2.DCDU Power Connection Standard and Inspection Key Points - PPTX (2.42MB) ...
2.DCDU Power Connection Standard and Inspection Key Points - PPTX (2.42MB) ...
2.DCDU Power Connection Standard and Inspection Key Points - PPTX (2.42MB) ...
www.huawei.com
2. Check the positive and negative cable is reversed by 4. Check the RRU power connection as well should follow above standard
mistake or, also check the screws tightened at 1.4N.m (there is also logo of standard marked length) like below showing:
or not like below showing:
Page 4
HUAWEI TECHNOLOGIES CO., LTD.
Scenario 2: the loose of tighten connector or the cable exiting
after loosening
Poor fastening of connector lead the contact surface Of the wire decreased, So the
electric resistance increase, after Long-term use of heat lead to burn 。(Q=I²Rt , “R
“ increase,lead the Q increase)
Page 5
HUAWEI TECHNOLOGIES CO., LTD.
RRU/DCDU Power connector installation quality
inspection and rectification guide
1.4 N·m
Page 7
HUAWEI TECHNOLOGIES CO., LTD.
Inspection/Rectification Guide and Photo reference
3. Removing power line of the abnormal parts, Reference installation guide to
install the wires again, replace the damaged connector;
Page 8
HUAWEI TECHNOLOGIES CO., LTD.
Inspection/Rectification Guide and Photo reference
4. Tighten the screws to 1.4 N·m (12.39 lbf·in.) using a torque screwdriver;
1.4 N·m
5. Check whether the wires are securely installed. If the wires are pulled out
a bit or exposed outside the holes, remove and cut the split wires, and then
strip the sheaths and install the wires again.
Page 9
HUAWEI TECHNOLOGIES CO., LTD.
Thank you
www.huawei.com