Dataforth Elit PDF
Dataforth Elit PDF
Instrument Class ®
Industrial
Electronics
Signal Conditioning
Data Acquisition
Data Communications
Table of Contents
Quick Product Selection Guide.............................................................................. 1 SensorLex® 8B Isolated Miniature Signal Conditioning Products
SCM5B Isolated Analog Signal Conditioning Products
8B Selection Guide ...................................................... 101
SCM5B Selection Guide .................................................. 3 Voltage Input Modules, Narrow Bandwidth: 8B30/31 ........ 104
Analog Voltage Input Modules, Narrow Bandwidth: Current Input Modules: 8B32 ....................................... 106
SCM5B30/31..................................................................... 6 True RMS Input Modules: 8B33 ................................... 108
Analog Current Input Modules: SCM5B32 . ..................... 8 Linearized 2- or 3-Wire RTD Input Modules: 8B34 ........... 110
True RMS Input Modules: SCM5B33.............................. 10 Linearized 4-Wire RTD Input Modules: 8B35 . ............. 112
Linearized 2- or 3-Wire RTD Input Modules: SCM5B34 ... 12 Potentiometer Input Modules: 8B36 ................................................................. 114
Linearized 4-Wire RTD Input Modules: SCM5B35 ........ 14 Non-Linearized Thermocouple Input Modules: 8B37 ....................................... 116
Potentiometer Input Modules: SCM5B36 ........................................................... 16 Strain Gage Input Modules, Wide and Narrow Bandwidth: 8B38...................... 118
Non-Linearized Thermocouple Input Modules: SCM5B37 ................................. 18 Current Output Modules: 8B39 . ....................................................................... 120
Strain Gage Input Modules, Narrow Bandwidth: SCM5B38 ............................... 20 Voltage Input Modules, 1kHz Bandwidth: 8B40/41 .......................................... 122
Strain Gage Input Modules, Wide Bandwidth: SCM5B38 .................................. 22 2-Wire Transmitter Interface Modules: 8B42 . .................................................. 124
Current Output Modules: SCM5B39 . ................................................................. 24 Voltage Input Modules: 8B43 ........................................................................... 126
Matched-Pair Servo/Motor Controller Modules: SCM5B392 .............................. 26 Frequency Input Modules: 8B45 ...................................................................... 128
Analog Voltage Input Modules, Wide Bandwidth: SCM5B40/41 ........................ 28 Linearized Thermocouple Input Modules: 8B47 ............................................... 130
2-Wire Transmitter Interface Modules: SCM5B42 .............................................. 30 Voltage Output Modules: 8B49 . ....................................................................... 132
General Purpose Input Modules: SCM5B43 ...................................................... 32 Voltage Input Modules, 20kHz Bandwidth: 8B50/51 ........................................ 134
Frequency Input Modules: SCM5B45 ................................................................ 34 8B Module Dimensions and Pinouts.................................................................. 136
Linearized Thermocouple Input Modules: SCM5B47 ......................................... 36 8B Backpanels and Accessories ...................................................................... 137
Accelerometer Input Module: SCM5B48 ............................................................ 38
Voltage Output Modules: SCM5B49.................................................................... 40 SCM9B Isolated, Intelligent Signal Conditioning Products
SCM5B Module Dimensions and Pinouts............................................................ 42
SCM9B Selection Guide .............................................. 147
SCMVAS Voltage Attenuator System.................................................................. 43
Sensor-to-Computer Modules: SCM9B-1000/2000 ...........150
Isolated Analog Voltage Input Modules: SCM5B30/40-07................................... 44
Sensor-to-Computer Modules,
High Voltage Attenuator Modules: SCMVAS-Mnnn............................................. 45
4-Channel: SCM9B-5000.............................................. 154
SCM5B Backpanels and Accessories ................................................................ 48
DIN Rail Mount Sensor-to-Computer
SCM7B Isolated Process Control Signal Conditioning Products Modules: SCM9B-D100................................................ 156
Computer-to-Analog Output Modules: SCM9B-3000/4000............................... 159
SCM7B Selection Guide ................................................ 66 Converters/Repeaters: SCM9B-A1000/A2000 ................................................. 161
Analog Voltage Input Modules: SCM7B21/30/31 . ......... 68 DIN Rail Mount RS-485 Repeater: SCM9B-D192 ............................................ 162
Bipolar Voltage Output Modules: SCM7B22................... 70 SCM9B Mechanical Dimensions ...................................................................... 163
Process Current/Voltage Input Modules: SCM7B32/33.... 72 24- and 64-Channel Digital I/O Boards: SCM9B-H1750/H1770 . ..................... 164
Linearized 2- or 3-Wire RTD Input Modules: 8- and 14-Channel Mounting Backpanels......................................................... 165
SCM7B34/34N................................................................ 74 SCM9B Utilities Software ................................................................................. 166
2-Wire Transmitter Interface Modules with Loop Power: SCM7B35................... 76
Potentiometer Input Modules: SCM7B36............................................................ 78 isoLynx® SLX200/SLX300 Data Acquisition Systems and Software
Non-Linearized Thermocouple Input Modules: SCM7B37.................................. 80
SCM5B isoLynx® Data Acquisition System: SLX200.... 167
Process Current Output Modules: SCM7B39...................................................... 82
8B isoLynx® Data Acquisition System: SLX300 ................ 174
Analog Voltage Input Modules, Wide Bandwidth: SCM7B40/41 ........................ 84
ReDAQ® Freedom SCADA Software (for SLX200):
Linearized Thermocouple Input Modules: SCM7B47.......................................... 86
SLX920 ............................................................................178
SCM7B Module Dimensions and Pinouts............................................................ 88
ReDAQ® Shape Software (for SLX300): SLX930 ............ 179
SCM7B Backpanels and Accessories................................................................. 89
SCMD Isolated Digital I/O Modules DSCT DIN Rail Mount Two-Wire Transmitters
Key 5B Features
• ±0.03% Accuracy (Typical) • Low Output Noise
• ±0.005% Linearity • –40°C to +85°C Operating Temperature
• 1500Vrms Transformer Isolation & • CSA C/US Certified,
240Vrms Field-Side Protection (Class I, Division 2, Groups A, B, C, D)
• ANSI/IEEE C37.90.1 Transient Protection • CE and ATEX Compliant
• Manufactured per RoHS Directive
• 5V Power (30mA Typical)
2002/95/EC
• 4- to 6-Pole Low-Pass Filtering
Each SCM7B module provides a single channel of isolated analog input or output. Various input modules accept analog voltage or current signals
from all types of field sensors and sources; they provide high-level analog outputs suitable for use in a process control system. Output modules
accept high-level analog voltage signals from a process control system and provide current or voltage output to a field device.
Key 7B Features
• ±0.03% Accuracy (Typical) • Low Output Noise
• ±0.01% Linearity • –40°C to +85°C Operating Temperature
• 1500Vrms Transformer Isolation & • CSA C/US Certified
120Vrms Field-Side Protection (Class I, Division 2, Groups A, B, C, D)
The SCM5B, SCM7B, SensorLex® 8B, and SCM9B product lines include a complete selection of backpanels, DIN rail mounting options, cables, racks,
power supplies, and other accessory items.
Custom SCM5B, SCM7B, SensorLex® 8B, DSCA, and DSCT modules are available: consult factory for minimum quantity and pricing details on custom
input ranges, output ranges, bandwidth, and other key parameters.
SensorLex® 8B Isolated Analog Signal Conditioning Modules
Miniature Size, 2-Way Isolation, 5 Volt Supply Voltage, Instrument Class® Performance
19 family groups & 123 modules: an optimal solution for monitoring real-world process signals
and providing high-level signals for data acquisition
Developed in response to customer requests for a smaller isolated signal conditioner, SensorLex® 8B modules are housed in a miniature package
that is ideal for embedded and portable applications. All 8B modules are fully functional and provide Instrument Class® analog voltage output. They
interface to a wide variety of voltage, current, temperature, position, frequency, and strain measuring devices.
Din Rail, Head Mount Products - DSCA, DSCT, DSCL, DSCP, SCTP
Characteristic DSCA DSCT DSCL DSCP/SCTP
Mechanical Format DIN rail mount DIN rail mount DIN rail, component, panel DIN rail, head mount
Isolation: Voltage 1500Vrms 1500Vrms 500Vrms to 4000Vrms Non/1500Vrms/2300Vrms
Type Transformer 3-way Transformer 3-way Transformer/optical Transformer/optical 3-way
CMR 160dB 160dB 70-110dB Consult data sheet
NMR (60Hz) Rejection 85dB (3Hz modules) 85dB (3Hz XMTRs) 20dB/decade SW or dip-switch config
Bandwidth 3Hz to 3kHz 3Hz 5Hz to 750Hz SW or dip-switch config
Filter 6-pole 6-pole 2-pole SW or dip-switch config
Input Voltage Withstand 240Vrms 240Vrms N/A N/A
Input Signals (1) (5) 0/4-20mA (4)
Output Range to System 0-10VDC, ±10VDC, 0-1mA 4-20mA 0/4-20mA, V, & selectable SW or dip-switch config
4-20mA, 0-20mA
Output Range to Field 4-20mA, 0-20mA, N/A N/A N/A
± 20mA, ±10VDC,
0-10VDC
Gain/Offset Adjust ±5% ±10% ±10% on some models Software configurable
Accuracy 0.03% Typical 0.03% Typical 0.05% to 0.1% Typical 0.1% Typical
Output Control Always enabled Always enabled Always enabled Always enabled
Supply Voltage 15-30VDC (+24V Nom) 10.8-100VDC loop 24VDC loop 24VDC loop,
at 25-80mA at 4-20mA at 4-20mA or 24 to 230VDC/VAC
Dimensions 2.95” x 0.89” x 4.13” 2.95” x 0.89” x 4.13” Consult data sheet Consult data sheet
(h)(w)(d) 75mm x 22.5mm x 105mm 75mm x 22.5mm x 105mm
Interface 8-pos term block 6-pos term block Terminal block Terminal block
Customization yes yes no SW or dip-switch config
NOTES:
(1) V, I, RTD, TC, Potentiometer, Strain, True rms, 2-wire, Frequency (3) V, I, RTD, TC, Frequency, Digital I/O (5) V, I, RTD, TC, Potentiometer
(2) V, I, RTD, TC, Potentiometer, 2-wire (4) V, I, RTD, TC
SCM5B
Isolated SCM5B Analog Signal Conditioning Products
Features
• ±0.03% Accuracy (Typical)
• ±0.005% Linearity
• 1500Vrms Transformer Isolation &
240Vrms Field-side Protection
• ANSI/IEEE C37.90.1 Transient Protection
• 5V Power (30mA Typical)
• 4- to 6-Pole Low-Pass Filtering
• Up to 160dB CMR
• 95dB NMR at 60Hz, 90dB at 50Hz
• ±1µV°C Drift
• Output Noise as Low as 150µVrms
• –40°C to +85°C Operating Temperature
• CSA C/US Certified
(Class I, Division 2, Groups A, B, C, D)
SCM5B Modules • CE and ATEX Compliant
Dataforth Corporation offers cost-effective, isolated industrial signal • Manufactured per RoHS Directive 2002/95/EC
conditioning modules. The SCM5B analog modules are form, fit, and functional
equivalents to similar products from other manufacturers. The product line
includes a complete selection of backpanel options, interface cables, racks,
SCM5B
ANALOG VOLTAGE INPUT MODULES, NARROW BANDWIDTH (4Hz BW) Page 6 LINEARIZED 4-WIRE RTD INPUT MODULES (0 to +5V OUTPUT†, 4Hz BW)
MODEL INPUT RANGE OUTPUT RANGE † Page 14 OUTPUT
SCM5B30-01 ±10mV 1, 2 MODEL TYPE** INPUT RANGE RANGE†
SCM5B30-02 ±50mV 1, 2 SCM5B35-01 100Ω Pt –100°C to +100°C (–148°F to +212°F) 3, 4
SCM5B30-03 ±100mV 1, 2 SCM5B35-02 100Ω Pt 0°C to +100°C (+32°F to +212°F) 3, 4
SCM5B30-04 ±10mV 3, 4 SCM5B35-03 100Ω Pt 0°C to +200°C (+32°F to +392°F) 3, 4
SCM5B30-05 ±50mV 3, 4 SCM5B35-04 100Ω Pt 0°C to +600°C (+32°F to +1112°F) 3, 4
SCM5B30-06 ±100mV 3, 4 SCM5B35-05 100Ω Pt –100°C to +200°C (–148°F t o +392°F) 3, 4
SCM5B30-07 ±1V 1, 2 High Input Z SCM5B35C-01 10Ω Cu at 0°C 0°C to +120°C (+32°F to +248°F) 3, 4
SCM5B31-01 ±1V 1, 2 SCM5B35C-02 10Ω Cu at 25°C 0°C to +120°C (+32°F to +248°F) 3, 4
SCM5B31-02 ±5V 1, 2 SCM5B35C-03 10Ω Cu at 0°C 0°C to +160°C (+32°F to +320°F) 3, 4
SCM5B31-03 ±10V 1, 2 SCM5B35N-01 120Ω Ni 0°C to +300°C (+32°F to +572°F) 3, 4
SCM5B31-04 ±1V 3, 4
SCM5B31-05 ±5V 3, 4 POTENTIOMETER INPUT MODULES (4Hz BW) Page 16
SCM5B31-06 ±10V 3, 4 MODEL INPUT RANGE OUTPUT RANGE†
SCM5B31-07 ±20V 1, 2
SCM5B31-08 ±20V 3, 4 SCM5B36-01 0 to 100Ω 3, 4
SCM5B31-09 ±40V 1, 2 SCM5B36-02 0 to 500Ω 3, 4
SCM5B31-10 ±40V 3, 4 SCM5B36-03 0 to 1kΩ 3, 4
SCM5B36-04 0 to 10kΩ 3, 4
ANALOG CURRENT INPUT MODULES, 4Hz AND 1kHz BANDWIDTH Page 8
THERMOCOUPLE INPUT MODULES (0 to +5V OUTPUT †, 4Hz BW) Page 18
MODEL INPUT RANGE OUTPUT RANGE† BW
SCM5B32-01 4 to 20mA 3, 4 4Hz OUTPUT
SCM5B32-02 0 to 20mA 3, 4 4Hz MODEL TYPE‡ INPUT RANGE RANGE†
SCM5B392-11 4 to 20mA 0 to +5V 1kHz SCM5B37J J –100°C to +760°C (–148°F to +1400°F) 3, 4
SCM5B392-12 4 to 20mA ±5V 1kHz SCM5B37K K –100°C to +1350°C (–148°F to +2462°F) 3, 4
SCM5B392-13 4 to 20mA 0 to +10V 1kHz SCM5B37T T –100°C to +400°C (–148°F to +752°F) 3, 4
SCM5B392-14 4 to 20mA ±10V 1kHz SCM5B37E E 0°C to +900°C (+32°F to +1652°F) 3, 4
SCM5B37R R 0°C to +1750°C (+32°F to +3182°F) 3, 4
ISOLATED TRUE RMS INPUT MODULES Page 10 SCM5B37S S 0°C to +1750°C (+32°F to +3182°F) 3, 4
MODEL INPUT (rms) OUTPUT RANGE (dc)† SCM5B37B B 0°C to +1800°C (+32°F to +3272°F) 3, 4
SCM5B37C C +350°C to +1300°C (+662°F to +2372°F) 3, 4
SCM5B33-01 0-100mV 3, 4, 5, 6, 7 SCM5B37N N –100°C to +1300°C (–148°F to +2372°F) 3, 4
SCM5B33-02 0-1V 3, 4, 5, 6, 7
SCM5B33-03 0-10V 3, 4, 5, 6, 7 STRAIN GAGE INPUT MODULES (±5V OUTPUT †, 4Hz or 10kHz BW)
SCM5B33-04 0-150V 3, 4, 5, 6, 7 Page 20 OUTPUT
SCM5B33-05 0-300V 3, 4, 5, 6, 7 MODEL INPUT EXCITATION RANGE†
SCM5B33-06 0-1A 3, 4, 5, 6, 7
SCM5B33-07 0-5A 3, 4, 5, 6, 7 10KHz 4Hz
†
SCM5B38-01 -31 ±10mV Full Bridge Input, (3mV/V) +3.333V 1, 2
LINEARIZED 2- OR 3-WIRE RTD INPUT MODULES (0 to +5V OUTPUT , SCM5B38-02 -32 ±30mV Full Bridge Input, (3mV/V) +10.000V 1, 2
4Hz BW) Page 12 OUTPUT SCM5B38-03 -33 ±10mV Half Bridge Input, (3mV/V) +3.333V 1, 2
MODEL TYPE** INPUT RANGE RANGE† SCM5B38-04 -34 ±30mV Half Bridge Input, (3mV/V) +10.000V 1, 2
SCM5B34-01 100Ω Pt –100°C to +100°C (–148°F to +212°F) 3, 4 SCM5B38-05 -35 ±20mV Full Bridge Input, (2mV/V) +10.000V 1, 2
SCM5B34-02 100Ω Pt 0°C to +100°C (+32°F to +212°F) 3, 4 SCM5B38-06 -36 ±33.3mV Full Bridge Input, (10mV/V) +3.333V 1, 2
SCM5B34-03 100Ω Pt 0°C to +200°C (+32°F to +392°F) 3, 4 SCM5B38-07 -37 ±100mV Full Bridge Input, (10mV/V) +10.000V 1, 2
SCM5B34-04 100Ω Pt 0°C to +600°C (+32°F to +1112°F) 3, 4
SCM5B34-05 100Ω Pt –100°C to +200°C (–148°F to +392°F) 3, 4 ANALOG CURRENT OUTPUT MODULES, 400Hz AND 1kHz BANDWIDTH Page 24
SCM5B34C-01 10Ω Cu at 0°C 0°C to +120°C (+32°F to +248°F) 3, 4 MODEL INPUT RANGE OUTPUT RANGE BW
SCM5B34C-02 10Ω Cu at 25°C 0°C to +120°C (+32°F to +248°F) 3, 4 SCM5B39-01 0 to +5V 4 to 20mA 400Hz
SCM5B34C-03 10Ω Cu at 0° 0°C to +160°C (+32°F to +320°F) 3, 4 SCM5B39-02 ±5V 4 to 20mA 400Hz
SCM5B34N-01 120Ω Ni 0°C to +300°C (+32°F to +572°F) 3, 4 SCM5B39-03 0 to +5V 0 to 20mA 400Hz
SCM5B39-04 ±5V 0 to 20mA 400Hz
SCM5B39-05 0 to 20mA 0 to 20mA 400Hz
SCM5B39-07 ±10V ±20mA 275Hz
SCM5B392-01 0 to +5V 4 to 20mA 1kHz
SCM5B392-02 ±5V 4 to 20mA 1kHz
SCM5B392-03 0 to +10V 4 to 20mA 1kHz
SCM5B392-04 ±10V 4 to 20mA 1kHz
SCM5B
ACCESSORIES Starts on Page 48 NOTES:
†
MODEL DESCRIPTION OUTPUT RANGES AVAILABLE
SCMPB01 Non-multiplexed,16-channel backpanel. Output Range Part No. Suffix Example
SCMPB01-1 Non-multiplexed, 16-channel backpanel, no CJC.
SCMPB01-2 SCMPB01 with DIN rail mounting option. 1. –5V to +5V NONE SCM5B30-01
SCMPB01-3 SCMPB01-1 with DIN rail mounting option. 2. –10V to +10V D SCM5B30-01D
SCMPB02 Multiplexed, 16-channel backpanel.
SCMPB02-1 Multiplexed, 16-channel backpanel, no CJC.
3. 0V to +5V NONE SCM5B30-04
SCMPB02-2 SCMPB02 with DIN rail mounting option. 4. 0V to +10V D SCM5B30-04D
SCMPB02-3 SCMPB02-1 with DIN rail mounting option. 5. 4 to 20mA C SCM5B33-01C
SCMPB03 Single channel backpanel. 6. 0 to 20mA E SCM5B33-01E
Mounting hardware not included. 7. 0 to 1mA B SCM5B33-01B
SCMPB03-2 SCMPB03 with DIN rail mounting hardware.
SCMPB04 Dual channel backpanel.
‡
Mounting hardware not included. THERMOCOUPLE ALLOY COMBINATIONS
SCMPB04-1 Dual channel backpanel, DIN rail mount, no CJC. Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
SCMPB04-2 SCMPB04 with DIN rail mounting hardware.
TYPE MATERIAL
SCMPB04-3 SCMPB04-1 with DIN rail mounting hardware.
SCMXBEFE Base element with snap foot. J Iron vs. Copper-Nickel
SCMXBE Base element without snap foot. K Nickel-Chromium vs. Nickel-Aluminum
SCMXSE Side element. T Copper vs. Copper-Nickel
SCMXVS Connection pins. E Nickel-Chromium vs. Copper-Nickel
SCMPB05 Non-multiplexed, 8-channel backpanel. R Platinum-13% Rhodium vs. Platinum
SCMPB05-1 Non-multiplexed, 8-channel backpanel, no CJC. S Platinum-10% Rhodium vs. Platinum
SCMPB05-2 SCMPB05 with DIN rail mounting option. B Platinum-30% Rhodium vs.Platinum-6%Rhodium
SCMPB05-3 SCMPB05-1 with DIN rail mounting option. C Tungsten-5% Rhenium vs. Tungsten-26% Rhenium
SCMPB06 Multiplexed, 8-channel backpanel. N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4%
SCMPB06-1 Multiplexed, 8-channel backpanel, no CJC. Silicon-0.1% Magnesium
SCMPB06-2 SCMPB06 with DIN rail mounting option.
SCMPB06-3 SCMPB06-1 with DIN rail mounting option. **RTD STANDARDS
SCMPB07 8-channel high-density backpanel. TYPE ALPHA COEFFICIENT DIN JIS IEC
SCMPB07-1 SCMPB07, no CJC.
SCMPB07-2 SCMPB07, DIN rail mount. 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
SCMPB07-3 SCMPB07, no CJC, DIN rail mount. 120Ω Ni 0.00672
SCMXEV Single channel SCM5B evaluation board. 10Ω CU 0.004274
SCMXCA004-01,-02 System interface cable for both analog backpanels.
SCMXRK-002 19-inch metal rack for mounting analog backpanels.
SCMXIF Ribbon cable to screw terminal interface board.
SCMXIF-DIN Universal Interface Board.
SCMXCJC Encapsulated cold junction compensation circuit.
SCM5BPT Non-isolated signal pass thru module.
SCMXJP-003 Package of 10 jumpers.
SCMXFS-003 Package of 10, 4A fuses.
SCMXR1 Precision 20Ω resistor for SCM5B32 and SCM5B42.
SCM5B-PROTO Breadboard Kit.
SCMXRAIL1-XX DIN EN50022-35x7.5 (slotted steel), length -XX
in meters.
SCMXRAIL2-XX DIN EN50035-G32 (slotted steel), length -XX
in meters.
SCMXRAIL3-XX DIN EN50022-35x15 (slotted steel), length -XX in meters.
SCMXPRT-001 Power supply, 1A, 5VDC, 120VAC U.S.
SCMXPRT-001D SCMXPRT-001 with DIN rail mounting option.
SCMXPRE-001 Power supply, 1A, 5VDC, 220VAC European.
SCMXPRE-001D SCMXPRE-001 with DIN rail mounting option.
SCMXPRT-003 Power supply, 3A, 5VDC, 120VAC U.S.
SCMXPRE-003 Power supply, 3A, 5VDC, 220VAC European.
SCM5B30/31
Analog Voltage Input Modules, Narrow Bandwidth
Description
Each SCM5B30 and SCM5B31 voltage input module provides a single channel
of analog input which is filtered, isolated, amplified, and converted to a high-level
Features
analog voltage output (Figure 1). This voltage output is logic-switch controlled, • Accepts Millivolt and Voltage Level Signals
allowing these modules to share a common analog bus without the requirement • High-Level Voltage Outputs
of external multiplexers.
• 1500Vrms Transformer Isolation
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ±50V from Power Common, pin 16. This complete • ANSI/IEEE C37.90.1 Transient Protection
isolation means that no connection is required between I/O Common and Power • Input Protected to 240VAC Continuous
Common for proper operation of the output switch. If desired, the output switch • 160dB CMR
can be turned on continuously by simply connecting pin 22, the Read-Enable
pin, to I/O Common, pin 19. • 95dB NMR at 60Hz, 90dB at 50Hz
• ±0.03% Accuracy
Signal filtering is accomplished with a six-pole filter which provides 95dB
of normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter • ±0.005% Linearity
are on the field side of the isolation barrier, and the other four are on the • ±1µV/°C Drift
computer side.
• CSA C/US Certified, CE and ATEX Compliant
After the initial field-side filtering, the input signal is chopped by a proprietary • Mix and Match SCM5B Types on Backpanel
chopper circuit. Isolation is provided by transformer coupling, again using a
proprietary technique to suppress transmission of common mode spikes or
surges. The module is powered from +5VDC, ±5%.
A special input circuit on the SCM5B30 and SCM5B31 modules provides
protection against accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B30 SCM5B31 Model Input Range Output Range†
Input Range ±10mV to ±1V ±1V to ±40V SCM5B30-01 –10mV to +10mV 1, 2
Input Bias Current ±0.5nA ±0.05nA SCM5B30-02 –50mV to +50mV 1, 2
Input Resistance SCM5B30-03 –100mV to +100mV 1, 2
Normal 50MΩ 650kΩ (minimum) SCM5B30-04 –10mV to +10mV 3, 4
Power Off 40kΩ 650kΩ (minimum)
SCM5B30-05 –50mV to +50mV 3, 4
Overload 40kΩ 650kΩ (minimum)
Input Protection SCM5B30-06 –100mV to +100mV 3, 4
Continuous 240Vrms max * SCM5B30-07(3) –1V to +1V 1, 2
Transient ANSI/IEEE C37.90.1 *
SCM5B31-01 –1V to +1V 1, 2
CMV, Input to Output SCM5B31-02 –5V to +5V 1, 2
Continuous 1500Vrms max * SCM5B31-03 –10V to +10V 1, 2
Transient ANSI/IEEE C37.90.1 * SCM5B31-04 –1V to +1V 3, 4
CMR (50Hz or 60Hz) 160dB * SCM5B31-05 –5V to +5V 3, 4
NMR 95dB at 60Hz, 90dB at 50Hz *
SCM5B31-06 –10V to +10V 3, 4
Accuracy(1) ±0.03% Span * SCM5B31-07 –20V to +20V 1, 2
Linearity ±0.005% Span * SCM5B31-08 –20V to +20V 3, 4
Stability SCM5B31-09 –40V to +40V 1, 2
Input Offset ±1µV/°C ±20µV/°C
SCM5B31-10 –40V to +40V 3, 4
Output Offset ±20µV/°C *
Gain ±25ppm/°C ±50ppm/°C
Noise
†
Input, 0.1 to 10Hz 0.2µVrms 2µVrms Output Ranges Available
Output, 100kHz 200µVrms *
Bandwidth, –3dB 4Hz * Output Range Part No. Suffix Example
Response Time, 90% Span 0.2s *
1. –5V to +5V NONE SCM5B30-01
Output Range See Ordering Information * 2. –10V to +10V D SCM5B30-01D
Output Resistance 50Ω *
Output Protection Continuous Short to Ground *
3. 0V to +5V NONE SCM5B30-04
Output Selection Time 6µs at Cload = 0 to 2000pF * 4. 0V to +10V D SCM5B30-04D
(to ±1mV of VOUT)
Output Current Limit ±8mA *
Output Enable Control
Max Logic “0” +0.8V *
Min Logic “1” +2.4V *
Max Logic “1” +36V *
Input Current “0,1” 0.5µA *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 30mA *
Power Supply Sensitivity ±2µV/% RTI(2) ±200µV/% RTI(2)
Mechanical Dimensions 2.28" x 2.26" x 0.60" *
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD,EFT Performance B *
NOTES:
* Same specification as SCM5B30.
(1) Includes linearity, hysteresis and repeatability.
(2) RTI = Referenced to input.
(3) Same as SCM5B31-01 with 50MΩ input resistance.
SCM5B32
Analog Current Input Modules
Description
Each SCM5B32 current input module provides a single channel of analog input
which is filtered, isolated, amplified, and converted to a high-level analog voltage
Features
output (Figure 1). This voltage output is logic switch controlled, which allows • Accepts Milliamp Level Signals
these modules to share a common analog bus without the requirement of • High-Level Voltage Outputs
external multiplexers.
• 1500Vrms Transformer Isolation
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ±50V from Power Common, pin 16. This complete • ANSI/IEEE C37.90.1 Transient Protection
isolation means that no connection is required between I/O Common and • Input Protected to 240VAC Continuous
Power Common for proper operation of the output switch. If desired, the • 160dB CMR
output switch can be turned on continuously by simply connecting pin 22, the
Read-Enable pin, to I/O Common, pin 19. • 95dB NMR at 60Hz, 90dB at 50Hz
• ±0.03% Accuracy
A precision 20Ω current conversion resistor is supplied with the SCM5B32
module. Sockets are provided on the SCMPB01/02/03/04/05/06/07 backpanels • ±0.005% Linearity
to allow installation of this resistor. Extra resistors are available under part • CSA C/US Certified, CE and ATEX Compliant
number SCMXR1.
• Mix and Match SCM5B Types on Backpanel
Signal filtering is accomplished with a six-pole filter which provides 95dB of
normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter
are on the field side of the isolation barrier, and the other four are on the
computer side.
After the initial field-side filtering, the input signal is chopped by a proprietary
chopper circuit. Isolation is provided by transformer coupling, again using a
proprietary technique to suppress transmission of common mode spikes or
surges. The module is powered from +5VDC, ±5%.
A special input circuit on the SCM5B32 modules provides protection against
accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B32 Model Input Range Output Range†
Input Range 0mA to 20mA or 4mA to 20mA SCM5B32-01 4mA to 20mA 3, 4
Input Resistor
Value 20.00Ω SCM5B32-02 0mA to 20mA 3, 4
Accuracy ±0.1%
Refer to SCM5B392 specifications, p. 27, for additional current input models.
Stability ±10ppm/°C
Input Protection
†
Continuous 240Vrms max Output Ranges Available
Transient ANSI/IEEE C37.90.1
Output Range Part No. Suffix Example
CMV, Input to Output
Continuous 1500Vrms max 3. 0V to +5V NONE SCM5B32-01
Transient ANSI/IEEE C37.90.1 4. 0V to +10V D SCM5B32-01D
CMR (50Hz or 60Hz) 160dB
NMR 95dB at 60Hz, 90dB at 50Hz
SCM5B33
Isolated True RMS Input Modules
Description
Each SCM5B33 True RMS input module provides a single channel of AC input
which is converted to its True RMS DC value, filtered, isolated, amplified, and
Features
converted to a standard process voltage or current output (Figure 1). • Interfaces RMS Voltage (0 – 300V) or RMS
Current (0 – 5A)
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ±50V from Power Common, pin 16. This complete • Designed for Standard Operation with
isolation means that no connection is required between I/O Common and Power Frequencies of 45Hz to 1000Hz
Common for proper operation of the output switch. If desired, the output switch (Extended Range to 20kHz)
can be turned on continuously by simply connecting pin 22, the Read-Enable • Compatible with Standard Current and
pin, to I/O Common, pin 19. Potential Transformers
The field voltage or current input signal is processed through a pre-amplifier and • Industry Standard Output of either 0-1mA,
RMS converter on the field side of the isolation barrier. The converted DC signal 0-20mA, 4-20mA, 0-5V or 0-10VDC
is then chopped by a proprietary chopper circuit and transferred across the • ±0.25% Factory Calibrated Accuracy
transformer isolation barrier, suppressing transmission of common mode (Accuracy Class 0.2)
spikes and surges. The computer side circuitry reconstructs, filters and converts
the signal to industry standard outputs. Modules are powered from • 1500Vrms Continuous Transformer Isolation
+5VDC, ±5%. • Input Overload Protected to 480V Max
(Peak AC & DC) or 10A RMS Continuous
For current output models, in addition to the 5VDC module power, an external
loop supply of 4.2V to 26V is required. The loop supply connection, with series • ANSI/IEEE C37.90.1 Transient Protection
load, is between Pin 20 (+) and Pin 19 (-). • CSA C/US Certified and CE Compliant
Due to circuit limitations, SCM5B33-04x and -05x are not ATEX compliant. • ATEX Compliant (all models except
SCM5B33-04x, -05x)
• Mix and Match SCM5B Types on Backpanel
Isolation Barrier
SCM5B
Module SCM5B33 Model Input (rms)† Output (DC)†
Input SCM5B33-01 0mV to 100mV 0V to 5V
Signal Range 100mV to 300Vrms, 0 to 5Arms SCM5B33-02 0V to 1V 0V to 5V
Standard Frequency Range 45Hz to 1000Hz
Extended Frequency Range 1kHz to 20kHz SCM5B33-03 0V to 10V 0V to 5V
Impedance 1 MΩ shunted by 100pF (-01 thru -05), SCM5B33-04 0V to 150V 0V to 5V
0.10Ω (-06), 0.025Ω (-07) SCM5B33-05 0V to 300V 0V to 5V
Coupling AC SCM5B33-06 0A to 1A 0V to 5V
Protection(1)
SCM5B33-07 0A to 5A 0V to 5V
Continuous (-01 thru -05) 350Vrms
Continuous (-06 thru -07) 10Arms
Transient (-01 thru -05) ANSI/IEEE C37.90.1 SCM5B33-01B 0mV to 100mV 0mA to 1mA
Transient (-06 thru -07) See note 2 SCM5B33-02B 0V to 1V 0mA to 1mA
SCM5B33-03B 0V to 10V 0mA to 1mA
Output
Signal Range 0-5V or 0-10V or 0-1mA or 0-20mA or 4-20mA SCM5B33-04B 0V to 150V 0mA to 1mA
Current Limit 1.4mA (0-1mA models), 30mA (0/4-20mA models), SCM5B33-05B 0V to 300V 0mA to 1mA
8mA (0-5, 0-10V models) SCM5B33-06B 0A to 1A 0mA to 1mA
Voltage Limit ±18V (0-5, 0-10V models) SCM5B33-07B 0A to 5A 0mA to 1mA
Resistance 50Ω (0-5, 0-10V models)
Protection Continuous Short to Ground
Ripple and Noise (100kHz) 0.025% Span rms SCM5B33-01C 0mV to 100mV 4mA to 20mA
SCM5B33-02C 0V to 1V 4mA to 20mA
Accuracy (10-100% Span)(3)(4)
Sinusoid SCM5B33-03C 0V to 10V 4mA to 20mA
50/60 Hz ±0.25% Span SCM5B33-04C 0V to 150V 4mA to 20mA
45Hz to 1kHz ±0.25% Reading Additional Error SCM5B33-05C 0V to 300V 4mA to 20mA
1kHz to 20kHz ±0.75% Reading Additional Error SCM5B33-06C 0A to 1A 4mA to 20mA
Non-Sinusoid
SCM5B33-07C 0A to 5A 4mA to 20mA
Crest Factor = 1 to 2 ±0.05% Reading Additional Error
Crest Factor = 2 to 3 ±0.15% Reading Additional Error
Crest Factor = 3 to 4 ±0.30% Reading Additional Error SCM5B33-01D 0mV to 100mV 0V to 10V
Crest Factor = 4 to 5 ±0.40% Reading Additional Error SCM5B33-02D 0V to 1V 0V to 10V
Vs. Temperature ±100ppm/°C SCM5B33-03D 0V to 10V 0V to 10V
Isolation (Common Mode) SCM5B33-04D 0V to 150V 0V to 10V
Input to Output, Input to Power SCM5B33-05D 0V to 300V 0V to 10V
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
SCM5B33-06D 0A to 1A 0V to 10V
Output to Power SCM5B33-07D 0A to 5A 0V to 10V
Continuous 50VDC max
Rejection (50-60Hz Common Mode) 100dB SCM5B33-01E 0mV to 100mV 0mA to 20mA
SCM5B33-02E 0V to 1V 0mA to 20mA
Response Time (0 to 99%) <400ms
SCM5B33-03E 0V to 10V 0mA to 20mA
Output Enable Control SCM5B33-04E 0V to 150V 0mA to 20mA
Selection Time 6.0µS at CLOAD = 0 to 2000pF
Max Logic “0” +0.8V SCM5B33-05E 0V to 300V 0mA to 20mA
Min/Max Logic “1” +2.4V/+36V SCM5B33-06E 0A to 1A 0mA to 20mA
Current “0,1” 0.5µA SCM5B33-07E 0A to 5A 0mA to 20mA
Loop Voltage +4.2VDC min, +26VDC max, –40°C to +85°C
†
Load Resistance (maximum) (Loop Voltage - 4.2) / (Loop Current) Modules can be ordered with other input/output ranges. Consult
factory for ordering details and specifications.
Supply Voltage +5VDC ±5%
Current 120mA †
Output Ranges Available
Sensitivity ±200ppm/%
Environmental Output Range Part No. Suffix Example
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C 3. 0V to +5V NONE SCM5B33-01
Relative Humidity 0 to 95% Noncondensing 4. 0V to +10V D SCM5B33-01D
HazLoc ATEX All models except SCM5B33-04x, -05x 5. 4mA to 20mA C SCM5B33-01C
Emissions EN61000-6-4 ISM, Group 1 6. 0mA to 20mA E SCM5B33-01E
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
7. 0mA to 1mA B SCM5B33-01B
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Dimensions (h)(w)(d) 2.28" x 2.26" x 0.60" (58mm x 57mm x 15mm)
NOTES:
(1) SCM5B33 and SCMPB01, 02, 03, 04, 05, 06, 07, XEV rating only. Backpanels obtained from other sources may have lower ratings. (4) For 0-10% Span measurements, add 0.25% accuracy error
(2) For 1 to 25 seconds the max allowable transient current rating is √ 2500 / (event time). For less than 1 second, (-02 through -07) or 1.00% accuracy error (-01). Accuracy includes
ANSI/IEEE C37.90.1 applies with a 0.05Ω load. For greater than 25 seconds, the 10A rms continuous rating applies. linearity, hysteresis and repeatability but not source or external
(3) At standard 60Hz factory calibration. Consult factory for calibration at other frequencies. shunt inaccuracy (if used).
SCM5B34
Linearized 2- or 3-Wire RTD Input Modules
Description
Each SCM5B34 RTD input module provides a single channel of RTD input
which is filtered, isolated, amplified, linearized, and converted to a high-level Features
analog voltage output (Figure 1). This voltage output is logic switch controlled, • Interfaces to 100Ω Platinum, 10Ω Copper,
which allows these modules to share a common analog bus without the or 120Ω Nickel RTDs
requirement of external multiplexers.
• Linearizes RTD Signal
The SCM5B modules are designed with a completely isolated computer side • High-Level Voltage Outputs
circuit which can be floated to ±50V from Power Common, pin 16. This complete
isolation means that no connection is required between I/O Common and Power • 1500Vrms Transformer Isolation
Common for proper operation of the output switch. If desired, the output switch • ANSI/IEEE C37.90.1 Transient Protection
can be turned on continuously by simply connecting pin 22, the Read-Enable
• Input Protected to 240VAC Continuous
pin, to I/O Common, pin 19.
• 160dB CMR
RTD excitation is provided from the module by two matched current sources.
When using a three-wire RTD, this method allows an equal current to flow in • 95dB NMR at 60Hz, 90dB at 50Hz
each RTD lead, which cancels the effects of lead resistances. The excitation • CSA C/US Certified, CE and ATEX Compliant
currents are very small (0.25mA for 100Ω Pt and 120Ω Ni, and 1.0mA for 10Ω • Mix and Match SCM5B Types on Backpanel
Cu) which minimizes self-heating of the RTD.
Signal filtering is accomplished with a six-pole filter which provides 95dB of
normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter are on
the field side of the isolation barrier, and the other four are on the computer side.
After the initial field-side filtering, the input signal is chopped by a proprietary
chopper circuit. Isolation is provided by transformer coupling, again using a
proprietary technique to suppress transmission of common mode spikes or
surges. The module is powered from +5VDC, ±5%.
A special input circuit on the SCM5B34 modules provides protection against
accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B34 Model Input Range Output Range† Accuracy(2)
Input Range Limits –200°C to +850°C (100Ω Pt) 100Ω Pt **
–80°C to +320°C (120Ω Ni) SCM5B34-01 –100°C t o +100°C 3, 4 ±0.12°C
–100°C to +260°C (10Ω Cu) (–148°F t o +212°F)
Input Resistance
Normal 50MΩ SCM5B34-02 0°C t o +100°C 3, 4 ±0.06°C
Power Off 40kΩ (+32°F t o +212°F)
Overload 40kΩ SCM5B34-03 0°C t o +200°C 3, 4 ±0.12°C
Input Protection (+32°F t o +392°F)
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1 SCM5B34-04 0°C t o +600°C 3, 4 ±0.36°C
(+32°F t o +1112°F)
Sensor Excitation Current
100Ω Pt, 120Ω Ni 0.25mA SCM5B34-05 –100°C t o +200°C 3, 4 ±0.18°C
10Ω Cu 1.0mA (–148°F t o +392°F)
Lead Resistance Effect 10Ω Cu **
100Ω Pt, 120Ω Ni ±0.02°C/Ω(1) SCM5B34C-01 0°C t o +120°C 3, 4 ±0.23°C
10Ω Cu ±0.2°C/Ω(1) (10Ω at 0°C)
CMV, Input to Output (+32°F t o +248°F)
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1 SCM5B34C-02 0°C t o +120°C 3, 4 ±0.23°C
CMR (50 or 60Hz) 160dB (10Ω at 25°C)
NMR 95dB at 60Hz, 90dB at 50Hz (+32°F t o +248°F)
Accuracy See Ordering Information SCM5B34C-03 0°C t o +160°C 3, 4 ±0.32°C
Conformity Error(3) ±0.025% Span (10Ω at 0°C)
Stability (+32°F t o +320°F)
Input Offset ±0.01°C/°C
Output Offset ±20µV/°C 120Ω Ni **
Gain ±35ppm of Reading/°C SCM5B34N-01 0°C t o +300°C 3, 4 ±0.23°C
Noise (+32°F t o +572°F)
Input, 0.1 to 10Hz 0.2µVrms
Output, 100kHz 200µVrms
Bandwidth, –3dB 4Hz **RTD Standards
Response Time, 90% Span 0.2s
Output Range See Ordering Information Type Alpha Coefficient DIN JIS IEC
Output Resistance 50Ω 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
Output Protection Continuous Short to Ground 120Ω Ni 0.00672
Output Selection Time 6µs at Cload = 0 to 2000pF 10Ω Cu 0.004274
(to ±1mV of VOUT)
Output Current Limit +8mA
†
Output Enable Control Output Ranges Available
Max Logic “0” +0.8V
Min Logic “1” +2.4V Output Range Part No. Suffix Example
Max Logic “1” +36V
Input Current “0,1” 0.5µA 3. 0V to +5V NONE SCM5B34-01
4. 0V to +10V D SCM5B34-01D
Open Input Response Downscale
Open Input Detection Time 3s
Power Supply Voltage +5VDC ±5%
Power Supply Current 30mA
Power Supply Sensitivity
100Ω Pt, 120Ω Ni 0.2°C/V
10Ω Cu 0.5°C/V
SCM5B35
Linearized 4-Wire RTD Input Modules
Description
In RTD temperature measurement applications requiring a very high level of
accuracy, the SCM5B35 4-Wire RTD input module offers a significant advan- Features
tage over 3-wire measurement techniques (Figure 1). The SCM5B35 measures • Interfaces to 100Ω Platinum, 10Ω Copper,
only the voltage dropped across the RTD and almost completely ignores or 120Ω Nickel RTDs
the resistance or length of the RTD lead wires. The SCM5B34 3-Wire RTD
• True 4-Wire Input
module provides lead resistance compensation, but requires equal lead resis-
tances, while the SCM5B35 does not require matched lead resistances. • Linearizes RTD Signal
• High-Level Voltage Output
Each SCM5B35 RTD input module provides a single channel of RTD input
which is filtered, isolated, amplified, linearized, and converted to a high-level • 1500Vrms Transformer Isolation
analog voltage output. This voltage output is logic switch controlled, which • ANSI/IEEE C37.90.1 Transient Protection
allows these modules to share a common analog bus without the requirement • Input Protected to 240VAC Continuous
of external multiplexers.
• 160dB CMR
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ±50V from Power Common, pin 16. This complete • 95dB NMR at 60Hz, 90dB at 50Hz
isolation means that no connection is required between I/O Common and Power • CSA C/US Certified, CE and ATEX Compliant
Common for proper operation of the output switch. If desired, the output switch • Mix and Match SCM5B Types on Backpanel
can be turned on continuously by simply connecting pin 22, the Read-Enable
pin, to I/O Common, pin 19.
RTD excitation is provided from the module by a precision current source. The
excitation current is available on two leads which are separate from the two the field side of the isolation barrier, and the other four are on the computer side.
input signal measuring leads. The excitation current does not flow in the input After the initial field-side filtering, the input signal is chopped by a proprietary
signal leads, which allows RTD measurement to be totally independent of chopper circuit. Isolation is provided by transformer coupling, again using a
lead resistance. The excitation current is very small (0.25mA for 100Ω Pt and proprietary technique to suppress transmission of common mode spikes or
120Ω Ni and 1.0 mA for 10Ω Cu) which minimizes self-heating of the RTD. surges. The module is powered from +5VDC, ±5%.
Signal filtering is accomplished with a six-pole filter which provides 95dB of A special input circuit on the SCM5B35 modules provides protection against
normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter are on accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B35 Model Input Range Output Range† Accuracy(2)
Input Range Limits –200°C to +850°C (100Ω Pt) 100Ω Pt **
–80°C to +320°C (120Ω Ni) SCM5B35-01 –100°C t o +100°C 3, 4 ±0.12°C
–100°C to +260°C (10Ω Cu) (–148°F t o +212°F)
Input Resistance
Normal 50MΩ SCM5B35-02 0°C t o +100°C 3, 4 ±0.06°C
Power Off 40kΩ (+32°F t o +212°F)
Overload 40kΩ SCM5B35-03 0°C t o +200°C 3, 4 ±0.12°C
Input Protection (+32°F t o +392°F)
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1 SCM5B35-04 0°C t o +600°C 3, 4 ±0.36°C
Sensor Excitation Current (+32°F t o +1112°F)
100Ω Pt, 120Ω Ni 0.25mA SCM5B35-05 -100°C t o +200°C 3, 4 ±0.18°C
10Ω Cu 1.0mA (-148°F t o +392°F)
Lead Resistance Effect
100Ω Pt, 120Ω Ni ±0.0005°C/Ω(1) 10Ω Cu **
10Ω Cu ±0.005°C/Ω(1) SCM5B35C-01 0°C t o +120°C 3, 4 ±0.23°C
CMV, Input to Output (10Ω a t 0°C)
Continuous 1500Vrms max (+32°F t o +248°F)
Transient ANSI/IEEE C37.90.1
CMR (50Hz or 60Hz) 160dB SCM5B35C-02 0°C t o +120°C 3, 4 ±0.23°C
NMR 95dB at 60Hz, 90dB at 50Hz (10Ω a t 25°C)
Accuracy See Ordering Information
(+32°F t o +248°F)
Conformity Error(3) ±0.025% Span SCM5B35C-03 0°C t o +160°C 3, 4 ±0.32°C
Stability (10Ω a t 0°C)
Input Offset ±0.01°C/°C (+32°F t o +320°F)
Output Offset ± 20µV/°C
Gain ±35ppm of Reading/°C 120Ω Ni **
Noise SCM5B35N-01 0°C t o +300°C 3, 4 ±0.23°C
Input, 0.1 to 10Hz 0.2µVrms (+32°F t o +572°F)
Output, 100kHz 200µVrms
Bandwidth, –3dB 4Hz
Response Time, 90% Span 0.2s
Output Range See Ordering Information **RTD Standards
Output Resistance 50Ω
Output Protection Continuous Short to Ground Type Alpha Coefficient DIN JIS IEC
Output Selection Time 6µs at Cload = 0 to 2000pF
(to ±1mV of VOUT) 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
Output Current Limit +8mA 120Ω Ni 0.00672
Output Enable Control 10Ω Cu 0.004274
Max Logic “0” +0.8V
Min Logic “1” +2.4V
Max Logic “1” +36V †
Input Current “0,1” 0.5µA Output Ranges Available
Open Input Response Output Range Part No. Suffix Example
Lead 1,4 Downscale
Lead 2,3 Non-deterministic 3. 0V to +5V NONE SCM5B35-01
Open Input Detection Time 3s
4. 0V to +10V D SCM5B35-01D
Power Supply Voltage +5VDC ±5%
Power Supply Current 30mA
Power Supply Sensitivity
100Ω Pt, 120Ω Ni ±0.2°C/V
10Ω Cu ±0.5°C/V
Mechanical Dimensions 2.28" x 2.26" x 0.60"
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) "Ω" refers to the resistance in one lead.
(2) Includes conformity, hysteresis and repeatability.
(3) Conformity error is ±0.05% Span for SCM5B35N-01.
SCM5B36
Potentiometer Input Modules
Description
Each SCM5B36 Potentiometer input module provides a single channel of
potentiometer input which is filtered, isolated, amplified, and converted to a
Features
high-level analog voltage output (Figure 1). This voltage output is logic switch • Interfaces to Potentiometers up to 10,000Ω
controlled, which allows these modules to share a common analog bus without • High-Level Voltage Output
the requirement of external multiplexers.
• 1500Vrms Transformer Isolation
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ± 50V from Power Common, pin 16. This complete • ANSI/IEEE C37.90.1 Transient Protection
isolation means that no connection is required between I/O Common and Power • Input Protected to 240VAC Continuous
Common for proper operation of the output switch. If desired, the output switch • 160dB CMR
can be turned on continuously by simply connecting pin 22, the Read-Enable
pin, to I/O Common, pin 19. • 95dB NMR at 60Hz, 90dB at 50Hz
• ±0.03% Accuracy
Excitation for the potentiometer is provided from the module by two matched
current sources. When using a three-wire potentiometer, this method allows • ±0.005% Linearity
cancellation of the effects of lead resistances. The excitation currents are very • CSA C/US Certified, CE and ATEX Compliant
small (less than 1.0mA) which minimizes self-heating of the potentiometer.
• Mix and Match SCM5B Types on Backpanel
Signal filtering is accomplished with a six-pole filter which provides 95dB of
normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter are on
the field side of the isolation barrier, and the other four are in the output stage.
After the initial field-side filtering, the input signal is chopped by a proprietary
chopper circuit. Isolation is provided by transformer coupling, again using a
proprietary technique to suppress transmission of common mode spikes or
surges. The module is powered from +5VDC, ±5%.
A special input circuit on the SCM5B36 module provides protection against
accidental connection of power-line voltages up to 240VAC.
Isolation Barrier
SCM5B
Module SCM5B36 Model Input Range Output Range†
Input Range 0 to 10kΩ SCM5B36-01 0 to 100Ω 3, 4
Input Resistance
Normal 50MΩ SCM5B36-02 0 to 500Ω 3, 4
Power Off 40kΩ SCM5B36-03 0 to 1kΩ 3, 4
Overload 40kΩ SCM5B36-04 0 to 10kΩ 3, 4
Input Protection
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1 †
Output Ranges Available
Sensor Excitation Current 0.25mA; 100Ω, 500Ω, 1kΩ Sensor
0.10mA; 10kΩ Sensor Output Range Part No. Suffix Example
Lead Resistance Effect ±0.01Ω/Ω; 100Ω, 500Ω, 1kΩ Sensor
±0.02Ω/Ω; 10kΩ Sensor 3. 0V to +5V NONE SCM5B36-01
CMV, Input to Output 4. 0V to +10V D SCM5B36-01D
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 160dB
NMR 95dB at 60Hz, 90dB at 50Hz
Accuracy(1) ±0.03% Span
Linearity ±0.005% Span
Stability
Input Offset ±0.004Ω/°C; 100Ω, 500Ω, 1kΩ sensor
±0.010Ω/°C; 10kΩ sensor
Output Offset ±20µV/°C
Gain ±50ppm of Reading/°C
Noise
Input, 0.1 to 10Hz 0.2µVrms
Output, 100kHz 200µVrms
Bandwidth, –3dB 4Hz
Response Time, 90% Span 0.2s
Output Range See Ordering Information
Output Resistance 50Ω
Output Protection Continuous Short to Ground
Output Selection Time 6µs at Cload = 0 to 2000pF
(to ±1mV of VOUT)
Output Current Limit +8mA
Output Enable Control
Max Logic “0” +0.8V
Min Logic “1” +2.4V
Max Logic “1” +36V
Input Current “0,1” 0.5µA
Open Input Response Downscale
Open Input Detection Time 3s
Power Supply Voltage +5VDC ±5%
Power Supply Current 30mA
Power Supply Sensitivity ±2µV/% RTI(2)
Mechanical Dimensions 2.28" x 2.26" x 0.60"
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability.
(2) RTI = Referenced to input.
SCM5B37
Non-Linearized Thermocouple Input Modules
Description
Each SCM5B37 non-linearized thermocouple input module provides a single
channel of thermocouple input which is filtered, isolated, amplified, and Features
converted to a high-level analog voltage output (Figure 1). This voltage output • Interfaces to Types J, K, T, E, R, S, C, N and
is logic-switch controlled, allowing these modules to share a common analog B Thermocouples
bus without the requirement of external multiplexers.
• High-Level Voltage Output
The SCM5B modules are designed with a completely isolated computer side • 1500Vrms Transformer Isolation
circuit which can be floated to ±50V from Power Common, pin 16. This complete
isolation means that no connection is required between I/O Common and Power • ANSI/IEEE C37.90.1 Transient Protection
Common for proper operation of the output switch. If desired, the output switch • Input Protected to 240VAC Continuous
can be turned on continuously by simply connecting pin 22, the Read-Enable
• 160dB CMR
pin, to I/O Common, pin 19.
• 95dB NMR at 60Hz, 90dB at 50Hz
The SCM5B37 can interface to nine industry standard thermocouple types:
J, K, T, E, R, S, C, N, and B. Its corresponding output signal operates over a 0V • ±0.03% Accuracy
to +5V range. Each module is cold-junction compensated to correct for parasitic • ±0.005% Linearity
thermocouples formed by the thermocouple wire and screw terminals on the • ±1µV/°C Drift
mounting backpanel. Upscale open thermocouple detect is provided by an
internal pull-up resistor. Downscale indication can be implemented by installing • CSA C/US Certified, CE and ATEX Compliant
an external 47MΩ resistor, ±20% tolerance, between screw terminals 1 and 3 • Mix and Match SCM5B Types on Backpanel
on the SCMPB01/02/03/04/05/06/07 backpanels.
Signal filtering is accomplished with a six-pole filter which provides 95dB of
normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter are on
the field side of the isolation barrier, and the other four are on the computer side.
After the initial field-side filtering, the input signal is chopped by a proprietary
chopper circuit. Isolation is provided by transformer coupling, again using a
proprietary technique to suppress transmission of common mode spikes or A special input circuit on the SCM5B37 modules provides protection against
surges. The module is powered from +5VDC, ±5%. accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B37 TC Output
Model Type‡ Input Range Range† Accuracy(1)
Input Range –0.1V to +0.5V
Input Bias Current –25nA SCM5B37J J –100°C to +760°C 3, 4 ±0.03% ±0.26°C
Input Resistance (–148°F to +1400°F)
Normal 50MΩ
Power Off 40kΩ SCM5B37K K –100°C to +1350°C 3, 4 ±0.03% ±0.44°C
Overload 40kΩ (–148°F to +2462°F)
Input Protection
Continuous 240Vrms max SCM5B37T T –100°C to +400°C 3, 4 ±0.03% ±0.15°C
Transient ANSI/IEEE C37.90.1 (–148°F to +752°F)
CMV, Input to Output
SCM5B37E E 0°C to +900°C 3, 4 ±0.03% ±0.27°C
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1 (+32°F to +1652°F)
CMR (50Hz or 60Hz) 160dB
NMR 95dB at 60Hz, 90dB at 50Hz SCM5B37R R 0°C to +1750°C 3, 4 ±0.03% ±0.53°C
(+32°F to +3182°F)
Accuracy See Ordering Information
Linearity ±0.005% Span SCM5B37S S 0°C to +1750°C 3, 4 ±0.03% ±0.53°C
Stability (+32°F to +3182°F)
Input Offset ±1µV/°C(2)
Output Offset ±20µV/°C SCM5B37B B 0°C to +1800°C 3, 4 ±0.03% ±0.54°C
Gain ±25ppm/°C
(+32°F to +3272°F)
Noise
Input, 0.1 to 10Hz 0.2µVrms SCM5B37C C +350°C to +1300°C 3, 4 ±0.03% ±0.29°C
Output, 100kHz 200µVrms
Bandwidth, –3dB 4Hz (+662°F to +2372°F)
Response Time, 90% Span 0.2s
SCM5B37N N –100°C to +1300°C 3, 4 ±0.03% ±0.42°C
Output Range See Ordering Information (–148°F to +2372°F)
Output Resistance 50Ω
Output Protection Continuous Short to Ground
Output Selection Time 6µs at Cload = 0 to 2000pF ‡
Thermocouple Alloy Combinations
(to ±1mV of VOUT) Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
Output Current Limit +8mA
Output Enable Control
Max Logic “0” +0.8V Type Material
Min Logic “1” +2.4V J Iron vs. Copper-Nickel
Max Logic “1” +36V K Nickel-Chromium vs. Nickel-Aluminum
Input Current “0,1” 0.5µA T Copper vs. Copper-Nickel
Open Input Response Upscale E Nickel-Chromium vs. Copper-Nickel
Open Input Detection Time <10s R Platinum-13% Rhodium vs. Platinum
Cold Junction Compensation S Platinum-10% Rhodium vs. Platinum
Accuracy, 25°C ±0.25°C B Platinum-30% Rhodium vs. Platinum-6% Rhodium
Accuracy, +5°C to +45°C ±0.5°C C Tungsten-5% Rhenium vs. Tungsten-26% Rhenium
Accuracy, –40°C to +85°C ±1.25°C N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4%
Power Supply Voltage +5VDC ±5% Silicon- 0.1% Magnesium
Power Supply Current 30mA
Power Supply Sensitivity ±2µV/% RTI(3)
†
Mechanical Dimensions 2.28" x 2.26" x 0.60" Output Ranges Available
(h)(w)(d) (58mm x 57mm x 15mm)
Output Range Part No. Suffix Example
Environmental
Operating Temperature Range –40°C to +85°C 3. 0V to +5V NONE SCM5B37J
Storage Temperature Range –40°C to +85°C 4. 0V to +10V D SCM5B37JD
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability. Does not include CJC accuracy.
(2)This is equivalent to °C as follows: Type J 0.020 °C/°C, Types K, T 0.025°C/°C,
Type E 0.016°C/°C, Types R, S 0.168°C/°C, Type N 0.037°C/°C, Type C, 0.072°C/°C.
(3) RTI = Referenced to input.
SCM5B38
Strain Gage Input Modules, Narrow Bandwidth
Description
Each SCM5B38 Strain Gage input module provides a single channel of strain
gage input which is filtered, isolated, amplified, and converted to a high-level Features
analog voltage output (Figure 1). This voltage output is logic switch controlled, • Interfaces to 100Ω Thru 10kΩ, Full-Bridge,
which allows these modules to share a common analog bus without the Half-Bridge, or Quarter-Bridge Strain Gages
requirement of external multiplexers.
• High-Level Voltage Output
The SCM5B modules are designed with a completely isolated computer side • 1500Vrms Transformer Isolation
circuit which can be floated to ±50V from Power Common, pin 16. This
complete isolation means that no connection is required between I/O • ANSI/IEEE C37.90.1 Transient Protection
Common and Power Common for proper operation of the output switch. If • Input Protected to 240VAC Continuous
desired, the output switch can be turned on continuously by simply connecting
• Fully Isolated Excitation Supply
pin 22, the Read-Enable pin, to I/O Common, pin 19.
• 160dB CMR
The SCM5B38 can interface to full-bridge or half-bridge transducers with a
nominal resistance of 100Ω to 10kΩ. A matched pair of bridge-completion • 95dB NMR at 60Hz, 90dB at 50Hz
resistors (to ±1mV at +10V excitation) allows use of low cost half-bridge or • 4Hz Signal Bandwidth
quarter-bridge transducers (Figures 2, 3, 4). • ±0.03% Accuracy
Strain gage excitation is provided from the module by a very stable 10V • ±0.01% Linearity
or 3.333V source. The excitation supply is fully isolated, allowing the amplifier
inputs to operate over the full range of the excitation voltage. This feature offers • ±1µV/°C Drift
significant flexibility in real world applications. Full scale sensitivities of 2mV/V, • CSA C/US Certified, CE and ATEX Compliant
3mV/V or 10mV/V are offered as standard. With 10V excitation, this results in • Mix and Match SCM5B Types on Backpanel
±20mV, ±30mV or ±100mV full scale input range producing ± 5V full scale
output.
After initial field side filtering the input signal is chopped by a proprietary
chopper circuit. Isolation is provided by transformer coupling, again using a
proprietary technique to suppress transmission of common mode spikes or Special input circuits on the SCM5B38 module provide protection of the signal
surges. The module is powered from +5VDC, ±5%. inputs and the isolated excitation supply up to 240VAC.
SCM5B
Full Bridge Half Bridge Input
Module SCM5B38-31,-32,-35,-36,-37 SCM5B38-33,-34
Bridge Output
Input Range ±10mV to ±100mV * Model Type Input Range Excitation Sens. Range†
Input Bias Current ±0.5nA *
Input Resistance SCM5B38-31 Full –10mV to +10mV +3.333V 3mV/V 1, 2
Normal 50MΩ * SCM5B38-32 Full –30mV to +30mV +10.0V 3mV/V 1, 2
Power Off 40kΩ * SCM5B38-33 Half –10mV to +10mV +3.333V 3mV/V 1, 2
Overload 40kΩ * SCM5B38-34 Half –30mV to +30mV +10.0V 3mV/V 1, 2
Signal Input Protection SCM5B38-35 Full –20mV to +20mV +10.0V 2mV/V 1, 2
Continuous 240Vrms max * SCM5B38-36 Full –33.3mV to +33.3mV +3.333V 10mV/V 1, 2
Transient ANSI/IEEE C37.90.1 * SCM5B38-37 Full –100mV to +100mV +10.0V 10mV/V 1, 2
Excitation Output (-32, -34, -35, -37) +10V ±3mV * †
Load Resistance 300Ω to 10kΩ * Output Ranges Available
Excitation Output (-31, -33, -36) +3.333V ±2mV * Output Range Part No. Suffix Example
Load Resistance 100Ω to 10kΩ *
Excitation Load Regulation ±5ppm/mA * 1. –5V to +5V NONE SCM5B38-31
Excitation Stability ±15ppm/°C *
Half Bridge Voltage Level (-34) NA +5V ±1mV 2. –10V to +10V D SCM5B38-31D
Half Bridge Voltage Level (-33) NA +1.667V ±1mV
Isolated Excitation Protection
Continuous 240Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMV, Input to Output
Continuous 1500Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMR (50 or 60Hz) 160dB *
NMR 95dB at 60Hz, 90dB at 50Hz *
Accuracy(2) ±0.03% Span *
Linearity ±0.01% Span *
Stability
Input Offset ±1µV/°C *
Output Offset ±20µV/°C *
Gain ±25ppm of Reading/°C *
Figure 2: Full Bridge Connection
Noise
Input, 0.1 to 10Hz 0.2µVrms 1µVrms
Output, 100kHz 200µVrms *
Bandwidth, –3dB 4Hz *
Response Time, 90% Span 0.2s *
Output Range See Ordering Information *
Output Resistance 50Ω *
Output Protection Continuous Short to Ground *
Output Selection Time 6µs at Cload = 0 to 2000pF *
(to ±1mV of VOUT)
Output Current Limit ±8mA *
Output Enable Control
Max Logic “0” +0.8V *
Min Logic “1” +2.4V * Figure 3: Half Bridge Connection
Max Logic “1” +36V *
Input Current “0,1” 0.5µA *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 170mA Full Exc.Load, *
70mA No Exc. Load
Power Supply Sensitivity ±2µV/% RTI(3) *
Mechanical Dimensions 2.28" x 2.26" x 0.60" *
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Figure 4: Quarter Bridge Connection
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES: (1) Strain element.
* Same as -31, -32, -35, -36, -37 modules. (2) Includes linearity, hysteresis and repeatability.
(3) RTI = Referenced to input.
SCM5B38
Strain Gage Input Modules, Wide Bandwidth
Description
Each SCM5B38 Strain Gage input module provides a single channel of strain
gage input which is filtered, isolated, amplified, and converted to a high-level
Features
analog voltage output (Figure 1). This voltage output is logic switch controlled, • Interfaces to 100Ω Thru 10kΩ, Full-Bridge,
which allows these modules to share a common analog bus without the Half-Bridge, or Quarter-Bridge Strain Gages
requirement of external multiplexers. • High-Level Voltage Output
The SCM5B modules are designed with a completely isolated computer side • 1500Vrms Transformer Isolation
circuit which can be floated to ±50V from Power Common, pin 16. This complete
• ANSI/IEEE C37.90.1 Transient Protection
isolation means that no connection is required between I/O Common and
Power Common for proper operation of the output switch. If desired, the output • Input Protected to 240VAC Continuous
switch can be turned on continuously by simply connecting pin 22, the Read- • Fully Isolated Excitation Supply
Enable pin, to I/O Common, pin 19.
• 100dB CMR
The SCM5B38 can interface to full-bridge or half-bridge transducers with a
• 10kHz Signal Bandwidth
nominal resistance of 100Ω to 10kΩ. A matched pair of bridge-completion
resistors (to ±1mV at +10V excitation) allows use of low cost half-bridge or • ±0.03% Accuracy
quarter-bridge transducers (Figures 2, 3, 4). The 10kHz bandwidth allows • ±0.01% Linearity
measurement of high speed processes such as vibration analysis.
• ±1µV/°C Drift
Strain gage excitation is provided from the module by a very stable 10V • CSA C/US Certified, CE and ATEX Compliant
or 3.333V source. The excitation supply is fully isolated, allowing the amplifier
inputs to operate over the full range of the excitation voltage. This feature • Mix and Match SCM5B Types on Backpanel
offers significant flexibility in real world applications. Full scale sensitivities of
2mV/V, 3mV/V or 10mV/V are offered as standard. With 10V excitation, this
results in ±20mV, ±30mV or ±100mV full scale input range producing ± 5V full
scale output.
again using a proprietary technique to suppress transmission of common mode
The input signal is processed through a pre-amplifier on the field side of the
spikes or surges. The module is powered from +5VDC, ±5%.
isolation barrier. This pre-amplifier has a gain-bandwidth product of 5MHz and
is bandwidth limited to 10kHz. After amplification, the input signal is chopped by Special input circuits on the SCM5B38 module provide protection of the signal
a proprietary chopper circuit. Isolation is provided by transformer coupling, inputs and the isolated excitation supply up to 240VAC.
SCM5B
Full Bridge Half Bridge Input
Module SCM5B38-01,-02,-05,-06,-07 SCM5B38-03,-04 Model Bridge Output
Input Range ±10mV to ±100mV * (10kHz) Type Input Range Excitation Sens. Range†
Input Bias Current ±0.3nA *
Input Resistance SCM5B38-01 Full –10mV to +10mV +3.333V 3mV/V 1, 2
Normal 50MΩ * SCM5B38-02 Full –30mV to +30mV +10.0V 3mV/V 1, 2
Power Off 40kΩ * SCM5B38-03 Half –10mV to +10mV +3.333V 3mV/V 1, 2
Overload 40kΩ * SCM5B38-04 Half –30mV to +30mV +10.0V 3mV/V 1, 2
Signal Input Protection SCM5B38-05 Full –20mV to +20mV +10.0V 2mV/V 1, 2
Continuous 240Vrms max * SCM5B38-06 Full –33.3mV to +33.3mV +3.333V 10mV/V 1, 2
Transient ANSI/IEEE C37.90.1 * SCM5B38-07 Full –100mV to +100mV +10.0V 10mV/V 1, 2
Excitation Output (-02, -04, -05, -07) +10V ±3mV * †
Load Resistance 300Ω to 10kΩ * Output Ranges Available
Excitation Output (-01, -03, -06) +3.333V ±2mV *
Output Range Part No. Suffix Example
Load Resistance 100Ω to 10kΩ *
Excitation Load Regulation ±5ppm/mA *
1. –5V to +5V NONE SCM5B38-01
Excitation Stability ±15ppm/°C *
Half Bridge Voltage Level (-04) NA +5V ±1mV 2. –10V to +10V D SCM5B38-01D
Half Bridge Voltage Level (-03) NA +1.667V ±1mV
Isolated Excitation Protection
Continuous 240Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMV, Input to Output
Continuous 1500Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMR (50 or 60Hz) 100dB *
NMR (–3dB at 10kHz) 120dB per Decade above 10kHz *
Accuracy(2) ±0.03% Span *
Linearity ±0.01% Span *
Stability
Input Offset ±1µV/°C *
Output Offset ±40µV/°C *
Gain ±25ppm of Reading/°C *
Noise Figure 2: Full Bridge Connection
Input, 0.1 to 10Hz 0.4µVrms 2µVrms
Output, 100kHz 10mVp-p *
Bandwidth, –3dB 10kHz *
Rise Time, 10 to 90% Span 35µs *
Settling Time, to 0.1% 250µs *
Output Range See Ordering Information *
Output Resistance 50Ω *
Output Protection Continuous Short to Ground *
Output Selection Time 6µs at Cload = 0 to 2000pF *
(to ±1mV of VOUT)
Output Current Limit ±8mA *
Output Enable Control
Max Logic “0” +0.8V *
Min Logic “1” +2.4V * Figure 3: Half Bridge Connection
Max Logic “1” +36V *
Input Current “0,1” 0.5µA *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 170mA Full Exc. Load, *
70mA No Exc. Load
Power Supply Sensitivity ±2µV/% RTI(3) *
Mechanical Dimensions 2.28" x 2.26" x 0.60" *
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Figure 4: Quarter Bridge Connection
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error * NOTES:
ESD, EFT Performance B * * Same as –01, –02, –05, –06, –07 modules.
(1) Strain element. (2) Includes linearity, hysteresis and repeatability. (3) RTI =
Referenced to input.
SCM5B39
Current Output Modules
Description
Each SCM5B39 current output module provides a single channel of analog
output. The track-and-hold circuit in the input stage can be operated in a hold Features
mode where one DAC can supply many output modules, or a track mode where • Accepts High-Level Voltage or Process Current
one DAC is dedicated to each module. In addition to the track-and-hold circuit, Input
each module provides signal buffering, isolation, filtering, and conversion to a
• Unipolar or Bipolar Current Output
high-level current output (Figure 1).
• 1500Vrms Transformer Isolation
Setting of the track or hold mode is controlled by the logic state of WR EN\,
module pin 23. When pin 23 is low, the track mode is enabled. If pin 23 is high, • ANSI/IEEE C37.90.1 Transient Protection
the hold mode is enabled. The module is designed with a completely isolated • Output Protected to 240VAC Continuous
computer side circuit which can be floated to ±50V from Power Common, pin 16. • 110dB CMR
This complete isolation means that no connection is required between I/O
Common and Power Common for proper operation of the track and hold circuit. • 400Hz Signal Bandwidth
For a low state, simply connect pin 23, the Write-Enable pin, to I/O Common, pin • ±0.03% Accuracy
19.
• ±0.005% Linearity
The SCMPB02 and SCMPB06 backpanels allow host computer control of the • CSA C/US Certified, CE and ATEX Compliant
WR EN\ control line, which allows multiplexing of one host DAC to up to 64
SCM5B39 output modules. During power-up, the output remains at 0mA for • Mix and Match SCM5B Types on Backpanel
100ms on all models except the SCM5B39-07, which allows the track-and-hold
circuit to be initialized.
A special circuit in the output stage of the module provides protection against
accidental connection of power-line voltages up to 240VAC on all models.
SCM5B
Unipolar Output Current Bipolar Output Current Model Input Range Output Range Bandwidth
Module SCM5B39-01,-02,-03,-04,-05 SCM5B39-07
Input Voltage Range ±5V or 0V to +5V ±10V SCM5B39-01 0V to +5V 4mA to 20mA 400Hz
Input Current Range (-05) 0 to 20mA N/A SCM5B39-02 –5V to +5V 4mA to 20mA 400Hz
Input Voltage Maximum ±36V (no damage) * SCM5B39-03 0V to +5V 0mA to 20mA 400Hz
Input Current, Maximum (-05) 75mA (no damage) N/A SCM5B39-04 –5V to +5V 0mA to 20mA 400Hz
Input Resistance 50MΩ 2MΩ
Input Resistance (-05) 250Ω N/A SCM5B39-05 0mA to 20mA 0mA to 20mA 400Hz
SCM5B39-07 –10V to +10V –20mA to +20mA 275Hz
Output Current Range 0 to 20mA or 4 to 20mA ±20mA
Power-Up Delay(1) 100ms N/A Refer to SCM5B392 specifications, p.27, for additional current output models.
Current Out 0mA N/A
Over Range Capability 10% *
Output Compliance Voltage
(Open Circuit) 22VDC ±15VDC
Load Resistance Range 0 to 650Ω 0 to 450Ω
(0 to 750Ω for Power Supply (0 to 500Ω for Power Supply
Voltage greater than 4.95VDC) Voltage greater than 4.95VDC)
Output I Under Fault, max 26mA *
Output Protection
Continuous 240Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMV, Output to Input
Continuous 1500Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMR (50Hz or 60Hz) 110dB *
NMR (–3dB) 80dB per Decade 80dB per Decade
above 400Hz above 275Hz
Accuracy ±0.03% Span ±0.05% Span
Linearity ±0.005% Span ±0.03% Span
Stability
Offset ±0.5µA/°C *
Gain ±20ppm/°C ±40ppm/°C
Noise
Output Ripple, 100kHz 10µAp-p *
Bandwidth, –3dB 400Hz 275Hz
Rise Time, 10 to 90% Span 1.0ms 1.2ms
Sample and Hold
Output Droop Rate 40µA/s *
Acquisition Time 50µs *
Track-and-Hold Enable Control
Max Logic “0” +0.8V *
Min Logic “1” +2.4V *
Max Logic “1” +36V *
Input Current “0” 0.5µA *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 170mA 130mA
Power Supply Sensitivity ±0.5µA/% typ *
Mechanical Dimensions 2.28" x 2.26" x 0.6" *
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES:
* Same as -01, -02, -03, -04, -05 modules.
(1) See Product Description for further details.
SCM5B392
Matched-Pair Servo/Motor Controller Modules
Description
The SCM5B392 servo/motor controller module set is designed to solve the
problem of extending a servo or motor controller signal a long distance with Features
the possibility for noise pickup and/or contacting hazardous voltages. Each • Extends the Distance and Isolates
SCM5B392 module set is made up of two modules: a voltage input/current Servo/Motor Controller Signals
output module and a current input/voltage output module (Figure 1).
• Provides Isolated Current Loop Interface
The voltage input module connects to the servo or motor controller voltage Between Controller and Motor or Actuator
output and provides an isolated 4 to 20mA output which connects to the input • Accepts High-Level Voltage Inputs up to ±10V
of the current input module. The current input module isolates and provides an
output voltage identical to that of the servo or motor controller. Thus the original • Provides High-Level Voltage Outputs
control signal has been isolated (twice) and extended via a 4 to 20mA current up to ±10V
loop. • 1500VrmsTransformer Isolation
Several mounting options are available for the SCM5B392 module set. If a large (3000Vrms Total Loop)
number of channels are required, the SCMPB01 16 channel backpanel and • ANSI/IEEE C37.90.1 Transient Protection
SCMPB05 8 channel backpanel are available. Smaller channel numbers can • Current Loop is Protected to 240VAC
be accommodated with the SCMPB03 single channel mounting panel and Continuous
SCMPB04 dual channel mounting panel. These can be mounted on a DIN rail.
• 1kHz Signal Bandwidth
• 100dB CMR
• ±0.06% Total Loop Accuracy
• ±0.01% Total Loop Linearity
• CSA C/US Certified, CE and ATEX Compliant
• Mix and Match SCM5B Types on Backpanel
Specifications Typical at TA=+25°C and +5V power Ordering Information (for module pairs)
SCM5B
SCM5B392-01,-02,-03,-04 SCM5B392-11,-12,-13,-14 Model Input Range Interface Output Range
Module (Input) (Output)
Input Range See Ordering Information 4mA to 20mA SCM5B392-0111 0V to +5V 4mA to 20mA 0V to +5V
Input Resistance 50MΩ (-01,-02) 2MΩ (-03,-04) 20Ω SCM5B392-0212 –5V to +5V 4mA to 20mA –5V to +5V
Accuracy N/A ±0.1% SCM5B392-0313 0V to +10V 4mA to 20mA 0V to +10V
Stability N/A ±10ppm/°C
SCM5B392-0414 –10V to +10V 4mA to 20mA –10V to +10V
Input Protection
Continuous ±36V (no damage) 240Vrms max
Transient N/A ANSI/IEEE C37.90.1
Output Range 4mA to 20mA See Ordering Information Ordering Information (for single modules)
Over Range Capability 10% N/A
Output Compliance Voltage Model Input Range Output Range Bandwidth
(Open Circuit) 22VDC N/A
Loop Resistance Range 0 to 600Ω N/A SCM5B392-01 0V to +5V 4mA to 20mA 1kHz
(0 to 700Ω for Power Supply SCM5B392-02 –5V to +5V 4mA to 20mA 1kHz
Voltage greater than 4.95VDC) SCM5B392-03 0V to +10V 4mA to 20mA 1kHz
Output Resistance N/A 50Ω SCM5B392-04 –10V to +10V 4mA to 20mA 1kHz
Output Selection Time N/A 6µs at Cload = 0 to 2000pF
(to ±1mV of VOUT) SCM5B392-11 4mA to 20mA 0V to +5V 1kHz
Output Current Limit 26mA +8mA SCM5B392-12 4mA to 20mA –5V to +5V 1kHz
Output Protection
Continuous 240Vrms max Short to Ground SCM5B392-13 4mA to 20mA 0V to +10V 1kHz
Transient ANSI/IEEE C37.90.1 N/A SCM5B392-14 4mA to 20mA –10V to +10V 1kHz
CMV
Continuous 1500Vrms max, output to input *
Transient ANSI/IEEE C37.90.1 *
CMR (50Hz or 60Hz) 100dB *
NMR (–3dB at 1KHz) 80dB per Decade 120dB per Decade
above 1kHz above 1kHz
Accuracy ±0.03% Span *
Linearity ±0.005% Span *
Stability
Offset ±0.5µA/°C ±50µV/°C
Gain ±20ppm/°C ±25ppm/°C
Noise
Output, 100kHz 10µAp-p 200µVrms
Bandwidth, –3dB 1kHz 1kHz
Rise Time, 10 to 90% Span 340µs 750µs
Sample and Hold
Output Droop Rate 40µA/s N/A
Acquisition Time 50µs N/A
Enable Control
Max Logic “0” +0.8V *
Min Logic “1” +2.4V *
Max Logic “1” +36V *
Input Current “0” 0.5µA *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 170mA 30mA
Power Supply Sensitivity ±0.5µA/% typ ±20µV/% RTI
Mechanical Dimensions 2.28" x 2.26" x 0.6" *
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
SCM5B40/41
Analog Voltage Input Modules, Wide Bandwidth
Description
Each SCM5B40 and SCM5B41 wide bandwidth voltage input module provides
a single channel of analog input which is amplified, isolated, and converted to Features
a high-level analog voltage output (Figure 1). This voltage output is logic-switch • Accepts Millivolt and Voltage Level Signals
controlled, allowing these modules to share a common analog bus without the
• High-Level Voltage Outputs
requirement of external multiplexers.
• 1500Vrms Transformer Isolation
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ±50V from Power Common, pin 16. This complete • ANSI/IEEE C37.90.1 Transient Protection
isolation means that no connection is required between I/O Common and Power • Input Protected to 240VAC Continuous
Common for proper operation of the output switch. If desired, the output switch • 100dB CMR
can be turned on continuously by simply connecting pin 22, the Read-Enable
pin, to I/O Common, pin 19. • 10kHz Signal Bandwidth
• ±0.03% Accuracy
The input signal is processed through a pre-amplifier on the field side of the
isolation barrier. This pre-amplifier has a gain-bandwidth product of 5MHz and • ±0.01% Linearity
is bandwidth limited to 10kHz. After amplification, the input signal is chopped by • ±1µV/°C Drift
a proprietary chopper circuit. Isolation is provided by transformer coupling,
again using a proprietary technique to suppress transmission of common mode • CSA C/US Certified, CE and ATEX Compliant
spikes or surges. The module is powered from +5VDC, ±5%. • Mix and Match SCM5B Types on Backpanel
A special input circuit on the SCM5B40 and SCM5B41 modules provides
protection against accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B40 SCM5B41 Model Input Range Output Range†
Input Range ±10mV to ±1V ±1V to ±40V SCM5B40-01 –10mV to +10mV 1, 2
Input Bias Current ±0.5nA ±0.05nA SCM5B40-02 –50mV to +50mV 1, 2
Input Resistance
Normal 200MΩ 650kΩ (minimum) SCM5B40-03 –100mV to +100mV 1, 2
Power Off 40kΩ 650kΩ (minimum) SCM5B40-04 –10mV to +10mV 3, 4
Overload 40kΩ 650kΩ (minimum) SCM5B40-05 –50mV to +50mV 3, 4
Input Protection SCM5B40-06 –100mV to +100mV 3, 4
Continuous 240Vrms max *
Transient ANSI/IEEE C37.90.1 *
SCM5B40-07(3) –1V to +1V 1, 2
CMV, Input to Output SCM5B41-01 –1V to +1V 1, 2
Continuous 1500Vrms max * SCM5B41-02 –5V to +5V 1, 2
Transient ANSI/IEEE C37.90.1 * SCM5B41-03 –10V to +10V 1, 2
CMR (50Hz or 60Hz) 100dB * SCM5B41-04 –1V to +1V 3, 4
NMR (–3dB at 10kHz) 120dB per Decade above 10kHz *
SCM5B41-05 –5V to +5V 3, 4
Accuracy(1) ±0.03% Span *
SCM5B41-06 –10V to +10V 3, 4
Linearity ±0.01% Span *
Stability SCM5B41-07 –20V to +20V 1, 2
Input Offset ±1µV/°C ±20µV/°C SCM5B41-08 –20V to +20V 3, 4
Output Offset ±40µV/°C * SCM5B41-09 –40V to +40V 1, 2
Gain ±25ppm/°C ±50ppm/°C
SCM5B41-10 –40V to +40V 3, 4
Noise
Input, 0.1 to 10Hz 0.4µVrms 2µVrms
Output, 100kHz 10mVp-p *
†
Bandwidth, –3dB 10kHz * Output Ranges Available
Rise Time, 10 to 90% Span 35µs *
Settling Time, to 0.1% 250µs * Output Range Part No. Suffix Example
Output Range See Ordering Information * 1. –5V to +5V NONE SCM5B40-01
Output Resistance 50Ω *
2. –10V to +10V D SCM5B40-01D
Output Protection Continuous Short to Ground *
Output Selection Time 6µs at Cload = 0 to 2000pF 3. 0V to +5V NONE SCM5B40-04
(to ±1mV of VOUT ) * 4. 0V to +10V D SCM5B40-04D
Output Current Limit ±8mA *
Output Enable Control
Max Logic “0” +0.8V *
Min Logic “1” +2.4V *
Max Logic “1” +36V *
Input Current “0,1” 0.5µA *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 30mA *
Power Supply Sensitivity ±2µV/% RTI(2) ±200µV/% RTI(2)
Mechanical Dimensions 2.28" x 2.26" x 0.60" *
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD,EFT Performance B *
NOTES:
* Same specification as SCM5B40.
(1) Includes linearity, hysteresis and repeatability.
(2) RTI = Referenced to input.
(3) Same as SCM5B41-01 with 50MΩ input resistance.
SCM5B42
2-Wire Transmitter Interface Modules
Description
Each SCM5B42 2-wire transmitter interface module provides a single channel
which accepts a 4 to 20mA process current input and provides a standard +1 to Features
+5V or +2 to +10V output signal (Figure 1). An isolated +20VDC regulated power • Isolated +20VDC Current Loop Supply
supply is provided to power the current transmitter. This allows a 2-wire loop
• Provides Isolation for Non-Isolated 2-Wire
powered transmitter to be directly connected to the SCM5B42 without requiring
Transmitters
an external power supply. The regulated supply will provide a nominal +20VDC
at a loop current of 4mA to 20mA. • High-Level Voltage Output +1V to +5V
or +2V to +10V
The SCM5B42 will provide a 1500V isolation barrier for non-isolated 2-wire field
transmitters. It can also be used when additional isolation is required between • 1500Vrms Transformer Isolation
an isolated 2-wire transmitter and the input stage of the control room computer. • ANSI/IEEE C37.90.1 Transient Protection
The voltage output is logic switch controlled, which allows these modules to • Input Protected to 240VAC Continuous
share a common analog bus without the requirement of external multiplexers. • 100dB CMR
The SCM5B modules are designed with a completely isolated computer side • 100Hz Signal Bandwidth
circuit which can be floated to ±50V from Power Common, pin 16. This complete
• ±0.03% Accuracy
isolation means that no connection is required between I/O Common and Power
Common for proper operation of the output switch. If desired, the output switch • ±0.005% Linearity
can be turned on continuously by simply connecting pin 22, the Read-Enable • CSA C/US Certified, CE and ATEX Compliant
pin, to I/O Common, pin 19.
• Mix and Match SCM5B Types on Backpanel
A precision 20Ω current conversion resistor is supplied with the module.
Sockets are provided on the SCMPB01/02/03/04/05/06/07 backpanels to allow
installation of this resistor. Extra resistors are available under part number
SCMXR1. All field inputs are fully protected from accidental connection of
power-line voltages up to 240VAC. The module has a 3dB bandwidth of 100Hz.
Signal filtering is accomplished with a six-pole filter, with two poles on the field
side of the isolation barrier, and the other four on the computer side.
SCM5B
Module SCM5B42 Model Input Range Output Range
Input Range 4mA to 20mA
SCM5B42-01 4mA to 20mA +1V to +5V
Input Resistor
Value 20.00Ω
SCM5B42-02 4mA to 20mA +2V to +10V
Accuracy ±0.1%
Stability ±10ppm/°C
Loop Supply Voltage Nominal 20V at 4mA to 20mA
Environmental
Operating Temp. Range –40°C to +85°C
Storage Temp. Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD,EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability.
(2) RTI = Referenced to input.
SCM5B43
General Purpose Input Modules, with DC Excitation
Description
Each SCM5B43 general purpose input module provides a single channel of
transducer input which is filtered, isolated, scaled, and converted to a high-level
Features
analog voltage output (Figure 1). This voltage output is logic switch controlled, • Interfaces to DC Displacement Transducers
which allows these modules to share a common analog bus without the and Other Devices Requiring a Stable DC
requirement of external multiplexers. Supply
The SCM5B modules are designed with a completely isolated computer side • High-Level Voltage Outputs
circuit which can be floated to ±50V from Power Common, pin 16. This complete • 1500Vrms Transformer Isolation
isolation means that no connection is required between I/O Common and Power
Common for proper operation of the output switch. If desired, the output switch • ANSI/IEEE C37.90.1 Transient Protection
can be turned on continuously by simply connecting pin 22, the Read-Enable • Input Protected to 240VAC Continuous
pin, to I/O Common, pin 19. • Fully Isolated Excitation Supply
The SCM5B43 can interface to devices which require a precision 10VDC • 100dB CMR
excitation supply. The 1kHz bandwidth significantly reduces ripple and noise
• 1kHz Signal Bandwidth
inherent in these devices.
• ±0.03% Accuracy
Transducer excitation is provided from the module by a very stable 10V source.
The excitation supply is fully isolated, allowing the amplifier inputs to operate • ±0.005% Linearity
over the full range of the excitation voltage. This feature offers significant • ±20µV/°C Drift
flexibility in real world applications. Ten full scale input ranges are provided, from
• CSA C/US Certified, CE and ATEX Compliant
±1V to ±10V, producing ±5V full scale output.
• Mix and Match SCM5B Types on Backpanel
The input signal is processed through a pre-amplifier on the field side of the
isolation barrier. This pre-amplifier has a gain-bandwidth product of 5MHz and
is bandwidth limited to 1kHz. After amplification, the input signal is chopped by
a proprietary chopper circuit. Isolation is provided by transformer coupling,
again using a proprietary technique to suppress transmission of common mode
spikes or surges. The module is powered from +5VDC, ±5%.
Special input circuits on the SCM5B43 module provide protection of the signal
inputs and the isolated excitation supply up to 240VAC.
SCM5B
Module SCM5B43 Model Maximum Input Output Range†
Input Range ±1V to ±10V SCM5B43-01 ±1V 1, 2
Input Bias Current ±0.05nA
SCM5B43-02 ±2V 1, 2
Input Resistance
Normal 2MΩ (minimum) SCM5B43-03 ±3V 1, 2
Power Off 2MΩ (minimum) SCM5B43-04 ±4V 1, 2
Overload 2MΩ (minimum) SCM5B43-05 ±5V 1, 2
Input Protection SCM5B43-06 ±6V 1, 2
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1 (formerly IEEE-472) SCM5B43-07 ±7V 1, 2
SCM5B43-08 ±8V 1, 2
Excitation Voltage, VEXC +10.0VDC ±2mV SCM5B43-09 ±9V 1, 2
Excitation Current 40mA (maximum)
SCM5B43-10 ±10V 1, 2
Excitation Load Regulation ±5ppm/mA
Excitation Stability ±15ppm/°C
Isolated Excitation Protection
†
Continuous 240Vrms max Output Ranges Available
Transient ANSI/IEEE C37.90.1 (formerly IEEE-472)
Output Range Part No. Suffix Example
CMV, Input to Output
Continuous 1500Vrms max 1. –5V to +5V NONE SCM5B43-01
Transient ANSI/IEEE C37.90.1 (formerly IEEE-472) 2. –10V to +10V D SCM5B43-01D
CMR (50 or 60Hz) 100dB
NMR (–3dB at 1kHz) 120dB per Decade Above 1kHz
Stability
Input Offset ±20µV/°C
Output Offset ±40µV/°C
Gain ±50ppm/°C
Noise
Input, 0.1 to 10Hz 0.4µVrms
Output, 100kHz 5mVp-p
SCM5B45
Frequency Input Modules
Description
Each SCM5B45 frequency input module provides a single channel of frequency
input which is isolated and converted to a high-level analog voltage output. This Features
voltage output is logic switch controlled, which allows these modules to share • Accepts Frequency Inputs of 0 to 100kHz
a common analog bus without the requirement of external multiplexers
• Provides High-Level Voltage Outputs
(Figure1).
• TTL or Zero Crossing Signal Inputs
The frequency input signal can be a TTL level signal or a zero-crossing signal.
Terminal 3 on the field-side terminal block is the “common” or ground connection • 1500 Vrms Transformer Isolation
for input signals. A TTL signal is connected from terminal 2 to terminal 3, • ANSI/IEEE C37.90.1 Transient Protection
while a zero-crossing signal is connected from terminal 4 to terminal 3. Input • Input Protected to 240VAC Continuous
circuitry for each of the signal types has hysteresis built in. An input signal
must cross entirely through the hysteresis region in order to trigger the threshold • 120dB CMR
comparator. • ±0.05% Accuracy
A 5.1V excitation is available for use with magnetic pick-up or contact-closure • CSA C/US Certified, CE and ATEX Compliant
type sensors. The excitation is available on pin 1 and the excitation common is • Mix and Match SCM5B Types on Backpanel
pin 3.
The SCM5B modules are designed with a completely isolated computer side
circuit which can be floated to ±50V from Power Common, pin 16. This complete
isolation means that no connection is required between I/O Common and Power
Common for proper operation of the output switch. If desired, the output switch
can be turned on continuously by simply connecting pin 22, the Read-Enable
pin, to I/O Common, pin 19.
A special circuit in the input stage of the module provides protection against
accidental connection of power-line voltages up to 240VAC.
SCM5B
Module SCM5B45 Zero Crossing
Model Input Range Output Range† Hysteresis
Input Range 0Hz to 100kHz SCM5B45-01 0Hz to 500Hz 3, 4 ± 20mV
Input Threshold Zero Crossing
Minimum Input 60mVp-p
SCM5B45-02 0Hz to 1kHz 3, 4 ± 20mV
Maximum Input 350Vp-p SCM5B45-03 0Hz to 3kHz 3, 4 ± 20mV
Minimum Pulse Width 4µs SCM5B45-04 0Hz to 5kHz 3, 4 ± 20mV
TTL Input Low 0.8V max SCM5B45-05 0Hz to 10kHz 3, 4 ± 20mV
TTL Input High 2.4V min SCM5B45-06 0Hz to 25kHz 3, 4 ± 20mV
Input Hysteresis
Zero Crossing ±20mV (±400mV on -2x models) SCM5B45-07 0Hz to 50kHz 3, 4 ± 20mV
TTL 1.5V SCM5B45-08 0Hz to 100kHz 3, 4 ± 20mV
Input Resistance
Normal 100kΩ SCM5B45-21 0Hz to 500Hz 3, 4 ± 400mV
Power Off 100kΩ SCM5B45-22 0Hz to 1kHz 3, 4 ± 400mV
Overload 100kΩ SCM5B45-23 0Hz to 3kHz 3, 4 ± 400mV
Input Protection
SCM5B45-24 0Hz to 5kHz 3, 4 ± 400mV
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1 SCM5B45-25 0Hz to 10kHz 3, 4 ± 400mV
Excitation +5.1V at 8mA max SCM5B45-26 0Hz to 25kHz 3, 4 ± 400mV
CMV, Input to Output SCM5B45-27 0Hz to 50kHz 3, 4 ± 400mV
Continuous 1500Vrms max SCM5B45-28 0Hz to 100kHz 3, 4 ± 400mV
Transient ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 120dB
Accuracy(1) ±0.05% Span †
Output Ranges Available
Linearity ±0.02% Span
Stability Output Range Part No. Suffix Example
Offset ±8ppm/°C
Gain ±40ppm/°C 3. 0V to +5V NONE SCM5B45-01
Noise 4. 0V to +10V D SCM5B45-01D
Output Ripple <10mVp-p at Input >2% span
Response Time (0 to 90%)
SCM5B45-01, -02, -21, -22 300ms
SCM5B45-03, -23 170ms
SCM5B45-04, -05, -24, -25 90ms
SCM5B45-06, -07, -08, -26, -27, -28 20ms
Output Range See Ordering Information
Output Resistance 50Ω
Output Protection Continuous Short to Ground
Output Selection Time 6µs at Cload = 0 to 2000pF
(to ±1mV of VOUT)
Output Current Limit +8mA
SCM5B47
Linearized Thermocouple Input Modules
Description
Each SCM5B47 thermocouple input module provides a single channel of
thermocouple input which is filtered, isolated, amplified, linearized and con- Features
verted to a high-level analog voltage output (Figure 1). This voltage output is • Interfaces to Types J, K, T, E, R, S, N
logic-switch controlled, allowing these modules to share a common analog bus and B Thermocouples
without the requirement of external multiplexers.
• Linearizes Thermocouple Signal
The SCM5B modules are designed with a completely isolated computer side • High-Level Voltage Outputs
circuit which can be floated to ±50V from Power Common, pin 16. This complete
isolation means that no connection is required between I/O Common and Power • 1500Vrms Transformer Isolation
Common for proper operation of the output switch. If desired, the output switch • ANSI/IEEE C37.90.1 Transient Protection
can be turned on continuously by simply connecting pin 22, the Read-Enable
• Input Protected to 240VAC Continuous
pin, to I/O Common, pin 19.
• 160dB CMR
The SCM5B47 can interface to eight industry standard thermocouple types: J,
K, T, E, R, S, N, and B. Its corresponding output signal operates over a 0V to +5V • 95dB NMR at 60Hz, 90dB at 50Hz
range. Each module is cold-junction compensated to correct for parasitic • ±1µV/°C Drift
thermocouples formed by the thermocouple wire and screw terminals on the • CSA C/US Certified, CE and ATEX Compliant
mounting backpanel. Upscale open thermocouple detect is provided by an
internal pull-up resistor. Downscale indication can be implemented by installing • Mix and Match SCM5B Types on Backpanel
an external 47MΩ resistor, ±20% tolerance, between screw terminals 1 and 3
on the SCMPB01/02/03/04/05/06/07 backpanels.
Signal filtering is accomplished with a six-pole filter which provides 95dB of proprietary technique to suppress transmission of common mode spikes or
normal-mode rejection at 60Hz and 90dB at 50Hz. Two poles of this filter are on surges. The module is powered from +5VDC, ±5%.
the field side of the isolation barrier, and the other four are on the computer side.
A special input circuit on the SCM5B47 modules provides protection against
After the initial field-side filtering, the input signal is chopped by a proprietary accidental connection of power-line voltages up to 240VAC.
chopper circuit. Isolation is provided by transformer coupling, again using a
SCM5B
Module SCM5B47 TC Output
Model Type‡ Input Range Range† Accuracy(1)
Input Range –0.1V to +0.5V SCM5B47J-01 J 0°C to +760°C 3, 4 ±0.08% ±0.61°C
Input Bias Current –25nA (+32°F to +1400°F)
Input Resistance
Normal 50MΩ SCM5B47J-02 J –100°C to +300°C 3, 4 ±0.08% ±0.32°C
Power Off 40kΩ (–148°F to +572°F)
Overload 40kΩ
Input Protection SCM5B47J-03 J 0°C to +500°C 3, 4 ±0.07% ±0.36°C
Continuous 240Vrms max (+32°F to 932°F)
Transient ANSI/IEEE C37.90.1
SCM5B47K-04 K 0°C to +1000°C 3, 4 ±0.08% ±0.80°C
CMV, Input to Output (+32°F to +1832°F)
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1 SCM5B47K-05 K 0°C to +500°C 3, 4 ±0.08% ±0.38°C
CMR (50Hz or 60Hz) 160dB (+32°F to +932°F)
NMR 95dB at 60Hz, 90dB at 50Hz
SCM5B47T-06 T –100°C to +400°C 3, 4 ±0.16% ±0.80°C
Accuracy See Ordering Information (–148°F to +752°F)
Stability
Input Offset ±1µV/°C(2) SCM5B47T-07 T 0°C to +200°C 3, 4 ±0.13% ±0.25°C
Output Offset ±20µV/°C (+32°F to +392°F)
Gain ±25ppm/°C
Noise SCM5B47E-08 E 0°C to +1000°C 3, 4 ±0.10% ±1.0°C
Input, 0.1 to 10Hz 0.2µVrms (+32°F to +1832°F)
Output, 100kHz 300µVp-p,150µVrms SCM5B47R-09 R +500°C to +1750°C 3, 4 ±0.10% ±1.3°C
Bandwidth, –3dB 4Hz (+932°F to +3182°F)
Response Time, 90% Span 0.2s
Output Range See Ordering Information
SCM5B47S-10 S +500°C to +1750°C 3, 4 ±0.10% ±1.3°C
Output Resistance 50Ω
(+932°F to +3182°F)
Output Protection Continuous Short to Ground SCM5B47B-11 B +500°C to +1800°C 3, 4 ±0.15% ±2.0°C
Output Selection Time 6µs at Cload = 0 to 2000pF (+932°F to +3272°F)
(to ±1mV of VOUT )
Output Current Limit +8mA SCM5B47J-12 J –100°C to +760°C 3, 4 ±0.08% ±0.70°C
(–148°F to +1400°F)
Output Enable Control
Max Logic “0” +0.8V SCM5B47K-13 K –100°C to +1350°C 3, 4 ±0.08% ±1.20°C
Min Logic “1” +2.4V (–148°F to +2462°F)
Max Logic “1” +36V
Input Current “0,1” 0.5µA SCM5B47K-14 K 0°C to +1200°C 3, 4 ±0.08% ±0.96°C
Open Input Response Upscale (+32°F to +2192°F)
Open Input Detection Time <10s
Cold Junction Compensation SCM5B47N-15 N –100°C to +1300°C 3, 4 ±0.08% ±1.15°C
Accuracy, 25°C ±0.25°C (–148°F to +2372°F)
Accuracy, +5°C to +45°C ±0.5°C
Accuracy, –40°C to +85°C ±1.25°C
‡
Power Supply Voltage +5VDC ±5%
Thermocouple Alloy Combinations
Power Supply Current 30mA Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
Power Supply Sensitivity ±2µV/% RTI(3)
Mechanical Dimensions 2.28" x 2.26" x 0.6" Type Material
(h)(w)(d) (58mm x 57mm x 15mm)
J Iron vs. Copper-Nickel
Environmental K Nickel-Chromium vs. Nickel-Aluminum
Operating Temperature Range –40°C to +85°C T Copper vs. Copper-Nickel
Storage Temperature Range –40°C to +85°C E Nickel-Chromium vs. Copper-Nickel
Relative Humidity 0 to 95% Noncondensing R Platinum-13% Rhodium vs. Platinum
Emissions EN61000-6-4 ISM, Group 1 S Platinum-10% Rhodium vs. Platinum
Radiated, Conducted Class A B Platinum-30% Rhodium vs. Platinum-6% Rhodium
Immunity EN61000-6-2 ISM, Group 1 N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4%
RF Performance A ±0.5% Span Error Silicon- 0.1% Magnesium
ESD, EFT Performance B
NOTES:
(1) Includes conformity, hysteresis and repeatability. Does not include CJC accuracy.
(2) This is equivalent to °C as follows: Type J 0.020 °C/°C, Types K, T 0.025°C/°C, †
Output Ranges Available
Type E 0.016°C/°C, Types R, S 0.168°C/°C, Type N 0.037°C/°C, Type C 0.072°C/°C.
(3) RTI = Referenced to input. Output Range Part No. Suffix Example
3. 0V to +5V NONE SCM5B47J-01
4. 0V to +10V D SCM5B47J-01D
SCM5B48
Accelerometer Input Module
Description
The SCM5B48 provides excitation to piezoelectric sensors with built-in
microelectronic amplifiers, commonly known as ICP®* or IEPE* or LIVM* Features
sensors. The module provides a constant current excitation to the sensor, then • Interfaces to ICP®* or IEPE* or LIVM* Sensors
isolates, filters, and amplifies the sensor output, yielding a high-level analog • ±10V Output Range
voltage output. The excitation current, signal gain, and filter high-pass and
low-pass cutoff frequencies are field-configurable through a set of slide switches. • 1500Vrms Transformer Isolation
• ANSI/IEEE C37.90.1 Transient Protection
Six poles of signal filtering in the SCM5B48 module result in greater than 100dB
of normal-mode rejection for signal frequencies above the cutoff frequency. One • Input Protection to 240Vrms Continuous
pole of filtering is on the field side of the isolation barrier for anti-aliasing • 1, 10, and 100 Programmable Gain
purposes and the remaining five-pole programmable Bessel filter is located on • 2.5, 5, 10, and 20kHz Programmable LP Filter
the system side. High-pass filtering is achieved through a second order passive
• 0.2 and 10Hz Programmable HP Filter
filter, located on the field side. If desired, the output switch can be turned on
continuously by simply connecting pin 22, the Read-Enable pin, to I/O Common, • 4mA or 9mA Programmable Current Excitation
pin 19. • 100dB CMR
The SCM5B48 offers the option of setting the constant current source for sensor • ±0.2% Accuracy
excitation to common values of 4mA or 9mA with a compliance voltage of • ±0.01% Linearity
24VDC. Programmable gains of 1, 10 and 100 are selectable and the module • Low Drift with Ambient Temperature
offers a ±10V output. The required supply level is +5VDC, ±5%.
• –40°C to +85°C Operating Temperature Range
To ensure protection of expensive data acquisition equipment, the SCM5B48 • CE Compliant, CSA C/US Certification Pending
module signal inputs and sensor excitation outputs are protected against
accidental connection of voltages up to 240Vrms. • Mix and Match SCM5B Types on Backpanel
SCM5B
Module SCM5B48
Excitation
Constant Current(2) 4mA or 9mA, ±10%
Compliance Voltage 24V ±10%
Protection
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1
Gain
Programmable(2) 1, 10, 100
Ordering Information
Mechanical Isolation Voltage
Model Input Range Output Range Bandwidth Format (Vrms)
SCM5B48-01 ± 10V max(1) ± 10V 2.5kHz to 20kHz(2) Modular plug-in board 1500
SCM5B49
Voltage Output Modules
Description
Each SCM5B49 voltage output module provides a single channel of analog
output. The track-and-hold circuit in the input stage can be operated in a hold
Features
mode where one DAC can supply many output modules, or a track mode where • Accepts High-Level Voltage Inputs to ±10V
one DAC is dedicated to each module. In addition to the track-and-hold circuit, • Provides High-Level Voltage Outputs to ±10V
each module provides signal buffering, isolation, filtering, and conversion to a
high-level voltage output. • 1500 Vrms Transformer Isolation
Setting of the track or hold mode is controlled by the logic state of WR EN\, • ANSI/IEEE C37.90.1 Transient Protection
module pin 23. When pin 23 is low, the track mode is enabled. If pin 23 is high, • 5 Poles of Filtering
the hold mode is enabled. The module is designed with a completely isolated • 110dB CMR
computer side circuit which can be floated to ±50V from Power Common, pin 16.
This complete isolation means that no connection is required between I/O • 400Hz Signal Bandwidth
Common and Power Common for proper operation of the track and hold circuit. • ±0.03% Accuracy
For a low state, simply connect pin 23, the Write-Enable pin, to I/O Common, pin 19.
• ±0.015% Linearity
The SCMPB02 and SCMPB06 backpanels allow host computer control of the • CSA C/US Certified, CE and ATEX Compliant
WR EN\ control line, which allows multiplexing of one host DAC to up to 64
SCM5B49 output modules. • Mix and Match SCM5B Types on Backpanel
SCM5B
Module SCM5B49 Model Input Range Output Range
Input Voltage Range ±5V, 0 to +5V, ±10V, 0 to +10V SCM5B49-01 0V to +5V –5V to +5V
Input Voltage Maximum ±36V (no damage)
SCM5B49-02 –5V to +5V –5V to +5V
Input Resistance 50MΩ
SCM5B49-03 –5V to +5V 0V to +5V
Output Voltage Range ±5V, 0 to +5V, ±10V, 0 to +10V
SCM5B49-04 0V to +10V –10V to +10V
Over Range Capability 5% at 10V output
Output Drive 50mA max SCM5B49-05 –10V to +10V –10V to +10V
Output Resistance 0.5Ω SCM5B49-06 –10V to +10V 0V to +10V
Output I Under Fault, Max 75mA SCM5B49-07 –5V to +5V –10V to +10V
Output Protection
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1
CMV, Output to Input
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 110dB
NMR (–3dB at 400Hz) 80dB per Decade Above 400Hz
Accuracy(1) ±0.03% Span (0-5mA Load)
Linearity ±0.015% Span
Stability
Zero ±25ppm/°C
Span ±20ppm/°C
Noise
Output Ripple, 2mVp-p
100kHz bandwidth
Bandwidth, –3dB 400Hz
Response Time, 90% Span 1.25ms
Sample and Hold
Output Droop Rate 0.2% Span/s
Acquisition Time 50µs
Track-and-Hold Enable Control
Max Logic “0” +0.8V
Min Logic “1” +2.4V
Max Logic “1” +36V
Input Current “0” 0.5µA
Power Supply Voltage +5VDC ±5%
Power Supply Current 350mA Full Load, 135mA no load
Power Supply Sensitivity ±12.5ppm/%
Mechanical Dimensions 2.28" x 2.26" x 0.60"
(h)(w)(d) (58mm x 57mm x 15mm)
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability.
SCM5B
Module Dimensions and Pinouts
The following mechanical drawing is useful if designing circuit boards to number 50865-5. The captive nut for the 3mm mounting screw can be obtained
mount the SCM5B modules. Many sockets are available which accept from PEM (Penn Engineering and Manufacturing), part number KFS2-M3.
the mounting pins. As an example, AMP Inc. provides a socket with part
SCMVAS
SCM5B
Voltage Attenuator System
Description
The SCMVAS (Signal Conditioning Modular Voltage Attenuator System) is an
analog signal conditioning system designed to safely monitor and accurately Features
measure voltage potentials up to 495VAC (1400V peak-to-peak). These high- • Accepts High Voltage Signals up to 495VAC
level voltages are typically found in industrial applications such as induction (1400V Peak-to-Peak)
heaters or electric-motor drive controllers. The system reduces the input signal
• 5 or 10 Volt Output for A/D Systems
to a level suitable for interface to data acquisition systems, while at the same
time providing various filter characteristics and 1500Vrms isolation (Figure 1). • 1500Vrms Transformer Isolation
For each channel of analog input, an attenuator module, SCMVAS-Mnnn, • True 3-Way Isolation
pre-conditions the signal which is then filtered, isolated, and converted to a • Up to 160dB CMR
high-level voltage output using an SCM5B30-07 or SCM5B40-07 module. The • ±0.06% Accuracy
SCM5B40-07 module with a 10kHz bandwidth is recommended for common 50/
60Hz signals low in harmonics where the user is interested in measuring only • Panel or DIN Rail Mounting Options
AC voltage. The SCM5B30-07 module is used for low frequency AC signals • CSA Certified and CE Compliant
below 4Hz. The attenuator and signal conditioning modules have excellent
• ATEX Compliant (all models except
stability over time and do not require recalibration. Overall system accuracy is
SCMVAS-M400, -M500, -M600, -M650)
±0.06%.
Input signal connections to the SCMVAS-Mnnn attenuator module are made
using a pluggable terminal block for ease of system assembly and reconfiguration.
For safety purposes, the terminal block has a cover over the screws and there
are no other exposed high-voltage points on the SCMVAS-Mnnn series mod-
ules, SCM5B30-07 or SCM5B40-07 module, or the mounting backpanel.
The SCMVAS system has two specially designed backpanels for mounting the
attenuator and signal conditioning modules. The SCMVAS-PB8 high density, 8-
channel backpanel (Figures 2, 3) can be panel mounted or DIN rail mounted and
provides the conditioned output signal on screw terminal blocks. Jumpers are
provided on each channel to optionally connect or isolate each module’s I/O
Common from other channel’s I/O Common and/or Power Common. The
SCMVAS-PB16 (Figures 4, 5) has 16 channels of analog I/O simultaneously
available to high-speed data acquisition (ADC) boards through a 26-conductor
ribbon cable. Refer to the SCMPB01 Data Sheet in this catalog and Application
Note AN502 at www.dataforth.com for recommended ground connections and
host system interfaces. Both the SCMVAS-PB8 and SCMVAS-PB16 backpanels
can be mounted on the SCMXRK-002 19-inch metal rack.
SCM5B30/40-07
Isolated Analog Voltage Input Modules
Specifications Typical at TA=+25°C and +5V power Ordering Information
Module SCM5B30-07 SCM5B40-07 Model Description
Input Range –1.0V to +1.0V * SCM5B30-07 V Isolation Module, ±5V Output, 4Hz Bandwidth
Input Bias Current ±0.5nA * SCM5B40-07 V Isolation Module, ±5V Output, 10kHz Bandwidth
Input Resistance
Normal 50MΩ 200MΩ SCM5B30-07D V Isolation Module, ±10V Output, 4Hz Bandwidth
Power Off 40kΩ * SCM5B40-07D V Isolation Module, ±10V Output, 10kHz Bandwidth
Overload 40kΩ *
Input Protection
Continuous 240Vrms max *
Transient ANSI/IEEE C37.90.1 *
Noise
Input, DC to 10Hz 2µ Vrms *
Output, 100kHz 200µ Vrms 2mVp-p
SCMVAS-Mnnn
SCM5B
High Voltage Attenuator Modules
Specifications Typical at TA=+25°C
Module SCMVAS-Mnnn
Input Range ±100Vpeak to ±700Vpeak (70VAC to 495VAC)
Input Voltage Maximum ±750Vpeak
Input Resistance 10MΩ
Accuracy ±0.03%
Stability ±50ppm/°C
Ordering Information
Model Description Input Range with V Isolation Module
SCM5B
Figure 5: SCMVAS-PB16 Schematic
Features
• 1-, 2-, 8-, 16-Position Backpanels • Interface Cables
• Panel or DIN Rail Mounting Options • Module Evaluation Board
• 19-Inch Mounting Rack For Backpanels • Cable-to-Screw-Terminal Interface Board
• Multiplexed and Non-Multiplexed Backpanels • Power Supplies
SCMPB01
16-Position Analog I/O Backpanel,
Non-Multiplexed
Description
The SCMPB01 16-channel backpanel (Figure 1) can accept any of the SCM5B Specifications
analog modules in any mixture. It can be mounted on the SCMXRK-002 19-inch
metal rack. The SCMPB01 has 16 non-addressable analog I/O signal channels Operating Temperature –40°C to +85°C
Relative Humidity 95% Noncondensing
which provides each module with it’s own analog bus. The module output switch
is continuously “on” when using this backpanel and all sixteen module outputs Interface Connector:
are simultaneously accessible to high-speed data acquisition (ADC) boards. A Field high density screw clamp, 14 AWG max
System 26-pin, male header connector
set of inter-channel bridge jumpers permits connecting an input module’s output
to an output module’s input, providing two levels of isolation. A temperature Isolation:
sensor is mounted on each channel to provide cold junction compensation for Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
thermocouple input modules (see Figure 2 for schematic). Field connections are
terminated with four screw terminals at each module site. Use system interface
cable SCMXCA004-XX for connection to the host system.
SCM5B
Power
The SCMPB01 backpanel requires external +5VDC ±5% power. The chassis
mounted SCMXPRE-003 or SCMXPRT-003 power supplies have adequate
capacity to power any combination of modules.
Figure 4: SCMPB01 Grounding Diagram
Fusing
If the connection of power common and AGND shield wires exist in the host
The SCMPB01 backpanel power is fuse protected through F1. This is a
measurement system, an optional resistive connection between AGND and
Littelfuse type 252007, 7 amp fuse. Zener diode DZ1 provides extra protection
the backpanel signal ground can be made via R1. R1 can be as large as 10K
by clamping the input power voltage to +5.6V. If the input supply voltage
ohms; 100 ohms is a recommended value. Jumper J2 can be used to connect
connection is reversed, this zener diode will be forward biased and fuse F1
the SENSE line to R1 when this ground configuration is used.
will be blown.
Grounding For full protection against large electrical disturbances on the field-side of the
SCM5B modules, a #10-32 ground stud is provided on the backpanel. An
Figure 4 details the optional ground jumper configuration available on the electrical connection between this ground stud and system ground should be
SCMPB01 backpanel. Jumpers J1, J3, and J4 are factory installed. provided with a large gauge wire of the shortest possible length. When this
connection is made, a possible ground loop could result through the AGND
Jumper J1 connects the AGND shield wires (pins 3, 6, 9, 12, 15, 18, 21, and 24)
shield wires and backpanel signal ground. If the application involves only input
to the backpanel signal ground. This provides a ground connection between the
modules and a differential input is used by the host measurement system, J1
host system and backpanel. Jumper J1 is required if output modules (SCM5B39,
should be removed. Remember that J1 is required if output modules are used
SCM5B49) are used, or if there is no high impedance sense input (input low of
or if the host system does not have differential inputs.
a differential or pseudo-differential system) on the host measurement system.
Jumper J3 connects the SENSE line (pin 25) to the backpanel signal ground. If
the host system has the capability, this allows measuring the SCMPB01
ground potential.
SCMPB02
SCM5B
16-Position Analog I/O Backpanel, Multiplexed
Description Specifications
The SCMPB02 16-channel backpanel (Figure 5) can accept any of the SCM5B Operating Temperature –40°C to +85°C
analog modules in any mixture. It can be mounted on the SCMXRK-002 19-inch Relative Humidity 95% Noncondensing
metal rack. The SCMPB02 has two analog buses; one for analog input and one Interface Connector:
for analog output. This two-bus configuration takes advantage of the switch Field high density screw clamp, 14 AWG max
controlled outputs on the input modules and the track-and-hold inputs on the System 26-pin, male header connector
output modules. A temperature sensor is mounted on each channel to provide Isolation:
cold junction compensation for thermocouple input modules (see Figure 6 for Input-to-Output 1500Vrms continuous, max
schematic). Field connections are terminated with four screw terminals at each Channel-to-Channel 1500Vrms continuous, max
module site. Up to four SCMPB02 backpanels may be daisy-chained.Use
SCMXCA004-XX cable for daisy chaining and connecting to host computer. Address Input Logic Levels:
Max Logic “0” 0.8V
Min Logic “1” 2.0V
SCM5B
P1 Connector Part Number Description
The 26 pin P1 and P2 connectors provide the signal interface between the
SCMPB02 16-channel backpanel with standoffs for mounting.
SCMPB02 backpanel and the host measurement system. Two separate analog
bus connections are provided; one for analog input signals and one for SCMPB02-1 16-channel backpanel without cold junction compensation
analog output signals. Two sets of six address lines and an enable pin allow circuits and standoffs for mounting. Use when cost savings is
input and output modules to be independently multiplexed onto their respective desired and thermocouple input modules SCM5B37 and
SCM5B47 will not be used.
analog signal bus. R0 thru R5 and RD EN\ are used for input modules, and W0
thru W5 and WR EN\ are used for output modules. SCMPB02-2 16-channel backpanel with DIN rail mounting option. The
backpanel is mounted on a plate which is captured by the
Address Selection SCMXBExx DIN rail mounting elements. Shipped fully
assembled.
The SCMPB02 backpanel has address decoding circuitry to allow multiplexing
any combination of up to 16 input or output modules. Capability is also provided SCMPB02-3 16-channel backpanel without cold junction compensation
in the address decode circuitry to expand the system to 64 channels (four circuits and with DIN rail mounting option. Shipped fully
assembled.
SCMPB02 backpanels) of multiplexed input or output. Jumpers on HD10
header, E1 and E2 group, select which set of 16 addresses are assigned to a
particular backpanel. The E1 group assigns a set of 16 addresses for input For proper operation of the output switch or track-and-hold circuit when using
modules, and the E2 group assigns a set of 16 addresses for output modules. the SCMPB02/06 backpanels, a current path must exist between the host
The table below shows the correlation of jumper position to address range. control logic power common and module I/O Common (module pin 19). This
path can be established on the SCMPB02 via jumper J4. If this connection exists
E1 Jumper Pos E2 Jumper Pos Address Range/Mode
elsewhere in the system, jumper J4 should be removed since possible ground
4 4 0-15, STAND ALONE loops could exist. Other connections of power ground and signal ground usually
3 3 48-63, EXPANDED occur at the A/D or D/A converter of the host measurement system. More
information on grounding can be found in Application Note AN502.
2 2 32-47, EXPANDED
If the connection of power common and SIG COM shield wires exist in the host
1 1 16-31, EXPANDED
measurement system, a resistive connection between SIG COM and the
0 0 0-15, EXPANDED backpanel signal ground can be made via R1. R1 can be as large as 10K ohms;
To connect multiple SCMPB02 backpanels in this expanded configuration, use 100 ohms is a recommended value. Jumper J3 can be used to connect the SNS
interconnect cable SCMXCA004-XX. LO line to R1 when this ground configuration is used.
Modules with system output of ±10V or 0-10V cannot be mixed with modules For full protection against large electrical disturbances on the field-side of the
with system output of ±5V or 0-5V within a given system. SCM5B modules, a #10-32 ground stud is provided on the backpanel. An
electrical connection between this ground stud and system ground should be
Power provided with a large gauge wire of the shortest possible length. When this
The SCMPB02 backpanel requires external +5VDC ±5% power. The chassis connection is made, a possible ground loop could result through the SIG COM
mounted SCMXPRE-003 or SCMXPRT-003 power supplies have adequate shield wires and backpanel signal ground. If the application involves only input
capacity to power any combination of modules. modules and a differential input is used by the host measurement system, J1
should be removed. Remember that J1 is required if output modules are used
Fusing or if the host system does not have differential inputs.
The SCMPB02 backpanel power is fuse protected through F1. This is a
Littelfuse type 252007, 7 amp fuse. Zener diode DZ1 provides extra protection
by clamping the input power voltage to +5.6V. If the input supply voltage
connection is reversed, this zener diode will be forward biased and fuse F1 will
be blown.
Grounding
Figure 7 below details the optional ground jumper configuration available on the
SCMPB02 backpanel. Jumpers J1, J2, and J4 are factory installed.
Jumper J1 connects the SIG COM shield wires (pins 2, 5, and 6) to the backpanel
signal ground. This provides a ground connection between the host system and
backpanel. Jumper J1 is required if output modules (SCM5B39, SCM5B49) are
used, or if there is no high impedance sense input (input low of a differential or Figure 7: SCMPB02 Grounding Diagram
pseudo-differential system) on the host measurement system.
Jumper J2 connects the SNS LO line (pin 4) to the backpanel signal ground. If
the host system has the capability, this allows measuring the SCMPB02
ground potential.
SCMPB03/SCMPB04
One/Two Position Analog I/O Backpanels
Description Ordering Information
The SCMPB03 and SCMPB04 are single and dual channel mounting panels Part Number Description
for the SCM5B modules. Both are intended for DIN rail mounting.
See Figures 9 and 10 for wiring diagrams, Figure 11 for schematic. SCMPB03 Single channel backpanel. No mounting hardware included.
The following accessories are required for mounting one SCMPB03/04 panel SCMPB03-2 Single channel backpanel with DIN rail mounting hardware.
(Figure 8): Shipped fully assembled.
Qty Model Description SCMPB04 Dual channel backpanel. No mounting hardware included.
1 SCMXBEFE Base element with snap foot SCMPB04-1 Dual channel backpanel without cold junction compensation
2 SCMXSE Side element circuits. Use when cost savings is desired and thermocouple
input modules SCM5B37 and SCMPB47 will not be used. No
The following accessories are required for mounting two or more mounting hardware included.
SCMPB03/04 panels: SCMPB04-2 Dual channel backpanel with DIN rail mounting hardware.
Qty Model Description Shipped fully assembled.
2 SCMXBEFE Base element with snap foot SCMPB04-3 Dual channel backpanel without cold junction compensation
circuits and with DIN rail mounting hardware. Shipped fully
2 SCMXSE Side element assembled.
(# panels)-2 SCMXBE Base element without snap foot
(4 x (# panels))-4 SCMXVS Connection pins
The following DIN rail styles are available. Specify length in meters (-XX)
SCMXRAIL1-XX DIN EN 50022-35x7.5 (slotted steel)
SCMXRAIL2-XX DIN EN 50035-G32 (slotted steel)
SCMXRAIL3-XX DIN EN 50022-35x15 (slotted steel)
Specifications
Operating Temperature –40°C to +85°C
Relative Humidity 95% Noncondensing
Interface Connector:
Field high density screw clamp, 14 AWG max
System high density screw clamp, 14 AWG max Figure 9: SCMPB03 Analog I/O Backpanel
Isolation:
Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
SCM5B
NOTES:
1. Jumpers Jn are on SCMPB07
only. Factory installed.
2. Jumper Jm is factory installed
and is a OΩ resistor.
3. SCMXCJC are CJC
temperature sensors.
4. Resistors SCMXR1 are
optional I/V conversion
resistors for current inputs, not
factory installed.
5. Fuse is on SCMPB07 only.
SCMPB05
8-Position Analog I/O Backpanel, Non-Multiplexed
Description Ordering Information
The SCMPB05 backpanel (Figure 12) can accept up to eight SCM5B analog Part Number Description
input and/or output modules in any combination. It can be mounted on the
SCMXRK-002 19-inch metal rack. A separate analog signal path is provided for SCMPB05 8-channel backpanel with standoffs for mounting.
each channel and each channel’s signal is accessible at redundant SCMPB05-1 8-channel backpanel without cold junction compensation
26-pin connectors. The module output switch is continuously “on” when using circuits and standoffs for mounting. Use when cost savings is
this backpanel and all eight module outputs are simultaneously accessible to desired and thermocouple input modules SCM5B37 and
SCM5B47 will not be used.
high-speed data acquistion (ADC) boards.
SCMPB05-2 8-channel backpanel with DIN rail mounting option. The
On-board jumpers permit paralleling two SCMPB05 boards to form a SCMPB01 backpanel is mounted on a plate which is captured by the
equivalent. An additional set of inter-channel bridge jumpers permits connecting SCMXBExx DIN rail mounting elements. Shipped fully
assembled.
an input module’s output to an output module’s input, providing two levels of
isolation (Figures 12, 13). SCMPB05-3 8-channel backpanel without cold junction compensation circuits
and with DIN rail mounting option. Shipped fully assembled.
Jumpers on the SCMPB05 permit user selection of low (i.e. channels 0-7) or high
(i.e. channels 8-15) addresses. Electrical
A temperature sensor mounted on each channel provides cold junction Address Selection
compensation for thermocouple input modules (see Fig. 13 for schematic). Field Module addresses may be selected as low (channels 0-7) or high (channels 8-
connections are terminated with four screw terminals at each module site. Use 15) using the sets of 3 pins labeled J5 through J12. Place a jumper over the two
system interface cable SCMXCA004-XX for connection to the host system. pins closest to the ribbon cable connectors, P1 and P2, to select a low address
(factory configuration) or over the two pins furthest from the ribbon cable
Specifications connectors, P1 and P2, to select a high address.
Operating Temperature –40°C to +85°C Adjacent Channel Jumper
Relative Humidity 95% Noncondensing
Interface Connector: Adjacent channels may be connected together to provide an isolated output
Field high density screw clamp, 14 AWG max signal from an isolated input module, providing two levels of 1500V isolation.
System 26-pin, male header connector This capability is provided with the seven jumpers labeled JP1–JP7. See page
Isolation: 48 for an example.
Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
Refer to page 50 for additional notes on the P1 and P2 connectors, power
requirements, fusing and grounding issues.
SCM5B
SCMPB06
8-Position Analog I/O Backpanel, Multiplexed
Description Ordering Information
The SCMPB06 backpanel (Figure 14) can accept up to eight SCM5B modules Part Number Description
in any combination. It can be mounted on the SCMXRK-002 19-inch metal rack.
The SCMPB06 has two analog buses; one for analog input and one for analog SCMPB06 8-channel backpanel with standoffs for mounting.
output. This two-bus configuration takes advantage of the switch controlled SCMPB06-1 8-channel backpanel without cold junction compensation
outputs on the input modules and the track-and-hold inputs on the output circuits and standoffs for mounting. Use when cost savings is
modules. A temperature sensor is mounted on each channel to provide cold desired and thermocouple input modules SCM5B37 and
junction compensation for thermocouple input modules (see Figure 15 for SCM5B47 will not be used.
schematic). Field connections are terminated with four screw terminals at each SCMPB06-2 8-channel backpanel with DIN rail mounting option. The
module site. Up to eight SCMPB06 backpanels may be daisy-chained. Use backpanel is mounted on a plate which is captured by the
SCMXBExx DIN rail mounting elements. Shipped fully
SCMXCA004-XX cable for daisy chaining and connecting to host computer. assembled.
Jumpers on the SCMPB06 permit user selection of low (i.e. channels 0-7) or high SCMPB06-3 8-channel backpanel without cold junction compensation circuits
(i.e. channels 8-15) addresses. and with DIN rail mounting option. Shipped fully assembled.
Electrical
Specifications
Address Selection
Operating Temperature –40°C to +85°C
Module read and write addresses may be selected as low (channels 0-7) or high Relative Humidity 95% Noncondensing
(channels 8-15) using the four sets of 3 position jumpers labeled J5 through J8. Interface Connector:
Place a jumper over the two pins furthest from the field I/O termination blocks Field high density screw clamp, 14 AWG max
on all four sets to select a low address (factory configuration) or over the two pins System 26-pin, male header connector
closest to the field I/O termination blocks on all four sets to select a high address. Isolation:
Input-to-Output 1500Vrms continuous, max
The SCMPB06 backpanel has address decoding circuitry to allow multiplexing any Channel-to-Channel 1500Vrms continuous, max
combination of up to 8 input or output modules. Capability is also provided in the Address Input Logic Levels:
address decode circuitry to expand the system to 64 channels (eight SCMPB06 Max Logic “0” 0.8V
backpanels) of multiplexed input or output. Jumpers select which set of 16 Min Logic “1” 2.0V
addresses are assigned to a particular backpanel. The Read Address group
II Input Current, “0” or “1” 0.1µA max at 25°C
assigns a set of 16 addresses for input modules, and the Write Address group 1.0µA max –25°C to +85°C
assigns a set of 16 addresses for output modules. The table on the next page shows
RD EN\ or WR EN\ Signal Delay
the correlation of jumper position to address range. Refer to page 53 for additional
from Connector P1 to Channels 0-7
notes on the P1 and P4 connectors, power requirements, fusing, and grounding issues. Standalone (address 0-7) 51ns at 25°C, 64ns at –25°C to +85°C
Expanded (address 8-63) 100ns at 25°C, 126ns at –25°C to +85°C
Modules with system output of ±10V or 0-10V cannot be mixed with modules
with system output of ±5V or 0-5V within a given system.
SCM5B
Address Selection Jumpers
Read Write High/Low
Address Address Channel Address
Jumper (P2) Jumper (P3) (J5,J6,J7,J8) Address Range
1 6 L 0-7 Stand Alone
1 6 H 8-15 Stand Alone
2 7 L 48-55 Expanded
2 7 H 56-63 Expanded
3 8 L 32-39 Expanded
3 8 H 40-47 Expanded
4 9 L 16-23 Expanded
4 9 H 24-31 Expanded
5 10 L 0-7 Expanded
5 10 H 8-15 Expanded
SCMPB07
8-Position Backpanel, High Density
Description Ordering Information
The SCMPB07 8-channel high-density backpanel can accept any of the SCM5B Part Number Description
analog modules in any mixture. Its overall width is 5.5 inches (139.7mm) versus
10 inches (254mm) for the SCMPB05 and SCMPB06 8-channel backpanels. SCMPB07 8-channel backpanel. No mounting hardware included.
Separate analog signal paths are provided for each channel. Each channel SCMPB07-1 8-channel backpanel without cold junction compensation
provides four high-density screw terminals for field connections and circuits. Use when cost savings is desired and thermocouple
two high-density screw terminals for host system connection. It also provides a input modules SCM5B37 and SCMPB47 will not be used.
jumper on each channel to optionally connect or isolate each module’s I/O SCMPB07-2 8-channel backpanel with DIN rail mounting hardware. Shipped
common from other channel's I/O common and/or power common (Figure 16). fully assembled.
See Figure 11 on page 55 for schematic. SCMPB07-3 8-channel backpanel without cold junction compensation
circuits and with DIN rail mounting hardware. Shipped fully
assembled.
Specifications
Operating Temperature –40°C to +85°C
Relative Humidity 95% Noncondensing
Interface Connector:
Field high density screw clamp, 14 AWG max
System high density screw clamp, 14 AWG max
Isolation:
Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
SCMXEV
SCM5B
Analog Module Evaluation Board
Description
The SCMXEV is a single channel board with a test socket for SCM5B module
evaluation (Figure 17). All signal input/output, control, and power connections
are connected to terminal blocks for ease of user access. A cold junction
temperature sensor circuit is included for evaluation of thermocouple modules
(see Figure 18 for schematic).
The SCMXEV is mechanically compatible with DIN rail mounting. Phoenix
brand Universal Module (UM) elements may be used. The following Phoenix
parts would be used to mount one SCMXEV.
2, UM-BEFE base elements with snap foot
2, UM-SE side elements
4, UM-VS connection pins
Two jumpers are provided for customer use. The first, J1, provides a current
path between +5V Power Common (module pin 16) and I/O Common (module
pin 19). A path must exist between the host control logic power common and
module I/O Common for proper operation of the module output switch or track-
and-hold circuit. If this connection exists elsewhere in the system, jumper J1
should be removed since possible ground loops could exist. Other connections
of power ground and signal ground usually occur at the A/D or D/A converter of Figure 17: SCMXEV Evaluation Board Dimensions and Pin Layout
the host measurement system.
Jumper J2 is used in the cold junction compensation circuit. If it is installed, the should be removed. The external voltage is applied at the sockets labled CJC+
compensation circuit is enabled and will provide the proper compensation and CJC–. An external voltage of 510.0mV corresponds to an ambient tempera-
voltage to correct for the thermoelectric effect at the +In and –In screw terminals. ture of +25 °C. The transfer function of the onboard compensation circuit is VCJC
If an external simulation voltage is desired for cold junction compensation, J2 = 0.510 –0.0025(T–25)V.
SCMXRK-002
19-Inch Metal Mounting Rack
Description
The SCMXRK-002 is a 19-inch metal rack for mounting the SCMPB01/02/05/06, SCM7BP04/08/16, SCMVAS-PB8/16 and isoLynx® SLX200-xx backpanels. It
also provides capability to mount the SCMXPRT-001, SCMXPRE-001, SCMXPRT-003 or SCMXPRE-003 power supplies, and the SCMXIF interface board (see
Figure 21 for dimensions).
SCMXCJC
SCM5B
Encapsulated Cold Junction Compensation
Description
The SCMXCJC is the identical circuit used on the SCMPB01/02/03/04/05/06/07
backpanels except it is packaged as a component for use in customer designed
mounting boards (Figure 22). When interfaced to an SCM5B37 or 47 module the
transfer function of the voltage across the +SEN and –SEN pins is VCJC = 0.510
–0.0025(T –25)V.
Specifications
Accuracy +25°C ±0.25°C
+5°C to +45°C ±0.5°C
–40°C to +85°C ±1.25°C
SCM5BPT-1367 input module or SCM5B42 two-wire transmitter interface module (Figure 23).
Sockets are provided on the SCMPB01/02/03/04/05/06/07 and SCMXEV
Pass Thru Module with Switch backpanels to allow installation of this resistor. One SCMXR1 is shipped with
each SCM5B32 or SCM5B42 module.
Description
The SCM5BPT-1367 is a pass-through module used to establish a direct
connection between an input signal and the SCM5B series backplane analog
bus. It has unity gain, no isolation, and a logic controlled output switch which
allows sharing of a common analog bus with other SCM5B modules. It accepts
up to ± 10V input and provides up to ± 10V output. Resettable fuses and
overvoltage protection circuitry protect computer-side electronics.
SCMXJP-003
Jumper Strap
Description
Package of 10 jumpers for connecting adjacent input/output modules on the
SCMPB01 backpanel. This connection is made if it is desired to direct the output
of any input module to the input of an adjacent output module. The jumpers can
also be used for configuring I/O addresses on the SCMPB02 backpanel.
Fuse
Ordering Information
Description
Part Number Description
Package of 10 fuses for use on the SCMPBxx backpanels. This is a series fuse
in the five volt power line. It provides protection against inadvertent reverse SCMXFS-003 4A fuse. Use for SCMPB05/06/07, SCMVAS-PB8, -PB16.
connection of five volt power or overvoltage. SCMXFS-004 7A fuse. Use for SCMPB01/02.
SCM5B-PROTO
Breadboard Kit
Description
The SCM5B-PROTO breadboard kit was designed to allow users to incorporate designed for breadboard circuits, a module case, header and mounting screw.
their own module functions using an SCM5B format. The kit includes a pc board Contact the factory for additional information.
SCMXPRT-001/D, SCMXPRE-001/D
Power Supplies
Description
The SCMXPRT-001/D and SCMXPRE-001/D encapsulated power supplies are
available in 120VAC or 220VAC input voltage ranges and provide 5VDC outputs
suitable for all SCM5B modules. They are designed to mount on the SCMXRK-
002 metal rack or DIN rail EN 50022-35x7.5 (D versions). The supplies are
UL-recognized. Their compact size and low weight are ideal for high-density
applications (see Figure 25).
Specifications
Module SCMXPRT-001/D SCMXPRE-001/D
Input Voltage Range, 105-125VAC 200-240VAC
47Hz to 63Hz
Output Voltage 5VDC 5VDC
Output Current, +50°C 1A 1A
(derate 2.5%/°C above +50°C)
Operating Temperature –25°C to +71°C –25°C to +71°C
Dielectric Withstand V 2500Vrms 2500Vrms
(Input to Ground)
Line Regulation ±0.05% ±0.05%
Load Regulation ±0.15% ±0.15%
Output Ripple, max 2mVrms 2mVrms
Overvoltage Protection 6.2V 6.2V
Weight 1.25 lbs (567g) 1.25 lbs (567g)
Supplies are UL recognized, File No. E65890.
SCMXPRT-003, SCMXPRE-003
SCM5B
Power Supplies
Description
The SCMXPRT/E-003 Linear Power Supplies are available in 120VAC or
220VAC input. They have sufficient output current capacity to supply any
combination of SCM5B modules. The SCMXRK-002 metal rack provides
mounting capability for the SCMXPRT/E-003 power supplies (see Figure 26).
Specifications
Module SCMXPRT-003 SCMXPRE-003
Both supplies are tested and certified by TUV to VDE 0806 and IEC 380. They are UL Recognized (File Number E55974)
and CSA Certified (CSA File Number LR38879).
SCM7B
Isolated Process Control Signal Conditioning Products
Features
• ±0.03% Accuracy (Typical)
• ±0.01% Linearity
• 1500Vrms Transformer Isolation &
120Vrms Field-side Protection
• ANSI/IEEE C37.90.1 Transient Protection
• Wide Supply Voltage, 14 to 35VDC
• 5-Pole Low-Pass Filtering
• Low Peak and RMS Noise
• Low Drift Input Circuitry for Long-Term Stability
• Up to 160dB CMRR
• 85dB NMR at 60Hz, 80dB at 50Hz
• –40°C to +85°C Operating Temperature
• Backpanels Allow Use of Industry Standard
Digital I/O, Solid State Relay Modules
• DIN Rail Mounting
• CSA C/US Certified
SCM7B Modules
(Class I, Division 2, Groups A, B, C, D)
SCM7B Isolated Process Control Signal Conditioning modules include a • CE and ATEX Compliant
complete selection of backpanels, DIN rail mounting accessories, interface
cables, and rack mounting hardware. Each SCM7B module provides a single • Manufactured per RoHS Directive 2002/95/EC
channel of isolated analog input or output. Various input modules accept analog
voltage or current signals from all types of field sensors and sources, filter, isolate,
amplify, linearize, and convert these input signals to high-level analog outputs Custom Signal Conditioning
suitable for use in a process control system. Output modules accept high-level Custom modules are available: consult factory for minimum quantity and pricing
analog voltage signals from a process control system, then buffer, isolate, filter, details on custom input ranges, output ranges, bandwidth, and other key
and amplify before providing a current or voltage output to a field device. parameters.
ISOLATED VOLTAGE OUTPUT MODULES Page 70 ISOLATED LINEARIZED 120Ω Ni RTD INPUT MODULES ** Page 74
MODEL INPUT RANGE OUTPUT RANGE MODEL INPUT RANGE OUTPUT RANGE
SCM7B22 ±10V ±10V OF SPAN SCM7B34N-01 0°C to +300°C (+32°F to +572°F) †
†
SCM7B34N-02 0°C to +200°C (+32°F to +392°F)
ISOLATED 2-WIRE XMTR INTERFACE MODULES WITH LOOP POWER Page 76 ACCESSORIES Page 89
MODEL INPUT RANGE OUTPUT RANGE MODEL DESCRIPTION
SCM7B35-01 4 to 20mA † SCM7BXEV 1 channel evaluation backpanel
SCM7B35-02 4 to 20mA +2 to +10V SCM7BP01 1 channel backpanel
SCM7BP02 2 channel backpanel
SCM7B
ISOLATED POTENTIOMETER INPUT MODULES Page 78 SCM7BP01-DIN SCM7BP01 with DIN rail mounting option
MODEL INPUT RANGE OUTPUT RANGE SCM7BP02-DIN SCM7BP02 with DIN rail mounting option
SCMXBEFE DIN Base element with snap foot
†
SCM7B36-01 0 to 100Ω SCMXBE DIN Base element without snap foot
†
SCM7B36-02 0 to 200Ω SCMXSE DIN Side elements
†
SCM7B36-03 0 to 500Ω SCMXVS DIN Connection pins
†
SCM7B36-04 0 to 1kΩ SCMXRAIL1-XX DIN EN 50022-35x7.5 (slotted steel), length -XX in meters
†
SCM7B36-05 0 to 5kΩ SCMXRAIL2-XX DIN EN 50035-G32 (slotted steel), length -XX in meters
†
SCM7B36-06 0 to 10kΩ SCMXRAIL3-XX DIN EN 50022-35x15 (slotted steel), length -XX in meters
SCM7BP04 4 channel backpanel
ISOLATED THERMOCOUPLE INPUT MODULES Page 80 SCM7BP04-DIN SCM7BP04 with DIN rail mounting option
MODEL TYPE‡ INPUT RANGE OUTPUT RANGE SCM7BP08 8 channel backpanel
†
SCM7BP08-DIN SCM7BP08 with DIN rail mounting option
SCM7B37J-01 J –100°C to +760°C (–148°F to +1400°F) SCM7BP16 16 channel backpanel
†
SCM7B37J-10 J 0°C to +200°C (+32°F to +392°F) SCM7BP16-DIN SCM7BP16 with DIN rail mounting option
†
SCM7B37J-11 J 0°C to +400°C (+32°F to +752°F) SCMXRK-002 19" rack for mounting backplanes
†
SCM7B37J-12 J 0°C to +600°C (+32°F to +1112°F) SCM7BXCA01 6" system adapter cable (DB25F to 26M)
†
SCM7B37J-13 J +300°C to +600°C (+572°F to +1112°F) SCM7BXCA02 3' system interface cable (DB25F to DB25F)
†
SCM7B37K-02 K –100°C to +1350°C (–148°F to +2462°F) SCMXCA004-XX xx-meter system interface cable (26F to 26F)
†
SCM7B37K-20 K 0°C to +300°C (+32°F to +572°F) SCMXCA006-XX System interface cable for backpanels
†
SCM7B37K-21 K 0°C to +600°C (+32°F to +1112°F) 8BXIF DB25 to screw terminal interface board
†
SCM7B37K-22 K 0°C to +1200°C (+32°F to +2192°F) SCM7BXR1 250Ω current conversion resistor
SCM7B37K-23 K +600°C to +1200°C (+1112°F to +2192°F) † SCM7BPT Non-isolated signal pass thru module
†
SCM7B37T-03 T –100°C to +400°C (–148°F to +752°F) SCM7B-PROTO Breadboard kit
†
SCM7B37E-04 E 0°C to +900°C (+32°F to +1652°F)
†
SCM7B37R-05 R 0°C to +1750°C (+32F to +3182°F) †
OUTPUT RANGES AVAILABLE
†
SCM7B37S-06 S 0°C to +1750°C (+32F to +3182°F)
†
SCM7B37B-07 B 0°C to +1800°C (+32F to +3272°F) Output Range Part No. Suffix Example
ISOLATED CURRENT OUTPUT MODULES Page 82 +1 to +5V NONE SCM7B30-01
MODEL INPUT RANGE OUTPUT RANGE 0 to +5V A SCM7B30-01A
SCM7B39-01 +1 to +5V 4 to 20mA 0 to +10V D SCM7B30-01D
SCM7B39-02 0 to +10V 0 to 20mA
SCM7B39-03 0 to +10V 4 to 20mA
SCM7B39-04 4 to 20mA 4 to 20mA POWER SUPPLIES Page 200
PWR-PS5RA Power Supply, 24V, 0.3A, 100-240VAC Input
ISOLATED VOLTAGE INPUT MODULES, WIDE BANDWIDTH Page 84 PWR-PS5RB Power Supply, 24V, 0.6A, 100-240VAC Input
MODEL INPUT RANGE OUTPUT RANGE PWR-PS5RC Power Supply, 24V, 1.3A, 100-240VAC Input
SCM7B40-02 0 to +100mV † PWR-PS5RD Power Supply, 24V, 2.1A, 100-240VAC Input
SCM7B40-03 0 to +1V † PWR-PS5RE Power Supply, 24V, 4.2A, 100-240VAC Input
†
SCM7B40-07 ±100mV
†
SCM7B40-08 ±1V ‡
THERMOCOUPLE ALLOY COMBINATIONS
†
SCM7B41-01 0 to +10V STANDARDS: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
†
SCM7B41-02 ±5V TYPE MATERIAL
†
SCM7B41-03 ±10V J Iron vs. Copper-Nickel
†
SCM7B41-04 0 to +5V K Nickel-Chromium vs. Nickel-Aluminum
†
SCM7B41-05 0 to +20V T Copper vs. Copper-Nickel
†
SCM7B41-06 0 to +40V E Nickel-Chromium vs. Copper-Nickel
R Platinum-13% Rhodium vs. Platinum
ISOLATED LINEARIZED THERMOCOUPLE INPUT MODULES Page 86 S Platinum-10% Rhodium vs. Platinum
MODEL TYPE‡ INPUT RANGE OUTPUT RANGE B Platinum-30% Rhodium vs. Platinum-6% Rhodium
†
N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4% Silicon- 0.1%
SCM7B47J-01 J 0°C to +760°C (+32°F to +1400°F) Magnesium
†
SCM7B47J-02 J –100°C to +300°C (–148°F to +572°F)
†
SCM7B47K-03 K 0°C to +1300°C (+32°F to +2372°F)
SCM7B47K-04 K 0°C to +600°C (+32°F to +1112°F) † **RTD STANDARDS
SCM7B47T-05 T 0°C to +400°C (+32°F to +752°F) † TYPE ALPHA COEFFICIENT DIN JIS IEC
SCM7B47T-06 T –100°C to +200°C (–148°F to +392°F) † 100Ω PT 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
SCM7B47E-07 E 0°C to +900°C (+32°F to +1652°F) † 120Ω NI 0.00672
†
SCM7B47R-08 R +500°C to +1750°C (+932°F to +3182°F)
†
SCM7B47S-09 S +700°C to +1750°C (+1292°F to +3182°F)
†
SCM7B47B-10 B +800°C to +1800°C (+1472°F to +3272°F)
†
SCM7B47N-11 N +200°C to +1300°C (+392°F to +2372°F)
SCM7B21/30/31
Isolated Analog Voltage Input Modules
Description
Each SCM7B21/30/31 voltage input module accepts one channel of analog
voltage input which is filtered, isolated, amplified, and converted to a high-level Features
analog voltage for output to the process control system. • Accepts Millivolt and Voltage Level Signals
These modules incorporate a five-pole filtering approach to maximize both time • Provides High-Level Voltage Outputs
and frequency response by taking advantage of both Thomson (Bessel) and • 1500Vrms Transformer Isolation
Butterworth characteristics. One pole of the filter is on the field side of the
isolation barrier; four are on the process control system side. • Accuracy, ±0.03% of Span Typical,
±0.1% Max
After the initial field-side filtering, the input signal is chopped by a proprietary
• ANSI/IEEE C37.90.1 Transient Protection
chopper circuit and transferred across the transformer isolation barrier, sup-
pressing transmission of common mode spikes and surges. The signal is then • Input Protected to 120Vrms Continuous
reconstructed and filtered for process control system output. • Noise, 500µVp-p (5MHz), 250µVrms (100kHz)
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal). • Up to 160dB CMRR
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal • 85dB NMR at 60Hz, 80dB at 50Hz
for high channel density applications. They are designed for easy DIN rail
mounting using any of the “-DIN” backpanels. • Easy DIN Rail Mounting
• CSA C/US Certified
• CE and ATEX Compliant
SCM7B
Resistance
Normal 2MΩ min 50MΩ 500kΩ min SCM7B30-05 +1 to +5V
Power Off 2MΩ min 30kΩ min 500kΩ min SCM7B30-06 ±10mV
Overload 2MΩ min 30kΩ min 500kΩ min SCM7B30-07 ±100mV
Protection SCM7B30-08 ±1V
Continuous 120Vrms max * * SCM7B31-01 0 to +10V
Transient ANSI/IEEE C37.90.1 * * SCM7B31-02 ±5V
SCM7B31-03 ±10V
Output SCM7B31-04 0 to +5V
Signal Range(1) ±10V † †
SCM7B31-05 0 to +20V
Effective Available Power(1) 10mW 40mW * SCM7B31-06 ±20V
Resistance <1Ω * * SCM7B31-07 0 to +50V
Protection Continuous Short-to-Ground * * SCM7B31-08 ±50V
Voltage/Current Limit ±12V, ±14mA * *
CMV (Input-to-Output) †
Continuous 1500Vrms max * * Output Ranges Available
Transient ANSI/IEEE C37.90.1 * *
CMRR (50 or 60Hz) 100dB 160dB 120dB Output Range Part No. Suffix Example
Accuracy(2) ±0.03% Span typical, * * +1 to +5V NONE SCM7B30-01
±0.1% Span max 0 to +5V A SCM7B30-01A
(3)
Linearity ±0.01% Span typical, * *
±0.02% Span max
0 to +10V D SCM7B30-01D
Stability (–40°C to +85°C)
Gain ±55ppm/°C ±35ppm/°C ±55ppm/°C
Input Offset N/A(4) ±0.5µV/°C ±5µV/°C
Zero Suppression N/A ±0.005%(Vz)(5)/°C *
Output Offset ±0.001% Span/°C ±0.002% Span/°C *
Noise
Peak at 5MHz B/W 1mV 500µV *
RMS at 10Hz to 100kHz B/W 250µV * *
Peak at 0.1Hz to10Hz B/W 1µV RTI * *
Frequency and Time Response
Bandwidth, –3dB 300Hz 3Hz *
NMR (50/60Hz) 80dB/decade >300Hz 80/85dB *
Step Response, 90% Span 1.5ms 165ms *
Supply Voltage 14 to 35VDC * *
Current(1) 16mA 12mA *
Sensitivity ±0.0002%/%VS ±0.0001%/%VS *
Mechanical Dimensions 2.13" x 1.705" x 0.605" max * *
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max * *
Environmental
Operating Temperature Range –40°C to +85°C * *
Storage Temperature Range –40°C to +85°C * *
Relative Humidity 0 to 95% Noncondensing * *
Emissions EN61000-6-4 ISM, Group 1 * *
Radiated, Conducted Class A * *
Immunity EN61000-6-2 ISM, Group 1 * *
RF Performance A ±0.5% Span Error * *
ESD, EFT Performance B * *
NOTES:
* Specification same as preceding model.
(1) Output Range and Supply Current specifications are based on minimum output load resistance. Minimum output load
resistance is calculated by VOUT2/PE, where PE is the Output Effective Available Power that guarantees output range, accuracy, and
linearity specifications.
(2) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(3) Linearity is calculated using the best-fit straight line method.
(4) Input offset term included in output offset specification.
(5) VZ is the nominal input voltage that results in a 0V output.
(6) SCM7B21 is available only as ±10V output.
SCM7B22
Isolated Bipolar Voltage Output Modules
Description
SCM7B22 voltage output modules accept input signals in the ±10V range from
the process control system. The signal is isolated, buffered, and filtered to
Features
provide a unity gain field voltage output (Figure 1). • Accepts High-Level Input to ±10V
These modules incorporate a five-pole filtering approach to maximize both time • Provides High-Level Output to ±10V
and frequency response by taking advantage of both Thomson (Bessel) and • 1500Vrms Transformer Isolation
Butterworth characteristics. One pole of the filter is on the process control
system side of the isolation barrier; four are on the field side. • Accuracy, ±0.03% of Span Typical,
±0.1% Max
After the initial process control system-side filtering, the input signal is chopped • ANSI/IEEE C37.90.1 Transient Protection
by a proprietary chopper circuit and transferred across the transformer isolation
barrier, suppressing transmission of common mode spikes and surges. The • Output Protected to 120Vrms Continuous
signal is then reconstructed and filtered for field-side output. • Input Protected to ±35VDC
Modules accept a wide 19 - 29VDC power supply range (+24VDC nominal). • Noise, 2mVp-p (5MHz), 1mVrms (100kHz)
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal • 100dB CMRR
for high channel density applications. They are designed for easy DIN rail
mounting using any of the “-DIN” backpanels. • Easy DIN Rail Mounting
• CSA C/US Certified
• CE and ATEX Compliant
SCM7B
Protection
Continuous 120Vrms
Transient ANSI/IEEE C37.90.1
Voltage/Current Limit ±12.5V, ±40mA
Input
Signal Range ±10V
Bias Current ±0.5nA
Resistance 2MΩ min
Protection ±35Vdc (no damage)
CMV (Input-to-Output)
Continuous 1500Vrms
Transient ANSI/IEEE C37.90.1
CMRR (50 or 60Hz) 100dB
Accuracy(1) ±0.03% Span typical,
±0.1% Span max
Linearity(2) ±0.01% Span typical,
±0.02% Span max
Stability (–40°C to +85°C)
Gain ±35ppm/°C
Output Offset ±0.001% Span/°C
Noise
Peak at 5MHz B/W 2mV
RMS at 10Hz to 100kHz B/W 1mV
Peak at 0.1Hz to 10Hz B/W 10µV RTI
Frequency and Time Response
Bandwidth, -3dB 400Hz
NMR (-3dB at 400Hz) 100dB per decade above 400Hz
Step Response, 90% Span 1ms
Supply Voltage 19 to 29VDC
Current 16mA
Sensitivity ±0.0001%/%VS
Mechanical Dimensions 2.13" x 1.705" x 0.605" max
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(2) Linearity is calculated using the best-fit straight line method.
SCM7B32/33
Isolated Process Current/Voltage Input Modules
Description
The SCM7B32 current input modules accept input signals in the 4-20mA or
0-20mA ranges from the field and provide a high-level output to the process
Features
control system (Figure 1). Current to voltage conversion occurs internal to the • Accepts Current or Voltage Input
module, which is factory calibrated to ensure the highest accuracy. • Provides High-Level Voltage Outputs
SCM7B33 voltage input modules accept input signals in the +1V to +5V or 0 to • 1500Vrms Transformer Isolation
+5V ranges from the field and provide a high-level output to the process
control system. As an alternative, the SCM7B33 can be used with an external • Accuracy, ±0.03% of Span Typical,
250Ω resistor (Dataforth SCM7BXR1 or equivalent), to accept input signals in ±0.1% Max
the 4-20mA or 0-20mA ranges. Using the external sense resistor allows the • ANSI/IEEE C37.90.1 Transient Protection
module to be removed without disrupting the current loop. All SCM7B33s are • Input Protected to 120Vrms Continuous
shipped with a SCM7BXR1 resistor.
• Noise, 500µVp-p (5MHz), 300µVrms
These modules incorporate a five-pole filtering approach to maximize both time (100kHz)
and frequency response by taking advantage of both Thomson (Bessel) and
• 105dB CMRR
Butterworth characteristics. One pole of the filter is on the field side of the
isolation barrier; four are on the process control system side. • Easy DIN Rail Mounting
After the initial field-side filtering (conversion-SCM7B32 only), the input signal • CSA C/US Certified
is chopped by a proprietary chopper circuit and transferred across the trans- • CE and ATEX Compliant
former isolation barrier, suppressing transmission of common mode spikes and
surges. The signal is then reconstructed and filtered for process control system
output.
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal).
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal
for high channel density applications. They are designed for easy DIN rail
mounting using any of the “-DIN” backpanels.
SCM7B
Resistance
Normal <100Ω 2MΩ SCM7B33-02 0 to +5V
Power Off <100Ω 2MΩ
Overload 30kΩ 2MΩ
†
Protection Output Ranges Available
Continuous 120Vrms max *
Transient ANSI/IEEE C37.90.1 * Output Range Part No. Suffix Example
Output
Signal Range(1) † † +1 to +5V NONE SCM7B32-01
Effective Available Power(1) 40mW * 0 to +5V A SCM7B32-01A
Resistance <1Ω * 0 to +10V D SCM7B32-01D
Protection Continuous Short-to-Ground *
Voltage/Current Limit ±12V, ±14mA *
CMV (Input-to-Output)
Continuous 1500Vrms *
Transient ANSI/IEEE C37.90.1 *
CMRR (50 or 60Hz) 105dB *
Accuracy(2) ±0.03% Span typical, *
±0.1% Span max
Linearity(3) ±0.01% Span typical, *
±0.02% Span max
Stability (–40°C to +85°C)
Gain ±35ppm/°C *
Input Offset N/A(4) *
Output Offset ±0.003% Span/°C *
Noise
Peak at 5MHz B/W 500µV *
RMS at 10Hz to 100kHz B/W 300µV *
Peak at 0.1Hz to 10Hz B/W 1µV RTI *
Frequency and Time Response
Bandwidth, –3dB 100Hz *
NMR (–3dB at 100Hz) 80dB per decade above 100Hz *
Step Response, 90% Span 5ms *
Supply Voltage 14 to 35VDC *
Current(1) 12mA *
Sensitivity ±0.0001%/%VS *
Mechanical Dimensions 2.13" x 1.705" x 0.605" max *
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max *
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES:
*Specification same as preceding model
(1) Output Range and Supply Current specifications are based on minimum output load resistance. Minimum
output load resistance is calculated by VOUT2/PE, where PE is the output Effective Available Power that guarantees
output range, accuracy, and linearity specifications.
(2) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(3) Linearity is calculated using the best-fit straight line method.
(4) Input offset term included in output offset specification.
SCM7B34/34N
Isolated Linearized 2- or 3-Wire RTD Input Modules
Description
Each SCM7B34/34N RTD input module accepts a single channel of 100Ω
Platinum (α = 0.00385) or 120Ω Nickel (α = 0.00672) RTD input and produces
Features
an input voltage in response to a low-level current excitation. The input signal • Interfaces to 100Ω Platinum or 120Ω
is filtered, isolated, amplified, linearized, and converted to a high-level analog Nickel RTDs
voltage for output to the process control system (Figure 1). • Provides 250µA RTD Excitation Current
These modules incorporate a five-pole filtering approach to maximize both time • Linearizes RTD Signal Response
and frequency response by taking advantage of both Thomson (Bessel) and
Butterworth characteristics. One pole of the filter is on the field side of the • Provides High-Level Voltage Outputs
isolation barrier; four are on the process control system side. • 1500Vrms Transformer Isolation
In response to the low-level current excitation signal, the RTD input signal is • Accuracy, ±0.05% to ±0.15% of
chopped by a proprietary chopper circuit and transferred across the transformer Span Typical
isolation barrier, suppressing transmission of common mode spikes and surges. • Nonconformity, ±0.025% to ±0.07% of
The signal is then reconstructed and filtered for process control system output. Span Typical
Linearization is achieved by creating a non-linear transfer function through the • ANSI/IEEE C37.90.1 Transient Protection
module itself. This non-linear transfer function is configured at the factory and • Input Protected to 120Vrms Continuous
is designed to be equal and opposite to the specific RTD non-linearity. Lead
compensation is achieved by matching two current paths thus cancelling the • Noise, 500µVp-p (5MHz), 250µVrms
effects of lead resistance. (100kHz)
• 160dB CMRR
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal).
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal • 85dB NMR at 60Hz, 80dB at 50Hz
for high channel density applications. They are designed for easy DIN rail • Easy DIN Rail Mounting
mounting using any of the “-DIN” backpanels.
• CSA C/US Certified
• CE and ATEX Compliant
SCM7B
Protection (–148°F to +212°F) (0.15°C) (0.30°C) (0.05°C) (0.10°C)
Continuous 120Vrms max *
Transient ANSI/IEEE C37.90.1 * SCM7B34-02 0°C to +100°C ±0.10% ±0.2% ±0.025% ±0.05%
Sensor Excitation Current(1) ≈250µA * (+32°F to +212°F) (0.10°C) (0.20°C) (0.025°C) (0.05°C)
Lead Resistance Effect ±0.02°C/Ω max *
SCM7B34-03 0°C to +200°C ±0.075% ±0.15% ±0.025% ±0.05%
Output
(+32°F to +392°F) (0.15°C) (0.30°C) (0.05°C) (0.10°C)
Signal Range(2) † †
Effective Available Power(2) 40mW * SCM7B34-04 0°C to +600°C ±0.05% ±0.1% ±0.025% ±0.05%
Resistance <1Ω *
Protection Continuous Short-to-Ground * (+32°F to +1112°F) (0.30°C) (0.60°C) (0.15°C) (0.30°C)
Voltage/Current Limit ±12V, ±14mA *
SCM7B34-05 –50°C to +350°C ±0.05% ±0.1% ±0.025% ±0.05%
CMV (Input-to-Output) (–58°F to +662°F) (0.20°C) (0.40°C) (0.1°C) (0.20°C)
Continuous 1500Vrms *
Transient ANSI/IEEE C37.90.1 * 120Ω Ni **
CMRR (50 or 60Hz) 160dB * SCM7B34N-01 0°C to +300°C ±0.15% ±0.3% ±0.06% ±0.12%
Accuracy(3) See Ordering Information * (+32°F to +572°F) (0.45°C) (0.90°C) (0.18°C) (0.36°C)
Nonconformity(4) See Ordering Information *
Stability (–40°C to +85°C) SCM7B34N-02 0°C to +200°C ±0.15% ±0.3% ±0.07% ±0.14%
Gain ±60ppm/°C * (+32°F to +392°F) (0.30°C) (0.60°C) (0.14°C) (0.28°C)
Input Offset ±1µV/°C *
Zero Suppression ±0.002%(RZ/RSPAN)(5)/°C *
Output Offset ±0.002% Span/°C *
Noise †
Output Ranges Available
Peak at 5MHz B/W 500µV *
RMS at 10Hz to 100kHz B/W 250µV * Output Range Part No. Suffix Example
Peak at 0.1Hz to 10Hz B/W 1µV RTI *
Open Input Response
‘+’ Lead Upscale * +1 to +5V NONE SCM7B34-01
‘–’ Lead Non-deterministic * 0 to +5V A SCM7B34-01A
‘x’ Lead Downscale * 0 to +10V D SCM7B34-01D
Open Input Detection Time <5s *
Frequency and Time Response
Bandwidth, –3dB 3Hz * **RTD Standards
NMR (50/60Hz) 80/85dB *
Step Response, 90% Span 250ms *
Type Alpha Coefficient DIN JIS IEC
Supply Voltage 14 to 35VDC *
Current(2) 12mA * 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
Sensitivity ±0.0001%/%VS * 120Ω Ni 0.00672
Mechanical Dimensions 2.13" x 1.705" x 0.605" max *
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max *
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES:
*Specification same as preceding model.
(1) Sensor excitation current is model dependent.
(2) Output Range and Supply Current specifications are based on minimum output load resistance.
Minimum output load resistance is calculated by VOUT2/PE, where PE is the output Effective Available
Power that guarantees output range, accuracy, and conformity specifications.
(3) Accuracy includes the effects of repeatability, hysteresis, and conformity.
(4) Nonconformity is calculated using the best-fit straight line method.
(5) RZ is the value of the RTD resistance at the lowest measurement point. RSPAN is the change in
resistance over the measurement span.
SCM7B35
Isolated 2-Wire Transmitter Interface Modules With Loop Power
Description
SCM7B35 current input modules accept input signals in the 4-20mA range from
the field and provide a high-level voltage output to the process control system
Features
(Figure 1). Current to voltage conversion occurs internal to the module, which • 2-Wire Transmitter Interface
is factory calibrated to ensure the highest accuracy. • Accepts 4-20mA Signals
Loop power is provided by the module, enabling a 2-wire transmitter to be • Provides an Isolated +24VDC Supply to Power
directly connected without the need for a separate dc power supply for the 2-wire the Loop
transmitter.
• Provides High-Level Voltage Outputs
These modules incorporate a five-pole filtering approach to maximize both time • 1500Vrms Transformer Isolation
and frequency response by taking advantage of both Thomson (Bessel) and
Butterworth characteristics. One pole of the filter is on the field side of the • Accuracy, ±0.03% of Span Typical,
isolation barrier; four are on the process control system side. ±0.1% Max
After the initial field-side filtering, the input signal is chopped by a proprietary • ANSI/IEEE C37.90.1 Transient Protection
chopper circuit and transferred across the transformer isolation barrier, sup- • 120Vrms Input Protection
pressing transmission of common mode spikes and surges. The signal is then • 105dB CMRR
reconstructed and filtered for process control system output.
• Easy DIN Rail Mounting
Modules accept a wide 18 - 35VDC power supply range (+24VDC nominal).
• CSA C/US Certified
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal
for high channel density applications. They are designed for easy DIN rail • CE and ATEX Compliant
mounting using any of the “-DIN” backpanels.
SCM7B
Transient ANSI/IEEE C37.90.1 SCM7B35-02 4 to 20mA +2 to +10V
Loop Voltage(1) +24VDC
Output
Signal Range(2) See Ordering Information
Effective Available Power(2) 40mW
Resistance <1Ω
Protection Continuous Short-to-Ground
Voltage/Current Limit ±16V, ±14mA
CMV (Input-to-Output)
Continuous 1500Vrms
Transient ANSI/IEEE C37.90.1
CMRR (50 or 60Hz) 105dB
Accuracy(3) ±0.03% Span typical,
±0.1% Span max
Linearity(4) ±0.01% Span typical,
±0.02% Span max
Stability (–40°C to +85°C)
Gain ±40ppm/°C
Input Offset N/A(5)
Output Offset ±0.003% Span/°C
Noise
Peak at 5MHz B/W 5mV
RMS at 10Hz to 100kHz B/W 500µV
Peak at 0.1Hz to 10Hz B/W 3µV RTI
Frequency and Time Response
Bandwidth, –3dB 100Hz
NMR (–3dB at 100Hz) 80dB per decade above 100Hz
Step Response, 90% Span 5ms
Supply Voltage 18 to 30VDC
Current(2) 56mA
Sensitivity ±0.0002%/%VS
Mechanical Dimensions 2.13" x 1.705" x 0.605" max
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) +24V will be supplied to the loop for an open loop condition. Approximately +22V to +16V will be
supplied for a corresponding 4mA to 20mA input. Loop voltage is independent of supply voltage.
(2) Output Range and Supply Current specifications are based on minimum output load resistance.
Minimum output load resistance is calculated by VOUT2/PE, where PE is the Output Effective Available
Power that guarantees output range, accuracy, and linearity specifications.
(3) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(4) Linearity is calculated using the best-fit straight line method.
(5) Input offset term included in output offset specification.
SCM7B36
Isolated Potentiometer Input Modules
Description
Each SCM7B36 Potentiometer input module provides a single channel of
resistance input which is filtered, isolated, amplified, and converted to a high-
Features
level analog voltage output. • Industry’s First 7B Potentiometer Input Module
The SCM7B36 module interfaces to slidewires and potentiometers in both two • Interfaces 100Ω to 10kΩ Potentiometers
or three wire configuration and incorporates a five-pole filtering approach to • Provides High-Level Voltage Outputs
maximize both time and frequency response by taking advantage of both Bessel
and Butterworth characteristics. One pole of the filter is on the field side of the • 1500Vrms Transformer Isolation
isolation barrier; four are on the process control system side. In the 3-Wire • Accuracy, ±0.03% of Span Typical,
configuration, lead resistance compensation is provided if the resistance of the ±0.1% Max
“x” lead is closely equivalent to that of the “+” lead. Internal to the module, • ANSI/IEEE C37.90.1 Transient Protection
measurement error due to lead resistance is canceled.
• Input Protected to 120Vrms Continuous
In response to the low-level current excitation, and after initial field-side filtering,
• 120dB CMRR
the input signal is chopped by a proprietary chopper circuit and transferred
across the transformer isolation barrier, suppressing transmission of common • 85dB NMR at 60Hz, 80dB at 50Hz
mode spikes and surges. The signal is then reconstructed and filtered for • Easy DIN Rail Mounting
process control system output.
• CSA C/US Certified
Six standard input resistance ranges are offered, from 100Ω to 10kΩ, with three
• CE and ATEX Compliant
output ranges available: 0-5V, 1-5V, and 0-10V. Modules accept a wide 14-
35VDC power supply range (+24VDC nominal). Their compact packages (2.13"
x 1.705" x 0.605" max.) save space and are ideal for high channel density
applications. They are designed for easy DIN rail mounting using any of
Dataforth’s “-DIN” backpanels.
SCM7B
SCM7B36-04 0 to 1kΩ
Sensor Excitation Current 65µA (10kΩ) to 260µA (100Ω) SCM7B36-05 0 to 5kΩ
Lead Resistance Effect (3-Wire)(1)
-01 thru -04 : ±0.005Ω/Ω SCM7B36-06 0 to 10kΩ
-05 : ±0.02Ω/Ω
-06 : ±0.04Ω/Ω †
Output Ranges Available
Output Range(2) †
SCM7B37
Non-Linearized Isolated Thermocouple Input Modules
Description
SCM7B37 non-linearized modules accept a single channel of input from Type
J, K, T, E, R, S, or B thermocouples. The signal is filtered, isolated, amplified, Features
and converted to a high-level analog voltage for output to the process control • Interfaces to Type J, K, T, E, R, S, and B
system (Figure 1). Thermocouples
Cold junction compensation (CJC) is performed using an NTC thermistor (see • Provides High-Level Voltage Outputs
“Additional SCM7B Part Numbers” section for P/N and AN701 for further • 1500Vrms Transformer Isolation
information) externally mounted under the field-side terminal block on the
backpanel (Figure 1). Open thermocouple detection is upscale using a 30nA • Accuracy, ±0.03% of Span Typical,
current source in the input circuitry. ±0.1% Max
• ANSI/IEEE C37.90.1 Transient Protection
These modules incorporate a five-pole filtering approach to maximize both time
and frequency response by taking advantage of both Thomson (Bessel) and • Input Protected to 120Vrms Continuous
Butterworth characteristics. One pole of the filter is on the field side of the • Noise, 500µVp-p (5MHz), 250µVrms
isolation barrier; four are on the process control system side. (100kHz)
After the initial field-side filtering, the input signal is chopped by a proprietary • 160dB CMRR
chopper circuit and transferred across the transformer isolation barrier, sup-
• 85dB NMR at 60Hz, 80dB at 50Hz
pressing transmission of common mode spikes and surges. The signal is then
reconstructed and filtered for process control system output. • Easy DIN Rail Mounting
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal). • CSA C/US Certified
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal • CE and ATEX Compliant
for high channel density applications. They are designed for easy DIN rail
mounting using any of the “-DIN” backpanels.
SCM7B
Resistance SCM7B37J-10 0°C to +200°C ±0.03% ±0.1% ±0.01% ±0.02%
Normal 50MΩ (+32°F to +392°F) (0.06°C) (0.20°C) (0.02°C) (0.04°C)
Power Off 30kΩ min
Overload 30kΩ min SCM7B37J-11 0°C to +400°C ±0.03% ±0.1% ±0.01% ±0.02%
Protection (+32°F to +752°F) (0.12°C) (0.40°C) (0.04°C) (0.08°C)
Continuous 120Vrms max
Transient ANSI/IEEE C37.90.1 SCM7B37J-12 0°C to +600°C ±0.03% ±0.1% ±0.01% ±0.02%
(+32°F to +1112°F) (0.18°C) (0.60°C) (0.06°C) (0.12°C)
Output
Signal Range(2) †
SCM7B37J-13 300°C to +600°C ±0.03% ±0.1% ±0.01% ±0.02%
Effective Available Power(2) 40mW (572°F to +1112°F) (0.09°C) (0.30°C) (0.03°C) (0.24°C)
Resistance <1Ω
Protection Continuous Short-to-Ground SCM7B37K-02 –100°C to +1350°C ±0.03% ±0.1% ±0.01% ±0.02%
Voltage/Current Limit ±12V, ±14mA (–148°F to +2462°F) (0.44°C) (1.45°C) (0.15°C) (0.29°C)
CMV (Input-to-Output)
SCM7B37K-20 0°C to +300°C ±0.03% ±0.1% ±0.01% ±0.02%
Continuous 1500Vrms
Transient ANSI/IEEE C37.90.1 (+32°F to +572°F) (0.09°C) (0.30°C) (0.03°C) (0.06°C)
CMRR (50 or 60Hz) 160dB SCM7B37K-21 0°C to +600°C ±0.03% ±0.1% ±0.01% ±0.02%
Accuracy(3) ±0.03% Span typical, (+32°F to +1112°F) (0.18°C) (0.60°C) (0.06°C) (0.12°C)
±0.1% Span max
Linearity(4) See Ordering Information SCM7B37K-22 0°C to +1200°C ±0.03% ±0.1% ±0.01% ±0.02%
Stability (–40°C to +85°C) (+32°F to +2192°F) (0.36°C) (1.20°C) (0.12°C) (0.24°C)
Gain ±35ppm/°C
Input Offset ±0.5µV/°C SCM7B37K-23 600°C to +1200°C ±0.03% ±0.1% ±0.01% ±0.02%
Zero Suppression ±0.005%(Vz)(5)/°C (+1112°F to +2192°F) (0.18°C) (0.60°C) (0.06°C) (0.12°C)
Output Offset ±0.002% Span/°C
Noise SCM7B37T-03 –100°C to +400°C ±0.03% ±0.1% ±0.01% ±0.02%
Peak at 5MHz B/W 500µV (–148°F to +752°F) (0.15°C) (0.50°C) (0.05°C) (0.10°C)
RMS at 10Hz to 100kHz B/W 250µV
Peak at 0.1Hz to 10Hz B/W 1µV RTI
SCM7B37E-04 0°C to +900°C ±0.03% ±0.1% ±0.01% ±0.02%
CJC Accuracy(6), ±0.25°C typ, ±1°C max (+32°F to +1652°F) (0.27°C) (0.90°C) (0.09°C) (0.18°C)
+5°C to +45°C ambient
SCM7B37R-05 0°C to +1750°C ±0.03% ±0.1% ±0.01% ±0.02%
Open Input Response Upscale
Open Input Detection Time <10s (+32°F to +3182°F) (0.53°C) (1.75°C) (0.18°C) (0.35°C)
Frequency and Time Response SCM7B37S-06 0°C to +1750°C ±0.03% ±0.1% ±0.01% ±0.02%
Bandwidth, –3dB 3Hz (+32°F to +3182°F) (0.53°C) (1.75°C) (0.18°C) (0.35°C)
NMR (50/60Hz) 80/85dB
Step Response, 90% Span 165ms SCM7B37B-07 0°C to +1800°C ±0.03% ±0.1% ±0.01% ±0.02%
(+32°F to +3272°F) (0.54°C) (1.80°C) (0.18°C) (0.36°C)
Supply Voltage 14 to 35VDC
Current(2) 12mA
†
Sensitivity ±0.0001%/%VS Output Ranges Available
Mechanical Dimensions 2.13" x 1.705" x 0.605" max Output Range Part No. Suffix Example
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max
Environmental +1 to +5V NONE SCM7B37J-01
Operating Temperature Range –40°C to +85°C 0 to +5V A SCM7B37J-01A
Storage Temperature Range –40°C to +85°C 0 to +10V D SCM7B37J-01D
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A ‡
Thermocouple Alloy Combinations
Immunity EN61000-6-2 ISM, Group 1 Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
RF Performance A ±0.5% Span Error
ESD, EFT Performance B Type Material
NOTES:
(1) Thermocouple characteristics per NIST monograph 175, ITS-90. J Iron vs. Copper-Nickel
(2) Output Range and Supply Current specifications are based on minimum output load resistance. K Nickel-Chromium vs. Nickel-Aluminum
Minimum output load resistance is calculated by VOUT2/PE, where PE is the output Effective Available
Power that guarantees output range, accuracy, and linearity specifications. T Copper vs. Copper-Nickel
(3) Accuracy includes the effects of repeatability, hysteresis, and linearity. E Nickel-Chromium vs. Copper-Nickel
(4) Linearity is calculated using the best-fit straight line method. R Platinum-13% Rhodium vs. Platinum
(5) VZ is the nominal input voltage that results in a 0V output. S Platinum-10% Rhodium vs. Platinum
(6) The CJC sensor accuracy should be added to the module accuracy and thermocouple accuracy
to compute the overall measurement accuracy. B Platinum-30% Rhodium vs. Platinum-6% Rhodium
SCM7B39
Isolated Process Current Output Modules
Description
SCM7B39 process current modules accept high-level signals from the process
control system and provide either 0 to 20mA or 4 to 20mA current to the field
Features
(Figure 1). • Accepts High-Level Voltage Input
These modules incorporate a five-pole filtering approach to maximize both time • Provides 4-20mA or 0-20mA Current Output
and frequency response by taking advantage of both Thomson (Bessel) and • 1500Vrms Transformer Isolation
Butterworth characteristics. One pole of the filter is on the process control
system side of the isolation barrier, and the other four poles are on the field side. • Accuracy, ±0.03% of Span Typical, ±0.1% Max
• ANSI/IEEE C37.90.1 Transient Protection
After the initial process control system side filtering, the signal is chopped by a
proprietary chopper circuit and transferred across the transformer isolation • Output Protected to 120Vrms Continuous
barrier, suppressing transmission of common mode spikes and surges. The • Noise, 46µAp-p (5MHz), 4µArms (100kHz)
signal is then reconstructed, filtered, and converted to a process current for
• 110dB CMRR
output to the field.
• Easy DIN Rail Mounting
Modules accept a wide 18 - 35VDC power supply range (+24VDC nominal).
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal • CSA C/US Certified
for high channel density applications. They are designed for easy DIN rail • CE and ATEX Compliant
mounting using any of the “-DIN” backpanels.
SCM7B
Protection SCM7B39-04 4 to 20mA 4 to 20mA
Continuous 120Vrms max *
Transient ANSI/IEEE C37.90.1 *
Current Limit 32mA *
Input
Signal Range 1 to +5V, 0 to +10V 4-20mA
Bias Current ±1nA N/A
Resistance
Normal 10MΩ 270Ω
Power Off 30kΩ min >20kΩ
Overload 30kΩ min N/A
Protection ±35Vpeak (no damage) ±7.5Vpeak
Compliance N/A 35VDC max
CMV (Input-to-Output)
Continuous 1500Vrms *
Transient ANSI/IEEE C37.90.1 *
CMRR (50 or 60Hz) 110dB *
Accuracy(2) ±0.03% Span typical, *
±0.1% Span max
Linearity(3) ±0.01% Span typical, *
±0.02% Span max
Stability (–40°C to +85°C)
Gain ±25ppm/°C ±50ppm/°C
Output Offset ±0.0035% Span/°C ±0.0045% Span/°C
Noise
Peak at 5MHz B/W 46µA *
RMS at 10Hz to 100kHz B/W 4µA *
Peak at 0.1Hz to 10Hz B/W 42nA *
Open Output Loop Detection
Response N/A Input Resistance
> 20kΩ
Detection Time N/A 5ms
Frequency and Time Response
Bandwidth, –3dB 100Hz *
NMR (–3dB at 100Hz) 80dB per decade above 100Hz *
Step Response, 90% Span 5ms *
Supply Voltage 18 to 35VDC *
Current(1) 56mA *
Sensitivity ±0.0003%/%VS *
Mechanical Dimensions 2.13" x 1.705" x 0.605" max *
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max *
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES:
* Same specification as SCM7B39-01, -02, -03.
(1) Output Range and Supply Current specifications are based on maximum output load resistance. Maximum
output load resistance is calculated by PE/IOUT2 where PE is the Output Effective Available Power that guarantees
output range, accuracy, and linearity specifications. Output effective available power is independent of supply
voltage.
(2) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(3) Linearity is calculated using the best-fit straight line method.
SCM7B40/41
Isolated Analog Voltage Input Modules, Wide Bandwidth
Description
Each SCM7B40/41 voltage input module accepts one channel of analog voltage
input which is filtered, isolated, amplified, and converted to a high-level analog
Features
voltage for output to the process control system. • Accepts Millivolt or Voltage Inputs
These modules incorporate a five-pole filtering approach to maximize both time • Provides High-Level Voltage Outputs
and frequency response by taking advantage of both Thomson (Bessel) and • 10kHz Bandwidth
Butterworth characteristics. One pole of the filter is on the field side of the
isolation barrier; four are on the process control system side. • 1500Vrms Transformer Isolation
• Accuracy, ±0.03% of Span Typical,
After the initial field-side filtering, the input signal is chopped by a proprietary ±0.1% Max
chopper circuit and transferred across the transformer isolation barrier, sup-
pressing transmission of common mode spikes and surges. The signal is then • ANSI/IEEE C37.90.1 Transient Protection
reconstructed and filtered for process control system output. • Input Protected to 120Vrms Continuous
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal). • Noise, 2mVp-p (5MHz), 1mVrms (100kHz)
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal • Up to 110dB CMRR
for high channel density applications. They are designed for easy DIN rail
mounting using any of the “-DIN” backpanels. • Easy DIN Rail Mounting
• CSA C/US Certified
• CE and ATEX Compliant
SCM7B
Resistance
Normal 50MΩ 500kΩ min SCM7B40-08 ±1V
Power Off 30kΩ min 500kΩ min
Overload 30kΩ min 500kΩ min
SCM7B41-01 0 to +10V
Protection SCM7B41-02 ±5V
Continuous 120Vrms max * SCM7B41-03 ±10V
Transient ANSI/IEEE C37.90.1 * SCM7B41-04 0 to +5V
Output SCM7B41-05 0 to +20V
Signal Range(1) † †
SCM7B41-06 0 to +40V
Effective Available Power(1) 40mW *
Resistance <1Ω *
Protection Continuous Short-to-Ground * †
Output Ranges Available
Voltage/Current Limit ±12V, ±14mA *
CMV (Input-to-Output) Output Range Part No. Suffix Example
Continuous 1500Vrms max *
Transient ANSI/IEEE C37.90.1 * +1 to +5V NONE SCM7B40-02
CMRR (50 or 60Hz) 110dB 100dB 0 to +5V A SCM7B40-02A
Accuracy(2) ±0.03% Span typical, * 0 to +10V D SCM7B40-02D
±0.1% Span max
(3)
Linearity ±0.01% Span typical, *
±0.02% Span max
Stability (–40°C to +85°C)
Gain ±35ppm/°C ±55ppm/°C
Input Offset ±0.5µV/°C ±5µV/°C
Zero Suppression ±0.005%(Vz)(4)/°C *
Output Offset ±0.002% Span/°C *
Noise
Peak at 5MHz B/W 2mV *
RMS at 10Hz to 100kHz B/W 1mV *
Peak at 0.1Hz to10Hz B/W 1µV RTI *
Frequency and Time Response
Bandwidth, –3dB 10kHz *
NMR 80dB/decade >10kHz *
Step Response, 90% Span 50µs *
Supply Voltage 14 to 35VDC *
Current(1) 12mA *
Sensitivity ±0.0001%/%VS *
Mechanical Dimensions 2.13" x 1.705" x 0.605" max *
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max *
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES:
* Specification same as preceding model.
(1) Output Range and Supply Current specifications are based on minimum output load resistance.
Minimum output load resistance is calculated by VOUT2/PE, where PE is the Output Effective Available
Power that guarantees output range, accuracy, and linearity specifications.
(2) Accuracy includes the effects of repeatability, hysteresis, and linearity.
(3) Linearity is calculated using the best-fit straight line method.
(4) VZ is the nominal input voltage that results in a 0V output.
SCM7B47
Isolated Linearized Thermocouple Input Modules
Description
SCM7B47 modules accept a single channel of input from Type J, K, T, E, R, S,
B, or N thermocouples. The signal is filtered, isolated, amplified, linearized, and
Features
converted to a high-level analog voltage for output to the process control system • Interfaces to Type J, K, T, E, R, S, B and N
(Figure 1). Thermocouples
Linearization is achieved by creating a non-linear transfer function through the • Linearizes Thermocouple Signals
module itself; refer to AN505. This non-linear transfer function is configured at • Provides High-Level Voltage Outputs
the factory and is designed to be equal and opposite to the thermocouple
non-linearity. • 1500Vrms Transformer Isolation
• Accuracy, ±0.06% to ±0.16% of Span Typical
Cold junction compensation (CJC) is performed using an NTC thermistor (see
“Additional SCM7B Part Numbers” section for P/N and AN701 for further • ANSI/IEEE C37.90.1 Transient Protection
information) externally mounted under the field-side terminal block on the • Input Protected to 120Vrms Continuous
backpanel (Figure 1). Open thermocouple detection is upscale using a 30nA
• Noise, 1mVp-p (5MHz), 500µVrms (100kHz)
current source in the input circuitry.
• 160dB CMRR
These modules incorporate a five-pole filtering approach to maximize both time
and frequency response by taking advantage of both Thomson (Bessel) and • 85dB NMR at 60Hz, 80dB at 50Hz
Butterworth characteristics. One pole of the filter is on the field side of the • Easy DIN Rail Mounting
isolation barrier; four are on the process control system side.
• CSA C/US Certified
After the initial field-side filtering, the input signal is chopped by a proprietary • CE and ATEX Compliant
chopper circuit and transferred across the transformer isolation barrier, sup-
pressing transmission of common mode spikes and surges. The signal is then
reconstructed and filtered for process control system output.
Modules accept a wide 14 - 35VDC power supply range (+24VDC nominal).
Their compact packages (2.13"x1.705"x0.605" max) save space and are ideal
for high channel density applications. They are designed for easy DIN rail
mounting using any of the “-DIN” backpanels.
SCM7B
Resistance SCM7B47J-02 –100°C to +300°C ±0.10% Span ±0.30% Span
Normal 50MΩ (–148°F to +572°F) (0.40°C) (1.20°C)
Power Off 30kΩ min
Overload 30kΩ min SCM7B47K-03 0°C to +1300°C ±0.11% Span ±0.32% Span
Protection (+32°F to +2372°F) (1.43°C) (4.16°C)
Continuous 120Vrms max
Transient ANSI/IEEE C37.90.1 SCM7B47K-04 0°C to +600°C ±0.06% Span ±0.18% Span
Output (+32°F to +1112°F) (0.36°C) (1.08°C)
Signal Range(2) †
Effective Available Power(2) 40mW SCM7B47T-05 0°C to +400°C ±0.13% Span ±0.38% Span
Resistance <1Ω (+32°F to +752°F) (0.52°C) (1.52°C)
Protection Continuous Short-to-Ground
Voltage/Current Limit ±12V, ±14mA SCM7B47T-06 –100°C to +200°C ±0.16% Span ±0.47% Span
(–148°F to +392°F) (0.48°C) (1.41°C)
CMV (Input-to-Output)
Continuous 1500Vrms SCM7B47E-07 0°C to +900°C ±0.11% Span ±0.34% Span
Transient ANSI/IEEE C37.90.1
CMRR (50 or 60Hz) 160dB (+32°F to +1652°F) (0.99°C) (3.06°C)
Accuracy(3) (See Ordering Information) SCM7B47R-08 +500°C to +1750°C ±0.10% Span ±0.30% Span
Stability (–40°C to +85°C) (+932°F to +3182°F) (1.25°C) (3.75°C)
Gain ±40ppm/°C
Input Offset ±0.5µV/°C SCM7B47S-09 +700°C to +1750°C ±0.08% Span ±0.25% Span
Zero Suppression ±0.005%(Vz)(4)/°C (+1292°F to +3182°F) (0.84°C) (2.63°C)
Output Offset ±0.002% Span/°C
Noise SCM7B47B-10 +800°C to +1800°C ±0.12% Span ±0.35% Span
Peak at 5MHz B/W 1mV (+1472°F to +3272°F) (1.20°C) (3.50°C)
RMS at 10Hz to 100kHz B/W 500µV
Peak at 0.1Hz to 10Hz B/W 1µV RTI SCM7B47N-11 +200°C to +1300°C ±0.09% Span ±0.27% Span
CJC Accuracy(5), ±0.25°C Typ, ±1°C max
(+392°F to +2372°F) (0.99°C) (2.97°C)
+5°C to +45°C ambient
Open Input Response Upscale
Open Input Detection Time <10s
†
Frequency and Time Response Output Ranges Available
Bandwidth, –3dB 3Hz
NMR (50/60Hz) 80/85dB Output Range Part No. Suffix Example
Step Response, 90% Span 165ms
+1 to +5V NONE SCM7B47J-01
Supply Voltage 14 to 35VDC
Current(2) 16mA
0 to +5V A SCM7B47J-01A
Sensitivity ±0.0001%/%VS 0 to +10V D SCM7B47J-01D
Mechanical Dimensions 2.13" x 1.705" x 0.605" max
(h)(w)(d) 54.1mm x 43.3mm x 15.4mm max
‡
Thermocouple Alloy Combinations
Environmental Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing Type Material
Emissions EN61000-6-4 ISM, Group 1 J Iron vs. Copper-Nickel
Radiated, Conducted Class A K Nickel-Chromium vs. Nickel-Aluminum
Immunity EN61000-6-2 ISM, Group 1 T Copper vs. Copper-Nickel
RF Performance A ±0.5% Span Error
E Nickel-Chromium vs. Copper-Nickel
ESD, EFT Performance B
NOTES: R Platinum-13% Rhodium vs. Platinum
(1) Thermocouple characteristics per NIST monograph 175, ITS-90. S Platinum-10% Rhodium vs. Platinum
(2) Output Range and Supply Current specifications are based on minimum output load resistance. B Platinum-30% Rhodium vs. Platinum-6% Rhodium
Minimum output load resistance is calculated by VOUT2/PE, where PE is the output Effective Available N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4%
Power that guarantees output range, accuracy, and linearity specifications.
(3) Accuracy includes the effects of repeatability, hysteresis, and conformity. Silicon- 0.1% Magnesium
(4) VZ is the nominal input voltage that results in a 0V output.
(5)The CJC sensor accuracy should be added to the module accuracy and thermocouple accuracy
to compute overall measurement accuracy.
SCM7B
Module Dimensions and Pinouts
The following mechanical drawing is useful if designing circuit boards to mount The captive nut for the 4-40 mounting screw can be obtained from PEM (Penn
the SCM7B modules. Many sockets are available which accept the mounting Engineering and Manufacturing), part number KSF2-440.
pins. As an example, AMP Inc. provides a socket with part number 50865-5.
SCM7BXEV
Description Field Side - Signal
SCM7B
The SCM7BXEV (Figures 1 and 2) is a single channel backpanel that can accept On the field side, a temperature sensor is mounted underneath the field side
any of the SCM7B analog modules. It is meant to be used primarily for module terminal block to provide cold junction compensation for thermocouple modules,
evaluation. Unlike multiple channel backpanels, the single high-level system and a current-to-voltage conversion resistor (P/N SCM7BXR1) socketing loca-
output (or input) signal is routed to all channel pins on the system interface tion is provided (supplied with SCM7B33 modules). Field connections are
DB25 connector. The backpanel contains four standoffs to allow mounting, terminated with three screw terminals
using a #6 or smaller screw.
System Side - Power Specifications
Using the “V+” supply input, the power supply voltage can be as little as +14VDC. Operating Temperature –40°C to +85°C
If +15VDC is available, it is recommended that the supply be connected between Relative Humidity 95% Noncondensing
the “V+A” or “V+B” connections and “COM”; this will protect the module against Interface Connector:
accidental supply reversal. Using both these connections with two power Field high density screw clamp, 10-24 AWG
supplies enables redundant operation. It is also recommended that a diode System DB25 (male) with 4-40 screwlocks and
transient absorber be installed to reduce power supply transient events from high density screw clamp, 10-24 AWG
degrading system performance. An “accessory” location, between the supply
and common lines, is provided for this purpose. The backpanel is fused at
1/4 Amp for module protection.
System Side - Signal
The SCM7BXEV uses either the SCM7BXCA01 (DB25 to 26-pin adapter cable)
and SCMXCA004-XX (26-pin to 26-pin interface cable), or the SCM7BXCA02
(DB25 to DB25 interface cable), depending on system requirements.
SCM7BP01/SCM7BP02
Backpanel
Description Field Side - Signal
The SCM7BP01 (Figure 3) and SCM7BP02 (Figure 4) are 1 and 2 channel On the field side, a temperature sensor is mounted underneath the field side
SCM7B
backpanels. Unlike other backpanels available, both the system and field side terminal block to provide cold junction compensation for thermocouple modules,
sides have screw terminal connectors able to accept discrete wire (10-24 AWG). and a current-to-voltage conversion resistor (P/N SCM7BXR1) socket location
The backpanels can be ordered with standoffs to allow mounting, using a #6 or is provided (supplied with SCM7B33 modules).
smaller screw, or with DIN rail mounting hardware.
Specifications
System Side - Power
Operating Temperature –40°C to +85°C
Both backpanels accept 14-35VDC between “V+” and “COM” using a screw Relative Humidity 95% Noncondensing
terminal (10-24 AWG) block. No reverse supply diodes are provided with this Interface Connector:
model, but both are fused at 1/4 Amp (01) or 1/2 Amp (02) for module protection. Field high density screw clamp, 10-24 AWG
System high density screw clamp, 10-24 AWG
Isolation:
Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
SCM7BP01-DIN/SCM7BP02-DIN
Panels & DIN Rail Mounting Accessories
Description Ordering Information
The SCM7BP01 and SCM7BP02 are single and dual channel mounting panels for Part Number Description
the SCM7B modules. Both have options for standoffs or DIN rail mounting.
SCM7BP01 Single channel backpanel with standoffs for mounting.
The following accessories are required for DIN rail mounting one SCM7BP01 or
SCM7BP02 panel (Figure 5): SCM7BP01-4 Single channel backpanel. No mounting hardware included.
Qty Model Description SCM7BP01-DIN Single channel backpanel with DIN rail mounting hardware.
1 SCMXBEFE Base element with snap foot Shipped fully assembled.
2 SCMXSE Side element SCM7BP02 Dual channel backpanel with standoffs for mounting.
The following accessories are required for DIN rail mounting two or more SCM7BP02-4 Dual channel backpanel. No mounting hardware included.
SCM7BP01-4 or SCM7BP02-4 panels:
SCM7BP02-DIN Dual channel backpanel with DIN rail mounting hardware.
Qty Model Description Shipped fully assembled.
2 SCMXBEFE Base element with snap foot
2 SCMXSE Side element
(# panels) - 2 SCMXBE Base element without snap foot
(4 x (# panels))-4 SCMXVS Connection pins
The following DIN rail styles are available. Specify length in meters (-XX).
SCMXRAIL1-XX DIN EN 50022-35x7.5 (slotted steel)
SCMXRAIL2-XX DIN EN 50035-G32 (slotted steel)
SCMXRAIL3-XX DIN EN 50022-35x15 (slotted steel)
SCM7B
Figure 6: SCM7BP01 (-DIN) Schematic Diagram
SCM7BP04(-DIN)/SCM7BP08(-DIN)/SCM7BP16(-DIN)
Backpanels
Description Field Side - Signal
The SCM7BP04, SCM7BP08, and SCM7BP16 (see Figures 10-13) are 4, 8, & On the field side a temperature sensor is mounted underneath the field side
16 channel backpanels that can accept any of the SCM7B analog modules. All terminal block to provide cold junction compensation for thermocouple input
three of these backpanels can either be rack mounted using Dataforth’s 19-inch modules. A current-to-voltage conversion resistor (P/N SCM7BXR1, supplied
rack P/N SCMXRK-002 (using the provided 3mm screws), or directly mounted with SCM7B33 modules) socket is provided for each channel. Field connections
to a surface using #6 or smaller screws. The SCM7BP04-DIN, SCM7BP08-DIN, are terminated with three screw terminals at each module site.
and SCM7BP16-DIN are identical to the SCM7BP04, SCM7BP08, and
SCM7BP16, but with DIN rail mounting clips attached instead of standoffs. Ordering Information
These brackets allow the backpanels to be mounted on either EN 50022-35 x 7.5
(35 x 15) or EN 50035-G32 type DIN rails. Part Number Description
System Side - Power SCM7BP04 4-channel backpanel with standoffs for mounting.
Using the “V+” power supply input, the power supply voltage can be as little as SCM7BP04-DIN 4-channel backpanel with DIN rail mounting clips.
+14VDC. If +15VDC is available, it is recommended that the supply be Shipped fully assembled.
connected between the “V+A” or “V+B” connections and “COM”; this will protect
SCM7BP08 8-channel backpanel with standoffs for mounting.
the modules against accidental supply reversal. Using both these connections
with two power supplies enables redundant power supply operation. It is also SCM7BP08-DIN 8-channel backpanel with DIN rail mounting clips.
recommended that a diode transient absorber be installed to reduce power Shipped fully assembled.
supply transient events from degrading system performance. An “accessory”
location, between the supply and common lines, is provided for this purpose. A SCM7BP16 16-channel backpanel with standoffs for mounting.
system side grounding #10-32 stud is also provided for use if desired. SCM7BP16-DIN 16-channel backpanel with DIN rail mounting clips.
All backpanels are fused according to channel count, allowing 1/4 Amp Shipped fully assembled.
per channel.
System Side - Signal
Specifications
Two system interface DB25 connectors are used, to enable using both input and
Operating Temperature –40°C to +85°C
output modules simultaneously, or to route the signal from an input module Relative Humidity 95% Noncondensing
backplane to an output module backplane. These backpanels use either the
SCM7BXCA01 (DB25 to 26-pin adapter cable) and SCMXCA004-XX (26-pin to Interface Connector:
Field high density screw clamp, 10-24 AWG
26-pin interface cable), or the SCM7BXCA02 (DB25 to DB25 interface cable), System 2 DB25 (male) connectors with 4-40 screwlocks
depending on system requirements.
Isolation:
Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
SCM7B
Figure 12: SCM7BP16(-DIN) Dimensions
Figure 11: SCM7BP08(-DIN) Dimensions
SCM7B
Figure 14: SCMXRK-002 Analog Rack Dimensions
SCM7BXR1
Current Conversion Resistor
Description
The SCM7BXR1 current-to-voltage conversion resistor (250Ω, 0.1%, 10ppm) is
used with the SCM7B33 voltage input modules. Sockets are provided on all
backpanels to allow installation of this resistor. Other values are available;
consult the factory for ordering details and specifications.
SCM7BPT
Non-Isolated Pass Thru Module Additional Part Numbers of Interest
The following is a list of parts that are available for use with your SCM7B system,
Description or for fabrication of your own backpanel, along with manufacturer’s part number.
The SCM7BPT is a non-isolated signal pass-thru module which shorts together Dataforth makes no claim as to availability and/or quality of parts purchased
SCM7B
the signal inputs-to-outputs. from vendors other than Dataforth.
Part Description Part Number Manufacturer
CJC Thermistor 100K6A1 Betatherm Corp.
DC95G104W Thermometrics
Diode Transient Absorber SA series General Semiconductor
Sockets for SCM7B pins 50865-5 Amp Incorporated
Module retaining screw KSF2-440 PEM Engineering
captive nut, 4-40 thread
Grounding Stud, 0.625", KFH 10-32-10 PEM Engineering
10-32 thread
Part Description Part Number Manufacturer
Axial Fuse PICO II series Littelfuse
Figure 21: SCM7BPT
2 position termination block MKDS5/2-6,35 Phoenix Contact, Inc.
3 position termination block MKDS5/3-6,35 Phoenix Contact, Inc.
DB25 (male) PCB connector 745078-3 AMP Incorporated
SCM7B-PROTO DB25 (female) ribbon 745078-5 AMP Incorporated
connector (for custom cables)
Breadboard Kit
0.062" PCB Standoff 647A-5015-19 Concord
Description 0.094" PCB Standoff 647A-5023-19 Concord
The SCM7B-PROTO breadboard kit was designed to allow users to incorporate
their own module functions using an SCM7B format. The kit includes a pc board
designed for breadboard circuits, a module case, header and mounting screw.
Contact the factory for additional information.
8B
SensorLex® 8B Isolated Analog Signal Conditioners
Features
• ±0.05% Accuracy (Typical)
• ±0.02% Linearity
• 1500Vrms Transformer Isolation & up to
240Vrms Field-side Protection
• ANSI/IEEE C37.90.1 Transient Protection
• 5V Power (30mA Typical)
• 5-Pole Low-Pass Filtering
• Up to 120dB CMR
• 70dB NMR at 60Hz
• –40°C to +85°C Operating Temperature
• CE Compliant
8B Modules
• UL/CUL Listing and ATEX Compliance Pending
Dataforth's new SensorLex® 8B line of isolated analog signal conditioners
• Manufactured per RoHS Directive 2002/95/EC
provides 19 family groups with a total of 123 models that interface to a wide
variety of voltage, current, temperature, position, frequency, and strain
measuring devices. Housed in a package only one-fifth the size of competing
products, the 8B offers fully functional Instrument Class® performance with Applications
superior specifications such as ±0.05% accuracy, ±0.02% linearity,
5-pole filtering, 1500Vrms isolation, low output noise and much more. • Designed for Embedded Applications
• PC/104 Embedded Solutions
Custom Signal Conditioning
• Compact PCI Systems
Custom modules are available: consult factory for minimum quantity and • VMEbus Systems
pricing details on custom input ranges, output ranges, bandwidth, and other
key parameters. • PXI Systems
• Protects User Equipment from Lightning and
Industrial Equipment Power-Line Voltage
• Reduces Electrical Noise in Measured Signals
• Convenient System Expansion and Repair
8B Selection Guide
VOLTAGE INPUT MODULES, 3Hz BANDWIDTH Page 104 THERMOCOUPLE INPUT MODULES (0 to +5V OUTPUT, 3Hz BW) Page 116
MODEL INPUT RANGE OUTPUT RANGE MODEL TYPE INPUT RANGE
8B30-01 ±10mV ±5V 8B37J J –100°C to +760°C (–148°F to +1400°F)
8B30-02 ±50mV ±5V 8B37K K –100°C to +1350°C (–148°F to +2462°F)
8B30-03 ±100mV ±5V 8B37T T –100°C to +400°C (–148°F to +752°F)
8B31-01 ±1V ±5V 8B37R R 0°C to +1750°C (+32°F to +3182°F)
8B31-02 ±5V ±5V 8B37S S 0°C to +1750°C (+32°F to +3182°F)
8B31-03 ±10V ±5V
8B31-04 ±1V 0 to +5V STRAIN GAGE INPUT MODULES Page 118
8B31-05 ±5V 0 to +5V MODEL INPUT RANGE EXCITATION SENS OUTPUT BW
8B31-06 ±10V 0 to +5V VOLTAGE RANGE
8B
8B31-07 ±20V ±5V 8B38-01 ±10mV +3.333V 3mV/V ±5V 8kHz
8B31-08 ±20V 0 to +5V 8B38-02 ±30mV +10.0V 3mV/V ±5V 8kHz
8B31-09 ±40V ±5V 8B38-05 ±20mV +10.0V 2mV/V ±5V 8kHz
8B31-10 ±40V 0 to +5V
8B31-12 ±60V ±5V 8B38-31 ±10mV +3.333V 3mV/V ±5V 3Hz
8B31-13 ±60V 0 to +5V 8B38-32 ±30mV +10.0V 3mV/V ±5V 3Hz
8B38-35 ±20mV +10.0V 2mV/V ±5V 3Hz
2-WIRE TRANSMITTER INTERFACE MODULES Page 124 VOLTAGE OUTPUT MODULES, 100Hz BANDWIDTH Page 132
MODEL INPUT RANGE OUTPUT RANGE MODEL INPUT RANGE OUTPUT RANGE
8B42-01 4 to 20mA 0 to +5V 8B49-01 0 to +5V ±5V
8B42-02 4 to 20mA +1 to +5V 8B49-02 ±5V ±5V
8B49-03 ±5V 0 to +5V
8B49-04 0 to +10V ±10V
VOLTAGE INPUT MODULES, 1kHz BANDWIDTH Page 126 8B49-05 ±10V ±10V
MODEL INPUT RANGE OUTPUT RANGE 8B49-06 ±10V 0 to +10V
8B49-07 ±5V ±10V
8B43-01 ±1V ±5V
8B43-02
8B43-03
±2V
±3V
A RY ±5V
±5V VOLTAGE INPUT MODULES, 20kHz BANDWIDTH Page 134
8B43-04 ±4V
IMI N ±5V
MODEL INPUT RANGE OUTPUT RANGE
PREL
8B43-05 ±5V ±5V
8B50-01 ±20mV ±5V
8B43-11 ±1V 0 to +5V 8B50-02 ±50mV ±5V
8B43-12 ±2V 0 to +5V 8B50-03 ±100mV ±5V
8B43-13 ±3V 0 to +5V
8B43-14 ±4V 0 to +5V 8B51-01 ±1V ±5V
8B43-15 ±5V 0 to +5V 8B51-02 ±5V ±5V
8B51-03 ±10V ±5V
8B51-04 ±1V 0 to +5V
FREQUENCY INPUT MODULES Page 128 8B51-05 ±5V 0 to +5V
MODEL INPUT RANGE OUTPUT RANGE 8B51-06 ±10V 0 to +5V
8B45-01 0 to 500Hz 0 to +5V 8B51-07 ±20V ±5V
8B45-02 0 to 1kHz 0 to +5V 8B51-08 ±20V 0 to +5V
8B45-03 0 to 2.5kHz 0 to +5V 8B51-09 ±40V ±5V
8B45-04 0 to 5kHz 0 to +5V 8B51-10 ±40V 0 to +5V
8B45-05 0 to 10kHz 0 to +5V 8B51-12 ±60V ±5V
8B45-06 0 to 25kHz 0 to +5V 8B51-13 ±60V 0 to +5V
8B45-07 0 to 50kHz 0 to +5V
8B45-08 0 to 100kHz 0 to +5V
‡
ACCESSORIES Starts on Page 137 THERMOCOUPLE ALLOY COMBINATIONS
STANDARDS: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
MODEL DESCRIPTION
TYPE MATERIAL
8BP01 Single channel DIN rail mount carrier J Iron vs. Copper-Nickel
8BP02 Standard 2-channel backpanel K Nickel-Chromium vs. Nickel-Aluminum
8BP02-1 8BP02 without cold junction compensation sensor T Copper vs. Copper-Nickel
8BP02-2 8BP02 with DIN rail mounting option R Platinum-13% Rhodium vs. Platinum
8BP02-3 8BP02-1 with DIN rail mounting option S Platinum-10% Rhodium vs. Platinum
8BP04 Standard 4-channel backpanel
8BP04-1 8BP04 without cold junction compensation sensor
8BP04-2 8BP04 with DIN rail mounting option **RTD STANDARDS
8BP04-3 8BP04-1 with DIN rail mounting option TYPE ALPHA COEFFICIENT DIN JIS IEC
8B
8BP08 Standard 8-channel backpanel
100Ω PT 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
8BP08-1 8BP08 without cold junction compensation sensor 120Ω NI 0.00672
8BP08-2 8BP08 with DIN rail mounting option
8BP08-3 8BP08-1 with DIN rail mounting option
8BP16 Standard 16-channel backpanel
8BP16-1 8BP16 without cold junction compensation sensor
8BP16-2 8BP16 with DIN rail mounting option
8BP16-3 8BP16-1 with DIN rail mounting option
8BPWR-2 Power Supply Module
SCMXPRT-001 Power supply, 1A, 5VDC, 120VAC
SCMXPRE-001 Power supply, 1A, 5VDC, 220VAC
SCMXPRT-003 Power supply, 3A, 5VDC, 120VAC
SCMXPRE-003 Power supply, 3A, 5VDC, 220VAC
PWR-4505 Power supply, 5A, 5VDC, 85-264VAC
SCMXCA006-xx System interface cable for backpanels
8BXIF DB25 to screw terminal interface board
8BXCJC Cold Junction Compensation sensor
8BPT Non-isolated signal pass thru module
8B-PROTO Breadboard kit
SCMXRK-002 19-inch metal rack for mounting backpanels
SCMXRAIL1-XX DIN EN50022-35x7.5 (slotted steel), length -XX in meters
SCMXRAIL2-XX DIN EN50035-G32 (slotted steel), length -XX in meters
SCMXRAIL3-XX DIN EN50022-35x15 (slotted steel), length -XX in meters
8B30/31
Voltage Input Modules, Narrow Bandwidth
Description
8B modules are an optimal solution for monitoring real-world process signals
Features
and providing high-level signals to a data acquisition system. Each 8B30 or
8B31 module isolates, filters, and amplifies a voltage input signal and provides • Accepts Millivolt and Voltage Level Signals
an analog voltage output. • High-Level Voltage Outputs
Signal filtering is accomplished with a 5-pole filter optimized for time and • 1500Vrms Isolation
frequency response which provides 70dB of normal-mode rejection at 60Hz.
• ANSI/IEEE C37.90.1 Transient Protection
One pole of this filter is on the field side of the isolation barrier for anti-aliasing,
and the other four are on the system side. • Input Protection to 240VAC Continuous
A special input circuit on the 8B30 and 8B31 modules provides protection • 120dB CMR
against accidental connection of power-line voltages up to 240VAC. Clamp • 70dB NMR at 60Hz
circuits on the I/O and power terminals protect against harmful transients.
• ±0.05% Accuracy
Isolation is provided by optical coupling to suppress transmission of common • ±0.02% Linearity
mode spikes or surges. The module is powered from +5VDC, ±5%.
• Low Drift with Ambient Temperature
The modules are designed for installation in Class I, Division 2 hazardous
• CE Compliant
locations and have a high level of immunity to environmental noise.
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
CMV, Input to Output 1500Vrms max * 8B31-06 –10V to +10V 0V to +5V
Transient, Input to Output ANSI/IEEE C37.90.1 * 8B31-07 –20V to +20V –5V to +5V
CMR (50Hz or 60Hz) 120dB *
NMR 70dB at 60Hz * 8B31-08 –20V to +20V 0V to +5V
8B31-09 –40V to +40V –5V to +5V
Accuracy(2) ±0.05% Span * 8B31-10 –40V to +40V 0V to +5V
Linearity ±0.02% Span * 8B31-12 –60V to +60V –5V to +5V
Stability
Offset ±10ppm/°C *
8B31-13 –60V to +60V 0V to +5V
Gain ±50ppm/°C ±75ppm/°C
Noise
Output, 100kHz 250µVrms *
Bandwidth, –3dB 3Hz *
Response Time, 90% Span 160ms *
Output Range See Ordering Information *
Output Protection Continuous Short to Ground *
Transient ANSI/IEEE C37.90.1 *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 25mA *
Power Supply Sensitivity ±75ppm/% *
Mechanical Dimensions 1.11" x 1.65" x 0.40" *
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD,EFT Performance B *
NOTES:
* Same specification as 8B30.
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) Includes linearity, hysteresis and repeatability.
8B32
Current Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B32 module
Features
isolates, filters, and amplifies a process current input signal and provides an • Accepts Milliamp Level Signals
analog voltage output. • High-Level Voltage Outputs
Current to voltage conversion is accomplished internal to the module to ensure • 1500Vrms Isolation
high accuracy.
• ANSI/IEEE C37.90.1 Transient Protection
Signal filtering is accomplished with a 3-pole filter optimized for time and
• Input Protection to 40VAC Continuous
frequency response which provides 70dB of normal-mode rejection at 60Hz.
One pole of this filter is on the field side of the isolation barrier for anti-aliasing, • 120dB CMR
and the other two are on the system side. • 70dB NMR at 60Hz
A special input circuit on the 8B32 module provides protection against acciden- • ±0.05% Accuracy
tal connection of power-line voltages up to 40VAC. Clamp circuits on the I/O and • ±0.02% Linearity
power terminals protect against harmful transients.
• Low Drift with Ambient Temperature
Isolation is provided by optical coupling to suppress transmission of common
• CE Compliant
mode spikes or surges. The module is powered from +5VDC, ±5%.
• UL/CUL Listing and ATEX Compliance Pending
The modules are designed for installation in Class I, Division 2 hazardous
locations and have a high level of immunity to environmental noise. • Mix and Match Module Types on Backpanel
8B
NMR 70dB at 60Hz
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability.
8B33
Isolated True RMS Input Modules
Description
Each 8B33 True RMS input module provides a single channel of AC input which
is converted to its True RMS DC value, filtered, isolated, amplified, and
Features
converted to a standard process voltage output (Figure 1). • Interfaces to RMS Voltage (0-300V) or RMS
Current (0-1A)
The field voltage or current input signal is processed through a pre-amplifier and
RMS converter on the field side of the isolation barrier. The converted DC signal • Designed for Standard Operation with
is then chopped by a proprietary chopper circuit and transferred across the Frequencies of 45Hz to 1000Hz (Extended
transformer isolation barrier, suppressing transmission of common mode Range to 10kHz)
spikes and surges. The computer side circuitry reconstructs, filters, and • Compatible with Standard Current and
converts the signal to an industry standard output of 0 to 5VDC. Potential Transformers
Special input circuits provide protection against accidental connection of power • Industry Standard Output of 0 to 5VDC
line voltages up to 350VAC and against transient events defined by ANSI/IEEE
• ±0.25% Factory Calibrated Accuracy
C37.90.1.
• 1500Vrms Transformer Isolation
• Input Overload Protected to 350Vrms Max
(Peak AC & DC) or 2Arms Continuous
• 120dB CMR
• 70dB NMR at 60Hz
• ANSI/IEEE C37.90.1 Transient Protection
• CE Compliant
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
Transient (-01 thru -05) ANSI/IEEE C37.90.1
Transient (-06) See note 2
Output
Signal Range 0V to 5V
Voltage Limit ±9V
Protection Continuous Short to Ground
Ripple and Noise 0.0375% Span rms
Accuracy (10-100% Span)(3) (4)
Sinusoid
50/60Hz ±0.25% Span
45Hz to 1kHz ±0.625% Span
1kHz to 10kHz ±1.375% Span, ±3.25% Span(-06)
Non-Sinusoid
Crest Factor = 1 ±0.25% Span
Crest Factor = 2 ±0.325% Span
Crest Factor = 3 ±0.475% Span
Crest Factor = 4 ±0.7% Span
Vs. Temperature ±100ppm/ºC
Isolation (Common Mode)
Input to Output, Input to Power
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
NOTES:
(1) 8B33 and 8BP01, 8BP02, 8BP04, 8BP08, 8BP16, XEV rating only. Backpanels obtained from
other sources may have lower ratings.
(2) For 1 to 25 seconds the max allowable transient current rating is √2500/(event time). For less
than 1 second, ANSI/IEEE C37.90.1 applies with a 0.05 Ω load. For greater than 25 seconds, the
2 Arms continous rating applies.
(3) At standard 60Hz factory calibration. Consult factory for calibration at other frequencies.
(4) For 0-10% Span measurements, add 0.25% accuracy error (-02 through -07) or 1.00% accuracy
error (-01). Accuracy includes linearity, hysteresis and repeatability but not source or external
shunt inaccuracy (if used).
8B34
Linearized 2- or 3-Wire RTD Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B34 input Features
module isolates, filters, amplifies, and linearizes a single channel of temperature • Interfaces to 100Ω Platinum RTDs
input from an RTD and provides an analog voltage output.
• Linearizes RTD Signal
RTD excitation is provided from the module using two matched current sources. • High-Level Voltage Outputs
When using a 3-wire connection, this method allows equal currents to flow
through the sensor leads, canceling the effects of lead resistances.The excita- • 1500Vrms Isolation
tion currents are small (0.25mA) which minimizes self-heating of the RTD. • ANSI/IEEE C37.90.1 Transient Protection
Signal filtering is accomplished with a 3-pole filter optimized for time and • Input Protection to 240VAC Continuous
frequency response which provides 70dB of normal-mode rejection at 60Hz. • 120dB CMR
One pole of this filter is on the field side of the isolation barrier for anti-aliasing,
and the other two are on the system side. • 70dB NMR at 60Hz
• Low Drift with Ambient Temperature
A special input circuit on the 8B34 module provides protection against
accidental connection of power-line voltages up to 240VAC. Clamp circuits on • CE Compliant
the I/O and power terminals protect against harmful transients. • UL/CUL Listing and ATEX Compliance Pending
The modules are designed for installation in Class I, Division 2 hazardous • Mix and Match Module Types on Backpanel
locations and have a high level of immunity to environmental noise.
8B
CMV, Input to Output 1500Vrms max
Transient, Input to Output ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 120dB
NMR 70dB at 60Hz **RTD Standards
Accuracy See Ordering Information Type Alpha Coefficient DIN JIS IEC
Stability
Offset ±20ppm/°C 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
Gain ±50ppm/°C
Noise
Output, 100kHz 200µVrms
Bandwidth, –3dB 3Hz
Response Time, 90% Span 150ms
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) "Ω" refers to the resistance in one lead.
(3) Includes conformity, hysteresis and repeatability.
8B35
Linearized 4-Wire RTD Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B35 input Features
module isolates, filters, amplifies, and linearizes a single channel of temperature • Interfaces to 100Ω Platinum RTDs
input from an RTD and provides an analog voltage output.
• True 4-Wire Input
RTD excitation is provided from the module using a precision current source. • Linearizes RTD Signal
Excitation current does not flow in the input signal leads, which allows RTD
measurements to be made independently of lead resistance. The excitation • High-Level Voltage Outputs
currents are small (0.25mA) which minimizes self-heating of the RTD. • 1500Vrms Isolation
Signal filtering is accomplished with a 3-pole filter optimized for time and • ANSI/IEEE C37.90.1 Transient Protection
frequency response which provides 70dB of normal-mode rejection at 60Hz. • Input Protection to 240VAC Continuous
One pole of this filter is on the field side of the isolation barrier for anti-aliasing,
and the other two are on the system side. • 120dB CMR
• 70dB NMR at 60Hz
A special input circuit on the 8B35 module provides protection against
accidental connection of power-line voltages up to 240VAC. Clamp circuits on • Low Drift with Ambient Temperature
the I/O and power terminals protect against harmful transients. • CE Compliant
The modules are designed for installation in Class I, Division 2 hazardous • UL/CUL Listing and ATEX Compliance Pending
locations and have a high level of immunity to environmental noise. • Mix and Match Module Types on Backpanel
8B
CMV, Input to Output 1500Vrms max
Transient, Input to Output ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 120dB
NMR 70dB at 60Hz **RTD Standards
Accuracy See Ordering Information Type Alpha Coefficient DIN JIS IEC
Stability
Offset ±20ppm/°C 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
Gain ±50ppm/°C
Noise
Output, 100kHz 200µVrms
Bandwidth, –3dB 3Hz
Response Time, 90% Span 150ms
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) "Ω" refers to the resistance in one lead.
(3) Includes conformity, hysteresis and repeatability.
8B36
Potentiometer Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B36 input
Features
module isolates, filters, and amplifies a single channel of potentiometer input • Interfaces to Potentiometers up to 10,000Ω
and provides an analog voltage output. • High-Level Voltage Output
Excitation for the potentiometer is provided by using two matched current • 1500Vrms Isolation
sources. When using a 3-wire connection, this method allows equal currents to
flow through the sensor leads, canceling the effects of lead resistances.The • ANSI/IEEE C37.90.1 Transient Protection
excitation currents are small (equal to or less than 0.25mA) which minimizes • Input Protection to 240VAC Continuous
self-heating of the potentiometer. • 120dB CMR
Signal filtering is accomplished with a 3-pole filter optimized for time and • 70dB NMR at 60Hz
frequency response which provides 70dB of normal-mode rejection at 60Hz.
• ±0.05% Accuracy
One pole of this filter is on the field side of the isolation barrier for anti-aliasing,
and the other two are on the system side. • ±0.02% Linearity
A special input circuit on the 8B36 module provides protection against acciden- • Low Drift with Ambient Temperature
tal connection of power-line voltages up to 240VAC. Clamp circuits on the I/O • CE Compliant
and power terminals protect against harmful transients.
• UL/CUL Listing and ATEX Compliance Pending
The modules are designed for installation in Class I, Division 2 hazardous • Mix and Match Module Types on Backpanel
locations and have a high level of immunity to environmental noise.
8B
Lead Resistance Effect ±0.01Ω/Ω; 100Ω, 500Ω, 1kΩ Sensor
±0.02Ω/Ω; 10kΩ Sensor
CMV, Input to Output 1500Vrms max
Transient, Input to Output ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 120dB
NMR 70dB at 60Hz
Accuracy(2) ±0.05% Span
Linearity ±0.02% Span
Stability
Offset ±20ppm/°C
Gain ±50ppm/°C
Noise
Output, 100kHz 200µVrms
Bandwidth, –3dB 3Hz
Response Time, 90% Span 150ms
Output Range 0V to +5V
Output Protection Continuous Short to Ground
Transient ANSI/IEEE C37.90.1
Open Input Response Downscale
Open Input Detection Time 1s
Power Supply Voltage +5VDC ±5%
Power Supply Current 25mA
Power Supply Sensitivity ±75ppm/%
Mechanical Dimensions 1.11" x 1.65" x 0.40"
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) Includes linearity, hysteresis and repeatability.
8B37
Non-Linearized Thermocouple Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
Features
and providing high-level signals to a data acquisition system. Each 8B37 non-
linearized module isolates, filters, and amplifies a single channel of temperature • Interfaces to Types J, K, T, R, and S
input from a thermocouple input signal and provides an analog voltage output. Thermocouples
The 8B37 can interface to industry standard thermocouple types • High-Level Voltage Output
J, K, T, R, and S and has an output signal of 0 to +5V. Each module is cold- • 1500Vrms Isolation
junction compensated to correct for parasitic thermocouples formed by the • ANSI/IEEE C37.90.1 Transient Protection
thermocouple wire and screw terminals on the mounting backpanel. Upscale
open thermocouple detect is provided by an internal pull-up resistor. • Input Protection to 240VAC Continuous
• 120dB CMR
Signal filtering is accomplished with a 3-pole filter optimized for time and
frequency response which provides 70dB of normal-mode rejection at 60Hz. • 70dB NMR at 60Hz
One pole of this filter is on the field side of the isolation barrier for anti-aliasing, • ±0.05% Accuracy
and the other two are on the system side.
• ±0.02% Linearity
A special input circuit on the 8B37 module provides protection against
• Low Drift with Ambient Temperature
accidental connection of power-line voltages up to 240VAC. Clamp circuits on
the I/O and power terminals protect against harmful transients. • Accurate CJC –40°C to +85°C
The modules are designed for installation in Class I, Division 2 hazardous • CE Compliant
locations and have a high level of immunity to environmental noise. • UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
Transient, Input to Output ANSI/IEEE C37.90.1
CMR (50Hz or 60Hz) 120dB (+32°F to +3182°F)
NMR 70dB at 60Hz
8B37S S 0°C to +1750°C 0V to +5V ±0.05% ±0.88°C
Accuracy See Ordering Information (+32°F to +3182°F)
Linearity ±0.02% Span
Stability
Offset ±20ppm/°C
Gain ±50ppm/°C ‡
Thermocouple Alloy Combinations
Noise Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
Output, 100kHz 250µVrms
Bandwidth, –3dB 3Hz
Response Time, 90% Span 150ms Type Material
Output Range 0V to +5V J Iron vs. Copper-Nickel
Output Protection Continuous Short to Ground K Nickel-Chromium vs. Nickel-Aluminum
Transient ANSI/IEEE C37.90.1 T Copper vs. Copper-Nickel
Cold Junction Compensation R Platinum-13% Rhodium vs. Platinum
Accuracy, 25°C ±0.5°C S Platinum-10% Rhodium vs. Platinum
Accuracy, –40°C to +85°C (J,K,T) ±1.5°C
Accuracy, –20°C to +65°C (R,S) ±3.0°C
Accuracy, –40°C to +85°C (R,S) ±5.0°C
Open Input Response Upscale
Open Input Detection Time <10s
Power Supply Voltage +5VDC ±5%
Power Supply Current 30mA
Power Supply Sensitivity ±75ppm/%
8B38
Strain Gage Input Modules, Wide and Narrow Bandwidth
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B38 module
Features
isolates, filters, and amplifies a full-bridge strain gage input signal and provides • Interfaces to 100Ω through 2kΩ Full-Bridge
an analog voltage output. Strain Gages
The 8B38 can interface to transducers with a nominal resistance of 100Ω to 2kΩ. • High-Level Voltage Outputs
Bridge excitation is provided from the module with a stable 10.00V or 3.33V • 1500Vrms Isolation
source. Full scale sensitivities of 2mV/V and 3mV/V are offered as standard.
• ANSI/IEEE C37.90.1 Transient Protection
Signal filtering is accomplished with a 5-pole filter optimized for time and • Input Protection to 240VAC Continuous
frequency response which provides 100dB per decade of normal-mode
rejection above the filter cutoff frequency. One pole of this filter is on the field side • 100dB CMR
of the isolation barrier for anti-aliasing, and the other four are on the system side. • 3Hz or 8kHz Signal Bandwidth
A special input circuit on the 8B38 module provides protection against acciden- • ±0.05% Accuracy
tal connection of power-line voltages up to 240VAC. Clamp circuits on the I/O • ±0.02% Linearity
and power terminals protect against harmful transients.
• Low Drift with Ambient Temperature
Isolation is provided by transformer coupling to suppress transmission of
• CE Compliant
common mode spikes or surges. The module is powered from +5VDC, ±5%.
• UL/CUL Listing and ATEX Compliance Pending
The modules are designed for installation in Class I, Division 2 hazardous
locations and have a high level of immunity to environmental noise. • Mix and Match Module Types on Backpanel
8B
Excitation Output (-x1) +3.333V ±2mV *
Load Resistance 100Ω to 2kΩ *
Excitation Output (-x2,-x5) +10V ±5mV *
Load Resistance 300Ω to 2kΩ *
Excitation Load Regulation 15ppm/mA *
Excitation Stability 50ppm/°C *
Excitation Protection 120VAC *
8B39
Current Output Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B39 Features
module accepts an input signal from a non-isolated source, then isolates, filters, • Accepts High-Level Voltage or Process Current
and converts the signal to an analog process current output. Input
Signal filtering is accomplished with a 3-pole filter optimized for time and • Process Current Output
frequency response which provides 60dB per decade of normal-mode rejection • 1500Vrms Isolation
above 100Hz. One pole of this filter is on the system side and the other two are
on the isolated field side. • ANSI/IEEE C37.90.1 Transient Protection
• Output Protection to 40VAC Continuous
A special output circuit in the 8B39 module provides protection against acciden-
tal connection of power-line voltages up to 40VAC continuous. Clamp circuits • 110dB CMR
on the I/O and power terminals protect against harmful transients. • 100Hz Signal Bandwidth
The modules are designed for installation in Class I, Division 2 hazardous • ±0.05% Accuracy
locations and have a high level of immunity to environmental noise. • ±0.02% Linearity
• Low Drift with Ambient Temperature
• CE Compliant
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
Continuous 40VAC *
Transient ANSI/IEEE C37.90.1 *
CMV, Output to Input 1500Vrms max *
Transient, Output to Input ANSI/IEEE C37.90.1 *
CMR (50Hz or 60Hz) 110dB *
NMR (–3dB at 100Hz) 60dB per decade above 100Hz *
Accuracy(1) ±0.05% Span *
Linearity ±0.02% Span *
Stability
Offset ±10ppm/°C *
Gain ±50ppm/°C ±100ppm/°C
Noise
Output, 100kHz 2µArms *
Bandwidth, –3dB 100Hz *
Rise Time, 10 to 90% Span 5ms *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 100mA *
Power Supply Sensitivity ±100ppm/% *
Mechanical Dimensions 1.11" x 1.65" x 0.40" *
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm) *
Environmental
Operating Temperature Range –40°C to +85°C *
Storage Temperature Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
NOTES:
* Same specification as -01, -02, -03, -04 models.
(1) Includes linearity, hysteresis and repeatability.
8B40/41
Voltage Input Modules, 1kHz Bandwidth
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B40 or
Features
8B41 module isolates, filters, and amplifies a voltage input signal and provides • Accepts Millivolt and Voltage Level Signals
an analog voltage output. • High-Level Voltage Outputs
Signal filtering is accomplished with a 5-pole filter optimized for time and • 1500Vrms Isolation
frequency response which provides 100dB per decade of normal-mode
rejection above 1kHz. One pole of this filter is on the field side of the isolation • ANSI/IEEE C37.90.1 Transient Protection
barrier for anti-aliasing, and the other four are on the system side. • Input Protection to 240VAC Continuous
A special input circuit on the 8B40 and 8B41 modules provides protection • 100dB CMR
against accidental connection of power-line voltages up to 240VAC. Clamp • 1kHz Signal Bandwidth
circuits on the I/O and power terminals protect against harmful transients.
• ±0.05% Accuracy
Isolation is provided by optical coupling to suppress transmission of common • ±0.02% Linearity
mode spikes or surges. The module is powered from +5VDC, ±5%.
• Low Drift with Ambient Temperature
The modules are designed for installation in Class I, Division 2 hazardous
• CE Compliant
locations and have a high level of immunity to environmental noise.
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
CMV, Input to Output 1500Vrms max * 8B41-06 –10V to +10V 0V to +5V
Transient, Input to Output ANSI/IEEE C37.90.1 * 8B41-07 –20V to +20V –5V to +5V
CMR (50Hz or 60Hz) 100dB *
NMR (-3dB at 1kHz) 100dB per decade above 1kHz *
8B41-08 –20V to +20V 0V to +5V
8B41-09 –40V to +40V –5V to +5V
Accuracy(2) ±0.05% Span * 8B41-10 –40V to +40V 0V to +5V
Linearity ±0.02% Span * 8B41-12 –60V to +60V –5V to +5V
Stability 8B41-13 –60V to +60V 0V to +5V
Offset ±10ppm/°C *
Gain ±50ppm/°C ±75ppm/°C
Noise
Output, 100kHz 500µVrms *
Bandwidth, –3dB 1kHz *
Response Time, 90% Span 550µs *
Output Range See Ordering Information *
Output Protection Continuous Short to Ground *
Transient ANSI/IEEE C37.90.1 *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 25mA *
Power Supply Sensitivity ±75ppm/% *
Mechanical Dimensions 1.11" x 1.65" x 0.40" *
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD,EFT Performance B *
NOTES:
* Same specification as 8B40.
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) Includes linearity, hysteresis and repeatability.
8B42
2-Wire Transmitter Interface Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B42 module Features
provides power to a current transmitter, then isolates, filters, and amplifies the • +12VDC Loop Supply
resulting process current input signal and provides an analog voltage output.
• Provides Isolation for Non-Isolated 2-Wire
Current to voltage conversion is accomplished internal to the module to ensure Transmitters
high accuracy. • High-Level Voltage Outputs
Signal filtering is accomplished with a 3-pole filter optimized for time and • 1500Vrms Isolation
frequency response which provides 60dB per decade of normal-mode
• ANSI/IEEE C37.90.1 Transient Protection
rejection above 100Hz.
• Input Protection to 40VAC Continuous
A special input circuit on the 8B42 module provides protection against
accidental connection of power-line voltages up to 40VAC. Clamp circuits on the • 100dB CMR
I/O and power terminals protect against harmful transients. • 100Hz Bandwidth
Isolation is provided by transformer coupling to suppress transmission of • ±0.05% Accuracy
common mode spikes or surges. The module is powered from +5VDC, ±5%. • ±0.02% Linearity
The modules are designed for installation in Class I, Division 2 hazardous • Low Drift with Ambient Temperature
locations and have a high level of immunity to environmental noise. • CE Compliant
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
Transient, Input to Output ANSI/IEEE C37.90.1
CMR (50Hz or 60Hz) 100dB
NMR 60dB per decade above 100Hz
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability.
8B43
DC LVDT Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B43 module
Features
isolates, filters, and amplifies a voltage input signal and provides an analog • Interfaces to DC Linear Voltage Displacement
voltage output. Transducers
The 8B43 can interface to transducers that will operate on a 10V excitation • High-Level Voltage Outputs
voltage and up to 20mA of excitation current. • 1500Vrms Isolation
Signal filtering is accomplished with a 5-pole filter optimized for time and • ANSI/IEEE C37.90.1 Transient Protection
frequency response which provides 100dB per decade of normal-mode • Input Protection to 240VAC Continuous
rejection above 1kHz. One pole of this filter is on the field side of the isolation
barrier for anti-aliasing, and the other four are on the system side. • 100dB CMR
A special input circuit on the 8B43 modules provides protection against • 1kHz Signal Bandwidth
accidental connection of power-line voltages up to 240VAC. Clamp circuits on • ±0.05% Accuracy
the I/O and power terminals protect against harmful transients. • ±0.02% Linearity
Isolation is provided by transformer coupling to suppress transmission of • Low Drift with Ambient Temperature
common mode spikes or surges. The module is powered from +5VDC, ±5%.
• CE Compliant
The modules are designed for installation in Class I, Division 2 hazardous • UL/CUL Listing and ATEX Compliance Pending
locations and have a high level of immunity to environmental noise.
• Mix and Match Module Types on Backpanel
N A RY
L I M I
P R E
8B
Excitation 8B43-14 –4V to +4V 0V to +5V
Voltage +10V ±5mV 8B43-15 –5V to +5V 0V to +5V
Current 5mA min, 30mA max
Load Regulation 15ppm/mA
Stability 50ppm/°C
Protection 120VAC
Y
120VAC between +EXC and –EXC terminals.
R
(2) Includes linearity, hysteresis and repeatability.
M I N A
R E L I
P
Visit our website www.dataforth.com 127
©1995-2011 Dataforth Corporation, All Rights Reserved ISO9001:2008-Registered QMS
SensorLex® 8B Isolated Analog Signal Conditioning Products 8B
8B45
Frequency Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B45 module
Features
isolates and conditions a frequency input signal and provides an analog voltage • Accepts Frequency Input Signals 0 to 100kHz
output. • TTL or Zero-Crossing Signal Inputs
The frequency input signal can be either a TTL level or zero crossing with as little • High-Level Voltage Outputs
as ±100mV amplitude. Input circuitry for each signal type has built-in hysteresis
to prevent spurious noise from corrupting the module output. TTL signals are • 1500Vrms Isolation
applied to the + and – terminals while zero crossing signals are applied to the • ANSI/IEEE C37.90.1 Transient Protection
+EXC and – terminals. Reference the block diagram below. • Input Protection to 240VAC Continuous
A 5V excitation is available for use with magnetic pick-up or contact closure type • 100dB CMR
sensors. The excitation is available on the –EXC terminal with return on the
• ±0.10% Accuracy
– terminal.
• ±0.05% Linearity
A special input circuit on the 8B45 module provides protection against
accidental connection of power-line voltages up to 240VAC. Clamp circuits on • Low Drift with Ambient Temperature
the I/O and power terminals protect against harmful transients. • CE Compliant
Isolation is provided by optical coupling to suppress transmission of common • UL/CUL Listing and ATEX Compliance Pending
mode spikes or surges. The module is powered from +5VDC, ±5%. • Mix and Match Module Types on Backpanel
The modules are designed for installation in Class I, Division 2 hazardous
locations and have a high level of immunity to environmental noise.
8B
Normal 68kΩ
Power Off 68kΩ
Overload 68kΩ
Input Protection
Continuous(1) 240Vrms max
Transient ANSI/IEEE C37.90.1
Excitation +5V at 8mA max
CMV, Input to Output
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 100dB
Accuracy(2) ±0.05% Span
Linearity ±0.02% Span
Stability
Offset ±25ppm/°C
Gain ±100ppm/°C
Noise
Output Ripple <10mVp-p at Input >2% span
Response Time (0 to 90%)
8B45-01, -02, -03 160ms, 80ms, 35ms
8B45-04, -05, -06 16ms, 8.5ms, 3.4ms
8B45-07, -08 1.6ms, 0.8ms
Output Range 0 to +5V
Output Protection Continuous Short to Ground
Transient ANSI/IEEE C37.90.1
Power Supply Voltage +5VDC ±5%
Power Supply Current 45mA
Power Supply Sensitivity ±75ppm/%
Mechanical Dimensions 1.11" x 1.65" x 0.40"
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Environmental
Operating Temp. Range –40°C to +85°C
Storage Temp. Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD,EFT Performance B
NOTES:
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) Includes linearity, hysteresis and repeatability.
8B47
Linearized Thermocouple Input Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B47 Features
module isolates, filters, amplifies, and linearizes a single channel of temperature • Interfaces to Types J, K, and T Thermocouples
input from a thermocouple and provides an analog voltage output.
• Linearizes Thermocouple Signal
Linearization is accomplished using a four breakpoint piecewise linear • High-Level Voltage Outputs
approximation.
• 1500Vrms Isolation
The 8B47 can interface to industry standard thermocouple types
• ANSI/IEEE C37.90.1 Transient Protection
J, K, and T and has an output signal of 0 to +5V. Each module is cold-junction
compensated to correct for parasitic thermocouples formed by the • Input Protection to 240VAC Continuous
thermocouple wire and screw terminals on the mounting backpanel. Upscale • 120dB CMR
open thermocouple detect is provided by an internal pull-up resistor.
• 70dB NMR at 60Hz
Signal filtering is accomplished with a 3-pole filter optimized for time and
• Low Drift with Ambient Temperature
frequency response which provides 70dB of normal-mode rejection at 60Hz.
One pole of this filter is on the field side of the isolation barrier for anti-aliasing, • Accurate CJC –40°C to +85°C
and the other two are on the system side. • CE Compliant
A special input circuit on the 8B47 module provides protection against • UL/CUL Listing and ATEX Compliance Pending
accidental connection of power-line voltages up to 240VAC. Clamp circuits on • Mix and Match Module Types on Backpanel
the I/O and power terminals protect against harmful transients.
The modules are designed for installation in Class I, Division 2 hazardous
locations and have a high level of immunity to environmental noise.
8B
Transient, Input to Output ANSI/IEEE C37.90.1
CMR (50Hz or 60Hz) 120dB 8B47K-04 K 0°C to +1000°C 0V to +5V ±0.15% ±2.40°C
NMR 70dB at 60Hz (+32°F to +1832°F)
Accuracy See Ordering Information 8B47K-05 K 0°C to +500°C 0V to +5V ±0.15% ±1.05°C
Stability (+32°F to +932°F)
Offset ±20ppm/°C
Gain ±75ppm/°C 8B47K-13 K –100°C to +1350°C 0V to +5V ±0.15% ±3.60°C
Noise (–148°F to +2462°F)
Output, 100kHz 250µVrms
Bandwidth, –3dB 3Hz 8B47K-14 K 0°C to +1200°C 0V to +5V ±0.15% ±2.88°C
Response Time, 90% Span 150ms (+32°F to +2192°F)
Output Range 0V to +5V 8B47T-06 T –100°C to +400°C 0V to +5V ±0.20% ±2.40°C
Output Protection Continuous Short to Ground (–148°F to +752°F)
Transient ANSI/IEEE C37.90.1
Cold Junction Compensation 8B47T-07 T 0°C to +200°C 0V to +5V ±0.20% ±0.75°C
Accuracy, 25°C ±0.5°C (+32°F to +392°F)
Accuracy, –40°C to +85°C ±1.5°C
Open Input Response Upscale ‡
Thermocouple Alloy Combinations
Open Input Detection Time <10s
Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
Power Supply Voltage +5VDC ±5%
Power Supply Current 30mA
Power Supply Sensitivity ±100ppm/% Type Material
Mechanical Dimensions 1.11" x 1.65" x 0.40" J Iron vs. Copper-Nickel
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm) K Nickel-Chromium vs. Nickel-Aluminum
T Copper vs. Copper-Nickel
Environmental
Operating Temperature Range –40°C to +85°C
Storage Temperature Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) Includes conformity, hysteresis and repeatability. Does not include CJC accuracy.
8B49
Voltage Output Modules
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B49 Features
module accepts an input signal from a non-isolated source, then isolates, filters • Accepts High-Level Voltage
and converts the signal to a high-level process voltage output.
• Isolated Process Voltage Output
Signal filtering is accomplished with a 4-pole filter optimized for time and • 1500Vrms Isolation
frequency response which provides 80dB per decade of normal-mode rejection
above 100Hz. One pole of this filter is on the system side and the other three are • ANSI/IEEE C37.90.1 Transient Protection
on the isolated field side. • Output Protection to 40VAC Continuous
A special output circuit in the 8B49 module provides protection against • 110dB CMR
accidental connection of power-line voltages up to 40VAC continuous. Clamp • 100Hz Signal Bandwidth
circuits on the I/O and power terminals protect against harmful transients.
• ±0.05% Accuracy
The modules are designed for installation in Class I, Division 2 hazardous • ±0.02% Linearity
locations and have a high level of immunity to environmental noise.
• Low Drift with Ambient Temperature
• CE Compliant
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
CMV, Output to Input
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
CMR (50 or 60Hz) 110dB
NMR (–3dB at 100Hz) 80dB per decade above 100Hz
Accuracy(1) ±0.05% Span (0 to 10mA Load)
±0.075% Span (10 to 20mA Load)
Linearity ±0.02% Span
Stability
Offset ±10ppm/°C
Gain ±50ppm/°C
Noise
Output, 100kHz 1.5mVrms
Bandwidth, –3dB 100Hz
Response Time, 90% Span 5ms
Power Supply Voltage +5VDC ±5%
Power Supply Current 120mA Full Load, 55mA No Load
Power Supply Sensitivity ±100ppm/%
Mechanical Dimensions 1.11" x 1.65" x 0.40"
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Environmental
Operating Temp. Range –40°C to +85°C
Storage Temp. Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes linearity, hysteresis and repeatability.
8B50/51
Voltage Input Modules, 20kHz Bandwidth
Description
8B modules are an optimal solution for monitoring real-world process signals
and providing high-level signals to a data acquisition system. Each 8B50 or Features
8B51 module isolates, filters, and amplifies a voltage input signal and provides • Accepts Millivolt and Voltage Level Signals
an analog voltage output.
• High-Level Voltage Outputs
Signal filtering is accomplished with a 5-pole filter optimized for time and • 1500Vrms Isolation
frequency response which provides 100dB per decade of normal-mode
rejection above 20kHz. One pole of this filter is on the field side of the isolation • ANSI/IEEE C37.90.1 Transient Protection
barrier for anti-aliasing, and the other four are on the system side. • Input Protection to 240VAC Continuous
A special input circuit on the 8B50 and 8B51 modules provides protection • 100dB CMR
against accidental connection of power-line voltages up to 240VAC. Clamp • 20kHz Signal Bandwidth
circuits on the I/O and power terminals protect against harmful transients.
• ±0.05% Accuracy
Isolation is provided by optical coupling to suppress transmission of common • ±0.02% Linearity
mode spikes or surges. The module is powered from +5VDC, ±5%.
• Low Drift with Ambient Temperature
The modules are designed for installation in Class I, Division 2 hazardous
locations and have a high level of immunity to environmental noise. • CE Compliant
• UL/CUL Listing and ATEX Compliance Pending
• Mix and Match Module Types on Backpanel
8B
Transient, Input to Output ANSI/IEEE C37.90.1 * 8B51-06 –10V to +10V 0V to +5V
CMR (50Hz or 60Hz) 100dB *
NMR (–3dB at 20kHz) 100dB per decade above 20kHz *
8B51-07 –20V to +20V –5V to +5V
8B51-08 –20V to +20V 0V to +5V
Accuracy(2) ±0.05% Span *
Linearity ±0.02% Span * 8B51-09 –40V to +40V –5V to +5V
Stability 8B51-10 –40V to +40V 0V to +5V
Offset ±10ppm/°C * 8B51-12 –60V to +60V –5V to +5V
Gain ±50ppm/°C ±75ppm/°C 8B51-13 –60V to +60V 0V to +5V
Noise
Output, 100kHz 500µVrms *
Bandwidth, –3dB 20kHz (15kHz, 50-01) *
Rise Time, 10 to 90% Span 25µs *
Output Range See Ordering Information *
Output Protection Continuous Short to Ground *
Transient ANSI/IEEE C37.90.1 *
Power Supply Voltage +5VDC ±5% *
Power Supply Current 25mA *
Power Supply Sensitivity ±75ppm/% *
Mechanical Dimensions 1.11" x 1.65" x 0.40" *
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Environmental
Operating Temp. Range –40°C to +85°C *
Storage Temp. Range –40°C to +85°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD,EFT Performance B *
NOTES:
* Same specification as 8B50.
(1) 240VAC between +Input terminal and –Input, +EXC, or –EXC terminals.
120VAC between –Input and +EXC or –EXC terminals.
120VAC between +EXC and –EXC terminals.
(2) Includes linearity, hysteresis and repeatability.
8B
Module Dimensions and Pinouts
The following mechanical drawing is useful when designing circuit boards to number 0660. The captive nut for the 4-40 mounting screw can be obtained from
mount the 8B modules. Many sockets are available which accept PEM (Penn Engineering and Manufacturing), part number KFS2-440.
the mounting pins. As an example, Mill-Max provides a socket with part
Features
• Single Channel DIN Rail Mounting Accessory • Interface Cables
• 2-, 4-, 8-, 16-Position Backpanels • Cable-to-Screw-Terminal Interface Board
• Panel or DIN Rail Mounting Options • Power Supplies
• 19-Inch Mounting Rack for Backpanels
8BP01
8B
Single Channel DIN Rail Mount Carrier
Description
The 8BP01 is offered as a 5VDC powered (8BP01-X05) or 7 to 34VDC powered (EN 50022-35 and EN 50035-G32). The 8BP01 measures only 2.32” x 3.54” x
(8BP01-X24) single channel DIN rail mount carrier suitable for any 8B signal 0.65” (59mm x 90mm x 16.5mm), making it ideal for use in high-density
conditioner. The 8B carrier can be mounted on any standard DIN rail installations (see Figure 1). It has a flammability rating of UL-94 V-0.
Specifications Typical at TA=+25°C and +5V power Typical at TA=+25°C and +24V power 8BP01-205 5V Power, No CJC
8BP01-305 5V Power, CJC
Input Voltage Range 4.85 to 5.2VDC 7 to 34VDC 8BP01-224 24V Power, No CJC
Over-Voltage Protection 6V TVS, 1A Fuse, OV detection 36V TVS, 1A Fuse, OV detection 8BP01-324 24V Power, CJC
Over-Voltage Shutdown Voltage 5.6V max 35.5V max
Under-Voltage Turn-on – 6.5V min
Reverse Voltage Protection 1A Fuse 1A Fuse
Specifications
Operating Temperature –40°C to +85°C
Relative Humidity 95% Noncondensing
Interface Connector:
Field high density screw clamp, 16 AWG max
System high density screw clamp, 16 AWG max
Isolation:
Input-to-Output 1500Vrms continuous, max
Channel-to-Channel 1500Vrms continuous, max
Figure 2: 8BP02 Analog I/O Backpanel Figure 3: 8BP04 Analog I/O Backpanel
8B
Fusing
Backpanel power is fuse-protected through F1 and F2. Zener diodes D3 and D4
8BP04 Standard 4-channel backpanel with standoffs for mounting.
provide extra protection from overvoltage and supply reversal.
8BP04-1 8BP04 without cold junction compensation sensor. Use when
Grounding cost savings are desired and thermocouple input modules
8B37 and 8B47 will not be used.
For full protection against large electrical disturbances on the field-side of the 8B
modules, a #10-32 ground stud is provided on the backpanel. An electrical 8BP04-2 8BP04 with DIN rail mounting option. The backpanel is
connection between this ground stud and the system ground should be provided captured by DIN rail mounting elements and is shipped
fully assembled.
with a large gage wire of the shortest possible length.
8BP04-3 8BP04-1 with DIN rail mounting option.
8B
8BPWR-2
Power Supply Module
Description
The 8BPWR-2 encapsulated power supply has a wide ranging 7-34VDC input
voltage range and provides 5VDC output suitable for all 8B modules. It is
designed to mount on the 8B backpanels. The compact size and low weight are
ideal for high-density applications (see Figure 7).
Specifications Typical at TA=+25°C and +24V power
Module 8BPWR-2
Input Voltage Range 7 to 34VDC
Overvoltage Protection None (provided on backpanel)
Reverse Voltage Protection None (provided on backpanel)
Output Voltage 5VDC ±1%
Output Voltage Temp. Coeff. ±200ppm/°C
Output Current 3A (–40°C to +65°C)
2A (85°C)
Output Current Limit 4A, Auto Recovery
Line Regulation ±0.20%
Load Regulation ±0.30%
Efficiency 85%
Output Ripple 50mVp-p
Mechanical Dimensions 1.11" x 1.65" x 0.40"
(h)(w)(d) (28.1mm x 41.9mm x 10.2mm)
Figure 7: 8BPWR-2 Power Supply Module
SCMXPRT-001/D, SCMXPRE-001/D
Power Supplies
Description
The SCMXPRT-001/D and SCMXPRE-001/D encapsulated power supplies are
available in 120VAC or 220VAC input voltage ranges and provide 5VDC outputs
suitable for all 8B modules. They are designed to mount on the SCMXRK-002
metal rack (see Figure 13) or DIN rail EN 50022-35x7.5 (D versions). The
supplies are UL-recognized. Their compact size and low weight are ideal for
high-density applications (see Figure 8).
Specifications
Module SCMXPRT-001/D SCMXPRE-001/D
Input Voltage Range, 105 to 125VAC 210 to 250VAC
47Hz to 420Hz
Output Voltage 5VDC 5VDC
Output Current, +50°C 1A 1A
Operating Temperature –20°C to +71°C –20°C to +71°C
Line Regulation ±0.05% ±0.05%
Load Regulation ±0.25% ±0.25%
Output Ripple, max 1mVrms 1mVrms
Weight 1.25 lbs (567g) 1.25 lbs (567g)
Supplies are UL recognized, File No. E45344.
SCMXPRT-003, SCMXPRE-003
Power Supplies
Description
The SCMXPRT/E-003 linear power supplies are available in 120VAC or
220VAC input. They have sufficient output current capacity to supply any
combination of 8B modules. The SCMXRK-002 metal rack provides mounting
capability for the SCMXPRT/E-003 power supplies (see Figure 13).
Specifications
8B
Module SCMXPRT-003 SCMXPRE-003
Both supplies are tested and certified by TUV to VDE 0806 and IEC 380. They are UL Recognized (File Number E55974),
CSA Certified (CSA File Number LR38879), and CE Compliant.
PWR-4505
25W Single Output Industrial DIN Rail Switching Power Supply
Specifications
Input 85 to 264VAC, 120 to 370VDC
Frequency 47 to 63Hz
Input Current 1.5A/115VAC, 0.75A/230VAC
Features
Inrush Current Cold start 30A/115VAC, 60A/230VAC • Universal AC Input (85 to 264VAC)
Efficiency 72%
• DC Compatible Input (120 to 370VDC)
Output Voltage & Current Rating 5V, 5A
Temperature Coefficient ±0.03%/°C • Protections: Short Circuit, Overload, Over
Ripple Voltage 100mVp-p Voltage, Over Temperature
Overload Protection 105 to 150% rated output power
Over Voltage Protection 5.75 to 6.75V
• Mounts on DIN Rail TS-35/7.5 & 15
Over Temperature Protection 135°C detect on heatsink of power transistor • Approvals: UL, CUL, TUV, CB, CE
Dielectric Strength Between input and output terminals: 3kV, 1 minute • CE Compliant, UL 508 Listed
Between input and FG: 1.5kV, 1 minute
Between output and FG: 0.5kV, 1 minute • TUV EN60950-1 Approved
Insulation Resistance Between input and output terminals/input and FG/ • Compliant with EMC Directive EN50082-2
output and FG: 100MΩ/500VDC
• LED Indicator for Power On
Operating Temperature –10°C to +50°C
Storage Temperature –20°C to +85°C
Relative Humidity 10 to 95%
Mechanical Dimensions 3.66" x 3.07" x 2.24"
(l)(w)(h) (93mm x 78mm x 57mm)
Terminal Screw M3
8B
Male DB25 Female DB25
SCMXRK-002
19-Inch Metal Mounting Rack
Description
The SCMXRK-002 is a 19-inch metal rack for mounting the 8BP04/08/16
backpanels and the 8BXIF interface board (see Figure 13 for dimensions).
Figure 14: DIN Rail Styles Figure 15: 8BPxx-2, 8BPxx-3 Backpanel DIN Rail Mounting Option
8B-PROTO 8BXCJC
Breadboard Kit Cold Junction Compensation Sensor
Description Description
The 8B-PROTO breadboard kit was designed to allow users to incorporate their Packaged for use in customer designed mounting boards. This part has an initial
own module functions using an 8B format. The kit includes a PC board with pins tolerance of ±0.25% and comes in a standard 1206 resistor format.
designed for breadboard circuits, a module case, header and mounting screw.
Contact the factory for additional information.
8BPT
Pass-Through Module
Description
The 8BPT is a pass-through module used to establish a direct connection
between an input signal and the 8B series backplane analog bus. It has unity
gain and no isolation. It accepts up to ± 10V input and provides up to ± 10V output.
SCM9B
Isolated, Intelligent Signal Conditioning Products
SCM9B Modules
Dataforth offers high quality SCM9B products providing cost-effective protec-
tion and conditioning for a wide range of valuable industrial control signals and
systems. Our extensive line includes fixed and programmable sensor-to-
computer and computer-to-analog output interface modules, RS-232/RS-485
converters, RS-485 repeaters, and associated backplanes, accessories, and
applications software. All products are European EMC Directive Compliant.
SCM9B-1000/2000/5000/D100
Sensor-to-Computer Modules
Features
These isolated modules provide complete sensor/RS-232C or /RS-485
SCM9B
interfaces with 15-bit measurement resolution. They accept a variety of SCM9B Sensor-to-Computer Modules
voltage, current, thermocouple, RTD/thermistor, strain gage, timer/frequency, • 500Vrms Input Isolation
and multichannel digital inputs/outputs. “2000” Series modules include • Programmable Scaling and Linearization
additional programmable features such as ASCII output scaling to
• ASCII Command/Response Protocol
desired engineering units and linearization using straight-line segment
approximation. “5000” Series modules provide four analog input channels. • 15-bit Measurement Resolution
D100 Series modules are DIN rail mountable. • Continuous Self-Calibration
• Analog Readback
SCM9B-3000/4000 • DIN Rail Mountable D100 Series
Computer-to-Analog Output Modules SCM9B Computer-to-Analog Output Modules
These are complete, isolated interfaces designed for remote installation • 0-1V, ±1V, 0-5V, ±5V, 0-10V, ±10V, 0-20mA,
and communications with host computers via standard RS-232C and RS-485 4-20mA Output Ranges
serial ports. They offer 12-bit resolution in a range of analog output voltages and • 500Vrms Output Isolation
currents. “4000” series modules have fully programmable output
• 12-bit Output Resolution
slopes, true analog readback, and data scaling.
• Programmable 0.01V/s (mA/s) to
10,000V/s (mA/s) Output Slopes
SCM9B-A1000/2000/D192
SCM9B Converters and Repeaters
Converters and Repeaters
• Transparent to Host
These products convert RS-232C communications signal levels to the correct • Optically Isolated Bidirectional Data Flows
RS-485 signal requirements, and may also be configured as repeaters to
• Automatic Internal RS-485 Bus Supervision
extend communications bus lengths. They are optically isolated, require no
external control signals, and are completely transparent to host software. • DIN Rail Mountable D192 Model
All SCM9B Modules
• CE Compliant
MODEL INPUT RANGE OUTPUT SCM9B-D192 DIN Rail Mount RS-485 Repeater Page 162
Timer/Frequency Inputs MODEL DESCRIPTION
SCM9B-D161 Frequency RS-485
SCM9B-D192 RS-485 Repeater
DIGITAL DIGITAL RS SCM9B-H1700 Digital I/O Boards Page 164
MODEL INPUTS OUTPUTS OUTPUT
MODEL DESCRIPTION
Digital Input/Outputs
SCM9B-D171 6 0 RS-485 SCM9B-H1750 24 Digital Inputs/Outputs
SCM9B-D172 0 6 RS-485 SCM9B-H1770 64 Digital Inputs/Outputs
SCM9B-HCA1 4 Ribbon Connector Assembly
SCM9B-3000/4000 Computer-to-Analog Output Products Page 159
(“4000” Series products have user-programmable features) Accessories and Software Page 165
MODEL DESCRIPTION
MODEL OUTPUT RANGE INPUT SCM9B-PB08 8 Channel Backpanel
Voltage Output SCM9B-PB14 14 Channel Backpanel
SCM9B-3121/4121 ±1V RS-232C SCM9B-S300 Utility Software
SCM9B
SCM9B-3122/4122 ±1V RS-485 MA-1001 User’s Manual, SCM9B-1000
SCM9B-3131/4131 ±5V RS-232C MA-1002 User’s Manual, SCM9B-2000
SCM9B-3132/4132 ±5V RS-485 MA-1003 User’s Manual, SCM9B-3000/4000
SCM9B-3141/4141 ±10V RS-232C MA-1004 User’s Manual, SCM9B-1700
SCM9B-3142/4142 ±10V RS-485 MA-1005 User’s Manual, SCM9B-A1000/A2000
SCM9B-3161/4161 0 to 1V RS-232C MA-1011 User’s Manual, SCM9B-5000
SCM9B-3162/4162 0 to 1V RS-485 MA-1013 User’s Manual, SCM9B ModBus Protocol
SCM9B-3171/4171 0 to 5V RS-232C MA-1014 User’s Manual, SCM9B-D100
SCM9B-3172/4172 0 to 5V RS-485
SCM9B-3181/4181 0 to 10V RS-232C
SCM9B-3182/4182 0 to 10V RS-485
Current Output
SCM9B-3251/4251 0 to 20mA RS-232C
SCM9B Reliability Data
SCM9B-3252/4252 0 to 20mA RS-485 Failure rate calculations for the SCM9B modules are derived from the MIL-HDBK-217E
SCM9B-3261/4261 4 to 20mA RS-232C specification. The stress-analysis method is used at naval sheltered environment, 40°C
SCM9B-3262/4262 4 to 20mA RS-485 temperature, and quality level of B-2. Our specified humidity level is 95% RH noncondensing.
MODEL FAILURES/106 HRS MTBF (HRS)
SCM9B-A1000/A2000 Converters/Repeaters Page 161 SCM9B-1xxx/2xxx/3xxx/4xxx/5xxx 9.52 105,000
SCM9B-17xx 8.16 123,000
MODEL DESCRIPTION
SCM9B-A1000-115 RS-232C/RS-485 Converter/Repeater, 115VAC
SCM9B-A1000-230 RS-232C/RS-485 Converter/Repeater, 230VAC
SCM9B-A2000 RS-232C/RS-485 Converter/Repeater, +10 to +30VDC
SCM9B-1000/2000 Series
Sensor-to-Computer Modules
Description
The SCM9B-1000/2000 Sensor-to-Computer Modules are a family of complete
solutions designed for data acquisition systems based on personal computers Features
and other processor-based equipment with standard serial I/O ports. The • Complete Sensor to RS-485 or RS-232C Interface
modules convert analog input signals to engineering units and transmit in ASCII
• ASCII Format Command/Response Protocol
format to any host with standard RS-485 or RS-232C ports. These modules can
measure temperature, pressure, voltage, current and various types of • 500Vrms Analog Input Isolation
digital signals. The modules provide direct connection to a wide variety of • 15-Bit Measurement Resolution
sensors and perform all signal conditioning, scaling, linearization and conver-
sion to engineering units. Each module also provides digital I/O lines for • Continuous Self-Calibration; No Adjustments of Any Kind
controlling devices through solid state relays or TTL signals. These digital I/O • Programmable Digital Filter
lines along with built-in limit setting capability provide alarm and control outputs • Digital Limit Setting and Alarm Capability
(see Figure 1).
• Digital Inputs and Outputs Connect to Solid State Relays
The modules contain no pots or switches to be set. Features such as address,
• Events Counter to 10 Million
data rate, parity, alarms, echo, etc. are selectable using simple commands
over the communications port—without requiring access to the module. The • Requires +10V to +30VDC Unregulated Supply
selections are stored in nonvolatile EEPROM which maintains data even after • Transient Suppression on RS-485
power is removed. Communications Lines
The 2000 series is an enhanced version of the 1000 series of sensor interfaces. • Screw Terminal Plug Connectors Supplied
The 2000 series allows the user to scale the output data in any desired
• CE Compliant
engineering units. The 2000 also provides the ability to program nonlinear
transfer functions. This feature may be used to linearize nonstandard sensors Programmable Features (2000 Series)
or to provide outputs in engineering units which are nonlinear functions (Provides intelligent features not found in the 1000 series.)
of the input.
• ASCII Output Scaled to Desired Engineering Units
• User Programmable Nonlinear Transfer Function
• Straight-Line Segment Approximation: up to 24 Segments
Specifications Typical at 25°C and nominal power supply unless otherwise noted
SCM9B
±1.0 °C max (J, K, T, E).
Digital inputs ±2.5 °C max (R, S, B, C)(300°C to FS).
• Voltage levels: ±30V without damage. • Common mode rejection: 100dB at 50/60Hz.
• Switching levels: High, 3.5V min., low, 1.0V max. • Input impedance: 100MΩ min.
• Internal pull up resistors for direct switch input. • Lead resistance effect: <20µV per 350Ω.
• Open thermocouple indication.
Digital outputs
• Input burnout protection to 250VAC.
• Open collector to 30V, 30mA max. load. • User selectable °C or °F.
• Overrange indication.
Alarm outputs
• Automatic cold junction compensation and linearization.
• HI/LO limit checking by comparing input values to down-loaded HI/LO limit values • 2 Digital inputs, Event counter, 3 Digital outputs.
stored in memory.
• Alarms: latching (stays on if input returns to within limits) or momentary (turns off if 1400 RTD Input Modules
input returns to within limits.) • RTD types: α = .00385, .00392, 100Ω at 0°C,
.00388, 100Ω at 25°C.
Communications • Ranges: .00385 = –200°C to +850°C.
• Communications in ASCII via RS-232C, RS-485 ports. .00392 = –200°C to +600°C.
• Selectable data rates: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400bps. .00388 = –100°C to +125°C.
• NRZ asynchronous data format; 1 start bit, 7 data bits, 1 parity bit and 1 stop bit. • Resolution: 0.1°.
• Parity: odd, even, none. • Accuracy: ±0.3°C.
• User selectable channel address. • Common mode rejection: 100dB at 50/60Hz.
• ASCII format command/response protocol. • Input connections: 2, 3, or 4 wire.
• Up to 124 multidrop modules per host serial port. • Excitation current: 0.25mA.
• Communications distance up to 10,000 feet (RS-485). • Lead resistance effect: 3 wire - 2.5°C per Ω of imbalance.
• Transient suppression on RS-485 communications lines. 4 wire - negligible.
• Communications error checking via checksum. • Max lead resistance: 50Ω.
• Can be used with "dumb terminal". • Input protection to 120VAC .
• Scan up to 250 channels per second. • Automatic linearization and lead compensation.
• All communications setups stored in EEPROM. • User selectable °C or °F.
• 1 Digital output.
Power
• Requirements: Unregulated +10V to +30VDC, 0.75W max (1500/2500, 2.0W max.) 1450 Thermistor Input Modules
• Internal switching regulator. • Thermistor types: 2252Ω at 25°C, TD Series
• Protected against power supply reversals. • Ranges: 2252Ω = –0°C to +100°C.
TD = –40°C to +150°C.
Environmental • Resolution: 2252Ω = 0.01°C or F.
• Temperature Range: Operating –25°C to +70°C. TD = 0.1°C or F
Storage –25°C to +85°C. • Accuracy: 2252Ω = ±0.1°C.
• Relative Humidity: 0 to 95% Noncondensing. TD = ±0.2°C
• Common mode rejection: 100dB at 50/60Hz.
1100/2100 Voltage Input Modules • Input protection to 30VDC .
• Voltage ranges: ±10mV, ±100mV, ±1V, ±5V, ±10V, ±100VDC. • User selectable °C or °F.
• Resolution: 0.01% of FS (4 digits). • 1 Digital input/ Event counter, 2 Digital outputs.
• Accuracy: ±0.02% of FS max.
• Common mode rejection: 100dB at 50/60Hz.
• Zero drift: ±1 count max (autozero).
• Span tempco: ±50ppm/°C max.
• Input burnout protection to 250VAC .
• Input impedance: ≤ ±1V input = 100MΩ min.
≥ ±5V input = 1MΩ min.
• 1 Digital input/Event counter, 2 Digital outputs.
Specifications Typical at 25°C and nominal power supply unless otherwise noted
Ordering Information
Voltage Input Strain Gage Inputs
Model Description Model Description
SCM9B-1101/2101 ±10mV Input/RS-232C Output SCM9B-1511/2511 ±30mV Bridge Input, 5V Excitation/RS-232C Output
SCM9B-1102/2102 ±10mV Input/RS-485 Output SCM9B-1512/2512 ±30mV Bridge Input, 5V Excitation/RS-485 Output
SCM9B-1111/2111 ±100mV Input/RS-232C Output SCM9B-1521/2521 ±30mV Bridge Input, 10V Excitation/RS-232C Output
SCM9B-1112/2112 ±100mV Input/RS-485 Output SCM9B-1522/2522 ±30mV Bridge Input, 10V Excitation/RS-485 Output
SCM9B-1121/2121 ±1V Input/RS-232C Output SCM9B-1531/2531 ±100mV Bridge Input, 5V Excitation/RS-232C Output
SCM9B-1122/2122 ±1V Input/RS-485 Output SCM9B-1532/2532 ±100mV Bridge Input, 5V Excitation/RS-485 Output
SCM9B-1131/2131 ±5V Input/RS-232C Output SCM9B-1541/2541 ±100mV Bridge Input, 10V Excitation/RS-232C Output
SCM9B-1132/2132 ±5V Input/RS-485 Output SCM9B-1542/2542 ±100mV Bridge Input, 10V Excitation/RS-485 Output
SCM9B-1141/2141 ±10V Input/RS-232C Output SCM9B-1551/2551 1-6V Bridge Input, 8V Excitation/RS-232C Output
SCM9B-1142/2142 ±10V Input/RS-485 Output SCM9B-1552/2552 1-6V Bridge Input, 8V Excitation/RS-485 Output
SCM9B-1151/2151 ±100V Input/RS-232C Output SCM9B-1561/2561 1-6V Bridge Input, 10V Excitation/RS-232C Output
SCM9B-1152/2152 ±100V Input/RS-485 Output SCM9B-1562/2562 1-6V Bridge Input, 10V Excitation/RS-485 Output
SCM9B
Current Inputs Timer/Frequency Inputs
Model Description Model Description
SCM9B-1211/2211 ±10mA Input/RS-232C Output SCM9B-1601/2601 Frequency Input/RS-232C Output
SCM9B-1212/2212 ±10mA Input/RS-485 Output SCM9B-1602/2602 Frequency Input/RS-485 Output
SCM9B-1221/2221 ±1mA Input/RS-232C Output SCM9B-1611/2611 Timer Input/RS-232C Output
SCM9B-1222/2222 ±1mA Input/RS-485 Output SCM9B-1612/2612 Timer Input/RS-485 Output
SCM9B-1231/2231 ±100mA Input/RS-232C Output SCM9B-1621 Event Counter/RS-232C Output
SCM9B-1232/2232 ±100mA Input/RS-485 Output SCM9B-1622 Event Counter/RS-485 Output
SCM9B-1241/2241 ±1A Input/RS-232C Output SCM9B-1631/2631 Accumulator, Frequency Input/RS-232C Output
SCM9B-1242/2242 ±1A Input/RS-485 Output SCM9B-1632/2632 Accumulator, Frequency Input/RS-485 Output
SCM9B-1251/2251 4-20mA Input/RS-232C Output SCM9B-1641/2641 Accumulator, Timer Input/RS-232C Output
SCM9B-1252/2252 4-20mA Input/RS-485 Output SCM9B-1642/2642 Accumulator, Timer Input/RS-485 Output
RTD Inputs
Model Description
SCM9B-1411 .00385 RTD Input/RS-232C Output
SCM9B-1412 .00385 RTD Input/RS-485 Output
SCM9B-1421 .00392 RTD Input/RS-232C Output
SCM9B-1422 .00392 RTD Input/RS-485 Output
SCM9B-1431 .00388 RTD Input/RS-232C Output
SCM9B-1432 .00388 RTD Input/RS-485 Output
SCM9B-1451 2252Ω Thermistor Input/RS-232C Output
SCM9B-1452 2252Ω Thermistor Input/RS-485 Output
SCM9B-1461 TD Thermistor Input/RS-232C Output
SCM9B-1462 TD Thermistor Input/RS-485 Output
SCM9B-5000 Series
4-Channel Sensor-to-Computer Modules
Description
The SCM9B-5000 4-Channel Sensor-to-Computer Modules are a family of
complete solutions designed for data acquisition systems based on personal
Features
computers and other processor-based equipment with standard serial I/O ports. • Four Analog Input Channels
The modules convert four analog input signals to engineering units and transmit • Complete Sensor to RS-485 or RS-232 Interface
in ASCII format to any host with standard RS-485 or RS-232C ports. These
modules can measure temperature, voltage, and current. The modules provide • ASCII Format Command/Response Protocol
direct connection to a wide variety of sensors and perform all signal conditioning, • 500Vrms Analog Input Isolation
scaling, linearization, and conversion to engineering units.
• 15-Bit Measurement Resolution
Each channel of the SCM9B-5000 Series can be independently programmed by • Continuous Self-calibration; No Adjustments of
the user for zero, span, and filter, to scale linear input signals such as millivolts Any Kind
and milliamps to desired engineering units such as pounds or percent of full
scale. • Programmable Digital Filter
• Requires +10V to +30VDC Unregulated Supply
The SCM9B-5000 modules are easy to use. With these modules, anyone
familiar with a personal computer can construct a data acquisition system. This • Transient Suppression on RS-485
modular approach to data acquisition is extremely flexible, easy to use, and Communications Lines
cost effective. Data is acquired on a per channel basis so you only buy as many • Screw Terminal Plug Connectors Supplied
channels as you need. The modules can be mixed and matched to fit the
application. They can be placed remote from the host and from each other. • Mix and Match with Single-Channel Units on
Same Backpanel
The modules contain no pots or switches to be set. Features such as address,
• CE Compliant
data rate, parity, echo, and scaling are selectable using simple commands
over the communications port—without requiring access to the module. The
selections are stored in nonvolatile EEPROM which maintains data even after
power is removed.
Applications
The 5000 series is completely hardware and software-compatible with the 1000,
2000, 3000 and 4000 series and may be mixed in any combination. • Process Monitoring and Control
All modules are supplied with removable screw-terminal connectors and captive • Remote Data Logging to any Host Computer
mounting hardware. The connectors allow system expansion, reconfiguration • Product Testing
or repair without disturbing field wiring.
• Direct Connection to Modems
Although software is not required, utility software (S1000) is available on IBM-
compatible diskette to make the 5000 easier to learn and use.
Specifications Typical at 25°C and nominal power supply unless otherwise noted
SCM9B
• Selectable data rates: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600,
115200bps. 5300 Thermocouple Inputs
• NRZ asynchronous data format; 1 start bit, 7 data bits, 1 parity bit and 1 stop bit. • Thermocouple types: J, K, T, E (factory set).
• Parity: odd, even, none. • Ranges: J = –200°C to +760°C T = –200°C to +400°C
• User selectable channel address. K = –150°C to +1250°C E = –100°C to +1000°C
• ASCII format command/response protocol. • Resolution: ±1°.
• Up to 3721 multidrop modules per host serial port. • Overall Accuracy (error from all sources) from 0 to +40°C
• Communications distance up to 4,000 feet (RS-485). ambient: ±1.0°C.
• Transient suppression on RS-485 communications lines. • Input impedance: 100MΩ min.
• Communications error checking via checksum. • Lead resistance effect: <20µV per 350Ω.
• Scan up to 250 channels per second. • Open thermocouple and overrange indication.
• All communications setups stored in EEPROM. • Input burnout protection to 250VAC.
• User selectable °C or °F.
Power • Automatic cold junction compensation and linearization.
• Requirements: Unregulated +10V to +30VDC, 0.75W max.
5450 Thermistor Inputs
• Protected against power supply reversals.
• Thermistor types: 2252Ω at 25°C.
Environmental • Range: 0°C to +100°C.
• Temperature Range: Operating –25°C to +70°C. • Resolution: 0.01°C or F.
Storage –25°C to +85°C. • Accuracy: ±0.1°C.
• Relative Humidity: 0 to 95% Noncondensing. • Input protection to 30VDC.
• User selectable °C or °F.
Mechanical
• Dimensions: See Dimension drawing.
• Case: ABS with captive mounting hardware.
• Connectors: Screw terminal barrier plug (supplied).
Replace with Phoenix MSTB 1.5/10ST 5.08 or equivalent.
Ordering Information
Voltage Input Thermocouple Inputs
Model Description Model Description
SCM9B-5111 ±100mV Input/RS-232C Output SCM9B-5311 J Thermocouple Input/RS-232C Output
SCM9B-5112 ±100mV Input/RS-485 Output SCM9B-5312 J Thermocouple Input/RS-485 Output
SCM9B-5121 ±1V Input/RS-232C Output SCM9B-5321 K Thermocouple Input/RS-232C Output
SCM9B-5122 ±1V Input/RS-485 Output SCM9B-5322 K Thermocouple Input/RS-485 Output
SCM9B-5131 ±5V Input/RS-232C Output SCM9B-5331 T Thermocouple Input/RS-232C Output
SCM9B-5132 ±5V Input/RS-485 Output SCM9B-5332 T Thermocouple Input/RS-485 Output
SCM9B-5141 ±10V Input/RS-232C Output SCM9B-5341 E Thermocouple Input/RS-232C Output
SCM9B-5142 ±10V Input/RS-485 Output SCM9B-5342 E Thermocouple Input/RS-485 Output
SCM9B-5151 ±100V Input/RS-232C Output
SCM9B-5152 ±100V Input/RS-485 Output Thermistor Inputs
Model Description
Current Inputs
Model Description SCM9B-5451 2252Ω Thermistor Input/RS-232C Output
SCM9B-5452 2252Ω Thermistor Input/RS-485 Output
SCM9B-5251 4-20mA Input/RS-232C Output
SCM9B-5252 4-20mA Input/RS-485 Output
SCM9B-D100 Series
DIN Rail Mount Sensor-to-Computer Modules
Description
The SCM9B-D100 Sensor to Computer Modules are a family of data acquisition
modules that convert analog input signals to digital data and transmit via RS-485 Features
to a controller which may be a computer or other processor-based equipment. • Complete Sensor to RS-485 Interface
The modules can measure temperature, pressure, voltage, current, digital input
• 500Vrms Analog Input Isolation
or digital output signals. The modules provide direct connection to a wide variety
of sensors and perform all signal conditioning, scaling, linearization and • 15 Bit Measurement Resolution
conversion to either linearized ASCII data values or Modbus RTU data values. • Continuous Self-Calibration; No Adjustments
Features such as address, data rate, parity, echo, etc., are selectable using of Any Kind
simple commands over the RS-485 port. The selections are stored in nonvolatile • Programmable Digital Filter
EEPROM which maintains data even after power is removed. • Requires +5VDC Supply
Data is acquired on a per channel basis so you only buy as many channels as • Transient Suppression on RS-485
you need. The modules can be mixed and matched to fit your application. They Communications Lines
can be placed remote from the host and from each other. You can string up to
247 modules on a twisted pair of wires by using RS-485 with repeaters. • Screw Terminal Plug Connectors Supplied
• CE Compliant
All modules are supplied with screw terminal plug connectors. The connectors
allow system expansion, reconfiguration or repair without disturbing field wiring.
Utility software is available from Dataforth to make the D100 easier to learn and Command Set
use. The software is provided at no charge on request with a purchase order and
The D100 series uses the Modbus RTU or the Dataforth ASCII protocol for
is not copy protected.
communication.
Theory Of Operation
The Modbus RTU binary protocol uses a master-slave technique, in which only
Each Dataforth module is a complete single-channel data acquisition system. the master device can initiate transactions. The slave devices respond by
Each unit contains analog signal conditioning circuits optimized for a specific supplying the requested data to the master or by taking the action requested in
input type. Sensor signals are converted to digital data with a micro the query. The master can address any slave device. The returned messages
processor-controlled integrating A/D converter. Offset and gain errors in the are considered response messages. The supported master codes are:
analog circuitry are continuously monitored and corrected using microprocessor
Modbus RTU Functions and Descriptions
techniques. The D100 converts the digital signal data and stores the resultant
data in a memory buffer. The modules continuously convert data at the rate of 01 Read Coil Status (Digital Inputs)
8 conversions per second and store the latest result in the buffer. 04 Read Input Register (Analog Inputs)
05 Force Single Coil (One Digital Input)
Host processors may request data by sending a query to the module. The D100
06 Preset Single Register (Dataforth/RTU Protocol)
will instantly respond by communicating the memory buffer data back to the host
15 Force Multiple Coils (Multiple Digital Output)
processor. Up to 247 modules may be linked to a single RS-485 port. Each
module on a serial line is identified by a unique user-programmable address.
The Dataforth ASCII protocol is a command and response protocol using ASCII
This addressing technique allows modules to be interrogated in any order.
characters for easy troubleshooting and interpretation of data values.
Digital Inputs/Outputs
D170 digital input/output modules contain open-collector transistor switches
that may be controlled by the host processors. These switches may be used to
control solid-state relays which in turn may control heaters, pumps and other
power equipment. The digital inputs may be read by the host processor and used
to sense the state of remote digital signals. They are ideal for sensing the state
of limit or safety switches.
Digital Filter
The D100 analog input modules include two unique programmable single pole
digital filters. The filter is used to smooth analog data in noisy environments.
Separate time constants may be specified for small and large signal changes.
Typically a large time constant is specified for small signal changes to filter out
noise and provide stable output readings. A smaller time constant may be
chosen for large signal changes to provide fast response to such changes. Figure 1: SCM9B-D100 Block Diagram
Command and Definition Typical Typical The D100 series are initiated at the factory using the Dataforth ASCII protocol.
Command Response This allows setup and configuration, including the Modbus device address, to
Message Message be easily performed using the Dataforth setup software or a dumb terminal. Each
($ prompt) D100 module must be properly configured before installation into a Modbus
system.
DI Digital Input $1DI *0003
DO Digital Output $1DOFF * Utility Software
RD Read Data $1RD *+00072.00
Complimentary Utility Software is included with each purchase order. The
RS Read Setup $1RS *31070142
software is compatible with Windows 95, 98, NT 4.0+, 2000, XP operating
RSU Read Setup $1RSU *31070142
systems and distributed on CD-ROM. The Utility Software simplifies
RZ Read Zero $1RZ *+00000.00
configuration of all user-selectable options such as device address, data rate and
WE Write Enable $1WE *
filtering constants.
Write Protected Commands
Process Control Software
SCM9B
CZ Clear Zero $1CZ *
Modbus RTU protocol is supported by virtually all commercial process control
RR Remote Reset $1RR *
software programs available today. These programs operate on IBM and
SU Setup Module $1SU31070142 *
compatible personal computers in the Windows 95, 98, NT and IBM OS/2
TS Trim Span $1TS+00600.00 *
environments.
TZ Trim Zero $1TZ+00000.00 *
Specifications Typical at TA=+25°C and nominal power supply unless otherwise noted
SCM9B-3000/4000 Series
Computer-to-Analog Output Modules
Description
The SCM9B-3000/4000 series are complete computer-to-analog output
interfaces. They are designed to be mounted remotely from a host computer and Features
communicate, in ASCII, with standard RS-232 and RS-485 serial ports. Simple • Analog Output Ranges: 0-1V, ±1V, 0-5V, ±5V, 0-10V,
ASCII commands are used to control a 12-bit DAC (Digital-to-Analog ±10V, 0-20mA, 4-20mA
Converter) which is scaled to provide commonly used current and voltage • Communicates in ASCII with RS-232 or RS-485 Serial Ports
ranges. An 8-bit CMOS microprocessor provides an intelligent interface be-
tween the host and the DAC. The 3000/4000 are compatible with the 1000/2000 • Programmable High/Low Output Limits
input modules and may be mixed in any order. • 500Vrms Output Isolation
The modules are easy to use. You do not need engineering experience in • 12-bit Output Resolution
complicated data acquisition hardware. This modular approach to data • Scaling in Engineering Units
SCM9B
acquisition is extremely flexible, easy to use and cost effective. The modules can • Data Rates: 300 to 38,400bps
be mixed and matched to fit the application. They can be placed remote from the
host and from each other. You can string up to 124 modules on one set of wires. • Nonvolatile Digital Calibration
• Output Protection: 240VAC (Current Output)
Although software is not required, utility software (SCM9B-S1000) is available ±30V (Voltage Outputs)
on IBM-compatible diskette to make the 3000/4000 easier to learn and use.
S1000 software is provided at no charge on request with a purchase order and • Direct Connection to ‘Dumb’ Terminals or Modems
is not copy protected. • Requires +10 to +30VDC Unregulated Supply
• May be Located up to 10,000 Feet from Host (RS-485)
• Addressable: up to 124 Units per Serial Port
• ‘Bumpless’ Manual Control Inputs
• CE Compliant
Programmable Features (4000 Series)
(Provides intelligent features not found in the 3000 Series)
• Fully Programmable Output Slopes: 0.01V/s (mA/s) to
10,000V/s (mA/s)
• Programmable Data Scaling to any Desired Units
• True Analog Readback of Output Signal
• Programmable Starting Value
• Programmable Watchdog Timer Provides Orderly
Shutdown in the Event of Host Failure
Specifications Typical at 25°C and nominal power supply unless otherwise noted
Digital Inputs
• Three digital inputs per module.
• Voltage levels: ±30V without damage.
• Switching levels: High, 3.5V min., Low, 1.0V max.
• Internal pull up resistors for direct switch input.
Ordering Information
Voltage Output
Model Description
SCM9B-3121/4121 ±1V Output/RS-232C Input
SCM9B-3122/4122 ±1V Output/RS-485 Input
SCM9B-3131/4131 ±5V Output/RS-232C Input
SCM9B-3132/4132 ±5V Output/RS-485 Input
SCM9B-3141/4141 ±10V Output/RS-232C Input
SCM9B-3142/4142 ±10V Output/RS-485 Input
SCM9B-3161/4161 0 to 1V Output/RS-232C Input
SCM9B-3162/4162 0 to 1V Output/RS-485 Input
SCM9B-3171/4171 0 to 5V Output/RS-232C Input
SCM9B-3172/4172 0 to 5V Output/RS-485 Input
SCM9B-3181/4181 0 to 10V Output/RS-232C Input
SCM9B-3182/4182 0 to 10V Output/RS-485 Input
Current Output
Model Description
SCM9B-3251/4251 0 to 20mA Output/RS-232C Input
SCM9B-3252/4252 0 to 20mA Output/RS-485 Input
SCM9B-3261/4261 4 to 20mA Output/RS-232C Input
SCM9B-3262/4262 4 to 20mA Output/RS-485 Input
SCM9B-A1000/A2000
RS-232C/RS-485 Converters, RS-485 Repeaters
Description
The A1000 and A2000 series converter boxes convert RS-232 communication
signal levels to the correct electrical signals required by RS-485. The
Features
RS-485 communications standard is recommended when many SCM9B modules, • Completely Transparent to Host Software
or other addressable devices, must be connected to a host computer over long • No External Flow Control Signals Required
distances. The A1000 and A2000 converters allow communications bus lengths up
to 4,000 feet and data rates up to 115kbps using one twisted pair of wires. • Optically-Isolated Bidirectional Data Flow
The RS-485 standard allows for bidirectional data on the same pair of wires. • Standard Data Rates: 300 to 115kbps
Therefore, some means of arbitrating the data direction is required. The A1000 • Automatic Internal RS-485 Bus Supervision
and A2000 automatically control the bus direction without external handshaking • Networking up to 4,000 Feet
signals from the host. Host software written for half-duplex RS-232 may be used
SCM9B
without modification, RS-485 bus control is completely transparent to the user. • CE Compliant
The A1000 and A2000 can also operate as repeaters for RS-485. Repeaters are Ordering Information
required to extend communications bus lengths or to allow more than 32 RS-485
devices to be connected to a communications bus. A repeater simply reamplifies, Model Description
or boosts, existing RS-485 signals transmitted over long distances. SCM9B-A1000-115 RS-232C/RS-485 Converter/Repeater, 115VAC
SCM9B-A1000-230 RS-232C/RS-485 Converter/Repeater, 230VAC
SCM9B-A2000 RS-232C/RS-485 Converter/Repeater, +10 to +30VDC
Specifications
Communications A2000 Power Specifications
• Max common mode voltage: 1500Vrms, 1 minute duration. • Power requirements: +10 to +30VDC unregulated.
• Data rates: 300, 600, 1200, 2400, 4800, 9600, 19200, • Power consumption (at +15VDC): Max. current w/RS-485 output
38400, 57600, 115200bps. short, 100mA.
• Idle current w/LEDs off, less than 10mA.
Environmental
Mechanical and Dimensions
• Temperature range (operating & storage): –25°C to +70°C.
• Relative humidity: 0 to 95% Noncondensing. • Case: Impact resistant ABS.
• Weight: 2.8lbs. (A1000), 1.0lb. (A2000).
A1000 Power Specifications • Dimensions: 8.08"W X 2.50"H X 6.25"D (A1000).
• Power requirements: 115VAC (order SCM9B-A1000-115) or 7.06"W X 1.53"H X 5.30"D (A2000).
230VAC (order SCM9B-A1000-230) ±10%, 50-60Hz.
• Power consumption: 30W full load.
• Power supply output: +24VDC at 1A.
SCM9B-D192
DIN Rail Mount RS-485 Repeater
Features
Description • Completely Transparent to Host Software
The SCM9B-D192 RS-485 repeater reamplifies, or boosts, existing RS-485 • No External Flow Control Signals Required
signals transmitted over long distances. Repeaters are required to extend
• Optically-Isolated Bidirectional Data Flow
communications bus lengths or to allow more than 32 RS-485 devices to be
connected to a communications bus. • Standard Data Rates: 300 to 115kbps
The SCM9B-D192 operates on +5VDC power supply input voltage. • Automatic Internal RS-485 Bus Supervision
• Networking up to 4,000 Feet
Automatic RS-485 Bus Supervision
• Transient Suppression on RS-485 Data Lines
The SCM9B-D192 automatically controls bus direction in hardware without the
need of handshaking signals from the host computer. As shown in figure 1, the • Internal Jumper Selectable Termination Resistors
I/O control circuitry monitors both RS-485 drivers. The RS-485 drivers in the • CE Compliant
converter are always in the receive mode until either RS-485 driver receives the
start of a character to be retransmitted. When the start of a character is detected, Specifications Typical at 25°C and nominal power supply unless otherwise noted
the I/O circuitry enables the proper RS-485 driver for one character time at the
selected data rate. When the character time expires the drivers return to receive • Max common mode voltage: 500Vrms, 60s duration.
mode. Since the converters are bidirectional it does not matter which driver • Data rates: 300,600,1200,2400, 4800, 9600, 19200,
receives the character. 38400, 57600, 115200bps (dip-switch selectable).
• Temperature range (operating & storage): –25°C to +70°C.
Isolation • Relative humidity: 0 to 95% Noncondensing.
• Warranty: 12 months on workmanship and materials.
The SCM9B-D192 is designed to protect host computers from destructive fault
conditions that may occur on the RS-485 data lines. The host input connections Power Specifications
on each converter are optically-isolated to 500VAC from the RS-485 connec- • Requirements: +5VDC regulated.
• Power consumption: 1.0W Max (RS-485 driver on).
tions. The optical-isolation will prevent short circuits to hazardous AC voltages
on the RS-485 data lines, or static discharges, from reaching a host computer. Mechanical
The RS-485 output is connected to earth ground to provide a safe path for static • Case: ABS case with screw terminal barrier plug (supplied).
discharge. The power supply ground should reference earth ground to provide
a safe path for static discharge. Ordering Information
Surge Protection Model Description
The SCM9B-D192 RS-485 drivers contain internal surge-protection on the data SCM9B-D192 RS-485 Repeater
lines. Internal high speed transient suppressors on each RS-485 data line
protect the driver from dangerous voltage levels, or spikes, that can occur on the RS-485 Termination
data lines. Thermistors are installed in series with each RS-485 data line to
protect the drivers against overcurrent and excessive voltage conditions. In a The RS-485 standard is highly immune to noise when each data line is properly
fault condition the normally low impedence thermistor reacts by rapidly increas- biased and terminated. Each RS-485 driver is connected to pull-up and pull-
ing its impedance thus limiting excessive current flow. Once the fault condition down biasing resistors and termination resistors to insure the proper termination
is corrected the thermistor will return to its normally low impedance. technique for any RS-485 system.
SCM9B Series
Mechanical Dimensions
Mechanicals and Dimensions-SCM9B-1000/2000/3000/4000/5000
Case: ABS with captive mounting hardware.
Connectors: Screw terminal barrier plug (supplied).
Replace with Phoenix MSTB 1.5/10 ST 5.08 or equivalent.
SCM9B
D100 Series
SCM9B-H1750/H1770
24- and 64-Channel Digital I/O Boards
Features
• Computer Monitoring and Control of Standard Digital
I/O Modules via RS-232 or RS-485
• Digital Inputs and Outputs Interface with Solid State Relays
to Sense AC and DC Voltages
• Controls Digital Inputs and Outputs Individually
• User Can Define Any Bit as Input or Output
• 24- and 64-Channel Versions
• Expands up to 7936 Digital I/O Channels
(124 Multidropped 64-Channel Boards)
• Read or Set 7936 Inputs or Outputs in Less Than 1s
• Mounts in 19" Racks
• Compatible with All SCM9B Products
Description • Same Command Set as 1700 Series Modules
Mechanical
H1750: 4.00" x 4.60"
H1770: 5.00" x 10.00"
Ordering Information
Model Description
SCM9B-H1750 24 Digital Inputs/Outputs
SCM9B-H1770 64 Digital Inputs/Outputs
SCM9B-HCA1 4 Ribbon Connector Assembly
SCM9B Accessories
SCM9B-PB08/PB14
8- and 14-Channel Mounting Backplanes
Description
The SCM9B-PB08 and PB14 are 8- and 14-channel mounting backplanes The backplanes reduce wiring costs by providing all common connections on
(Figure 1). The backplanes accept any RS-485 analog input or analog output the backplane. Each backplane includes screw terminals for all inputs, outputs,
modules and are designed to be mounted in standard 19 inch racks. RS-485 power connections and communications signals. The backplanes also include
modules are used because RS-485 is the preferred communications standard swaged thru-hole standoffs for mounting, a hold-down bar, and holes for an
for high channel count applications. Although analog modules are used it must RS-485 termination resistor.
be noted that every module has some digital I/O capability. Therefore the
combination of modules with the backplanes make a cost effective, high density
remote analog and digital data acquisition system.
SCM9B
SCM9B-S1200
Scansoft Data Logging Software
Features
• Menu-Driven Utility Software
• Scan and Display up to 64 1000/2000 Modules
• Scan and Display up to 24 Digital Inputs
• Real Time Display of Acquired Data
• Bargraph, Trend and Text Displays
• Label Channels — Boiler Room, Furnace, etc.
• Save & Recall System & Module Setups
• Selectable Module Scan Rate
• Selectable Log to Printer Rate
SCM9B-S1200 Scansoft Data Logging Software is a menu-driven • Selectable Log Data to Disk Rate
program that acquires data from 1000 and 2000 series modules. The program • Selectable Alarm Notification to Printer
uses menus to configure up to 64 analog inputs and 24 digital inputs. The
acquired data is displayed as text or graphically using bar or trend graphs. The
software is provided at no charge on request with a purchase order and is not Ordering Information
copy protected.
Model Description
Menus are used to set up the modules for a data acquisition run allowing SCM9B-S300 Series S1000/2000/3000/4000 Utility Software and
configuration of start-up, data rates, display, and data logging. Each channel S1200 Data Logging Software
has a set up screen status that allows you to specify your data acquisition
hardware, and software options.
SCM5B ®
Features
• Modbus RTU Support on RS-232 and RS-485
• Modbus TCP Support (optional)
• 1500Vrms Input-to-Output &
Channel-to-Channel Isolation
• 240Vrms Field-side Protection
• 16-Bit A/D, D/A
• Up to 6-Pole Analog Input Filtering
• ±0.012% Base System Accuracy, No Modules
• ±0.005% Base System Linearity, No Modules
• ±0.03% Module Accuracy
• ±0.005% Module Linearity
• Best I/O Selection: 250+ Different I/O Modules
Description • –40°C to +85°C Operating Temperature
isoLynx
Faulty thousand-dollar data acquisition systems can shut down billion-dollar • Supported by ReDAQ® Freedom Software
operations. The SCM5B isoLynx® SLX200 is a fast, intelligent, fully isolated • All Analog I/O Modules Certified to CSA C/US,
data acquisition system providing superior reliability, accuracy, and isolation
for a wide range of rugged industrial applications. It offers maximum flexibility CE, and ATEX Requirements
of analog and digital I/O selection at competitive prices for a broad range of • SLX200 & SLX101 CE Compliant
factory automation, process control, test and measurement, machine control,
• SLX200 CSA C/US Certified
and data acquisition applications. The isoLynx® SLX200 implements the
(Class I, Division 2, Groups A, B, C, D)
industry standard Modbus RTU and TCP protocols, thereby enabling communica-
tion with a wide variety of existing third-party software drivers and HMI/SCADA • Free Configuration Software
packages. It is fully certified by Modbus-IDA and compatible with OPC. • Manufactured per RoHS Directive 2002/95/EC
All I/O Channel-to-Channel Isolated
The flexible, modular design combines a 6- or 12-channel I/O Controller base
system and optional 8- or 16-channel expansion backplanes, which can be
either panel or DIN rail mounted (see Figure 1). The operation and storage temperature range for the SCM5B isoLynx®
One I/O Controller module can operate up to 60 channels of differential analog SLX200 is –40°C to +85°C; the relative humidity is 0 to 95% non-condensing.
I/O and 128 channels of digital I/O, using Dataforth’s SCM5B analog and Power requirement is +5VDC, 2.5W base system with no modules installed.
SCMD digital modules. The Controller contains a powerful high-speed The SLX200 and SLX101 are CE Compliant. SLX200 is CSA C/US Certified
microcontroller, A/D and D/A subsystem, communication interface, data for Class I, Division 2 Hazardous Locations.
storage memory, and status LEDs. The A/D system is built around a 16-bit, Flexible Communications and Configuration
successive approximation converter and can convert a maximum 60-channel The SCM5B isoLynx® SLX200 communicates on RS-232/RS-485 serial links
configuration in 17msec. The D/A converter is also a 16-bit device and can up to 115.2kbps or 10Mb/s Ethernet. Up to 32 systems can be multidropped on
write a maximum 60-channel configuration in 33msec. the RS-485 serial link and up to 4 sockets are supported on Ethernet. Optional
Industry’s Widest I/O Selection Ethernet communication boards are available; these can be factory installed
By selecting from over 250 standard and custom single-channel SCM5B or field upgradeable.
analog I/O modules, the isoLynx® SLX200 can interface to a broad spectrum The communication protocol is Modbus RTU for RS-232/RS-485 or Modbus
of analog signals, including millivolt, volt, milliamp, amp, linearized and TCP for Ethernet. Modbus is an open, industry-standard protocol that defines
non-linearized thermocouple, RTD, potentiometer, slidewire, strain gage, AC- how devices on a network or bus communicate with each other. Full certifica-
to-True RMS output, frequency, 2-wire transmitter, and transducers requiring tion of the SCM5B isoLynx® SLX200 by Modbus-IDA ensures the device can
DC excitation. Analog output modules are available which provide a wide be integrated onto existing Modbus networks, and most common Modbus
selection of current or voltage output ranges. Industry standard miniature function codes are supported. The system is also OPC compatible.
digital I/O modules are used for digital AC/DC input and output requirements. As device configuration is performed using standard Modbus function codes,
Users can mix and match most I/O module types on a per-channel basis, thus any third-party software application that supports the Modbus RTU and/or
reducing wasted I/O channels and saving costs. Modbus TCP protocol can be used to configure the device. Configuration
Interface to digital signals is provided by the dedicated SLX101 digital I/O parameters are stored in non-volatile memory, so configuration only has to
backpanel. This intelligent backpanel is designed to interface to the SLX200 happen once. Free configuration software is provided to ensure configuration
but can also be used stand-alone for digital I/O only systems. is easy and intuitive (see Figure 2 and Figure 3).
Figure 2: Configuration Utility - Communications Setup Figure 3: Configuration Utility - Analog Channel Setup
Specifications
5B isoLynx® SLX200 Analog I/O Base Unit 5B isoLynx® SLX101 Digital I/O Backpanel
General System General System
Protocol Modbus RTU or TCP, OPC Server Compatible Protocol Modbus RTU or TCP, OPC Server Compatible
I/O Capability One 6-ch or 12-ch backpanel minimum. Expandable to through SLX200. Proprietary as stand-alone.
60-ch Analog I/O, 128-ch Digital I/O. I/O Capability One 16-ch backpanel minimum. Expandable to
Software Tools Free Configuration Utility, Win32 DLL, LabVIEW VI library 128-ch Digital I/O.
Digital System Digital System
Microcontroller High Performance RISC Microcontroller High Performance RISC
Status LEDs +5V, System Status, TD/RD (Serial), LNK/ACK (Ethernet) Status LEDs +5V, System Status, Channel State
Failsafe Features Watchdog Timer & Brownout Detection - Reset to user Failsafe Features Watchdog Timer & Brownout Detection - Reset to
defined configuration user defined configuration
Communication Interface Communication Interface
Serial I/O Separate RJ-45 modular phone jacks for RS-232 and RS-485 Serial I/O Two RJ-45 modular phone jacks for daisy-chain
115.2kbps max connection
Port for SLX101 Digital RJ-45 modular phone jack, 2-wire RS-485 115.2kbps max
I/O Panel RS-485 2W 4000 feet max distance, 32 max multidrops, non-isolated
RS-485 2-wire or 4-wire, 4000 feet max distance, 32 max
multidrops, non-isolated Digital I/O
To isolate, extend, or convert RS-232 or RS-485, use Channels Mix and match I/O types on a per channel basis
Dataforth LDM and DCP Data Communication products Field Connector High density screw clamp, 14 AWG max, 0.5N-M torque
Ethernet RJ-45 modular phone jack, 10Base-T Isolation 1000 Vrms ch-to-ch or ch-to-internal bus
Default IP Address 192.168.0.215, Keep-alive timeout 7200s Throughput 8ms for 16 ch (~2000 ch/sec) at 115.2kbps Modbus RTU
isoLynx
27ms for 128 ch (~4740 ch/sec) at 115.2kbps Modbus
Analog I/O RTU
Channels Mix and match I/O types on a per channel basis(1)
Maximum 60-ch differential I/O of SCM5B modules Power Supply Requirements +5VDC ±5% at 40mA, no modules installed
Input modules must have system output of ±5V or Dimensions (l)(w)(h) 10.0" x 3.47" x 1.95" (254.0mm x 88.1mm x 49.5mm)
0 to +5V (±10V or 0 to +10V cannot be used)
Calibration NIST traceable test and calibration sheets ship with modules Mounting Options Panel Mount or DIN Rail Mount
System Accuracy Analog Input ±0.024%(2), Analog Output ±0.006%(2) Environmental
Field Connector High density screw clamp, 14 AWG max, 0.5N-M torque Operating Temp. Range –40°C to +85°C
System Connector 26-pin, male header connector Storage Temp. Range –40°C to +85°C
Ground Network Jumpers Factory Default R1 100Ω; J1-J4: J1, J2, and J4 installed; Relative Humidity 0 to 95% Noncondensing
J3 not installed. See Hardware User Manual for Emissions EN61000-6-4 ISM, Group 1
recommended grounding practices. Radiated, Conducted Class A
A/D Converter 16-bit, ±10V input, 14-bit min accuracy Immunity EN61000-6-2 ISM, Group 1
Resolution vs. input range: 16-bit at ±10V, RF Performance A ±0.5% Span Error
15-bit at ±5V, 14-bit at 0 to +5V ESD,EFT Performance B
D/A Converter 16-bit, ±10V output
Isolation 1500 Vrms ch-to-ch or ch-to-internal bus Certifications
Input Protection 240VAC continuous, ESD CE Compliant
Throughput, Analog Input 8ms for 16 ch (~2000 ch/sec) at 115.2kbps Modbus RTU CSA, FM Not covered under the SLX200 certifications.
17ms for 60 ch (~3600 ch/sec) at 115.2kbps Modbus RTU Must qualify separately based on source of I/O modules.
Throughput, Analog Output 13ms for 16 ch (~1230 ch/sec) at 115.2kbps Modbus RTU
33ms for 60 ch (~1850 ch/sec) at 115.2kbps Modbus RTU
Expansion Panels SCMPB02 (16-ch, can use up to 3),
SCMPB06 (8-ch, can use up to 6)
Power Supply Requirements
SLX200-1xx +5VDC ±5% at 500mA, no modules installed
SLX200-2xx +5VDC ±5% at 700mA, no modules installed
SLX200-3xx +5VDC ±5% at 900mA, no modules installed
Dimensions (l)(w)(h)
SLX200-xx, 12-ch 17.4" x 3.47" x 3.30" (442.0mm x 88.1mm x 83.8mm)
SLX200-xxAx, 6-ch 11.8" x 3.47" x 3.30" (300.7mm x 88.1mm x 83.8mm)
Mounting Options Panel Mount or DIN Rail Mount
Environmental
Operating Temp. Range –40°C to +85°C (–40°C to +70°C for SLX200-2xx,-3xx)
Storage Temp. Range –40°C to +85°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
Certifications
(1) Modules with system output of ±10V or 0-10V cannot be used in the SLX200 systems. This
CE Compliant includes SCM5Bxx-xxD, SCM5B392-13, -14, SCM5B42-02, and SCM5B48-01.
CSA, FM Class I, Division 2, Groups A, B, C, D Hazardous Locations (2) 10V span for analog input, 20V span for analog output. Does not include SCM5B module
Modbus IDA Conformance Tested accuracy.
Ordering Information
Model Description
(1)
SLX200-10 12-Ch, RS-232/485, Panel Mount
SLX200-20(1) 12-Ch, Ethernet, Panel Mount
SLX200-30(1) 12-Ch, Dual-Ethernet, Panel Mount
SLX200-11(1) 12-Ch, RS-232/485, No CJC(2), Panel Mount
SLX200-21(1) 12-Ch, Ethernet, No CJC(2), Panel Mount
SLX200-31(1) 12-Ch, Dual-Ethernet, No CJC(2), Panel Mount
SLX200-10D(1) 12-Ch, RS-232/485, DIN Rail Mount
SLX200-20D(1) 12-Ch, Ethernet, DIN Rail Mount
SLX200-30D(1) 12-Ch, Dual-Ethernet, DIN Rail Mount
SLX200-11D(1) 12-Ch, RS-232/485, No CJC(2), DIN Rail Mount
SLX200-21D(1) 12-Ch, Ethernet, No CJC(2), DIN Rail Mount
SLX200-31D(1) 12-Ch, Dual-Ethernet, No CJC(6), DIN Rail Mount
( For 6-Ch. Base Unit, See Note(1))
SLX101 Backpanel Digital: 16-Ch
SLX101-D Backpanel Digital: 16-Ch, DIN Rail Mount
SLX141-01,-02,-07 Ethernet and Serial Cable Options
SLX141-X01,-X02,-X07 Ethernet Crossover Cable Options
SLX142,143 RJ45 to DB9 Adapters
SLX144 RJ45 RS-485 Multidrop Adapter
SLX145 Fuse 4A, package of 5
SLX270 Software Tools and User Manuals on CD-Rom
SLX280 Software and Hardware User Manuals, Print Version
SCMPB02 Backpanel Analog: 16-Ch
SCMPB02-1 Backpanel Analog: 16-Ch, No CJC(2)
SCMPB02-2 Backpanel Analog: 16-Ch, DIN Rail Mount
SCMPB02-3 Backpanel Analog: 16 Ch, No CJC(2), DIN Rail Mount
SCMPB06 Backpanel Analog: 8-Ch
SCMPB06-1 Backpanel Analog: 8-Ch, No CJC(2)
SCMPB06-2 Backpanel Analog: 8-Ch, DIN Rail Mount
SCMPB06-3 Backpanel Analog: 8-Ch, No CJC(2), DIN Rail Mount
SCMXRK-002 Accessory: 19-Inch Rack Analog Backpanels
(3)
SCM5B30/31 Analog Voltage Input Modules
SCM5B32(3) Analog Current Input Modules
SCM5B33(3) Isolated True RMS Input Modules
SCM5B34(3) Linearized 2- or 3-Wire RTD Input Modules
SCM5B35(3) Linearized 4-Wire RTD Input Modules
SCM5B36(3) Potentiometer Input Modules
SCM5B37(3) Thermocouple Input Modules
SCM5B38(3) Strain Gage Input Modules
SCM5B39 Current Output Modules
SCM5B392(3) Matched-Pair Servo/Motor Controller Modules
SCM5B40/41(3) Analog Voltage Input Modules, Wide Bandwidth
SCM5B42(3) 2-Wire Transmitter Interface Modules
SCM5B43(3) General Purpose Input Modules, with DC Exc.
SCM5B45(3) Frequency Input Modules
SCM5B47(3) Linearized Thermocouple Input Modules
SCM5B49 Voltage Output Modules
SCMD-MIAC5x Miniature Digital AC Input Modules
SCMD-MIDC5x Miniature Digital DC Input Modules
SCMD-MOAC5x Miniature Digital AC Output Modules
SCMD-MODC5x Miniature Digital DC Output Modules
SCMD-MORx5 Miniature Relay Output Modules
SCMXCA004-xx System interface cable for both analog backpanels
SCMXPRT-001 Power supply, 1A, 5VDC, 120VAC U.S.
SCMXPRE-001 Power supply, 1A, 5VDC, 220VAC European
SCMXPRT-003 Power supply, 3A, 5VDC, 120VAC U.S.
SCMXPRE-003 Power supply, 3A, 5VDC, 220VAC European
NOTES:
(1) SLX200 suffix changes to -xxA or -xxAD for 6-ch base unit.
(2) Cold Junction Compensation. Required for SCM5B37 and SCM5B47.
(3) Modules with system output of ±10V or 0-10V cannot be used in the SLX200 systems. This includes SCM5Bxx-xxD, SCM5B392-13, -14, SCM5B42-02, and SCM5B48-01.
isoLynx
isoLynx
8B ®
Features
• Modbus RTU and TCP Support
• 1500Vrms Input-to-Output &
Channel-to-Channel Isolation
• 240Vrms Field-side Protection
• Wide I/O Selection:
Analog - 15 Families, 70 Models
Digital - 5 Families, 14 Models
• Mix and Match Analog & Digital I/O
• Advanced Features Including Alarms,
Counters, Timers, PWMs, and More
• –40°C to +85°C Operating Temperature
• CE Compliant
• UL/CUL Listing and ATEX Compliance Pending
• Manufactured per RoHS Directive 2002/95/EC
Description
Dataforth’s newest data acquisition system builds on the proven reliability and solid-state relay modules provide AC/DC input and output monitoring and
outstanding performance of the SCM5B isoLynx® SLX200 DAQ system and control. Both analog and digital output channels can be configured as alarm
miniature-sized SensorLex® 8B isolated signal conditioning modules to outputs. The ability to mix and match module types on a per-channel basis
provide a compact, low cost solution for wide ranging, rugged industrial ensures maximum system flexibility. Operation and storage temperature for
applications. Like the SLX200, the SLX300 ensures superior reliability, the isoLynx® SLX300, as well as for all analog and digital I/O modules used in
accuracy, and isolation. Through the use of pluggable modules, the SLX300 the most extreme environments, is –40ºC to +85ºC; the relative humidity range
offers maximum flexibility of analog and digital channel configuration for is 0 to 95% noncondensing. The SLX300 system is CE Compliant and
factory automation, process control, test and measurement, machine control, designed for operation in Class I, Division 2 Hazardous Locations.
and data acquisition applications. The isoLynx® SLX300 uses industry standard
Modbus RTU and TCP protocols, thus enabling communication with a wide Powerful Functionality
range of existing third-party software tools and HMI/SCADA packages. The SLX300 has many features and special purpose functions specifically for
Fast I/O Channel-to-Channel Isolated data acquisition and control. Current sampled data from analog input channels
is stored to a 192k sample buffer. Data is available as minimum, maximum, and
Using Dataforth’s SensorLex® 8B analog modules and SCMD digital modules, average readings with selectable averaging weight. A burst mode of operation
the flexible, modular SLX300 design can be configured with up to twelve allows up to 100kS/s sampling rate on analog input channels and also provides
channels of isolated analog input, four channels of isolated analog output, and a waveform generator function using the analog output channels. Continuous
eight channels of isolated digital I/O. The isolation rating is 1500Vrms from scan mode scans up to 16 input channels, and burst sampling mode can be set
input to output and from channel to channel. The system can be powered by up with a 48 entry scan list to specify scan sequence, scan rate, and scan count.
+5VDC or a wide range 7 to 34VDC using the 8BPWR-2 module, and it can In addition to performing standard digital I/O, the eight digital I/O channels can
be either panel or DIN rail mounted. Multiple powerful, high-speed be configured to perform seven different special functions: pulse/frequency
microcontrollers and high performance data converters at the heart of the counter, pulse/frequency counter with de-bounce, waveform measurement,
system enable simultaneous analog and digital I/O at sustained rates of up to time between events, frequency generator, pulse width modulation (PWM)
3.0kS/s. In addition, a burst mode of operation is provided for analog input that generator, and one-shot generator. The SLX300 also allows four alarm states
allows sampling up to 100kS/s on analog input channels. – high, high-high, low, and low-low – to be set on the analog input and digital
I/O special function channels with alarm output mapped to a user selectable
Industry’s Widest I/O Selection analog or digital output channel.
The isoLynx® SLX300 can be configured for any application by selecting from Configurable analog and digital default output values ensure output signals are
over 70 analog I/O modules and 14 digital I/O modules. These module set to safe values upon system startup or when unexpected power outages or
selections enable monitoring of common industrial signals including millivolt, brownouts occur. System status and mode LEDs constantly display commu-
volt, milliamp, amp, linearized and non-linearized thermocouple, 3- and 4-wire nication activity, mode of operation, and alarm status.
RTD, potentiometer, slidewire, strain gage, AC-to-True RMS output, fre-
quency, 2-wire transmitter, and DC LVDT. Analog output modules provide
isolated high-level voltage and current options. Industry standard digital I/O
isoLynx
Figure 1: Configuration Tool - System Setup
Ordering Information
Model Description Model Description
SLX300-10 12-Ch AI, 4-Ch AO, 8-Ch DIO, RS-232, Panel Mount 8B39-01, -03 Current Output Modules, 100Hz BW
SLX300-20 12-Ch AI, 4-Ch AO, 8-Ch DIO, RS-485, Panel Mount 8B40-04, -05, -06 milliVolt Input Modules, 1kHz BW
SLX300-30 12-Ch AI, 4-Ch AO, 8-Ch DIO, USB (VCP), Panel Mount 8B41-04, -05, -06, -08, -10, -13 Voltage Input Modules, 1kHz BW
SLX300-40 12-Ch AI, 4-Ch AO, 8-Ch DIO, Ethernet, Panel Mount 8B42-01, -02 2-Wire Transmitter Input Modules, 100Hz BW
SLX300-10D 12-Ch AI, 4-Ch AO, 8-Ch DIO, RS-232, DIN Rail Mount 8B43-11 through -20 DC LVDT Input Modules, 1kHz BW
SLX300-20D 12-Ch AI, 4-Ch AO, 8-Ch DIO, RS-485, DIN Rail Mount 8B45-01 through -08 Frequency Input Modules
SLX300-30D 12-Ch AI, 4-Ch AO, 8-Ch DIO, USB (VCP), DIN Rail Mount 8B47J-xx, K-xx, T-xx Thermocouple Input Modules, Linearized, 3Hz BW
SLX300-40D 12-Ch AI, 4-Ch AO, 8-Ch DIO, Ethernet, DIN Rail Mount 8B49-01, -02 Voltage Output Modules, 100Hz BW
8B50-04, -05, -06 milliVolt Input Modules, 20kHz BW
SLX146-02, -07 Null Modem Serial Cable, Female DB-9 to Female DB-9; 2m, 7m 8B51-04, -05, -06, -08, -10, -13 Voltage Input Modules, 20kHz BW
SLX147-01, -02, -05 USB Cable, Type A to Type B; 1m, 2m, 5m 8BPT Non-Isolated Signal Pass Thru Module
SLX370 Software Tools on CD; Config Sample, LabVIEW VI 8BPWR-2 Power Supply Module, 7-34VDC Input
SLX380 Quick Start Guide, Hardware Manual, Software Manual
SCMD-MIAC5x Miniature Digital AC Input Modules
SLX141-01, -02, -07 Ethernet Cable, 1m, 2m, 7m SCMD-MIDC5x Miniature Digital DC Input Modules
SLX141-X01, -X02, -X07 Ethernet Crossover Cable, 1m, 2m, 7m SCMD-MOAC5x Miniature Digital AC Output Modules
SCMXRK-002 19” Metal Rack for Mounting Backpanels SCMD-MODC5x Miniature Digital DC Output Modules
SCMXRAIL1-XX DIN EN50022-35x7.5 (slotted steel), length -XX in meters SCMD-MORx5 Miniature Relay Output Modules
SCMXRAIL3-XX DIN EN50022-35x15 (slotted steel), length -XX in meters SCMD-PT Miniature Pass Thru Module
8B30-04, -05, -06 milliVolt Input Modules, 3Hz BW SCMXPRT-001 Power Supply, 5VDC, 1A, 120VAC Input
8B31-04, -05, -06, -08, -10, -13 Voltage Input Modules, 3Hz BW SCMXPRE-001 Power Supply, 5VDC, 1A, 220VAC Input
isoLynx
8B32-01, -02 Current Input Modules, 3Hz BW SCMXPRT-003 Power Supply, 5VDC, 3A, 120VAC Input
8B34-01, -02, -03, -04 2- and 3-Wire RTD Input Modules, 3Hz BW SCMXPRE-003 Power Supply, 5VDC, 3A, 220VAC Input
8B35-01, -02, -03, -04 4-Wire RTD Input Modules, 3Hz BW PWR-4505 Power Supply, 5VDC, 5A, 85-264VAC Input
8B36-01, -02, -03, -04 Potentiometer Input Modules, 3Hz BW PWR-PS5RB Power Supply, 24VDC, 0.6A, 100-240VAC Input
8B37J, K, T, R, S Thermocouple Input Modules, Non-linearized, 3Hz BW PWR-PS5RC Power Supply, 24VDC, 1.3A, 100-240VAC Input
8B38-06, -07, -08 Strain Gage Input Modules, 3kHz BW PWR-PS5RD Power Supply, 24VDC, 2.1A, 100-240VAC Input
8B38-36, -37, -38 Strain Gage Input Modules, 3Hz BW PWR-PS5RE Power Supply, 24VDC, 4.2A, 100-240VAC Input
SLX920
ReDAQ® Freedom SCADA Software for
Features
SCM5B isoLynx® SLX200 ReDAQ® Freedom - Server
• Generates Data Tables and Excel
Description Spreadsheets
Combined with one or more SCM5B isoLynx® SLX200 systems, Dataforth’s
ReDAQ® Freedom supervisory control and data acquisition (SCADA) software • Integrated XML Data Exchange
provides an effective solution for factory automation, process control, test and • Dynamic Calculations including Mean,
measurement, machine control, and data acquisition applications. ReDAQ® Median, Maximum, Minimum,
Freedom enables data to be monitored and outputs to be set, locally or Variance and Standard Deviation
remotely, via an intranet or the Internet.
Establishing a complete automation or test system with ReDAQ® Freedom is • Built-in Real-time, Lossless Historian
simple. The core software runs under Windows and sets up the central server, • Built-in SMTP Client Generates
which then can connect to many SLX200 units via one or more networks. The Emails upon Alarm
networks can be RS-485, dedicated Ethernet connections, or a combination
of the two. Users access the system with an intranet or the Internet; no • No User Application Software Required:
application software is required because the HMI is delivered via web Access Entirely Browser-based
browsers.
• Streams Real-time Data to ReDAQ®
Because this powerful software is browser-based, remote control and moni- Freedom - Designer for Graphical Displays
toring are readily achieved. The administrator creates an I/O website using
ReDAQ® Freedom - Designer, which generates Java applets such as pie ReDAQ® Freedom - Designer
charts, histograms, graphs, and mimics using a graphical user interface.
When viewed in users’ browsers, these dynamic real-time graphical displays • Generates Real-time and History Graphics
respond in real-time to external signals. Input data to the graphics comes from Including:
SCM5B isolated analog signal conditioning modules in the SLX200 units. - Live Tables
Multiple alarm levels can be set and, whenever a monitored signal crosses an - Graphs
alarm level, a built-in SMTP client generates an email indicating system status.
- Histograms
A lossless data historian is built into ReDAQ® Freedom. The historian runs
automatically and continuously captures data at regular intervals. This historized - Pie Charts
data then can be used to generate history tables or graphs.
- Mimics
ReDAQ® Freedom also provides for the exchange of current and historical
data with other applications via XML. In addition, users can create Excel • Evaluates Math Expressions Using: +, -, *, /,
spreadsheets using current and historical data. ^, %, sqrt, sqr, sin, cos, tan, acos, asin, atan,
sinh, cosh, tanh, asinh, acosh, atanh, exp,
log, min, max, ceil, floor, abs, neg, and rand
Ordering Information
Model Description
SLX920 ReDAQ® Freedom Software including ReDAQ®
Freedom - Server and ReDAQ® Freedom - Designer
SLX930
ReDAQ® Shape Software for
Features
8B isoLynx® SLX300 • 3 Easy Steps to Create Customized
Presentation Panels
Description • No Setup or Configuration Required in
ReDAQ® Shape, Dataforth’s out-of-the-box DAQ software for the SLX300,
Acquire and Analyze Panels
provides the easiest and most efficient development tool to create, save, and • 18 High Quality Controls
open graphical user interface projects as well as to test, process, and analyze • Supports Any Graphical File Format
acquired data. Built-in functions in the Acquire and Analyze panels can be
used without setup and configuration. Just three easy steps are required to
• Integrated, Across-the-Board Applicability
create customized Presentation panels using 18 high quality controls and • Most Effective Way to Set Up & Configure
powerful isoLynx® SLX300 functions. 8B isoLynx® SLX300 Functions:
The ReDAQ Shape controls include:
– Continuous and burst scan modes for 12
analog input and 4 analog output channels
– Button – Slide
– Automatically scales data from counts to
– Picture Box – Tank
engineering units
– Text Box – Gage
– Group Box – Meter – 8 discrete I/O with 7 special functions:
– Label – Knob pulse/frequency counter, pulse/frequency
isoLynx
– LED – Chart Recorder counter with de-bounce, waveform
– Switch – Oscilloscope measurement, time between events,
– Numeric Edit – XY Plot frequency generator, PWM generator,
– Thermometer – Discrete Waveform Graph one-shot pulse generator
ReDAQ® Shape also provides the most effective way to set up and configure – Customer user tag name for any input
the 8B isoLynx® SLX300 functions. The software controls are easily used to and output
create, move, re-size, cut, copy, paste, and delete; they also support any – Cold Junction Compensation and
graphical file format so presentations made with other software can be loaded linearization for thermocouple input modules
into ReDAQ® Shape.
– Control loop and alarm output
In contrast to other graphical software environments, ReDAQ® Shape SLX300
software has a very short user-learning curve. It was created using – Three function timer (count-down, 24hr/day,
programming tools incorporated from Microsoft Visual Studio® and National day/time) with 10 programmable events
Instruments Measurement StudioTM, ensuring its integrated, across-the-board
applicability.
Acquire
Analyze
Present
SCMD
Isolated SCMD Digital I/O Modules
Dataforth offers a broad line of digital input and output modules and accessories
Features
providing safe, reliable interfacing to industrial measurement and control
applications. When installed near individual field loads, our SCMD series I/O • 4000Vrms Optical Isolation
modules create a rugged protective isolation barrier, effective to 4kV, between • Industry Standard Packaging
the field and computer system. Use of these modules can also reduce field
• Input Modules Incorporate Input Filtering for
wiring costs while establishing an economical, manageable approach for Transient-Free Switching
system expansion and repair.
• Complete Selection of Backpanels and
The SCMD Series Accessories
SCMD miniature digital I/O modules are solid-state devices which send “ON” and • Optional Low Noise, Fast Switching Models
“OFF” electrical signals to and from a computer. The input modules, depending on • UL Listed, CSA Certified, CE Compliant
the type selected, convert AC or DC voltages to DC logic signals and send them • Manufactured per RoHS Directive 2002/95/EC
to the computer system. Output modules work in the opposite direction, switching
either AC or DC circuits on or off in response to logic-level voltage commands from
the computer. SCMD modules are available in “miniature” versions of four basic Applications
types: AC input, DC input, AC output, and DC output. Input Modules Interface To:
• SCMD–MIAC and –MIDC miniature input modules are used for sensing “ON”
• Proximity Switches
and “OFF” AC or DC voltage levels in the ranges 10-60, 90-140, and 180-
280VAC and 3.3-32 and 10-60VDC. Models with low noise, fast switching, • Limit Switches
and other special features are also available. • Photoelectric Switches
• SCMD–MOAC and –MODC are miniature output modules accepting 5VDC or • TTL Devices
24VDC inputs and providing several different output ranges, including • Pushbuttons
12/24 to 140/280VAC and 0/3/5 to 50/60/200VDC. Fast switching, and other
special options are also available. Output Modules For Switching AC and DC Loads:
• SCMD–MORO and –MORC are miniature relay output modules used for • Relays • Solenoids
switching AC and DC loads up to 125Vrms or 100VDC at maximum 30WDC • Motor Starters • Indicator Lamps
or 62.5VA.
SCMD-MIAC/MIDC
Miniature Digital Input Modules
Description
SCMD digital input modules provide highly reliable and safe interfaces to
Features
harsh industrial measurement and control applications. With SCMD modules
installed near individual field signals, a reliable isolation barrier is provided • Plug into Backpanels for Miniature or
between the field wiring computer system. Other benefits include reduction of Full-Sized Modules
field wiring costs and establishment of a cost effective and manageable method • AC Inputs for 24V, 120V, 240V
for system expansion and repair.
• DC Inputs for 3.3 to 32V, 10 to 60V
The SCMD-MIAC digital input modules are used for sensing ON/OFF AC or DC
• 4000Vrms Optical Isolation
voltage levels in the ranges of 18-36, 90-140 and 180-280VAC or VDC
respectively. They are protected from damage due to high-voltage transients on • Open-Collector Output
the input signal. • Industry-Standard Pinout and Footprint
The SCMD-MIDC digital input modules provide DC voltage sensing at the lower • Operating Temperature –30° C to +80° C
ranges of 3.3 to 32VDC and 10 to 60VDC.
• UL Listed, CSA Certified, CE Compliant
High voltage, low voltage, fast switching, and low noise options are available,
designated by suffixes “A”, “E”, “F”, and “N” respectively.
Five backpanels are available for mounting SCMD-M digital input modules. See
“Accessories” section.
Ordering Information
Model Input Range Supply Voltage
SCMD
SCMD-MIAC5 90 to 140VAC/DC 5V
SCMD-MIAC5A 180 to 280VAC/DC 5V
SCMD-MIAC5E 10 to 60VAC/DC 5V
Digital Input Modules - Model No. Suffixes Identifying Optional Features SCMD-MIAC24 90 to 140VAC/DC 24V
Suffix Feature SCMD-MIAC24A 180 to 280VAC/DC 24V
A High voltage versions (280VAC for AC modules). SCMD-MIDC5 3.3 to 32VDC 5V
E Low voltage 10VAC input for AC modules. SCMD-MIDC5F 3.3 to 32VDC 5V
F Fast-switching version of DC modules. SCMD-MIDC5N 10 to 60VDC 5V
N Enhanced noise immunity version of DC modules. SCMD-MIDC24 3.3 to 32VDC 24V
SCMD-MOAC/MODC
Miniature Digital Output Modules
Description
The SCMD digital output modules are used for switching AC and DC loads such
as relays, solenoids, motor starters, or indicator lamps. All models provide up
Features
to 4000Vrms of optical isolation between the field device and the control logic. • AC Modules have High Current Thyristor with
The AC output modules incorporate zero voltage switching and an RC snubber 100 Amp Surge Capability
circuit which allows switching heavy inductive loads. Functionality is denoted by • Zero or Random Turn-On Available in AC
case color—AC modules are black, and DC modules are red. Modules
Six backpanels are available for mounting SCMD-M digital output modules. See • Plug into Backpanels for Miniature or
“Accessories” section . Full-Sized Modules
• 4000Vrms Optical Isolation (except ML suffix)
• 1500Vrms Optical Isolation (with ML suffix)
• Industry Standard Pinout and Footprint
• 3.5 Amp AC Modules Provide Extra Switching
Capability
• 5.0 Amp DC Modules Available
• Operating Temperature –30° C to +80° C
• UL Listed, CSA Certified, CE Compliant
Ordering Information
Model Output Range Supply Voltage
SCMD-MOAC5 12 to 140VAC 5V
Figure 1: SCMD-MOAC/MODC Physical Dimensions SCMD-MOAC5A 24 to 280VAC 5V
SCMD-MOAC5B 24 to 280VAC 5V
Digital Output Modules - Model No. Suffixes Identifying Optional Features SCMD-MOAC24 12 to 140VAC 24V
Suffix Feature
SCMD-MOAC24A 24 to 280VAC 24V
SCMD-MODC5 3.0 to 60VDC 5V
A High voltage versions (280VAC for AC modules,
SCMD-MODC5A 5.0 to 200VDC 5V
200VDC for DC modules).
B High voltage version (280VAC for AC modules) with low leakage SCMD-MODC5ML 0 to 50VDC 5V
output current. SCMD-MODC24 3.0 to 60VDC 24V
ML FET output version of DC module, 5.0A, 50VDC.
SCMD-MORO/MORC
Miniature Digital Relay Output Modules
Description
The SCMD digital relay output modules are used for switching AC and DC loads
such as relays, solenoids, motor starters, or indicator lamps. All models provide
Features
up to 1000Vrms of optical isolation between the field device and the control logic. • Resistive Load Only
Functionality is denoted by case color—relay modules are brown. • Max On-state Current 1A, 30WDC, 62.5VA
The -MOROxx models have a normally open contact and the -MORCxx models • Max Turn-on Time 2ms
have a normally closed contact.
• Max Turn-off Time 1ms
Six backpanels are available for mounting SCMD-M relay output modules. • 1000Vrms Isolation
See “Accessories” section.
• Plug into Backpanels for Miniature or
Full-Sized Modules
• Industry Standard Pinout and Footprint
• Operating Temperature –30° C to +80° C
• UL Listed, CSA Certified, CE Compliant
SCMD
Ordering Information
Model Output Range Supply Voltage Contact
SCMD-MORO5 100/125 VDC/Vrms 5V Normally open
SCMD-MORC5 100/125 VDC/Vrms 5V Normally closed
SCMD-MORO24 100/125 VDC/Vrms 24V Normally open
SCMD-MORC24 100/125 VDC/Vrms 24V Normally closed
SCMD Accessories*
Digital I/O Module Backpanels
Ordering Information
Model Description Features
SCMD-PB4 4-Ch Backpanel, Full Size & Miniature • Plug-Compatible Logic Connections on 8-,
SCMD-PB4R 4-Ch Backpanel, Full Size & Miniature, Output Only 16- and 24-Position Backpanels. Screw
SCMD-PB8SM 8-Ch Backpanel, 50-trace I/O male card edge Terminal Barrier Block for Logic
SCMD-PB16SM 16-Ch Backpanel, 50-trace I/O male card edge Connections on 4-Position Backpanels
SCMD-PB16TSM 16-Ch Backpanel, screw terminal input and output
• Screw Terminal Barrier Block for Load
SCMD-PB24SM 24-Ch Backpanel, 50-trace I/O male card edge
Connections
SCMD-PB4D 4-Ch Backpanel, Full Size & Miniature, DIN Rail Mount • Resident Pull-Up Resistors
SCMD-PB4RD 4-Ch Backpanel, Full Size & Miniature, Output Only, • 5 Amp Field-Replaceable Fuses
DIN Rail Mount (Littelfuse #251005 or Equivalent)
SCMD-PB8SMD 8-Ch Backpanel, 50-trace I/O male card edge,
DIN Rail Mount • LEDs Indicate Logic Status
SCMD-PB16SMD 16-Ch Backpanel, 50-trace I/O male card edge, • All Even-Numbered Logic Connections are
DIN Rail Mount Logic Ground
SCMD-PB16TSMD 16-Ch Backpanel, screw terminal input and output, • Input and Output Modules Accepted
DIN Rail Mount Interchangeably
SCMD-PB24SMD 24-Ch Backpanel, 50-trace I/O male card edge,
DIN Rail Mount • Operate with 5 or 24 Volt Logic Supplies
• Plastic Captive-Screw Retaining System for All
Jumpers (Connect common terminals on backpanels) Modules
• PB4, PB4R, PB8SM, PB16SM, PB16TSM, and
Model Description PB24SM, UL Listed, CSA Certified and CE
SCMD-JM8 Miniature, 8-position Compliant
Connectors
Mating connector for 50-trace I/O male card edge
66317-150 FCI-Berg
3415-0001 3M
DSCA
High Performance DIN Isolated Analog Signal Conditioners
Description
Each Instrument-ClassTM DSCA module provides a single channel of isolated
analog input or output. Various input modules accept analog voltage or current
Features
signals from all types of field sensors and sources and filter, isolate, amplify, • ±0.03% Accuracy (Typical)
linearize, and convert these input signals to high-level analog outputs suitable
• ±0.01% Linearity
for use in data acquisition, test and measurement, and control systems. Output
modules accept high-level analog voltage signals from a system, then buffer, isolate, • 1500Vrms Transformer Isolation &
filter, and amplify before providing a current or voltage output to a field device. 240Vrms Field-side Protection
• ANSI/IEEE C37.90.1 Transient Protection
• True 3-Way Isolation
• Wide Supply Voltage, 15 to 30VDC
• Industry Standard Output of 0 to +10V, ±10V,
0 to 20mA, or 4 to 20mA
• 4- to 6-Pole Low-Pass Filtering
• Up to 160dB CMR
• 85dB NMR at 60Hz, 80dB at 50Hz
• –40°C to +85°C Operating Temperature
• Screw Terminals and Plug-in Terminal Blocks
Simplify Wiring and Maintenance
• C-UL-US Listed
(Class I, Division 2, Groups A, B, C, D)
• CE and ATEX Compliant
• Manufactured per RoHS Directive 2002/95/EC
DSCA
ANALOG CURRENT INPUT MODULES Page 190
POTENTIOMETER INPUT MODULES Page 196 ANALOG VOLTAGE INPUT MODULES, 3kHz BW Page 204
MODEL INPUT RANGE OUTPUT RANGE † MODEL INPUT RANGE OUTPUT RANGE†
DSCA36-01 100Ω 2, 3, 4 DSCA40-01 –10mV to +10mV 1
DSCA36-02 500Ω 2, 3, 4 DSCA40-02 –50mV to +50mV 1
DSCA36-03 1kΩ 2, 3, 4 DSCA40-03 –100mV to +100mV 1
DSCA36-04 10kΩ 2, 3, 4 DSCA40-04 –10mV to +10mV 2, 3, 4
DSCA40-05 –50mV to +50mV 2, 3, 4
THERMOCOUPLE INPUT MODULES Page 198 DSCA40-06 –100mV to +100mV 2, 3, 4
MODEL TYPE‡ INPUT RANGE OUTPUT RANGE† DSCA40-07 0 to +10mV 2, 3, 4
DSCA40-08 0 to + 50mV 2, 3, 4
DSCA37J-01 J –100°C to +760°C (–148°F to +1400°F) 2, 3, 4 DSCA40-09 0 to +100mV 2, 3, 4
DSCA37K-02 K –100°C to +1350°C (–148°F to +2462°F) 2, 3, 4
DSCA41-01 –1V to +1V 1
DSCA37T-03 T –100°C to +400°C (–148°F to +752°F) 2, 3, 4
DSCA41-02 –5V to +5V 1
DSCA37E-04 E 0°C to +900°C (+32°F to +1652°F) 2, 3, 4
DSCA41-03 –10V to +10V 1
DSCA37R-05 R 0°C to +1750°C (+32°F to +3182°F) 2, 3, 4
DSCA41-04 –1V to +1V 2, 3, 4
DSCA37S-06 S 0°C to +1750°C (+32°F to +3182°F) 2, 3, 4
DSCA41-05 –5V to +5V 2, 3, 4
DSCA37B-07 B 0°C to +1800°C (+32°F to +3272°F) 2, 3, 4
DSCA41-06 –10V to +10V 2, 3, 4
DSCA37N-08 N –100°C to +1300°C (–148°F to +2372°F) 2, 3, 4
DSCA41-07 –20V to +20V 1
DSCA41-08 –20V to +20V 2, 3, 4
STRAIN GAGE INPUT MODULES Page 200 DSCA41-09 –40V to +40V 1
OUTPUT DSCA41-10 –40V to +40V 2, 3, 4
MODEL INPUT EXCITATION RANGE† DSCA41-11 0 to +1V 2, 3, 4
DSCA38-01 ±10mV Full Bridge Input, (3mV/V) +3.333V 1 DSCA41-12 0 to +5 V 2, 3, 4
DSCA38-02 ±30mV Full Bridge Input, (3mV/V) +10.0V 1 DSCA41-13 0 to +10V 2, 3, 4
DSCA38-03 ±10mV Half Bridge Input, (3mV/V) +3.333V 1 DSCA41-14 0 to +20V 2, 3, 4
DSCA38-04 ±30mV Half Bridge Input, (3mV/V) +10.0V 1 DSCA41-15 0 to +40V 2, 3, 4
DSCA38-05 ±20mV Full Bridge Input, (2mV/V) +10.0V 1
DSCA38-06 ±33.3mV Full Bridge Input, (10mV/V) +3.333V 1
DSCA38-07 ±100mV Full Bridge Input, (10mV/V) +10.0V 1 2-WIRE TRANSMITTER INTERFACE MODULES Page 206
DSCA38-08 ±10mV Full Bridge Input, (3mV/V) +3.333V 2, 3, 4 MODEL INPUT RANGE OUTPUT RANGE†
DSCA38-09 ±30mV Full Bridge Input, (3mV/V) +10.0V 2, 3, 4 DSCA42-01 4mA to 20mA 0V to +10V & 3, 4
DSCA38-10 ±10mV Half Bridge Input, (3mV/V) +3.333V 2, 3, 4 DSCA42-02 4mA to 20mA 2V to +10V
DSCA38-11 ±30mV Half Bridge Input, (3mV/V) +10.0V 2, 3, 4
DSCA38-12 ±20mV Full Bridge Input, (2mV/V) +10.0V 2, 3, 4
DSCA38-13 ±33.3mV Full Bridge Input, (10mV/V) +3.333V 2, 3, 4 GENERAL PURPOSE INPUT MODULES, DC EXCITATION Page 208
DSCA38-14 ±100mV Full Bridge Input, (10mV/V) +10.0V 2, 3, 4 MODEL INPUT RANGE OUTPUT RANGE†
DSCA38-15 0 to +10mV Full Bridge Input, (3mV/V) +3.333V 2, 3, 4 DSCA43-01 –1V to +1V 1
DSCA38-16 0 to +30mV Full Bridge Input, (3mV/V) +10.0V 2, 3, 4 DSCA43-02 –2V to +2V 1
DSCA38-17 0 to +10mV Half Bridge Input, (3mV/V) +3.333V 2, 3, 4 DSCA43-03 –3V to +3V 1
DSCA38-18 0 to +30mV Half Bridge Input, (3mV/V) +10.0V 2, 3, 4 DSCA43-04 –4V to +4V 1
DSCA38-19 0 to +20mV Full Bridge Input, (2mV/V) +10.0V 2, 3, 4 DSCA43-05 –5V to +5V 1
DSCA38-20 0 to +33.3mV Full Bridge Input, (10mV/V) +3.333V 2, 3, 4 DSCA43-06 –6V to +6V 1
DSCA38-21 0 to +100mV Full Bridge Input, (10mV/V) +10.0V 2, 3, 4 DSCA43-07 –7V to +7V 1
DSCA43-08 –8V to +8V 1
DSCA43-09 –9V to +9V 1
CURRENT OUTPUT MODULES Page 202 DSCA43-10 –10V to +10V 1
MODEL INPUT RANGE OUTPUT RANGE DSCA43-11 –1V to +1V 2, 3, 4
DSCA39-01 0V to +10V 4mA to 20mA DSCA43-12 –2V to +2V 2, 3, 4
DSCA39-02 –10V to +10V 4mA to 20mA DSCA43-13 –3V to +3V 2, 3, 4
DSCA39-03 0V to +10V 0mA to 20mA DSCA43-14 –4V to +4V 2, 3, 4
DSCA39-04 –10V to +10V 0mA to 20mA DSCA43-15 –5V to +5V 2, 3, 4
DSCA39-05 0mA to 20mA 0mA to 20mA DSCA43-16 –6V to +6V 2, 3, 4
DSCA39-07 –10V to +10V -20mA to +20mA DSCA43-17 –7V to +7V 2, 3, 4
DSCA43-18 –8V to +8V 2, 3, 4
DSCA43-19 –9V to +9V 2, 3, 4
DSCA43-20 –10V to +10V 2, 3, 4
DSCA
DSCA49-06 –10V to +10V 0V to +10V
**RTD STANDARDS
TYPE ALPHA COEFFICIENT DIN JIS IEC
100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
120Ω Ni 0.00672
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA30/31
Analog Voltage Input Signal Conditioners, Narrow Bandwidth
Description
Each DSCA30/31 voltage input module provides a single channel of analog
input which is filtered, isolated, amplified, and converted to a high-level voltage Features
output. Signal filtering is accomplished with a five-pole filter which provides • Accepts Millivolt and Voltage Level Signals
85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An anti-aliasing
pole is located on the field side of the isolation barrier, and the other four poles • Industry Standard Output of 0 to +10V, ±10V,
are on the system side. After the initial field-side filtering, the input signal is 0 to 20mA, or 4 to 20mA
chopped by a proprietary chopper circuit. Isolation is provided by transformer • 1500Vrms Transformer Isolation
coupling, again using a proprietary technique to suppress transmission of • ANSI/IEEE C37.90.1 Transient Protection
common mode spikes or surges.
• Input Protected to 240VAC Continuous
Module output is either voltage or current. For current output models a dedicated
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • True 3-Way Isolation
4 (-OUT). The system-side load may be either floating or grounded. • Wide Range of Supply Voltage
Special input circuits provide protection against accidental connection of • 160dB CMR
power-line voltages up to 240VAC and against transient events as defined by • 85dB NMR at 60Hz, 80dB at 50Hz
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal output
• ±0.03% Accuracy
and power input terminals to guard against transient events and power reversal.
Signal and power lines are secured to the module using screw terminals which • ±0.01% Linearity
are in pluggable terminal blocks for ease of system assembly and reconfiguration. • Easily Mounts on Standard DIN Rail
The modules have excellent stability over time and do not require recalibration, • C-UL-US Listed
however, zero and span settings are adjustable up to ±5% to accommodate
• CE and ATEX Compliant
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
DSCA
Response Time, 90% Span 165ms * †
Output Ranges Available
Power Supply
Voltage 15 to 30VDC * Output Range Part No. Suffix Example
Current 25mA (VOUT), 55mA (IOUT) *
Sensitivity ±0.0001%/% * 1. –10V to +10V NONE DSCA30-01
Protection 2. 0V to +10V NONE DSCA30-04
Reverse Polarity Continuous *
3. 4 to 20mA C DSCA30-04C
Transient ANSI/IEEE C37.90.1 *
4. 0 to 20mA E DSCA30-04E
Environmental
Operating Temp. Range –40°C to +80°C *
Storage Temp. Range –40°C to +80°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD,EFT Performance B *
Mechanical Dimensions 2.95" x 0.89" x 4.13" *
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail *
NOTES:
* Same specification as DSCA30.
(1) Includes linearity, hysteresis and repeatability.
(2) Vz is the nominal input voltage that results in 0V or 0mA output.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA32
Analog Current Input Signal Conditioners
Description
Each DSCA32 current input module provides a single channel of analog input
which is filtered, isolated, amplified, and converted to a high-level voltage
Features
output. Signal filtering is accomplished with a five-pole filter which which is • Accepts Milliamp Level Signals
optimized for step response. An anti-aliasing pole is located on the field side of • Industry Standard Output of 0 to +10V,
the isolation barrier, and the other four poles are on the system side. After the 0 to 20mA, or 4 to 20mA
initial field-side filtering, the input signal is chopped by a proprietary chopper
circuit. Isolation is provided by transformer coupling, again using a proprietary • 1500Vrms Transformer Isolation
technique to suppress transmission of common mode spikes or surges. • ANSI/IEEE C37.90.1 Transient Protection
Module output is either voltage or current. For current output models a dedicated • Input Protected to 240VAC Continuous
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • True 3-Way Isolation
4 (-OUT). The system-side load may be either floating or grounded.
• Wide Range of Supply Voltage
Special input circuits provide protection against accidental connection of
• 105dB CMR
power-line voltages up to 240VAC and against transient events as defined by
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal output • 5 Poles of Filtering
and power input terminals to guard against transient events and power reversal. • ±0.03% Accuracy
Signal and power lines are secured to the module using screw terminals which
are in pluggable terminal blocks for ease of system assembly and reconfiguration. • ±0.01% Linearity
• Easily Mounts on Standard DIN Rail
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate • C-UL-US Listed
situations where fine-tuning is desired. The adjustments are made using • CE and ATEX Compliant
potentiometers located under the front panel label and are non-interactive for
ease of use.
DSCA
Voltage 15 to 30VDC
Current 25mA (VOUT), 55mA (IOUT)
Sensitivity ±0.0001%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail
NOTES:
(1) Includes linearity, hysteresis and repeatability.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA33
Isolated True RMS Input Signal Conditioners
Description
Each DSCA33 True RMS input module provides a single channel of AC input
which is converted to its True RMS DC value, filtered, isolated, amplified, and
Features
converted to standard process voltage or current output (Figure 1). • Interfaces RMS Voltage (0 – 300V) or
RMS Current (0 – 5A)
The field voltage or current input signal is processed through an AC coupled
pre-amplifier and RMS converter on the field side of the isolation barrier. The • Designed for Standard Operation with
converted dc signal is then filtered and chopped by a proprietary chopper Frequencies of 45Hz to 1000Hz
circuit and transferred across the transformer isolation barrier, suppressing (Extended Range Operation to 20kHz)
transmission of common mode spikes and surges. The computer side circuitry • Compatible with Standard Current and
reconstructs, filters and converts the signal to industry standard outputs. Potential Transformers
Module output is either voltage or current. For current output models a • Industry Standard Output of 0 to 1mA,
dedicated loop supply is provided at terminal 3 (+OUT) with loop return located 0 to 20mA, 4 to 20mA, 0 to +5V, or 0 to +10V
at terminal 4 (-OUT). The system-side load may be either floating or grounded. • ±0.25% Factory Calibrated Accuracy
Special input circuits provide protection against accidental connection of (Accuracy Class 0.2)
power-line voltages up to 480VAC and against transient events as defined by • ±5% Adjustable Zero and Span
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal output
and power input terminals to guard against transient events and power • 1500Vrms Transformer Isolation
reversal. Signal and power lines are secured to the module using screw • Input Overload Protected to 480V
terminals which are pluggable terminal blocks for ease of system assembly (Peak AC & DC) or 10Arms Continuous
and reconfiguration. • 100dB CMR
DSCA33 modules have excellent stability over time and do not require • ANSI/IEEE C37.90.1 Transient Protection
recalibration, however, both zero and span settings are adjustable to accom-
• Easily Mounts on Standard DIN Rail
modate situations where fine tuning is desired. The adjustments are made
using potentiometers located under the front panel label and are • C-UL-US Listed and CE Compliant
non-interactive for ease of use. • ATEX Compliant (all models except
Due to circuit limitations, DSCA33-04x and -05x are not ATEX compliant. DSCA33-04x, -05x)
DSCA
Input to Output, Input to Power
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
Output to Power
Continuous 50VDC max
Response Time (0 to 99%) <400ms
CMR (50 or 60Hz) 100dB
Power Supply
Voltage 19 to 29VDC
Current 45mA (VOUT), 65mA (IOUT)
Sensitivity ±0.0002%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
HazLoc ATEX All models except DSCA33-04x, -05x
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.83% Span Error
ESD, EFT Performance B
Installation Notes:
Mechanical Dimensions (h)(w)(d) 2.95" x 0.89" x 4.13" (75mm x 22.5mm x 105mm) 1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B,
Mounting DIN EN50022-35x7.5 or -35x15 rail C, D, or Non-Hazardous Locations Only.
NOTES: 2.) Warning - Explosion Hazard - Substitution of Components May Impair
(1) For 1 to 25 seconds the max allowable transient current rating is √ 2500 / (event time). For less than 1 second, Suitability for Class I, Division 2.
ANSI/IEEE C37.90.1 applies with a 0.05Ω load. For greater than 25 seconds, the 10A max continuous rating applies. 3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless
(2) For 0-10% Span measurements, add 0.25% accuracy error (-02 thru -07) or 1.00% accuracy error (-01). Accuracy includes Power Has Been Switched Off or The Area is Known to be Non-Hazardous.
linearity, hysteresis and repeatability but not source or external shunt inaccuracy (if used).
(3) At standard 60Hz factory calibration (90Hz for -01, -06). Consult factory for calibration at other frequencies.
DSCA34
Linearized 2- or 3-Wire RTD Input Signal Conditioners
Description
Each DSCA34 RTD input module provides a single channel of RTD input which
is filtered, isolated, amplified, linearized, and converted to a high-level voltage Features
output. Signal filtering is accomplished with a five-pole filter which provides • Interfaces to 100Ω Platinum or 120Ω
85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An anti-aliasing pole Nickel RTDs
is located on the field side of the isolation barrier, and the other four poles are
• Linearizes RTD Signal
on the system side. After the initial field-side filtering, the input signal is chopped
by a proprietary chopper circuit. Isolation is provided by transformer coupling, • Industry Standard Output of 0 to +10V,
again using a proprietary technique to suppress transmission of common mode 0 to 20mA, or 4 to 20mA
spikes or surges. • 1500Vrms Transformer Isolation
RTD excitation is provided from the module using a precision current source. • ANSI/IEEE C37.90.1 Transient Protection
Lead compensation is achieved by matching two current paths which cancels • Input Protected to 240VAC Continuous
the effects of lead resistance. The excitation current is small ( approx. 0.25mA)
which minimizes self-heating of the RTD. • True 3-Way Isolation
Module output is either voltage or current. For current output models a dedicated • Wide Range of Supply Voltage
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • 160dB CMR
4 (-OUT). The system-side load may be either floating or grounded. • 85dB NMR at 60Hz, 80dB at 50Hz
Special input circuits provide protection against accidental connection of power- • ±0.08% Accuracy
line voltages up to 240VAC and against transient events as defined by ANSI/
• ±0.025% Conformity
IEEE C37.90.1. Protection circuits are also present on the signal output and
power input terminals to guard against transient events and power reversal. • Easily Mounts on Standard DIN Rail
Signal and power lines are secured to the module using screw terminals which • C-UL-US Listed
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
• CE and ATEX Compliant
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±3% to accommodate
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
DSCA
‘+’ Lead Upscale
‘–’ Lead Non-deterministic **RTD Standards
‘x’ Lead Downscale
Power Supply Type Alpha Coefficient DIN JIS IEC
Voltage 15 to 30VDC
Current 25mA (VOUT), 55mA (IOUT) 100Ω Pt 0.00385 DIN 43760 JIS C 1604-1989 IEC 751
Sensitivity ±0.0001%/% 120Ω Ni 0.00672
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail
NOTES:
(1) Includes conformity, hysteresis and repeatability.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA36
Potentiometer Input Signal Conditioners
Description
Each DSCA36 potentiometer input module provides a single channel of
Features
potentiometer input which is filtered, isolated, amplified, and converted to a
high-level voltage output. Signal filtering is accomplished with a five-pole filter • Interfaces to Potentiometers up to 10kΩ
which provides 85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An • Industry Standard Output of 0 to +10V,
anti-aliasing pole is located on the field side of the isolation barrier, and the other 0 to 20mA, or 4 to 20mA
four poles are on the system side. After the initial field-side filtering, the input
signal is chopped by a proprietary chopper circuit. Isolation is provided by • 1500Vrms Transformer Isolation
transformer coupling, again using a proprietary technique to suppress • ANSI/IEEE C37.90.1 Transient Protection
transmission of common mode spikes or surges. • Input Protected to 240VAC Continuous
Potentiometer excitation is provided from the module using a precision current • True 3-Way Isolation
source. Lead compensation is achieved by matching two current paths which
cancels the effects of lead resistance. The excitation current is small (approx. • Wide Range of Supply Voltage
0.25mA) which minimizes self-heating of the sensor. • 160dB CMR
Module output is either voltage or current. For current output models a dedicated • 85dB NMR at 60Hz, 80dB at 50Hz
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • ±0.03% Accuracy
4 (-OUT). The system-side load may be either floating or grounded.
• ±0.01% Linearity
Special input circuits provide protection against accidental connection of power- • Easily Mounts on Standard DIN Rail
line voltages up to 240VAC and against transient events as defined by ANSI/
IEEE C37.90.1. Protection circuits are also present on the signal output and • C-UL-US Listed
power input terminals to guard against transient events and power reversal. • CE and ATEX Compliant
Signal and power lines are secured to the module using screw terminals which
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
DSCA
Open Input Response
‘+’ Lead Upscale
‘–’ Lead Non-deterministic
‘x’ Lead Downscale
Power Supply
Voltage 15 to 30VDC
Current 25mA (VOUT), 55mA (IOUT)
Sensitivity ±0.0001%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail
NOTES:
(1) Includes linearity, hysteresis and repeatability.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA37
Non-Linearized Thermocouple Input Signal Conditioners
Description
Each DSCA37 non-linearized thermocouple input module provides a single
channel of thermocouple input which is filtered, isolated, amplified, and Features
converted to a high-level voltage output. Signal filtering is accomplished with a • Interfaces to Types J, K, T, E, R, S, B, and N
five-pole filter which provides 85dB of normal-mode rejection at 60Hz and 80dB Thermocouples
at 50Hz. An anti-aliasing pole is located on the field side of the isolation barrier,
and the other four poles are on the system side. After the initial field-side filtering, • Industry Standard Output of 0 to +10V,
the input signal is chopped by a proprietary chopper circuit. Isolation is provided 0 to 20mA, or 4 to 20mA
by transformer coupling, again using a proprietary technique to suppress • 1500Vrms Transformer Isolation
transmission of common mode spikes or surges. • ANSI/IEEE C37.90.1 Transient Protection
The DSCA37 can interface to eight industry standard thermocouple types: J, K, T, • Input Protected to 240VAC Continuous
E, R, S, B and N. Each module has cold junction compensation to correct for
parasitic thermocouples formed by the thermocouple wire and input screw • True 3-Way Isolation
terminals on the module. Upscale open thermocouple detection is provided • Wide Range of Supply Voltage
by internal circuitry. Downscale indication can be implemented by installing a • 160dB CMR
47MΩ, ±20% resistor between screw terminals 6 and 8 on the input terminal block.
• 85dB NMR at 60Hz, 80dB at 50Hz
Module output is either voltage or current. For current output models a dedicated
• ±0.05% Accuracy
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal
4 (-OUT). The system-side load may be either floating or grounded. • ±0.01% Linearity
Special input circuits provide protection against accidental connection of • Easily Mounts on Standard DIN Rail
power-line voltages up to 240VAC and against transient events as defined by • C-UL-US Listed
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal output
• CE and ATEX Compliant
and power input terminals to guard against transient events and power reversal.
Power lines are secured to the module using screw terminals which are in
pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate
situations where fine-tuning is desired. The adjustments are made using potentiom-
eters located under the front panel label and are non-interactive for ease of use.
DSCA
Bandwidth, –3dB 3Hz
3. 4 to 20mA C DSCA37J-01C
NMR 85dB at 60Hz, 80dB at 50Hz 4. 0 to 20mA E DSCA37J-01E
Response Time, 90% Span 165ms
Open Input Response Upscale
Open Input Detection Time <5s ‡
Thermocouple Alloy Combinations
Power Supply Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
Voltage 15 to 30VDC
Current 25mA (VOUT), 55mA (IOUT)
Sensitivity ±0.0001%/% Type Material
Protection
Reverse Polarity Continuous J Iron vs. Copper-Nickel
Transient ANSI/IEEE C37.90.1 K Nickel-Chromium vs. Nickel-Aluminum
T Copper vs. Copper-Nickel
Environmental E Nickel-Chromium vs. Copper-Nickel
Operating Temperature Range –40°C to +80°C R Platinum-13% Rhodium vs. Platinum
Storage Temperature Range –40°C to +80°C S Platinum-10% Rhodium vs. Platinum
Relative Humidity 0 to 95% Noncondensing B Platinum-30% Rhodium vs. Platinum-6% Rhodium
Emissions EN61000-6-4 ISM, Group 1 N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4%
Radiated, Conducted Class A Silicon- 0.1% Magnesium
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail
NOTES:
(1) Includes conformity, hysteresis, repeatability, and CJC error.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA38
Strain Gage Input Signal Conditioners
Description
Each DSCA38 strain gage input module provides a single channel of strain gage
Features
input which is filtered, isolated, amplified, and converted to a high-level voltage
output. Signal filtering is accomplished with a five-pole filter which is optimized • Interfaces to 100Ω through 10kΩ Strain Gages
for step response. An anti-aliasing pole is located on the field side of the isolation • Industry Standard Output of ±10V,
barrier, and the other four poles are on the system side. After the initial field-side 0 to 20mA, or 4 to 20mA
filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is
provided by transformer coupling, again using a proprietary technique to • 1500Vrms Transformer Isolation
suppress transmission of common mode spikes or surges. • ANSI/IEEE C37.90.1 Transient Protection
The DSCA38 can interface to transducers with a nominal resistance of 100Ω to • Input Protected to 240VAC Continuous
10kΩ. Strain gage excitation is provided from the module by a stable 10V or • True 3-Way Isolation
3.333V source. This source is fully isolated, allowing the amplifier inputs to
operate over the full range of the excitation voltage. This feature enables the • Wide Range of Supply Voltage
module to be interfaced to other sensors requiring exctitation. • 100dB CMR
Module output is either voltage or current. For current output models a dedicated • Fully Isolated Excitation Supply
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • ±0.03% Accuracy
4 (-OUT). The system-side load may be either floating or grounded.
• ±0.01% Linearity
Special input circuits provide signal input and excitation protection against • Easily Mounts on Standard DIN Rail
accidental connection of power-line voltages up to 240VAC and against
transient events as defined by ANSI/IEEE C37.90.1. Protection circuits are also • C-UL-US Listed
present on the signal output and power input terminals to guard against transient • CE and ATEX Compliant
events and power reversal. Signal and power lines are secured to the module
using screw terminals which are in pluggable terminal blocks for ease of system
assembly and reconfiguration.
situations where fine-tuning is desired. The zero adjustment can be used to
The modules have excellent stability over time and do not require recalibration, offset bridge imbalances. The adjustments are made using potentiometers
however, zero and span settings are adjustable up to ±5% to accommodate located under the front panel label and are non-interactive for ease of use.
DSCA
Accuracy(1) ±0.03% Span 2. 0V to +10V NONE DSCA38-08
Linearity ±0.01% Span 3. 4 to 20mA C DSCA38-08C
Adjustability ±5% Zero and Span
Stability 4. 0 to 20mA E DSCA38-08E
Input Offset ±1µV/°C
Output Offset ±6ppm/°C (VOUT), ±20ppm/°C (IOUT)
Gain ±55ppm/°C
Output Noise, 100kHz Bandwidth 750µVrms (VOUT), 3µArms (IOUT)
Power Supply
Voltage 19 to 29VDC
Current 60mA (VOUT), 80mA (IOUT)
Sensitivity ±0.0002%/%
Protection Figure 2: Half Bridge Connection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13" Figure 3: Quarter Bridge Connection
(h)(w)(d) (75mm x 22.5mm x 105mm) Installation Notes:
Mounting DIN EN 50022 -35x7.5 or -35x15 rail 1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
NOTES: 2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
(1) Includes linearity, hysteresis and repeatability. (2) Strain Element. 3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA39
Current Output Signal Conditioners
Description
Each DSCA39 current output module provides a single channel of analog
output. The input signal is buffered, isolated, filtered and converted to a unipolar Features
or bipolar current output. Signal filtering is accomplished with a five-pole filter • Accepts High-Level Voltage Input
which provides 100dB per decade of attenuation above 1kHz. An anti-aliasing
• Provides 4 to 20mA, 0 to 20mA, or –20
pole is located on the system side of the isolation barrier, and the other four poles
to +20mA Output
are on the field side. After the initial system-side filtering, the input signal is
chopped by a proprietary chopper circuit. Isolation is provided by transformer • ANSI/IEEE C37.90.1 Transient Protection
coupling, again using a proprietary technique to suppress transmission of • 1500Vrms Transformer Isolation
common mode spikes or surges.
• ±0.03% Accuracy
Special output circuits provide protection against accidental connection of • ±0.01% Linearity
power-line voltages up to 240VAC and against transient events as defined by
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal input and • Output Protected to 240VAC Continuous
power input terminals to guard against transient events and power reversal. • True 3-Way Isolation
Signal and power lines are secured to the module using screw terminals which
• Wide Range of Supply Voltage
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
• 100dB CMR
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate • Easily Mounts on Standard DIN Rail
situations where fine-tuning is desired. The adjustments are made using • C-UL-US Listed
potentiometers located under the front panel label and are non-interactive for • CE and ATEX Compliant
ease of use.
Output Range 4 to 20mA or 0 to 20mA 0 to 20mA –20mA to +20mA DSCA39-01 0V to +10V 4mA to 20mA
Over Range Capability 10% * 5% DSCA39-02 –10V to +10V 4mA to 20mA
Output Compliance Voltage DSCA39-03 0V to +10V 0mA to 20mA
(Open Circuit) 22VDC * ±15VDC
Load Resistance Range 0 to 750Ω * 0 to 500Ω DSCA39-04 –10V to +10V 0mA to 20mA
Output Protection DSCA39-05 0mA to 20mA 0mA to 20mA
Continuous 240Vrms max * * DSCA39-07 –10V to +10V –20mA to +20mA
Transient ANSI/IEEE C37.90.1 * *
Input Range ±10V or 0V to +10V 0 to 20mA ±10V
Input Resistance
Normal 2MΩ <100Ω *
Power Off 2MΩ <100Ω *
Overload 2MΩ 65kΩ *
Input Protection
Continuous ±35V max 75mA *
Transient ANSI/IEEE C37.90.1 * *
CMV, Output to Input, Output to Power
Continuous 1500Vrms max * *
Transient ANSI/IEEE C37.90.1 * *
CMV, Input to Power
Continuous 50VDC max * *
CMR (50Hz or 60Hz) 110dB * *
Accuracy(1) ±0.03% Span * ±0.05%
Linearity ±0.01% Span * *
Adjustability ±5% Zero and Span * *
Stability
Offset ±20ppm/°C * *
Gain ±40ppm/°C ±50ppm/°C *
Output Noise, 100kHz Bandwidth 4µArms * *
Bandwidth, –3dB 1kHz * *
NMR 100dB/Decade Above 1kHz * *
DSCA
Response Time, 90% Span 475µs * *
Power Supply
Voltage 15 to 30VDC * 19 to 29VDC
Current 65mA * *
Sensitivity ±0.0003%/% * *
Protection
Reverse Polarity Continuous * *
Transient ANSI/IEEE C37.90.1 * *
Environmental
Operating Temperature Range –40°C to +80°C * *
Storage Temperature Range –40°C to +80°C * *
Relative Humidity 0 to 95% Noncondensing * *
Emissions EN61000-6-4 ISM, Group 1 * *
Radiated, Conducted Class A * *
Immunity EN61000-6-2 ISM, Group 1 * *
RF Performance A ±0.5% Span Error * *
ESD, EFT Performance B * *
Mechanical Dimensions 2.95" x 0.89" x 4.13” * *
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 * *
or -35x15 rail
NOTES:
* Same specification as DSCA39-01, -02, -03, -04
(1) Includes linearity, hysteresis and repeatability.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA40/41
Analog Voltage Input Signal Conditioners, Wide Bandwidth
Description
Each DSCA40/41 voltage input module provides a single channel of analog
input which is filtered, isolated, amplified, and converted to a high-level voltage
Features
output. Signal filtering is accomplished with a five-pole filter. An anti-aliasing • Accepts Millivolt and Voltage Level Signals
pole is located on the field side of the isolation barrier, and the other four poles • Industry Standard Output of 0 to +10V, ±10V,
are on the system side. After the initial field-side filtering, the input signal is 0 to 20mA, or 4 to 20mA
chopped by a proprietary chopper circuit. Isolation is provided by transformer
coupling, again using a proprietary technique to suppress transmission of • 1500Vrms Transformer Isolation
common mode spikes or surges. • ANSI/IEEE C37.90.1 Transient Protection
Module output is either voltage or current. For current output models a dedicated • Input Protected to 240VAC Continuous
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • True 3-Way Isolation
4 (-OUT). The system-side load may be either floating or grounded.
• Wide Range of Supply Voltage
Special input circuits provide protection against accidental connection of power-
• 100dB CMR
line voltages up to 240VAC and against transient events as defined by ANSI/
IEEE C37.90.1. Protection circuits are also present on the signal output and • 3 kHz Signal Bandwidth
power input terminals to guard against transient events and power reversal. • ±0.03% Accuracy
Signal and power lines are secured to the module using screw terminals which
are in pluggable terminal blocks for ease of system assembly and reconfiguration. • ±0.01% Linearity
• Easily Mounts on Standard DIN Rail
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate • C-UL-US Listed
situations where fine-tuning is desired. The adjustments are made using • CE and ATEX Compliant
potentiometers located under the front panel label and are non-interactive for
ease of use.
DSCA
Response Time, 90% Span 170µs *
Power Supply
Output Range Part No. Suffix Example
Voltage 15 to 30VDC * 1. –10V to +10V NONE DSCA40-01
Current 25mA (VOUT), 55mA (IOUT) *
Sensitivity ±0.0001%/% * 2. 0V to +10V NONE DSCA40-04
Protection 3. 4 to 20mA C DSCA40-04C
Reverse Polarity Continuous * 4. 0 to 20mA E DSCA40-04E
Transient ANSI/IEEE C37.90.1 *
Environmental
Operating Temperature Range –40°C to +80°C *
Storage Temperature Range –40°C to +80°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
RF Performance A ±0.5% Span Error *
ESD, EFT Performance B *
Mechanical Dimensions 2.95" x 0.89" x 4.13" *
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 *
or -35x15 rail
NOTES:
* Same specification as DSCA40.
(1) Includes linearity, hysteresis and repeatability.
(2) Vz is the nominal input voltage that results in 0V or 0mA output.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA42
2-Wire Transmitter Interface Signal Conditioners with Loop Power
Description
Each DSCA42 2-wire transmitter interface module provides a single channel of
4 to 20mA process current input which is filtered, isolated, amplified, and Features
converted to a high-level voltage output. An isolated 24V power supply is • Accepts Process Loop Signals
provided to power the 2-wire transmitter. Signal filtering is accomplished with a
five-pole filter which is optimized for step response. An anti-aliasing pole is • Industry Standard Output of 0 to +10V,
located on the field side of the isolation barrier, and the other four poles are on 2 to +10V, 0 to 20mA, or 4 to 20mA
the system side. After the initial field-side filtering, the input signal is chopped by • Provides Isolated Loop Excitation
a proprietary chopper circuit. Isolation is provided by transformer coupling, again • 1500Vrms Transformer Isolation
using a proprietary technique to suppress transmission of common mode spikes
or surges. • ANSI/IEEE C37.90.1 Transient Protection
• Input Protection to 240VAC Continuous
Module output is either voltage or current. For current output models a dedicated
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • True 3-Way Isolation
4 (-OUT). The system-side load may be either floating or grounded. • Wide Range of Supply Voltage
Special input circuits provide protection against accidental connection of power- • 105dB CMR
line voltages up to 240VAC and against transient events as defined by ANSI/
• 5 Poles of Filtering
IEEE C37.90.1. Protection circuits are also present on the signal output and
power input terminals to guard against transient events and power reversal. • ±0.03% Accuracy
Signal and power lines are secured to the module using screw terminals which • ±0.01% Linearity
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
• Easily Mounts on Standard DIN Rail
The modules have excellent stability over time and do not require recalibration, • C-UL-US Listed
however, zero and span settings are adjustable up to ±5% to accommodate
situations where fine-tuning is desired. The adjustments are made using • CE and ATEX Compliant
potentiometers located under the front panel label and are non-interactive for
ease of use.
DSCA
NMR (-3dB at 100Hz) 100dB/Decade Above 100Hz
Response Time, 90% Span 5ms
Power Supply
Voltage 19 to 29VDC
Current 60mA (VOUT), 80mA (IOUT)
Sensitivity ±0.0002%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail
NOTES:
(1) Includes linearity, hysteresis and repeatability.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA43
General Purpose Input Signal Conditioners, with DC Excitation
Description
Each DSCA43 general purpose input module provides a single channel of
Features
transducer input which is filtered, isolated, amplified, and converted to a
high-level voltage output. Signal filtering is accomplished with a five-pole filter • Interfaces to Transducers and Other Devices
which is optimized for step response. An anti-aliasing pole is located on the field Requiring a Stable, Isolated DC Supply
side of the isolation barrier, and the other four poles are on the system side. After • Industry Standard Output of 0 to +10V, ±10V,
the initial field-side filtering, the input signal is chopped by a proprietary chopper 0 to 20mA, or 4 to 20mA
circuit. Isolation is provided by transformer coupling, again using a proprietary
• 1500Vrms Transformer Isolation
technique to suppress transmission of common mode spikes or surges.
• ANSI/IEEE C37.90.1 Transient Protection
Transducer excitation is provided from the module by a stable 10V source. This
source is fully isolated, allowing the amplifier inputs to operate over the full range • Input Protected to 240VAC Continuous
of the excitation voltage. This feature enables the module to be interfaced to a • True 3-Way Isolation
wide variety of sensors requiring exctitation. • Wide Range of Supply Voltage
Module output is either voltage or current. For current output models a dedicated • 100dB CMR
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal • Fully Isolated Excitation Supply
4 (-OUT). The system-side load may be either floating or grounded.
• ±0.03% Accuracy
Special input circuits provide signal input and excitation protection against
• ±0.01% Linearity
accidental connection of power-line voltages up to 240VAC and against transient
events as defined by ANSI/IEEE C37.90.1. Protection circuits are also present on • Easily Mounts on Standard DIN Rail
the signal output and power input terminals to guard against transient events and • C-UL-US Listed
power reversal. Signal and power lines are secured to the module using screw
• CE and ATEX Compliant
terminals which are in pluggable terminal blocks for ease of system assembly and
reconfiguration.
situations where fine-tuning is desired. The adjustments are made using
The modules have excellent stability over time and do not require recalibration, potentiometers located under the front panel label and are non-interactive for ease
however, zero and span settings are adjustable up to ±5% to accommodate of use.
DSCA
Stability
Input Offset ±5µV/°C 4. 0 to 20mA E DSCA43-11E
Output Offset ±6ppm/°C (VOUT), ±20ppm/°C (IOUT)
Gain ±55ppm/°C
Output Noise, 100kHz Bandwidth 750µVrms (VOUT), 3µArms (IOUT)
Bandwidth, –3dB 3kHz
NMR 100dB/Decade Above 3kHz
Response Time, 90% Span 170µs
Power Supply
Voltage 19 to 29VDC
Current 60mA (VOUT), 80mA (IOUT)
Sensitivity +0.0002%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 Installation Notes:
or -35x15 rail 1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
NOTES:
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
(1) Includes linearity, hysteresis and repeatability.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA45
Frequency Input Signal Conditioners
Description
Each DSCA45 frequency input module provides a single channel of frequency
input which is isolated and converted to a standard analog voltage or current
Features
output (Figure 1). • Accepts Frequency Inputs of 0 to 100kHz
The frequency input signal can be a TTL level or zero-crossing signal. Terminal • Industry Standard Output of 0 to +10V,
7 (-IN) on the field-side terminal block is the “common” or ground connection for 0 to 20mA, or 4 to 20mA
input signals. A TTL signal is connected from terminal 6 (+IN) to terminal 7 (-IN), • ±0.05% Factory Calibrated Accuracy
while a zero-crossing signal is connected from terminal 5 (+EXC) to terminal 7
(-IN). Input circuitry for each of the signal types has hysteresis built in. An input • Adjustable Zero (±5%) and Span (±5%)
signal must cross entirely through the hysteresis region in order to trigger the • 1500Vrms Transformer Isolation
threshold comparator. • Input Overload Protected to 240VAC
A +5.1V excitation is available for use with magnetic pick-up or contact-closure Continuous
type sensors. The excitation is available on terminal 8 (-EXC) with return at • 120dB CMR
terminal 7 (-IN).
• ANSI/IEEE C37.90.1 Transient Protection
Module output is either voltage or current. For current output models a dedicated • Mounts on Standard DIN Rail
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal
4 (-OUT). The system-side load may be either floating or grounded. • C-UL-US Listed
• CE and ATEX Compliant
Special input circuits provide protection against accidental connection of power-
line voltages up to 480VAC and against transient events as defined by ANSI/
IEEE C37.90.1. Protection circuits are also present on the signal output and
power input terminals to guard against transient events and power reversal.
Signal and power lines are secured to the module using screw terminals which
are pluggable terminal blocks for ease of system assembly and reconfiguration.
date situations where fine tuning is desired. The adjustments are made using
DSCA45 modules have excellent stability over time and do not require potentiometers located under the front panel label and are non-interactive for
recalibration, however, both zero and span settings are adjustable to accommo- ease of use.
DSCA
Rejection (50-60Hz Common Mode) 120dB
Response Time (0 to 90%)
DSCA45-01, -02, -03 310ms, 175ms, 50ms
DSCA45-04, -05, -06 30ms, 30ms, 15ms
DSCA45-07, -08 15ms, 1.5ms
Field Excitation +5.1V ±5% at 8mA max
Power Supply
Voltage 19 to 29VDC
Current 60mA (VOUT), 80mA (IOUT)
Sensitivity ±0.0002%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN50022-35x7.5
or -35x15 rail
NOTES: Installation Notes:
(1) Includes linearity, hysteresis and repeatability. 1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA47
Linearized Thermocouple Input Signal Conditioners
Description
Each DSCA47 thermocouple input module provides a single channel of thermo-
couple input which is filtered, isolated, amplified, linearized, and converted to a
Features
high-level voltage output. Signal filtering is accomplished with a five-pole filter • Interfaces to Types J, K, T, E, R, S, B, and N
which provides 85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An Thermocouples
anti-aliasing pole is located on the field side of the isolation barrier, and the other • Linearizes Thermocouple Signal
four poles are on the system side. After the initial field-side filtering, the input
signal is chopped by a proprietary chopper circuit. Isolation is provided by • Industry Standard Output of 0 to +10V,
transformer coupling, again using a proprietary technique to suppress transmis- 0 to 20mA, or 4 to 20mA
sion of common mode spikes or surges. • 1500Vrms Transformer Isolation
The DSCA47 can interface to eight industry standard thermocouple types: J, K, T, • ANSI/IEEE C37.90.1 Transient Protection
E, R, S, B and N. Each module has cold junction compensation to correct for • Input Protected to 240VAC Continuous
parasitic thermocouples formed by the thermocouple wire and input screw termi-
nals on the module. Upscale open thermocouple detection is provided by internal • True 3-Way Isolation
circuitry. Downscale indication can be implemented by installing a 47MW, ±20% • Wide Range of Supply Voltage
resistor between screw terminals 6 and 8 on the input terminal block. • 160dB CMR
Module output is either voltage or current. For current output models a dedicated • 85dB NMR at 60Hz, 80dB at 50Hz
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal
4 (-OUT). The system-side load may be either floating or grounded. • ±0.08% Accuracy
• Easily Mounts on Standard DIN Rail
Special input circuits provide protection against accidental connection of power-
line voltages up to 240VAC and against transient events as defined by ANSI/ • C-UL-US Listed
IEEE C37.90.1. Protection circuits are also present on the signal output and • CE and ATEX Compliant
power input terminals to guard against transient events and power reversal.
Power lines are secured to the module using screw terminals which are in
pluggable terminal blocks for ease of system assembly and reconfiguration.
situations where fine-tuning is desired. The adjustments are made using
The modules have excellent stability over time and do not require recalibration, potentiometers located under the front panel label and are non-interactive for
however, zero and span settings are adjustable up to ±3% to accommodate ease of use.
DSCA
Bandwidth, –3dB 3Hz DSCA47B-11 B +500°C to +1800°C 2, 3, 4 ±0.15% ±1.95° C
NMR 95dB at 60Hz, 85dB at 50Hz (+932°F to +3272°F)
Response Time, 90% Span 165ms
Open Input Response Upscale DSCA47N-15 N –100°C to +1300°C 2, 3, 4 ±0.08% ±1.12° C
Open Input Detection Time <5s (–148°F to +2372°F)
Power Supply
Voltage 15 to 30VDC †
Current 25mA (VOUT), 55mA (IOUT)
Output Ranges Available
Sensitivity ±0.0001%/%
Protection Output Range Part No. Suffix Example
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
1. –10V to +10V NONE N/A
2. 0V to +10V NONE DSCA47J-01
Environmental 3. 4 to 20mA C DSCA47J-01C
Operating Temperature Range –40°C to +80°C
Storage Temperature Range –40°C to +80°C 4. 0 to 20mA E DSCA47J-01E
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
‡
Radiated, Conducted Class A Thermocouple Alloy Combinations
Immunity EN61000-6-2 ISM, Group 1 Standards: DIN IEC 584, ANSI MC96-1-82, JIS C 1602-1981
RF Performance A ±0.5% Span Error
ESD, EFT Performance B Type Material
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm) J Iron vs. Copper-Nickel
K Nickel-Chromium vs. Nickel-Aluminum
Mounting DIN EN 50022 -35x7.5 T Copper vs. Copper-Nickel
or -35x15 rail E Nickel-Chromium vs. Copper-Nickel
NOTES: R Platinum-13% Rhodium vs. Platinum
(1) Includes conformity, hysteresis, repeatability, and CJC error. S Platinum-10% Rhodium vs. Platinum
B Platinum-30% Rhodium vs. Platinum-6% Rhodium
Installation Notes: N Nickel-14.2% Chromium-1.4% Silicon vs. Nickel-4.4%
Silicon- 0.1% Magnesium
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA49
Voltage Output Signal Conditioners
Description
Each DSCA49 voltage output module provides a single channel of analog
output. The input signal is buffered, isolated, filtered and converted to a voltage Features
output. Signal filtering is accomplished with a five-pole filter which provides • Accepts High-Level Voltage Input
100dB per decade of attenuation above 1kHz. An anti-aliasing pole is located
• Provides High-Level Voltage Outputs to
on the system side of the isolation barrier, and the other four poles are on the
±10V at 50mA
field side. After the initial system-side filtering, the input signal is chopped by a
proprietary chopper circuit. Isolation is provided by transformer coupling, again • ANSI/IEEE C37.90.1
using a proprietary technique to suppress transmission of common mode spikes • 1500Vrms Transformer Isolation
or surges.
• ±0.05% Accuracy
Special output circuits provide protection against accidental connection of • ±0.02% Linearity
power-line voltages up to 240VAC and against transient events as defined by
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal input and • Output Protected to 240VAC Continuous
power input terminals to guard against transient events and power reversal. • True 3-Way Isolation
Signal and power lines are secured to the module using screw terminals which
• Wide Range of Supply Voltage
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
• 110dB CMR
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate • Easily Mounts on Standard DIN Rail
situations where fine-tuning is desired. The adjustments are made using • C-UL-US Listed
potentiometers located under the front panel label and are non-interactive for • CE and ATEX Compliant
ease of use.
DSCA
Power Supply
Voltage 19 to 29VDC
Current 80mA
Sensitivity ±0.0003%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temperature Range –40°C to +80°C
ATEX Group II, Category 3 –40°C to +75°C
Storage Temperature Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13”
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5
NOTES:
(1) Includes linearity, hysteresis and repeatability.
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
PWR-PS5R Series
Switching Power Supplies
Description Features
Dataforth’s new PWR-PS5R series sets new standards for switching power • Universal AC Input (85 to 264VAC)
supply technology. Combining rugged, compact enclosures, incorporating all
international standards and approvals, and offering customers a broad selection • DC Compatible Input (105 to 370VDC)
of inputs and outputs, the PWR-PS5R series makes your power supply choice • Unique Spring-Up Terminals
a simple one. The PWR-PS5R series is UL, C-UL and TUV Approved, CE • DIN Rail or Panel Mount
Compliant, and UL 508 Listed. Models are available with output ratings from
7.5W to 100W with 24VDC output voltages. Customers may choose from a very • Five Different Output Capacities: 7.5W to 100W
wide range of input voltages (85 to 264VAC, and 105 to 370VDC compatible), • UL, C-UL, and TUV Approvals
making the PWR-PS5R series an unbeatable package of versatility.
• CE Compliant, UL 508 Listed
• Certified to EN60950
• IP20 Protection (EN60529)
• Compliant with EMC Directives EN50081-2 and
EN50082-2
Specifications PWR-PS5R Series
Frequency 47 to 63Hz
Input Current 0.17A at 100V 0.3A at 100V 0.68A at 100V 1.15A at 100V 2.5A at 100V
0.11A at 200V 0.2A at 200V 0.45A at 200V 0.75A at 200V 1.5A at 200V
Output Voltage &
Current Ratings 24V, 0.3A 24V, 0.6A 24V, 1.3A 24V, 2.1A 24V, 4.2A
Temperature Change 0.05%
Ripple Voltage 2% p-p maximum (including noise)
Overcurrent Protection 105% minimum
Overvoltage Protection 120% minimum (Zener-limiting) 120% minimum, auto reset
Between input and output terminals: 3,000VAC, 1 minute
Dielectric Strength Between input terminals and housing: 2,000VAC, 1 minute
Between output terminal and housing: 500VAC, 1 minute
Insulation Resistance Between input and output terminals/input terminal and housing: 100MΩ minimum (500VDC megger)
Operating Temperature –10 to +60°C
StorageTemperature –30 to +85°C
Operating Humidity 20 to 90% RH (avoid condensation)
Dimensions 1.77" x 2.76" 1.77" x 3.74" 3.54" x 3.74" 3.54" x 3.74" 5.71" x 3.74"
(w x d) (45mm x 70mm) (45mm x 95mm) (90mm x 95mm) (90mm x 95mm) (145mm x 95mm)
All H = 2.95" (75mm)
Terminal Screw M3.5 Phillips screws in spring-up terminals
PWR-PS5RC/D
Front View Bottom View
Ordering Information
Model Power Output
2.95"
(75mm) 3.54"
PWR-PS5RA 7.5W 24VDC/0.3A (90mm)
PWR-PS5RB 15W 24VDC/0.6A
PWR-PS5RC 30W 24VDC/1.3A
PWR-PS5RD 50W 24VDC/2.1A 3.54"
(90mm)
PWR-PS5RE 100W 24VDC/4.2A 3.74"
(Consult factory for other model drawings.) (95mm)
DSCA
Module Dimensions
DSCA
SCMXRAIL1-XX/SCMXRAIL3-XX
Din Rail
Features
Dataforth’s new DSCL, DSCP, and SCTP series of products is a complete family • Full Family of Loop Isolators and Transmitters
of loop and universal AC/DC powered models of isolators and transmitters in
component, DIN and head-mount packages. They include basic loop-powered • Signal-Powered Passive Loop Isolator Models
isolators, wide-range AC/DC powered isolators and transmitters, and fixed-gain • Wide Range 24 to 60V or 85 to 230V AC/DC-
or hardware and software configurable models. Depending on the model, they Powered Models
accept a wide range of voltage, current, thermocouple, or RTD signals • Jumper and Software Configurable Models
then filter, isolate, amplify, linearize, and convert these input signals to
high-level analog outputs suitable for use in data acquisition, test and • 6.2mm Dip-switch Configurable Models
measurement, and control systems. They protect valuable measurement and • 4000Vrms Isolation
control signals as well as connected equipment from the dangerous and
• Multiple Channels per Package Available
degrading effects of noise, transient power surges, internal ground loops, and
other hazards present in industrial environments. • PCB, DIN Rail, Panel, and Instrument Head
Mounting Options
• No Recalibration or Maintenance Required
• Fault Detection of Input Signal Available
• CE Compliant
• Manufactured per RoHS Directive 2002/95/EC
DSCL20
Loop Powered Isolator - “Component Module”
Description
Each DSCL20 loop powered isolator provides a single channel of analog signal
protection by electrically isolating its input from output for any DC process Features
signal in the range of 0-20mA (or 4-20mA). The DSCL20 operates passively, • No Power Supply Required, Signal Powered
obtaining its power from the transmitted signal (see Figure 1). From 0-20mA (or 4-20mA) Input
The input signal is chopped by a proprietary DC chopper circuit, isolation is • Simplified Wiring, Easy to Install Plug-In
provided by transformer coupling, a proprietary technique is used to suppress Accessories
transmission of common mode spikes or surges, and the output signal from • Small OEM Modular Package Ideal for
the secondary of the transformer is reconstructed to the original input signal. PCB Mounting
• I/O Packaging for Vertical or Horizontal
Mounting
• 500Vrms Transformer Isolation
• Prevents Ground-Loop Problems
• Prevents the Transfer of Interference Voltages
and Currents
• High Accuracy Over Full Span
• CE Compliant
DSCL21
Loop Powered Isolator - DIN Mount
Description
Each DSCL21 loop powered isolator provides a single channel of analog
signal protection by electrically isolating its input from output for any DC process
Features
signal in the range of 0-20mA (or 4-20mA). The DSCL21 operates passively, • No Power Supply Required, Signal Powered
obtaining its power from the transmitted signal (see Figure 1). from 0-20mA (or 4-20mA) Input
The input signal is chopped by a proprietary DC chopper circuit, isolation is • Simplified Wiring for Fast Installation
provided by transformer coupling, a proprietary technique is used to suppress • Narrow 12.5mm DIN Package for
transmission of common mode spikes or surges, the output signal from the High-Density Mounting
secondary of the transformer is reconstructed to the original input signal.
• No Recalibration or Maintenance Required
• 500Vrms Transformer Isolation
• Prevents Ground-Loop Problems
• Prevents the Transfer of Interference Voltages
and Currents
• High Accuracy Over Full Span
• CE Compliant
+ 4
The DSCL21 DIN mount package accepts EN50022 (35 x 7.5) and EN50035 (G32)
type rails; Dataforth SCMXRAIL1-xx or SCMXRAIL2-xx. Multiple DSCL21 modules
may be mounted next to each other without affecting input or output signals.
Screw terminals with wire protection clamps sized for 0.2 to 4mm 2 solid or 0.2 to
DSCL
2.5mm 2 stranded wires. The DSCL21 may be mounted in any position. The DSCL21
requires no maintenance.
DSCL22
Loop Powered Isolator - DIN or Panel Mount
Description
Features
Each DSCL22 loop powered isolator provides 1, 2, or 3 channels of analog • No Power Supply Required, Signal Powered
signal protection by electrically isolating its input from output for any DC process from 0-20mA (or 4-20mA) Input
signal in the range of 0-20mA (or 4-20mA). The DSCL22 operates passively,
obtaining its power from the transmitted signal (see Figure 1). • Simplified Wiring For Fast Installation
• DIN Rail or Panel Mountable
The input signal is chopped by a proprietary DC chopper circuit, isolation is
provided by transformer coupling, a proprietary technique is used to suppress • Narrow DIN Package, Mounts up to 27
transmission of common mode spikes or surges, and the output signal from the Devices into a 19” Rack Space
secondary of the transformer is reconstructed to the original input signal. • No Recalibration or Maintenance Required
If one input to two isolated outputs is desired, multiple channel units may be • Up to 4000Vrms Transformer Isolation
configured as a splitter (see Figure 2).
• Prevents Ground-Loop Problems
• Prevents the Transfer of Interference Voltages
and Currents
• High Accuracy Over Full Span
• CE Compliant
NOTES:
(1) Additional error <0.05% per 100Ω above 250Ω
(2) Vin=IORL + <2.6V
DSCL
to each other without affecting input or output signals. The DSCL22 may be
mounted in any position.
Screw terminals with wire protection clamps sized for 2 x 0.75mm 2 or 1 x
2.5mm 2 wires. The DSCL22 requires no maintenance.
DSCL23
4 to 20mA Isolator with DC Supply - DIN or Panel Mount
Description
Each DSCL23 loop powered isolator provides 1 or 2 channels of analog signal
protection by electrically isolating its input from output for any DC process signal
Features
in the range 4-20mA. The DSCL23 feeds isolated DC power to the field • Feeds DC Power to 4 to 20mA Transmitter,
transmitter and returns a fully isolated 4-20mA analog signal (see Figure 1). Isolates Loop
The input signal is chopped by a proprietary DC chopper circuit, isolation is • Simplified Wiring for Quick Install and
provided by transformer coupling, a proprietary technique is used to suppress Signal Protection
transmission of common mode spikes or surges, and the output signal from the • DIN Rail or Panel Mountable
secondary of the transformer is reconstructed to the original input signal.
• Narrow DIN Package, Mounts up to
27 Devices into a 19” Rack Space
• No Recalibration or Maintenance Required
• 2300Vrms Transformer Isolation
• Prevents Ground-Loop Problems
• Prevents the Transfer of Interference Voltages
and Currents
• High Accuracy Over Full Span
• CE Compliant
DSCL
DSCL23
NOTES:
*Same specification as DSCL23-01
(1) At connection between isolator and Power Supply
(2) At connection between isolator and 2-Wire Transmitter.
DSCL
of process current or voltage inputs and outputs. A unique snap-in tool allows
Features
quick extraction of the module’s circuit board to permit the user to reposition four • Uses Universal Power Supply of 24 to 60V or
(4) jumpers and reconfigure each module’s I/O. The factory default setting 85 to 230V AC/DC
provides 4-20mA input and output current. • Configuration Jumpers Allows up to 36 I/O
Each module provides full 3-way isolation with 2300Vrms CMV input to output Settings
and 3700Vrms CMV power supply to I/O protection. Two module versions are • Three-Way Isolation for 2300Vrms Protection
offered that accept universal power supply of either 24 to 60VDC or AC and 85
to 230VDC or AC with the alternating current usage accepting 45 to 400Hz • Prevents Ground-Loop Problems
power. • Prevents the Transfer of Interference Voltages
and Currents
• High Accuracy Over Full Span
• No Recalibration or Maintenance Required
• Narrow DIN Package, Mounts up to 27
Devices into a 19” Rack Space
• DIN Rail or Panel Mountable
• CE Compliant
Specifications Typical at TA=+25°C and 24VDC or 230VAC ±10% supply voltage Ordering Information
Module DSCL24-01,-02 Model Input (default(1)) Output (default(1)) Power Supply
(1)
Input Range 0/4-20mA, ±20mA, 2-10V, 0-10V, ±10V DSCL24-01 4-20mA 4-20mA 24-60VDC/AC
Input Limit (Iin) 50mA, ±50mA DSCL24-02 4-20mA 4-20mA 85-230VDC/AC
Input Limit (Vin) 40V, ±40V
CMV Input to Output 2300Vrms, 1 min.
CMV Power Supply to I/O 3700Vrms, 1 min.
Accuracy (at 250Ω Load) ±0.1% Span Typical
±0.2% Span Max
Input Resistance 15Ω Current Mode, 100kΩ Voltage Mode
Linearity Included in Accuracy
Table 1: Select Output Voltage or Current
Stability <100ppm/°C
Input Overshoot <20µA (Typical 5µA)
Output Range(1) 0/4-20mA, ±20mA, 2-10V, 0-10V, ±10V
Output Limit (Iout) 20mA, ±20mA
Output Limit (Vout) 10V, ±10V
Limit Upper Range 40mA
Bandwidth, –3dB 15Hz
CMR (50Hz or 60Hz) 110dB
NMR 16dB at 50/60 Hz
Response Time 30ms, to 90% Span
Load Resistance Range ≤600Ω Current Mode, ≥2kΩ Voltage Mode
Output Noise <0.5% p-p
Power Supply
Voltage (24 to 60) or (85 to 230)VDC/AC at 45-400Hz
Tolerance DC –15% to +33%, AC ±15%
Power consumption DC ≤1.2W, AC ≤3VA
Environmental Weight Approximately 180g
Table 2: Select Voltage or Current Ranges
Housing Material Lexan 940 (UL 94 V-O)
Shock Test 50g (3 Shocks, 6 Axis)
Operating Temp. Range –25°C to +55°C
Storage Temp. Range –40°C to +70°C
Relative Humidity 0 to 75% Noncondensing
Emissions EN50081-2 (Radiated, Conducted)
Immunity EN50082-2 (ESD, RF, EFT)
NOTES:
(1) Thirty-six unique I/O ranges are jumper configurable. See Tables 1 & 2 for configuration options.
DSCL
Configuration Guide
NOTE: B1 through B6 Jumpers marked on PC board
The default setting of factory stock modules is 4 to 20mA for both module input
and output, that is, jumpers are inserted in positions B1 and B4 designating
4-20mA input and jumpers ST4 and ST3 are in position for current output.
However, the output can be user reconfigured for an alternative voltage or
current signal by inserting the plug-in jumpers ST4 and ST3 in the appropriate
positions shown in table 1.
Connection Guide
Jumpers B1 to B6 (table 2) are used for selecting the standard configurable ranges.
Providing that the ‘Span’ and ‘Zero’ potentiometers are not adjusted, changing the
range has no effect on the modules’ accuracy. The ‘Span’ and ‘Zero’ allow ±10%
adjustments.
Dimensions
DSCL24 (Multi-Channel)
Factory Configurable Isolator - DIN or Panel Mount
Description
Each multi-channel DSCL24 module provides up to 252 different configurations
of process current or voltage inputs and outputs. The factory default setting
Features
provides 4-20mA input and output current. Alternatively, users may complete • Uses Universal Power Supply of 24 to 60V or
and submit a specific configuration table that instructs the factory on how to 85 to 230V AC/DC
solder in configuration jumpers. • Factory Configured Soldered Jumpers Allows
Each module provides full 3-way isolation with 2300Vrms CMV input to output up to 250+ I/O Settings
and 3700Vrms CMV power supply to I/O protection. Two module versions are • Three-Way Isolation for 2300Vrms Protection
offered that accept universal power supply of either 24 to 60VDC or AC and 85
to 230VDC or AC with the alternating current usage accepting 45 to 400Hz • Prevents Ground-Loop Problems
power. • Prevents the Transfer of Interference Voltages
and Currents
• High Accuracy Over Full Span
• No Recalibration or Maintenance Required
• Narrow DIN Package, Mounts up to 27
Devices into a 19” Rack Space
• DIN Rail or Panel Mountable
• CE Compliant
DSCL
Specifications Typical at TA=+25°C and 24VDC or 230VAC ±10% supply voltage Table 1: Configuration Checklist
Module DSCL24-11,-12 Input Current (mA) Chn 1 Chn 2
0 to 0.1
Input Range(1) 4-20mA 0 to 0.2
Input Limit 40mA, ±40mA 0 to 0.5
CMV Input to Output 2300Vrms, 1 min.
0 to 1
CMV Power Supply to I/O 3700Vrms, 1 min.
Accuracy (at 250Ω Load) ±0.1% Span Typical, ±0.2% Span Max 0 to 2
Input Resistance 15Ω Current Mode 0 to 5
Linearity Included in Accuracy 0 to 10
Stability <100ppm/°C
0 to 20
Input Overshoot <20µA (Typical 5µA)
0.2 to 1
Output Range(1) 4-20mA 1 to 5
Limit Upper Range 40mA
2 to 10
Bandwidth, –3dB 15Hz
CMR (50Hz or 60Hz) 110dB 4 to 20
NMR 16dB at 50/60Hz -0.1 to 0.1
Response Time 30ms, to 90% Span -0.2 to 0.2
Load Resistance Range ≤600Ω Current Mode -0.5 to 0.5
Output Noise <0.5% p-p
-1 to 1
Power Supply -2 to 2
Voltage (24 to 60) or (85 to 230)VDC/AC at 45-400Hz -5 to 5
Tolerance DC –15% to +33%, AC ±15%
-10 to 10
Power Consumption DC ≤1.6W, AC ≤3.4VA
-20 to 20
Environmental Weight Approximately 180g. Input Voltage (V) Chn 1 Chn 2
Housing Material Lexan 940 (UL 94 V-O)
0 to 0.1
Shock Test 50g (3 Shocks, 6 Axis)
Operating Temp. Range –25°C to +55°C 0 to 0.2
Storage Temp. Range –40°C to +70°C 0 to 0.5
Relative Humidity 0 to 75% Noncondensing 0 to 1
Emissions EN50081-2 (Radiated, Conducted)
0 to 2
Immunity EN50082-2 (ESD, RF, EFT)
0 to 5
NOTES: 0 to 10
(1) 250+ unique I/O ranges are factory configurable. See Table 1 for configuration options. 0 to 20
0 to 40
0.2 to 1
Configuration Options
1 to 5
The default setting of factory stock modules is 4 to 20mA for both module input 2 to 10
and output. 4 to 20
-0.1 to 0.1
Alternatively, users may complete and submit Table 1 specifics that the factory
-0.2 to 0.2
will use to apply solder-in jumpers configuring the module as desired.
-0.5 to 0.5
NOTE: Modules once configured for a specific user I/O range cannot be -1 to 1
subsequently reconfigured. -2 to 2
-5 to 5
Factory Configuration -10 to 10
Check-mark the desired Input and Output range for each channel in the table at -20 to 20
right. Copy and submit this configuration sheet with your purchase order. The Output Current (mA) Chn 1 Chn 2
factory will assign a DSCL24-xxxx part number to your specific configuration. 0 to 20
This part number may be used on subsequent orders. The ‘Span’ and ‘Zero’ 4 to 20
potentiometers allow ±10% adjustments beyond the following factory solder -20 to 20
jumper settings. Output Voltage (V) Chn 1 Chn 2
0 to 10
2 to 10
-10 to 10
DSCL
DSCP20
Programmable 2-Wire Temperature Transmitter, DIN Mount
Description
Each DSCP20 2-wire transmitter is designed for measuring temperature using
thermocouples or RTDs. The input type, measurement range, and other
Features
features are software configurable. A PC, the DSCX-887 and DSCX-416 • Low-Cost Non-Isolated 4-20mA Transmitter
interface cables, and the DSCX-895 configuration software are required to • No Power Supply Required, Powered
configure the transmitter. Communication is serial RS-232C. from Output Loop Current
The DSCP20 can interface to 12 industry standard thermocouple types: J, K, T, • Interfaces to All Standard Thermocouples
E, R, S, B, N, L, U, C, and D. Cold junction compensation is selectable as either and RTDs
internal or external. Three RTD types, Pt 100, Ni 100, and Cu 50* can be
• Software Configurable Input Type and Range
interfaced in a two, three or four wire connection. All inputs are linearized using
up to 23 points of interpolation, and total errors are less than ±0.2%. • Open and Short-Circuit Input Detection
Other configurable features include: zero point and input range adjustment, • Configurable with or without Output Loop
output response for open or short-circuit sensor or cable failure, normal or Power Connected
inverted output, ripple suppression for 50Hz or 60Hz, and output time response. • Mounts on Standard DIN Rail
The DSCX-895 configuration software allows query, print-out and saving of
• –25°C to +80°C Operating Temperature
configuration settings, display of input measurement value, and display of
interpolation table points. • CE Compliant
*Call factory for Cu RTD information.
(see Electrical
Connections
on page 240 for
connection details)
The following grounding condition must be observed when pro- Thermocouple Type and Material
gramming the instrument.
Type Material
If one of the power supply or input wires is grounded to earth, a PC
B Pt30Rh-Pt6Rh
without an earth connection must be used when programming E NiCr-CuNi
(e.g. a Laptop running on batteries). J Fe-CuNi
K NiCr-Ni
Under no circumstances should a PC be used running from a L Fe-CuNi
N NiCrSi-NiSi
power supply with an earth connection, as this will damage the R Pt13Rh-Pt
module. S Pt10Rh-Pt
T Cu-CuNi
U Cu-CuNi
C W5 Re/W26 Re
D W3 Re/W25 Re
DSCP
(1): Load Resistance: RL(max) = Loop Supply (V) – 12V RTD 2L active – 2 2.5 3 5 9.5 17.5 33.5
IOUTPUT(max)
RTD 3L, 4L active active 2 2.5 4 6.5 11.5 21 40.5
RTD 2L, 3L, 4L off off 1.5 2.5 3.5 7.5 14 26.5 50.5
†
Additional Errors
Low Measuring Range
Resistance Thermometer
(<200°C Span) ±0.015% Span Typ., ±0.05% Span max
Thermocouples (<500°C Span) ±0.015% Span Typ., ±0.05% Span max
NOTE A NOTE B
NOTE A: Minimum span is 15Ω when the end value(3) is less than or equal to 400Ω.
Minimum span is 150Ω when the end value(3) is greater than 400Ω and not exceeding 4000Ω.
The ratio of the min value to the span must be less than or equal to 10.
NOTE B: Range of span is 2mV minimum to 80mV maximum. The ratio of the min value to the span must be less than or equal to 10.
NOTE (1): W5 Re W26 Re (ASTM E 988-90)
NOTE (2): W3 Re W25 Re (ASTM E 988-90)
NOTE (3): For two-wire connections, the end value is made up of the measured end value (Ω) plus the total resistance of the leads.
Electrical Connections
Example of the set-up for programming a DSCP20 without the power supply.
For this case the switch on the interface must be set to “ON’.
Dimensions
DSCP
Dimensions: inches (millimeters)
DSCP20 Clipped onto a Top-Hat Rail EN 50-022-35 x 7.5 DSCP20 Clipped onto a Rail “G” EN 50-035-G32
DSCP55
Pt100, Ni100/Loop-Powered Converter
Description
Each DSCP55 RTD Loop-Powered Converter provides a single channel of RTD
input which is amplified, linearized and converted to a highlevel 4 to 20mA or 20
Features
to 4mA output. Inputs may be connected by 2, 3, or 4 wires and measurement • Input: Pt100 (–200°C to + 650°C)
range may be configured by dip-switch. Ni100 (–60°C to + 250°C)
• Output: Current (4 to 20 or 20 to 4mA)
• Spring Cage Clamp Connection
• 16-Bit Resolution
• Better than ±0.1% Accuracy
• Configuration by Dip-Switch
• Compact 6.2mm DIN Housing
• CE Compliant
DSCP
DSCP61
Pt100-to-DC Current/Voltage Converter
Description
Each DSCP61 RTD Pt100 Converter provides a single channel of RTD input
which is amplified, linearized and converted to a high-level current or voltage
Features
output. Inputs may be connected by 2, 3, or 4 wires and measurement range may • Input: Pt100 (2, 3, 4 wires, –150°C to +650°C)
be configured by dip-switch to cover a range of –150°C to +650°C. Power can • Output Current: 0 to 20, 4 to 20, 20 to 0, 20 to 4mA
be applied directly to the converter’s terminals or through a DIN rail mounted bus
connector accessory, eliminating the need to wire power to each individual • Output Voltage: 0 to 5, 1 to 5, 0 to 10, 10 to 0VDC
converter. • 1500Vrms Galvanic Isolation, 3-Way
• 19.2 to 30VDC Power
• Spring Cage Clamp Connection
• 14-Bit Resolution
• Better than ±0.1% Accuracy
• Configuration by Dip-Switch
• Compact 6.2mm DIN Housing
• CE Compliant
DSCP
DSCP62
Thermocouple-to-DC Current/Voltage Converter with Relay Output
Description
Each DSCP62 Thermocouple Converter provides a single channel of
thermocouple input which is amplified, linearized and converted to a high-level Features
current or voltage output. Thermocouple type, measurement range, filter, • Input: Thermocouple types J, K, E, N, S, R, B, T
output type and range, and fault indication may be configured by dip-switch. An • Output Current: 0 to 20, 4 to 20, 20 to 0, 20 to 4mA
auxiliary relay output is provided to generate an alarm or act as a ther-mostat.
Power can be applied directly to the converter’s terminals or through a DIN rail • Output Voltage: 0 to 5, 1 to 5, 0 to 10, 10 to 0VDC
mounted bus connector accessory, eliminating the need to wire power to each • Auxiliary Relay for Alarm or Control
individual converter.
• 1500Vrms Galvanic Isolation, 3-Way
• 14-Bit Resolution
• Configuration by Dip-Switch
• CE Compliant
DSCP
DSCP63
DC Voltage/Current Converter
Description
Each DSCP63 Voltage/Current Converter provides a single channel of voltage
Features
or current input which is converted to a voltage or current output. It is designed
for industrial standard voltage or current signals. Input/output range, filter, fault • Input Voltage: 0 to 5, 0 to 10, 0 to 15, 0 to 30,
indication, square root function and other functions may be configured by 1 to 5, 2 to 10VDC
dip-switch. Power can be applied directly to the converter’s terminals or • Input Current: 0 to 20, 4 to 20mA
through a DIN rail mounted bus connector accessory, eliminating the need to
wire power to each individual converter. • Output Voltage: 0 to 5, 0 to 10, 1 to 5, 2 to 10VDC
• Output Current: 0 to 20, 4 to 20, 20 to 0, 20 to 4mA
• 1500Vrms Galvanic Isolation, 3-Way
• 19.2 to 30VDC Power
• Spring Cage Clamp Connection
• 14-Bit Resolution
• Better than ±0.1% Accuracy
• Configuration by Dip-Switch
• Compact 6.2mm DIN Housing
• CE Compliant
DSCP
DSCP64
DC Voltage/Current Converter with Transducer Power Supply
Description
Each DSCP64 Voltage/Current Converter provides a single channel of voltage Features
or current input which is converted to a current or voltage output. An auxiliary
• Input Voltage: 0 to 5, 0 to 10, 1 to 5, 2 to 10VDC
power supply is provided for powering the input transducer/sensor. It is
designed for industrial standard voltage or current signals. Input/output range, • Input Current: 0 to 20, 4 to 20mA
filter, fault indication, square root function and other functions may be configured • Output Voltage: 0 to 5, 0 to 10, 1 to 5, 2 to 10VDC
by dip-switch. Power can be applied directly to the converter’s terminals or • Output Current: 0 to 20, 4 to 20, 20 to 0, 20 to 4mA
through a DIN rail mounted bus connector accessory, eliminating the need to
• 1500Vrms Galvanic Isolation, 4-Way
wire power to each individual converter.
• 19.2 to 30VDC Power
• Spring Cage Clamp Connection
• 14-Bit Resolution
• Better than ±0.1% Accuracy
• Configuration by Dip-Switch
• Compact 6.2mm DIN Housing
• CE Compliant
DSCP
DSCP65
DC Low Voltage Converter
Description
Each DSCP65 Low Voltage Converter provides a single channel of low voltage Features
input which is converted to a current or voltage output. It is designed for
• Input Voltage: 25mV to 2VDC in 15 Settable Steps
industrial standard voltage or current signals. Input/output range, filter, fault
indication, and other functions may be configured by dip-switch. Power can be • Output Voltage: 0 to 5, 1 to 5, 0 to 10, 2 to 10VDC
applied directly to the converter’s terminals or through a DIN rail mounted bus • Output Current: 0 to 20, 4 to 20, 20 to 0, 20 to 4mA
connector accessory, eliminating the need to wire power to each individual • 1500Vrms Galvanic Isolation, 3-Way
converter.
• 19.2 to 30VDC Power
• Spring Cage Clamp Connection
• 14-Bit Resolution
• Better than ±0.1% Accuracy
• Configuration by Dip-Switch
• Compact 6.2mm DIN Housing
• CE Compliant
DSCP
DSCP70
Power Supply Connection Module for DIN Rail Power Bus
Description
Each DSCP70 Power Supply Connection Module permits the delivery of power
Features
to DSCP6x modules through DIN rail mounted power-bus connectors. An
external power supply, or supplies for redundant operation, are connected to • Delivers Power to DSCP6x Modules Via DIN Rail
the terminals of the DSCP70. The DSCP70 then routes the power to the DIN • Two Independent Inputs Allow Redundant Power
rail power-bus, provides protection against power supply reversal, provides • LED Indication of Power Supply Presence
LED status indication of correct power, inverted power connection and presence
• LED Indication of Reversed Power Connection
of AC, and provides over-voltage protection.
• 19.2 to 30VDC Power
• Spring Cage Clamp Connection
• Compact 6.2mm DIN Housing
• CE Compliant
DSCP
DSCP81
Configurable Voltage/Current Input Signal Conditioner, DIN Mount
Description
Each isolated DSCP81 signal conditioner is designed for measuring voltages up
to ±1000VDC and currents up to ±100mA. The input type, measurement range,
Features
and other features are software configurable. A PC with RS-232C serial port, • Interfaces to Voltages up to ±1000VDC and
the DSCX-787 and DSCX-587 interface cables, and the DSCX-557 configura- Currents up to ±100mA
tion software are required to program the DSCP81. • Software Configurable Input Type and Range
The DSCP81 can interface to either a current or voltage input and provide a • Software Configurable Filter
current or voltage output. The input filter characteristics, input and output
ranges, input signal linearization, signal inversion, and optional alarm relay • 3700Vrms Transformer Isolation
output are all software configurable by the user. The input signal may be • Supply Voltage of 24 to 60VDC/AC or 85 to
linearized using up to 50 points of interpolation. Optionally, the user may specify 230VDC/AC
all configurable parameters and request factory configuration. • Alarm Relay Output
Two models are available offering wide-range power supply connection: 24 to • Mounts on Standard DIN Rail
60VDC/AC, and 85 to 230VDC/AC. The DSCX-557 configuration software
• –25C to +55C Operating Temperature
allows query, print-out and saving of configuration settings, display of input
measurement value, and display of interpolation table points. • CE Compliant
Specifications Typical at TA=+25°C and 24VDC or 230VAC ±10% supply voltage Ordering Information
Module DSCP81 Model Input Range/Description Output Range
Input Range, Voltage –1000VDC to +1000VDC max, Configurable DSCP81-01 User Configurable User
Input Resistance 1MΩ (Vin≤±1.7V), (Standard Configuration(2)) V or I Input, Configurable
540kΩ (Vin>±1.7V to ≤±100V), 24 to 60VDC/AC Power V or I Output
5.5MΩ (Vin>±100V to ±1000V)
Input Range, Current –100mA to +100mA max, Configurable DSCP81-02 User Configurable User
Input Resistance 1kΩ (Iin=-1.5mA to +1.5mA), (Standard Configuration(2)) V or I Input, Configurable
15.4Ω (Iin=-100mA to +100mA) 85 to 230VDC/AC Power V or I Output
Output Range, Voltage –10V to +10V max, Configurable DSCP81-01-xxxx Factory Configured, Factory
V Limit Under Overload Approx. ±11V (Contact Factory(3)) 24 to 60VDC/AC Power Configured
Short Circuit Current ≤60mA V or I Output
External Resistance Rextmin (kΩ)≥Vev/10mA
Note: Vev=Output Voltage End Value DSCP81-02-xxxx Factory Configured, Factory
Output Range, Current –20mA to +20mA max, Configurable (Contact Factory(3)) 85 to 230VDC/AC Power Configured
Output Load Voltage 12V V or I Output
Current Limit Under Overload Approx. ±22mA
Open-Circuit Voltage <16V
External Resistance Rextmax (kΩ)=12V/Iev Accessories
Note: Iev =Output Current End Value
Output Ripple (Voltage or Current) <0.5% p-p Model Description
CMV, Input to Output & Relay 3700Vrms, 1 min. DSCX-787 PC Interface Cable
CMV, Power Supply to Input 3700Vrms, 1 min. DSCX-587 Module Interface Cable
& Output DSCX-557 Configuration Software
CMV, Power Supply to Relay 2300Vrms, 1 min.
CMV, Output to Relay 2300Vrms, 1 min.
Mains Ripple Suppression Configurable to 50 or 60Hz Table 1: Configurable Input Filter Settings
Input Filter Configurable, see Table 1 Response Time (63%) [s] Response Time(4) (99%) [s]
50Hz 60Hz 50Hz 60Hz
Accuracy(1) ±0.1% Span Typ., ±0.2% Span max.
Output Stability 100ppm/°C 0.04 0.03 0.08 0.07
0.06 0.05 0.17 0.14
Linearization Configurable; Linear, Custom, x1/2, x3/2, x5/2 0.10 0.08 0.36 0.30
0.18 0.15 0.72 0.60
Alarm Relay SPST Isolated Contact 0.34 0.28 1.5 1.2
Material Gold Flashed Silver Alloy 0.66 0.55 3.0 2.5
Contact Rating AC: ≤2A at 250V (500VA), 1.3 1.1 6.0 5.0
DC:≤2A at 125V (60W) 2.6 2.2 12 10
Mode of Action Configurable; Alarm and Power Loss 5.1 4.3 24 20
(see Table 2 Feature 6) 10.3 8.6 48 40
Trip Point Type Configurable; Inactive, Low, High 20.5 17 94 80
(see Table 2 Feature 7) 41 34 190 160
Trip Point Setting Configurable, –10 to 110% Input Span 82 68 380 315
(see Table 2 Feature 7) 160 140 750 630
Trip Point Hysteresis Configurable, 0 to 100% Input Span 330 270 1500 1260
(see Table 2 Feature 7)
DSCP
Energize/De-energize Delay Configurable, 0.01 to 1000s NOTES:
(see Table 2 Feature 8) (1) Includes linearity and repeatability errors at reference conditions.
Visible Alarm Front Panel Green LED flashes “ON” (2) Shipped as 4 to 20mA input, 4 to 20mA output, linearization = linear, input filter = 80ms,
ripple suppression = 60Hz, alarm function = inactive.
(3) Submit configuration form shown on page 243, and factory will assign part number prior to
Power Supply
order entry.
Voltage 24 to 60VDC/AC, or 85 to 230VDC/AC; (4) Configuration software allows selection of the (99%) values.
45 to 400Hz AC
Tolerance DC –15% to +33%, AC ±15%
Power Consumption DC ≤1.2W, AC ≤2.5VA
Environmental
Operating Temperature Range –25°C to +55°C
Storage Temperature Range –40°C to +70°C
Relative Humidity 0 to 75% Noncondensing
Emissions EN50081-2 (Radiated, Conducted)
Immunity EN50082-2 (ESD, RF, EFT)
Figure 3: Configuring the DSCP81 A PC, DSCX-787 PC interface cable, DSCX-587 module interface cable, and
DSCX-557 configuration software are required to program the DSCP81. Power
must be connected to the DSCP81 for configuration. The DSCX-557 configu-
ration software is supplied on a CD and runs under Windows 95, 98, NT and
2000.
IMPORTANT!
1. DO NOT connect the DSCX-587 module interface cable to the DSCP81
programming connector when >253 V is applied to the DSCP81 input.
2. The DSCX-587 module interface cable must first be connected to the
DSCX-787 cable before it is connected to the DSCP81.
3. The programming connector on the DSCP81 is DC connected to the
DSCP81 input circuit. DO NOT touch any metal parts of the plug or socket
if an input voltage >24 V is connected to the DSCP81.
DSCP
SCTP20
Programmable 2-Wire Temperature Transmitter, Head Mount
Description
Each SCTP20 2-wire transmitter is designed for measuring temperature using
thermocouples or RTDs. The input type, measurement range, and other Features
features are software configurable. A PC, the DSCX-887 and DSCX-440 • No Power Supply Required, Powered
interface cables, and the DSCX-895 configuration software are required to From Output Loop Current
configure the transmitter. Communication is serial RS-232C. User can choose
• Interfaces to All Standard Thermocouples
an isolated or non-isolated model.
and RTDs
The SCTP20 can interface to 12 industry standard thermocouple types: • Software Configurable Input Type and Range
J,K,T,E,R,S,B,N,L,U,C, and D. Cold junction compensation is selectable as
either internal or external. Three RTD types, Pt 100, Cu50*, and Ni 100, can be • Isolated (1500Vrms) and Non-Isolated
interfaced in a two, three or four wire connection. All inputs are linearized using Versions Available
up to 23 points of interpolation, and total errors are less than ±0.2%. • Open and Short-Circuit Input Detection
Other configurable features include: zero point and input range adjustment, • Configurable with or without Output Loop
output response for open or short-circuit sensor or cable failure, normal or Power Connected
inverted output, ripple suppression for 50Hz or 60Hz, and output time response. • –25°C to +80°C Operating Temperature
The DSCX-895 configuration software allows query, print-out and saving of
configuration settings, display of input measurement value, and display of • CE Compliant
interpolation table points.
*Call factory for Cu RTD information.
(see Electrical
Connections
on page 250 for
connection details)
The following grounding condition must be observed when pro- Thermocouple Type and Material
gramming the instrument.
Type Material
If one of the power supply or input wires is grounded to earth, a PC B Pt30Rh-Pt6Rh
without an earth connection must be used when programming E NiCr-CuNi
(e.g. a Laptop running on batteries). J Fe-CuNi
K NiCr-Ni
Under no circumstances should a PC be used running from a L Fe-CuNi
N NiCrSi-NiSi
power supply with an earth connection, as this will damage the R Pt13Rh-Pt
module. S Pt10Rh-Pt
T Cu-CuNi
U Cu-CuNi
C W5 Re/W26 Re
D W3 Re/W25 Re
SCTP
RTD 3L, 4L active active 2 2.5 4 6.5 11.5 21 40.5
RTD 2L, 3L, 4L off off 1.5 2.5 3.5 7.5 14 26.5 50.5
†
Additional Errors
Low Measuring Range
Resistance Thermometer
(<200°C Span) ±0.015% Span Typ., ±0.05% Span max
(2) Includes hysteresis, conformity and repeatability at reference conditions. Does not include CJC Thermocouples (<500°C Span) ±0.015% Span Typ., ±0.05% Span max
error.
(3) Shipped as PT 100 for 3-wire connection, 0 to 600°C range, 4 to 20mA output, open circuit
detect = 21.6mA output. High Initial Value Factor: ±0.0002 Typ., ±0.0005 max
(4) Submit configuration form shown on page 248, and factory will assign part number prior to order Error: (Factor)*(Initial Value/Span)*100 [%]
entry.
(5) Many different ranges may be programmed as long as the min/max limits are observed. For Influence of Lead Resistance ±0.01% per Ω
minimum range examples, a K type thermocouple could be programmed for +30°C to +78.5°C, or
+100°C to +149°C, or +900°C to +995°C, and so on. Internal Cold Junction Compensation ±(0.5°C/Span)*(100) [%]
NOTE A NOTE B
NOTE A: Minimum span is 15Ω when the end value(3) is less than or equal to 400Ω.
Minimum span is 150Ω when the end value(3) is greater than 400Ω and not exceeding 4000Ω.
The ratio of the min value to the span must be less than or equal to 10.
NOTE B: Range of span is 2mV minimum to 80mV maximum. The ratio of the min value to the span must be less than or equal to 10.
NOTE (1): W5 Re W26 Re (ASTM E 988-90)
NOTE (2): W3 Re W25 Re (ASTM E 988-90)
NOTE (3): For two-wire connections, the end value is made up of the measured end value (Ω) plus the total resistance of the leads.
Electrical Connections
Example of the set-up for programming a SCTP20 without the power supply.
For this case the switch on the interface must be set to “ON’.
SCTP
DSCT
Isolated DIN Rail Mount 2-Wire Transmitters
Features
• ±0.03% Accuracy (Typical)
• ±0.01% Linearity
• 1500Vrms Transformer Isolation &
240Vrms Field-side Protection
• ANSI/IEEE C37.90.1 Transient Protection
• Wide Loop Supply Voltage, 10.8V to 60V
• 5-Pole Low-Pass Filtering
• Up to 160dB CMR
• 85dB NMR at 60Hz, 80dB at 50Hz
• Protected Against Reverse Connection of
Loop Voltage
• –40°C to +80°C Operating Temperature
• Mounts on DIN Rail EN 50022, 35x7.5 or
35x15
Instrument Class® Performance • CSA C/US Certified
(Class I, Division 2, Groups A, B, C, D)
"Best of Breed" accuracy, linearity, stability and noise specifications. Outstand-
ing protection and isolation performance for Input, Output and Power connections. • CE Compliant
Capable of operating on the widest of loop supply power and over the broadest • Manufactured per RoHS Directive 2002/95/EC
operating temperature range!
Description
Dataforth’s new DSCT series of loop powered 2-wire transmitters consists of
seven family groups with a total of 48 transmitter models that interface to a wide
variety of voltage, current, temperature and position measuring devices. The
DSCT is the latest introduction of Instrument Class® products available from
Dataforth, which provide superior specifications such as ±0.03% accuracy, five
poles of filtering, 1500Vrms continuous isolation, low output noise, and much
more.
The DSCT 2-wire transmitter conditions and sends analog signals from sensors
located in the “field” to monitoring and control equipment, usually computers,
located thousands of feet away in central control areas. The DSCT accepts a
wide range of inputs, including millivolt, volt, milliamp, thermocouple, RTD,
potentiometer, and slide wire. It operates on power from a 2-wire signal loop and
modulates the supply current to represent the input signal within a 4 to 20-
milliamp range.
Two-wire transmission loops are very economical methods for connecting
sensors to distant control rooms. Since the DSCT operates from the signal loop
current, no additional, expensive power and wiring are required. Only low cost,
twisted pair wiring is needed.
DSCT30/31
Analog Voltage Input Transmitters
Description
Each DSCT30 and DSCT31 voltage input transmitter provides a single channel
of analog input which is filtered, isolated, amplified, and converted to a process
Features
current output (Figure 1). Signal filtering is accomplished with a five-pole filter, • Accepts Millivolt and Voltage Level Signals
which provides 85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An • Process Current Output
anti-aliasing pole is located on the field side of the isolation barrier, and the other
four are on the process loop side. After the initial field-side filtering, the input • 1500Vrms Transformer Isolation
signal is chopped by a proprietary chopper circuit. Isolation is provided by • ANSI/IEEE C37.90.1 Transient Protection
transformer coupling, again using a proprietary technique to suppress
• Input and Output Protected to 240VAC
transmission of common mode spikes or surges.
Continuous
Special input and output circuits on the DSCT30 and DSCT31 transmitters • Up to 60V Loop Voltage
provide protection against accidental connection of power-line voltages up to
240VAC and against transient events as defined by ANSI/IEEE C37.90.1. • 160dB CMR
Signal and loop power lines are secured to the module using screw terminals, • 85dB NMR at 60Hz, 80dB at 50Hz
which are in pluggable terminal blocks for ease of system assembly and
• ±0.03% Accuracy
reconfiguration.
• ±0.01% Linearity
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±10% to accommodate • Easily Mounts on Standard DIN Rail
situations where fine-tuning is desired. The adjustments are made using • CSA C/US Certified
potentiometers located under the front panel label and are non-interactive for • CE Compliant
ease of use.
Environmental
Operating Temp. Range –40°C to +80°C *
Storage Temp. Range –40°C to +80°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13” *
(h)(w)(d) (75mm x 22.5mm x 105mm) *
Mounting DIN EN 50022 –35x7.5 or –35x15 rail *
NOTES:
* Same specification as DSCT30.
(1) Includes linearity, hysteresis and repeatability. DSCT
DSCT32
Analog Current Input Transmitters
Description
Each DSCT32 current input transmitter provides a single channel of analog
input which is filtered, isolated, amplified, and converted to a process current Features
output (Figure 1). Signal filtering is accomplished with a five-pole filter, which • Accepts Milliamp Level Signals
provides 80dB per decade of normal-mode rejection above 100Hz. An
• Process Current Output
anti-aliasing pole is located on the field side of the isolation barrier, and the other
four are on the process loop side. After the initial field-side filtering, the input • 1500Vrms Transformer Isolation
signal is chopped by a proprietary chopper circuit. Isolation is provided by • ANSI/IEEE C37.90.1 Transient Protection
transformer coupling, again using a proprietary technique to suppress
• Input and Output Protected to 240VAC
transmission of common mode spikes or surges.
Continuous
Special input and output circuits on the DSCT32 transmitters provide protection • Up to 60V Loop Voltage
against accidental connection of power-line voltages up to 240VAC and against
transient events as defined by ANSI/IEEE C37.90.1. Signal and loop power lines • 105dB CMR
are secured to the module using screw terminals, which are in pluggable • ±0.03% Accuracy
terminal blocks for ease of system assembly and reconfiguration.
• ±0.01% Linearity
The modules have excellent stability over time and do not require recalibration, • Easily Mounts on Standard DIN Rail
however, zero and span settings are adjustable up to ±10% to accommodate
situations where fine-tuning is desired. The adjustments are made using • CSA C/US Certified
potentiometers located under the front panel label and are non-interactive for • CE Compliant
ease of use.
Environmental
Operating Temp. Range –40°C to +80°C
Storage Temp. Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13”
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 –35x7.5 or –35x15 rail
NOTES:
(1) Includes linearity, hysteresis and repeatability.
DSCT
DSCT34
Linearized 2- or 3-Wire RTD Input Transmitters
Description
Each DSCT34 RTD input transmitter provides a single channel of RTD input
which is filtered, isolated, amplified, linearized, and converted to a process Features
current output (Figure 1). Signal filtering is accomplished with a five-pole filter, • Interfaces to 100Ω Platinum or 120Ω
which provides 85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An Nickel RTDs
anti-aliasing pole is located on the field side of the isolation barrier, and the other
• Linearizes RTD Signal
four are on the process loop side. After the initial field-side filtering, the input
signal is chopped by a proprietary chopper circuit. Isolation is provided by • Process Current Output
transformer coupling, again using a proprietary technique to suppress • 1500Vrms Transformer Isolation
transmission of common mode spikes or surges.
• ANSI/IEEE C37.90.1 Transient Protection
RTD excitation is provided from the transmitter using a precision current source. • Input and Output Protected to 240VAC Continuous
The excitation currents are very small (0.26mA max for 100Ω Pt and 120Ω Ni)
which minimizes self-heating of the RTD. Linearization is achieved by creating • Up to 60V Loop Voltage
a non-linear transfer function through the module itself. This non-linear transfer • 160dB CMR
function is configured at the factory and is designed to be equal and opposite to
• 85dB NMR at 60Hz, 80dB at 50Hz
the specific RTD non-linearity. Lead compensation is achieved by matching two
current paths thus canceling the effects of lead resistance. • ±0.1% Accuracy
The specifications listed are for a 3-wire connection. A 2-wire connection of the • ±0.025% Conformity
RTD to the module is also possible and is achieved by adding a jumper between • Easily Mounts on Standard DIN Rail
pin 5 (+EXC) and pin 6 (+IN) on the terminal block and connecting the RTD leads • CSA C/US Certified
between pin 6 (+IN) and pin 7 (-IN). The 2-wire connection nullifies the lead
resistance compensation feature of the module. • CE Compliant
Special input and output circuits on the DSCT34 transmitters provide protection The modules have excellent stability over time and do not require recalibration,
against accidental connection of power-line voltages up to 240VAC and against however, zero and span settings are adjustable up to ±3% to accommodate
transient events as defined by ANSI/IEEE C37.90.1. Signal and loop power lines situations where fine-tuning is desired. The adjustments are made using
are secured to the module using screw terminals, which are in pluggable potentiometers located under the front panel label and are non-interactive for
terminal blocks for ease of system assembly and reconfiguration. ease of use.
Environmental
Operating Temp. Range –40°C to +80°C
Storage Temp. Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13”
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 –35x7.5 or –35x15 rail
NOTES:
(1) Includes conformity, hysteresis and repeatability.
DSCT
DSCT36
Potentiometer Input Transmitters
Description
Each DSCT36 potentiometer input transmitter provides a single channel of
potentiometer input which is filtered, isolated, amplified, and converted to a
Features
process current output (Figure 1). Signal filtering is accomplished with a • Interfaces to Potentiometers up to 10kΩ
five-pole filter, which provides 85dB of normal-mode rejection at 60Hz and 80dB • Process Current Output
at 50Hz. An anti-aliasing pole is located on the field side of the isolation barrier,
and the other four are on the process loop side. After the initial field-side filtering, • 1500Vrms Transformer Isolation
the input signal is chopped by a proprietary chopper circuit. Isolation is provided • ANSI/IEEE C37.90.1 Transient Protection
by transformer coupling, again using a proprietary technique to suppress
• Input and Output Protected to 240VAC
transmission of common mode spikes or surges.
Continuous
Potentiometer excitation is provided from the transmitter using a precision • Up to 60V Loop Voltage
current source. The excitation current is small (less than 0.26mA) which
minimizes self-heating of the potentiometer. Lead compensation is achieved by • 160dB CMR
matching two current paths which cancels the effects of lead resistance. • 85dB NMR at 60Hz, 80dB at 50Hz
Special input and output circuits on the DSCT36 transmitters provide protection • ±0.03% Accuracy
against accidental connection of power-line voltages up to 240VAC and against • ±0.01% Linearity
transient events as defined by ANSI/IEEE C37.90.1. Signal and loop power lines
are secured to the module using screw terminals, which are in pluggable • Easily Mounts on Standard DIN Rail
terminal blocks for ease of system assembly and reconfiguration. • CSA C/US Certified
The modules have excellent stability over time and do not require recalibration, • CE Compliant
however, zero and span settings are adjustable up to ±10% to accommodate
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
Environmental
Operating Temp. Range –40°C to +80°C
Storage Temp. Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
DSCT37
Non-Linearized Thermocouple Input Transmitters
Description
Each DSCT37 non-linearized thermocouple input transmitter provides a single
channel of thermocouple input which is filtered, isolated, amplified, and Features
converted to a process current output (Figure 1). Signal filtering is accomplished • Interfaces to Types J, K, T, E, R, S, B, and N
with a five-pole filter, which provides 85dB of normal-mode rejection at 60Hz and Thermocouples
80dB at 50Hz.An anti-aliasing pole is located on the field side of the isolation
• Process Current Output
barrier, and the other four are on the process loop side. After the initial field-side
filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is • 1500Vrms Transformer Isolation
provided by transformer coupling, again using a proprietary technique to • ANSI/IEEE C37.90.1 Transient Protection
suppress transmission of common mode spikes or surges.
• Input and Output Protected to 240VAC
The DSCT37 can interface to eight industry standard thermocouple types: Continuous
J, K, T, E, R, S, B and N. Each transmitter is cold-junction compensated to
• Up to 60V Loop Voltage
correct for parasitic thermocouples formed by the thermocouple wire and
screw terminals on the transmitter. Upscale open thermocouple detection is • 160dB CMR
provided by circuitry. Downscale indication can be implemented by installing a • 85dB NMR at 60Hz, 80dB at 50Hz
47MΩ, ±20% resistor between screw terminals 6 (+IN) and 8 (-EXC) on the
• ±0.05% Accuracy
input terminal block.
• ±0.01% Linearity
Special input and output circuits on the DSCT37 transmitters provide protection
against accidental connection of power-line voltages up to 240VAC and against • Easily Mounts on Standard DIN Rail
transient events as defined by ANSI/IEEE C37.90.1. Loop power lines are • CSA C/US Certified
secured to the module using screw terminals, which are in pluggable terminal
• CE Compliant
blocks for ease of system assembly and reconfiguration. Transmitter zero and
span settings are adjustable up to ±10%. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
Environmental
Operating Temp. Range –40°C to +80°C
Storage Temp. Range –40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
RF Performance A ±0.5% Span Error
ESD, EFT Performance B
NOTES:
(1) Includes conformity, hysteresis, repeatability and CJC error.
DSCT47
Linearized Thermocouple Input Transmitters
Description
Each DSCT47 thermocouple input transmitter provides a single channel of
thermocouple input which is filtered, isolated, amplified, linearized, and
Features
converted to a process current output (Figure 1). Signal filtering is accomplished • Interfaces to Types J, K, T, E, R, S, B, and N
with a five-pole filter, which provides 85dB of normal-mode rejection at 60Hz and Thermocouples
80dB at 50Hz. An anti-aliasing pole is located on the field side of the isolation • Linearizes Thermocouple Signal
barrier, and the other four are on the process loop side. After the initial
field-side filtering, the input signal is chopped by a proprietary chopper circuit. • Process Current Output
Isolation is provided by transformer coupling, again using a proprietary • 1500Vrms Transformer Isolation
technique to suppress transmission of common mode spikes or surges.
• ANSI/IEEE C37.90.1 Transient Protection
Linearization is achieved by creating a non-linear transfer function through the • Input and Output Protected to 240VAC
module itself. This non-linear transfer function is configured at the factory and Continuous
is designed to be equal and opposite to the thermocouple non-linearity.
• Up to 60V Loop Voltage
The DSCT47 can interface to eight industry standard thermocouple types: J, K,
• 160dB CMR
T, E, R, S, B and N. Each transmitter is cold-junction compensated to correct
for parasitic thermocouples formed by the thermocouple wire and screw • 85dB NMR at 60Hz, 80dB at 50Hz
terminals on the transmitter. Upscale open thermocouple detection is provided • ±0.10% Accuracy
by circuitry. Downscale indication can be implemented by installing a 47MΩ,
±20% resistor between screw terminals 6 (+IN) and 8 (-EXC) on the input • Easily Mounts on Standard DIN Rail
terminal block. • CSA C/US Certified
Special input and output circuits on the DSCT47 transmitters provide protection • CE Compliant
against accidental connection of power-line voltages up to 240VAC and against
transient events as defined by ANSI/IEEE C37.90.1. Loop power lines are span settings are adjustable up to ±3%. The adjustments are made using
secured to the module using screw terminals, which are in pluggable terminal potentiometers located under the front panel label and are non-interactive for
blocks for ease of system assembly and reconfiguration. Transmitter zero and ease of use.
NOTES:
(1) Includes conformity, hysteresis, repeatability and CJC error.
DSCT
Features
inside and outside, with signals exposed to electrical transients, noise, ground
loops, power surges, and lightning. Commercial communications equipment • 1500Vrms Isolation with Optocouplers and
often is not designed for use in these environments, which can lead to unreliable Power DC-to-DC Converter (3000Vp, 1 min)
signal quality, damage to expensive CRTs, computers, and other online • Industrial Temperature Range
equipment, and production downtime. Our heavy duty modems “harden” and
protect these systems, and can extend communications for many miles without • DTE/DC Selection Switches, Diagnostic LEDs
expensive cabling. • Rugged, Compact Industrial Packaging,
Choice of Host Connectors
Our LDM Series limited distance modems protect host computers and
equipment and extend the distances over which computers, terminals, and • Data Rates to 115.2kbps
other devices can communicate within hazardous industrial and institutional • Distances to 12 Miles (20km)
environments – up to 12 miles using wire pairs and current loop protocols, or two
miles with fiber optic data links for total electrical isolation. • Multidrop, Handshake Functions
• 2- or 4-Wire, Simplex/Duplex Connection
Our DCP485 DIN Rail RS-232 to RS-485 converter/line driver provides
1500 Vrms continuous isolation and data transfer up to 115.2 kbps with • Full Line of Power and Connector Accessories
automatic RS-485 line control while powered from +10 to +30 VDC. • CE Compliant
• Manufactured per RoHS Directive 2002/95/EC
Applications
• Protects Equipment from Damage due to
Power Surges, Transients, Lightning;
Breaks Ground Loops
• Extends RS-232 Communication Distances
without Expensive Low-Capacitance Cabling
• Connects RS-232 Devices to RS-422 and
DCP485 DCP35
RS-485 Devices
• Ideal Choice for Industrial and Institutional
LANs
LDM30 LDM35
DCP485 115.2k (.8 mi) 7 mi (2.4k) Electrical Simplex 2 Screw Comm(2)/ RS-232 Fe/Male Ext.(6) DIN Rail mounting
(1.3 km) 11.3 km RS-485 Half/ 2 Terminals Power(3) DB-9/ Auto RS-485
Differential Full- Screw Line control
Voltage Duplex 4 Terms
LDM30 57.6k (.5 mi) 12 mi (1.2k) Electrical Simplex 2 Screw Terms Male/
(.8 km) 19.3 km Current Full- Mod Phone Comm(2) RS-232 Female Ext.(1) Low Cost
Loop Duplex 4 Jack DB-25
LDM35 19.2k (.5 mi) 12 mi (0.3k) Electrical Simplex 2 Screw Terms Male/ Port Port-Signal
(.8 km) 19.3 km Current Full- Mod Phone Comm(2) RS-232 Female Signals Powered
Loop Duplex 4 Jack DB-25
LDM70 57.6k (.5 mi) 12 mi (1.2k) Electrical Simplex 2 Screw Terms Comm(2)/ RS-232 Male/ Full isolation,
(.8 km) 19.3 km Current Full- Mod Phone Power(3) Female Ext.(1) DTR/RLSD handshake
Loop Duplex 4 Jack DB-25
LDM422 19.2k (1 mi) 7 mi (1.2k) Electrical Simplex 2 Screw Comm(2)/ RS-232 Male/ Multidrop capable
(1.6 km) 11.3 km RS-422 Half/ Terminals Power(3) Female Ext.(1) RTS/CTS handshake
Differential Full- 2 DB-25 or 2nd data channel
Voltage Duplex 4
LDM485 57.6k (.5 mi) 8 mi (2.4k) Electrical Simplex 2 Screw Comm(2)/ RS-232 Male/ Multidrop capable
(.8 km) 12.9 km RS-485 Half/ Terminals Power(3) Female Ext.(1) RTS/CTS handshake
Differential Full- 2 DB-25 or 2nd data channel
Voltage Duplex 4
LDM80 19.2k (2.2 mi) 2.2 mi (19.2k) Optical Simplex 1 fiber SMA (905) Total(4) RS-232 Male/ Port Total electrical isolation,
(3.5 km) 3.5 km Full- ST Female Signals intrinsic safety
Duplex 2 fibers DB-25
(5)
LDM85 5M (1.2 mi) 1.2 mi (5M) Optical Simplex 1 fiber SMA (905) Total(4) RS-232 Male/ Multipoint optical loop,
(2 km) 2 km Full- ST RS-422/ Female Ext.(1) total electrical isolation
Duplex 2 fibers RS-423 DB-25
TTL
Accessories
NOTES:
Model Description (1) Externally powered LDMs may be powered with wall transformer (supplied)
or through pins 9 and 10 on host interface.
Power Supply DIN Rail Mount, 85-264 VAC, 47-63 Hz In (2) Comm isolation provides an optical barrier on receive circuits and/or
PWR-PS5RA 24 VDC, 0.31 A Out transmit circuits plus ANSI/IEEE C37.90.1 surge protection.
PWR-PS5RB 24 VDC, 0.63 A Out (3) Power isolation by DC/DC converter to field circuits.
PWR-PS5RC 24 VDC, 1.25 A Out (4) Fiber optic units provide total electrical isolation.
PWR-PS5RD 24 VDC, 2.08 A Out (5) Max data rate for LDM85 is 2.5M bps NRZ TTL and 100K bps RS-232/422.
PWR-PS5RE 24 VDC, 4.17 A Out (6) Externally powered +10V to +30VDC.
Data Comm
DCP485
Fully Isolated DIN Rail RS-232 to RS-485 Converter/Line Driver
Description
The DCP485 is a compact RS-232 to RS-485 converter which features a
complete electrical isolation barrier and heavy duty electrical surge protectors.
Features
These devices feature a DIN rail mountable enclosure for application to a • Complete Isolation with Optical Couplers and
junction box, a panel, a relay rack, the sides of computer equipment, or Transformer-Coupled DC-to-DC Converter
anywhere a DIN rail can be mounted. Isolation is provided by optical couplers • Industrial Surge Protection Devices and 15kV
and a transformer isolated DC-to-DC converter. The RS-232 connection is ESD Protected RS-232 Inherent
through male or female EIA 9-pin D-sub connectors, or a 3-wire RS-232
connection can be made through convenient pluggable screw terminals. The • Four LED Diagnostic Indicators
RS-485 connections are made through convenient pluggable solderless screw • 38.4kbps at 1 Mile (1.6km),
terminals. 115.2kbps at 0.8 Mile (1.3km)
The DCP485 series is designed for full duplex operation over two wire pairs. • RTS, DTR, or Auto RS-485 Transmitter
Outputs are tri-state, allowing multidropping of up to 32 units over one pair. Control
Data rates are DC to 115.2k bits per second. Four diagnostic LED indicators • Tri-state Outputs for Multidrop Applications,
are provided for installation guidance and system troubleshooting. The RS-232 up to 32 Devices
interface includes Request To Send (RTS) and Data Terminal Ready (DTR)
either of which can be used via DIP switches to enable the RS-485 transmitter. • Selection of Connectors
Alternately, the DCP485 offers automatic line switching in which the RS-485 • Wide Operating Temperature Range
transmitter is enabled automatically by each character sent on the RS-232 • Pluggable Solderless Screw Terminal Field
Transmit Data (TD) line. Additionally, the RS-485 transmitter and receiver may Connections
be independently enabled continuously or under RS-232 control. A convenient
null modem switch is provided for the data lines. Also, line termination switches • CE Compliant
independently connect line termination and line bias resistors to the RS-485
lines. The units are powered from wide-range voltages of +10 to +30VDC
through pluggable solderless screw terminals.
DCP35
DIN Rail Signal-Powered RS-232 Line Drivers
Description
The DCP35 series of products is designed to allow RS-232 devices to be
inter-connected over distances sufficient to cover any industrial or institutional
Features
complex of buildings. These line drivers feature a DIN rail mountable enclosure • Signal-powered: No Power Source Required
for application to a junction box, a panel, a relay rack, the sides of computer • Optical Isolation: Breaks Ground Loops
equipment, or anywhere a DIN rail can be mounted.
• Heavy Duty Surge Protectors: Prevents
The DCP35 series does not require a power supply for operation. The use of low Lightning Damage
power circuits and a sensitive optically isolated receiver allows the devices to
derive all necessary power from the RS-232 data and control signals. They are • LED Diagnostic Indicators: Simplifies
designed for full-duplex, asynchronous operation over two, DC-continuous, Installation and System Troubleshooting
non-loaded, twisted-wire pairs. Two-wire simplex operation may be accom- • 19.2kbps to 0.5 Mile (0.8km),
plished over one twisted- wire pair. The line driver circuits and, consequently, 9.6kbps to 2.0 Miles (3.2km), 1.2kbps to 7.0
the host device are protected from electrical transients due to lightning strikes Miles (11.3km)
or operation of heavy industrial equipment. • Four-Wire Full Duplex, Two-Wire Simplex
Each device features a convenient DCE (Data Communication Equipment) to • Pluggable Solderless Screw Terminal Field
DTE (Data Terminal Equipment) switch which reverses pins 2 and 3 of the Connections
RS-232 connector. For installation and system troubleshooting each unit has
• Null Modem Switch
diagnostic Light Emitting Diodes (LEDs) on the transmit and receive lines.
• CE Compliant
The RS-232 connector may be ordered as a male or female 9-pin connector.
Field connection is made through pluggable solderless screw terminals.
Data Comm
LDM30
General Purpose Limited Distance Modem
Description
The LDM30 series of products is designed to allow video display terminals
(VDTs) and other RS-232 devices to be connected over distances sufficient to
Features
cover any industrial or institutional complex of buildings. These modems • DC to 57,600bps
feature a rugged aluminum enclosure small enough to mount on the back panel • Optical Isolation
of VDT units, saving valuable desk and floor space.
• Surge Protectors
The LDM30 series is designed for full-duplex, asynchronous operation over
two, DC-continuity, non-loaded, twisted-wire pairs. Through special high- • LED Diagnostic Indicators
speed optically-coupled circuits they may communicate at data rates up to • Operation to 3 Miles (5km) at 9600bps,
57,600bps. A self-powered model and a host-powered model are available. 1 Mile (1.7km) at 19,200bps, 0.5 Miles (0.8km)
The self-powered unit uses 12VAC from a wall-mounted transformer while the at 57,600bps
host-powered unit takes ±DC power from pins 9 and 10 of the RS-232 • Four-Wire Full Duplex, Two-Wire Simplex
connector. The modem circuits — and, consequently, the host device — are
protected from electrical transients due to lightning strikes or operation of • Self-Powered or Host-Powered
heavy industrial equipment. • Selection of Connectors
Each device features a convenient Data-Communication Equipment (DCE) to • Wide Operating Temperature Range, 0 to +70°C
Data-Terminal Equipment (DTE) switch which reverses pins 2 and 3 of the • CE Compliant
RS-232 connector. For installation and troubleshooting, each unit has
diagnostic Light-Emitting Diodes (LEDs) on the transmit and receive lines.
The RS-232 connector may be ordered as a male or female 25-pin connector.
Field connection is made through a modern, solderless, screw-termination
assembly.
NOTES:
(1) TD, RD: mark = -V, space = +V.
(2) LDM30 can operate on AC or DC power. AC is applied
on field pins 1 and 2, 12VAC max. DC is applied on RS-
232 pins 9 and 10: +9 to +15VDC at 35mA on pin 9, -9 to -
15VDC at 35mA on pin 10.
Channel Lines(1) TD, RD PT3 U.S. style wall mount transformer, 120VAC
Control Lines(1) RTS, CTS, DTR, DSR, RLSD PT3E Euro style wall mount transformer, 220VAC
Power
AC operation(2) 12VAC at 92mA RS-232 P1 Pin Descriptions Field P2 Pin Description
DC operation ±9VDC to ±15VDC, 35mA
Screw Terms
Environmental: Pin 1 CASE Ground Pin 1 12VAC
Operating Temperature Range 0°C to +70°C Pin 2 TD [3] Transmit Data Pin 2 AC GND
Storage Temperature Range –10°C to +85°C Pin 3 RD [2] Receive Data Pin 3 RD+
Relative Humidity 0 to 95% Noncondensing Pin 4 RTS [7] Req. To Send Pin 4 RD-
Pin 5 CTS [8] Clear To Send Pin 5 TD+
Dimensions 3.6” x 2.1” x 1” Pin 6 DSR [6] Data Set Ready Pin 6 TD-
(91.4mm x 53.3mm x 25.4mm) Pin 7 GND [5] Signal Ground
Weight 3.5 oz (100g) max Pin 8 RLSD [1] Receive Line Signal Detect RD+ = Receive Data +
PT3 and PT3E 11.0 oz (312g) max Pin 9 +DC Positive DC Supply Input RD- = Receive Data -
Pin 10 -DC Negative DC Supply Input TD+ = Transmit Data +
MTTF(3) >150,000 hrs Pin 20 DTR [4] Data Terminal Ready TD- = Transmit Data -
NOTES:
Pin numbers given are for the 25-pin connector with the 9-pin equivalent
(1) TD = Transmit Data, RD = Receive Data, RTS = Request To Send, CTS = Clear To Send, DTR = Data
Terminal Ready, DSR = Data Set Ready, RLSD = Received Line Signal Detect. in [ ].
(2) 120VAC and 220VAC power transformers are available.
(3) Ground-benign environmental conditions (no salt atmosphere, <50°C ambient temperature).
Data Comm
LDM35
Signal Powered Limited Distance Modem
Description
The LDM35 series of products is designed to allow video display terminals
(VDTs) and other RS-232 devices to be connected over distances sufficient to
Features
cover any industrial or institutional complex of buildings. These modems feature • Signal-powered: No Power Source Required
a rugged enclosure small enough to mount on the back panel of VDT units, • Optical Isolation: Breaks Ground Loops
saving valuable desk and floor space.
• Heavy Duty Surge Protectors: Prevents Lightning
The LDM35 series does not require a power supply for operation. The use of low Damage
power circuits and a sensitive optical receiver allows the devices to derive all
necessary power from the RS-232 data and control signal. They are designed • LED Diagnostic Indicators: Simplifies Installation
for full-duplex, asynchronous operation over two, DC-continuity, non-loaded, and System Troubleshooting
twisted-wire pairs. Two-wire simplex operation may be accomplished over two • Operation to Two Miles (3.3km) at 9600bps,
wires. The modem circuits and, consequently, the host device are protected One-Half Mile (0.8km) at 19,200bps, Seven
from electrical transients due to lightning strikes or operation of heavy industrial Miles (11.7km) at 1200bps
equipment. • Four-Wire Full Duplex, Two-Wire Simplex
Each device features a convenient Data-Communication Equipment (DCE) to • Selection of Connectors
Data-Terminal Equipment (DTE) switch which reverses pins 2 and 3 of the
• Wide Operating Temperature Range, 0°C to +70°C
RS-232 connector. For installation and troubleshooting, each unit has
diagnostic Light-Emitting Diodes (LEDs) on the transmit and receive lines. • Null Modem Switch
The RS-232 connector may be ordered as a male or female 25-pin connector. • CE Compliant
Field connection is made through a modern, solderless, screw-termination
assembly.
Data Comm
LDM70
Fully Isolated Limited Distance Modem
Description
The LDM70 series of products is designed to allow video display terminals
(VDTs) and other RS-232 devices to be connected over distances sufficient to
Features
cover any industrial or institutional complex of buildings. These modems • DC to 57,600bps
feature a rugged aluminum enclosure small enough to mount on the back panel • Complete Isolation with Optical Couplers and
of VDT units, saving valuable desk and floor space. Power DC-to-DC Converter
The LDM70 series is designed for full duplex, asynchronous operation over two • Data Terminal Ready, Carrier Detect
DC-continuity, non-loaded, twisted-wire pairs. Through special high-speed Handshake without Extra Wires
optically coupled circuits, they may communicate at data rates up to 57,600 bits
per second. A handshake operation is implemented over the same two-wire • Surge Protectors
pairs. A self-powered model and a host-powered model are available. The • Four LED Diagnostic Indicators
self-powered unit uses 12VAC from a wall-mounted transformer, while • Operation to 3 Miles (5km) at 9600bps,
the host-powered unit takes ±DC power from pins 9 and 10 of the RS-232 1 Mile (1.7km) at 19,200bps, 0.5 Miles (0.8km)
connector. The modem circuits —and, consequently, the host device — are at 57,600bps
protected from electrical transients due to lightning strikes or operation of
heavy industrial equipment. • Four-Wire Full Duplex, Two-Wire Simplex
• Self-Powered or Host-Powered
Each device features a convenient Data-Communication Equipment (DCE) to
Data-Terminal Equipment (DTE) switch which reverses pins 2 and 3 of the • Selection of Connectors
RS-232 connector. For installation and troubleshooting, each unit has • Wide Operating Temperature Range,
diagnostic Light-Emitting Diodes (LEDs) on the transmit and receive lines. In 0 to +70°C
addition, LEDs indicate valid carrier detect and data terminal ready.
• CE Compliant
The RS-232 connector may be ordered as a male or female 25-pin connector.
Field connection is made through a modern, solderless, screw-termination
assembly.
Data Comm
LDM422
Fully Isolated Limited Distance Modem, RS-232/422 Converter
Description
The LDM422 is a compact RS-232 to RS-422 converter which features a
complete electrical isolation barrier and heavy duty electrical surge protectors.
Features
These devices feature a rugged aluminum enclosure small enough to mount on • Complete Isolation with Optical Couplers and
the back panel of typical computer equipment, saving valuable desk and floor Power DC-to-DC Converter
space. Isolation is provided by optical couplers and a DC-to-DC converter. • Industrial Surge Protection Devices
The RS-232 connection is through male or female EIA 25-pin connectors. The
RS422 connections are made through convenient solderless screw terminals. • Six LED Diagnostic Indicators
The LDM422 series is designed for full duplex operation over two-wire pairs. • DC to 19,200bps at 6000 Feet (1800m),
Outputs are tri-state, allowing multidropping of up to 32 units. Hardware 9600bps at 3 Miles (5km)
handshake is available over two separate wire pairs. Data rates are 75 to 19,200 • Request-To-Send, Clear-To-Send Handshake
bits per second. Six diagnostic LED indicators are provided (see Figure 1) for • Tri-state Outputs for Multidrop Applications
installation guidance and system troubleshooting. The RS-232 interface sup-
ports Request To Send, Clear To Send, Data Set Ready, Received Line Signal • Selection of Connectors
Detect, and Data Terminal Ready. A convenient null modem switch is provided • Wide Operating Temperature Range
for the data lines. The RS-422 interface supports Request To Send and Clear • Solderless Screw Terminal Field Connections
To Send on separate wire pairs. The LDM422 may be used to convert two sets
of send and receive channels by using RTS and CTS circuits as the second data • CE Compliant
channels. Data rates are the same. The units use 12VAC from a wall-mounted
transformer or ±12VDC to pins 9 (+) and 10 (–) of the RS-232 connector.
Data Comm
LDM485
Fully Isolated Limited Distance Modem, RS-232/485 Converter
Description
The LDM485 is a compact RS-232 to RS-485 converter which features a
complete electrical isolation barrier and heavy duty electrical surge protectors.
Features
These devices feature a rugged aluminum enclosure small enough to mount • Complete Isolation with Optical Couplers and
on the back panel of typical computer equipment, saving valuable desk and Power DC-to-DC Converter
floor space. Isolation is provided by optical couplers and a DC-to-DC con- • Industrial Surge Protection Devices
verter. The RS-232 connection is through male or female EIA 25-pin connectors.
The RS-485 connections are made through convenient solderless screw • Six LED Diagnostic Indicators
terminals. • 19.2kbps at 3 Miles (5km), 57.6kbps at 0.5
The LDM485 series is designed for full duplex operation over two-wire pairs. Miles (0.8 km)
Outputs are tri-state, allowing multidropping of up to 64 units. Hardware • Request-To-Send, Clear-To-Send Handshake
handshake is available over two separate wire pairs. Data rates are DC to • Tri-state Outputs for Multidrop Applications, Up
57.6k bits per second. Six diagnostic LED indicators are provided (see to 64 Devices
Figure 1) for installation guidance and system troubleshooting. The RS-232
interface supports Request To Send, Clear To Send, Data Set Ready, • Selection of Connectors
Received Line Signal Detect, and Data Terminal Ready. A convenient null • Wide Operating Temperature Range
modem switch is provided for the data lines. Also, a line termination switch • Solderless Screw Terminal Field Connections
connects a line termination resistor and line bias resistors to the RS-485
receive lines. The RS-485 interface supports Request To Send and Clear To • CE Compliant
Send on separate wire pairs. The LDM485 may be used to convert two sets of
send and receive channels by using RTS and CTS circuits as the second data
channels. Data rates are the same. The units use 12VAC from a wall-mounted
transformer to screw terminals 1 and 2 on the RS-485 connector. Alternately,
they can use ±12VDC to pins 9 (+) and 10 (–) of the RS-232 connector.
Data Comm
LDM80
Signal Powered Fiber Optic Modem
Description
The LDM80 is a small, inexpensive fiber optic transmitter/receiver completely
powered by the host RS-232 port. The enclosure for the LDM80 is a conductive
Features
shell which greatly reduces RF radiation and susceptibility. The rugged metal • Data Rates to 19.2kbps at 2.2 Miles (3.5km)
enclosure is small enough to mount on the back panel of typical computer • 17dB Optical Link Power Budget
equipment saving valuable desk and floor space. A pair of these units allows
most RS-232C cable links to be replaced and extended with a duplex fiber optic • Powered by RS-232 Host Port Signals
cable. The normal 50-foot (15m) RS-232 limit may be extended to 2.2 miles • Full Duplex Asynchronous Operation
(3.5 km). Fiber optic data communications provide complete EMI/RFI rejec-
• Indicating LEDs
tion, isolation, elimination of ground loops, and reduced error rates. Data
security is enhanced by almost nonexistent electromagnetic emissions. The • DCE/DTE Switch
RS-232 connection is through male or female EIA 25-pin connectors. The fiber • Designed for FCC Class A Requirements
optic connection is through ST connectors.
• Complies with FCC Class A Requirements
The LDM80 is equivalent to a 3-wire, full duplex, RS-232 circuit. Handshake • Pinned or Socketed RS-232 Connectors
signals are locally connected as in Figure 1. Indicating LEDs come on during
a "SPACE" on transmit or receive data. A TD/RD reversing DIP switch is • CE Compliant
provided for connection to DTE (Data Terminal Equipment) or DCE (Data
Communication Equipment) ports.
Data Comm
LDM85
Fiber Optic Modem
Description
The LDM85 is a small, inexpensive fiber optic transmitter/receiver. It features
a complete RS-232/422/423 port as well as high speed TTL data transmit and
Features
receive. It is capable of data rates from DC to 5Mbps. A pair of these units • Data Rates to 5Mbps
allows most RS-232C cable links to be replaced and extended with a duplex • RS-232, RS-422, TTL System Interfaces
fiber optic cable. The normal 50-foot RS-232 limit may be extended to 1.2 miles
(2 km). Fiber optic data communications provide complete EMI/RFI rejection, • Multipoint Capability
isolation, elimination of ground loops, and reduced error rates. Data security • LED Indicators
is enhanced by almost nonexistent electromagnetic emissions. A unique
• DCE/DTE Switch
multipoint capability allows local area networks to be formed with the isolation
and data security of a fiber optic data highway. • Small Size
The LDM85 is packaged in a rugged aluminum enclosure small enough to • Low Cost
mount on the back panel of typical computer equipment, saving valuable desk • SMA- or ST-Compatible Optic Connectors
and floor space. The RS-232 connection is through male or female EIA • 120/220VAC, +5VDC or 8 to 20VAC/DC Power
25-pin connectors. The fiber optic connection is either through SMA (905) or
ST connectors. Additional features include a TD/RD reversing switch for • CE Compliant
connection to DTE (Data Terminal Equipment) or DCE (Data Communication
Equipment) ports, three diagnostic LED indicators, and locally connected
handshake lines. The TTL port combined with the RS-232 port may be
interfaced to RS-422/423 ports in 4-wire point-to-point mode only.
T 0.566
LDM85 TD (14.4)
0.216 (5.5)
0.116 (3.0)
0
1.00 (25.4)
0.45
0.497 (12.6)
(11.4)
Data Comm
0.252 (6.4)
0
PT3 PT3E
US Style Wall-Mount Transformer European Style Transformer
Specifications Specifications
Model PT3 Model PT3E
Electrical Specifications Electrical Specifications
Input 120VAC, 60Hz, 18W Input 230VAC, 50Hz, 10W
Output 12VAC, 1000mA, 12.0VA Output 12VAC, 500mA, 6VA
Output Cable Length 6.0 ft (1.83m) minimum Input Cable Length 3.5 ft (1.1m) minimum
Output Cable Length 6.0 ft (1.83m) minimum
Dimensions 2.21 in x 2.14 in x 1.65 in
(56.1 mm x 54.4 mm x 41.9 mm) Dimensions 2.70 in x 1.95 in x 1.60 in
(68.6 mm x 49.5 mm x 40.6 mm)
Weight 11.0 oz (312g)
Weight 11.0 oz (312g)
Application Support The product should be carefully packaged, making sure the RMA number appears on the
outside of the package, and shipped prepaid to:
Dataforth provides timely, high-quality product support. Call 1-800-444-7644 TOLL-FREE
Dataforth Corporation
Returns/Repair Policy 3331 E. Hemisphere Loop
Tucson, AZ 85706 USA
All warranty and repair requests should be directed to the Dataforth Customer Service
Department at (520) 741-1404. If a product return is required, request a Return Material The information provided herein is believed to be reliable; however, DATAFORTH assumes
Authorization (RMA) number. You should be ready to provide the following information: no responsibility for inaccuracies or omissions. DATAFORTH assumes no responsibility
1. Complete product model number. for the use of this information, and all use of such information shall be entirely at the user’s
2. Product serial number. own risk. Application information is intended as suggestions for possible use of the products
and not as explicit performance in a specific application. Prices and specifications are sub-
3. Name, address, and telephone number of person returning product. ject to change without notice. No patent rights or licenses to any of the circuits described
4. Special repair instructions. herein are implied or granted to any third party. DATAFORTH does not authorize or warrant
5. Purchase order number for out-of-warranty repairs. any DATAFORTH product for use in life-support devices and/or systems.
High Performance Industrial Signal Conditioning, Data Acquisition,
and Data Communication Products Since 1984
WORLD HEADQUARTERS
Dataforth Corporation
3331 E. Hemisphere Loop
Tucson, AZ 85706 USA
Toll Free: 800-444-7644
Tel: 520-741-1404
Fax: 520-741-0762
Email: sales@dataforth.com
www.dataforth.com
Dataforth Europe
Tel: +49.8631.308111
Fax: +49.8631.308118
Email: datafortheurope@dataforth.eu
www.dataforth.eu
Dataforth Asia
Tel: 949-829-3678
Email: dataforthasia@dataforth.com
www.dataforth.com.cn
www.dataforth.com
CAT-103K 01/11
©1995-2011 Dataforth Corporation, All Rights Reserved ISO9001:2008-Registered QMS