Steps To Program The GST GMC Monitoring Software

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Steps to program the GST GMC Monitoring Software

 
Preparation: 
1. The auto‐cad drawing must be exported to jpeg or bmap extension file. 
The project data base must be the currently viewed in the GSTDef programming tool and must be saved 
properly before closing the application. 
 
2.  Install the GSTGMC software, by double click the GSTGMC_Setup.exe and follow the instructions. Click 
Start>All Programs>GSTGMC2.0 Graphic Monitor Center>GSTGMC2.0 Server and Click Register. (To get the 
Register code, please send by mail to GST office the User Code together with the SO Number ) For software 
demo use “Debug Use” 
 

 
 

 
Procedures: 
 
1. Open the Graphic Designer by clicking the GSTGMC2.1 Graphic Designer  
 

 
 
2. The graphic designer window will pop‐up 
 
 
 
 
 
 
 

3. To setup the project,  click the    icon – “Create a project”. 

Type the project name and attached project photo if required, click the    to browse the location .Then 
click OK 
 
 
 
4. Then setup the zone by clicking the   icon – ““Create a zone”. Type the zone name and attached zone photo 

in the “Project picture”, click the    to browse the location .Then click OK. To set‐up another zones, repeat 
the procedure.  

 
5. After set‐up the number of zones required. Select the zone to be configured 
 

 
Note: Ensure that zone back picture is the proper floor plan. 
 
6. Then in the drop down button, select the FACP, Loop and Zone. 
Note: If there are two or more selections in the drop down, select the required proper one. 
 

 
 
7.  Select, drag and paste each device to the required location, note that the device placed on the photo will 
removed from the devices list. 
 

 
 
8. Use the Device edit to arrange the devices location and size. 
 
  
9. Repeat the procedures 7 to 10 till the all the zones are completed. 
10. Click the save icon  once configuration was done. 
11. Click the   ‐ “Describe a project” then click OK. This command is very important, the project must be 
described so that the system will identify which photo and GST data base are being used for this program. 
 

 
 
 
 
12. Exit the Graphic Designer window  
 
13. Open the SERVER by clicking the GSTGMC2.1 SERVER  
 
 

 
 
14. The SERVER window will pop‐up 
 
 
 
15. There are two communications to be configured the “Fire Controller” and the “Client” 

16. First configure the “Communication with the controller” by clicking the   icon‐Config, then it will asked 


for the password. (Note: default no password just click OK) 
 

 
 
 
17. Then dialog window will pop‐up 
 

 
 
Note: by default there was the configured panel, please select and click “DELETE” 
 
To configure the new panel, click the “ADD” and the System configuration window will pop‐up.  
 
 
 
Select the Serial Port number, select the correct part number of the control panel and the address of the 
control panel to interface with. Then click OK also in the Dialog. 
 

18. Then click the   icon to start the communication of the computer and the panel. 


Note: The colour green indicates there is a communication otherwise red no communication. 
 

 
With communication from the panel 

 
No communication with the panel 
 
 

19. Second configure the “Communication with Clients” by clicking the   icon‐Config, but incase 


the icon is hidden click the   . Then, it will ask for the password. (Note: default no password 
just click OK) 
 
 
 
20. Then the User Define window will pop‐up 
 

 
 
To configure the new panel, click the “ADD” and the User Define window will pop‐up.  
 

 
 
Type the User name and the password. Select the type of server connection (LOCAL‐ the server and the client 
are working in the same PC, REMOTE – the client is from the other PC which is connected through LAN). Click 
the type of privilege. Then click OK also in the user define. 
 
21. Click the   to start the communication from the server. 
 

22. Close the server window but do not EXIT the system. In the right corner of tool bar the   is showed 


indicates that the server is running. 
 
 
23. Open the Client by clicking the GSTGMC2.1 CLIENT  
 

 
 
24. The Login window will pop up to confirm the password, the click LOGIN 
 

 
 
Note: if the type of connection from the server is LOCAL on the Server Login type “localhost” and if it is REMOTE 
type the IP address of the server PC.   
 
The initial CLIENT window will pop up and updating the configuration. 
 

 
 
 
 
25. Once the updating is done. The MONITORING window will pop‐up 
 