Steps To Program The GST GMC Monitoring Software
Steps To Program The GST GMC Monitoring Software
Steps To Program The GST GMC Monitoring Software
Preparation:
1. The auto‐cad drawing must be exported to jpeg or bmap extension file.
The project data base must be the currently viewed in the GSTDef programming tool and must be saved
properly before closing the application.
2. Install the GSTGMC software, by double click the GSTGMC_Setup.exe and follow the instructions. Click
Start>All Programs>GSTGMC2.0 Graphic Monitor Center>GSTGMC2.0 Server and Click Register. (To get the
Register code, please send by mail to GST office the User Code together with the SO Number ) For software
demo use “Debug Use”
Procedures:
1. Open the Graphic Designer by clicking the GSTGMC2.1 Graphic Designer
2. The graphic designer window will pop‐up
Type the project name and attached project photo if required, click the to browse the location .Then
click OK
4. Then setup the zone by clicking the icon – ““Create a zone”. Type the zone name and attached zone photo
in the “Project picture”, click the to browse the location .Then click OK. To set‐up another zones, repeat
the procedure.
5. After set‐up the number of zones required. Select the zone to be configured
Note: Ensure that zone back picture is the proper floor plan.
6. Then in the drop down button, select the FACP, Loop and Zone.
Note: If there are two or more selections in the drop down, select the required proper one.
7. Select, drag and paste each device to the required location, note that the device placed on the photo will
removed from the devices list.
8. Use the Device edit to arrange the devices location and size.
9. Repeat the procedures 7 to 10 till the all the zones are completed.
10. Click the save icon once configuration was done.
11. Click the ‐ “Describe a project” then click OK. This command is very important, the project must be
described so that the system will identify which photo and GST data base are being used for this program.
12. Exit the Graphic Designer window
13. Open the SERVER by clicking the GSTGMC2.1 SERVER
14. The SERVER window will pop‐up
15. There are two communications to be configured the “Fire Controller” and the “Client”
17. Then dialog window will pop‐up
Note: by default there was the configured panel, please select and click “DELETE”
To configure the new panel, click the “ADD” and the System configuration window will pop‐up.
Select the Serial Port number, select the correct part number of the control panel and the address of the
control panel to interface with. Then click OK also in the Dialog.
With communication from the panel
No communication with the panel
To configure the new panel, click the “ADD” and the User Define window will pop‐up.
Type the User name and the password. Select the type of server connection (LOCAL‐ the server and the client
are working in the same PC, REMOTE – the client is from the other PC which is connected through LAN). Click
the type of privilege. Then click OK also in the user define.
21. Click the to start the communication from the server.
24. The Login window will pop up to confirm the password, the click LOGIN
Note: if the type of connection from the server is LOCAL on the Server Login type “localhost” and if it is REMOTE
type the IP address of the server PC.
The initial CLIENT window will pop up and updating the configuration.
25. Once the updating is done. The MONITORING window will pop‐up