this load profile
are as per Table-29. The capture object values will be copied into buffer of this object either
automatically or asynchronously. The capture period is set to zero, billing action is controlled by
billing dates as provided in 10 and table 31.
2 ) Support for Selective access shall be as defined in Section 11.3
3 ) The current cycle billing parameters shall be readable as the values of the latest
billing period, on demand. This shall be in addition to the last 6 billing period data which shall be
available in the Profile buffer as the last 6 entries in the buffer.
4) The captured attributes in case of Interface Class 4 (Extended register) used for MD
values will be attributes 2 and 5 (Value and Timestamp)
(Clause F-1)
NOTE : - For item Sl No 4), a value of ―0‖ indicates 3P-3W; a value of ―1‖ indicates 3P-4W
(Clause F-2)
NOTES : -
1 . The parameters are programmable by the utility engineers with required access rights.
2 . Unit for Demand Integration Period and profile capture period is in ―seconds‖.
3 . Programming of any of the parameters shall increment the ―Cumulative programming
count‖ value.
Sl No Event ID Descriptions
Sl No Event Descriptions
ID
Sl No Event Descriptions
ID
Sl No Event Descriptions
ID
Sl No Event Descriptions
ID
(Clause G-1.1)
Sl No Event ID Descriptions
Sl No Parameter A B C D E F IC
Tamper Logic:
Feeder Meter CAT A
OCC REST.
TAMPERS Occ Condition REST. CONDITIONS TIME(MIN) TIME(MIN)
1 Missing Vx< 5% Vref Vx> 40% Vref
potential Any other phase voltage > 75% of Any other phase 5
Vref voltage > 75% of Vref
I3x> 10 % of Ib I3x> 10 % of Ib
Missing potential tamper detection
will be phase wise
2 Voltage
Unbalance V3x> 75% Vref V3x> 75% Vref
5
Vmax-Vmin> 30% Vref Vmax-Vmin<30% Vref
I3x> 10 % of Ib I3x> 10 % of Ib
3 Low Voltage Vx< 60% Vref V3x> 70% Vref
5
Current Ignored Current Ignored
4 High Voltage Vx>120% Vref V3x< 120% Vref
5
Current Ignored Current Ignored
Voltage Unbalance should not occur
with high voltage event.
5 Power Failure If power goes off for more than the
persistance time or all phase voltage 5 Immediate
goes less than 30% of Vref
6 Current Open Residual Current >20% Ib Residual Current<20%
Ib
Ix< 2% Ib Ix Ignored
5
Average line Current :Ignored Average Current >
10% of Ib
V3x>60% Vref V3x> 60% Vref
7 Current Bypass Residual Current >20% Ib Residual Current <20%
Ib
Ix>2% Ib Ix Ignored
5
Average line Current :Ignored Average Current >
10% Ib
V3x>60% Vref V3x>60% Vref
8 Current Residual Current < 20% Ib Residual Current <
Unbalance 20% Ib
Imax- Imin > 30% 0f Imax for that Imax- Imin <27% 0f
period Imax for that period
Average Line Current> 10% Ib Average Line Current> 5
10% Ib
In> 5% of Ib In Ignore
V3x>60 % Vref V3x>60 % Vref
Current Unbalance tamper should occur only on activation of Neutral CT
9 Current Ix> 10 % Ib Ix> 10 % Ib
Reversal Direction : Negative Direction: positive
Net Power Factor> 0.5 Net Power Factor> 0.5
5
12 Cover Open On removal of meter cover the meter will log cover open Immediate. No Restoration
event along with date and time.
13 Invalid Phase When Voltage or current sequence is When voltage or No tamper will be logged
Association different. For example: Voltage current sequence is except low pf if satisfied
sequence RYB and Current sequence same after 5 Mins
is YBR
In case of Low and High Voltage Tamper, no current related tamper will be logged except CT Reverse Tamper
V3x= Voltage in All Phases
Vx= Voltage In Any Phase
I3X= Current in All Phases
IX= Current in any phase
SCHEDULE - II
Undertaking from Meter manufacturer
We also confirm that these meters will not be phased out by us in the
next 10 years from the date of supply. Necessary repairs/replacements if
necessary during this period will be made available by us.
Company Seal :
Company Seal :
------------------------------