Da 950065 001

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

DA-950065 001 00 M88 J NOTES:

FOR USE WITH PRESSURE FREE DOUBLE ACTING


REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PNEUMATIC ACTUATOR.

1. THE GENERAL FORM AND COMPONENTS OF THE


LOCAL SHUTDOWN CONTROL CABINET SHALL BE IN
ACCORDANCE WITH VE-133561 AND 34-SAMSS-634.
CONTROL SWITCHES, INDICATING LIGHTS, AND WIRING
TERMINALS SHALL BE INCORPORATED AS SHOWN.
AS PROJECT REQUIREMENT.

2. ALL ELECTRICAL COMPONENTS AND FITTINGS SHALL


BE SUITABLE AND CERTIFIED FOR USE IN A
CLASS 1 DIVISION 2 AREA.

3. ALL INSTRUMENTS INCLUDING THE CABINET SHALL


BE PROVIDED WITH NAMEPLATE INSCRIBE WITH TAG
NUMBER AND SERVICE. TAG NUMBER FOR THE
CABINET SHALL INCLUDE THE SERVICE OF THE
RESPECTIVE VALVE.

4. WIRING AND TERMINALS SHALL BE PROVIDED WITH


MARKERS.

5. THE LOCAL SHUTDOWN CONTROL CABINET SHALL


HAVE THE FACILITY FOR TESTING THE VALVE BY
LIMITED OR PARTIAL MOVEMENT, i.e. TRAVEL TO
PERCENTAGE OF THE FULLY CLOSED POSITION
WHICH IS APPROPRIATE TO THE PROCESS.

6. PNEUMATIC INTERLOCK VALVE (PIV) SHALL HAVE


COMMON ROTATING SHAFT WITH THE MODE SELECT
SWITCH HS-C. "PUSH TO CLOSE" SWITCH HS-A SHALL
BE SHROUDED MAINTAINED TYPE.

7. SOLENOID VALVES AND PNEUMATIC INTERLOCK


VALVE (PIV) ARE SHOWN IN THE NORMAL POSITION.
SOLENOID VALVES SHALL BE AS PER REFERENCE
INSTRUMENT SPECIFICATION SHEET.

8. PRESSURE GAUGES SHALL BE AS PER REFERENCE


INSTRUMENT SPECIFICATION.

9. SHOWN WITH OPTIONAL LOCAL VALVE POSITION


INDICATION LIGHTS AND LIGHT TEST FEATURE.
10. OPTIONAL POLE MOUNTING TO SUIT POLE SIZE OF
:- ROUND UP TO 190 MM DIA. SQUARE UP TO 150
MM DIA.

SCALE:

REV. DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.


NO.
THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION DESIGN REVIEW FOR
UNTIL CERTIFIED AND DATED. CERTIFICATION KEY DRAWINGS

DESIGN CERTIFICATION
DRAWN BY WED CHECKED BY MNL
DATE STARTED 01-27-99 DATE COMPLETED 01-30-99
DISCIPLINE ENGINEER
PROJECT ENGINEER

THIS DRAWING IS NOT TO BE CERTIFIED BY:


USED FOR CONSTRUCTION (NAME)
UNTIL CERTIFIED AND DATED. SIGNATURE DATE

SAUDI ARABIAN OIL COMPANY


REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED
CONSTRUCTION AGENCY
OPERATIONS
OTHER

DRAWING TYPE

LOCAL SHUT-DOWN CABINET PNL


WITH PARTIAL STROKE TEST
DOUBLE ACTING ACTUATOR
LIB. DWG. SAUDI
SAUDIARABIA
ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

M88 J DA-950065 001 00


Saudi Aramco 2615 ENG. (07/93)

VECTOR CADD-03
Copyright©Saudi Aramco 2009. All rights reserved.