Temperature Transmitter: Current or Voltage Output, NEMA 4X Enclosures
Temperature Transmitter: Current or Voltage Output, NEMA 4X Enclosures
Temperature Transmitter: Current or Voltage Output, NEMA 4X Enclosures
TEMPERATURE TRANSMITTER
Current or Voltage Output, NEMA 4X Enclosures 4-19/64
[109.29]
2-51/64 4-11/32
4-3/64 [71.09] [110.42]
2X ø13/64 [102.94] ø5-7/64
[ø5.08] ø47/64 [ø129.59]
SLOT [ø18.58]
3-55/64
ø3-5/16 [98.06]
[ø84.07]
1/8 [3.30]
BALL CHAIN GASKET
CONNECTOR 8-51/64
[223.58]
ø3-5/16 2-13/16 4-21/64
[ø84.08] [71.48] [109.91]
ø47/64
[ø18.58]
Duct Mount
Outside Air with
Radiation Shield
BALL CHAIN 1/8 [3.30]
CONNECTOR GASKET 7-3/32
[180.18]
2-15/64 2X ø13/64
5-1/8 [56.60] [ø5.00] 4-17/32
[130.00] [115.00]
27/32
[21.50]
Outside Air without
Radiation Shield
The SERIES BTT Temperature Transmitter offers transmitter output signals with the SPECIFICATIONS
same form and fit as our popular TE thermistor and RTD sensors for building HVAC Temperature Sensor: Pt1000 RTD.
applications. Range: -40 to 140°F (-40 to 60°C).
Temperature Limits: -40 to 140°F (-40 to 60°C).
FEATURES/BENEFITS Accuracy: Voltage: 0 to 60°C: ±0.5°C; -40 to 0°C: ±1.0°C; Current: -20 to 50°C:
Temperature
Transmitters
• Duct, immersion, and outside air models available ±0.5°C; -40 to -20°C and 50 to 60°C: ±0.75°C.
• Radiation shield available for mounting in direct sunlight Response Time: 100 ms.
• Transmitter output allows for longer wire runs than standard thermistor sensors Wetted Materials: All models: 304 SS (probe), polycarbonate (housing); Duct and
immersion models: Neoprene (gasket); Outside air models: Nylon (insert), silocone
APPLICATIONS (O-ring).
• Building automation system temperature monitoring Process Connection: 1/2˝ NPT (immersion models only).
Electrical Connection: Removable terminal block, knocks out for conduit fitting.
Conduit Connection: 1/2˝ NPT.
Probe Lengths: 2.5 to 18˝ (depending on configuration).
MODEL CHART
Power Requirements: 13 to 36 VDC.
Example BTT -D 04 -1 BTT-D04-1 Output Signal: 4 to 20 mA or 0 to 10 VDC (depending on model).
Series BTT Temperature transmitter Enclosure Rating: NEMA 4X (IP66) (immersions models require thermowell).
Mounting D Duct mount Weight: 5.11 oz (145 g) (duct/immersion); 8.4 oz (238 g) (OSA without radiation
Configuration I Immersion mount shield); 1 lb 7.4 oz (663.4 g) (OSA with radiation shield).
O Outside air Agency Approvals: CE.
R Outside air with radiation shield
Probe 25 2.5˝ (required for “O” and “R”
Length models)
04 4˝
06 6˝
THERMOWELLS - WELDED
08 8˝
Insertion
12 12˝
Model Material Length
18 18˝
TE-TNS-N253N-00 304 SS 2.5˝
Output 1 4 to 20 mA TE-TNS-N043N-00 304 SS 4˝
2 0 to 10 V TE-TNS-N063N-00 304 SS 6˝
Options Blank None TE-TNS-N083N-00 304 SS 8˝
FC Factory calibration certificate TE-TNS-N123N-00 304 SS 12˝
NIST NIST calibration certificate TE-TNS-N183N-00 304 SS 18˝