Cooling Tower Noise Reduction Presentation - Kinetics PDF
Cooling Tower Noise Reduction Presentation - Kinetics PDF
Cooling Tower Noise Reduction Presentation - Kinetics PDF
70
65
60
55
50
63 125 250 500 1000 2000 4000
Octave Band (Hz)
• Two-speed motor
• Variable frequency drive
• Day-night operation
• On-off cycling noise annoying
• Reducing fan speed by 50%
reduces noise by 8 to 10 dBA
Noise Barrier Walls
• Close as possible to unit
• Clearance for air movement
(restriction or recirculation)
• Maintenance access
• Sound absorbing material
facing noise source
• Barrier must at least block line-
of-sight at receptor
Roof-Top Noise Barrier Wall
Cooling Tower Silencing
Intake Silencers
Octave
63 125 250 500 1000 2000 4000 8000
Band (Hz)
Insertion
6 8 16 29 24 12 11 10
Loss (dB)
Maintenance Issues
• Short plenums provided between
cooling tower fans and silencers
for access
• Silencer material - galvanized
steel
• Zinc-rich paint on exposed welds
• Acoustic media - fiberglass
Casino Cooling Tower Silencers
Cooling Tower Silencing Overview
Summary
• There are several strategies for
reducing cooling tower noise.
• Properly designed silencers can
reduce noise levels by about
10 to 20 dBA without affecting
cooling tower operation.
• Silencers can easily be adapted
to induced-draft cooling towers.