P
P
P
th
Overload Protection of
RCCBs and Switches
within Consumer Units
Contents
Executive Summary 3
Introduction 4
Pre 18th Edition approach to rated current / overload protection of RCCBs and switches 5
Rated Current derived from maximum demand and diversity 5
InA 5
Inc 5
Overload protection 6
Proposed solutions 12
Conclusion 12
Notes 12
2 Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units
Executive Summary
The rewriting of chapter 53 of BS 7671:2018 IET wiring regulations has highlighted some areas where designers will have to
change their habits when it comes to the selection of consumer units with regard to the rated current of the consumer unit and
the rated current(s) of any RCCBs or switches contained within the assembly.
Electrical designers in the UK have traditionally determined the rated current of residual current circuit breakers (RCCBs) and
switches after taking into account diversity factors. This method is still the accepted practice. However, the wiring regulations
tell us that RCCBs and switches provide no overload protection, therefore, they shall be protected by an overcurrent protective
device. The wiring regulations also tell us that overload protection shall not solely be based on the use of diversity factors of
the downstream circuits and that overload protection of RCCBs or switches shall be selected to according manufacturer’s
instructions.
The electrical manufacturers association (BEAMA²) provide two methods to determine the rated current of switches and
RCCBs within an assembly with respect to their overload protection:
-- Method 1 – ensure that the rated current of the sum of the downstream MCBs1 do not exceed the rated current of the
switch or RCCB when installed within the consumer unit (Inc), or
-- Method 2 – ensure that the rated current of the switch or RCCB in the related assembly circuit in the consumer unit (Inc)
stated by the assembly manufacturer, is not less than the rated current of the upstream overcurrent protective device
(OCPD). For a domestic installation this is likely to be the cut-out fuse rated at 60 A, 80 A or 100 A.
Spare ways offer the potential for future additions to the installation, e.g. additional circuit(s) for electric vehicle charging,
electric showers or hot tubs and therefore method 2 would generally be the most robust method to determine the rated current
of the switch or RCCB in the related assembly circuit within the consumer unit. However even with method 2, consideration
should also be given to the uprating of the supply fuse from 60 A to 80 A, or from 80 A to 100 A to accommodate potential
additional circuits and related increased current demand.
Therefore, the most flexible solution would be a consumer unit with an InA 100 A and Inc 100 A for each RCCB protected
assembly circuit.
Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units 3
Introduction
Changes to BS 7671 18th Edition IET wiring regulations released July 2018 have drawn our attention to the specification of
RCCBs and switches when incorporated into assemblies such as consumer units in relation to overload protection of these
components. This report will highlight the impact of the changes to the regulations on installations, show methods which will
allow compliance to be determined and provide robust product solutions.
Regulation 536.4.3.2 states that RCCBs and switches provide no protection against overload therefore they shall be protected
by an overcurrent protective device (OCPD). The rated current of this OCPD shall be selected according to manufacturer’s
instructions. Regulation 536.4.202 also needs to be taken into account, this states that overload protection shall not solely
be based on the use of diversity factors of the downstream circuits. Again manufacturer’s instructions should be used when
selecting the OCPD.
The wiring regulations take account of the technical substance of agreements reached at CENELEC level in harmonised
documents (HD). The technical intent of HD 60364-5-53 November 2015 was implemented into the 18th Edition which included
Regulation 536.4.3.2 covering overload protection of an RCCB or switch.
4 Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units
Pre 18th Edition approach to rated
current / overload protection of
RCCBs and switches
Before the 18th Edition, the approach was to use the application of diversity factors to determine maximum demand / rated
current and an assumption of overload protection for switches and RCCBs.
Maximum demand is generally calculated with the application of diversity factors. A method to calculate the maximum demand
and apply allowances for diversity can be found in Appendix A of the IET on site guide. This guidance gives methods for
application to the demand current for individual circuits and also guidance for standard arrangements of final circuits from
Appendix H which reads 100% of the current demand of largest circuit +40% of current demand of every other circuit.
In practice this could be a very difficult process for the electrical designer in residential applications as in many cases the
actual load(s) are not fully known at the time of design and are likely to alter a number of times during the expected life of the
installation. For example, on a new house the actual cooker which is to be installed may not have been selected at the time of
design and is likely to be exchanged for a different cooker before the electrical system is updated. Hence it may be prudent to
carry out calculations based upon the rated current of the final circuit protective devices e.g. MCBs¹.
Note: There is no change to the methods employed to calculate the maximum demand for an installation, diversity can still be
taken into consideration.
Once the maximum demand has been established, the required rated current of the assembly (consumer unit) can be
determined (InA).
InA – The rated current of an assembly (consumer unit). This is not necessarily the rating shown in amperes on the incoming
device, and is required to be provided on the consumer unit designation label.
Where a split load arrangement of a main switch supplying two RCCBs is used in order to provide additional protection for a
group of downstream circuits, the rated current of this group of circuits has the symbol (Inc) and also needs to be taken into
account in the same manner as for the complete assembly.
Inc – The rated current of a section within an assembly (assembly circuit). This is not necessarily the rating shown in
amperes on the specific devices within the assembly, and is required to be provided in the technical documentation
supplied with the consumer unit.
Devices are manufactured to their individual product standards, when they are integrated into an enclosure to form an
assembly the assembly (consumer unit) manufacturer carries out further verification of this assembly to determine and validate
the rated values shown in their product information.
Overload protection
Generally, overload protection of RCCBs and switches has been related to the application of diversity.
Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units 5
What the regulations say
As can be seen from the introduction the 18th Edition IET wiring regulations clearly state that:
Regulation 536.4.3.2 states that devices including; RCCBs complying with BS EN 61008 series, switches complying with
BS EN 60947-3 or BS EN 60669-2-4, impulse relays complying with BS EN 60669-2-2 and transfer switching equipment
complying with BS EN 60947-6-1 are used to switch loads or circuits. None of these devices provide protection against
overload, therefore they shall be protected by an overcurrent protective device (OCPD).
For overload protection of RCCBs and switches the rated current of the OCPD shall take account of manufacturer’s
information; in general, the OCPD is installed upstream of the RCCB or switch.
The rated current of a switch or RCCB may also be based on the application of diversity factors to the downstream
circuits according to regulation 311.1 and the rated current of the OCPD shall be selected according to the manufacturer’s
instructions. See also Regulation 536.4.202
Regulation 536.4.202 states that overload protection shall not solely be based on the use of diversity factors of the
downstream circuits. To achieve overload protection of RCCBs or switches, the rated current of the OCPD shall be selected
according to manufacturer’s instructions.
For most residential applications the OCPD will be the supply authority fuse. On multi-residential installations this may be a
fuse or MCB¹ housed in a TP&N board, a fused distribution board, a switched fuse or similar assembly.
Hence RCCBs and switches shall be protected by an OCPD and that overload protection cannot solely be based on the
application of diversity. Both of these regulations state that manufacturer’s instructions (assembly manufacturer’s instructions)
shall be used to determine the rating of the OCPD.
The manufacturers of electrical distribution equipment are therefore required to instruct designers and installers on how to
determine the rated current of the OCPD for both the assembly (InA) and the related assembly circuits (Inc) within it. BEAMA
the leading trade association representing manufacturers of electrical infrastructure products has provided some guidance to
assist manufacturers, designers and installers.
6 Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units
What the electrical product
manufacturers association say
British Electrotechnical and Allied Manufacturers Association (BEAMA) offers guidance on the subject by providing two
methods that can be utilised to establish the rated current for the RCCB or switch.
Method 1
In1 or
The rated current in the assembly circuit Inc(A) of the switch or RCCB
shall be greater than or equal to the sum of the rated current of all the
associated downstream outgoing circuit OCPDs
Inc2 or
Inc2 ≥ In3 + In4 + In5 + In6 + In7
Method 2
In1 or
Have a rated current based upon diversity and a suitably rated overload
protective device conforming to one of the following: a general-purpose
Inc2 ≥ In1
type (gG) fuse to BS 88-3, a circuit breaker to BS EN 60898, a circuit-
breaker to BS EN 60947-2 or a residual current circuit breaker with
integral overcurrent protection (RCBO) to BS EN 61009-1. Inc2 or
In1 ≤ Inc2
Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units 7
Overload protection of RCCBs
and switches when applied to
consumer unit.
If we take a consumer unit application fig 1 where typical circuits may include;
40 A Shower or Garage
32 A Socket Circuit 1
6 A Lighting Circuit 1
6 A Smoke Detectors
Spare
32 A Cooker
32 A Socket Circuit 2
16 A Water Heater
6 A Lighting Circuit 2
Spare
Method 1
With the arrangement in fig 1 and applying method 1, Inc2 refers to the rated current of the RCCB or switch controlling the
assembly circuits contained within the consumer unit and In3, In4 etc. refers the rated current of the MCBs¹ downstream of
these devices.
Spare
Service
Cut-Out
RCCB RCCB Sw/D/I
MCB
MCB
MCB
MCB
MCB
MCB
MCB
MCB
(In12) (In11) (In10) (In9) (Inc3) (In6) (In5) (In4) (In3) (Inc2) (Inc1)
Fig 1: Method 1
Hence for assembly circuit 1 the rating of RCCB 1 should be equal to or greater than the sum of the downstream MCBs
100 A ≥ 40 A + 32 A + 6 A + 6 A
100 A > 84 A
For this arrangement method 1 meets the requirements for overload protection. However, an additional circuit to replace the
blank should be considered.
8 Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units
This is then repeated for assembly circuit 2
For this arrangement method 1 meets the requirements for overload protection. However, the impact of an additional circuit to
replace the blank should be considered.
The same methodology needs now to be applied to the main switch assembly circuit 3
For this arrangement method 1 cannot be used determine overload protection of the main switch. Method 2 should be
considered.
Method 2
When looking at the consumer unit arrangement in Fig 2 and applying method 2, In1 refers to the service cut out fuse and Inc2
is shown as RCCB 1, however it applies equally to RCCB 2 (Inc3) and the main switch (Inc1).
005625.00
Meter
RCCB 2 RCCB 1
6A 16A 32A 32A 100A 6A 6A 32A 40A 100A 100A
Spare
Spare
Service
Cut-Out
RCCB RCCB Sw/D/I
MCB
MCB
MCB
MCB
MCB
MCB
MCB
MCB
(In1)
Fig 2: Method 2
In1 ≤ Inc2
100A ≤ 100A
For this arrangement method 2 can be used to determine overload protection. As the rated current within the assembly of both
RCCB and the main switch are 100 A this method works for all of the assembly circuits. (In1 ≤ Inc3, In1 ≤ Inc1)
There are two types of supply authority service heads currently being used in the UK. The first type will incorporate a 60 A or
80 A cut-out fuse, whilst the second type will incorporate an 80 A or 100 A cut-out fuse. The challenge is to be sure which
size of cut-out fuse is actually installed within the sealed fuse carrier. This could be achieved either by contacting the supply
authority or by allowing for the highest rated current of the cut-out fuse (100 A).
For example with the arrangement shown in Fig 3 with 100 A main switch and 100 A RCCBs, In1 ≤ Inc2 will allow method 2 to
be used for 60 A, 80 A or 100 A supply authority cut-out fuse.
Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units 9
Installations where the upstream
protection is known.
Obviously there are occasions where the upstream protection of the consumer unit is known. Fig 3 is an example of where a
consumer unit is utilised for such an application. To determine overload protection of the RCCBs and switch, the two methods
shown already can be utilised.
Assembly Circuit 3
38A 70A
Meter
RCCB 2 RCCB 1
6A 32A 63A 6A 32A 32A 63A 63A
Spare
Spare
Spare
Spare
Spare
Service
Cut-Out
RCCB RCCB Sw/D/I
MCB
MCB
MCB
MCB
MCB
(In1)
Fig 3
Method 1
RCCB 1 (Assembly Circuit 1)
10 Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units
Method 2 (In1 ≤ Inc2)
For a 60 A cut-out fuse method 2 can be used to determine overload protection, however, for an 80 A or 100 A cut-out fuse
method 2 cannot be used to determine overload protection. This applies equally for an 80 A rated RCCB and main switch
arrangement with an 80 A supply authority fuse.
If we look at the principles applied to conductors on the same installation. The current carrying capacity of a cable for
continuous service under the particular installation conditions concerned (Iz) should be equal to or greater than the rated
current or current setting of protective device (In) represented by the formula Iz ≥ In. This is demonstrated for instance with the
selection of meter tails to BS 6004 for a consumer unit, where a 60 A cut-out fuse is installed it is common for a 16mm² meter
tail to be selected, however where a 100 A cut-out fuse is installed and the cables are clipped direct 25mm² meter tails would
typically be installed. The sizing of these conductors for overload protection is determined by the upstream fuse and not by
using the diversified downstream loads
Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units 11
Proposed Solutions
On installations where the designer is required to make so many assumptions in relation to the characteristics of the loads,
along with the very real prospect of additional circuits in the coming years to provide for example for electric vehicle charging,
ensuring the correct selection of consumer unit is essential.
As can be seen from the examples in the previous section, method 1 is difficult to implement where there is a possibility for an
additional circuit(s) to be added. It is suggested that method 2 is a more robust method for anticipating future demands.
This suggests that the solution where the rated current of the consumer unit InA and the rated current of the related assembly
circuits within the consumer unit Inc are equal to or greater than the rated current of the upstream protection. On installations
where the rated current of the cut-out fuse is not known, it would be prudent to design for the highest rated current of cut-
out fuse i.e. a 100 A fuse resulting in the specification for the split load consumer unit being 100 A InA, with related RCCB
assembly circuits 100 A Inc to provide overload protection for RCCBs and switches in line with the 18th Edition IET wiring
regulations.
Conclusion
With the introduction of the 18th Edition of BS 7671:2018 IET wiring regulations electrical designers will need to ensure that
they specify the correct consumer unit rated currents with regards to overload protection of RCCBs and switches.
This paper has identified two methods which can be implemented to achieve overload protection for RCCBs and switches:
Method 1 – ensure that the sum of the rated current of the downstream MCBs do not exceed the rated current of the switch
or RCCB. This method would need to consider the consequences of any spare ways and later additions.
Method 2 – ensure that the rated current of a switch or RCCB stated by the assembly manufacturer is not less than the
rating of the upstream OCPD. In a domestic installation this could be a 60 A, 80 A or 100 A cut-out fuse.
Notes:
1 ‘MCB’ is used as generic term for a circuit breaker to BS EN 60898.
2 BEAMA, British Electrotechnical and Allied Manufacturers Association.
12 Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units
Hager White Paper - 18th Edition Overload Protection of RCCBs and Switches within Consumer Units 13
Hager Ltd.
Hortonwood 50
Telford
Shropshire
TF1 7FT
hager.co.uk
sales@hager.co.uk
technical@hager.co.uk
hager.ie
customer.service@hager.ie