Maintenance of SF6 Gas Circuit Breakers
Maintenance of SF6 Gas Circuit Breakers
Maintenance of SF6 Gas Circuit Breakers
Premium Membership
×
Get Notifications
SM6 10kV switchgear with circuit
breakers by Schneider Electric
Applications for SF6 include gas insulated transmission lines and’gas insulated
power distributions.
The combined electrical, physical, chemical and thermal properties offer many
advantages when used in power switchgears.
SF6 is odorless, colorless, tasteless, and nontoxic in its pure state. It can,
however, exclude oxygen and cause suffocation. If the normal oxygen content
of air is reduced from 21 percent to less than 13 percent, suffocation can
occur without warning. Therefore, circuit breaker tanks should be purged out
after opening.
×
Get Notifications
of rotten eggs. Do not breathe the vapors remaining in a circuit breaker where
arcing or corona discharges have occurred in the gas.
Evacuate the faulted SF6 gas from the circuit breaker and flush with fresh air
before working on the circuit breaker.
c) Physical Properties
SF6 is one of the heaviest known gases with a density about five times the
density of air under similar conditions. SF6 shows little change in vapor
pressure over a wide temperature range and is a soft gas in that it is more
compressible dynamically than air.
The heat transfer coefficient of SF6 is greater than air and its cooling
characteristics by convection are about 1.6 times air.
d) Dielectric Strength
https://electrical-engineering-portal.com/maintenance-of-sf6-gas-circuit-breakers 2/5
10/28/2019 Maintenance Of SF6 Gas Circuit Breakers
SF6 has a dielectric strength about three times that of air at one atmosphere
pressure for a given electrode spacing. The dielectric strength increases with
increasing pressure; and at three atmospheres, the dielectric strength is
roughly equivalent to transformer oil. The heaters for SF6 in circuit breakers
are required to keep the gas from liquefying because, as the gas liquifies, the
pressure drops, lowering the dielectric strength.
.
The exact dielectric strength, as compared to air, varies with electrical
configuration, electrode spacing, and electrode configuration.
e) Arc Quenching
SF6 is approximately 100 times more effective than air in quenching spurious
arcing. SF6 also has a high thermal heat capacity that can absorb the energy
of the arc without much of a temperature rise.
×
Because of the arc-quenching ability of SF6, corona and arcing in SF6 does
Get Notifications
not occur until way past the voltage level of onset of corona and arcing in air.
SF6 will slowly decompose when exposed to continuous corona.
All SF6 breakdown or arc products are toxic. Normal circuit breaker operation
produces small quantities of arc products during current interruption which
normally recombine to SF6.
Arc products which do not recombine, or which combine with any oxygen or
moisture present, are normally removed by the molecular sieve filter material
within the circuit breaker.
Toxicity
FAULTED SF6 GAS – Faulted SF6 gas smells like rotten eggs and can cause
nausea and minor irritation of the eyes and upper respiratory tract. Normally,
faulted SF6 gas is so foul smelling no one can stand exposure long enough at
a concentration high enough to cause permanent damage.
SOLID ARC PRODUCTS – Solid arc products are toxic and are a white or off-
white, ashlike powder. Contact with the skin may cause an irritation or
possible painful fluoride burn. If solid arc products come in contact with the
skin, wash immediately with a large amount of water. If water is not available,
vacuum off arc products with a vacuum cleaner.
When handling and re moving solid arc products from faulted SF6, the
following clothing and safety equipment should be worn:
×
Get Notifications
Coveralls are not required after all solid arc products are cleaned up.
Disposable coveralls are recommended for use when removing solid arc
products; however, regular coveralls can be worn if disposable ones are not
available, provided they are washed at the end of each day.
HOODS – Hoods must be worn when removing solid arc products from inside
a faulted dead-tank circuit breaker.
GLOVES – Gloves must be worn when solid arc products are hah-died.
Inexpensive, disposable gloves are recommended. Non-disposable gloves
must be washed in water and allowed to drip-dry after use.
https://electrical-engineering-portal.com/maintenance-of-sf6-gas-circuit-breakers 4/5
10/28/2019 Maintenance Of SF6 Gas Circuit Breakers
The use of respirators is optional for work on circuit breakers whose in-
terrupter units are not large enough for a man to enter and the units are well
ventilated.
×
Disposal of waste
Get Notifications
All materials used in the cleanup operation for large quantities of SF6 arc
products shall be placed in a 55 gal drum and disposed of as hazardous
waste.