Sonet Operating Manual
Sonet Operating Manual
Sonet Operating Manual
DominoCom ANT-20
Advanced Network Tester
“SONET Version”
BN 3035/42,
BN 3035/22,
BN 3035/12
Operating Manual
BN 3035/98.22
Please direct all enquiries to your
local Wavetek Wandel Goltermann sales
company. The addresses are given at the
end of this handbook.
Copyrights
This product or parts of it are based upon
Recommendations and/or Standards of the
Standardization Sector of the International
Telecommunication Union - ITU-T and/or of the
European Telecommunications Standards Institute -
ETSI. These Recommendations and Standards are
subject to copyrights of these organizations. Without
written permission of the ITU-T and/or ETSI it is not
permitted to copy ITU-T Recommendations or ETSI
standards or parts thereof and/or make them available
to third parties.
Please follow these hints to walk your way through the demo
The demo is not protected by a password. When you are prompted by the program to enter your
user name and password, simply press the “Enter” key. The preset sequence will then be
loaded automatically. Start the sequence by clicking on the “Test UUT” button. You can enter
any text you like in the “UUT No.” field.
The preset demo sequences “_DEMO... .SQU” are a selection of typical test cases with loop
measurements between the generator and receiver of the ANT-20.
You may change the individual parameters in a test case by double-clicking on the appropriate
line in the display. The sequence can be edited from the “SEQUENCE / EDIT SEQUENCE”
menu.
You can also create your own test sequence using the demo. Use the test cases provided by
Wavetek Wandel Goltermann as templates. This test sequence cannot be saved for
subsequent use.
We hope you find the demo useful. If you want to know more about the ANT-20 Test Sequencer
and the CATS product range, please contact your local Wavetek Wandel Goltermann sales
engineer.
If you have questions or suggestions regarding this demo, please contact Walter Besse at:
Email: walter.besse@wwgsolutions.com
or
FAX: --49 7121 862 054 c/o Walter Besse.
Introduction 1
Getting started 2
Operating Fundamentals 3
Virtual Instruments 4
Application Guide 5
Standards/Abbreviations 6
Technical Background 7
Maintenance 8
Remote Operation 9
Specifications 10
11
Index 12
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Introduction
1 The ANT-20, ANT-20E concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .I-1
Getting Started
1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-1
Operating Fundamentals
1 Control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .O-1
6 Measuring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .O-27
i
Mainframe, SONET Version ANT-20/ANT-20E
Virtual instruments
1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .VI-1
Application Guide
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
ii
ANT-20/ANT-20E Mainframe, SONET Version
25 Measuring the CLR with a variable cell rate (VBR traffic) . . . . . . A-81
Standards/Abbreviations
1 Recommendations/Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-1
3 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-12
Technical Background
1 Multiplexing structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TB-1
Maintenance
1 Cleaning the instrument . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .M-1
2 Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .M-1
iii
Mainframe, SONET Version ANT-20/ANT-20E
Remote operation
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RO-1
Specifications
1 Generator section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S-2
4 E1 to E4 signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S-16
Index
iv
1
Introduction
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Introduction
i
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
ii
ANT-20/ANT-20E Mainframe, SONET Version
Introduction
ANT-20E
The Advanced Network Tester ANT-20E (E = Extended) is the logical further development of
the ANT-20. All the advantages of the ANT-20 concept have been retained and allow for
extended combinations of functions within a single portable instrument.
The ANT-20E can, for example, measure synchronous functions at high bit rates and also jitter
simultaneously. To do this, the 2.5 Gbit/s Module and the 2.5 Gbit/s Jitter Module can be
combined with the 622 Mbit/s Jitter Module in the ANT-20E. This eliminates the complicated
and time consuming need for several different test instruments during network installation or
troubleshooting.
The ANT-20E can make measurements on all standard electrical and optical interfaces from
2 Mbit/s up to STM-64 and from DS1 up to OC-192. It can resolve signal structures up to the
10 Gbit/s level and analyze them down to the lowest level. Access to all standardized mappings
is available both for different transmission methods (SDH, SONET, ATM) and for mixed
structures (e.g. DS1 in STM-1).
The ANT-20E is equipped with a powerful operating processor and 16 MB RAM. The use of the
Windows95 operating system provides for extra advantages:
• Standard software ensures future viability
• Modern operating system
• Other Windows95 compatible software can be used
• Matches the normal work environment
• Easy access to PCMCIA interface without additional software
Introduction I-1
I-2
Fig. I-1
Add/Drop Mux
- Test for correct
path switching
- Test of alarm
Mainframe, SONET Version
sensors
- Capture range test Cross Connects
- Pointer simulation - Test for correct
and analysis path switching
- Synchronization test - Check of alarm
- Jitter tests sensors
- Tributary perfor- - Pointer simulation
mance analysis and analysis
- Signal delay
- Investigation of
jitter behavior
transmission for
STS-3/12/48/192
ATM Multiplexers STM-1/4/16/64 or
- Test for correct - Pointer simulation
path switching and analysis
(BERT) - Performance
- OAM test (ITU-T G.826/G.821
- ATM layer perfor- G.828/G.829
mance tests M.2100/M.2101)
(cell loss, cell - APS test (automatic
delay, etc.) International
setting) Gateways
- Traffic and error
statistics - Simultaneous
SDH and SONET
mappings
- Test of path
configuration
- Test for correct
path switching
The PC concept and standard color display screen of the ANT-20E make for superior ease of
ANT-20/ANT-20E
Introduction
ANT-20/ANT-20E Mainframe, SONET Version
The ANT-20 can always provide the answer to the wide range of measurement tasks on modern
network components, as the functions can be combined to match your current requirements just
like adding building blocks. Functions can be added at any time.
Miscellaneous
V.24 remote control
GPIB remote control
LabWindows/CVI driver
Remote control via modem
Remote control via LAN
Test Sequencer for
SDH/SONET/ATM
Introduction I-3
Mainframe, SONET Version ANT-20/ANT-20E
Virtual instruments
G.821/G826/M.2100
Windows
ATM traffic tester
Pointer tester
Applications
SOH monitor
Error tester
SOH editor
AT processor
Test box
processor Instrument driver
Measurement
hardware Test module
Despite the exceptional flexibility and wide range of functions of the ANT-20, it is one of the
most compact instruments of its class. The low-volume casing with extra large area display
screen was designed specifically with the requirements of mobile use in mind. The protective
cover and carrying handle also have other useful functions (see the section “Getting started”).
I-4 Introduction
Getting Started 2
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Getting Started
i
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
ii
ANT-20/ANT-20E Mainframe, SONET Version
Getting Started
1 Safety instructions
This instrument was shipped in perfect condition. To ensure that this condition is maintained
and that operation is safe, please follow the instructions in this section carefully.
This instrument may only be used under the conditions and for the purpose for which it was
constructed. Further information on this is given in the sections “Specifications” and
"Introduction" of this operating manual.
Use outside the specified conditions may be dangerous and may also damage the
instrument.
Sec. 1.4, Page G-2.
In particular, the instrument must not be connected to measurement circuits for which it is not
designed.
Before switching the instrument on, make sure that the instrument operating voltage
corresponds to the voltage of your local AC power supply.
The ANT-20 is a Safety Class 1 equipment as defined in EN 61010-1 (IEC Publ. 1010-1). The
AC line cord supplied with the instrument contains a protective ground conductor. The AC line
plug may only be inserted into AC line socket outlets equipped with a protective ground contact
unless the AC line circuit is specially isolated.
The protective ground conductor must not be interrupted, either inside or outside the
instrument casing.
A connection to measurement circuits carrying dangerous voltages is not intended.
If the AC line protective ground connection can be used for this purpose, connect the
instrument to the AC line before connecting it to the measurement circuit.
If the measurement circuit itself is equipped with a protective ground conductor, this should be
connected to the instrument casing before connecting the rest of the measurement circuit.
If it is suspected that the instrument is no longer safe to use, it should be taken out of service
and secured against unintentional operation. This situation is possible if:
• the instrument is visibly damaged,
• the instrument does not work,
• the instrument is exposed to stresses of any kind which are outside the permitted limits,
• the instrument has been stored for a long period under unsuitable conditions or handled
roughly during transport (see Sec. 2, Page G-6).
In such cases, contact your nearest Wavetek Wandel Goltermann Service Center. The
addresses are listed at the end of this operating manual.
If the covers are removed or parts of the instrument are manipulated using tools, it is possible
that other parts carrying dangerous voltages may be exposed. The connectors may also be live.
For this reason, the instrument must be disconnected from all voltage sources before it
is opened. Simply switching it off using the AC line switch is not sufficient.
Capacitors in the instrument may retain a charge even long after the instrument has been
disconnected from all voltage sources.
If subsequent calibration, maintenance or repair of the opened instrument under voltage
becomes necessary, such work should only be performed by trained persons familiar with the
risks involved.
Repairs
Repairs must be carried out by trained persons. The constructional features of the instrument
must not be altered in any way which might adversely affect the safety characteristics of the
instrument. In particular, creepage and air paths and the insulation spacing must not be
reduced.
Wherever possible, use only original spare parts for replacement. Other parts may only be used
if they do not adversely affect the safety characteristics of the instrument.
Fuses
Use only the prescribed fuses (see Sec. 3.1, Page G-8).
The following options for the ANT-20 are fitted with laser output devices:
• BN 3035/90.40 through BN 3035/90.59
• BN 3035/91.40
• BN 3035/91.41
• BN 3035/91.53 through BN 3035/91.59
Optical radiation with wavelengths in the range 1300 to 1600 nm is present at sockets [18], [47]
and [103].
Maintenance and repair work on the laser sources should only be carried out by qualified
service operatives familiar with the risks involved.
The laser source is active if the yellow LED next to the connector is on.
The output power at socket [18] of the STM-4/OC-12 module is within the limits for a
CLASS 1 LASER PRODUCT.
The output power at socket [47] or [103] of the STM-16/OC-48 module or STM-64/OC-192 is
also within the limits for a CLASS 1 LASER PRODUCT (IEC 825-1: 1993) during normal
operation. Under fault conditions, the output power level may exceed these limits and the output
is then a CLASS 3A LASER PRODUCT (IEC 825-1: 1993).
103
LASER ON
DATA
18 47
0 dBm
Mainframe STM-16/OC-48 Module STM-64/OC-192 Module
Fig. G-1 ANT-20 optical connections
We recommend that the laser safety warning label is affixed to the front panel of the ANT-20/
ANT-20E below socket [05] (see Fig. G-3).
Use the following laser safety warning labels:
• CLASS 1 LASER PRODUCT
for Options BN 3035/90.43 through 90.48
• CLASS 3A LASER PRODUCT
for Options BN 3035/90.53, BN 3035/90.54, BN 3035/90.59, BN 3035/91.53,
BN 3035/91.54, BN 3035/91.59, BN 3035/91.40 and BN 3035/91.41
A sheet of laser safety warning labels is included with each module.
Note: If Options in the BN 3035/90.43 through 90.48 range and
BN 3035/90.53, BN 3035/90.54, BN 3035/90.59, BN 3035/91.53, BN 3035/91.54,
BN 3035/91.59, BN 3035/91.40 or BN 3035/91.41 are both fitted, the CLASS 3A
LASER PRODUCT label should be affixed.
Any CLASS 1 LASER PRODUCT label already affixed to the instrument should be
removed or the new label affixed over it so that it is completely concealed.
Fig. G-3 Laser safety warning label on the front panel of the ANT-20/ANT-20E
2.1 Unpacking
Do not discard the packing materials and any transport protection. These items have been
specially designed to be reused if they are not damaged. The instrument can only be reliably
protected against damage if the original packing is used when transporting it.
After unpacking the instrument check it for transport damage. Such damage is likely if the
packaging itself has been severely damaged. Do not attempt to use an instrument which is
visibly damaged, as this may result in further damage to the instrument and may be dangerous
(see Sec. 1, Page G-1).
If the instrument is to be shipped, e.g. to a Wavetek Wandel Goltermann Service Center for
repairs, follow the instructions below to ensure that damage does not occur during transport.
Packing
If possible, use the original packing (undamaged) for shipping the instrument.
If the original packing is not available, use a strong box made from double-layer corrugated
cardboard which is at least 4 mm thick.
The box should be big enough to allow padding of at least 70 mm thickness to be placed all
round the instrument. The padding can be rigid foam plastic or corrugated cardboard.
The padding should cover as large an area of the instrument surface as possible and ensure
that the instrument does not move within the box. Any spaces can be filled with polystyrene
chips or similar.
The use of polystyrene chips as the only padding material is insufficient.
The box should be sealed along the butt edges using waterproof textile adhesive tape which is
at least 70 mm wide.
Check list
Make a list of all the items in the box and place it in the box.
Storage and transport can subject the instrument to severe stresses. Refer to the safety
instructions Sec. 1, Page G-1 and all of the instructions for packing and unpacking, transport
Sec. 2, Page G-6.
Recovery time
Condensation may form on an instrument which has been stored or transported at a low
temperature when it is brought into a warm environment. To prevent any damage, wait until all
signs of condensation on the instrument surfaces have disappeared before switching the
instrument on. The instrument is only ready for use when it has reached the guaranteed
operating temperature range of +5 to +45 °C.
The latter also applies if the instrument has been stored at a higher temperature.
2.5 Ventilation
Make sure that the ventilation slots are not obscured during operation.
The instrument must not be operated above the permitted maximum ambient temperature of
+45 °C. Adequate ventilation must be provided.
3 Power supply
AC line frequency
The ANT-20 is operated from AC line power supplies having a frequency of 50 or 60 Hz.
Fuse
The following type and value of fuse must be used:
The ANT-20 contains lithium batteries for buffering the data storage memory. Replacement of
expired (flat) batteries can be carried out by your local Wavetek Wandel Goltermann Service
Center.
The batteries need not be removed from the instrument if it is to be scrapped.
3.3 Switching on
Switching on
The ANT-20 is switched on using the AC power switch located on top of the instrument
(switch position “I”).
When you switch on, the MS-DOS and Windows 3.11 (Windows95 for ANT-20E) operating
systems will start. MS-DOS, MS-Excel, Windows, Windows 3.11 and Windows95 are registered
trademarks of Microsoft Corporation. The ANT-20 software will then start automatically.
The display will then look something like the next figure.
The following situations may lead to a loss of the “CMOS setup” data:
• Switching off the instrument during boot-up
• Power supply failure during boot-up
• Software crash
First select C: USR1 and then press the “AUTO” key. All other parameters
will then be set automatically.
System: [✓] Simultaneous Display (not available for every BIOS version)
Shadow: Cache:
[✓] System BIOS (*) CPU only
[✓] Video BIOS
VGA Setup: [✓] Simultaneous (not available for every BIOS version)
First press “Auto All Drives”. Then set the missing flags.
4 Protective cover
The next figure shows how the cover of the ANT-20 can be used.
Position 1
Position 2 Position 3
There are slots on the horizontal edge of the top side and on the lower horizontal edge of the
front panel for locating the locking clips (A) of the cover.
5 Carrying handle
The carrying handle of the ANT-20 can be extended. Two positions are possible. The figure
below shows how to set these positions.
The ANT-20E is fitted with an adjustable carry strap instead of the carry handle.
A
Handle side B
Ends of
handle extention
(sprung)
A
1 (Handle position 1) 2
D
Grip
C F Handle extention
Slot D
3 (Handle position 2) 4
Notes on diagrams 1 to 4
1. Handle position 1: The ends of the handle extension are locked in the lower slots of the
handle sides. This is the shortest length of the handle.
2. To extend the handle: Press the ends of the handle extension (A) into the slots on both
handle sides simultaneously and slide upwards (B).
3. Pull the grip up until the ends of the handle extension lock into the upper slots in the handle
sides (C). This is the longest length of the handle (handle position 2).
4. To shorten the handle: Press the ends of the handle extension into the slots (D) on both
handle sides simultaneously and slide down (E). Push the grip down (F in diagram 3.) until
the ends of the handle extension lock into the lower slots in the handle sides.
6 Instrument checklist
The following items are supplied with the ANT-20/ANT-20E:
• ANT-20/ANT-20E Mainframe
• Protective cover
• Options (will be built in to the Mainframe according to your order instructions)
• Trackball (instruments equipped with touchscreen are supplied without trackball)
• AC line power cord
• Bag containing two spare fuses and tools
(allen key and mounting key)
• Windows and MS-DOS operating systems and handbooks (ANT-20) or
Windows95 operating system and handbook (ANT-20E)
• Operating manual
• Calibration certificate (or optional calibration report)
7 Data backup
The ANT-20 software together with the MS-DOS and Windows operating systems are pre-
installed on the hard disk drive of the ANT-20. The instrument is ready to use immediately.
The following directories are stored on the hard disk drive of the ANT-20:
Directory Contents
c:\windows\ … Windows
\…
\…
\disk2 \ …
\diskn \ …
To back up the ANT-20 data, copy each one of the directories c:\ant20.sup\disk1 through
c:\ant20.sup\disk n on to a separate floppy disk.
Tip: It is a good idea to make a backup of all the data on the hard disk drive using a suitable
backup program.
The ANT-20/ANT-20E software together with the Windows95 operating system is pre-installed
on the hard disk drive of the ANT-20/ANT-20E. The instrument is ready to use immediately.
The following directories are stored on the hard disk drive of the ANT-20/ANT-20E:
Directory Contents
c:\windows\ … Windows95
\…
\…
\disk2 \…
\diskn \…
To back up the ANT-20E data, copy each one of the directories c:\ant20.sup\disk1 through
c:\ant20.sup\disk n on to a separate floppy disk.
Tip: It is a good idea to make a backup of all the data on the hard disk drive using a suitable
backup program.
8 DominoCOM ANT-20
The DominoCOM ANT-20 “Black Box” concept is the ideal solution for use in automatic test
systems.
• It is equipped with remote-control interfaces as standard.
• It is particularly suitable for space-saving rack mounting.
• It is easily stackable.
The DominoCOM ANT-20 is connected to a standard or notebook PC via the V.24 or GPIB
interface.
SCPI commands are used to control the DominoCOM ANT-20.
LabWindows/CVI drivers can be supplied as an optional extra. They reduce the time required
for program development and simplify control of the DominoCOM ANT-20 or ANT-20.
Tip: Further details on this operating mode are found in the Remote-Control Instructions,
BN 3035/98.09.
Tip: Further details on this operating mode are found in the Remote-Control Instructions,
BN 3035/98.09.
Notes:
3
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Operating Fundamentals
i
Mainframe, SONET Version ANT-20/ANT-20E
6 Measuring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . O-27
6.1 Setting the parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . O-27
6.2 Starting and stopping the measurement . . . . . . . . . . . . . . . O-29
6.2.1 Starting and stopping a measurement manually. . . . . . . . . O-29
6.2.2 Starting a measurement manually and
stopping automatically . . . . . . . . . . . . . . . . . . . . . . . . . . . . O-30
6.2.3 Starting and stopping a
measurement automatically (timer). . . . . . . . . . . . . . . . . . . O-30
6.3 Displaying results e.g. anomalies . . . . . . . . . . . . . . . . . . . . O-31
ii
ANT-20/ANT-20E Mainframe, SONET Version
iii
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
iv
ANT-20/ANT-20E Mainframe, SONET Version
Operating Fundamentals
1 Control elements
see Fig. O-1, Page O-1 and Fig. O-5, Page O-7
Position Designation
I LED array
IV Function keys
VI Built-in keyboard
Fig. O-2, Page O-2 (ANT-20), Fig. O-3, Page O-3 (ANT-20E)
and Fig. O-4, Page O-4 (DominoCOM ANT-20)
Position Designation
Position Designation
B Manufacturer’s name
CE label
ANT-20 serial number
C AC line switch
AC line connector
Fuse
HISTORY
CURRENT
Fig. O-5 Meanings of the LED indicators on the ANT-20 front panel
AIS-L RDI-L
LOP-P AIS-P
UNEQ-P PLM-P
RDI-P LOP-V
AIS-V UNEQ-V
PLM-V BIP-V
RDI-V (AIS-)Yellow
2 Basic operation
The ANT-20 or ANT-20E are operated just like any other Windows application. Entries are
usually made using the trackball. More complex entries are made using the built-in keyboard
and pre-defined function keys. An external keyboard can be connected to socket [03] if
required.
The following sections describe the operating concept of the ANT-20 and ANT-20E with the aid
of some typical examples. Most functions are self-explanatory, so you will become familiar with
the basic operation of the instrument fairly quickly. On-line help is provided to allow you to use
the ANT-20 to the full and to match it to your requirements. For this reason, these operating
instructions have been kept brief. On-line help is accessed by pressing function key F1 (see
Sec. 7, Page O-33).
The ANT-20 and ANT-20E differ in the operating systems that they use. The ANT-20 (series A
through W) uses “Windows for Workgroups 3.11”. The ANT-20 (from series X) and ANT-20E
use “Windows95”. All the “screen shots” illustrated in this operating manual are taken from the
“Windows95” environment. They are practically identical with the “Windows3.11” displays.
Where the ANT-20 differs from the ANT-20E, this is indicated separately.
3.1 Connecting up
1. Connect the ANT-20/ANT-20E a.c. line input to the local a.c. power supply using the line
cord supplied with the instrument.
2. Connect the signal output [14] and signal input [15] together with a screened coaxial cable.
3.2 Switching on
⇒ Switch on the ANT-20/ANT-20E by setting the POWER switch to the “I” position.
If you want to start the ANT-20 with the default settings and ignore the last application that was
saved
– or –
if problems occur with a previously-saved application during boot-up of the ANT-20 software:
1. Press function key F3 “APPL” when the welcome screen is displayed.
A dialog window opens after a few seconds.
2. Click on the “Yes” button in the dialog window.
When switched on for the first time, the ANT-20 screen will look like this:
ANT20
Application Title
Signal Structure
In the following sections of part 3, the basic elements of the “ANT20 - <Application Title>”
window are described first. This will teach you the operating concept of the ANT-20 and tell you
how to call up the virtual instruments (VI) required for a particular application, and how to use
them for future tasks.
In part 4 of this manual you will find detailed information about the windows and dialogs of the
individual virtual instruments. This information is also found in the on-line help for the particular
VI to provide instant assistance for measurement tasks.
In part 5 you will find some selected measurement examples which will help you to understand
the basic operating sequences for the ANT-20 and how you can approach each measurement
effectively.
Note: When you switch on the ANT-20, Windows starts by default and the ANT-20 software
will be loaded (see Fig. O-6).
Other programs are installed on the ANT-20. These programs can be started with the “Instant
Access Buttons” or using icons (shortcuts). Proceed as follows:
1. Click on “Exit” in the “Application” menu of the “ANT-20 - <Application Title>” (Application
Manager) window.
The ANT-20 program terminates.
Note: Programs that do not utilize the ANT-20E hardware, such as “Notepad”, “Acrobat
Reader” or other Windows applications, can be run at the same time as the ANT-20
program.
Start “ANT-20”
programs
Fig. O-7 ANT-20 desktop after activating the “Instant Access Buttons”
3. Click on the “Instant Access Button” or on the icon for the program that you want to start.
The program will start.
The following programs can be started in this way:
Instant
Access
Button Program / File Explanation
ANT-20 NEXT Starts the demo version1 of the “ANT-20 NEXT” (ANT-20
BN 3035/95.40 Network Expert Test) software.
ANT-20 CATS Starts the demo version1 of the “ANT-20 CATS” software with
BN 3035/95.90 a pre-defined application.
NOTEPAD.EXE Opens the readme file about the “Instant Access Buttons”.
1 The full version of the program starts once software access has been released.
Table O-3 Programs / Files that may be started with the “Instant Access Buttons”
ANT-20 Starts the ANT-20 program with the last application that was
loaded.
CATS Test Sequencer Starts the demo version1 of the “CATS Test Sequencer”
BN 3035/95.90 software.
1 The full version of the program starts once software access has been released.
Table O-4 Programs / Files that may be started with icons (links)
Shortcut Opens a folder with pdf files that can be read using the
Acrobat Reader.
Shortcut Opens a folder with pdf files that can be read using the
Acrobat Reader.
1 The full version of the program starts once software access has been released.
Table O-4 Programs / Files that may be started with icons (links) (continued)
4 ANT-20 windows
4.1 Overview
The “ANT20 - <Application Title>” window is the control panel for the ANT-20. It performs the
following important tasks:
Management of:
• Measurement applications
• Virtual instruments (VI) associated with the measurements
• Results recorded by the measurements
Other functions:
• Starting a measurement
• Stopping a measurement
• Entering the duration of a measurement
• etc.
The “Signal Structure” VI is a universal instrument that is required for practically every
application. It is normally loaded at the same time as the Application Manager when the
program is booted up.
• Physical Layer
These VIs are used for measurements in the physical layer:
• ATM Standard
These VIs are used for measurements in the ATM layer if the “ATM Module/ATM Mappings”
option is fitted.
• ATM Advanced
These instruments are used for measurements in the ATM and higher service layers if the
“Broadband Analyzer/Generator” option is fitted.
The “ANT20 - <Application Title>” window is made up from the following elements:
• Toolbar
• Menu bar with pull-down menus
• Title bar
Some functions can be accessed from the menus and from the icons in the toolbar. The
individual elements are described in the sections that follow.
To allow you to make the best use of the screen area while you are working, the “ANT20 -
<Application Title>” window can be switched from its normal size (see Fig. O-8) to a space-
saving reduced size (see Sec. 4.2.1).
Toolbar
Menu bar
Title bar
The Toolbar includes the main functions of the Application Manager and corresponds to the
reduced form of the Application Manager window, also called “Minibar”. You still have instant
access to the central control and management functions of the ANT-20 from this Minibar. You
can configure it so that it is always on top (never hidden by other windows).
Next to the toggle button there is an arrow button which is used to select the virtual instruments
for an application (Add & Remove). The example shows an application with three virtual
instruments. To enter parameters or read the results in a particular VI, simply click on the
corresponding icon button in the Minibar. The corresponding window will then be placed on top.
This gives you instant access to every window in an application even if some windows are
concealed by others or have been reduced to icons (see Fig. O-33).
Measurements are started and stopped using the “traffic signal” icon button. The progress of the
measurement can be monitored in the adjacent display fields.
These show the status of the measurement and the elapsed measurement time as well as the
set measurement time.
You can disable entries from the keyboard, touchscreen or trackball to prevent unintentional
operation.
⇒ Click on the “Keyboard Lock ...” command in the “Configure” menu.
– or –
1. Press the “Alt” + “Tab” keys repeatedly until the “Minibar” is activated.
2. Press the “ESC” key.
The Minibar still provides access to all major instrument functions. If you click on an area where
there are no icon buttons, a pop-up menu appears. This contains a selection of functions from
the menu bar, including functions for application management and closing the program.
Tip: If you want the reduced Application Manager to be always visible, select the “Always on
Top” option in the “Configure” menu (see Sec. 4.2.2.4).
Pop-up menu
Fig. O-9 Elements of the Minibar or reduced “ANT20 - <Application Title>” window
Pull-down
menu
The menu bar shows the names of the various pull-down menus.
Menu commands followed by an ellipsis (…) open further windows or dialogs. Some commands
are followed by a hotkey combination. Press the keys shown to execute the command directly.
The “Application” menu (see Fig. O-10) handles the following functions for ANT-20 applications:
• Create
• Load
• Save
• Delete
• Import
• Export
The “Exit” command closes the “ANT20 - <Application Title>” window and any other ANT-20
windows that are open. The program stops and all settings are saved.
Fig. O-11 The “Instruments” menu of the “ANT20 - <Application Title>” window (example)
Fig. O-12 The “Measurement” menu of the “ANT20 - <Application Title>” window
Fig. O-13 The “Configure” menu of the “ANT20 - <Application Title>” window
The “Configure” menu sets whether the Minibar (Application Manager) is to be always visible or
not. It is also used to set the menu language and lock the keyboard to prevent inadvertent
operation, if required.
The “LED Display ...” command extends the functions of the LED display on the front panel. The
“AU-LOP/LOP-P” LED can be used to indicate the message “AU-NDF” in addition to the “AU-
LOP/LOP-P” messages. The “TU-LOP/LOP-V” LED can be used in the same way to indicate
the message “TU-NDF” in addition to the “TU-LOP/LOP-V” messages.
The “Keyboard Lock ...” command disables entries using the keyboard, touchscreen or trackball
to prevent unintentional operation. Entry is enabled again when you press the “ESC” key. The
“ANT20 - <Application Title>” (“Minibar”) window must be active for this (also see
Sec. 4.2.1.4, Page O-16).
The “Delete result warning” item is used to activate a warning message that will appear if you
perform an operating step that will result in deletion of results.
Fig. O-14 The “Print” menu of the “ANT20 - <Application Title>” window
The “Print” menu of the Application Manager allows you to collectively print out the available
measurement results from the opened virtual instruments.
Fig. O-15 The “Help” menu of the “ANT20 - <Application Title>” window
This menu opens the on-line help for the Application Manager window and also opens the error
window. The “About...” option displays a window showing the instrument version, software
version and a list of the options fitted to the mainframe.
Title
The title shows the name of the application that is loaded, e.g. “STM-1 Error Test”. If you create
a new application the title will initially show “Untitled”.
Minimize button
Click on the “Minimize” button to reduce the Application Manager to its reduced size. The
“Minimize” button reduces all other virtual instruments to icons.
Maximize button
The “Maximize” button has no function in the main VI windows. It is grayed out in Windows 95.
It does not exist in Windows 3.11.
The virtual instruments to be used for an application are selected in the “Add & Remove
Instruments” dialog of the Application Manager (see Fig. O-17). There are two basic ways to set
up an application:
⇒ You can create a new application by modifying an existing selection. To do this, call up the
“Add & Remove Instruments” dialog directly by clicking on the icon button shown above.
– or –
⇒ You can create a new application without reference to a previous selection. To do this, call
up the “Add & Remove Instruments” dialog using the “Application / New” command.
This removes all the currently loaded VIs and loads the default settings.
Fig. O-17 The “Add & Remove Instruments” dialog window of the Application Manager
Fig. O-18 “Add & Remove Instruments” dialog window after adding the VIs required
(“Physical Layer” group pre-selected)
The “Add & Remove” dialog when ATM options are fitted
If your ANT-20 is equipped with one or more ATM options (ATM Module, Broadband Analyzer/
Generator), you can display the virtual instruments in groups for selection from the “Instruments
available” list box.
This reduces the scope of the list for a given application to make it easier to locate the VIs you
want to select. When all options are fitted, the following instrument groups are available:
• Group 1: “Physical Layer”: VIs for the physical layer (standard)
• Group 2: “ATM Standard”: VIs for the “ATM Module” option (BN 3035/90.70)
• Group 3: “ATM Advanced”: VIs for the “Broadband Analyzer/Generator” option
(BN 3035/90.80)
For applications that only involve the physical layer, the Group 2 and 3 instruments can be
removed.
The Signal Structure“ virtual instrument has a special position among the ANT-20 VIs. Before
you start to make the settings for your application in the various VIs, the structure of the signal
to which the ANT-20 is to be connected must be entered (sets the interface conditions for the
physical layer).
1. In the Application Manager, click on the icon button shown above to activate the instrument.
The “Signal Structure” window opens. The display area of the window depicts the signal
structure setting that is currently valid.
Example
The following example shows how to set up a “STS-1/VT1.5/DS1 framed” multiplex structure for
the generator (TX) and receiver (RX).
3. Click on the “TX” button in the “Edit” field of the “Edit Signal Structure - TX“ dialog window.
4. Click on the “Clear” button.
The TX signal structure is cleared.
5. Click on the “ANSI” button.
6. Click on the following buttons in the “Edit Signal Structure - TX” dialog window in the order
given:
– “TX”
– “STS1”
– “VT1.5 SPE”
– “DS1”
– “Framed”
– “TX => RX”
The “Signal Structure” dialog window will then look like this:
Fig. O-22 “Signal Structure” dialog window after entering the signal structure
Once you have created an application, it is saved using the “Save Application As” dialog.
Depending on the Application Manager setting (reduced or normal size) the dialog is opened in
various ways.
⇒ Open the dialog using the “Application Save As...” command in the pop-up menu (reduced
size Application Manager).
– or –
⇒ Open the dialog using the command sequence “Application / Save As...” (normal size
Application Manager).
The “Save Application As” dialog window opens.
Comment for
the application
To save an application
1. Click on the “Comment” box.
2. Use the keyboard to enter a comment for the application, e.g. “Error Measurement”.
3. Click on “OK”.
The application is saved. The window title shown in the title bar of the Application Manager
will change from “Untitled” to the title you entered in the “Comment” box, e.g. “Error
Measurement”.
• The “Application Save” (reduced size) and “Application / Save” (normal size) Application
Manager menu commands modify the current application in the database.
• The “Application Save As...” (reduced size) and “Application / Save As...” (normal size)
Application Manager menu commands create a new application.
The ANT-20 allows you to load pre-defined applications using the “Open Application” dialog.
⇒ Open the dialog using the “Application Open...” command in the pop-up menu (reduced size
Application Manager).
– or –
⇒ Open the dialog using the command sequence “Application / Open...” (normal size
Application Manager).
– or –
⇒ Press function key “F3” APPL.
The “Open Application...” dialog window opens.
To load an application
1. Click on the item in the list corresponding to the application that you want to load.
The item is highlighted in gray.
2. Click on the “OK” button.
The selected application is loaded and the ANT-20 is immediately ready to measure.
Drive selection
List of applications
Scrollbars
Press function key “F5” MEASUREMENT START to start a measurement using the pre-
selected measurement parameters.
Tip: Handling of applications is simplified by selecting filter criteria.
Saved applications are differentiated by the following features:
• Date/time saved
• TX signal structure
• RX signal structure
• Comment
Using the buttons in the “Application Filter:” field, you can select a signal structure, separate for
the generator and receiver.
Only those applications having this signal structure will then be displayed.
Enter a comment in the “Comment:” field to search for applications with corresponding
comments. The “W&G” button lists only those pre-defined applications with names beginning
with “W&G …”.
6 Measuring
This section basically describes how to
• set the measurement duration
– for a manually-started measurement
– for an automatically-started measurement
• set the measurement parameters, e.g. insert an anomaly
• start the measurement
• stop the measurement
• display the results e.g. using the “Anomaly/Defect Analyzer” VI
• Other TX parameters are normally set using the Generator VIs or windows.
• Results are normally displayed using the Analyzer VIs or windows.
Further information is found in Part 4.
The measurement duration (e.g. 60 seconds) is set using the “Measurement Settings” dialog in
the Application Manager.
1. Open the dialog using the “Measurement Settings...” command in the pop-up menu
(reduced size Application Manager).
– or –
Open the dialog using the command sequence “Measurement / Settings...” (normal size
Application Manager).
The “Measurement Settings” dialog window opens.
2. Activate the “Seconds” option button in the “Gate Time” field (“Seconds” button is marked
with a dot).
3. Enter the value 60 into the “Gate Time” input field unless this value is not already displayed.
4. Click on “OK”.
Start mode
manual
automatic
Start time
Set to current date (system clock)
Units
Anomalies or defects are inserted from the “Anomaly/Defect Insertion” window. The following
example describes how to insert a “TSE” (Test Sequence Error) with an error rate of 10-6.
Toolbar
Anomaly rate
Tip: More information about the “Anomaly/Defect Insertion” VI is found in Part 4, Section 3 or
in the on-line help for the window.
Measurements can be controlled manually by clicking on the “Traffic signal” icon in the
Application Manager (start / stop toggle function).
✓ “Manual” start mode must be activated, see “Measurement Settings” dialog.
✓ Before starting the measurement, the traffic signal icon is set to “green”.
Measurements can also take place fully automatically by programming the start time and stop
time. The start time is specified as an absolute time (date and time). The stop time is a relative
time, determined by the measurement time or “Gate Time”.
Fig. O-30 Settings: Start mode (Timer), Start Time and Gate Time
The results are displayed by various virtual instruments (see Analyzer VIs in Part 4).
The “Anomaly/Defect Analyzer” VI is used here as an example. This instrument displays the
intermediate and final results of measurements of anomalies or defects.
⇒ Click on the above icon for this VI in the Application Manager.
The “Anomaly/Defect Analyzer” VI is placed on top.
Select display mode
Histogram
(Graph) Table Summary
Count
(Num)
Fig. O-31 Example result display in “Anomaly/Defect Analyzer” window (View “Graph”)
7 On-line help
On-line help is available for each VI window.
The on-line help function provides information about a particular task, function, command or
parameter.
F1
⇒ Click on the terms underlined in green in the text on which you require more information.
– or –
⇒ Click on the context-sensitive areas of the figures when this feature is indicated.
When on-line help is called up, the help window fills the entire display area. You can reduce the
size of the window and move its position on the display as required.
If you make the help window very small, part of the text may be obscured. If this is so, scrollbars
appear down the right-hand side and along the bottom of the window. These are used to scroll
through the text.
Tip: If you reduce the size of the help window so as to display the measurement program at
the same time, select the “Small” font (“Options” menu). This makes best use of the
available area of the help window.
The number of virtual instruments in your ANT-20 depends on the hardware and software fitted.
The VIs are included into applications that are created and managed using the Application
Manager. When an application is loaded, all the windows for the VIs included in the application
will be opened. The parameters for the VIs are set using these windows and other dialog
windows. The dialog windows open when you click on various buttons or certain menu
commands in the VI windows.
Tip: As the display area of the screen is limited, all VI windows that are not needed should be
reduced to icon buttons (use the “Minimize” button).
An iconized VI window can be restored to its original size at any time
- by clicking on the corresponding icon in the Application Manager, or
- by clicking on the corresponding icon button in the task bar at the bottom of the screen.
Task bar
VI: Anomaly/Defect Analyzer
VI: Signal Structure
reduced to icon buttons
When you select a menu command or an icon, a dialog window may appear in the foreground
for you to make further settings. If required, a dialog window can be open at the same time as
a display window, for example if you want to display results during a measurement and change
the parameters on-line.
The commonly-used dialog window controls are described below using the “User Filter” (VI
“Anomaly/Defect Analyzer”) dialog as an example.
Option buttons
Dialog specific
action buttons
Option buttons
Option buttons are arranged in groups. Only one button can be activated in each group. The
selected or activated option is indicated by a black dot. Inactive option buttons are empty.
Action buttons
Clicking on an action button executes an action directly.
Action buttons with toggle functions appear pressed when clicked on once and the label on the
button changes (e.g. from “OFF” to “ON”). Clicking the button again causes it to “pop up” and
the label reverts to its original function (e.g. “OFF”).
Check boxes
Check boxes are used to activate / deactivate other options. The option that you selected is
indicated by a check (✔).
List boxes
List boxes generally contain one or more items arranged in a certain order. A current item in the
list is activated by clicking on it. A scrollbar appears next to the list if it contains more items than
can be displayed in the box at one time.
Entry boxes
These are boxes where you enter alphanumeric characters (parameter values, names). Where
numerical values are to be entered, the range of values allowed for the parameter will be
checked. Invalid parameter values are ignored.
Important: Entries are accepted only when the cursor in the entry box stops blinking. This
happens when you move to another entry box by clicking on it or by pressing the “TAB” key.
You can enter characters from the normal keyboard or by means of the “Keyboard” window if
you have activated the “Keyboard On” option.
“OK” button
The “OK” button confirms the parameter entries or changes you made and closes the dialog.
“Cancel” button
The “Cancel” button cancels the parameter entries or changes you made and closes the dialog
window.
Keyboard
If the keyboard is activated, you can enter numerical values “on-screen”. The “Keyboard”
window appears whenever a dialog window containing entry boxes is opened.
The alpha keys are also activated if the parameter to be entered is in hexadecimal code.
The “OK” button transfers the value in the “Keyboard” entry box to the entry box in the dialog
window that was previously selected.
The “Keyboard” window closes as soon as you close the dialog window.
Entry box
Clear all
Clear last digit
Increment
Decrement
Exponent
Confirm entry
for negative values
Fig. O-35 The “Keyboard” window for entering numerical parameter values
Table O-5 Possible results included in the printout for the “Print all ...” command
If the driver for the printer that you want to use is not yet installed on the ANT-20/ANT-20E, you
must install the driver first.
You can install the driver from Windows 3.11/Windows95 if it is included in these programs.
The printer drivers are located in directory C:\WFW311 (Windows 3.11) or C:\WIN95.SUP
(Windows95).
We recommend that you install the driver supplied with your printer, or a newer version if this is
available. The latest version of the driver can usually be downloaded from the printer
manufacturer’s Internet home page.
The “Print” menu of the Application Manager allows you to collectively print out the available
measurement results from the opened virtual instruments.
The “Print Headers” dialog is used to select information that is to be printed out together with the
results. The dialog window contains entry fields for:
• Company logo stored as a bitmap (*.BMP- or *.DIB file) in a directory
• Signal structure
– as a graph if the “Signal Structure” VI is loaded
– as text if the “Signal Structure” VI is not loaded
• Printout header with data identifying the measurement:
Test instrument inventory number, Customer name, Test object description, Tester’s name,
Date
• Comment text (information about the measurement)
The company logo is printed out at a fixed size with its original aspect ratio preserved on all
pages of the printout. The other items are printed out on the first page only.
Header1
Inventory no of instrument
Customer name1
Test object description1
Tester’s names1
Date, signature
Comment text
The “Print” menu is used to print out the results or to export them for further processing with
other programs.
The “Print” dialog is used to trigger the printout. The following options can be pre-selected:
• Selection and input of additional informations via sub-dialogs
• Selection of printer, paper format via sub-dialog
• Setting the print quality
• Setting number of copies
Start printout!
The standard Windows “Printer Setup” dialog is used to select the following settings:
• Actual printer
• Paper size / format
• Other options in the “Options” sub-dialog.
The results can be stored in a specified destination directory or on floppy disk for archiving or
for further processing.
1. Select the “Export...” command in the “Print” menu.
The “Save as” dialog opens (see Sec. 9.3.2.1).
2. Select the destination directory where you want the result file to be stored
(if you want to save to a floppy disk, insert one in the drive first).
3. Select the type of file for the saved results.
4. Click on the “OK” button to start exporting the results.
The file type can be altered using the “Export Setup” dialog (see Sec. 9.3.2.2).
The file type selection does not affect the contents of the file.
This dialog is used to define the file in which the results are to be exported. Exported data can
be processed with other programs, e.g. spreadsheet programs.
Data are output in CSV format (comma separated values). Each item of data is separated from
the next by a list separator. The list separator can be selected in the “Export Format” dialog.
Start exporting!
File type
Fig. O-40 Standard Windows “Save As” dialog for exporting results
This dialog is used to select a list separator character to be used when exporting data. You can
also select the character to be used to indicate a decimal point. This allows you to match the
exported results to the requirements of any spreadsheet program you may be using.
If the results include time information, the time format can also be selected, e.g. “hh:mm:ss,ms”.
The “Defaults” button sets the current Windows system settings. These settings are useful if, for
example, you have installed MS Excel on your ANT-20/ANT-20E. Data exported using the
“Defaults” setting can be directly imported into MS Excel. When importing to another Windows
PC, the default configuration can be viewed and edited by opening the window “Control Panel”/
“International” (Windows 3.11) or the window “Control Panel”/“Regional Settings” (Windows95).
Time format
You can print out a copy of the screen display if a printer is connected to the ANT-20/ANT-20E.
Once a measurement has started, the ANT-20/ANT-20E generates a set of backup data once
every minute. This data set contains all the measurement parameters and all measurement
results up to that point collected from the VIs. The ANT-20/ANT-20E can use the backup data
set to continue with the measurement after an AC power failure. The first backup data set is
available approximately 10 to 15 seconds after the start of the measurement. If a backup data
set has not yet been saved before a power failure occurs, the measurement cannot be
continued when power is restored.
The AC power failure time is saved as a “No-Power” alarm and is displayed when a backup data
set is generated.
Exceptions
No backup data are generated for automatic measurement sequences (Autoconfiguration, MTJ,
JTF, etc.).
A wander measurement is not an automatic measurement sequence. Wander measurements
will be resumed after an AC power failure.
The “intermediate” evaluation starts afresh on restoration of AC power. The “intermediate”
intervals are then no longer synchronous with the absolute time.
10.2 Examples
Time
No restore start
1.
No restore start
2.
Restore start
3.
4.
Fig. O-42 Examples of ANT-20/ANT-20E behavior in the event of an AC power failure (manually trig-
gered measurements)
2. AC power fails before the first set of backup data is generated. The power failure lasts much
longer than in the previous case:
On restoration of AC power, the measurement is not resumed.
A power failure within the first 15 seconds of a measurement means that no backup data has
been generated. A “restore start” is therefore not possible; the measurement must be
restarted manually. The duration of the power failure in this case is almost until the normal
end of the measurement. A “No-Power” alarm will not be displayed.
3. AC power fails after the first set of backup data has been generated:
On restoration of AC power, the last set of backup data is loaded. The data is restored and
the measurement resumed.
The time from the generation of the last set of backup data until the “restore start” of the
measurement is indicated as a “No-Power” alarm and is taken into account in the restored
measurement values. The original stop time is retrieved from the last backup data and the
measurement restarted so that it ends at the stop time originally programmed (“Restore
Start”).
The “No-Power” alarm time is included in the “Elapsed Time”. At the end of the
measurement, the “Elapsed Time” is equal to the “Gate Time”.
4. AC power fails after the first set of backup data has been generated:
AC power is restored after the normal end of the measurement time.
As backup data was generated before the power failure, this backup data will be loaded
when power is restored. The data is restored and the end results generated (measurement
has ended). The time from the start of the AC power failure until the programmed end of the
measurement is indicated as a “No-Power” alarm. The “No-Power” alarm time up to the
programmed end of the measurement is included in the “Elapsed Time”. Hence the “Elapsed
Time” is equal to the “Gate Time”.
If the measurement start time that you enter has already passed, the ANT-20/ANT-20E will start
measuring immediately when you press “F5” MEASUREMENT START. The measurement will
run for the set gate time. This behavior is independent of the AC power failure behavior.
Timer-controlled measurements are handled as follows:
The ANT-20/ANT-20E calculates the remaining time to the originally-programmed end of the
measurement from the configuration parameters. The measurement resumes and runs for this
calculated remaining time.
Time
Normal measurement
1.
Actual start
2.
Actual start
3.
4.
Restore start
5.
6.
Fig. O-43 Examples of ANT-20/ANT-20E behavior in the event of an AC power failure (timer-controlled
measurements)
1. The AC power failure occurs between activation of the timer and the time when the timer
triggers the start of the measurement:
The AC power failure has no effect.
As no backup data could be generated and the actual start of the measurement is still in the
future, the measurement will be set normally with timer activated as soon as the AC power
is restored. A “No-Power” alarm will not be recorded or displayed.
2. The AC power failure lasts beyond the time when the timer should trigger the measurement
start:
The measurement starts asynchronously as soon as AC power is restored and runs for the
remaining time to the programmed stop time. The stop time is given by the timer start time
setting plus the gate time setting. A “No-Power” alarm will be detected and recorded. The
duration of the “No-Power” alarm is the time difference between the timer start and the actual
start. As the “No-Power” alarm is counted from the timer start time setting, the “Elapsed
Time” = “Gate Time” at the end of the measurement.
4. The AC power failure lasts for the entire programmed measurement time:
On restoration of AC power, the ANT-20/ANT-20E establishes that no backup data was
generated and that the stop time has already been reached. The measurement will therefore
not be started.
The ANT-20/ANT-20E stores the calculated stop time when the timer is activated and
compares this with the actual date and time when power is restored. The start time, “No-
Power” alarm duration and stop time may therefore be recorded.
4
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Virtual instruments
1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI-1
1.1 Application Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI-2
i
Mainframe, SONET Version ANT-20/ANT-20E
ii
ANT-20/ANT-20E Mainframe, SONET Version
Virtual instruments
1 Overview
To allow the instrument to be operated simply and logically despite the large number of
functions, a user interface was developed for the ANT-20 family of instruments that makes use
of virtual instruments, VIs. These VIs are designed so that each VI is assigned to a clearly
defined task. By selecting specific VIs, customized applications (or tools) can be generated
which are tailor-made for each particular measurement task.
The following is an overview of all VIs that are available.
Icon Name
Application Manager Control and management of measurement Sec. 1.1, Page VI-2
applications
Anomaly/Defect Generates anomalies and defects for the Sec. 3, Page VI-12
Insertion physical layer including the “Transmission
Convergence Sublayer”.
Anomaly/Defect Analyzes anomalies and defects for the Sec. 4, Page VI-14
Analyzer physical layer including the “Transmission
Convergence Sublayer”.
Overhead Generator Edit physical frame overhead information. Sec. 5, Page VI-23
Used with SDH, SONET and PDH/ATM
frames to G.832 (34 Mbit/s and 140 Mbit/s).
PDH Generator/ Set and display physical frame overhead. Sec. 9, Page VI-38
Analyzer Used with PDH frames.
The “ANT20 - <Application Title>” VI, also known as the Application Manager is the central
control panel for the ANT-20.
This VI has overall control of
• Measurement applications
• Measurement results generated using the applications
• Measurement sequence.
Detailed information is found in part 3 “Operating Fundamentals”.
2 Signal Structure
The “Signal Structure” VI is used to match your ANT-20 to the measurement interface of the
device under test and to generate appropriate signal structures for the generator and receiver.
The VI has the following functions:
• Entering the signal structure
• Selecting the Tx/Rx interfaces
• Automatic functions: Auto Config, Search, Trouble Scan, Delay, APS-measurement.
After the VI has booted up, the main window, “Signal Structure”, is displayed.
Display area
showing the
signal structure
Auto Automatic functions, e.g. receiver configuration Sec. 2.5, Page VI-8
Aux Select interface for Drop&Insert function Sec. 2.3, Page VI-7
This dialog is used to set the structures of the asynchronous (DSn, En), SONET and SDH
signals using corresponding buttons arranged in columns. Additional instrument modes are also
provided.
Fig. VI-2 Displaying and setting the signal structure using ANSI (Tx side) as an example
Basic procedure:
1. Set Rx signal structure.
2. Click the “Tx” button.
3. Click the “Through” button.
“Replace” Block&Replace: (only possible with STS3c SPE and STS1 SPE
mapping) Generator and receiver are coupled. The received signal
is looped through from the receiver to the generator. The ANT-20 is
used on the receive side as a measurement channel monitor. The
AU of the measurement channel is re-formed on the transmit side.
Example:
Basic procedure:
1. Set Rx signal structure.
2. Click the “TX” button.
3. Click the “Replace” button.
“ADM Test” Add/drop multiplexer test: ADMs require a valid optical signal, even
for measurements on tributaries. The instrument provides an optical
signal in addition to the electrical signal.
Example:
Basic procedure:
1. Set Rx signal structure.
2. Click the “Tx” button.
3. Click the “ADM Test” button.
4. Select the optical signal in the “SONET” column.
When the signal is ready, the “PDH” column is enabled.
5. Set the Tx signal structure in the “PDH” column.
Interface “Electric.” Electrical interfaces Tx: [13] or [15] Rx: [12] or [14]
“Optical” Optical interfaces Tx: [18] Rx: [17]
for OC-48/STM-16 Tx: [47] Rx: [44]
“Bulk” Fills the entire synchronous signal container with a pseudo random
test pattern.
“ATM” Generates an ATM cell stream in the selected PDH signal (ATM
mapping in PDH signals). For further signal definitions, see “ATM
Signal Structure” VI.
“Info” button
Press this button to display SONET or SDH signal structures conforming to the corresponding
standard, “ANSI” or “ITU-T”, that you have selected previously.
The “Interface” dialog is used to configure the parameters for the Tx and Rx interfaces.
Tip: The interfaces for “Drop & Insert” mode are configured in the “Aux” menu.
Switch wavelength
The “Channel” dialog is used to set the measurement channel in all hierarchy levels of the
tributary structure for the generator and receiver.
The “Autoconfiguration” dialog automatically sets the receiver of the ANT-20. A search is made
at the electrical inputs (input voltage ranges “ITU-T”/“High” or “PMP”/“Low”) or at the optical
inputs for standard SONET, SDH, PDH or ATM signals. The instrument version and options
fitted determine the scope of the search. The main objective is to determine the signal structure.
Detailed matching to the signal contents can be made manually if required.
Basic procedure
1. Select the type of input level (ITU-T or PMP).
2. Click the “Start” button to start the search.
The Rx signal is checked for its system bit rate, line code, pattern and signal level. If the
search is successful, the “Result” will display the signal structure that was detected.
3. To configure the receiver to the detected signal structure, click the “OK” button.
Only one channel is considered in the signal structure hierarchy in each case.
Status message “Autoconfiguration uncertain”
1. Click the “Start” button.
The search is triggered again.
2. If the search is successful, click the “OK” button.
– or –
If the search result is again uncertain, click the “Cancel” button.
If The previous signal structure settings will be reinstated, which was selected before
beginning Autoconfiguration.
Search criteria
The signal structure is determined according to the following search criteria:
Check Interface Matching to the physical parameters (bit rate / line code)
Check Mapping Searches for the mapping structure using the signal label and pointer bytes (distinction between
AU-4 / AU-3). The search is always made in channel #1. If the signal is STM-16 / OC-48, the
search is made for an AU-4 structure only in “ITU-T” mode or for an AU-3 structure only in
“ANSI” mode.
LOF/OOF LOF/OOF
AU-AIS AIS-P
MS-AIS AIS-L
TU-AIS AIS-V
AU-LOP LOP-P
TU-LOP LOP-V
LOM LOM
If an UNEQuipped signal is detected, the previously selected mapping setting will be reinstated
or a default mapping will be set.Autoconfiguration recognizes “C-11 via TU-12” mapping as
“C-12” mapping.
Check Payload The search only takes account of the test patterns recommended in the standards.
PDH signals: Search for unframed or framed payload signals on all hierarchy levels
.
If no pattern synchronization is reached (Defect LSS), the test pattern evaluation will be swit-
ched off (Pattern = Real Traffic).
The “Delay Measurement” is used to measure the signal delay times between the Tx and Rx
sides using characteristic patterns included in the pseudo-random sequences. The delay
measurement is an automatic measurement made by repeating single measurements
continuously. It can be made using practically all the available ANT-20 signal structures.
Exceptions:
• ATM signal structures
• Measurements in the overhead
• Through mode
• ADM test
• Contiguous concatenation
• Virtual concatenation
The measurement range and measurement time depend on the pattern bit rate and the pattern
selected. The maximum possible measured value is determined by the length of the pseudo-
random sequence. This maximum is calculated and displayed; it can be influenced by selecting
a shorter or a longer test pattern.
The “APS Time Measurement” dialog is used for measuring the switching times of automatic
protection switching (APS) to demonstrate that the permitted maximum drop-out times for a
connection are not exceeded. The dialog is only available if the “Extended Overhead Analysis”
option is fitted.
Using a selected criterion such as AIS or bit error burst, the drop-out times of tributary
connections are measured and compared with a pre-set check value. The selectable criteria
are:
• AIS-L, AIS-P, AIS-V, TSE (ANSI)
• MS-AIS, AU-AIS, TU-AIS and TSE (ITU-T)
The result is a simple “Passed” or “Failed” message.
Result display:
qualitative: PASSED / FAILED
quantitative: measured switching time
Tip: If the sensor criterion is already present in the signal at the start of the measurement, the
time cannot be measured. To correctly detect test pattern drop-out (sensor = TSE) the
basic bit error rate of the path must not exceed 2E-4.
Display Meaning
FAILED (Signal) An impermissible defect occurred during the measurement that blocked the
sensor (e.g. LOS or LOF if sensor = AIS-L)
Further information on the automatic scan functions such as “Trouble Scan” and “Search” are
found in part 5: “Application Guide” of this operating manual.
3 Anomaly/Defect Insertion
The “Anomaly/Defect Insertion” VI is used to insert anomalies (errors) and defects (alarms) into
signals of synchronous (SDH/SONET), asynchronous (PDH) and ATM communications
systems.
After the VI has booted up, the “Anomaly/Defect Insertion” window appears.
Menu bar and toolbar Anomaly entry Menu bar and toolbar Defect entry
Dynamic defects
4 Anomaly/Defect Analyzer
The “Anomaly/Defect Analyzer” VI is used to display the results obtained using the “Anomaly/
Defect Insertion” VI in four different ways.
After the VI has booted up, the results window for displaying the anomalies and defects as a
histogram (View - Graph) appears. The alternative display modes are described in subsequent
sections.
Cursor
The option buttons of the display filter (see Fig. VI-9) are used to select the results registered
within the measurement interval and enable their access in the appropriate results windows.
The results for anomalies and defects can be shown separately or in a combined display. Other
selection criteria are provided in the “User Filter” dialog.
The scrollbar lets you display all the registered results within the display window. Clicking on an
event button causes the rate per time for that event to be displayed.
In “View - Table” display mode, a table is displayed of anomalies as count values and defects
as duration values.
Display filter
Anomalies (count/second)
Anomalies (count/second)
Display filter
If a large number of events that cannot all be displayed at once occur during the measurement
interval (long-term measurement), the scrollbar can be used to move the results that are not
visible into the display window.
The option buttons (display filter) are used to select the results list. The results for anomalies
and defects can be shown separately or in a combined list in order of occurrence. The “Current”
option displays all current defects. “Current” can only be selected during a running
measurement.
Other selection criteria are provided in the “User Filter” dialog.
Print/Export
The “Print” menu is used to print out the measurement results or to export them for further
processing using other programs.
In “View - Num” display mode, all anomalies are listed in a table of “Total Results” (Count and
Ratio) and “Intermediate Results” (Count and Ratio).
“Total Results” is the number of events that occurred during the entire measurement interval.
“Intermediate Results” is the number of events occurring within a defined time period (“Interm.
Time”). Both these time periods are set in the Application manager (“Measurement Settings ...”).
Results
The “Anomalies: One” option button provides an enlarged display of a single result.
The single result to be displayed (Total or Intermediate Result) is selected from the list box. The
“Anomalies: All” option button switches the display back to “View - Num” mode. All other icons
and menus in the enlarged display correspond to the “View - Num” display.
In “View - Summary” display mode, anomalies and defects are shown as a summary during the
course of the measurement.
Display filter
Overall evaluation of "Anomalies and defects"
Accepted Depending on the setting selected in the “Hierarchy” menu, only “NEAR END”
results (e.g. TSE) or “NEAR END” and “FAR END” results will be taken into
account.
The “User Filter” dialog is used to select specific results to be displayed in the result windows of
the VI. To do this, the “User” option must be selected in the corresponding result window.
Select complete
result groups
Individual results can be evaluated and displayed by clicking on the event required in the
“Anomalies” or “Defects” list boxes. One or more events can be marked in each list box. You
can also select complete groups of anomalies and defects using the buttons in the “Preselect”
field.
The selected anomalies and defects are used for all four display modes of the VI.
The result display takes all registered result values for the events into account. If only a certain
range of values is of interest, count thresholds can be set for anomalies and time thresholds for
defects. When these thresholds are activated, only those values above the threshold value will
be displayed.
The “User Filter” can only be activated when there is no measurement running.
4.6 Dialog: Go to
The “Go to” dialog provides support in analyzing long-term measurements where a large
number of results are displayed. The date and exact time for the display are entered in the “Go
to” dialog. When you exit from the dialog (by clicking the “OK” button),
• the cursor jumps to the corresponding position in the histogram (View - Graph)
– or –
• the corresponding event is displayed in the first line of the table (View - Table).
Fig. VI-15 “Go to” dialog for entering the time for the analysis
The “Settings” menu is used to set various detection parameters and to select measurement
modes.
The menu contains the following commands:
Select measurements ... The “Select measurement” dialog window opens. Various
measurements can be selected for DS3 and DS3 PLCP
mappings.
Beep on Anomalies/ On / off toggle for “Beep on Anomalies/Defects”.
Defects1 If the toggle is on, any anomalies and / or defects occurring during
a measurement will be signaled by a beep.
1 in preparation
5 Overhead Generator
The “Overhead Generator” VI is used to edit the bytes in the TOH (SONET) / SOH (SDH) and
POH of the selected channel. The dynamic bytes (B1, B2, B3) and the pointer line cannot be
edited.
Overhead matrix
Descriptor Bytes for APS (ring and linear), synchronization and path label
Type Opens the “TCM Sequence” dialog for editing the TCM sequence
1. Click on the TOH/SOH byte in the main window, which has to be edited.
2. Select desired function in the toolbar.
3. Press “Edit” button.
Depending on the byte type selected, one of the following windows will open:
– “Edit Overhead Byte”
– “Trace Identifier Editor” (when J0, J1, J2 or TR selected)
– “H4 sequence editor” (for VT1.5/VT2/VT6 mapping or C-11/C-12/C2 mapping)
The selected byte is edited in this window. The button has no function for E1, E2, F1, F2 and D1
to D12 and K1 to K2 if the selected byte is set to TP (test pattern) or EX (external).
Note: If you want to edit the TCM sequence, first click on the N1 or Z6 byte in the main window
and then click on the “TCM” icon button.
Clicking this icon button sets all elements of the TOH/SOH and POH matrix to their default
values.
The “Descriptor” dialog is used to fill certain bytes in the overhead matrix with plain text
information:
• K1 to K4: APS commands
• S1: Clock source
• C2/V5: Path label
The information is identical to the commands in the corresponding standard. You can also
select whether the commands for Ring APS (G. 841) or Linear APS (G. 783) are to be applied.
K1 byte
S1 byte
C2/V5 byte
Fig. VI-17 “Descriptor” dialog with SOH/POH bytes for plain text input
This button opens the “Background POH” dialog. The button is only active if
option BN 3035/90.92 is fitted and “Virtual Concatenation” signal structure is selected.
Same as Channel #1 POH #2 through #4 are filled with the same content as POH #1.
Fixed Bytes POH #2 through #4 are filled with a fixed value.
The “TCM” button is only active if one of the bytes N1 or Z6 is marked in the overhead matrix
(POH).
The “TCM Sequence” dialog and the “Keyboard” dialog open when you click on the “TCM”
button. “TCM” stands for “Tandem Connection Monitoring”. You can edit the 76-byte TCM
sequence for the TCM bytes N1 and Z6 using the “Keyboard” dialog.
Fig. VI-19 “TCM Sequence” dialog with “Keyboard” dialog for editing the TCM sequence
If you click the “ON” button in the “TCM Sequence” dialog, the TCM sequence shown in the list
box will be transmitted. If the content of the list box is changed while a sequence is being
transmitted, the changes will not take effect until you click the “Update” button.
If you click the “Edit” button in the “TCM Sequence” dialog, the “Edit TCM Sequence” dialog
opens. This dialog allows you to insert TCM anomalies and TCM defects into the TCM
sequence very easily.
If you want to transfer the current content of the list box to the transmitter when the “Edit TCM
Sequence” dialog is open, you must click on the “Update” button in the “Edit TCM Sequence”
dialog.
Fig. VI-20 “TCM Sequence” dialog with “Edit TCM Sequence” dialog for editing the TCM sequence
6 Overhead Analyzer
The “Overhead Analyzer” VI is used to display the contents of the “TOH (SONET) / SOH (SDH)”
and “POH” overhead bytes of the received channel.
Test Pattern Group: Display test pattern in byte groups (e.g.. D1 to D4)
Settings Select expected values for trace identifier, path label and H1 byte
The “Type” menu is used to set the various evaluation modes for the individual bytes.
Basic procedure
1. Select the byte of interest in the overhead matrix.
The field color changes from gray to white.
2. Select the evaluation mode from the “Type” menu or using the corresponding icon buttons.
The “Interpreter” window is used to display the actual content of the various bytes in plain text.
You can also select whether the evaluation is to be performed according to “Ring APS (G. 841)”
or “Linear APS (G. 783)”.
Fig. VI-22 “Interpreter” window for plain text display of TOH/POH bytes
The “Settings” dialog is used to activate the receiver for checking the Trace Identifier or the Path
Label. To do this, specify expected values for the Trace Identifier (J0, J1, J2) or Path Label
(PLM-P, PLM-V). The device under test is operating correctly if the receive signal meets the
expected values. If the receive signal does not match the expected values, the “Trace Identifier
Mismatch” or “Path Label Mismatch” alarm messages can be generated. These defects are
indicated in the “Anomaly/Defect Analyzer” VI.
You can also set the expected values for the SS bits in the H1 byte in the “Settings” dialog. The
“LOP-P” alarm is generated if the SS bits received do not correspond to the expected SS bits.
SS bits will not be evaluated if you set the expected value of the SS bits to “Don’t care” (xx).
Defect definition
The “Byte Capture” dialog is part of the “Extended Overhead Analysis” option, BN 3035/90.15
and is opened by clicking on the above icon button.
The capture function allows you to record a single byte, or two bytes simultaneously in the case
of K1 and K2. Recording is prepared by clicking the “START” button and begins when a pre-set
trigger condition occurs. After this, a change into this byte is recorded on a frame-by-frame
basis with timestamp until the buffer is full or you click the “STOP” button. When recording 2
bytes (K1 and K2), the buffer capacity is 200 entries. For single bytes, 265 entries can be saved.
Selected byte
Structure setting (“Interpreter” dialog)
Compare The content of the recorded byte must be the same as the compare
value. Enter ‘X’ for ‘don’t care’ bit values
Compare not Inverse compare condition. Recording starts when the value no longer
corresponds to the compare value.
N1/N2-TCM N1/Z6-TCM Starts recording TCM frames when the TCM FAS word has occurred
(Tandem Connection Monitoring).
Requirement: The N1/N2 or N1/Z6 byte is activated for Tandem
Connection Monitoring.
7 Pointer Generator
The “Pointer Generator” VI is used to generate individual pointer actions and pointer sequences
according to the ANSI, Bellcore and ITU-T standards.
Unit - Frame Units for the time parameters (T1 to T5) in frames
Unit - Millisecond Units for the time parameters (T1 to T5) in milliseconds
Unit - Second Units for the time parameters (T1 to T5) in seconds
Standard sequences
All the standard sequences to ITU-T G.783/ANSI T1.105.03 can be used directly or can be
edited for special applications.
• “87-3” sequence
• “43-44” sequence with double pointer
• “86-4” sequence with double pointer
More information on generating special pointer actions / sequences is found in part 7 “Technical
Background”.
Selecting parameters
Clicking on this icon or selecting the “Delta Pointer Offset” command in the “Concatenation”
menu opens the “Delta Pointer Offset” dialog. This dialog remains open until you select the
“Delta Pointer Offset” command again.
An offset carried by the pointer for channel #1 can be set in this dialog for the pointers for
channels #2 through #4. The pointer actions for channel #1 are set in the display / entry box of
the main window.
The pointer actions for all channels are activated from the “Action” menu.
A change of more than 1 in the value of the pointer offset will be realized by consecutive
changes of 1 at intervals of 32 frames. During this time, the Pointer Generator cannot be
operated.
In the extreme case: 160 changes x 32 frames x 125 microseconds = 640 milliseconds.
8 Pointer Analyzer
The “Pointer Analyzer” VI is used to display the pointer values (addresses) and to show the
number of pointer actions graphically:
Result display:
Current STS and VT pointer values
Cursor
Pointer increments/decrements
The option buttons and the “Diagram” menu for selecting the diagram display and the “Print
Delta Pointer” command are only active for virtual concatenation.
Cursor - First/Last Set the cursor to the start / end of the record
The results for the actual position of the cursor are displayed in the “Cursor” window. It also
shows the pointer increments and decrements and the equivalent clock deviation in ppm.
The “Print” menu is used to print out the results or to export them for processing using other
programs.
9 PDH Generator/Analyzer
The “PDH Generator/Analyzer” VI is used to set and analyze selected parameters of framed
PDH signals.
Menu bar
Input:
Display: “RX” parameters
“TX” parameters:
Frame bits
Frame bits
Menu Function
Feac Loopcode Loops for system components can be activated and deactivated
(active only for “DS3/Framed/C-Parity”)
Timeslot contents
• TS 16 Frame 0: For timeslot 16 in frame 0 (user-defined 8-bit word).
• TS 16 Frame 1: For timeslot 16 in frame 1 (user-defined 8-bit word for signals with special
multiframe structure).
• TS 16 Frame 2 to 15: For timeslot 16 in frames 2 through 15 together (user-defined 8-bit
word for signals with special multiframe structure).
Offset (TX)
Static offset for the PDH tributary bit rate during insertion into the SDH container
(±100 ppm for all bit rates, relative to container; Step width: 1 ppm)
The offset is an average value. The actual offset at any given time may be above or below this
value.
Offsets (RX)
Display of tributary channel offset. The deviation from the nominal bit rate is shown for each
tributary in ppm.
Asterisks (*) are displayed in the boxes if display or measurement is not possible, e.g. because
of an alarm being present or because of the signal structure setting.
The “Idle” dialog is used to set the D and NFAS bits for the idle channels.
If signal structures according to ANSI are selected, the “PDH Generator/Analyzer” VI serves to
display offsets of DS1 and DS3 tributaries.
Menu bar
TX offset RX offsets
10 Performance Analysis
Result display
Analysis - G.826 ISM G.826 In-service measurement Sec. 10.4, Page VI-45
For performance analysis to ANSI/BELL standards, definitions from GR-253 and T1.231 are
used. The parameters ES, SES, EFS, SEFS and UAS measured for various hierarchy levels.
Analysis is performed on the following levels:
• SONET: Section (B1), line (B2SUM, REI-L), STS path (B3, REI-P), VT path (BIP-V,
REI-V)
• DS3: Line (BPV), path (FE, Parity, FEBE)
• DS2 Line (BPV)
• DS1: Line (BPV), path (FE, CRC6)
• Bit: TSE
Clicking on the above icon button allows you to perform a G.821 analysis in the “Performance
Analysis” window. The ITU-T G.821 analysis corresponds to Recommendation G.821 (Issue
date 07/95).
Degraded minutes are also evaluated.
A multiplex factor can be taken into account during the analysis, corresponding to older versions
of Recommendation G.821 (Annex D).
G.821 analysis can be performed on the following events:
• Bit errors (TSE, Test Sequence Error)
• FAS bit errors (FAS 2, FAS 8, FAS 34, FAS 140)
• CRC errors
• EBIT errors
The following signals can be measured when G.821 analysis is performed for test sequence
errors (TSE):
• Unframed pattern without bit rate limitations
• N x 64 kbit/s
• Framed patterns and bulk signals
• Overhead bytes E1, E2, F1, F2, F2L, D1 to D3 and D4 to D12 in the SOH / POH of
SDH signals
Note: As the G.821 analysis uses bit error evaluation, you cannot switch to block error
evaluation.
Clicking on the appropriate icon button shown above allows you to perform G.826 “In Service”
(ISM) and “Out of Service” (OOS) analysis in the “Performance Analysis” window.
The following results are determined for the various hierarchy levels:
EB, BBE, ES, EFS, SES, UAS, PATH UAS and VERDICT.
In the case of G.826 ISM, the ANT-20 analyses both forward and backward channel (“Near
End” and “Far End”), if this is possible at the measuring point selected.
Measurement is performed at framed signals of the primary system level or higher in the case
of G.826 ISM. The following anomalies can be evaluated:
B1, B2SUM/MS-REI, HP-B3/HP-REI, LP-BIP8/LP-REI, LP-BIP2/LP-REI,
FAS140, FAS34, FAS8, FAS2, CRC4/EBIT,
G832-FAS140, G832-EM140/REI, G832-FAS34 and G832-EM34/REI.
For ANSI mappings, the following anomalies can also be measured: DS3 P-Parity, DS3 C-
Parity, FAS45, FAS1.5 and DS1-CRC6.
The measuring point the G.826 ISM evaluation is performed at is set in the “Hierarchy” menu.
In the case of G.826 OOS, measurement is performed at unframed test signals. TSE block
errors are always evaluated.
Note: As the G.826 analysis uses block error evaluation, you cannot switch to bit error
evaluation.
Fig. VI-37 “Performance Analysis” window showing ITU-T G.826 ISM (in-service measurement)
Clicking on the above icon button allows you to perform a G.828 analysis in the “Performance
Analysis” window.
G.828 evaluation conforms to ITU-T Recommendation dated 3/2000. The G.828 standard is a
further development of Recommendation G.826 for synchronous digital paths.
Recommendation G.828 specifies additional measurement values and measurement points:
• SEP (Severely Errored Period, declared as optional)
• Performance measurement on TCM bytes (in preparation for ANT-20)
G.828 evaluation can be performed on the following events:
• B1
• B2SUM
• MS-REI
• B3
• HP-REI
• LP-BIP 2/8
• LP-REI
• Bit errors (TSE)
All G.828 results are determined separately for the near end and far end.
The far end evaluation will be interrupted by certain alarms, such as LOS, LOF or AIS. These
alarm times are excluded from the reference value for the rate computation at the far end.
Clicking on the above icon button allows you to perform a G.829 analysis in the “Performance
Analysis” window. G.829 evaluation can be performed on the following events:
• B1
• B2SUM
• MS-REI
• Bit errors (TSE)
Note: The special block error evaluation using BIP-1 blocks means that the instrument is run
in bit error evaluation mode. It is therefore not possible to switch to block error
evaluation. This does not apply to the TSE meas. point, for which real block errors are
evaluated. You cannot therefore switch to bit error evaluation when making a
G.829 evaluation on TSEs.
Further information see part 7 “Technical Background”.
Clicking on the above icon button allows you to perform a M.2100 analysis in the “Performance
Analysis” window. M.2100 analysis can be performed on the following events:
• Bit errors (TSE)
• FAS bit errors (FAS1.5, FAS2, FAS8, FAS34, FAS45 and FAS140)
• CRC errors (CRC-4 and CRC-6)
• EBIT errors
• PBIT errors
Parallel M.2100 analysis at the “near end” and the “far end”
Analysis of PCM30CRC signals is performed simultaneously at the “near end” and the “far end”.
All the M.2100 results for the near end and for the far end are determined separately.
Far end analysis will be interrupted by certain alarms, e.g. LOS, LOF or AIS. The times of these
alarms will be subtracted from the reference value for determining the far end ratio results.
M.2101 evaluation takes the issue of Recommendation M.2101 dated 6/2000 as well as the
version M.2101.1 of April 1997 into account. You can switch between the two versions via a list
box in the "Settings" menu. The main differences between the Recommendation M.2101 (4/
1997) and the Recommendation M.2101 (6/2000) concern additional measurement values as
well as differences in the error performance objectives:
• BBE (Background Block Error)
• SEP (Severely Errored Period)
• Performance measurement on TCM bytes (in preparation for ANT-20)
SEP evaluation is optional in the new Recommendation M.2101 (6/2000). The "Settings" menu
therefore includes a separate switch for including or excluding SEP from the assessment
verdict.
M.2101 evaluation can be performed on the following events:
• B1
• B2SUM
• MS-REI
• B3
• HP-REI
• LP-BIP 2/8
• LP-REI
• Bit errors (TSE)
Notes:
5
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Application Guide
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
1.1 The Application Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
1.2 Signal Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
i
Mainframe, SONET Version ANT-20/ANT-20E
ii
ANT-20/ANT-20E Mainframe, SONET Version
iii
Mainframe, SONET Version ANT-20/ANT-20E
25 Measuring the CLR with a variable cell rate (VBR traffic) . . . . . . A-82
25.1 Test setup and description . . . . . . . . . . . . . . . . . . . . . . . . . A-82
25.2 Switch configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-82
25.3 Application selection on the ANT-20. . . . . . . . . . . . . . . . . . A-82
25.4 Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-83
iv
ANT-20/ANT-20E Mainframe, SONET Version
Application Guide
1 Introduction
This manual is intended to simplify use of the ANT-20. Starting with the basic settings, the
procedure for a successful measurement is explained step by step for each of the various
measurement applications of the ANT-20. The basic settings are repeated for each subsequent
application described.
Once you have switched the instrument on and the Windows environment is displayed, the
Application Manager appears in reduced format.
Measurement dialog
Virtual instruments
The Application Manager is the starting point for each measurement. The various measurement
windows for a measurement are selected and the maximum measurement duration is set here.
The ANT-20 represents a collection of several specialized measuring instruments, each of
which fulfils a particular task. Each “instrument” is represented by a corresponding window. The
ANT-20 test windows are therefore called “Virtual Instruments” (VI). Depending on the
measurement, various VIs are combined to make an application.
Select the instruments required from the left-hand list box and add them to the application using
the “Add>>” button. In the initial state, the list of VIs used (right-hand list box) contains the
“Signal Structure” window. The other VIs needed for a particular application are detailed in this
documentation. We will begin with the “Signal Structure” VI.
The signal structure used for the measurement is set using the “Signal Structure” VI. Use the
Application Manager to activate the window:
.
⇒ To change the structure, select the “Signal Structure...” sub-menu from the “Edit” menu.
The following window will be displayed:
2 In-Service Monitoring
This section describes how you can use your ANT-20 to monitor systems that are in service.
This type of monitoring is required for various measurements that are described later on.
1. Monitoring from a protected monitoring point (PMP) of the DUT or a special test cable
Interfaces
Interfaces
Interfaces
Interfaces
see Sec. 2, Page A-5
This function allows sequential testing of all VT6, VT2 and VT1.5 channels in a STS-1/OC-1
signal. The ANT-20 receiver checks whether alarms have occurred in the input signal, in the
SONET structure and in the channels. The channels are then indicated in a table as being OK
or not OK. After the measurement, the detailed alarm status for each channel can be displayed.
Interfaces
• electrical unbalanced Rx : [14] Tx : [15]
• optical 52, 155, 622 Mbit/s Rx : [17] Tx : [18]
Schematic diagram
VIs required
• Signal Structure
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-13):
3.3 Measurement
1. Click on “Trouble Scan...” in the “Auto” menu in the “Signal Structure” window.
A window showing a matrix of all the channels opens.
2. Click on the “Start” button.
The measurement starts. Each channel is tested and marked separately.
The measurement stops automatically.
3. To analyze a channel in more detail, select the channel and then click on the “Details”
button.
The following window opens:
The alarms that occurred in the channel during the measurement are indicated by red dots.
In contrast to the Trouble Scan function, in this function the generator and receiver channels are
switched and tested simultaneously. The synchronization of the selected pattern is tested in all
channels in addition to the presence of any alarms. The channels are then indicated in a table
as being OK or not OK.
Interfaces
Schematic diagram
VIs required
• Signal Structure
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-18):
4.3 Measurement
• Errored channels are marked with a red cross (see channel 04 in example).
Interfaces
This function provides a rapid and simple way of finding channel shifts in synchronous DCS and
ADMs. The ANT-20 receiver searches all channels for a pre-selected test signal. When the
signal is found, the channel is marked in the table with a green check. Depending on the
configuration of the DUT, the test pattern may be present in more than one channel. The
ANT-20 transmit channels are not switched simultaneously.
Schematic diagram
VIs required
• Signal structure
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-22):
5.3 Measurement
The figure shows an example Search mode result. The channels to be located are channel 04
and 05.
Interfaces
APS stands for Automatic Protection Switching. This is a function of SONET networks that
prevents connections from being interrupted for a long period if a working line fails.
If a problem occurs with the working line, the system automatically switches to a back-up line.
The time taken to switch circuits must conform to certain requirements.
To check that the network meets these requirements, the ANT-20 measures how long a
particular event (e.g. AIS or loss of test pattern) remains present after APS has been triggered.
The measured time is compared with a previously set threshold. This provides a simple
PASSED/FAILED assessment of the APS switching time.
VIs required
• Signal Structure
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-25):
6.3 Measurement
Settings
1. Click on the APS icon button in the “Signal Structure” VI toolbar.
2. Select an event for triggering the switch process from the “Sensor” list box.
3. Set the maximum permitted switching time threshold value in the “Switch time limit (t1)” box.
4. Enter the required duration for the complete measurement in the “Gate time (t2)” box. This
time should be more than the threshold value in order to detect multiple switching.
5. Start the measurement by clicking the “START” button.
6. Trigger the switching process by e.g. interrupting the working line.
The measurement stops automatically when completed.
Analysis
Two results are displayed once the measurement is completed:
• The total duration of the event pre-set in the “Sensor” list box.
• An interpretation of the measured value.
Display Meaning
FAILED (Signal) A non-permitted defect occurred during the measurement that blocked the sensor
(e.g. LOS or LOF if “Sensor” is set to MS-AIS)
Interfaces
This measurement is used to monitor a certain channel for defects and error messages that
occur or to test the reaction of the DUT to artificially-induced defects and error messages.
VIs required
• Signal Structure
• Anomaly/Defect Analyzer
• Anomaly/Defect Insertion
✓ The signal structure has been set and the ANT-20 is connected to the DUT.
Tip: Make sure that you select the corresponding interface when you set the signal structure.
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-28).
2. Now click first on the “Anomaly and Defect Analyzer” button and then on the “Anomaly and
Defect Insertion” button in the Application Manager.
This activates both these applications. To monitor a signal, only the “Anomaly/Defect
Analyzer” is needed.
7.3 Measurement
Example
Measurement of the reaction of a DUT to the insertion of a B2 error at a rate of 1E-6.
Error insertion
Error analysis
The signal and the reaction of the DUT are monitored using the “Anomaly and Defect Analyzer”.
You can choose between four different types of result display.
Histogram (Graph)
The error rate is shown in the “Anomalies” box by clicking on the “B2” button.
Table
This display window is particularly useful if you want to determine when and for how long a
particular event occurred. Errors are shown as a count per second and alarm durations are
shown with a resolution of 100 millisecond.
Summary
Summary display of anomalies and defects. The “Summary” view allows you to see at a glance
whether anomalies or defects occurred during the measurement. The filter function allows you
to exclude certain anomalies and defects from the Summary evaluation.
If the Performance Analyzer is loaded and an evaluation has been selected, the results of this
evaluation will also be displayed.
1. In-service monitoring
Interfaces
These measurements are performed in order to determine the quality of a transmission path.
The measurements are in accordance to ANSI (T1.231) and Bellcore (GR 253)
recommendations. The measurement is based on transmission path test in three different
layers: Section layer, line layer and STS/VT path layer. In this case the corresponding parity
bytes (B1, B2, B3, BIP-V, C-Parity, CRC-6) and the transmitted alarm messages (RDI, REI,
DS3-FEBE) of the reverse direction will be evaluated.
In OOS mode the test signals will be transmitted with PRBS in the payload and evaluated on far
end of the path.
VIs required
• Signal Structure
• Performance Analysis
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-36):
2. Click on the “Performance Analysis” button to activate the VI.
8.3 Measurement
Example
ANSI performance analysis.
Settings
1. Select “ANSI” from the “Analysis” menu.
– or –
Click on the appropriate button in the toolbar.
2. Click on the “Hierarchy” menu (see Fig. A-37).
3. Set the desired hierarchy level for the measurement.
Selecting the TSE setting replaces the path payload by
a PRBS and performs an end-to-end measurement.
4. Start the measurement by pressing function key F5.
– or –
Click on the “green traffic signal” icon in the “Minibar” (Application Manager).
Fig. A-37 “Performance Analysis” window with open pull-down menü “Hierarchy”
Analysis
The analysis provides separate results for the “NEAR END” and the “FAR END”. Put simply, this
means that errors occurring directly in the path are analyzed as well as errors occurring in the
return path which are indicated by a REI message. This allows both directions to be monitored
without actually connecting to both.
For detailed descriptions of different evaluation modes see part 7 “Technical Background”.
Interfaces
This measurement is intended to demonstrate that a network does not produce errors even
when extreme pointer operations occur. Pointer sequences that are specified by the
Recommendation T.1.105.03 are used for this. User-defined sequences can also be used. The
following sequences are pre-defined:
• Single pointer with reversed polarity
• Pointer sequences with one double pointer
43/44 sequence: 43 pointers - 1 double pointer - 44 pointers
• Pointer sequences with missing pointers
87/3 sequence: 87 pointers - 3 missing pointers
86/4 sequence: 86 pointers - 4 missing pointers
26/1 sequence: 26 pointers - 1 missing pointers
• Double pointer with reversed polarity
VIs required
• Signal Structure
• Pointer Generator
• Pointer Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-39).
2. To open the “Pointer Generator” and “Pointer Analyzer” windows, click on the appropriate
buttons in the Application Manager.
.
9.3 Measurement
Example
Measurement of an 86/4 sequence for the STS pointer.
Settings
Synchronizing the ANT-20 to an external clock signal:
1. Click on “Settings...” in the “Interface” menu in the “Signal Structure” VI.
2. Select “Ext. Clock 2M/E1 [25]” from the “Clock Source” box and click “OK” to confirm.
Pointer analysis
The “Pointer Analyzer” has two windows for the two types of pointer, just like the “Pointer
Generator”. The measurement record starts once function key F5 has been pressed.
The results are shown as a display of pointer address versus time and as an absolute value of
increment/decrement (INC/DEC) versus time.
The graphic display makes it easy to see if the system is running synchronously or if wander is
present.
If you click on the “CSR” button, the “Cursor” window opens. This shows the actual pointer value
and the increment or decrement of the pointer per unit time. The corresponding clock deviation
is indicated under the heading “Deviation”.
Fig. A-43 Setup for editing and analyzing the transport/path overhead
Interfaces
Access for manipulation of the individual bits in the TOH and POH is very important for
conformance testing and fault clearance. The ANT-20 allows you to immediately see the
reaction to a manipulation, since the windows for OH generation and analysis are displayed
together on the screen. This allows you to check APS information in the K1 and K2 bytes, for
example. It is also possible to perform BERTs on the embedded communication channels
(ECCs).
VIs required
• Signal Structure
• Overhead Generator
• Overhead Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-44).
2. Click on the “Overhead Generator” and “Overhead Analyzer” buttons to activate both
windows.
10.3 Measurement
The TOH and POH bytes for the selected channel are displayed.
This tool can be used to change the overhead bytes to suit your requirements.
The following bytes are excluded: A1 and A2 (OC-48 only), B1 to B3 and H1 to H4.
The first row of the matrix shows the byte name. The hexadecimal value of the byte is shown in
the next row.
Other abbreviations:
Bytes K1/K2 and K3/K4 contain control commands for the APS system (automatic protection
switching).
The byte name is shown in the left-hand column. The byte is shown in binary code in the center
column. Plain text selection boxes are found on the right-hand side. You can set the various
commands from the ANSI standard here without having to edit individual bits.
The “Overhead Analyzer” window is very similar to the “Overhead Generator” in its layout. The
same byte matrix is used. The byte fields also correspond to those of the “Overhead Generator”.
The toolbar contains two different buttons.
IPR
This button opens the “Interpreter” window. This provides an overview of the contents of the K
bytes, the S1 byte and bytes C2/V5.
The bit patterns for each are interpreted and are also displayed in plain text.
SET
Click on this button to open the “Settings” window. In this window you can edit the expected
values for the trace identifier, path label mismatch and the H1 byte.
What happens if the generator and receiver trace identifiers do not match?
If the generator and receiver trace identifiers do not match a TIM alarm (trace identifier
mismatch) will be detected. This will not be indicated by the LED display on the instrument front
panel.
The presence of the alarm can be demonstrated using the “Anomaly and Defect Analyzer” (see
figure below).
You can select whether an alarm is to be triggered or not in the “Settings” window of the
“Overhead Analyzer” VI. The condition is activated by placing an identifier in front of the trace
identifier (e.g. TIM-V).
Common
alarm display (defects)
TIM-P alarm
Interfaces
• electrical balanced Rx : [12] Tx : [13]
• electrical unbalanced Rx : [14] Tx : [15]
• optical 52, 155, 622 Mbit/s Rx : [17] Tx : [18]
• optical 2.5 Gbit/s Rx : [44] Tx : [47] (1550 nm)
Tx : [48] (1310 nm)
• optical 10 Gbit/s Rx : [113] Tx : [103]
The data communication channels (DCC) are used to control network elements via the network
management system (TMN, Telecommunications Management Network). Bytes D1 to D4
(Section OH) and D5 to D12 (Line OH) make up the DCC. The embedded communication
channels (ECC) contain the DCCs and also bytes E1, E2 and F1. To ensure that these channels
operate correctly, the ANT-20 inserts a bit pattern and performs a bit error test on the receiver
side.
VIs required
• Signal Structure
• Overhead Generator
• Overhead Analyzer
• Anomaly and Defect Insertion
• Anomaly and Defect Analyzer
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-51).
11.3 Measurement
Example
BERT measurement in the DCC
Settings
1. First activate the “Overhead Generator“ and “Overhead Analyzer“ windows so that both are
in the foreground.
2. Select one of the D bytes in the Section OH or Line OH of the “Overhead Generator” (field
has a white background).
3. Click on the “TPG” (test pattern generator) button in the toolbar of the window.
This fills one group (D1 to D4, D5 to D12) with a test pattern.
4. Set the desired test pattern in the “Test pattern” list box of the “Edit Signal Structure” window
in the “Signal Structure“ VI.
5. Repeat the last three steps for the “Overhead Analyzer“ instead of the “Overhead
Generator”.
The D byte fields on both sides will now show “TP“.
6. Activate the “Anomaly and Defect Insertion“ VI and “Anomaly and Defect Analyzer“ VI
windows.
Analysis
You can see if errors occur by means of the “Anomaly and Defect Analyzer“. These are
displayed in the line labelled “TSE-OH“. You can insert TSEs using the “Anomaly and Defect
Insertion“ VI and then observe whether these errors are reflected in the “Anomaly and Defect
Analyzer“ (see Fig. A-53).
Interfaces
The measurement is used to check the maximum tolerable jitter of the electrical and optical line
and tributary inputs.
When a sine-wave modulation signal is used with a pseudorandom sequence as the test
pattern, at a given frequency, the amplitude of the jitter signals is increased using a half-interval
progression until errors occur at the output of the device under test.
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-55).
2. Click on the “JIT” button to open the window for the O.172 Jitter Generator/Analyzer.
12.3 Measurement
Settings
✓ The O.172 Jitter Generator/Analyzer window must already be open.
1. Select the “MTJ” command in the “Mode” menu.
– or –
Click on the corresponding button in the toolbar.
2. Select the error source (e.g. TSE, Test Sequence Error) in the “Error Source” list field
(currently only bit errors are available).
3. Enter the error threshold in the “Error Threshold” field. The error threshold provides a
decision criterion for the search algorithm.
4. In the “Settling Time” field, enter a delay for each measurement that allows the DUT to settle
before the measurement is made.
5. Enter the gate time in the “Gate Time” box.
6. In the “Settings” menu select the “MTJ ...” item.
– or –
Click on the “SET” symbol.
The “Settings” dialog box is opened.
In the box, you will find the measurement frequencies for the MTJ measurement and the
characteristic data for the tolerance mask.
7. If necessary select your own scan frequencies and modify the tolerance mask values.
8. Confirm the input with “OK”.
The “Settings” dialog box is closed.
9. Start the measurement with “Start”. The measurement stops automatically, but can be
halted at any time by clicking on “Stop”.
Analysis
When an MTJ measurement is made, the default values for the scan frequencies and the
tolerance mask are set in the “MTJ Settings” window according to the bit rate. The default
values are changed automatically when the bit rate is changed.
There are two windows for displaying results (see Fig. A-57).
Table format
• Measurement results are displayed in the table under “UI”.
• Measurement results where the tolerable jitter of the DUT is greater than the maximum
amplitude that can be set on the jitter generator, are indicated by a “>” (e.g. >64 UI).
• Measurement results which are below the tolerance mask are marked with an “!” in the table.
Graphics format
• Measurement results are marked with a “+” on the graphics.
• Measurement results where the tolerable jitter of the DUT is greater than the maximum
amplitude that can be set on the jitter generator are marked with “∆” on the graphics
(instead of the “+”).
Fig. A-57 MTJ measurements: Results displayed as a table (left) and graphics (right)
Interfaces
With a Fast MTJ measurement, given combinations of jitter frequencies and jitter amplitudes
which lie on the limit curves stipulated by ANSI are set on the jitter generator.
Each measurement point is classified as “OK” or “Failed”. This indicates whether the DUT meets
the limit curve or not.
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
1. Add the VIs required to the list of VIs used on the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-59).
2. Click on the “JIT” button to open the window for the O.172 Jitter Generator/Analyzer.
13.3 Measurement
Settings
✓ The “O.172 Jitter Generator/Analyzer” window has already been opened.
1. Select the “Fast MTJ” command in the “Mode” menu.
– or –
Click on the corresponding button in the tool bar.
2. Select the error source (e.g. TSE, Test Sequence Error) from the “Error Source” list box.
3. In the “Error Threshold” box, enter the error threshold above which a device under test is to
be considered as having “Failed” the test.
An error threshold cannot be entered if an alarm is selected from the “Error Source” list box.
4. In the “Settling Time” box, enter a settling time for each measurement to allow the d.u.t to
settle.
5. Select “MTJ ...” in the “Settings” menu.
– or –
Click on the “SET” icon.
The “Settings” dialog opens.
8. Click “Start” to start the measurement. The measurement stops automatically on completion
or when you click on “Stop”.
Analysis
• The table (see Fig. A-61) contains combinations of jitter frequencies and jitter amplitudes or
default values specified by the user. Starting with the smallest frequency, they are set when
the measurement is started.
• After the delay set with “Settling Time”, a check is made to determine if there are any alarms
or errors in the input signal.
• According to the result, each setting is classified as “OK” or “Failed”.
• The measurement stops automatically when the last measurement point has been
completed or by clicking on “Stop”.
TX
2.
1. Calibration
measurement
1. DUT
2. Measurement
with DUT
RX
Interfaces
Jitter transfer function measurements are of particular importance when dealing with
regenerative repeaters. Checks are carried out to demonstrate that the jitter gain of a
regenerative repeater is below a predefined value. If this is not the case, “jitter runaway” occurs
after several regenerative repeaters.
The jitter transfer function (JTF) is measured by applying a signal whose jitter is constant over
frequency to the DUT. The jitter amplitude is selected so that the DUT can handle it at high
frequencies.
The Jitter Analyzer measures the resulting jitter amplitude at the output of the DUT at various
TX jitter frequencies. The log of the ratio gives the jitter gain or attenuation.
Tip: For maximum measurement accuracy, it is a good idea to make a calibration
measurement before every JTF measurement (see Fig. A-62).
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-63).
2. Click on the “JIT” button to open the window for the O.172 Jitter Generator/Analyzer.
14.3 Measurement
Settings
✓ The “O.172 Jitter Generator/Analyzer” window has been opened already.
1. In the “Mode” menu, select the “JTF” command.
– or –
Click on the corresponding button in the tool bar.
2. Select the appropriate range (1.6 UI or 20 UI; the range is pre-set for STM-16/OC-48) in the
“RX: Range” box.
3. Enter an appropriate delay time for the various measurements in the “Settling Time” field, so
that the measurement starts after the DUT has settled.
The measurement frequencies for the JTF measurement and the specifications for the
tolerance mask are found here.
1. Select “JTF ...” in the “Settings” menu.
– or –
Click on the “SET” icon.
The “JTF Settings” dialog opens.
2. If required, select individual scan frequencies and amplitudes, as well as altered tolerance
mask values.
3. If you want the measurement to be performed using a constant amplitude for all scan
frequencies, check the “Fixed Amplitude” check box and enter the required amplitude in the
box below it.
4. If you want to use the results of a previous MTJ measurement for the scan frequencies and
amplitudes, click on the “MTJ Adaptation” button. The MTJ results are then automatically
matched to the permissible ranges (measurement and frequency) of the jitter meter. If there
are no MTJ results available, the button is grayed out.
5. Select whether you want to perform a calibration measurement before every JTF
measurement or to use a single calibration measurement (stored internally). For maximum
measurement accuracy, it is a good idea to make a calibration measurement before every
JTF measurement
6. Click “Start” to start the measurement. The measurement stops automatically when finished
or when you click “Stop”.
Analysis
The measurement results are displayed in three different windows. The default values for the
scan frequencies and the tolerance masks in the “JTF-Settings” window are set in the window
with the table display (see Fig. A-66).
• The default values depend on the bit rate and change automatically when the bit rate is
changed.
• Measurement results are displayed in the table under “dB”.
• Measurement results in the table that are outside the tolerance mask(s) are marked with an
“!”.
There are two graphics windows. The right window has the higher y-axis resolution. On the
graph, the measurement values are marked with a “+”.
Interfaces
Phase hits occur when a specific jitter threshold is exceeded. Events of this kind are recorded
using a counter. The current counter reading indicates how often the phase hit threshold has
been exceeded since the measurement was started.
Positive counts and negative counts can be made mutually with the ANT-20 Jitter Analyzer.
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should at least include the following instruments (see Fig. A-69).
2. Click on the “JIT” button to open the “O.172 Jitter Generator/Analyzer” window.
15.3 Measurement
Settings
1. In the “Mode” menu select the “PP+PH” command.
– or –
Click on the corresponding button in the toolbar.
The O.172 Jitter Generator/Analyzer” window opens.
Fig. A-70 “O.172 Jitter Generator/Analyzer” window when the auto function is turned off
3. Enter the threshold values you want under “Hit Threshold” using the list fields.
4. Confirm with “OK”.
5. Start the measurement by
– pressing function key F5 or
– clicking on the “green traffic signal” icon in the Application Manager.
Input to the “Hit Threshold” can be made with the normal keyboard or with the “virtual” keyboard
window.
Analysis
16 Wander Generator
The Wander Generator is used to make manually tolerance to wander measurements
conforming to ITU-T G.823, G.824, G.825, O.172 and ETSI EN302084.
Interfaces
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
• Anomaly/Defect Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should at least include the following instruments (see Fig. A-74).
2. Click on the “JIT” button to open the “O.172 Jitter Generator/Analyzer” window.
3. Click on the button to the right of the “JIT” button to open the “Anomaly/Defect Analyzer”
window.
16.3 Measurement
Settings
✓ The “O.172 Jitter Generator/Analyzer” window is already open.
1. Select the “Settings ...” command from the “Interface” menu in the “Signal Structure”
window.
The “Interface” dialog opens.
2. Select the clock source corresponding to the clock frequency at input [25] on the TX side
from the “Clock Source” list box.
3. Select the “Wander” command from the “TX” menu in the “O.172 Jitter Generator/Analyzer”
window.
4. Set the TX amplitude and frequency according to the tolerance masks of the appropriate
standard.
5. Select the “On” command from the “TX” menu.
Fig. A-76 “O.172 Jitter Generator/Analyzer” window with wander generator activated
6. In the Application Manager, select the “Settings ...” command from the “Measurement”
menu.
The “Measurement Settings” dialog opens.
Analysis
The “Anomaly/Defect Analyzer” window indicates the wander frequency or wander amplitude
above which errors or alarms occur.
SSU
Clock
STM-N
SEC
Wander
Ref. Clock RX
DUT
Interfaces
Every SDH network element can make use of an internal clock (SEC-SDH Equipment Clock).
This clock source is synchronized by means of an SSU (Synchronization Supply Unit) via a
2.048 MHz clock line. To check the quality of the internal clock source, the clock stability of the
reference source (SSU) is compared with that of the transmitted data signal. The difference is
referred to as wander.
The ANT-20 can be used to perform measurements on all interfaces of the instrument.
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should at least include the following instruments (see Fig. A-80).
2. Click on the “JIT” button to open the window for the “O.172 Jitter Generator/Analyzer”.
17.3 Measurement
Settings
1. In the “Mode” menu select “TIE”.
– or –
Click on the “Wander” button in the toolbar.
The wander display appears in the “O.172 Jitter Generator/Analyzer” window.
3. In the “Wander Settings” dialog, set the frequency or bit rate (not for 2488 Mbit/s) of the
reference signal.
4. Select the reference signal input required (BAL [34] or UNBAL [35]) (not for 2488 Mbit/s).
5. Select the sample rate required. The low-pass filter is set automatically.
6. Click “OK” to confirm.
7. Start the measurement by
– pressing function key F5 or
– clicking on the “green traffic signal” icon in the Application Manager.
Wander analysis
Wander analysis involves measurements that take a particularly long time. Measurement
intervals up to 99 days can be set on the ANT-20.
The measured values are displayed in the “O.172 Jitter Generator/Analyzer” window as a graph
of the TIE values and numerically in the MTIE and TIE fields above.
⇒ Click on the “CSR” button in the toolbar.
The “Cursor Position” window then opens. This gives you an overview of the current values
on the curve which is being recorded.
Storing results
1. Select the “Export ...” command in the “Print” menu.
The “Save as” dialog box is opened.
2. Select the target directory, under the current file shall be stored and set the “CSV” format.
3. Click on “Ok” to start exporting.
Starting the “MTIE/TDEV Analysis” program from the “O.172 Jitter Generator/Analyzer”
1. Click on the “TDEV” button in the “O.172 Jitter Generator/Analyzer” (wander side) window.
The program starts and the TIE data from the previous measurement (stored in the file
“WANDMSEC.BIN”) are loaded automatically.
The TIE data are displayed in the graphics box of the “TIE analysis” window.
2. Click on the “MTIE/TDEV ...” button.
The “MTIE analysis” window opens (see Fig. A-84).
3. Click on the “Analysis” button in this window.
The values are calculated and displayed.
Starting the “MTIE/TDEV Analysis” program from the Windows 95 Start menu
1. Click on the appropriate item in the Windows 95 “Start” menu.
The program starts.
2. Click on the “Load” button.
The “Load data file” dialog opens.
3. Select the “WANDMSEC.BIN” file from the “C:\ANT20\RESULTS” directory.
– or –
Select a previously exported CSV format file.
The TIE data are displayed in the graphics box of the “TIE analysis” window.
4. Click on the “MTIE/TDEV ...” button.
The “MTIE analysis” window opens (see Fig. A-84).
5. Click on the “Analysis” button in this window.
The values are calculated and displayed.
Possible evaluations
• The check boxes at the lower left of the “MTIE analysis” window are used to select the
values that you want to display.
• You can limit the number of measurement points to be displayed by entering a range in the
“Analysis range” text boxes.
• You can select different tolerance masks from the “Masks” list box. These can be used to
give you a quick impression of whether the measured values meet the tolerance
requirements or not.
• The displayed graph can be printed out (“Print” button) and exported (“Export” menu).
MTIE values
TDEV values
Passed/Failed
fulfilled or not fulfilled
Interfaces
VIs required
• Signal Structure
• O.172 Jitter Generator/Analyzer
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-86).
2. Click on the “JIT” button to open the window for the O.172 Jitter Generator/Analyzer.
18.3 Measurement
Settings
✓ The “O.172 Jitter Generator/Analyzer” window must already be open.
2. Select the clock source corresponding to the clock frequency at input [25] from the “Clock
Source” list box on the TX side of the box.
7. If required, select your own combinations of frequency and amplitude to be used for the
measurement.
8. Click “OK” to confirm your entries.
The “MTW Settings” closes.
9. Click “Start” to start the measurement. The measurement stops automatically after all
measurement points have been tested. It can also be stopped at any time by clicking on
“Stop”.
Note: The measurement times may be very long due to the frequency settings.
Analysis
• The table (see Fig. A-89) contains combinations pre-selected by the user or the default
values for wander frequencies and wander amplitudes. These are set one after the other in
the order they are entered in the table when the measurement is started.
• After the “Settling Time” has elapsed, the output signal of the ANT-20 is modulated for one
period of the current frequency and the input signal is monitored for the presence of alarms
or errors.
• Depending on the result, each setting will be indicated as “OK” or “Failed”.
• The measurement stops automatically when the last measurement point has been tested.
It can also be stopped at any time by clicking on “Stop”.
Interfaces
SDH network elements must operate without errors even when long sequences occur in which
the bit state remains the same (all zeros or all ones sequences). The Recommendations G.958
and G.783 stipulate that a network element must be able to cope with a bit sequence of zeros
or ones of a length of at least 72 bits (9 bytes) without errors. The tolerance of a network
element to all zeros or all ones sequences is known as consecutive identical digit (CID)
immunity.
A method for testing the CID immunity of network elements is suggested in Appendix X of the
1999 revision of ITU-T Recommendation G.783: The bytes in columns 7, 8 and 9 of the first row
of the SOH / TOH are filled with an all zeros or all ones signal. The J0 byte, i.e. byte S(1,7,1), is
not changed, since it contains the path trace information.
The maximum number of overhead bits that can contain the all ones or all zeros signal depends
on the signal structure:
STM-4/OC-12 88 (= 11 bytes)
To assist you in setting these CID overhead patterns, a number of example applications are
supplied along with the ANT-20 Software. The applications are found on the ITU-T or ANSI
Application Disk.
There is an application for each of the above signal structures, which sets an all ones signal with
a length of 72 bits. There is also an application which sets the maximum number of ones
indicated in the above table for each of the signal structures.
The applications have the following names:
ANSI SONET
• W&G STM-4 VC4 16c 72 bit CID • W&G OC-12 1SPE 72 bit CID
• W&G STM-4 VC4 16c 88 bit CID • W&G OC-12 1SPE 88 bit CID
• W&G STM-16 VC4 16c 72 bit CID • W&G OC-48 3c 72 bit CID
• W&G STM-16 VC4 16c 376 bit CID • W&G OC-48 3c 376 bit CID
• W&G STM-64 VC4 16c 72 bit CID • W&G OC-192 3cSPE 72 bit CID
• W&G STM-64 VC4 16c 1528 bit CID • W&G OC-192 3cSPE 1528 bit CID
When you invoke one of these applications, the bytes in columns 7 to 9 of SOH #1 through #N
are set to the value “FF” (all ones) instead of the default value (AA). The J0 byte remains
unchanged.
If you require CID sequences of other lengths (e.g. for other signal structures), you can gener-
ate these using the ANT-20 “Overhead Generator” VI.
Interfaces
To perform an ATM measurement with the ANT-20, you must first select the corresponding
signal structure. This section describes the step-by-step procedure for this with the aid of an
example.
VIs required
• Signal Structure
• ATM Signal Structure
1. Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-92).
2. For the following settings click on one of the buttons (minibar) to bring the desired window
on top.
Example
ATM signal structure with STS-3 / STS-3c SPE ATM mapping, electrical interface
Fig. A-93 Displaying and setting the signal structure to ANSI standard
2. Select the ATM SDU to be transmitted and received in the test channel:
– Testcell: Test cells to O.191
– AAL-0: PRBS or DW in cell payload
– AAL-1: PRBS or DW as AAL-1 PDU
3. Select the “Performance Measurement” to be used:
– Cell Transfer Delay Results shown in ATM Traffic Analyzer, and
– Error Related Performance Results shown in Anomaly and Defect Analyzer
4. Confirm your settings by clicking on the “OK” button.
The “ATM Structure” dialog will be closed.
Fig. A-96 The “ATM Channel” dialog (“ATM Signal Structure” VI)
2. Enter the VPI/VCI parameters of the test connection for the generator and receiver.
3. Confirm your entries by clicking on the “OK” button.
4. The “ATM Channel” dialog will be closed.
The desired ATM signal structure appears in the diaplay area
of the “ATM Signal Structure” VI.
Fig. A-97 ATM layer signal structure (“ATM Signal Structure” VI)
• Click on the “ON” icon in the “ATM Signal Structure” VI to activate ATM traffic and the
selected test cells are transmitted. If this channel is not active, empty cells will be
transmitted.
• The default setting of the ATM Generator is:
– Traffic type: CBR (constant bit rate)
– 100% load
Fig. A-98 Setup for the ATM bit error rate test
For ATM networks too the bit error test is a basic measurement method that makes it possible
to test network paths quickly and simply or to check configurations of network elements. With
the ANT-20, you measure the bit errors via a test cell channel. Apart from bit error measure-
ments on the cell payload, parallel measurements for correctable and non-correctable header
errors are also being performed. If this error measurement is performed on cells with an AAL-1
structure, the ANT-20 also simultaneously checks the cell sequence integrity so that cell losses
can also be found.
⇒ Set up an unidirectional, permanent connection with a UBR (Unspecified Bit Rate) contract
through the switch.
VIs required
• Signal Structure
• ATM-Signal Structure
• Anomaly and Defect Insertion
• Anomaly and Defect Analyzer
⇒ Add the VIs required to the list of VIs used in the Application Manager..
The Application Manager should include at least the following instruments (see Fig. A-99).
21.4 Measurement
Example 1
Determining the bit error rate in the ATM layer.
Settings
1. First of all, set the Signal Structure VI as described.
2. Open the ATM Signal Structure VI.
3. In the “Edit” menu select the item “ATM Structure...”.
– or –
Click on the corresponding button in the toolbar.
This activates the “ATM Structure” window.
4. In the “ATM SDU” field press the button “AAL0” and confirm with “OK”.
5. Start the measurement by pressing function key F5.
– or –
Click the “green traffic signal” icon in the Application Manager.
Analysis
Using the Anomaly and Defect Analyzer VI, you can observe whether errors are occurring or
not. In the example below, HUNC (Header error UNCorrectable) errors occur.
Example 2
Insertion of a HCOR at a repetition rate of 1E-6 with analysis of the DUT reaction.
Settings
Do not change the settings of the VIs Signal Structure and ATM Signal Structure. The VI
Anomaly and Defect Insertion must be reset.
Analysis
You can observe the effect of the inserted error in the window of the Anomaly and Defect
Analyzer VI. There is a choice of four different windows to display the result.
If the above configuration is used, the more port modules that are included the loop, the greater
the delay. Measurements are made on ATM switches to determine whether there is a constant
increase in delay as the number of looped-in port modules are increased.
1. Set up an unidirectional connection with a constant bit rate through the switch for the reason
that you can set up a physical loop at the second port.
2. Check that the switch accepts the PCR of 14.98 Mbit/s (35523 cells per second).
3. Set the CBR contract, say, to a PCR of 15 Mbit/s.
VIs required
• Signal Structure
• ATM Signal Structure
• ATM Traffic Analyzer
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-107).
22.4 Measurement
Settings
Signal Structure VI
⇒ First of all, set the Signal Structure VI as described.
Fig. A-108 “ATM Channel” dialog box of the “ATM Signal Structure” VI
6. In the “Channel” dialog box, enter your VPI/VCI parameters for the transmitter and receiver
and confirm with “OK”.
7. Transfer the send-side (Tx) settings in the “ATM Signal Structure” window to the receive side
(Rx), by clicking the “Tx=>Rx” button.
8. Using the slider, set a load of 10% or 14.98 MBit/s in the displayed signal structure.
9. Confirm your entries with “OK”.
The selected ATM signal structure is now activated.
10.Click on the “ON” button on the toolbar.
– The test channel is now connected and test cells are being sent.
– In the off-state, the transmitter outputs empty cells only.
3. Set the measurement interval in the “Cell Transfer Delay Setup” dialog box.
4. Activate “Cell Transfer Delay...” in the “Settings” menu.
– or –
Click on the “SET” icon button.
.
Application Manager VI
⇒ Start the measurement:
Press function key F5.
– or –
Click the “green traffic signal” button in the Application Manager.
Analysis
The results are displayed in the form of a histogram on the “ATM Traffic Analyzer” VI. There is
a bar for each class that contains at least one cell.
Cursor read-off
⇒ Click the “CSR” icon on the toolbar.
The window shown below opens and displays the numerical value indicated by the cursor.
Fig. A-111 “Cell Transfer Delay Cursor Position” display window on the ATM Traffic Analyzer
The cell delay variation (CDV) can be determined in the “Cell Transfer Delay” display mode. The
peak-to-peak CDV can be derived from the histogram. The peak-to-peak CDV corresponds to
the 2-point cell delay variation to ITU-T I.356. The following results are provided by the CDV
evaluation mode:
• the minimum cell delay
• the maximum cell delay
• the mean cell delay
• the 2-point cell delay variation (2-point CDV)
Peak-to-peak-CDV
Fig. A-112 “Cell Delay Results” display window on the ATM Traffic Analyzer and
definition of the peak-to-peak CDV
Fig. A-113 Setup for the ATM latency test (ATM switch) with background load
This test is performed to determine the extent to which the cell transit time through an ATM
switch goes up when the switch loading is increased by connection requests. The result from
the “ATM Latency Test for ATM switch” measurement is used as the reference. To perform this
measurement, you must first set up the switch configuration as shown above.
1. As shown above, set up two bidirectional connections with a constant bit rate via four port
modules in the ATM switch.
2. Check that the switch accepts the PCR of 149.76 Mbit/s (353209 cells per second), e.g. CBR
contract: PCR = 15 Mbit/s.
VIs required
• Signal Structure
• ATM Signal Structure
• ATM Traffic Analyzer
• ATM Background Generator
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-114).
23.4 Measurement
Example
Load test on an ATM switch
Settings
Fig. A-115 “Sequence Editor” dialog box in the “ATM Background Generator” window
Analysis
⇒ Activate the window of the “ATM Traffic Analyzer” VI.
The measurement results are analyzed in the same way as the results of the previous reference
measurement (ATM latency test for ATM switches).
Select the item “Export...” in the “Print” menu to store the measurement results in CSV format
for further processing with EXCEL.
The purpose of this test is to demonstrate that the alarm and error sensors in an ATM switch are
operating properly (to ITU-T or ATM Forum). If there is an LCD alarm, the system has lost cell
stream synchronization. The synchronization and the monitoring of the cell stream is performed
by a state automat which is specified in ITU-T Recommendation I.432.
When a simple LCD alarm is inserted, the ANT-20 sends 7 consecutive cells with header errors.
In this case, the ATM switch should output an LCD alarm for the port. The insertion time can be
limited to 6 cells with header errors. In this case, the switch should synchronize.
1. Set up a unidirectional, permanent connection with constant bit rate through the switch.
2. Check that the PCR (Peak Cell Rate) is 10% of the channel capacity (in cells per second).
VIs required
• Signal Stucture
• ATM Signal Structure
• Anomaly and Defect Insertion
• Anomaly and Defect Analyzer
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-118).
24.4 Measurement
Settings
Fig. A-119 “ATM Structure” dialog box in the “ATM Signal Structure” window
The Cell Loss Ratio (CLR) is a quality of service parameter. The CLR is the ratio of the number
of lost cells to the total cells sent.
1. Set up a unidirectional, permanent connection with a variable bit rate through the switch.
2. Configure the VBR contract for the connection.
VIs required
• Signal Structure
• ATM Signal Structure
• ATM Traffic Analyzer
• Anomaly and Defect Analyzer
⇒ Add the VIs required to the list of VIs used in the Application Manager.
The Application Manager should include at least the following instruments (see Fig. A-123).
25.4 Measurement
Settings
1. Open the “ATM Signal Structure” window.
2. In the “Edit” menu, select the item “ATM Structure...”.
– or –
Click on the corresponding button in the toolbar.
This activates the “ATM Structure” window.
3. In the “ATM SDU” field, click the “Testcell” button.
4. In the “Performance Measurement” field, click on “Error-Related Performance”.
5. Transfer the send-side settings to the receive side by clicking the “Tx => Rx” button.
6. Confirm your entries with “OK”.
7. In the “Traffic” menu, select the item “VBR”.
8. In the “Traffic” menu, select the item “Set VBR...”.
The “VBR” dialog box opens.
Contract parameters:
PCR Peak Cell Rate
SCR Sustainable Cell Rate
MBS Maximum Burst Size
Fig. A-124 “VBR” dialog box in the “ATM Signal Structure” window
Analysis
1. Open the “Anomaly and Defect Analyzer” window.
2. In the “View” menu, select the item “Table”.
– or –
Click the appropriate icon on the toolbar.
The measurement results are displayed as a table.
If there are cell losses, you will find the precise CLR in this table.
Notes:
6
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Standards/Abbreviations
1 Recommendations/Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-1
1.1 ITU-T recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-1
1.2 ANSI standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-4
1.3 Bellcore standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-4
1.4 ETSI standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-5
1.5 ATM Forum recommendations . . . . . . . . . . . . . . . . . . . . . .SA-6
3 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA-12
i
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
ii
ANT-20/ANT-20E Mainframe, SONET Version
Standards/Abbreviations
1 Recommendations/Standards
Recommendations Title
G.704 Synchronous frame structures used at primary and secondary hierarchical levels
G.706 Frame alignment and cyclic redundancy check (CRC) procedures relating to
basic frame structures defined in recommendation G.704
G.707 Network node interface for the synchronous digital hierarchy (SDH)
(replaces G.707, G.708 and G.709 version of 03/93)
G.742 Second order digital multiplex equipment operating at 8448 kbit/s and using
positive justification
G.751 Digital multiplex equipments operating at third order bit rate of 34368 kbit/s and
fourth order bit rate of 139264 bit/s and using positive justification
G.755 Digital multiplex equipment operating at 139264 kbit/s and multiplexing three
tributaries at 44736 kbit/s
G.774.02 SDH configuration of the payload structure for the network element view
G.774.03 SDH management of multiplex section protection for the network element view
G.774.04 SDH management of sub network connection protection from the network
element view
G.774.05 SDH management of the connection supervision functionality (HCS/LCS) for the
network element view
G.774.06 SDH unidirectional performance monitoring for the network element view
G.775 Loss of signal (LOS) and alarm indication signal (AIS) detection and clearance
criteria
Standards/Abbreviations SA-1
Mainframe, SONET Version ANT-20/ANT-20E
Recommendations Title
G.811 Timing requirements at the output of primary reference clocks suitable for
plesiochronous operation of international digital links
G.812 Timing requirements at the output of slave clocks suitable for plesiochronous
operation of international digital links
G.823 The control of jitter and wander within digital networks which are based on the
2048 kbit/s hierarchy
G.824 The control of jitter and wander within digital networks which are based on the
1544 kbit/s hierarchy
G.825 The control of jitter and wander in digital networks based on the SDH
G.826 Error performance parameters and objectives for international, constant bit rate
digital paths at or above the primary rate
G.828 Error performance parameters and objectives for international, constant bit rate
synchronous digital paths
G.829 Error performance events for SDH multiplex and regenerator section
G.911 Parameters and calculation methodologies for reliability of fibre optic systems
G.957 Optical interfaces for equipments and systems relating to the synchronous digital
hierarchy
G.958 Digital line systems based on the synchronous digital hierarchy for use on optical
fibre cables
SA-2 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Recommendations Title
M.2100 Performance limit for bringing into service and maintenance of international PDH
paths, sections and transmission systems
M.2101 Performance limit for bringing into service and maintenance of international SDH
paths and multiplex sections
M.2110 Bringing into service international digital paths, sections and transmission
systems
M.2120 Digital path, section and transmission fault detection and localization
O.151 Error performance measuring equipment operating at the primary rate and above
O.171 Timing jitter and wander measuring equipment for digital systems which are
based on the PDH
O.172 Jitter and Wander measuring equipment for digital systems which are based on
the SDH
Q.2110 B-ISDN ATM Adaptation Layer - Service Specific Connection Oriented Protocol
(SSCOP)
Q.2931 B-ISDN - Digital Subscriber Signalling No. 2 (DSS 2) - User Network Interface
Layer 3 Specification for Basic Call / Connection Control
Q.2961 B-ISDN - Digital Subscriber Signalling System No. 2 (DSS 2) - Additional Traffic
Parameters
X.21 Interface between data terminal equipment (DTE) and data circuit-terminating
equipment (DCE) for synchronous operation on public networks
Standards/Abbreviations SA-3
Mainframe, SONET Version ANT-20/ANT-20E
Standard Title
T1.105-1995 SONET - basic description including multiplex structure, rates and formats
T1.204-1993 OAM&P - lower layer protocol for interfaces between operation systems and
network elements
T1.208-1993 OAM&P - upper layer protocol for interfaces between operation systems and
network elements
T1.210-1993 OAM&P - principles of functions, architectures and protocols for TMN interfaces
Standard Title
SA-4 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Standard Title
ETS 300 147 R3 Synchronous digital hierarchy (SDH); Multiplexing structure (based on ITU-T
Recommendation G.707)
ETS 300 166 Physical and electrical characteristics of hierarchical digital interfaces for
equipment using the 2048 kbit/s-based plesiochronous or synchronous digital
hierarchies (based on ITU-T Recommendation G.703)
ETS 300 167 Functional characteristics of 2 048 Mbit/s interfaces (based on ITU-T
Recommendations G.704 and G.706)
ETS 300 417-1-1 Generic requirements of transport functionality of equipment - Part 1-1: Generic
processes and performances
ETS 300 417-2-1 Generic requirements of transport functionality of equipment - Part 2-1: SDH and
PDH physical section layer functions
ETS 300 417-3-1 Generic requirements of transport functionality of equipment - Part 3-1: STM-N
regenerator and multiplex section layer functions
ETS 300 417-4-1 Generic requirements of transport functionality of equipment - Part 4-1: SDH path
layer functions
ETS 300 417-5-1 Generic requirements of transport functionality of equipment - Part 5-1: PDH path
layer functions
ETS 300 417-6-1 Generic requirements of transport functionality of equipment - Part 6-1:
Synchronization layer functions
ETS 300 462-1 Generic requirements for synchronization networks - Part 1: Definitions and
terminology for synchronization networks
ETS 300 462-2 Generic requirement for synchronization networks - Part 2: Synchronization
network architecture
ETS 300 462-3 Generic requirement for synchronization networks - Part 3: The control of jitter and
wander within synchronization networks
ETS 300 462-4 Generic requirements for synchronization networks; Part 4: Timing characteristics
of slave clocks suitable for synchronization supply to SDH and PDH equipment
ETS 300 462-5 Generic requirements for synchronization networks; Part 5: Timing characteristics
of slave clocks suitable for operation in synchronous Digital Hierarchy (SDH)
equipment
ETS 300 462-6 Generic requirements for synchronization networks; Part 6: Timing characteristics
of primary reference clocks
Standards/Abbreviations SA-5
Mainframe, SONET Version ANT-20/ANT-20E
Data Exchange Data Exchange Interface version 1.0 af-dxi-0014.000 Aug, 1993
Interface
LAN Emulation LAN Emulation over ATM 1.0 af-lane-0021.000 Jan, 1995
SA-6 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Physical Layer ATM Physical Medium Dependent Interface af-phy-0015.000 Sep, 1994
Specification for 155 Mb/s over Twisted Pair
Cable
155 Mbps over MMF Short Wave Length af-phy-0062.000 July, 1996
Lasers, Addendum to UNI 3.1
PICS Proforma for the DS3 Physical Layer af-test-0023.000 Sep, 1994
Interface
Standards/Abbreviations SA-7
Mainframe, SONET Version ANT-20/ANT-20E
Testing PICS Proforma for the 100 Mbps Multimode af-test-0025.000 Sep, 1994
Fibre Physical Layer Interface
PICS Proforma for the ATM Layer (UNI 3.0) af-test-0028.000 Apr, 1995
Interoperability Test Suite for the ATM Layer af-test-0035.000 Apr, 1995
(UNI 3.0)
PICS Proforma for the DS1 Physical Layer af-test-0037.000 Apr, 1995
PICS Proforma for the 51.84 Mbps Mid- af-test-0044.000 Jan, 1996
Range PHY Layer Interface
PICS for the 25.6 Mbps over Twisted Pair af-test-0051.000 Mar, 1996
Cable (UTP-3) Physical Layer
Conformance Abstract Test Suite for the UNI af-test-0060.000 June, 1996
3.1 ATM Layer of End Systems
PICS for the 155 Mbps over Twisted Pair af-test-0070.000 Nov, 1996
Cable (UTP-5/STP-5) Physical Layer
Recommendation Title
SA-8 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
2 Alarm messages
2.1 SDH/SONET
AU-PJE - AU Pointer -
Justification Event
HO Path -
Standards/Abbreviations SA-9
Mainframe, SONET Version ANT-20/ANT-20E
LO Path -
SA-10 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Standards/Abbreviations SA-11
Mainframe, SONET Version ANT-20/ANT-20E
3 Abbreviations
Abbreviation Meaning
AGE Aging
AU Administrative Unit
SA-12 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Abbreviation Meaning
BT Burst Tolerance
BW Bandwidth
C1 STM-N Identifier
Signal Label
CI Concatenation Indication
Congestion Indicator
CK Clock
Standards/Abbreviations SA-13
Mainframe, SONET Version ANT-20/ANT-20E
Abbreviation Meaning
DC Dropped Cells
SA-14 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Abbreviation Meaning
EF Equipment Failure
f Frequency
FE Frame Error
Standards/Abbreviations SA-15
Mainframe, SONET Version ANT-20/ANT-20E
Abbreviation Meaning
INC Increment
SA-16 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Abbreviation Meaning
MS Multiplexer Section
MUX Multiplexer
Standards/Abbreviations SA-17
Mainframe, SONET Version ANT-20/ANT-20E
Abbreviation Meaning
NE Network Element
NU National Use
OH Overhead
PT Payload Type
SA-18 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Abbreviation Meaning
PTR Pointer
RS Regenerator Section
RX Receiver
SEL Selector
Standards/Abbreviations SA-19
Mainframe, SONET Version ANT-20/ANT-20E
Abbreviation Meaning
SIG Signaling
TC Tandem Connection
TC-UNEQ TC unequipped
TI Trace Identifier
TS Timeslot
TU Tributary Unit
TX Transmitter
SA-20 Standards/Abbreviations
ANT-20/ANT-20E Mainframe, SONET Version
Abbreviation Meaning
UNEQ Unequipped
UNEQ-V Unequipped - VT
UI Unit Interval
VI Virtual Instrument
VP Virtual Path
VT Virtual Tributary
Standards/Abbreviations SA-21
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
SA-22 Standards/Abbreviations
Technical Background
7
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Technical Background
i
Mainframe, SONET Version ANT-20/ANT-20E
ii
ANT-20/ANT-20E Mainframe, SONET Version
Technical Background
1 Multiplexing structures
T4
T4
T1 T1
n pointer
T2
✓ Condition: T4 = n x T2
T4
T3 T2
✓ Condition: T4 = n x T2
T5 T4
T2
T4
T5 T5
n pointer
T2
T4
87 pointer actions
T2 3 x no pointer action
T4
43 pointer actions 44 pointer action
T2 T3 3 x no pointer action
T4
86 pointer actions
T2 4 x no pointer action
n: 1 to 2000
3 Performance Analysis
VI: Performance Analysis (Physical layer instrument)
Definitions from GR-253 and T1.231 are used for this performance analysis.
EFS Error Free Sum of all error free seconds since the start of the measurement.
Seconds
SES Severely Errored Severely errored seconds (see Sec. 3.1.3, Page TB-7).
Seconds
SEFS Severely Errored Seconds containing OOF (LOF, LOS) in the Section Analysis.
Frame Seconds
These rules apply: The percentages quoted for ES, SES, SEFS and EFS refer to the available
time,
i.e. the measurement time less UAS.
The percentage quoted for UAS refers to the total measurement time:
ES (including SES, SEFS) + EFS = 100% (available time)
ES (including SES, SEFS) + EFS + UAS = total measurement time.
“Far End” evaluation is interrupted if certain alarms occur, e.g. LOS, LOF or
AIS. These alarm times are removed from the reference value for
calculating the ratio at the “Far end”.
Menu Explanation
• Hierarchy Select measurement point and hence the events used to perform the evaluation
(see Sec. 3.1.3).
The menu “Hierarchy” can be used for selecting the following Measurement points:
Section Layer PM
OC1 52
OC3 155
OC12 616
OC48 2392
OC192 9568
UAS SES ≥ 10 -
EFS no ES or UAS -
OC1 51
OC3 154
OC12 615
OC48 2459
OC192 9836
UAS SES ≥ 10 -
EFS no ES or UAS -
ES REI-L ≥1 or RDI-L -
OC1 51
OC3 154
OC12 615
OC48 2459
OC192 9836
UAS SES ≥ 10 -
EFS no ES or UAS -
ES B3 ≥1 or AIS-P or LOP-P -
STS1 2400
STS3c 2400
STS12c 2400
STS48c 2400
UAS SES ≥ 10 -
EFS no ES or UAS -
ES REI-P ≥1 or RDI-P -
STS1 2400
STS3c 2400
STS12c 2400
STS48c 2400
UAS SES ≥ 10 -
EFS no ES or UAS -
VTx 600
UAS SES ≥ 10 -
EFS no ES or UAS -
ES REI-V ≥1 or RDI-V -
VTx 600
UAS SES ≥ 10 -
EFS no ES or UAS -
3.1.3.5 BPV
ES BPV ≥1 or LOS -
UAS SES ≥ 10 -
EFS no ES or UAS -
UAS SES ≥ 10 -
EFS no ES or UAS -
1 EC stands for FE, PBit, FEBE or CBit
UAS SES ≥ 10 -
EFS no ES or UAS -
3.1.3.8 TSE
ES TSE ≥1 or LSS -
UAS SES ≥ 10 -
EFS no ES or UAS -
Result Explanation
EFS Error Free Seconds Determined as error count and error rate.
VERDICT Accepted/Rejected;
Overall assessment of path: accepted/rejected.
The ES and SES error ratios are compared with the appropriate
target values.
• Hierarchy Select measurement point and hence the events used to perform the evaluation.
The ANT-20/ANT-20E can perform “In Service” (ISM) and “Out of Service” (OOS) G.826
evaluation.
Result Explanation
BBE Background Block Errored blocks not in SES as a count and as an error rate.
Errors
EFS Error Free Seconds Error-free seconds as a count and as an error rate
SES Severely Errored Severely errored seconds as a count and as an error rate
Seconds
PATH UAS For “Far End” measurements, the “Unavailable Seconds” (UAS)
are determined for the complete path (Path UAS). They are
determined from the “Near End” and “Far End” results using a
logical OR function.
Example
A set of results for the “Near End” and for the “Far End” is determined in each case.
The PATH ALLOCATION is also displayed.
The “Unavailable Seconds” (UAS) for the entire path (Path UAS) are also determined in “Far
End” measurements. The “Path UAS” result is determined by logically ORing the “Near End”
and “Far End” UAS results.
The message “Attention: Check TIM/PLM Defect Evaluation please!” may be displayed. This
message indicates that you should check to see if evaluation of both these alarms has been
activated. These defects should normally be considered in a G.826 evaluation. Evaluation is
enabled or disabled in the “Overhead Analyzer”.
If “G.826 ISM” or “G.826 OOS” evaluation is selected, the following parameters are used:
• Hierarchy Select measurement point and hence the events used to perform the evaluation
(see Tab. TB-18). For G.826 OOS not available.
UAS-Limit Switch and threshold value for taking UAS into account in the path
status (VERDICT)
Off: UAS do not affect the path status.
On: If the UAS threshold is exceeded, the path status is assessed as
“Rejected”.
Setting range: 0 to 100000
Step width: 1
Default: 0
UAS-Mode Switch for separate or common rating of UAS for “Near” and
“Far End”.
Individual: Separate rating of UAS for “Near” and “Far End”.
Global: Common rating of UAS for “Near” and “Far End”.
The total path is “unavailable” as soon as one side is“unavailable”.
Default: Individual.
1 “Allocation” indicates what percentage of the “End to End” target values for ESR (Errored Seconds Ratio), SESR
(Severely Errored Seconds Ratio) and BBER (Background Block Error Ratio) must be met for the measured path
to be considered acceptable. The “End to End” target values are based on a hypothetical path of length 27 500 km.
The target values for various system bit rates are specified in Recommendation G.826.
2 This threshold indicates the number of EB (Errored Blocks) required before a one-second period is evaluated as
SES (Severely Errored Second).
• The measurement point where the G.826 ISM evaluation is made, is selected in the
“Hierarchy” menu. In the case of G.826 OOS, there is no “Hierarchy” menu, and evaluation
is always made on bit errors (TSE).
• “Near End” and “Far End” evaluations are simultaneous as soon as the set signal structure
allows the “Far End” measurement to be made.
The “Far End” evaluation requires the presence of REI or EBIT.
FAS140 21 µs 12
FAS34 44.7 µs 10
FAS8 100.4 µs 10
PDH2FAS 250 µs 7
PDH2CRC 1 ms 2048
DS1/ESF FAS 3 ms 24
Table TB-19 G.826 ISM/G.828/M.2101 (RSOH, MSOH, HP, LP), blocklength (continued)
Nx64 1 ms N x 64
Overhead Bytes 1 ms N x 64
RSOH: E1, F1, D1 to D3
MSOH: D4 to D12, E2
POH: F2, F2L
2M unframed 1 ms 2048
G.828 evaluation conforms to ITU-T Recommendation dated 3/2000. The G.828 standard is a
further development of Recommendation G.826 for synchronous digital paths.
Recommendation G.828 specifies additional measurement values and measurement points:
• SEP (Severely Errored Period, declared as optional)
• Performance measurement on TCM bytes (in preparation for ANT-20)
G.828 evaluation can be performed on the following events:
• B1
• B2SUM
• MS-REI
• B3
• HP-REI
• LP-BIP 2/8
• LP-REI
• Bit errors (TSE) blocks per s
Result Explanation
EFS Error Free Seconds Error-free seconds as a count and as an error rate
SES Severely Errored Severely errored seconds as a count and as an error rate
Seconds
VERDICT - Accepted/Uncertain/Rejected:
Overall assessment of the path quality
• Hierarchy Select measurement point and hence the events used to perform the evaluation.
UAS-Limit Switches and threshold for taking UAS into account in the path
status (VERDICT):
Off: UAS have no influence on path status.
On: If UAS limit exceeded, path status is rated as “Rejected”
Setting range: 0 to 100000
Step width: 1
Default: 0
UAS-Mode Switch for separate or common rating of UAS for “Near” and
“Far End”.
Individual: Separate rating of UAS for “Near” and “Far End”.
Global: Common rating of UAS for “Near” and “Far End”.
The total path is “unavailable” as soon as one side is“unavailable”.
Default: Individual.
G.829 evaluation conforms to ITU-T Recommendation dated 3/2000. The G.829 standard
describes the recording and classification of error performance events for SDH multiplex and
regenerator-sections. The Recommendation does not discuss allocations and does not specify
objectives to be met. An assessment verdict is therefore not possible. The measured values are
determined on a block basis in the sense that the individual bits of an EDC (Error Detection
Code) each monitor separate blocks. This is in contrast with the G.826 and G.828 evaluations,
where the entire EDC only monitors a single block in each case.
G.829 evaluation can be performed on the following events:
• B1
• B2SUM
• MS-REI
• Bit errors (TSE)
Result Explanation
EFS Error Free Seconds Error-free seconds as a count and as an error rate
SES Severely Errored Seconds Severely errored seconds as a count and as an error rate
BBE Background Block Error Number and ratio of background block errors
Bit rate Block length Blocks per frame Blocks per second Error detection code
• Hierarchy Select measurement point and hence the events used to perform the evaluation.
Result Explanation
EFS Error Free Seconds Error-free seconds as a count and as an error rate
SES Severely Errored Severely errored seconds as a count and as an error rate
Seconds
VERDICT - Accepted/Uncertain/Rejected:
Overall assessment of the path quality
• Hierarchy Select measurement point and hence the events used to perform the evaluation.
UAS-Limit Switches and threshold for taking UAS into account in the path
status (VERDICT):
Off: UAS have no influence on path status.
On: If UAS limit exceeded, path status is rated as “Rejected”
Setting range: 0 to 100000
Step width: 1
Default: 0
UAS-Mode Switch for separate or common rating of UAS for “Near” and
“Far End”.
Individual: Separate rating of UAS for “Near” and “Far End”.
Global: Common rating of UAS for “Near” and “Far End”.
The total path is “unavailable” as soon as one side is“unavailable”.
Default: Individual.
1 CRC4 word error and EBIT error are computed parallel.
2 “Allocation” indicates how many percent of the end-to-end target specs are to be met for the path under test to be
acceptable (see Tab. TB-28).
3 The BISO value is internally computed for ES and SES (see Sec. 3.6.2.2).
4 Bringing into Service (Performance) Objectives.
The BISO value is internally computed for ES and SES. It is defined as follows:
BISO ES[SES] = (Allocation x EERPO ES[SES] x Test Period x BISO Multiplier) / 2
From BISO, the thresholds S1 and S2 are computed for ES and SES:
S1 Limit ES[SES] = BISO ES[SES] - 2 x sqrt(BISO ES[SES])
S2 Limit ES[SES] = BISO ES[SES] + 2 x sqrt(BISO ES[SES])
For meas. times ≤ 15 minutes: BISO = S1 = S2 = 0
For meas. tiemes ≥ 7 days: BISO = S1 = S2
The computed values for BISO, S1 and S2 for ES and SES are displayed below the result page.
For determining the path status, the measurement results are compared with the thresholds S1
and S2 as follows:
Meas. value UAS may also be taken into account, cf. switch UAS-limit (see Tab. TB-27).
M.2101 evaluation takes the issue of Recommendation M.2101 dated 6/2000 as well as the
version M.2101.1 of April 1997 into account. You can switch between the two versions via a list
box in the “Settings” menu. The main differences between the Recommendation M.2101
(4/1997) and the Recommendation M.2101 (6/2000) concern additional measurement values
as well as differences in the error performance objectives:
• BBE (Background Block Error)
• SEP (Severely Errored Period)
• Performance measurement on TCM bytes (in preparation for ANT-20)
SEP evaluation is optional in the new Recommendation M.2101 (6/2000). The “Settings” menu
therefore includes a separate switch for including or excluding SEP from the assessment
verdict.
M.2101 evaluation can be performed on the following events:
• B1
• B2SUM
• MS-REI
• B3
• HP-REI
• LP-BIP 2/8
• LP-REI
• Bit errors (TSE)
Result Explanation
EFS Error Free Seconds Error-free seconds as a count and as an error rate
SES Severely Errored Severely errored seconds as a count and as an error rate
Seconds
VERDICT - Accepted/Uncertain/Rejected:
Overall assessment of the path quality
Result Explanation
• Hierarchy Select measurement point and hence the events used to perform the evaluation.
UAS-Limit Switches and threshold for taking UAS into account in the path
status (VERDICT):
Off: UAS have no influence on path status.
On: If UAS limit exceeded, path status is rated as “Rejected”
Setting range: 0 to 100000
Step width: 1
Default: 0
UAS-Mode4 Switch for separate or common rating of UAS for “Near” and
“Far End”.
Individual: Separate rating of UAS for “Near” and “Far End”.
Global: Common rating of UAS for “Near” and “Far End”.
The total path is “unavailable” as soon as one side is“unavailable”.
Default: Individual.
M.2101-Version This list box allows you to select between evaluation according to
M.2101.1 (4/1977) or M.2101 (6/2000).
The two Recommendations differ in the specified performance ob-
jective values. The newer Recommendation also includes evalua-
tion of BBE and SEP.
Default: 6/2000
The End to End Performance Objectives (EEPOs) are listed in table 3 of the M.2101.1
recommendation of 04/1997:
≤ 5 Mbit/s 2% 0.1%
Table TB-31 End to End Performance Objectives (EEPOs) from the recommendation M.2101.1 (4/1997)
The End to End Performance Objectives (EEPOs) are listed in the following tables of the
Recommendation M.2101 (06/2000):
:
The following values are used for measurement points that are not defined in the
recommendation:
Table TB-32 End-to-end performance objectives (EEPO) that are not defined in the recommendation
The BISO value is internally computed for ES, SES, BBE and SEP. The threshold values S1
and S2 are also determined from BISO. The values calculated for BISO, S1 and S2 are
displayed on the results page.
The BISO value is computed as follows:
Table TB-33 “BISO” formulae for the path section (B3, LPBIP 2/8) and regenerator section (B1)
The measurement results are compared with the threshold values S1 and S2 as follows when
determining the section status (Verdict).
Measured value of ES [SES, BBE, SEP] > S2 or EFS = 0: Path status = rejected
Measured value of ES [SES, BBE, SEP] between S1 and S2: Path status = uncertain
Measured value of ES [SES, BBE, SEP] ≤ S1: Path status = accepted
Meas. value UAS may also be taken into account, cf. switch UAS-limit (see Tab. TB-30).
The BISO value is internally computed for ES, SES, BBE and SEP. The threshold values S1
and S2 are also determined from BISO. The values calculated for BISO, S1 and S2 are
displayed on the results page.
The BISO value is computed as follows:
VC-1/VC-2
BISO BBE = (Allocation x EEPO BBE x Test Period x 2000 x BISO Multiplier)/2
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
VC-3/VC-4/VC-4-XC
BISO BBE = (Allocation x EEPO BBE x Test Period x 8000 x BISO Multiplier)/2
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
Table TB-36 “BISO” formulae for the path section (B3, LPBIP 2/8) and regenerator section (B1)
STM-0
BISO BBE = (Allocation x EEPO BBE x Test Period x 64000 x BISO Multiplier)/10
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
STM-1
BISO BBE = (Allocation x EEPO BBE x Test Period x 192000 x BISO Multiplier)/10
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
STM-4
BISO BBE = (Allocation x EEPO BBE x Test Period x 768000 x BISO Multiplier)/10
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
STM-16
BISO BBE = (Allocation x EEPO BBE x Test Period x 3072000 x BISO Multiplier)/10
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
STM-64
BISO BBE = (Allocation x EEPO BBE x Test Period x 12288000 x BISO Multiplier)/10
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
BISO BBE = (Allocation x EEPO BBE x Test Period x no. of blocks per sec.1x BISO Multiplier)/2
S1 Limit BBE = BISO BBE - 2 x sqrt(BISO BBE)
S2 Limit BBE = BISO BBE + 2 x sqrt(BISO BBE)
The measurement results are compared with the threshold values S1 and S2 as follows when
determining the section status (Verdict).
Measured value of ES [SES, BBE, SEP] > S2 or EFS = 0: Path status = rejected
Measured value of ES [SES, BBE, SEP] between S1 and S2: Path status = uncertain
Measured value of ES [SES, BBE, SEP] ≤ S1: Path status = accepted
Meas. value UAS may also be taken into account, cf. switch UAS-limit (see Tab. TB-30).
8
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Maintenance
2 Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .M-1
i
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
ii
ANT-20/ANT-20E Mainframe, SONET Version
Maintenance
2 Tools
The following tools are included with your instrument. These tools are required for maintenance
operations, e.g. opening the instrument in order to replace the air filter.
• Hexagon key wrench (Allen key)
for the hex socket head screws holding the housing together.
• Fitting wrench
for the Versacon 9 system connector inserts.
Maintenance M-1
Mainframe, SONET Version ANT-20/ANT-20E
Versacon® 9 insert
M-2 Maintenance
ANT-20/ANT-20E Mainframe, SONET Version
Maintenance M-3
Mainframe, SONET Version ANT-20/ANT-20E
5.1 ANT-20
M-4 Maintenance
ANT-20/ANT-20E Mainframe, SONET Version
Filter pad
Maintenance M-5
Mainframe, SONET Version ANT-20/ANT-20E
5.2 ANT-20E
M-6 Maintenance
ANT-20/ANT-20E Mainframe, SONET Version
Maintenance M-7
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
M-8 Maintenance
Remote Operation
9
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Remote operation
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RO-1
i
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
ii
ANT-20/ANT-20E Mainframe, SONET Version
Remote operation
With options BN 3035/95.30 and BN 3035/95.31 only.
1 Introduction
The remote operation options allow you to access a distant ANT-20 (or DominoCOM ANT-20)
from any Windows PC over a dial-up link via modems or over an Ethernet LAN.
Here are just some of the things you can do:
Remote control
Once connected to the distant ANT-20, you can use you mouse and keyboard to operate the
ANT-20 just as if you where sitting in front of it.
File transfer
Move or copy files quickly and reliably between ANT-20 and PC.
Remote printing
Redirect print jobs, e.g. from the distant ANT-20 to your local printer.
All this is accomplished with the remote access software called ReachOut from Stac Electronics
Inc.
In terms of ReachOut, the controlling PC is the Viewer and the distant ANT-20 is the Host.
For detailed information refer to the ReachOut user’s guide.
2.1 Overview
The Remote Operation Option 3035/95.30 includes the software required to operate a distant
ANT-20 (or DominoCOM ANT-20) from a Windows PC over a dial-up link via modems or over
a direct connection via a null modem cable. The direct connection may be used for testing
purposes or for operating a DominoCOM ANT-20 from a PC over short distances.
A null modem cable (3 meters long) with both 9-way and 25-way SUB-D female connectors on
each end is included.
The remote access software used, ReachOut (from Stac Electronics Inc.), handles hundreds of
different modem types, including ISDN modems and cellular modems. You can even define a
new modem if yours isn’t listed. For detailed information refer to the ReachOut user’s guide.
The modems should be purchased in the country where they are to be operated, to conform to
national regulations.
For ANT-20 with Windows 3.11 only:
• PCMCIA card modems require a standardized PCMCIA system software with Card and
Socket Services. CardWare (from Award Software Inc.) is included as PCMCIA system
software for the ANT-20. For detailed information refer to the CardWare user’s manual.
• The CardWare software contained on the ANT-20 PCMCIA System disk is already
configured for use with the ANT-20.
2.3 Installation
To install and configure the software on a DominoCOM ANT-20 in the same way as on an
ANT-20, connect an external monitor, keyboard and mouse to the built in PC-AT.
If you ordered the Remote Operation Option 3035/95.30 together with your ANT-20, the
CardWare and ReachOut software packages are already installed on the ANT-20 (in the
directories C:\CARDWARE and C:\REACHOUT) and the ReachOut program icon is shown in
the Windows “Program Manager”. The ReachOut security options are pre-configured as
follows:
The ReachOut “Password List” contains an entry with the “User Name” ANT-20 and the
accompanying password ANT-20. The option “Passwords Required” is set to “No”.
For detailed information about configuration options refer to the ReachOut user’s guide.
If you ordered the Remote Operation Option 3035/95.30 separately, install the software
packages as follows:
To install and configure the software on a DominoCOM ANT-20 in the same way as on an
ANT-20, connect an external monitor, keyboard and mouse to the built in PC-AT.
If you ordered the Remote Operation Option BN 3035/95.30 together with your ANT-20, the
ReachOut software is already installed on the ANT-20 (in the directory C:\REACHOUT) and the
ReachOut program icon is shown in the Windows95 file folder “Programs”.
The ReachOut security options are pre-configured as follows:
The ReachOut “Password List” contains an entry with the “User Name“ ANT-20 and the
accompanying password ANT-20. The option “Passwords Required” is set to “No”.
For detailed information about configuration options refer to the ReachOut user‘s guide.
If you ordered the Remote Operation Option 3035/95.30 separately, install the ReachOut
software as follows:
3.1 Overview
The Remote Operation Option 3035/95.31 includes the software required to operate a distant
ANT-20 (or DominoCOM ANT-20) from a Windows PC over an Ethernet LAN using the Internet
protocol TCP/IP.
The PCMCIA Ethernet card required (with 10Base2 and 10BaseT connectors) for the ANT-20 is
also included.
The remote access software used is ReachOut (from Stac Electronics Inc.). For detailed
information refer to the ReachOut user’s guide.
For ANT-20 with Windows 3.11 only:
• PCMCIA cards require a standardized PCMCIA system software with Card and Socket
Services. CardWare (from Award Software Inc.) is included as PCMCIA system software for
the ANT-20. For detailed information refer to the CardWare user’s manual.
• The CardWare software contained on the ANT-20 PCMCIA System disk is already
configured for use with the ANT-20.
• TCP/IP implementation for the ANT-20 is by means of MS TCP/IP-32 stack (from Microsoft).
3.3 Installation
Insert the SCM Ethernet LAN card into a free PCMCIA socket just like you insert a disk into a
floppy drive.
You do not need to power down the ANT-20 when you insert or remove the card.
Connect the SCM Ethernet LAN card to your LAN using the Media Coupler cable included.
To install and configure the software on a DominoCOM ANT-20 in the same way as on an
ANT-20, connect an external monitor, keyboard and mouse to the built-in PC-AT.
If you ordered the Remote Operation Option 3035/95.31 together with your ANT-20, the
CardWare, MS TCP/IP-32 and ReachOut software packages are already installed on the
ANT20 (CardWare in the directory C:\CARDWARE, MS TCP/IP-32 in the directory
C:\WINDOWS and ReachOut in the directory C:\REACHOUT) and the Microsoft TCP/IP-32 and
ReachOut icons are shown in the Windows “Program Manager”.
The ReachOut security options are pre-configured as follows:
The ReachOut “Password List” contains an entry with the “User Name” ANT-20 and the
accompanying password ANT-20. The option “Passwords Required” is set to “No”.
For detailed information about configuration options refer to the ReachOut user’s guide.
You now have to modify the pre-configured network setup to meet the specific requirements of
your network:
If you ordered the Remote Operation Option 3035/95.31 separately, install the software
packages as follows:
15. Set the “IP Address” of the ANT-20, the “Subnet Mask”, and (if required) the address of the
“Default Gateway”. Ask your network administrator for the required entries to adapt to your
network.
Confirm with “OK”.
16. Back in the “Network Drivers” dialog box, choose “Close”.
17. Back in the “Network Setup” dialog box, confirm with “OK”.
18. Type in the “Computer Name” (must be unique in the network) and the “User Name”.
Confirm with “OK”.
19. Back in the “Windows Setup” dialog box, remove the installation disk from drive A:, and
choose “Restart Computer”.
After this installation procedure, a NE2000 compatible driver is installed. It is not therefore
necessary to install the driver supplied together with the SCM Ethernet LAN card.
[cardware]
rem ---- PCMCIA Driver ----
DEVICEHIGH=C:\CARDWARE\PCSS.EXE
DEVICEHIGH=C:\CARDWARE\PCCS.EXE
DEVICE=C:\CARDWARE\PCRM.EXE /AUTODETECT
DEVICE=C:\CARDWARE\PCENABLE.EXE
DEVICE=C:\CARDWARE\PCDISK.EXE
[org]
[tcp]
include=cardware
LASTDRIVE=Z
To install and configure the software on a DominoCOM ANT-20 in the same way as on an
ANT-20, connect an external monitor, keyboard and mouse to the built-in PC-AT.
If you ordered the Remote Operation Option BN 3035/95.31 together with your ANT-20, the
required software packages are already installed on the ANT-20 (ReachOut in the directory
C:\REACHOUT) and the ReachOut icon is shown in the Windows95 file folder “Programs”.
The ReachOut security options are pre-configured as follows: The ReachOut “Password List”
contains an entry with the “User Name” ANT-20 and the accompanying password ANT-20. The
option “Passwords Required” is set to “No”.
For detailed information about configuration options refer to the ReachOut user‘s guide.
You now have to modify the pre-configured network setup to meet the specific requirements of
your network:
If you ordered the Remote Operation Option 3035/95.31 separately, install the software
packages as follows:
Installing the driver software for the SCM Ethernet LAN card
1. Start or return to Windows95.
2. Insert the SCM Ethernet LAN card into a free PCMCIA socket.
3. Follow the on-screen instructions of the “Update Device Driver Wizard” to install the driver
software:
– Insert the SCM distribution disk into drive A:
– Click “Other Locations …”, and then type the following folder name into the dialog box:
A:\WIN95
– Confirm with “OK”.
Back in the Update Device Driver Wizard” window, click “Finish”.
4. After complete installation, remove the SCM distribution disk from drive A:, and answer the
question “Do you want to restart your computer now?” with “Yes”.
After this installation procedure on the ANT-20 (the “Host” in terms of ReachOut ) you can start
the ReachOut Host and configure it as required.
To prevent a Viewer from accidentally tying up the Host, it is recommended setting the Host
configuration parameter “Inactivity Timeout” to a non zero value (in “Preferences …/Host
Options” menu).
After installing ReachOut on the controlling PC (the “Viewer” in terms of ReachOut ) and
configuring the ReachOut Viewer as required, you can start remote access to the ANT-20.
For detailed information refer to the ReachOut user‘s guide.
10
ANT-20/ANT-20E Mainframe, SONET Version
Contents
Specifications
4 E1 to E4 signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S-16
4.1 Error insertion and alarm generation (TX). . . . . . . . . . . . . . S-17
4.1.1 Error insertion (anomalies) . . . . . . . . . . . . . . . . . . . . . . . . . S-17
4.1.2 Alarm generation (defects) . . . . . . . . . . . . . . . . . . . . . . . . . S-17
i
Mainframe, SONET Version ANT-20/ANT-20E
ii
ANT-20/ANT-20E Mainframe, SONET Version
iii
Mainframe, SONET Version ANT-20/ANT-20E
Notes:
iv
ANT-20/ANT-20E Mainframe, SONET Version
Specifications
The numbers in square brackets […] correspond to the numbers printed on the instrument.
Calibrated specifications for the SDH Version ANT-20 3035/01 or ANT-20E 3035/21
are marked ***.
Calibrated specifications for the SONET Version ANT-20 3035/02 or ANT-20E 3035/22
are marked **.
Specifications S-1
Mainframe, SONET Version ANT-20/ANT-20E
1 Generator section
Output impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Ω
Interface3 Bit rate Line code Output voltage Output voltage Reflexion
(Mbit/s) tolerance coefficient
E1 2.0481 HDB3
1 3035/02 requires option 3035/90.33
2 3035/01 requires option 3035/90.34
3 depends on ANT-20 versions and options
4 from H series onwards
S-2 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . balanced
Output impedance
2.048 Mbit/s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 Ω
1.544 Mbit/s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Ω
Bit rate (Mbit/s) Line code Output voltage Output voltage Reflexion
tolerance coefficient
Specifications S-3
Mainframe, SONET Version ANT-20/ANT-20E
The TX bit rate is derived from the RX clock. The jitter of the incoming signal is suppressed.
S-4 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
2 Receiver section
“PMP” (“Low”) B3ZS, B8ZS, HDB3, AMI . . . . 15 to 26 dB attenuation referred to nominal level
Specifications S-5
Mainframe, SONET Version ANT-20/ANT-20E
Interface3 Bit rate (Mbit/s) Line code Signal equalization Reflexion coefficient
(adaptive)
Tolerance to jitter
Measured using PRBS 15 (≥ 8 Mbit/s) and PRBS 23 (> 8 Mbit/s) with “ITU-T” and “PMP” receive
levels attenuated by 20 dB referred to the nominal level.
Jitter amplitude
A1
A2
f2 f3 f4 Jitter frequency
S-6 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . balanced
Input impedance
2.048 Mbit/s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 Ω
1.544 Mbit/s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Ω
Specifications S-7
Mainframe, SONET Version ANT-20/ANT-20E
2.0481 HDB3 ≥ 18 dB
50 kHz to 3 MHz
1.5442 B8ZS, AMI
1 3035/02 requires option 3035/90.33
2 3035/01 requires option 3035/90.34
Tolerance to jitter
As per Tab. S-4, Page S-7
The appropriate bit clock is derived from the input signal and the offset from the nominal clock
rate is measured.
No offset measurement is possible for “Through Mode” and “TX clock from RX”.
The recovered clock can be used for synchronizing the TX bit rate (see Sec. 1.2.2, Page S-4).
S-8 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Test pattern
Pseudo-random bit sequences. . . . . . .PRBS 11, PRBS 11 invers, PRBS 15, PRBS 15 invers,
PRBS 20, PRBS 23, PRBS 23 invers,
QRSS 20 (QRSS 20 with max. 14 zeros)
Frames
Specifications S-9
Mainframe, SONET Version ANT-20/ANT-20E
BPV yes -
1 Mantissa: 1 to 9 (only 1 for TSE), exponent: -1 to -8 (whole numbers)
The insertion of errors (anomalies) and alarms (defects) is mutually exclusive. The first action
selected is active. The second action is rejected.
S-10 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
YELLOW-DS1, On/Off -
YELLOW-DS3 (RDI)
1 (see Tab. S-8)
The insertion of errors (anomalies) and alarms (defects) is mutually exclusive. The first action
selected is active. The second action is rejected.
Specifications S-11
Mainframe, SONET Version ANT-20/ANT-20E
Evaluation
All errors (anomalies) are counted simultaneously and stored.
.
Display
of anomalies via LEDs:
HISTORY LED (yellow) is on if the anomaly occurred at least once or is active within the
started measurement interval.
Anomaly LED
CRC6 FAS/CRC
P-DS3, CP-DS3 -
TSE TSE
BPV -
DS3-REI -
S-12 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Evaluation
All alarms (defects) which occur are evaluated simultaneously where possible and stored.
Storage takes place only within a started measurement interval
.
Display
of defects via LEDs:
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
Defect LED
IDLE-DS3, FEAC-DS3 -
Tip: DS3-AIC is used for autoconfiguring the instrument and can only be read out via remote
control.
Specifications S-13
Mainframe, SONET Version ANT-20/ANT-20E
Option: BN 3035/90.20
3.3.1 Functions
This Option provides the following functions for all PDH multiplex options fitted to the ANT-20.
Drop&Insert
This function is only available in conjunction with the following options:
– or –
– or –
The characteristics and specifications for the Drop&Insert function are given in the descriptions
for the various options.
Through Mode
The received signal is looped through the ANT-20 and re-transmitted by the generator.
The ANT-20 operates in Through Mode as a signal monitor without affecting the signal.
The ANT-20 provides access to the tributary channels within the “MUX/DEMUX” chain when
used in conjunction with the “PDH MUX/DEMUX” and “M13 MUX/DEMUX” options, BN 3035/
90.30 to BN 3035/90.32. This also applies if the PDH signal is transmitted in a container.
The looped-through signal can also be jittered using the Jitter Generator options (Jitter
Generator up to 155 or 622 Mbit/s, BN 3035/90.60 to 61). This function is available for all bit
rates fitted to the instrument.
S-14 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Through Mode
In Through Mode, clock generation is always derived from the receive signal clock.
No offset is possible in this operating mode (see Sec. 1.2.2, Page S-4).
Through Mode
Through Mode
Defect generation is not possible.
3.3.5 Measurements
Specifications S-15
Mainframe, SONET Version ANT-20/ANT-20E
4 E1 to E4 signals
Available with ANT-20 version 3035/01 or
with ANT-20 version 3035/02 and option 3035/90.33.
Test signals for bit error measurements.
Test pattern
Frames
S-16 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
BPV yes -
1 Mantissa: 1 to 9 (only 1 for TSE), exponent: -1 to -10 (whole numbers)
The insertion of errors (anomalies) and alarms (defects) is mutually exclusive. The first action
selected is active. The second action is rejected.
- On/Off M in N
The insertion of alarms (defects) and errors (anomalies) is mutually exclusive. The first action
selected is active. The second action is rejected.
Specifications S-17
Mainframe, SONET Version ANT-20/ANT-20E
Evaluation
All errors (anomalies) are counted simultaneously and stored.
.
Display
of anomalies via LEDs:
HISTORY LED (yellow) is on if the anomaly occurred at least once or is active within the
started measurement interval.
Anomaly LED
CRC-41 FAS/CRC
E bit1 -
TSE TSE
BPV -
1 Requires option 3035/90.30 or 3035/90.31
S-18 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Evaluation
All alarms (defects) which occur are evaluated simultaneously where possible and stored.
Storage takes place only within a started measurement interval.
Display
of defects via LEDs:
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
Defect LED
LSS LSS
Specifications S-19
Mainframe, SONET Version ANT-20/ANT-20E
Option: BN 3035/90.20
4.3.1 Functions
This Option provides the following functions for all PDH multiplex options fitted to the ANT-20.
Drop&Insert
This function is only available in conjunction with the following options:
• PDH MUX/DEMUX
M13 MUX/DEMUX: BN 3035/90.30 to BN 3035/90.32
– or –
– or –
The characteristics and specifications for the Drop&Insert function are given in the descriptions
for the various options.
Through Mode
The received signal is looped through the ANT-20 and re-transmitted by the generator.
The ANT-20 operates in Through Mode as a signal monitor without affecting the signal.
The ANT-20 provides access to the tributary channels within the “MUX/DEMUX” chain when
used in conjunction with the “PDH MUX/DEMUX” and “M13 MUX/DEMUX” options, BN 3035/
90.30 to BN 3035/90.32. This also applies if the PDH signal is transmitted in a container.
The looped-through signal can also be jittered using the Jitter Generator options (Jitter
Generator up to 155 or 622 Mbit/s, BN 3035/90.60 to 61). This function is available for all bit
rates fitted to the instrument.
S-20 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Through Mode
In Through Mode, clock generation is always derived from the receive signal clock.
No offset is possible in this operating mode (see Sec. 1.2.2, Page S-4).
Through Mode
Through Mode
Defect generation is not possible.
4.3.5 Measurements
Specifications S-21
Mainframe, SONET Version ANT-20/ANT-20E
5 Measurement modes
“Near End” and “Far End” analyses are performed simultaneously if available.
ES, SES, EFS, SEFS and UAS are evaluated.
The SES and UAS threshold settings correspond to GR-253 (Performance Monitoring) and
T1.231.
ES, EFS, SES and UAS are evaluated; DM (degraded minutes) are also evaluated.
The multiplex factor used in older versions of Recommendation G.821 (Annex D) can be
applied if required.
G.821 evaluation can be performed on the following events:
• FAS bit errors (FAS 2, FAS 8, FAS 34, FAS 140)
• CRC errors
• E bit errors
• Bit errors (TSE, Test Sequence Error)
The following signals can be measured when performing G.821 evaluation of bit errors (TSE):
• unframed patterns
• n x 64 kbit/s
• framed patterns and bulk signals
• Overhead bytes E1, E2, F1, F2, D1 to D3 and D4 to D12
Pass/fail assessment in conjunction with path allocation of between 0.1 and 100%.
The SES threshold can be set as required.
Since G.821 evaluation requires evaluation of bit errors, facilities for evaluating block errors are
disabled.
Display
of defects via LEDs:
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
S-22 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
The following are evaluated: EB, BBE, ES, EFS, SES and UAS.
Pass/Fail assessment depending on path allocation of 0.1 to 100%.
The thresholds for SES and UAS can be set by the user.
Near end: HP-B3, LP-B3, BIP2, FAS bei 140/34/8 oder 2M, CRC 4, DS3FAS,
DS3-P-Parity, DS3-C-Parity, DS1FAS, D1-CRC6
Display
of defects via LEDs:
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
Evaluation of the near end and the far end is simultaneous as soon as the signal structure set
allows a far end measurement.
Far end evaluations can only be made if REI is available.
Specifications S-23
Mainframe, SONET Version ANT-20/ANT-20E
Display
of defects using LED indicators
(also in the Anomaly/Defect Analyzer – Summary display window):
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
Evaluation of the near end and the far end is simultaneous as soon as the signal structure set
allows a far end measurement.
Far end evaluations can only be made if REI is available.
Bit errors can be evaluated for:
• unframed patterns
• framed patterns and bulk signals
• Overhead bytes E1, E2, F1, F2, F2L, D1 through D3 and D4 through D12 in the SOH/POH
of SDH signals
The special block error evaluation using BIP-1 blocks means that the instrument is run in bit er-
ror evaluation mode. It is therefore not possible to switch to block error evaluation. This does not
apply to the TSE meas. point, for which real block errors are evaluated. Therefore you cannot
switch to bit error evaluation when making a G.829 evaluation on TSEs.
S-24 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Display
of defects using LED indicators
(also in the Anomaly/Defect Analyzer – Summary display window):
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
Display
of defects using LED indicators
(also in the Anomaly/Defect Analyzer – Summary display window):
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
Specifications S-25
Mainframe, SONET Version ANT-20/ANT-20E
Evaluation of the near end and the far end is simultaneous as soon as the signal structure set
allows a far end measurement.
Far end evaluations can only be made if REI is available.
Bit errors can be evaluated for:
• unframed patterns
• framed patterns and bulk signals
• Overhead bytes E1, E2, F1, F2, F2L, D1 through D3 and D4 through D12 in the SOH/POH
of SDH signals
As the M.2101 evaluation measures block errors, bit error evaluation cannot be activated.
Exception: B2SUM. BIP-1 blocks are used for this. These are only accessible in the instrument
via a bit error measurement. For this reason, block error evaluation is not available for a M.2101
evaluation on B2SUM.
Display
of defects via LEDs
(also in the Anomaly/Defect Analyzer – Summary display window):
HISTORY LED (yellow) is on if the defect occurred at least once or is active within the
started measurement interval.
S-26 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
6 Automatic measurements
The auto configuration function sets the ANT-20 receiver automatically. The routine searches
for the presence of standard SDH, SONET, PDH or ATM signals at the electrical inputs (for the
input level ranges “ITU-T”/“High” or “PMP”/“Low”), or at the optical inputs. The instrument
version and options fitted are taken into account. The main emphasis is placed on detecting the
signal structure. Detailed matching to the signal contents can be carried out manually if desired.
The sequence is divided into three parts:
• Check Interface
• Check Mapping
• Check Payload
Other factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . input bit rate frequency offset > 150 ppm
A check is made for the mapping structure using the Signal Label and the pointer bytes (to
differentiate between AU-4 and AU-3). The check is always made in channel #1.
With STM-16 / OC-48 signals, a check is made for an AU-4 structure only in “ITU-T” mode or for
an AU-3 structure only in “ANSI” mode.
OC-12c/STM-4c Virtual Concatenation is not recognized by the autoconfiguration function.
Allowed-for defects:
LOF/OOF LOF/OOF
AU-AIS AIS-P
MS-AIS AIS-L
TU-AIS AIS-V
AU-LOP LOP-P
TU-LOP LOP-V
LOM LOM
If UNEQuipped is detected, the mapping previously selected or a default mapping will be set.
Auto configuration recognizes “C-11 via TU-12” mapping as “C-12” mapping.
Specifications S-27
Mainframe, SONET Version ANT-20/ANT-20E
The check only takes account of the test patterns recommended in the relevant standards.
S-28 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
8 Mbit/s (E2)
DS3 unframed
2 Mbit/s (E1) (bal/unbal)
DS3 framed (M13)
DS3 framed (C-Par)
DS3
DS3/DS1 (C-Par/ESF)
DS2
DS3/DS1 (C-Par/SF)
DS1 (bal/unbal)
DS3/DS1 (M13/ESF)
DS3/DS1 (M13/ESF)
Autoconfiguration failed
DS2 unframed
DS1 unframed
DS1 framed (ESF)
DS1 framed (SF)
uncertain
Specifications S-29
Mainframe, SONET Version ANT-20/ANT-20E
The “Scan” function permits sequential testing of all tributary channels in an SDH or SONET
signal. The appropriate mapping options are needed for this.
The test is performed within an AU (SDH version) or a SPE (SONET version). Selection of the
various AUs / SPEs for signals with higher bit rates is done manually.
The settings for the generator and receiver must be matched for loop measurements.
The channel scan takes place synchronously on the transmit and receive sides. If the signal
structure settings differ, only the receive channel settings will be altered.
The ANT-20 receiver checks the receive signal defects and those of the corresponding SDH or
SONET structure and of the channel and enters the results of the single channels in a matrix.
Allowed-for defects:
LOS LOS
AU-AIS AIS-P
MS-AIS AIS-L
TU-AIS AIS-V
AU-LOP LOP-P
TU-LOP LOP-V
HP-UNEQ UNEQ-P
LP-UNEQ UNEQ-V
TU-LOM LOM
LSS LSS
S-30 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
The “Search” function allows you to search for a tributary channel in a SDH or SONET signal.
The appropriate mapping options are needed for this.
The test is performed within an AU (SDH version) or a SPE (SONET version). Selection of the
various AUs / SPEs for signals with higher bit rates is done manually.
During the search, only the receive channels are altered.
The ANT-20 receiver checks the receive signal defects and those of the corresponding SDH or
SONET structure and of the channel and enters the results of the single channels in a matrix.
Allowed-for defects:
LOS LOS
AU-AIS AIS-P
MS-AIS AIS-L
TU-AIS AIS-V
AU-LOP LOP-P
TU-LOP LOP-V
HP-UNEQ UNEQ-P
LP-UNEQ UNEQ-V
TU-LOM LOM
LSS LSS
Specifications S-31
Mainframe, SONET Version ANT-20/ANT-20E
The “Trouble Scan” function permits sequential testing of all tributary channels in an SDH or
SONET signal. The appropriate mapping options are needed for this.
The test is performed within an AU (SDH version) or a SPE (SONET version). Selection of the
various AUs / SPEs for signals with higher bit rates is done manually.
During the “Trouble Scan”, only the receive channels are altered.
The ANT-20 receiver checks the receive signal defects and those of the corresponding SDH or
SONET structure and of the channel and enters the results of the single channels in a matrix.
You can display a detailed alarm history by selecting an individual channel from within the
matrix.
Allowed-for defects:
LOS LOS
AU-AIS AIS-P
MS-AIS AIS-L
TU-AIS AIS-V
AU-LOP LOP-P
TU-LOP LOP-V
MS-RDI RDI-L
HP-RDI RDI-P
LP-RDI RDI-V
HP-UNEQ UNEQ-P
LP-UNEQ UNEQ-V
TU-LOM LOM
HP-PDI PDI-P
LP-PDI PDI-V
S-32 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Table S-18 Defects allowed for in the “Trouble Scan” function (continued)
Specifications S-33
Mainframe, SONET Version ANT-20/ANT-20E
The ANT-20 measures the signal delay between the generator and receiver using characteristic
sequences in the selected PRBS. The signal delay measurement is automatic and continuous,
i.e. individual measurements are repeatedly performed. Practically any signal structure that can
be set on the ANT-20 can be used for the measurement.
Exceptions:
• ATM signal structures
• Overhead measurements
• Through Mode
• ADM test
The measurement range and measurement time depend on the pattern bit rate and the selected
pattern.
The maximum possible measurement value depends on the length of the PRBS. The maximum
value is calculated and shown in the results window. This value can be influenced by selecting
a shorter or a longer test pattern.
Signal structure Short test pattern Max. measured Long test pattern Max. measured
value, in ms value, in ms
C4 Bulk PRBS231 56 - 56
Table S-19 Max. measurement values as a function of signal structure and test pattern
S-34 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Signal structure Short test pattern Max. measured Long test pattern Max. measured
value, in ms value, in ms
Table S-19 Max. measurement values as a function of signal structure and test pattern (continued)
The accuracy and display resolution also depend on the pattern bit rate.
Specifications S-35
Mainframe, SONET Version ANT-20/ANT-20E
64 kbit/s: 1 byte/frame
128 kbit/s: 2 bytes/frame
192 kbit/s: 3 bytes/frame
576 kbit/s: 9 bytes/frame
1 Ground
2 Ground
3 RX data Input
4 RX data (inv) Input
5 RX control Output
6 RX control (inv) Output
7 RX clock Input/Output
8 RX clock (inv) Input/Output
9 RX synch Input/Output
10 RX synch (inv) Input/Output
11 TX data Output
12 TX data (inv) Output
13 TX control Output
14 TX control (inv) Output
15 TX clock Output
16 TX clock (inv) Output
17 TX synch Output
18 TX synch (inv) Output
19 Ground
20 +5 V/100 mA
S-36 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BNC
Input
Output
Socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BNC
Specifications S-37
Mainframe, SONET Version ANT-20/ANT-20E
Socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bantam
Socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BNC
S-38 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Operating system
CPU
The CPU is constantly being updated. The current CPU and hard disk characteristics are
displayed after switching on the instrument during the boot-up screen display.
Floppy drive
Specifications S-39
Mainframe, SONET Version ANT-20/ANT-20E
Display
Option 3035/93.10
S-40 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Keyboard
Built-in
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IBM-AT/PS/2
Battery
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lithium
Life time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .>5 years
The battery serves as the buffer for the PC clock’s supply voltage and for saving the CMOS
setup.
Specifications S-41
Mainframe, SONET Version ANT-20/ANT-20E
9 General specifications
Nominal voltage (automatic range switching) . . . . . . . . . . . . . . .100 to 127 V and 200 to 240 V
S-42 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Precipitation no 6 mm/min no
Water no 1 m/s no
Sinusoidal 9 to 200 Hz: 5 m/s2 8 to 200 Hz: 20 m/s2 9 to 200 Hz: 10 m/s2
vibration 200 to 500 Hz: 40 m/s2 200 to 500 Hz: 15 m/s2
Table S-25 Major parameters for the classes (see Fig. S-24)
Interference suppression
This instrument meets the requirements of EN 50 081-1 and hence limit value class B of
EN 55 022 (identical with CISPR 22:1985 modif., DIN VDE 0878 part 3) and FCC Rules Part 15
Subpart J Class A. The instrument conforms to the safety aims of European regulation
89/336/EWG of 03.05.89 in respect of interference suppression. A special permit for operation
is not required.
The instrument has been tested such that the requirements in respect of interference
suppression for this instrument will also be met if it is operated in a system.
This is conditional upon the correct construction of the system and the use of the specified
connecting cables, with particular attention being paid to adequate screening.
Specifications S-43
Mainframe, SONET Version ANT-20/ANT-20E
If the device under test connected to this instrument is in itself capable of generating interfering
radiation, e.g. when the screening to the device under test is not continuous, the user must
ensure that any interference generated remains within the prescribed limits. Suitable screening
precautions may be additionally required.
.
on signal circuits
on AC line circuits
S-44 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
9.5 Calibration/Maintenance
9.6 Dimensions/Weight
ANT-20
Weight
including protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approx. 9.6 kg
Dimensions (w x h x d) in mm
including protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approx. 360 x 370 x 200
ANT-20E
Weight
including protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .approx. 15 kg
Dimensions (w x h x d) in mm
including protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approx. 360 x 370 x 290
Specifications S-45
Mainframe, SONET Version ANT-20/ANT-20E
One STM-1 mapping is included in the price; select the mapping option you require.
With monochrome display, English and German language version.
.
One STS-1 mapping is included in the price; select the mapping option you require.
With monochrome display, English language version.
One STM-1 mapping is included in the price; select the mapping option you require.
With TFT display, English and German language version.
One STS-1 mapping is included in the price; select the mapping option you require.
With TFT display, English language version.
S-46 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
9.7.3 Options
SONET mappings
STM-1 mappings
Drop&Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BN 3035/90.20
PDH functions
Specifications S-47
Mainframe, SONET Version ANT-20/ANT-20E
Optical interfaces
OC-12c/STM-4c Options
Wavetek Wandel Goltermann can supply a wide selection of optical power level meters,
sources, attenuators and accessories. Please ask your local sales office for information.
S-48 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
ATM functions
ATM module
Includes ATM mapping STM-1/STS-3c . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .BN 3035/90.70
Additional ATM-Mappings
requires ATM-Module 3035/90.70 or BN 3035/90.80
Specifications S-49
Mainframe, SONET Version ANT-20/ANT-20E
9.7.7 Calibration
9.7.8 Accessories
Optional accessories
All options can be retrofitted by the Wavetek Wandel Goltermann worldwide service network
S-50 Specifications
ANT-20/ANT-20E Mainframe, SONET Version
Index
i
Mainframe, SONET Version ANT-20/ANT-20E
ii
ANT-20/ANT-20E Mainframe, SONET Version
O S
O.172 A-37, A-43, A-50, A-53, A-58 Safety class G-1
Offset VI-3 Save as dialog O-42
OK button O-36 Saving an application O-25
On-line help O-33 Selecting instruments O-21
Optical power splitter A-6 Sensor test A-78
Option buttons O-35 SEP used in Verdict TB-20, TB-28
Overhead Analyzer A-29 SES-Threshold (Performance analysis) TB-13,
Overhead Generator VI-23, A-29 TB-20, TB-22
Setting a new pointer TB-4
P Severely Errored Frame Seconds (Performance
analysis) TB-6 to TB-34
Packing G-6 Severely Errored Seconds (Performance analysis)
Path Overhead A-29 TB-6 to TB-34
PDH Generator/Analyzer VI-38, VI-40 Signal input [12] S-7
Peak cell rate A-83 Signal input [14] S-5
Peak-to-peak CDV A-74 Signal output [13] S-3
Performance Analysis A-22 Signal output [15] S-2
Performance analysis VI-41, TB-6 Signal Structure O-23, A-3
Performance monitoring (SONET) TB-7 SOH VI-23
Periodic pointer TB-2 Standard sequence TB-3
Phase hits A-47 Start/stop measurement O-29
Physical layer O-14, A-63 Storage under damp conditions G-6
POH A-29
Pointer action generation TB-2
Pointer Analyzer VI-35, A-26
T
Pointer burst VI-33, TB-3 T1.231 A-23
Pointer Generator VI-32, A-26 TCM Sequence VI-26
Pointer sequence VI-33, A-25 TDEV (Time Deviation) A-56
Pointer sequenzes parameter TB-5 Testcell A-65
Pointer stress test A-25 Through mode VI-4, A-5
Print dialog O-40 TIE A-55
Print Header O-39, O-41 TIM A-33
Print menu – Application manager O-19, O-39 Timer O-30
Print menu – Virtual instruments O-40 Timer-controlled measurements O-46
Printer Setup O-41 Title bar O-20
TOH VI-23, A-29
R Trace Identifier VI-29
Trace identifier A-31
Ratio (anomaly result) VI-17 Trace Identifier Mismatch A-33
Receiver section Traffic signal icon O-29
Specifications Transport Overhead A-29
Reference clock input[25] (REF CLOCK IN) Trigger VI-3
S-37
Trigger input/output [26] S-37
Recovery time G-7
Remote operation RO-1
iii
Mainframe, SONET Version ANT-20/ANT-20E
U
UAS-Limit TB-20, TB-24, TB-27
UAS-Mode TB-20, TB-24, TB-27
Unavailable Seconds (Performance analysis)
TB-6 to TB-34
Unpacking G-6
V
VBR A-82
Ventilation G-7
Versacon inserts M-2
Virtual instruments O-14, A-1
VPI/VCI parameters A-72
W
Wander A-53, A-55
Wander analysis (MTIE/TDEV) A-55
Wander Generator A-50
Wander modulation period A-52
iv