Power Distribution and Utilization
Power Distribution and Utilization
Section A (12)
1. The transmission system may be compare d with with...... (a) Arteries (b) capillaries (c) veins
2. The voltage drop in a doubly fed distributor is ..... than the equivalent singly fed Distributor.
voltages. (a) straight distributor (b) inter connected distributor (c) ring distributor
4. The distributor ring may be fed at ------ point. (a) one point (b) more than one point (c) both
5. The electrical energy produced at the power station is transmitted at very high voltages by—
(a) 3-phase, 3-wire system (b) 3-phase , 4 wire system (c) 132KVA line
6. The over head distribution system generally --- to – times cheaper than under ground
7. The primary distribution circuit is ----- (a) 3-phase, 3-wire system (b) 3-phase, 4 wire system
(c) 11KVA line
8. --------- has made possible to transmit ac power high voltage and utlise it at safe potential.
9. In a.c. Distribution system, the voltage drops are due to the ----
(a) Combined effects of resistance, inductance and capacitance (b) only resistance
(c) Combine effects of resistance and inductance.
10. in dc distribution system, the voltage drops are due to the -------
(a) Combined effects of resistance, inductance and capacitance (b) only resistance
(c) Combine effects of resistance and inductance.
11. The over head distribution conductor has considerably higher current carrying capacity T/F
12. Under ground cable conductor has much lower ------------ than that of overhead conductor
(a) Reactance (b) inductive reactance (c) capacitive reactance
Q2 a) Write the equation of power loss in transmission line.
b) What is the importance of minimum potential on the distributor?
Q4 The load distribution on a two-wire d.c. distributor is shown in Fig. 13.9. The cross-sectional
area of each conductor is 0·27 cm2. The end A is supplied at 250 V. Resistivity of the
wire is ρ = 1·78 μ Ω cm. Calculate (i) the current in each section of the conductor (ii) the two-
core resistance of each section (iii) the voltage at each tapping point.
Q5: Calculate the voltage drop at a distance of 200 m of a 300 m long distributor uniformly
loaded at the rate of 0.75 A per meter.(a)when it is fed from one end at 250 V, (b) when it
is fed from both ends at 250 V. The resistance of each conductor for both go and return is
0.00081Ω