IEEE
IEEE
IEEE
DESIGN CURRENT
The Regulations indicate the following symbols for use when selecting cables:
is the operating current for the fuse or circuit breaker (the current at
I2
which the fuse blows or the circuit breaker opens)
2. - Choose the type and rating of protective device (fuse or circuit breaker) to be used (In)
7. - The result is the rated current of the cable required, which must be chosen
----- from the appropriate tables
Ambient
Type of insulation
temperature
Number of
Correction factor Cg
circuits
- - Touching Spaced*
Table 4.5 - Derating factors (Ci) for cables up to 10mm² in cross-sectional area
buried in thermal insulation.
50 0.89
100 0.81
200 0.68
400 0.55
In In
Cross conduit conduit In In
Clipped Clipped
sectional in in conduit conduit Volt drop Volt drop
direct direct
area thermal thermal on wall on wall
insulation insulation
3 or 4 2 3 or 4 2 3 or 4 3 or 4
- 2 cables 2 cables
cables cables cables cables cables cables
Table 4.7 - Current ratings and volt drops for sheathed multi-core p.v.c.-insulated cables
3 or 4 3 or 4 3 or 4
- 2 core 3 or 4 core 2 core 2 core 2 core
core core core
U=IxR
1. For line conductors up to and including 16 mm2 , the cpc should be at least the same size.
2. For sizes between 16 mm2 and 35 mm2 , the cpc should be at least 16 mm2 .
3. For sizes of line conductor over 35 mm2 , the cpc should be at least half this size.
Ring circuit
2.5 2.5 30/32
(floor area 100 m2)
A2 radial circuit
4.0 2.5 30/32
(floor area 75 m2)
A3 radial circuit
2.5 1.5 20
(floor area 50 m2)
Light outlet
100 W 50%
(per lamp holder)
10 A, 30% remainder,
Domestic cooker
and 5 A for auxiliary socket
Other stationary
BS current rating or normal current
equipment
Table 4D1A
Single-core 70°C Thermoplastic Insulated Cables, Non-Armoured, with or without Sheath
Ambient Temperature: 30°C
Conductor Operating Temperature: 70°C
Current-carrying Capacity (amperes):
Conductor Reference Method A Reference Method B Reference Method C (clipped direct) Reference Method F (in free air or on a perforated cable tray
cross- (enclosed in conduit in (enclosed in conduit on a horizontal or vertical etc.)
sectional thermally insulating wall wall or in trunking etc.)
Touching Spaced by one diameter
area etc.)
2 cables, 3 or 4 cables, 2 cables, 3 or 4 2 cables, single- 3 or 4 cables, 2 cables, 3 cables, 3 cables, 2 cables, single-phase a.c. or
single-phase three-phase single-phase cables, phase a.c. or d.c. three-phase a.c. single-phase three-phase three-phase d.c. or 3 cables three-phase
a.c. or d.c. a.c. a.c. or d.c. three-phase flat and touching flat and touching a.c. or d.c. a.c. flat a.c. trefoil a.c. flat
a.c. or trefoil flat Horizontal Vertical
1 2 3 4 5 6 7 8 9 10 11 12
2
(mm ) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 10.5 13.5 12 15.5 14 - - - - -
1.5 14.5 13.5 17.5 15.5 20 18 - - - - -
2.5 20 18 24 21 27 25 - - - - -
4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 59 76 68 87 79 - - - - -
25 80 73 101 89 114 104 131 114 110 146 130
35 99 89 125 110 141 129 162 143 137 181 162
50 119 108 151 134 182 167 196 174 167 219 197
70 151 136 192 171 234 214 251 225 216 281 254
95 182 164 232 207 284 261 304 275 264 341 311
120 210 188 269 239 330 303 352 321 308 396 362
150 240 216 300 262 381 349 406 372 356 456 419
185 273 245 341 296 436 400 463 427 409 521 480
240 321 286 400 346 515 472 546 507 485 615 569
300 367 328 458 394 594 545 629 587 561 709 659
400 - - 546 467 694 634 754 689 656 852 795
500 - - 626 533 792 723 868 789 749 982 920
630 - - 720 611 904 826 1,005 905 855 1,138 1,070
800 - - - - 1,030 943 1,086 1,020 971 1,265 1,188
1000 - - - - 1,154 1,058 1,216 1,149 1,079 1,420 1,337
Note:
For cables having flexible conductors, see adjustment factors for current-carrying capacity and voltage drop.
Table 4D2A
Multicore 70°C Thermoplastic Insulated and Thermoplastic Sheathed Cables, Non-Armoured
Ambient Temperature: 30°C
Conductor Operating Temperature: 70°C
Current-carrying Capacity (amperes):
Conductor Reference Method A (enclosed in Reference Method B (enclosed in Reference Method C (clipped direct) Reference Method E (free air or on
cross- conduit in thermally insulating wall conduit on a wall or in trunking a perforated cable tray etc,
sectional etc.) etc.) horizontal or vertical)
area 1 two-core 1 three-core cable* 1 two-core 1 three-core cable* 1 two-core 1 three-core cable* 1 two-core 1 three-core cable*
cable* single- or 1 four-core cable* single- or 1 four-core cable* single- or 1 four-core cable* single- or 1 four-core
phase a.c. or cable, three-phase phase a.c. or cable, three-phase phase a.c. or cable, three-phase phase a.c. or cable, three-phase
d.c. a.c. d.c. a.c. d.c. a.c. d.c. a.c.
1 2 3 4 5 6 7 8 9
2
(mm ) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 10 13 11.5 15 13.5 17 14.5
1.5 14 13 16.5 15 19.5 17.5 22 18.5
2.5 18.5 17.5 23 20 27 24 30 25
4 25 23 30 27 36 32 40 34
6 32 29 38 34 46 41 51 43
10 43 39 52 46 63 57 70 60
16 57 52 69 62 85 76 94 80
Note:
* With or without protective conductor.
Table 4D2B
Voltage Drop (per ampere per metre): Conductor Operating Temperature: 70oC
Conductor Two-core cable d.c. Two-core cable Three- or four-core cable,
cross-sectional area single-phase a.c. three-phase a.c.
1 2 3 4
(mm2) (mV/A/m) (mV/A/m) (mV/A/m)
1 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.8 2.8 2.4
Table 4E1A
Single-Core 90°C Thermosetting Insulated Cables, Non-Armoured, with or without Sheath
Ambient Temperature: 30°C
Current-carrying Capacity (amperes):
Conductor Operating Temperature: 90°C
Table 4E1B
Single-Core 90°C Thermosetting Insulated Cables, Non-Armoured, with or without Sheath
Voltage Drop (per ampere per metre): Conductor Operating Temperature: 90oC
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Conductor Reference Methods C & F (clipped direct, Reference Reference Methods C, F & G
cross- 2 cables, Reference Method on tray or free air) Methods A & B (clipped direct, on tray or in free air)
sectional d.c. A & B (enclosed in
(enclosed in
area conduit or Cables touching, Cables spaced*,
Cables touching Cables spaced* conduit or Cables touching, flat
trunking) trefoil flat
trunking)
1 2 3 4 5 6 7 8 9
(mm2) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
1 46 46 46 46 40 40 40 40
1.5 31 31 31 31 27 27 27 27
2.5 19 19 19 19 16 16 16 16
4 12 12 12 12 10 10 10 10
6 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8
10 4.7 4.7 4.7 4.7 4.0 4.0 4.0 4.0
16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5
r x z r x z r x z r x z r x z r x z r x z
25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.85 0.28 1.85 1.60 0.27 1.65 1.60 1.165 1.60 1.60 0.190 1.60 1.60 0.27 1.65
35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.35 0.27 1.35 1.15 0.25 1.15 1.15 0.155 1.15 1.15 0.180 1.15 1.15 0.26 1.20
50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.99 0.27 1.00 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.180 0.87 0.86 0.26 0.89
70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.73 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.65
95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56 0.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49
120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47 0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.42
150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41 0.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.37
185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36 0.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.33
240 0.190 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31 0.185 0.22 0.29 0.170 0.140 0.22 0.170 0.165 0.24 0.170 0.24 0.29
300 0.155 0.175 0.25 0.31 0.160 0.160 0.22 0.155 0.25 0.29 0.150 0.22 0.27 0.140 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27
400 0.120 0.140 0.25 0.29 0.130 0.155 0.20 0.125 0.24 0.27 0.125 0.22 0.25 0.110 0.135 0.175 0.110 0.160 0.195 0.110 0.24 0.26
500 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26 0.100 0.22 0.24 0.090 0.135 0.160 0.088 0.160 0.180 0.085 0.24 0.25
630 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25 0.088 0.21 0.23 0.074 0.135 0.150 0.071 0.160 0.170 0.068 0.23 0.24
800 0.056 - 0.072 0.150 0.170 0.064 0.24 0.25 - 0.062 0.130 0.145 0.059 0.155 0.165 0.055 0.23 0.24
1,000 0.045 - 0.063 0.150 0.165 0.054 0.24 0.24 - 0.055 0.130 0.140 0.050 0.155 0.165 0.047 0.23 0.24
Table 4E2A
Multi-Core 90°C Thermosetting Insulated Cables and thermoplastic Sheathed Cables, Non-Armoured
1. Where it is intended to connect the cables in this table to equipment or accessories designed to operate at a temperature lower than the maximum operating
temperature of the cable, the cables should be rated at the maximum operating temperature of the equipment or accessory (see Regulation 512.1.5).
2. Where it is intended to group a cable in this table with other cables, the cable should be rated at the lowest of the maximum operating temperatures of any of the
cables in the group (see Regulation 512.1.5).
3. For cables having flexible conductors see section 2.4 of this appendix for adjustment factors for current-carrying capacity and voltage drop.
Table 4E2B
Voltage Drop (per ampere per metre): Conductor Operating Temperature: 90oC
Conductor
Two-core cable d.c. Two-core cable single-phase a.c. Three- or four-core cable, three-phase a.c.
cross-sectional area
1 2 3 4
(mm2) (mV/A/m) (mV/A/m) (mV/A/m)
1 46 46 40
1.5 31 31 27
2.5 19 19 16
4 12 12 10
6 7.9 7.9 6.8
10 4.7 4.7 4.0
16 2.9 2.9 2.5
r x z r x z
25 1.85 1.85 0.160 1.90 1.60 0.140 1.65
35 1.35 1.35 0.155 1.35 1.15 0.135 1.15
50 0.98 0.99 0.155 1.00 0.86 0.135 0.87
70 0.67 0.67 0.150 0.69 0.59 0.130 0.60
95 0.49 0.50 0.150 0.52 0.43 0.130 0.45
120 0.39 0.40 0.145 0.42 0.34 0.130 0.37
150 0.31 0.32 0.145 0.35 0.28 0.125 0.30
185 0.25 0.26 0.145 0.29 0.22 0.125 0.26
240 0.195 0.200 0.140 0.24 0.175 0.125 0.21
300 0.155 0.160 0.140 0.21 0.140 0.120 0.185
400 0.120 0.130 0.140 0.190 0.115 0.120 0.165
Table 4E3A
Single-Core Armoured 90°C Thermosetting Insulated Cables, Non-Magnetic Armour
Ambient Temperature: 30°C
Current-carrying Capacity (amperes):
Conductor Operating Temperature: 90°C
Conductor Reference Method C Reference Method F
crosss- (clipped direct) (in free air or on a perforated cable tray, horizontal or vertical)
sectional Touching Touching Spaced by one cable diameter
area
2 cables, single- 3 or 4 cables, 2 cables, single- 3 cables, three- 3 cables, three- 2 cables, 3 or 4 cables,
2 cables, d.c.
phase a.c. or three-phase phase a.c. or phase a.c. or phase a.c. or d.c. single-phase a.c. three-phase a.c.
d.c. flat a.c. flat d.c. flat d.c. flat trefoil Horizontal Vertical Horizontal Vertical Horizontal Vertical
1 2 3 4 5 6 7 8 9 10 11 12
(mm2) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
50 237 220 253 232 222 284 270 282 266 288 266
70 303 277 322 293 285 356 349 357 337 358 331
95 367 333 389 352 346 446 426 436 412 425 393
120 425 383 449 405 402 519 497 504 477 485 449
150 488 437 516 462 463 600 575 566 539 549 510
185 557 496 587 524 529 688 660 643 614 618 574
240 656 579 689 612 625 815 782 749 714 715 666
300 755 662 792 700 720 943 906 842 805 810 755
400 853 717 899 767 815 1,137 1,094 929 889 848 797
500 962 791 1,016 851 918 1,314 1,266 1,032 989 923 871
630 1,082 861 1,146 935 1,027 1,528 1,474 1,139 1,092 992 940
800 1,170 904 1,246 987 1,119 1,809 1,744 1,204 1,155 1,042 978
1,000 1,261 961 1,345 1,055 1,214 2,100 2,026 1,289 1,238 1,110 1,041
Notes:
1. Where it is intended to connect the cables in this table to equipment or accessories designed to operate at a temperature lower than the maximum operating
temperature of the cable, the cables should be rated at the maximum operating temperature of the equipment or accessory (see Regulation 512.1.5).
2. Where it is intended to group a cable in this table with other cables, the cable should be rated at the lowest of the maximum operating temperatures of any of the
cables in the group (see Regulation 512.1.5).
Table 4E3B
Voltage Drop (per ampere per metre): Conductor Operating Temperature: 90oC
Conductor 2 cables, Reference Methods C & F (clipped direct, on tray or free air)
cross-sectional d.c.
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
area
Touching Spaced* Trefoil and touching Flat and touching Flat and spaced*
1 2 3 4 5 6 7
2
(mm ) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
r x z r x z r x z r x z r x z
50 0.98 0.99 0.21 1.00 0.98 0.29 1.00 0.86 0.180 0.78 0.84 0.25 0.88 0.84 0.33 0.90
70 0.67 0.68 0.200 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.70
95 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58
120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.51
150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.45
185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41
240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37
300 0.155 0.170 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34
400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33
500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31
630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29
800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26
1,000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24
Note:
* Spacings larger than one cable diameter will result in a larger voltage drop.
Table 4E4A
Multicore 90°C Thermosetting Insulated Cables
Air Ambient Temperature: 30°C
Ground Ambient Temperature: 20°C
Current-carrying Capacity (amperes): Conductor Operating Temperature: 90°C
Reference Method E (in free air or on a
Reference Method D (direct in ground or in
Conductor Reference Method C (clipped direct) perforated cable tray etc, horizontal or
ducting in ground, in or around buildings)
cross- vertical)
sectional 1 two-core cable 1 two-core cable 1 two-core cable
area 1 three-or 1 four-core 1 three-or 1 four-core 1 three-or 1 four-core
single-phase a.c. or single-phase a.c. or single-phase a.c. or
cable, three-phase a.c. cable, three-phase a.c. cable, three-phase a.c.
d.c. d.c. d.c.
1 2 3 4 5 6 7
2
(mm ) (A) (A) (A) (A) (A) (A)
1.5 27 23 29 25 25 21
2.5 36 31 39 33 33 28
4 49 42 52 44 46 36
6 62 53 66 56 53 44
10 85 73 90 78 71 58
16 110 94 115 99 91 75
25 146 124 152 131 116 96
35 180 154 188 162 139 115
50 219 187 228 197 164 135
70 279 238 291 251 203 167
95 338 289 354 304 239 197
120 392 335 410 353 271 223
150 451 386 472 406 306 251
185 515 441 539 463 343 281
240 607 520 636 546 395 324
300 698 599 732 628 446 365
400 787 673 847 728 - -
Notes:
1. Where it is intended to connect the cables in this table to equipment or accessories designed to operate at a temperature lower than the maximum operating
temperature of the cable, the cables should be rated at the maximum operating temperature of the equipment or accessory (see Regulation 512.1.5).
2. Where it is intended to group a cable in this table with other cables, the cable should be rated at the lowest of the maximum operating temperatures of any of the
cables in the group (see Regulation 512.1.5).
Table 4E4B
Voltage Drop (per ampere per metre): Conductor Operating Temperature: 90°C
Conductor Two-core cable d.c. Two-core cable, single-phase a.c. Three- or four-core cable, three-phase a.c.
cross-sectional area
1 2 3 4
2
(mm ) (mV/A/m) (mV/A/m) (mV/A/m)
1.5 31 31 27
2.5 19 19 16
4 12 12 10
6 7.9 7.9 6.8
10 4.7 4.7 4.0
16 2.9 2.9 2.5
r x z r x z
25 1.85 1.85 0.160 1.90 1.60 0.140 1.65
35 1.35 1.35 0.155 1.35 1.15 0.135 1.15
50 0.98 0.99 0.155 1.00 0.86 0.135 0.87
70 0.67 0.67 0.150 0.69 0.59 0.130 0.60
95 0.49 0.50 0.150 0.52 0.43 0.130 0.45
120 0.39 0.40 0.145 0.42 0.34 0.130 0.37
150 0.31 0.32 0.145 0.35 0.28 0.125 0.30
185 0.25 0.26 0.145 0.29 0.22 0.125 0.26
240 0.195 0.20 0.140 0.24 0.175 0.125 0.21
300 0.155 0.16 0.140 0.21 0.140 0.120 0.185
400 0.120 0.13 0.140 0.190 0.115 0.120 0.165
Table 4F1A
60°C Thermosetting Insulated Flexible Cables with Sheath, Non-Armoured
Ambient Temperature: 30°C
Current-carrying Capacity (amperes): Conductor Operating Temperature: 60°C
Conductor Single-phase Three-phase Single-phase
cross-sectional a.c. or d.c. a.c. a.c. or d.c.
area
1 two-core cable, 1 three-core, 2 single-core
with or without protective conductor four-core or cable
five-core
1 2 3 4
2
(mm ) (A) (A) (A)
4 30 26 -
6 39 34 -
10 51 47 -
16 73 63 -
25 97 83 -
35 - 102 140
50 - 124 175
70 - 158 216
95 - 192 258
Notes:
1. The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface. If the cable is to be wound on a drum on load the ratings
should be reduced in accordance with Note 2 below and for cables which may be covered, Note 3 below.
2. Flexible cables wound on reeling drums
The current ratings of cables used on reeling drums are to be reduced by the following factors:
a) Radial type drum b) Ventilated cylindrical type drum
ventilated: 85% 1 layer of cable: 85%
unventilated: 75% 2 layers of cable: 65%
3 layers of cable: 45%
4 layers of cable: 35%A radial type drum is one where spiral layers of cable are accommodated between closely spaced flanges; if fitted with solid flanges the ratings
given above should be reduced and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is described as ventilated.
A ventilated cylindrical cable drum is one where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable
ventilating apertures.
3. Where cable may be covered over or coiled up whilst on load, or the air movement over the cable restricted, the current rating should be reduced. It is not possible to
specify the amount of reduction but the table of rating factors for reeling drums can be used as a guide.
Table 4F1B
60°C Thermosetting Insulated Flexible Cables
Voltage Drop (per ampere Conductor Operating Temperature:
per metre): 60°C
Conductor Two-core cable Two-core cable, single- 1 three-core, 2 single-core cables, touching
cross-sectional d.c. phase a.c. four-core or d.c. Single-phase a.c.*
area five-core cable, three-phase
a.c.
1 2 3 4 5 6
2
(mm ) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
4 12 12 10 - -
6 7.8 7.8 6.7 - -
10 4.6 4.6 4.0 - -
16 2.9 2.9 2.5 - -
r x z r x z r x z
25 1.80 1.80 0.175 1.85 1.55 0.150 1.55 - - - -
35 - - - - 1.10 0.150 1.15 1.31 1.31 0.21 1.32
50 - - - - 0.83 0.145 0.84 0.91 0.91 0.21 0.93
70 - - - - 0.57 0.140 0.58 0.64 0.64 0.20 0.67
95 - - - - 0.42 0.135 0.44 0.49 0.49 0.195 0.53
Note:
* A larger voltage drop will result if the cables are spaced.
Table 4F2A
90°C and 180°C Thermosetting Insulated Flexible Cables with Sheath, Non-Armoured (Copper Conductors)
Ambient Temperature: 30°C
Current-carrying Capacity (amperes): Conductor Operating Temperature: 90°C
Conductor Single-phase Three-phase Single-phase
cross-sectional a.c. or d.c. a.c. a.c. or d.c.
area 1 two-core cable, 1 three-core, 2 single-core cables, touching
with or without protective conductor four-core or
five-core
1 2 3 4
(mm2) (A) (A) (A)
4 42 37 -
6 55 49 -
10 76 66 -
16 103 89 -
25 136 119 -
35 - 146 200
50 - 146 200
50 - 177 250
70 - 225 310
95 - 273 369
120 - 316 432
150 - 363 497
185 - 414 567
240 - 487 673
300 - 560 773
400 - - 924
500 - - 1,062
630 - - 1,242
Rating Factor for Ambient Temperature
Ambient Temperature: 35°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C 85°C
Correction Factor: 0.95 0.91 0.86 0.82 0.76 0.70 0.64 0.57 0.50 0.40 0.28
180°C Thermosetting Insulated Cords:
Ambient Temperature: 35°C to90°C 95°C 100°C 105°C 110°C 150°C 120°C 125°C 130°C 135°C
Correction Factor: 1.0 0.96 0.91 0.86 0.81 0.76 0.70 0.64 0.57 0.50
Ambient Temperature: 140°C 145°C
Correction Factor: 0.40 0.28
Notes:
1. The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface. If the cable is to be wound on a drum on load the ratings
should be reduced in accordance with Note 2 below and for cables which may be covered, Note 3 below.
2. Flexible cables wound on reeling drums
The current ratings of cables used on reeling drums are to be reduced by the following factors:
a) Radial type drum b) Ventilated cylindrical type drum
ventilated: 85% 1 layer of cable: 85%
unventilated: 75% 2 layers of cable: 65%
3 layers of cable: 45%
4 layers of cable: 35%
A radial type drum is one where spiral layers of cable are accommodated between closely spaced flanges; if
fitted with solid flanges the ratings given above should be reduced and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is
described as ventilated.
A ventilated cylindrical cable drum is one where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable
ventilating apertures.
3. Where cable may be covered over or coiled up whilst on load, or the air movement over the cable restricted, the current rating should be reduced. It is not possible to
specify the amount of reduction but the table of rating factors for reeling drums can be used as a guide.
4. For 180oC cables, the rating factors for ambient temperature allow a conductor operating temperature up to 150oC. Consult the cable manufacturer for further
information.
5. Where it is intended to connect the cables in this table to equipment or accessories designed to operate at a temperature lower than the maximum operating
temperature of the cable, the cables should be rated at the maximum operating temperature of the equipment or accessory (see Regulations 512.1.5).
6. Where it is intended to group a cable in this table with other cables, the cable should be rated at the lowest of the maximum operating temperatures of any of the
cables in the group (see Regulations 512.1.5).
Table 4F2B
Voltage Drop (per ampere per
Conductor Operating Temperature: 90°C
metre):
Conductor 1 two-core or 2 single-core Two-core cable, single-phase 1 three-core, 2 single-core cables
cross-sectional cables a.c. four-core or touching
area d.c. five-core cable, three-phase
Single-phase a.c.*
a.c.
1 2 3 4 6
2
(mm ) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
4 13.2 13.2 11.1 -
6 8.5 8.5 7.4 -
10 5.1 5.1 4.4 -
16 3.2 3.2 2.7 -
r x z r x z r x z
25 2.03 2.03 0.175 2.04 1.73 0.15 1.73 - - -
35 1.42 - - - 1.22 0.15 1.23 1.44 0.21 1.46
50 1.00 - - - 0.91 0.145 0.93 1.00 0.21 1.02
70 0.71 - - - 0.62 0.14 0.64 0.71 0.20 0.73
95 0.54 - - - 0.47 0.135 0.49 0.54 0.195 0.57
120 0.42 - - - 0.37 0.135 0.39 0.42 0.190 0.46
150 0.34 - - - 0.29 0.130 0.32 0.34 0.190 0.39
185 0.27 - - - 0.24 0.130 0.27 0.27 0.190 0.33
240 0.21 - - - 0.188 0.130 0.23 0.21 0.185 0.28
300 0.167 - - - 0.147 0.125 0.195 0.173 0.180 0.25
400 0.127 - - - - - - 0.132 0.175 0.22
500 0.100 - - - - - - 0.107 0.170 0.20
630 0.074 - - - - - - 0.085 0.170 0.190
Notes:
1. The voltge drop figures given above are based on a conductor operating temperature of 90°C and are therefore not accurate when the operating temperature is in
excess of 90°C. In the case of the 180°C cables with a conductor temperature of 150°C the above resistive values should be increased by a factor of 1.2.
2. *A larger voltage drop will result if the cables are spaced.
Table 4F3A
Flexible Cords, Non-Armoured
Conductor Current-carrying capacity Maximum mass supportable by
cross-sectional twin flexible cord (see Regulations
Single-phase a.c. Three-phase a.c.
area 522.7.2 and 559.6.1.5)
1 2 3 4
2
(mm ) (A) (A) (kg)
0.5 3 3 2
0.75 6 6 3
1 10 10 5
1.25 13 - 5
1.5 16 16 5
2.5 25 20 5
4 32 25 5
Where cable is on a reel see the notes to the table in 4F1A.
Table 4F3B
Voltage Drop (per ampere per meter): Conductor Operating Temperature: 60°C*
Conductor cross-sectional area d.c. or single-phase a.c. Three-phase a.c.
1 2 3
(mm2) (mV/A/m) (mV/A/m)
0.5 93 80
0.75 62 54
1 46 40
1.25 37 -
1.5 32 27
2.5 19 16
4 12 10
Note:
* The tabulated values above are for 60°C thermoplastic or thermosetting insulated flexible cables and for other types of flexible cable they are to be multiplied by the
following factors:
For 90°C thermoplastic or thermosetting insulated 1.09
150°C 1.31
185°C glass fibre 1.43
AWG/Metric Conversion
American Wire Gauge to Metric Conversion – Listed below are some of the most popular strandings, however, many other combinations exist. Resistance figures are
approximate and are given for guidance only.
Table 7A – Example of conductor marking at the interface for additions and alterations to an a.c. installation identified with the
old cable colours
Function Old conductor New conductor
Colour Marking Marking Colour
Line 1 of a.c. Red L1 L1 Brown(1)
Line 2 of a.c. Yellow L2 L2 Black(1)
Line 3 of a.c. Blue L3 L3 Grey(1)
Neutral of a.c. Black N N Blue
Protective conductor Green-and-yellow Green-and-yellow
3 Switch wires in a new installation or an addition or alteration to an existing installation
Where a two-core cable with cores coloured brown and blue is used as switch wires, both conductors being line conductors, the blue conductor should be marked brown
or L at
its terminations.
4 Intermediate and two-way switch wires in a new installation or an addition or alteration to an existing installation
Where a three-core cable with cores coloured brown, black and grey is used as switch wires, all three conductors being line conductors, the black and grey conductors
should be marked brown or L at their terminations.
Outer positive of two-wire circuit derived from three-wire system Red L+ L+ Brown
Outer negative of two-wire circuit derived from three-wire system Red L- L- Grey
Positive of three-wire circuit Red L+ L+ Brown
Mid-wire of three-wire circuit Black M M Blue
Negative of three-wire circuit Blue L- L- Grey
Cable Certifications
Below are the most common European Cable Certifications:
DIN 47100 European Colour Codes
The DIN 47100 standard specifies the core colour of up to 44 cores. Above this it is usual practice to repeat the colours. The first colour is the colour of the base insulation
and the second colour is that of either a longitudinal stripe or printed rings.
British Standards
BS 7629-1 : 1997 Specification for 300 / 500 V fire resistant electric cables having low emission of smoke and corrosive gases when affected
by fire. Multicore cables.
BS 7629-2 : 1997 Specification for 300 / 500 V fire resistant electric cables having low emission of smoke and corrosive gases when affected
by fire. Multipair cables.
BSEN 50266-1 : Common test methods for cables under fire conditions. Test for vertical flame spread of vertically mounted bunched wires
2001 of cables.
BSEN 50267-1 : Common test methods for cables under fire conditions. Tests on gases evolved during combustion of materials from
1999 cables. Procedures. Determination of the amount of halogen acid gas.
BSEN 50267-2-2 : Common test methods for cables under fire conditions. Test on gases evolved during combustion of materials from
1999 cables. Procedures. Determination of degree of acidity of gases for materials by measuring pH and conductivity.
BSEN 60079-1 :
Electrical apparatus for explosive gas atmospheres : Flameproof enclosures ‘d’
2004
BSEN 60332-1-2 : test on electric and optical fibre cables under fire conditions. Test for vertical flame propagation for a single vertical
2004 insulated wire or cable. Procedure for 1kW pre-mixed flame.
BSEN 60332-1-3 : Tests on electric and optical fibre cables under fire conditions. Test for vertical flame propagation for a single vertical
2004 insulated wire or cable. Procedure for determination of flaming droplets / particles.
BSEN 60332 – 2 – Tests on electric and optical fibre cables under fire conditions. Tests for vertical flame propagation for a single vertical
2 : 2004 insulated wire or cable. Procedure for diffusion flame.
BS G 241 : 1988 Specification for fire proof electric cables for engine fire zone and airframe use
German Standards
DIN VDE 0266 Halogen free cables with improved characteristics in the case of fire, with reduced fire propagation and continuance of
Part 3 & 4 isolation for use in the containment of nuclear power plants
DIN VDE 0267 Halogen free cables with improved characteristics in the case of fire, nominal voltages from 6 up to 30kV
DIN VDE 0276
Power cables of nominal voltages 0.6 / 1kV with special fire performance for use in power stations
Part 604
DIN 4102-12 Fire behaviour of building materials and elements – fire resistance of electric cable systems required to maintain circuit
integrity – requirements and testing
DIN 4102-9 Fire behaviour of building materials and elements – seals for cable penetrations ; concepts, requirements and testing
International Standards
IEC 60331-11 Tests for electric cables under fire conditions – circuit integrity – Part 11 : apparatus – fire alone at a flame temperature of at
least 750oC
IEC 60331-12 Tests for electric cables under fire conditions – circuit integrity – Part 12 : apparatus – fire with shock at a temperature of at
least 830oC
IEC 60331-21 Tests for electric cables under fire conditions – circuit integrity – Part 21 : procedures and requirements – cables of rated
voltage up to an dincluding 0.6 / 1.0kV
IEC 60331-23 Tests for electric cables under fire conditions – circuit integrity – Part 23 : procedures and requirements – electric data
cables
IEC 60331-25 Tests for electric cables under fire conditions – circuit integrity – Part 25 : procedures and requirements – optical fibre
cables
IEC 60331-31 Tests for electric cables under fire conditions – circuit integrity – Part 31 : procedures and requirements for fire with shock –
cables of rated voltage up to and includign 0.6 / 1.0 kV
IEC 60332-1-1 Tests on electric and optical fibre cables under fire conditions part 1 : test for vertical flame propagation for a single
insulated wire or cable Section 1 : apparatus
IEC 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1 : test for vertical flame propagation for a single
insulated wire or cable Section 2: procedure for 1kW pre-mixed flame
IEC 60332-1-3 Test on electric and optical fibre cables under fire conditions Part 1 : test for vertical flame propagation for a single insulated
wire or cable Section 3 : procedure for determination of flaming droplets / particles
IEC 60332-2-1 Tests on electric and optical fibre cables under fire conditions Part 2 : test for vertical flame propagation for a single small
insulated wire or cable Section 1 : apparatus
IEC 60332-2-2 Tests on electric and optical fibre cables under fire conditions Part 2 : test for vertical flame propagation for a single small
insulated wire or cable Section 2 : procedure for diffusion flame
IEC 60332-3-10 Tests on electric cables under fire conditions Part 3 : test for vertical flame spread of vertically mounted bunched wires or
cables Section 10 : apparatus
IEC 60332-3-21 Tests on electric cables under fire conditions Part 3 : test for vertical flame spread of vertically mounted bunched wires or
cables Section 21 : category A F/R
IEC 60332-3-23 Tests on electric cables under fire conditions Part 3 : test for vertical flame spread of vertically mounted bunched wire or
cables Section 23 : category B
IEC 60332-3-24 Tests on electric cables under fire conditions Part 3 : test for vertical flame spread of vertically mounted bunched wire or
cables Section 24 category C
IEC 60332-3-25 Tests on electric cables under fire conditions Part 3 : test for vertical flame spread of vertically mounted bunched wires or
cables Section 25 category D
IEC / TR 6222 Fire performance of communication cables installed in buildings
VOLTAGE DROP PER AMPERE PER METER (mV). Conductor operating temperature: 70ºC
Conductor Cross Sectional Area Two Core Cable D.C. Two Core Cable SIngle Phase A.C. Three or Four Core Cable Three phase A.C.
mm mV mV mV
1.5 29 29 25
2.5 18 18 15
4 11 11 9.05
6 7.3 7.3 6.04
10 4.4 4.4 3.08
16 2.8 2.8 2.04
r x z r x z
25 1.75 1.75 0.170 1.75 1.50 0.145 1.50
35 1.25 1.25 0.165 1.25 1.10 0.145 1.10
50 0.93 0.93 0.165 0.94 0.80 0.140 0.81
70 0.63 0.63 0.160 0.65 0.55 0.140 0.57
95 0.46 0.47 0.155 0.50 0.41 0.135 0.43
120 0.36 0.38 0.155 0.41 0.33 0.135 0.35
150 0.29 0.30 0.155 0.34 0.26 0.130 0.29
185 0.23 0.28 0.150 0.29 0.21 0.130 0.25
240 0.180 0.190 0.150 0.24 0.165 0.130 0.21
300 0.145 0.155 0.145 0.21 0.136 0.130 0.185
400 0.105 0.115 0.145 0.185 0.100 0.125 0.160
VOLTAGE DROP PER AMPERE PER METRE (mV). Conductor operating temperature: 70ºc
Conductor Cross-Sectional Area Two Core Cable D.C. TWo Core Cable Single Phase A.C. Three or Four Core Cable Three Phase A.C.
1 2 3 4
Mm Mv MV MV
16 4.5 45 3.9
25 2.9 29 0.175 2.9 2.5 0.150 2.5
35 2.1 2.1 0.170 2.1 1.80 0.150 1.80
50 1.55 1.55 0.170 1.55 1.35 0.145 1.35
70 1.05 1.05 0.165 1.05 0.90 0.140 0.92
95 0.77 0.77 0.160 0.79 0.67 0.140 0.68
120 - - 0.53 0.135 0.55
150 - - 0.42 0.135 0.44
185 - - 0.34 0.135 0.37
240 - - 0.26 0.130 0.30
300 - - 0.21 0.130 0.25
Tables derive from IEE copyright information
PVC INSULATED 600/1000 VOLT CABLES WITH COPPER CONDUCTORS SUSTAINED CURRENT RATING (AMP) (50Hz)
PARAMETERS
600/100 VOLT
Normal Conductor Area
THREE-PHASE SINGLE CORE CABLES IN TREFOIL ARRANGEMENT
mm Direct Armoured Duct Armoured Air Unarmoured Air Armoured
50 203 199 184 193
70 248 241 233 249
95 297 282 290 298
120 337 311 338 347
150 376 342 338 395
185 423 375 450 452
240 485 419 537 532
300 542 459 620 607
700 600 489 722 690
500 660 523 832 776
630 721 563 957 869
800 758 587 1083 937
1000 797 621 1260 1010
APPROXIMATE CURRENT PER LINE OR PHASE TAKEN AT FULL RATED HP BY MOTORS OF AVERAGE EFFICIENCY AND POWER
FACTOR
Motor Rating Direct Current Alternating Current
110V 220V 550V 240V 380V 415V 550V
HP amp amp amp amp amp amp amp
0.5 5.7 2.8 1.1 3
1 10 5 2 6 1.9 1.7 1.3
2 18 9 3.6 10 3.6 3.3 2.5
3 26 13 5.2 15 5.1 4.6 3.5
5 42 21 8.4 24 8 7.3 5.5
7.5 60 30 12 35 11.6 10.6 8
10 80 40 16 46 15.1 13.8 10.4
15 117 59 23 67 22 20 16
20 154 77 31 88 29 27 21
25 190 95 38 110 37 34 26
30 227 114 46 130 43 40 30
40 300 150 60 180 59 54 41
50 375 187 75 210 73 67 50
50 445 223 89 253 87 80 60
60 520 260 104 291 102 94 70
80 600 300 120 332 117 107 81
100 740 370 148 412 145 133 100
125 460 184 515 181 166 125
150 220 217 199 150
175 256 253 232 175
200 292 288 264 199
250 353 323 244
300 421 385 291
Useful three phase formulae:
1. kW = kVA x power factor
Line amps x Line volts x 1.73 x p.f.
2. kW
= 1000
kW
3. kVA =
p.f.
4. Line kW x 1000
amps = Line volts x 1.73 x p.f.
h.p. x 746
6. Line
Line volts x 1.73 x
amps =
Efficiency x p.f.
kW x 1000 x Efficiency
10. h.p. =
746
CURRENT RATINGS OF CABLES CLIPPED DIRECT TO SURFACE OR TRAY BUNCHED AND UNENCLOSED
3 One-Core 1 Three Core
2 ONe-Core D.C. 1 Two Core DV
4 One-Core 1 Four Core
Conductor Size
One Phase A.C. Three Phase A.C. One-Phase A.C. Three Phase A.C.
R P R P R P R P
2
mm amp amp amp amp amp amp amp amp
1 16 13 15 12 14 12 12 10
1.5 21 16 19 15 18 15 15 13
2.5 29 23 26 20 24 21 21 18
4 38 30 34 27 31 27 27 24
6 49 38 45 34 40 35 35 30
10 67 51 60 46 56 48 48 41
16 90 38 81 61 72 64 64 54
25 115 89 105 80 96 71 84 62
35 145 109 130 98 115 87 100 72
50 205 175 185 160 170 140 150 125
70 260 220 235 200 210 175 185 155
95 320 270 285 240 255 215 225 190
120 370 310 335 280 300 250 260 215
150 420 355 380 320 335 285 300 250
185 480 405 435 365 385 325 345 280
240 570 480 520 430 450 385 400 335
300 660 560 600 500 520 445 460 390
400 770 680 700 610
500 890 800 800 710
630 1050 910 950 820
DERATING FACTORS
GROUND TEMPERATURE DERATING FACTORS
An (mm2) = (π/4)×dn2
SWG to mm conversion chart
Diameter Area
SWG #
(mm) (mm2)
0 8.230 53.1921
1 7.620 45.6037
2 7.010 38.5989
3 6.401 32.1780
4 5.893 27.2730
5 5.385 22.7735
6 4.877 18.6793
7 4.470 15.6958
8 4.064 12.9717
9 3.658 10.5071
10 3.251 8.3019
11 2.946 6.8183
12 2.642 5.4805
13 2.337 4.2888
14 2.032 3.2429
15 1.829 2.6268
16 1.626 2.0755
17 1.422 1.5890
18 1.219 1.1675
19 1.016 0.8107
20 0.914 0.6567
21 0.813 0.5189
22 0.711 0.3973
23 0.610 0.2919
24 0.559 0.2452
25 0.5080 0.2027
26 0.4572 0.1642
27 0.4166 0.1363
28 0.3759 0.1110
29 0.3454 0.0937
30 0.3150 0.0779
31 0.2946 0.0682
32 0.2743 0.0591
33 0.2540 0.0507
34 0.2337 0.0429
35 0.2134 0.0358
36 0.1930 0.0293
37 0.1727 0.0234
38 0.1524 0.0182
39 0.1321 0.0137
40 0.1219 0.0117
41 0.1118 0.0098
42 0.1016 0.0081
43 0.0914 0.0066
44 0.0813 0.0052
45 0.0711 0.0040
46 0.0610 0.0029
47 0.0508 0.0020
48 0.0406 0.0013
49 0.0305 0.0007
50 0.0254 0.0005