Attention:
Risk of electric shock from charged capacitors!
Always disconnect the system from the power supply
and then wait a further 10 minutes before touching
electrical components. The power capacitors take this
time to discharge.
Check the DC bus voltage at the system terminal strip
of the frequency converter by measuring this between
the +DC and -DC terminals (the exact position can
be found in the supplied operating manual of the
frequency converter), between the +DC terminal and
the chassis as well as between the -DC terminal and
the chassis. The voltage must read zero in the case
of all three measurements.
1
Contents
Cont en ts
3
1. Operator controls / arrangement
1st row / 2nd row / 3rd row 1.2 Status indicator (display / light
signals)
The control system is fitted with a three-row display.
1st row:
73ºC 10.4bar 10.3bar The final compression temperature, final compression -
TOTAL RUNNING 4711h
ON-LOAD
pressure and line pressure are permanently displayed
here.
Light signals
4
1. Operator controls / arrangement
The engine speed is displayed in the 2nd row of the alternating with
display. If the menu navigation is displayed, the speed
display is faded out. ... DE-PRESSURISE
[ !____________ ] 1300rpm
Speed in lower controlled range, WARNING START WITH ...
minimum speed not yet reached.
alternating with
[ |!___________ ] 1280rpm ... TIMER CONTROL
Minimum speed reached.
The unit has been switched on and is ready. The
[ ___________"| ] 3650rpm compressor is now waiting for start approval from the
timer (see section 5.3)
Maximum speed reached.
alternating with
READY TO START
... AFTER POWER LOSS
The unit is ready to start and can be switched on
(see section 3.1). A power loss has caused the unit to shut down. The
'automatic restart' function has been selected in the
control menu. The unit now starts automatically after a
WARNING START WITH ... previously set time (see section 5.1.5)
alternating with
The unit has been switched on and is ready. The unit alternating with
starts automatically following the pressure requirement
... AFTER DRYER PRE-RUN
from your system.
The unit has been switched on and is ready. The unit
starts automatically after the dryer pre-run (see section
5.1.3).
5
1. Operator controls / arrangement
OFF-LOAD
OFF-LOAD XXs
The system has been switched off. The unit stops after
the soft-stop time of xx seconds.
The unit has been shut down due to a fault. You will
find explanations of the fault texts in section 6.
MAINTENANCE ELAPSED
6
1. Operator controls / arrangement
!
# +!
$
!
# !
# +!
$ :
: !
$
!
$
TH 08.02.07 13:55:41
[ TIMER CONTROL ] 1 ____________ 00:00 00:00
:
!
# +!
$ 7 ____________ 00:00 00:00 !
#
:
!
#
p2 1 __________ 00:00 00:00 !
$
:
!
$
p2 7 __________ 00:00 00:00
!
#
MIN START TEMP
RUN-ON TIME
1ºC
90s
!
$
!
$ SOFT STOP
VOL.MAX.
30s
2.8m3/min
VOL.MIN. 1.0m3/min
SOFTWARE: DPro-LRS-1.00
!
# +!
$ OUTPUT 4 OFF
!
$
7
1. Operator controls / arrangement
To then fully exit the main menu, you must again press
the !
# +! $ keys at the same time.
Then press the key, the value flashes. You can now
press !# or !
$ to change the value. You must then
press the key again to confirm the value.
8
2. Default settings
Example:
9
3. Operations
3 Oper at io ns
10
4. Maintenance ([MAINTENANCE SCHED.] sub-menu)
11
5. Extended functions
5 Exten de d f un cti on s
5.1 [ CONTROL MENU ] sub-menu Section 5.3.2 contains a description of how to set the
timer for the second pressure range.
The most important parameters of the [ CONTROL MENU ]
Note
menu have already been explained in section 2 Default
settings. This section simply contains an overview and The values shown are examples only. The values used
explanation of additional (extended) functions. in your unit may be different.
12
5. Extended functions
After a power loss that has not exceeded the preset In this operating mode, the compressor may start
time, the unit can re-start automatically. automatically at any time and after an unlimited -
length of power loss. Check the safety notices
The settings needed must be undertaken in the (e.g. EN1012-1, EN60204) that apply in your country
[ CONTROL MENU ] sub-menu. The relevant menu
to find out whether you can run an unlimited autom.
items are:
re-start and what safety precautions must be taken.
AUTO RESTART OFF Always fit the compressor with warning signs, lock
POWER LOSS TIME Xs the room containing the compressor and instruct
START-UP DELAY Xs your staff.
You will find more details about the code in section 5.6
13
5. Extended functions
a) The same warning has occurred three times. Please go to the [ TIMER CONTROL ] sub-menu
where you can use ! # or !
$ to select from seven
b) Warning resulting from final compression different timer units. The status line of each switching
temperature being too high unit is as follows:
c) Warning occurred at 100 running hours. a) b) c) d)
The last eight warning messages or faults recorded are
displayed in the fault memory. All messages/faults
occurring before that are however retained in the long- 1 _______ 00:00 00:00
term memory. The frequency with which a warning or
a) Unit no.
fault occurs is therefore always recorded.
b) Days of the week [SMTWTFS] = Sunday, Monday ..
However you can access more detailed information on
warning messages and faults that have been recorded - c) Switch-in point
in the fault memory. The following are saved for every
warning message/fault recorded: d) Switch-out point
- time and date If there are no days of the week selected in the
- compressor status (e.g. on-load) switching unit line, the switching unit is not active. The
- speed switching unit only becomes active when the day of the
- final compression temperature, final compression week is set. When the is pressed, the first
pressure and line pressure underscore _ starts to flash. You can now use the ! #
key to set the first day of the week (Sunday). Then use
When accessed, these values flash to clearly show the key to confirm the day of the week. The next
that they are not the current display values. underscore _ then starts to flash. If you do not want to
confirm a day of the week as set, please immediately
press . You can run through all seven days of the
week in this way. Once you have confirmed the last day
of the week (Saturday), the first unit of the switch-in -
point starts to flash. You can either set this using ! # or
!$ .
14
5. Extended functions
Once the last unit of the switch-out point has been 5.3.2 Pressure changeover setting
confirmed, the whole timer unit is activated.
Please go to the [ TIMER CONTROL ] sub-menu. There
The next step is to go to the [ CONTROL MENU ] sub- you can use ! # or !$ to select between various timer
menu and then the TIMER CONTROL menu item. You units. The timer units of the 2nd (p2 ) pressure range are
will now see the default setting TIMER CONTROL OFF. in the menu under the normal timer units.
If you press the key, the OFF value starts to flash.
You can now use the ! # key to change the value to ON
. Then please press the key again to confirm the
entry. The timer is now switched on.
Example 1:
p2 TIMER CONTROL
Switching unit 1 not active:
Example 2:
a) b) c) ON-LOAD
15
5. Extended functions
When the is pressed, the first underscore _ starts to c) If an input is programmed on the function [ EXT.
flash. You can now use the ! # key to set the first day of RPM LIMIT ] and its contact is closed, the speed
the week (Sunday). Then use the key to confirm the of the plant will be restricted to the value set here.
day of the week. The next underscore _ now flashes. If
you do not want to confirm a day of the week as set, d) If the final compression temperature reaches
immediately press . You can run through all seven 110 °C, WARNING HIGH TEMP appears in the
days of the week in this way. Once you have confirmed display's third row.
the last day of the week (Saturday), the first unit of the
e) If the final compression temperature reaches
switch-in point starts to flash. You can either set this
120 °C, the compressor shuts down. FAULT
using ! # or !$ . Once the last unit of the switch-out
COMP TEMP then appears in the third row on the
point has been confirmed, the whole switching unit is
display
activated.
f) If the final compression temperature is below 1 °C,
Go to the [ CONTROL MENU ] sub-menu and then the
you cannot start the machine.
p2 TIMER CONTROL menu item. You will now see the
p2 TIMER CONTROL OFF default setting. If you press g) If the compressor is in automatic mode and there is
the key, the OFF value starts to flash. You can now no line pressure requirement, the OFF-LOAD xxs
use the ! # key to change the value to ON. Then please indication appears and the machine goes into off-
press the key again to confirm the entry. The timer is load. After the run-on time, the compressor
now switched on for the second pressure range. Please automatically shuts down and is ready to start
refer to section 5.1.2 for how to set the parameters for again.
the 2nd pressure range.
h) In order to protect the compressor stage, once the
!" key (shut down system) has been pressed, the
In the sub-menu [ LIMIT VALUES ] are the factory- i) The maximum volume flow that may be adjusted in
set and changeable parameters. These represent: relation to the compressor is displayed here.
a) DESIGN PRESS 13.0bar j) The minimum volume flow that may be adjusted in
b) START ProTECT 0.8bar relation to the compressor is displayed here
c) EXT. LIMIT 2500RPM
d) FINAL TEMP WARN 110°C k) You can find the software currently loaded on your
e) FINAL TEMP MAX 120°C unit here.
f) MIN START TEMP 1°C
g) RUN-ON TIME 90s
h) SOFT STOP 30s
i) VOL.MAX. 2.8m3/min
j) VOL.MIN. 1.0m3/min
k) SOFTWARE: DPro-LRS-1.00
Note
alternating with
... DE-PRESSURISE
16
5. Extended functions
17
5. Extended functions
When supplied, output 1 is programmed with the 5.6 Locking / unlocking code
'FAULT' function. The outputs 2..4 are not programmed
upon delivery. Each of the outputs can be programmed Settings (sub-menus) can be locked using a code to
with any of the functions listed below. You can also find prevent unauthorised programming.
an overview of outputs and corresoponding functions in
the circuit diagram of the machine. Limit values cannot be changed by the operator.
Locking
Explanation of functions: If the code is to be locked, this is done using the key.
OFF Please press this key for 5 seconds. The following
Output is not programmed. message then appears on the display:
TIMER
The output (relay) is activated when the compressor is
switched on by the internal timer.
18
5. Extended functions
If you have correctly entered the codes, the machine Fig. 4 Compressor with open switch panel
will have automatically been switched to its delivery
status.
The language has now been reset to English. If you
need a different language, please set this as described
in section 2.1.
19
5. Extended functions
Danger
In this operating mode, the compressor may start 5.8.2 Enabling on-load operation
automatically at any time.
Danger
Attention
In this operating mode, the compressor may start
Only potential-free contacts may be connected to automatically at any time.
the terminal strip. External voltages will destroy the
Attention
DELCOS Pro.
Only potential-free contacts may be connected to
The potential-free contacts must not be more than
the terminal strip. External voltages will destroy the
20 metres away from the terminal strip.
If necessary coupling relays must be fitted in the DELCOS Pro.
control cabinet. The potential-free contacts must not be more than
20 metres away from the terminal strip.
If necessary coupling relays must be fitted in the
control cabinet.
p2 CUT-OUT
CUT-OUT POINT
p2 TARGET
TARGET PRESSURE
p2 TIMER CONTROL PRESSURE
Input X:
2nd pressure
range
p2 TIMER CONTROL
INPUT X:
2nd PR. RANGE
INPUT X:
OPERATE_B1
ON-LOAD
20
5. Extended functions
To do this, go to the [OPTIONAL IN-/OUTPUTS] If the remote start / stop function is activated, you can
menu where you must program one input with the no longer control the machine using the On ! I and !"
OPERATE_B1 function. The unit can now be switched to keys on the DELCOS Pro. Only the emergency off
off-load using the input. button remains activated. The machine can now only be
switched on and off using the potential-free contact.
You will find a circuit diagram in Fig. 6.
2nd option
5.8.3 Remote start / stop
A control room is to decide whether the enable for the
Danger remote start / stop function is issued. The function for
In this operating mode, the compressor may start the enable is implemented using a digital input. If the
automatically at any time. enable is issued, the compressor can only be switched
on and off using the external potential-free contact
Attention (terminals see circuit diagram). If the enable is not
issued, the compressor can only be switched on and off
Only potential-free contacts may be connected to
on the DELCOS Pro.
the terminal strip. External voltages will destroy the
DELCOS Pro. Please connect the potential-free contact that you need
for the remote start / stop function to the corresponding
The potential-free contacts must not be more than
terminals (see circuit diagram). This input is
20 metres away from the terminal strip. If necessary
permanently programmed for the remote start / stop
coupling relays must be fitted in the control
function.
cabinet.
In the [OPTIONAL IN-/OUTPUTS] menu you now
This function allows the operator to externally switch
have to program one input with the ENAB.REM-START
the compressor on and off. You have two ways of
function (see section 5.5.1).
implementing this function. The remote start / stop
function is permanently programmed (terminals see The symbol appears in the first display row. In the
circuit diagram). [ CONTROL MENU ] sub-menu behind the
ENABLE REMOTE-START menu item, EXT. appears.
The unit continues to run while the potential-free
contact is closed. If the contact is opened, the soft-stop If the input is closed, the unit can only be switched on
is undertaken and the unit stops. and off using the potential-free contact.
1st option
21
6. Error rectification
6 Er r or r ectifica tio n
6.1 Safety regulations Please therefore always observe the following checklist:
The faults are shown in the third display row. The red - Circuit diagram drawing no. and ID
light signal on the DELCOS Pro also flashes quickly. - Information about the unit's operating conditions
Faults have to be rectified before the start and then - Information about the accessories your fitted
acknowledged using the key. The unit can now be later on (remote controls etc.)
started again.
- Other conversions/add-ons on your unit
undertaken later on
22
6. Error rectification
23
6. Error rectification
FAULT DIRECT ROT Drive motor running in wrong direction Connect up correct phase sequence
(see circuit diagram)
(2)
FAULT MAINT PER Shutdown maintenance activated and Carry out maintenance and
maintenance interval exceeded by reprogramme interval
(2)
100 hours
FAULT VSD COMMUNIC. Communication to frequency converter Check
disrupted, frequency converter not - Main contactor
responding - ModBus interface wiring
- If no fault can be found, notify
CompAir service engineer.
[FAULT SPEED LOW] Speed is below permissible minimum speed. Notify CompAir Service Engineer.
Oil level too low. Check.
FAULT EXT FAULT Shutdown resulting from external fault Check, find cause.
(3)
(monitored by INPUT: EXT FAULT )
WARNING EXT WARNING Warning from external device Check, find cause
(3)
(monitored by INPUT: EXT WARNING )
FAULT BEKOMAT FAULT Connected condensate drain valve Check, find cause.
(3)
(Bekomat) defective .
WARNING BEKOMAT WARN. Connected condensate drain valve Check, find cause.
(3)
(Bekomat) defective .
(3)
WARNING DRYER WARNING There is an external dryer error Check dryer
(3)
FAULT DRYER FAULT There is an external dryer error Check dryer
FAULT DELCOS DELCOS Pro hardware error Replace DELCOS Pro electronics
WARNING TIMER Wrong date and time setting The real timer must be reset
(see section 2.3).
WARNING LINE PRESS The LINE PRESS is larger than the DESIGN Suppress load requests via the RS485
PRESS + 0.5 bar and simultaneously a load interface if the LINE PRESS is higher
request was given via the RS485 interface. than the DESIGN PRESS + 0.5 bar.
WARNING INPUT 1 One of the reserve inputs 1..5 has been Check the assignment of the input in
(3)
WARNING INPUT 2 activated, but is programmed as FREE. question.
WARNING INPUT 3
WARNING INPUT 4
WARNING INPUT 5
*** COMPAIR *** DELCOS Pro hardware error DELCOS electronics must be replaced,
SETUP-CODE 1:____? as an emergency remedy: enter setup
codes, check all settings and reset if
(2)(3)(4)(5)
necessary
24
6. Error rectification
Pressure and temperature Ground fault or short circuit for sensor B1, Check fuses, changing if necessary
indicator failed, indicator (----) B2 or R2
Incorrect display of volumetric Volumetric flows incorrectly set. Check max. and min. volumetric flow in
flow [LIMIT VALUES] menu
(4)
Unit not automatically starting AUTO RESTART function not activated Activate
after power loss (4)
Power loss lasted too long
Unit runs continuously in off- CONTINUOUS OPERATION operating mode Select AUTOMATIC OPERATION
(4)
load without independently selected operating mode
switching to readiness (standby)
Very brief pressure requirements during the
run-on time
FAULT VSD FAULT xx The frequency converter (VSD) detected a Notify CompAir Service Engineer.
fault with error number xx that was not
subsequently listed.
FAULT VSD FAULT 4 The frequency converter (VSD) detected Check the power supply.
undervoltage.
Check back-up fuses, replace if
necessary
Check main contactor
Check that all connecting terminals and
plugs are tight, retighten if necessary
FAULT VSD FAULT 7 The frequency converter (VSD) detected a Check pressure differential of fine
motor overload separator
Check oil level
Check water content of the oil
FAULT VSD FAULT 8 Frequency converter (VSD) overtemperature Check inlet and outlet filters of switch
cabinet, and replace if necessary
Check that electric motor-driven switch
cabinet and frequency converter fans
are working correctly
Check frequency converter for
blockages in the cooling air supply and
dirty heat sinks
FAULT VSD FAULT 13 The frequency converter (VSD) detected an Check motor winding
FAULT VSD FAULT 38 earth fault at the output
Carry out insulation test
FAULT VSD FAULT 39
FAULT VSD FAULT 40
25
6. Error rectification
FAULT VSD FAULT 41 The frequency converter (VSD) detected a Check motor winding
FAULT VSD FAULT 42 short-circuit at the output
Carry out insulation test
FAULT VSD FAULT 43
FAULT VSD FAULT 64 Frequency converter (VSD) overload Check pressure differential of fine
separator
Check oil level
Check water content of the oil
FAULT VSD FAULT 81 The frequency converter (VSD) received no Check wiring of the Modbus interface
commands from the DELCOS Pro
FAULT E502 An error occurred while the frequency Notify CompAir Service Engineer.
FAULT E503 converter was being programmed.
26
Gardner Denver Deutschland GmbH
Argenthaler Str. 11
55469 Simmern
Germany
www.compair.com