1643 PDF
1643 PDF
1643 PDF
( Reaffirmed 1998 )
Indian Standard
CODE OF PRACTICE FOR
FIRE SAFETY OF BUILDINGS (GENERAL):
EXPOSURE HAZARD
( First Revision )
--_
IS : 1643 - 1988
Indian Standard
CODE OFPRACTICEFOR
FIRESAFETY OFBUILDINGS(GENERAL):
EXPOSUREHAZARD
( First Revision )
0, FOREWORD
0.1This IndianStandard ( First Revision ) was Canada. This revision includes the values in
adopted by the Bureau of Indian Standards on Of floor
K'eSpeCt area ratio, and open space accord-
2 May 1988, after the draft finalized by the Fire ing to norms adopted by these countries.
Safety Sectional Committee had been approved
by the Civil Engineering Division CkUnCil. o-3 For the purpose of deciding whether a
particular requirement of this standard is
0.2 A series of Indian Standards covering the fire complied with, the final value, observed or cal-
safety of buildings in general, principles of fire culated, expressing the result of a test or analysis,
grading, details of construction, exit requirements shall be rounded off in accordance with IS : 2-
and exposure hazard, have been formulated. This 1960*. The number of significant places retained
Indian Standard, covering the last aspect, was in the rounded off value should be the same as.
first formulated in 1960. In the past 25 years, that of the specified value in this standard.
useful data has become available based on studies
conducted in countries such as USA, UK and *Rules for rounding off numerical values ( revised 1.
2.2 The precautions taken by keeping proper 4.1 The comparative floor area ratios for diffe-
spacing of the building prevent spread of fire by rent occupancies and types of construction are
direct contact of flames and hot gases emitted given in Table 1.
from the burning building or by radiated heat
and flying brands.
4.2 Each portion of a building, which is sepa-
rated by one or more continuous fire resisting
2.3 The factors like type of construction ( see walls, having a fire resistance of not less than 4 h,
1s : 1642-1988t ) based on occupancy distance extending from the foundation to 1 m above the
roof at all points, may be considered to be a
*Cede of practice for fire safety of buildings ( general ):
General principles of fire grading and classification (first separate building for the calculation of maximum
revision ). permissible height and floor area, provided open-
+Codeof practice for fire safety of buildings ( general ): ings, if any, in the separating wall, are also,
Details of construction (first revision 1. protected by fire assemblies of 4 h.
1
1S:1643- 1988
2
IS : 1643- 1988
.. . I ..^. .. .
the open space lett up to halt the width
of the plot should also be taken into TABLE 2 SIDE AND REAR OPEN SPACES FOR
DIFFERENT HEIGHTS OF BUILDINGS
account for calculating the average width
of the rear open space. For plots of ( Clause 5.3.3.1 )
depth less than 9 m, for buildings up to Sr. No. HEIURT OF &DE AND REAP. OPEN
7 m in height, the rear open space may BCILDIXW SPACES TOBE LEFT
be reduced to 1’5 m. AROUNDBCILDINQ
(1) (2) (3)
b) Rear open space to extend throughout the m m
rear wall - The rear open space should i) 10 3
be co-extensive with the entire face of the ii) 15 5
rear wall. If a building abuts on two or iii) 18 6
more streets, such rear open space should iv) 21 7
be provided throughout the face of the 24
v) 8
rear wall. Such rear wall should be the
vi) 27 9
wall on the opposite side of the face of
vii) 30 10
the building abutting on the wider street,
viii) 35 11
unless the authority directs otherwise.
ix) 40 12
x) 45 13
5.3.1.3 Side open space xi) 50 14
xii) 53 and above 16
a>Every semi-detached and detached build-
NOTE 1 - For buildings above 24 m in height, there
ing should have a permanently open air
space, forming an integral part of the should be a minimum front open space of 6 m.
site as below: NOTE 2 -Where rooms do not derive light and venti-
lation from the exterior open space, the width of such
1) For detached buildings, there should exterior open space as given in co1 3 may be reduced by
be a minimum side open space of 3 m 1 m subject to a minimum of 3 m and a maximum of
8 m. No further projections shall be permitted.
on both the sides.
NOTE 3 -If the length or depth of the building
NOTE - For detached residential buildings up to exceeds 40 m. add to co1 3 ten percent of length or
7 m in height on plots with a frontage less than 12 m, depth of building minus 4.0 m.
one of the side open spaces may be reduced to 1.5 m.
3
IS : 1643 - 1988
Further, the inner courtyard should have more than one building belonging to the same
an area, throughout its height of not less owner, the width of such open air space should
than the square of one-fifth the height of be the one specified for the tallest building as
the highest wall abutting the courtyard. specified in 5.3.3 abutting on such open air
Provided that when any room ( excluding space.
staircase bay, bathroom and water-closet )
is dependent for its light and ventilation 5.3.6.2 If such interior or exterior open air
on an inner courtyard, the dimension space is jointly owned’by more than one person,
should be such as is required for each wing its width should also be as specified in 5.3, pro-
of the building. vided every such person agrees to allow his
portion of such joint open air space to be used
Where only water-closet and bathroom
for the benefit of every building abutting on such
are abutting on the interior courtyard joint open air space and provided he sends such
the size of the interior courtyard should be written consent to the authority for record. Such
in line with the provision for ventilation common open air space should thenceforth be
shaft as given in 5.3.5 (b). treated as a permanently open air space required
b) Ventilation shaft - For ventilating spaces for the purposes of the Code. No boundary
for water-closets and bathrooms, if not wall between such joint open air space should
opening on to front, side, rear and interior be erected or raised to a height of more than
open spaces, these should open on to the 2’0 m.
ventilation shaft, the size of which should
not be less than the values given below: 5.4 Other Occupancies
Height of Size of Venti- Minimum Size 54.1 Open spaces for other occupancies should
Building lation Shaft of Shaft be as below:
,rn me a) Educational buildings - Except for nursery
up to 10 1’2 0; schools, the open spaces around the build-
12 2.8 1.2 ing should be not less than 6 m;
18 4’0 1’5
b) Institutional buildings - The open space
24 5’4 1’8 at front should not be less than 12 m and
30 8’0 2’4 the other open spaces around the building
Above 30 9’0 3’0 should be not less than 6 m;
NOTE1 -For buildings of height above 30 m, a
mechanical ventilation system should be installed c) Assembly building - The open space at
besides the provision of minimum ventilation shaft. front should be not less than 1.2 m and
NOTE 2 - For fully air-conditioned residential
other spaces not less than 6 m;
buildings for lodging purposes,. the ventilation shaft
need not be insisted upon, pronded the air-condition- NOTE-However,. if assembly buildings are,permitt-
ing system works in an uninterrupted manner, also, ed in purely residenttal zones, the open spaces around
provided there is an alternative sources of power the building should be not less than 12 m.
supply.
d) Business, merkantile and storage build-
c) Outer courtyard - The minimum width of ings - The open spaces around the
the outer courtyard ( as distinguished from building should be not less than 4’5 m.
its depth ) should be not less than 2’4 m Where these occur in purely residential zone-
If the width of the outer courtyard is less or in a residential with shops line zone the
than 2’4 m, it should be treated as a notch open spaces may be relaxed;
and the provisions of outer courtyard
should not apply. However, if the depth e) Industrial buildings - The open spaces.
of the outer courtyard is more than the around the building should be not less
width, the provisions of 5.1.2 should apply than 4’5 m for heights up to 16 m, with
for the open spaces to be left between the an increase in the open spaces of 0’25 m
wings. for every increase of 1 m or fraction there-
of in height above 16 m; and
5.3.6 Joint Open Air Space - Every such
interior or exterior open air space, unless the NOTE- Special rules for narrow industrial plots in
the city, namely, plots less than 15 m in width, and
latter is a street, should be maintained for the with appropriate set-backs from certain streets and,
benefit of such building exclusively and should be highways, should be applicable.
entirely within the owner’s own premises.
f) Hazardous occupancies - The open spaces.
5.3.6.1 If such interior or exterior open air around the building should be as specified
space is intended to be used for the benefit of for industrial buildings [ see 5.4.1 ( e I I.
IS : 1643 - 1988
4 Projected balcony at higher floors of width e) The space under the portico should be
not more than 0’9 m; and paved and channelled as required.
e) Projecting rooms/balconies [ see 5.5.1(. d > ] 5.5.2.3 Sunshades over windows and ventilk
at alternate floors such that rooms of the tors - Projections of sunshades over windows
lower two floors get light and air and the or ventilators in existing built-up or congested
prqjection being not more than the height areas, when pe<mitted by the authority should
of the storey immediately below. fulfil the following conditions:
5
IS : 1643 - 1988
4 The width of the main street on which the the premises should be provided at the
building abuts should not be less than main entrance; the width of such entrance
12 m and one end of this street should should be not less than 4’5 m. If an arch
join another street not less than 12 m in or covered gate is constructed, it should
width; have a clear head-room of not less than
5 m.
b) The road should not end in a dead end; 6.2 Mired Oceupaacy - When any building is
4 The compulsory open spaces around the used for more than one type of occupancy, it
building should not be used for parking; should conform to the requirements for the most
and hazardous the occupancies. If mixed occupancies
are separated by a separating wall of 4 h fire
4 Adequate passageway and clearances rating, the occupancies should be treated
required for fire fighting vehicles to- enter Individually.
6
Bureau of Indian Standards
RIS is a statutory institution established under the B~rcatc of Irtdiorr Stnttdord.r Act, I986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may lx reproduced in any form
without the prior permission in writing of BIS. This does nc\t Ijrwlude the l’rcc use. in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also
reviewed periodically; a standard along with amendments is reaflirmed when such review indicates that
no changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users
of Indian Standards should ascertain that they arc in possession of the latest amendments or edition by
referring to the latest issue of ‘BIS Handbook’ and ‘Standards: Monthly Additions’.
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg. New Delhi 110 002 Tclcgr;lms : Manaksanstha
Telephones : 323 0 I 3 I, 323 33 75.323 94 02 (Common to all offices)