Manual n2000 v30x H English
Manual n2000 v30x H English
Manual n2000 v30x H English
The function to be used in each channel of I/O is defined by the user Note: Even when the execution of the program is interrupted,
in accordance with the options shown in the Table 2. the control output remains active and controlling the process at
the point (Setpoint) of interruption. The program will resume its
I/O FUNCTION I/O TYPE CODE normal execution starting from this same point when the digital
No function - OFF input is closed.
The alarm functions are described in Table 3. The analog output signal is scaleable, with the output range
determined by the values programmed in the parameters “SPLL”
TYPE PROMPT ACTION and “SPkL”. To obtain a voltage output, connect a resistor shunt to
Disabled off No active alarm. This output can be used as a the current output terminals.
digital output to be set by the serial
It is possible to obtain a voltage output by installing a resistor shunt
communication.
(550 Ω max.) to the current output terminals (terminals 7 and 8). The
Sensor Break ierr Alarm will be ON if PV sensor breaks, input signal actual resistor value depends on the desired output voltage span.
(input Error) is out of range or Pt100 is shorted.
Event Alarm rs Can be activated at a specific segment of ramp SOFT START
(ramp and and soak program. The soft-start feature avoids abrupt variations in the power delivered
Soak) to the load regardless of the system power demand.
Low Alarm lo PV This is accomplished by defining a limiting ramp for the control output.
SPAn The output is allowed to reach maximum value (100 %) only after the
High Alarm time programmed (in seconds) in the soft-start parameter has elapsed.
ki PV
SPAn
The Soft-start function is generally used in processes that require slow
start-up, where the instantaneous application of 100 % of the available
LOW difl PV PV
power to the load may cause damages to parts of the system.
Differential SV - SPAn SV SV SV - SPAn
s s
Output T1 T2 T1
The LDB is useful in system supervision and troubleshooting, allowing
Alarm Event early detection of problems in the actuator, power source or load.
Table 4 - Advanced Timer Alarm.
KEY FUNCTIONS
The LEDs associated to the alarms will light when the alarm Both the key digital input can be programmed to execute
condition is recognized, not following the actual state of the output, functions RVN , RSP, kPRG, PR1 shown in Table 2. The key
which may be temporarily OFF because of the temporization. function is configured in parameter (fFvn).
ALARM INITIAL BLOCKING KEY
The initial blocking option inhibits the alarm from being recognized if The key in front panel executes function 6 of Table 2:
an alarm condition is present when the controller is first energized. Auto/Manual mode change. Operation of this key is enabled in
The alarm will actuate only after the occurrence of a non alarm parameter mAN. The MAN indicator lights when the manual control
condition followed by a new occurrence for the alarm. mode is selected.
The initial blocking is disabled for the sensor break alarm function.
EXTRA 24 VDC POWER SUPPLY – AUXILIARY P.S.
SQUARE ROOT EXTRACTION The controller provides a voltage power supply of 24 Vdc to excite
Available when input type 19 is selected. The indicator displays the field transmitters with 25 mA current capacity. Available at the back
square root of the current signal input applied to terminals 22 and 24. panel terminals 17 and 18.
USB INTERFACE
The USB interface is used for CONFIGURING or MONITORING the
controller. The NConfig software must be used for the configuration.
It makes it possible to create, view, save and open configurations
from the equipment or files in your computer. The tool for saving and
opening configurations in files makes it possible to transfer
configurations between pieces of equipment and to make backup
copies. For specific models, the NConfig software also makes it
possible to update the firmware (internal software) of the controller
through the USB.
For MONITORING purposes you can use any supervisory software
(SCADA) or laboratory software that supports the MODBUS RTU
communication on a serial communications port. When connected to
the USB of a computer, the controller is recognized as a conventional
serial port (COM x). Use the NConfig software or consult the
DEVICE MANAGER in the Windows CONTROL PANEL to identify
the COM port that was assigned to the controller. Consult the
mapping of the MODBUS memory in the controller’s communications
manual and the documentation of your supervisory software to
conduct the MONITORING process.
Follow the procedure below to use the USB communication of the
Fig. 1 - Back panel terminals
equipment:
1. Download the NConfig software from our website and install it on RECOMMENDATIONS FOR INSTALLATION
your computer. The USB drivers necessary for operating the
• Input signal wires should be laid out away from power lines and
communication will be installed together with the software.
preferably inside grounded conduits.
2. Connect the USB cable between the equipment and the
• Instrument mains (line) supply should be suitable for this purpose
computer. The controller does not have to be connected to a
power supply. The USB will provide enough power to operate the and should not be shared.
communication (other equipment functions cannot operate). • In controlling and monitoring applications, possible consequences
3. Open the NConfig software, configure the communication and of any system failure must be considered in advance. The internal
start recognition of the device. alarm relay does not warrant total protection.
• Use of RC filters (47 R and 100 nF, serial) are highly recommended
The USB interface IS NOT SEPARATE from the when driving solenoids, contactor coils or other inductive loads.
signal input (PV) or the controller’s digital inputs and
outputs. It is intended for temporary use during ELECTRICAL CONNECTIONS
CONFIGURATION and MONITORING periods. For
the safety of people and equipment, it must only be
used when the piece of equipment is completely
disconnected from the input/output signals. Using the
USB in any other type of connection is possible but If high voltage is applied to
requires a careful analysis by the person responsible a low voltage input,
irreversible damage will
for installing it. When MONITORING for long periods occur
of time and with connected inputs and outputs, we Fig. 2 – High and Low Voltage AC power wiring
recommend using the RS485 interface, which is
available or optional in most of our products. INPUT CONNECTIONS
It is important that they are very well connected; the sensor wires
must be well fixed in the terminals of the rear panel.
INSTALLATION/ CONNECTIONS
The controller must be fastened on a panel, following the sequence
of steps described below:
• Prepare a panel cut-out of 45 x 93 mm;
• Remove the mounting clamps from the controller;
• Insert the controller into the panel cut-out;
Fig. 3a – T/C and Voltage wiring Fig. 3b - RTD input wiring
• Slide the mounting clamp from the rear to a firm grip at the panel.
The controller's internal circuits can be removed without undoing the
connections on the back panel. • Thermocouple (T/C) and 0-50 mV
The controller complete set of features is drawn in Fig. 1. The The Figure 3a indicates the wiring for the thermocouple and 0-50 mV
features loaded in a particular unit are shown on its label signals. If the thermocouple wires need to be extended, use
appropriate compensation cables.
• RTD (Pt100):
Figure 3b shows the Pt100 wiring, for 3 conductors. For proper cable
length compensation, use conductors of same gauge and length).
For 4-wires Pt100, leave one conductor disconnected at the
controller. For 2-wire Pt100, short-circuit terminals 22 and 23.
Other functions, including alarms, ramp and soak, timer, digital input, Master Password
etc., may be useful for a better system performance. The parameters The Master Password is intended for allowing the user to define a
are grouped in 7 cycles. new password in the event of it being forgotten. The Master
CYCLE ACCESS
Password doesn’t grant access to all parameters, only to the
Password Change parameter (PAS(). After defining the new
1- Operation Free access parameters password, the protected parameters may be accessed (and
2- Tuning modified) using this new password.
3- R&S Program The master password is made up by the last three digits of the serial
4- Alarms number of the controller added to the number 9000.
Reserved access parameters As an example, for the equipment with serial number 07154321, the
5- Input Configuration
master password is 9 3 2 1.
6- I/Os
7- Calibration CONFIGURATION PARAMETERS
The parameters in the operation level (1st
level) are easily accessed OPERATION CYCLE
through the P key. The access deeper levels use the combination
of Keys:
PV Indication
(Red) PV / SP indication - The upper display shows the
SV Indication current value of PV. The lower display shows the
(BACK) and (PROG) pressed simultaneously control SP value.
(Green)
P
Act Control Action: bla1 This function blocks the alarm at power-up when the
Action rE -Reverse Action usually used for heating. bla2 units is first energized.
Dir -Direct Action usually used for cooling. YES -enables.
bla3
bias Bias function - Allows adding a percentage value bla4 NO -Inhibits this blocking function.
between -100 % and +100 %. to the MV control Blocking
output. Alarm
The value 0 (zero) disables the function. Defines the differential range between the PV value
xya1
at which the alarm is turned on and the value at
Ovll Minimum percentage value for MV (Manipulated xya2 which it is turned off. (In engineering units).
Variable) when in automatic control and PID. Default
Output Low xya3
Limit value: 0.0 %
xya4
Ovxl Maximum percentage value for MV when in Histeresis of
automatic control and PID. Default value: 100.0% Alarm
Output High
Limit
A1t1 Defines the temporization time t1, for the alarms. In
Sfst SoftStart Function – Time in seconds during which seconds.
A2t1
Softstart the controller limits the MV value progressively from The value 0 (zero) disables the function.
0 to 100 %. It is enabled at power up or when the A3t1
control output is activated. If in doubt set zero (zero A4t1
value disables the Soft start function). Alarm Time t1
Sp.a1 Alarm SP: Value that defines the point of activation A1t2 Defines the temporization time t2 for the alarms time
for the programmed alarms with the functions “Lo” or functions. In seconds.
Sp.a2 A2t2
“ki”. The value 0 (zero) disables the function.
Sp.a3 A3t2
Sp.a4 For the alarms configured with Differential type
functions, this parameter defines deviation (band). A4t2
Not used for the other alarm functions. Alarm Time t2
e.rsp Enables remote SP. aven Enable The Key – Enable or disable operation of
Enable YES - Enables the Function the key.
Remote No - Does not enable the Function Yes key enabled.
SP This parameter is not displayed when the remote SP NO key disabled.
selection is defined by a Digital Input.
Defines the signal type for the remote SP. CALIBRATION CYCLE
rsp
Remote 0-20 - Current of 0-20 mA All input and output types are factory calibrated. This cycle should
4-20 - Current of 4-20 mA only be accessed by experienced personnel. If in doubt do not press
SP
0-5 - Voltage of 0-5 V the or keys in this cycle.
0-10 - Voltage of 0-10 V
pass Input of the Access Password.
Parameter displayed when remote SP is enabled.
Password This parameter is presented before the protected
Rsll Remote Set Point Low Limit: Selects the lower range cycles. See item Protection of Configuration.
for indication of the Remote Setpoint.
(alib Allows instrument calibration.
Rsxl Remote Set Point High Limit: Selects the upper YES - Perform calibration
Calibration
range for indication of the Remote Setpoint. NO - Do not perform calibration
IEov Percentage output value that will be transfer to MV Inl( Input Low Calibration. Enter the value corresponding
when the SAFE output function is enabled. If 1eov = Input Low to the low scale signal applied to the analog input.
0, the SAFE output function is disabled and the Calibration See section MAINTENANCE / Input Calibration.
outputs are turned off in the occurrence of a sensor
fail. Inx( Input High Calibration. Enter the value corresponding
Input High to the full scale signal applied to the analog input.
Bavd Serial Communication Baud Rate selection, in kbps:
Calibration See section MAINTENANCE / Input Calibration.
Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2
rsL( Remote SP Low Calibration. Enter the value
prty Parity of the serial communication.
Remote SP corresponding to the low scale signal applied to the
Parity none - Without parity Low remote SP input.
Ewem - Even parity Calibration See section MAINTENANCE / Input Calibration.
0dd - Odd parity
Rsx( Remote SP High Calibration. Enter the value
Addr Slave Address Selection: Identifies a slave in the Remote SP corresponding to the full scale signal applied to the
Address network. The possible address numbers are from 1 High remote SP input.
to 247. Calibration See section MAINTENANCE / Input Calibration.
I/O CYCLE (INPUTS AND OUTPUTS) ovL( Declaration of lower value present at analog output
Output Low See section MAINTENANCE / Input Calibration.
Io 1 I/O 1 Function: Selects the I/O function to be used at Calibration
I/O 1 (relay 1).Refer to Table 2 for functions.
I/O 2 Function: Selects the I/O function to be used at
Ovx( Declaration of upper value present at analog output.
Io 2 Output High See section MAINTENANCE / Input Calibration.
I/O 2 (relay 2). Refer to Table 2 for functions.
Calibration
Io 3 I/O 3 Function: Selects the I/O function to be used at Restores the factory calibration for all input, analog
I/O 3 (relay 3). Refer to Table 2 for functions. rstr
Restore output and remote SP, disregarding modifications
I/O 4 Function: Selects the I/O function to be used at carried out by the user.
Io 4
I/O 4 (relay 4). Refer to Table 2 for functions. YES - Recover original factory calibration parameters
I/O 5 Function: Selects the I/O function to be used at no - Leave as it is (keep current calibration).
Io 5
I/O 5 (relay 5).Refer to Table 2 for functions. Cold Junction Offset Calibration: Sets the cold
(j
Io 6 I/O 6 Function: Selects the I/O function to be used at Cold junction offset calibration.
I/O 6 (relay 6). Refer to Table 2 for functions. Junction
F Key Function: Selects the I/O function assigned to Pas.( Allows defining a new access password (≠0).
f.fnc
the front panel key. Available functions are: Password
off -Key not used; Sets up the Protection Level. See Table 5.
rvn -Start/Stop the controller (RUN function); Prot
rSP -Select remote setpoint; Protection
kprg -Execute/Hold ramp and soak profile;
PR1 -Enable/Disable ramp and soak profile 1.
SP0
SP7 Fig. 11 - Example of two linked programs
T6 T7
T1 T2 T3 T4 T5
time
EVENT ALARM
To enable this event function the alarms to be activated must be
Fig. 9 - Example of a complete ramp and soak profile selected for rS function and are programmed at the PE1 to PE7
To execute a profile with fewer segments just program 0 (zero) for prompts. The number to be programmed at the prompt defines the
the time intervals that follow the last segment to be executed. alarms to be activated.
Note:
SV SP2
SP1 1- When recovering from power outage the controller resumes the
SP3
ramp and soak execution from the beginning of the interrupted
SP0 segment a ramp and soak program:
T1 T2 T3 T4=0
time • Program the tolerance value, SP’s, time and event.
Fig. 10 - Example of a profile with fewer segments. (T4 is set 0) • If any event alarm is required program the ramp and soak event
function.
The program tolerance “Ptol” defines the maximum deviation
between PV and SV for the execution of the profile. If this deviation is • Set the control mode to automatic.
exceeded, the program will be interrupted until the deviation falls to • Enable program execution in “rS “ screen.
within the tolerance band. • Start control at the rvn prompt by selecting YES.
Programming 0 (zero) at this prompt disables the tolerance and the Before executing the program the controller waits for PV to reach the
profile execution will not to be halted even if PV does not follow SV first set point SP0. Should any power failure occur the controller
(time priority as opposed to SV priority). resumes at the beginning of the segment it currently is.
The ramp and soak event function is used to activate alarms at any
segment of program 1. This applies only to program 1.
AUTO TUNE 8) At the output low calibration ovLC prompt, press the and
key until the mA meter reads zero mA. Approach this value from
During auto tune the process is controlled in ON/OFF mode at the above.
programmed SetPoint (SV). Depending on the process
9) Set 100.0 % for the manipulated variable (MV).
characteristics large oscillations above and below SV may occur and
auto tuning may take several minutes to be concluded. 10) At the output high calibration ovkC prompt, press the and
key until the mA meter reads 20 mA. Approach this value
The recommended procedure is as follows:
from below.
• Disable the control output at the rvn prompt by selecting NO. 11) Repeat steps 7) to 10) as necessary.
• Select auto mode operation at the Avto prompt by selecting YES.
• Disable the ramp and soak function (select NO) and program a new PROBLEMS WITH THE CONTROLLER
SV value other than the present PV (close to the desired set point). Connection errors and inadequate programming are the most
common errors found during the controller operation. A final review
• Enable auto tuning at the Atvn prompt by selecting YES.
may avoid loss of time and damages.
• Enable the control output at the rvn prompt by selecting YES.
The controller displays some messages to help the user identify
• The “TUNE” indicator on the display stays lit until the completion problems.
of the automatic tuning process. MESSAGE PROBLEM
• For control output types relay or pulse, the automatic tuning ---- Open input. Without sensor or signal.
calculates the longest suitable period (cycle time (t) for the
PWM output. The cycle time period may be reduced if the nnnn Input signal is beyond the accepted upper limit.
process experiences some oscillation. When driving a SSR, it’s vvvv Input signal is beyond the accepted lower limit.
recommended to set (t = 1 s.
Err1 Configuration or connection problem in the Pt100
• If the automatic tuning does not result in a satisfactory control, Err6 cable
refer to Table 7 for guidelines on how to correct the behavior of
the process. Other error messages displayed by the controller can account for errors
in the input connections or type of selected input non-compliant with the
PARAMETER RESPONSE SOLUTION sensor or signal applied to the input. If errors persist, even after a
Slow Response Decrease review, contact the manufacturer. Inform also the device serial number.
Proportional Band To find out the serial number, press for more than 3 seconds.
Large Oscillation Increase
Slow Response Increase
The controller also has a visual alarm (the display flashes) when the
Integral Rate PV value is out of the range set by spxl and spll.
Large Oscillation Decrease
Derivative Time
Slow Response or Instability Decrease SERIAL COMMUNICATION
Large Oscillation Increase
The controller can be supplied with an asynchronous RS-485 digital
Table 7 - Suggestions for manual tuning of PID parameters communication interface for master-slave connection to a host
computer (master).
CALIBRATION The controller works as a slave only and all commands are started by
INPUT CALIBRATION the computer which sends a request to the slave address. The
addressed unit sends back the requested reply.
All inputs are factory calibrated and recalibration should only be done
by qualified personnel. If you are not familiar with these procedures Broadcast commands (addressed to all controller units in a multidrop
do not attempt to calibrate this instrument. The calibration steps are: network) are accepted but no reply is sent back in this case.
a) Select the input type to be calibrated. CHARACTERISTICS
b) Set the desired upper and lower display limits. • Signals compatible with RS-485 standard. MODBUS (RTU)
c) At the input terminals inject an electrical signal corresponding to a Protocol. Two wire connection between 1 master and up to 31
known indication value a little higher than the lower display limit. (addressing up to 247 possible) instruments in bus topology. The
d) Select the inL( prompt. Through the and keys adjust communication signals are electrically insulated from the rest of
PV so that it matches the injected signal. the device;
e) Inject a signal that corresponds to a value a little lower than the • Maximum connection distance: 1000 meters.
upper limit of the display. • Time of disconnection for the controller: Maximum 2 ms after last
f) Select the ink( prompt. Through the and keys adjust byte.
PV so that it matches the injected signal. • The communication signals are electrically isolated from the rest
g) Repeat steps c) to f) to improve calibration. of the instrument, and can be 1200, 2400, 4800, 9600 and 19200
bps.
Note: When checking the controller calibration with a Pt100
simulator, pay attention to the simulator minimum excitation current • Number of data bits: 8, without parity or pair parity. Number of
requirement, which may not be compatible with the 0.170 mA stop bits: 1
excitation current provided by the controller. • Time to start response transmission: up to 100 ms after
acknowledging the command.
ANALOG OUTPUT CALIBRATION
The RS-485 signals are:
1) Select type 11 or 12 at the I/O5 prompt.
D1 D D + B Bidirectional data line Terminal 25
2) Connect a current meter at the analog output.
D0 D: D - A Inverted bidirectional data line. Terminal 26
3) Disable the auto-tune and soft-start functions. C Ground. Optional connection to
4) Set the output low limit ovLL to 0.0 % and the output high limit Terminal 27
GND improve communication performance
ovkL to 100.0 %.
5) Select the manual mode at the avto prompt.
6) Enable the output at the rvn prompt.
7) At the operation cycle, set the MV to 0.0 %.