Schematic of FIRE ALARM (ESD or ILSD) & VHF Trans Receiver To VHF RADIO UNIT / PA System or PAGE PHONE

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Schematic of FIRE ALARM (ESD or ILSD) & VHF Trans Receiver to VHF RADIO UNIT / PA System or PAGE PHONE

BRIEF DESCRIPTION OF FIRE ALARM & VHF OPERATION


1. When any VHF Trans receiver press it’s PTT switch and talks , normally all other Trans receivers can listen & reply back by pressing their
PTT switch .
2. Now AS Techno India provides a solution for industrial customer for “FIRE ALARM & VHF ” Users. It is called “FIRE ALARM & VHF
INTERFACE PANEL” .
Customer asks the questions, What is the function of FIRE ALARM & VHF interface ? How to work it ? FIRE ALARM & VHF system is
different function .
We know , The Fire Alarm system is worked for your Fire Safety purpose or any emergency and VHF RADIO sets are worked for Your
communication Purpose at inside the plant premises / factory / industries premises /area . It is working as a Duplex communication
System .
“ FIRE ALARM & VHF interface” functions details are following .
At first we shall want to know , how many zone has Fire Panel ? So that our Interface Panel will be made as the same zone basis and then we
shall make a Prerecorded message player as same Zone of FIRE ALARM PANEL. Pre-recorded message will be play through whole VHF Radios , PA
system or Paging system when actuate the FIRE ALARM input like as MCP or any switch input
The FIRE ALARM, VHF RADIO COMMUNICATION system has Interfaced with Pre-recorded message player .
Pre-recorded announcement message will be play through whole VHF Radios when fire alarm signal will receive at our interface panel and panel would
be provide particulars signal at Pre-recorded driver . So it can play the particular message through whole VHF Radios which it has receive the signal
from FIRE ALARM (ESD) PANEL .
The pre-recorded message player , a VHF Base station and Interface panel are heart of the automatic Fire hazard announcement system .This is
Microprocessor based & it digitally stores voice message .The “FIRE ALARM & VHF INTERFACE PANEL” .
will be installed near the Fire Alarm Panel & will be connected
to the Fire Alarm Panel through Potential Free N.O. contacts. Each
MCP in the plant/ Terminal should have a corresponding “Normally Open
Contact” or Electrically Relay Contact in the panel Which Closes when MCP is actuated .The
“FIRE ALARM & VHF INTERFACE” monitors these Potential free Contacts & when It finds that
any contact has closed because of actuation of corresponding
MCP, It Sends Multiplexed Voice & Data Signal to the VHF Radios PA system
or PA/Paging network for recorded message announcement
throughout the Plant /Terminal /Business Mall /Administrative
building /office etc.
INPIUT: The “FIRE ALARM & VHF INTERFACE” Accepts Potential Free Contacts or any lamp
indication (LED/LAMP) From Fire Alarm System /Gas Monitoring
System /Manual Call Points /Any Pressure Switch (Water /Gas /Oil)
Or any Other Strategically Placed Switch.
OUTPUT: The system monitors the inputs .When it senses
activation of any input ,it plays the pre-recorded message for the
particular location from where input has been activated ,over
output lines .the output lines are interfaced to the existing PA
system PA/Paging /communication system through a control circuit
.The control signal & pre-recorded voice signal are multiplexed &
sent to all PA system, PA -Paging / communication points &the
message is played loudly over the PA /Paging speakers .The
message will be played respectively until the contact is reset
/removed at the actuating point or the zone is isolated .There is
provision depending upon the site requirement .Each message
can be of approximately 6 seconds durations & a total of 32
messages can be stored played back depending upon the
Configuration / capacity of the unit .
Example : In Case Of Fire In TLF/Manager room or any other
location, any person nearby will actuate the existing MCP
/Emergency Bottom Instantaneously the a pre –recorded message
for TLF location will be played over the whole VHF RADIOS /Public Address System /Paging
/communication system .For Fire at TLF/Manager room the
message can be:“EMMERGECY! EMMERGENCY! FIRE AT TLF----TLF ----TLF
Manager room “REPEAT “EMMERGECY! EMMERGENCY! FIRE AT
TLF/ Manager room “REPEAT “………”UNTIL RESET.
SPECIFICATIONS: Type: Microprocessors based.Storage:
Digital; Non-Volatile.Input Supply: 230Volt AC Preferably From UPS
;( Power Consumption = 50VA max)Input Channels: Max 32
contacts.Out put: 8v peak to peak voice signal .Indications:
RECORD LED, PLAYED LEDAudio Monitoring; By Built –in Speaker
(350mw) & speakerMessage duration; 6 Second per Message;
Max. No of Message: 32Enclosure: 16Gauge CRC Metal /Powder
coated- Wall Mounted Type.

1. IT will be installed, the above operation will take place as before. Simultaneously the VHF Radio units all over the location will also
announce the speech signal received from Tran receivers and if the Fire Alarm Zone panel pre-recorded message will be play the all Trans
receiver unit and page phone system and public address system.
2. In-case VHF Radio Set has not available and anybody who does not possess a VHF Tran receiver, but wants to join conversation or reply
back to VHF sets, can go to the nearest page phone, press the page switch and speak. Now all VHF Radios will listen to the page phone
.The conversation is carried out in a way similar to the between to VHF sets. When the page switch on the page phone will act like a PTT
switch on the VHF Tran receiver.
3. When any page phone is used for paging purpose, (i.e. Page switch is operated to make an announcement) it will be heard over the VHF
system. But when two page phones are in conversation through handset, in private mode, the same shall not be heard over VHF system.
4. An optional switch can be provided in any important location to disconnect the speech path between page phone system & VHF system.
When this switch is in “ON” position the page phone system or FIRE ALARM or ESD or ILSD SYSTEM will be connected to VHF system & it
will be disconnected when the switch is in “OFF” position .This switch is useful to avoid transmission of VHF voice over page phone & vice
versa, when it is not required.
5. When the ZONE ALARM SWITCH will be actuated through the Fire Alarm Zone panel or ESD Panel Signal or ILSD Panel then after it will be
send a voice message which it will be play own pre-recorded message the following location or zone and zone message will be heard the
all over the VHF RADIO SETS and PAGE PHONE SYSTEM and PA SYSTEM .
6. Operation Logic : When VHF to PAGE Phone will talk between two system and at this moment any other VHF SET user is required to talk
to other VHF SETS so VHF to page phone conversation will be stop via page phone and it will be stopped up to talking time when both VHF
sets will be conversed .

Make : AS TECHNO INDIA-NEW DELHI-110086


Call : +919968774806 / 8010007506 office : +91-986801640