SQ300i C-Interface B
SQ300i C-Interface B
SQ300i C-Interface B
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 2
Important Safety Notice
Instruct all persons working on the products described in this booklet to carefully read the entire
booklet before installing, operating, or maintaining those products.
Description of Symbols
We may use symbols throughout this manual to alert you to important warnings and helpful
information. When you see these symbols, please be sure to read the associated messages.
This symbol is used to warn you about the risk of electric shock and
dangerous voltage.
This symbol is used to bring your attention to situations that may cause
harm to people or equipment.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 3
• Only qualified electricians or electrical instrument technicians should
install or service all products described in this booklet.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 4
Introduction
The SQ-300i Operator Interface is an optional component of the SQ-300i control system. For
this reason, the Operator Interface is shipped in a separate package, instead of shipping with the
SQ-300i Microcontroller and SCR Firing Assembly.
The purpose of this manual is to provide general information and specific instructions on how to
install the SQ-300i Operator Interface. For configuration, network specifications and software
installation instructions please refer to the SQ-300i Automatic Voltage Control Operation Manual
(document number 8700700-M).
Communication between the SQ-300i and the operator may occur at the optional Operator
® ®
Interface. This unit runs Microsoft Windows XP (SP2) Embedded operating system, and a
proprietary software application that allows one interface to manage and display the operation of
one or more SQ-300i Microcontrollers.
B&W PGG’s touch-screen Operator Interface component offers a large, color display, with ample
room for displaying data, trending, waveforms and the navigation controls necessary to view and
edit all of the required settings for the SQ-300i. The Operator Interface has a 12-inch display that
provides 800 x 600 resolution. This panel is generally mounted in a cutout on the outside of the
electrical cabinet door. If B&W PGG has installed the Operator Interface on the AVC cabinet, no
further installation/wiring is required.
If the Operator Interface does not ship as part of an AVC cabinet, it will be shipped with an
optional power supply. This power supply is required to energize the display.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 5
Installing the SQ-300i Operator Interface
Overview
SQ-300i Operator Interface installation is typically performed by trained B&W PGG Field Service
Technicians. However, in some cases, the plant may choose to install the SQ-300i Operator
Interface. This manual will provide instructions on how to install the SQ-300i Operator Interface.
If you have questions concerning the installation, please contact your B&W PGG representative.
The SQ-300i is fully capable of communicating with a remote or local device, or operating in a
communications network through a standard Ethernet connection using Modbus TCP/IP
(Ethernet) communication.
Location Requirements
The SQ-300i Operator Interface is intended for indoor use primarily to provide a degree of
protection against contact with its enclosed circuitry and against a limited amount of falling dirt.
The Operator Interface is typically mounted in a cutout on the outside of the electrical cabinet
door.
Communication Requirements
The Operator Interface will be connected using Ethernet cabling, switches and/or routers
appropriate for the environment. The recommended cable is a high-quality Category 6 Ethernet
cable (Belkin A7L714-1000-P bulk, or equivalent). The recommended switch parts are the N-
Tron 508TX 8-port, 516TX 16-port (DIN-rail or backplane mount) or 524TX 24-port (rack-mount)
industrial-grade switches. Please consult your local IT department for plant specific network
wiring requirements.
IP address: 192.168.1.254
Subnet mask: 255.255.255.0
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 6
Installing the Operator Interface
Parts/Tools Required
Before you begin, check to make sure you have the proper parts and tools.
Parts
Qty Description
1 Operator Interface
1 Operator Interface power supply
1 Inner Bezel*
1 Outer Bezel*
1 Green power connector
6 Mounting anchors
6 1 ¼“ mounting anchor screws
Tools
Qty Description
1 Phillips-head screwdriver
1 Small flat-head screwdriver
* The bezels will be required only if you are replacing the 8700700-001B Operator Interface. The
cabinet cutout that was made for that operator interface is too large for this model (8700700-
001C) to fit securely.
1. Install the green power connector to the bottom of the operator interface.
a. Slide the male end of the connector into the green power input receptacle on the
Operator Interface.
b. Tighten the two captive screws to secure the adapter.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 7
b. Working from the back of the Operator Interface, install and secure each of the six
mounting anchors as follows:
(1) Partially thread one of the 1¼” screws provided into each of the mounting anchors.
(This will make it easier to install and secure the anchors.) Refer to Figure 1.
Figure 1
(2) Starting with one of the anchors on the top of the interface, slide the anchor into the
slots as shown in Figure 2. Then rotate the anchor back toward you until the anchor
is in position and the head of the screw is perpendicular to the back of the interface.
(3) Hold the anchor in place and tighten the screw securely to the metal cabinet facing.
(4) Repeat steps 2 and 3 to install the next anchor on the top of the interface.
(5) Repeat steps 2 and 3 to install the remaining four anchors on the sides of the
interface.
Top
mounting
anchor
Top
mounting
anchor
Slots for
mounting
anchor
Figure 2
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 8
Mounting Procedure (Replacement for 8700700-001B)
As discussed previously, the best location for the Operator Interface is in a cutout on the outside
of the electrical cabinet door. For this installation, you will need to use the supplied bezels.
1. Remove the protective covering from the front side of the outer bezel.
2. Install the green power connector to the bottom of the Operator Interface.
a. Slide the male end of the connector into the green power input receptacle on the
Operator Interface.
b. Tighten the two captive screws to secure the adapter.
Figure 3
c. Working from the back of the Operator Interface, slide the inner bezel (the piece with the
square corners) onto the back of the Operator Interface.
d. Again working from the back of the Operator Interface, install and secure each of the six
mounting anchors as follows:
i. Partially thread one of the 1¼” screws provided into each of the mounting
anchors. (This will make it easier to install and secure the anchors.) Refer to
Figure 1.
ii. Starting with one of the anchors on the top of the interface, slide the anchor into
the slots as shown in Figure 2. Then rotate the anchor back toward you until the
anchor is in position and the head of the screw is perpendicular to the back of the
interface.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 9
iii. Hold the anchor in place and tighten the screw securely to the metal cabinet
facing.
iv. Repeat steps 2 and 3 to install the next anchor on the top of the interface.
v. Repeat steps 2 and 3 to install the remaining four anchors on the sides of the
interface.
Connection Procedure
Once the Operator Interface has been mounted, refer to the installation drawings and follow the
procedure below to connect the interface to the power supply and the network.
+24V
24V Return
Figure 4
Configuration Procedure
Once the Operator Interface has been fully installed, you will need to configure it to work with the
SQ-300i controller. Please refer to the Configuring the SQ-300i Microcontroller and Operator
Interface section of the SQ-300i Automatic Voltage Control Operation Manual (document number
8700700-M).
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 10
Specifications
Operator Interface:
Dimensions ................................................... 12.9” x 10.3” x 2.1” (328 mm x 262 mm x 52 mm)
Weight .............................................................................................................. 5.46 lb. (2.48 kg)
General:
Operation Temperature ...................................................................32°F to 113°F (0°C to 45°C)
Relative Humidity (Operation or Storage) .......................10% to 90% @ 40°C, non-condensing
Vibration ......................................................................... 5 to 500 Hz, 2.0 G random for CF card
Power Input ............................................................. 10~30 V DC with phoenix power connector
Outer Bezel:
Dimensions ............................................ 13.9” x 11.4” x 0.0625” (353 mm x 290 mm x 1.6 mm)
Weight ............................................................................................................. 0.23 lbs. (0.10 kg)
Inner Bezel:
Dimensions .............................................. 13.9” x 11.4” x 0.125” (353 mm x 290 mm x 3.2 mm)
Weight ............................................................................................................. 0.46 lbs. (0.21 kg)
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 11
Appendices
Notes & Acknowledgements
All sales of B&W PGG's products or services are subject to B&W PGG's standard terms and
conditions. Those terms and conditions provide our customers with certain express warranties
for our products and services. Nothing in this booklet should be considered an express or implied
warranty. B&W PGG's products, designs and specifications are subject to change without notice.
SQ-300i is a registered trademark of Babcock & Wilcox Power Generation Group, Inc.
Microsoft and Windows are registered trademarks of Microsoft Corporation in the United States
and/or other countries.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved.
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 12
Service
USA
U.S.A. Toll-Free: (800) 336-2585
Latin America / China: (913) 284-7979
Fax: (913) 284-7949
Email: preciptech@babcock.com
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 13
Repairs
• Contact your B&W PGG representative for a Return Material Authorization (RMA) number
and instructions.
• Clean any loose dirt and dust from the product before packaging.
• Package the product securely. Use the original packaging and anti-static bags whenever
possible. Fill empty spaces with packing material to help minimize shifting during shipment.
• Please include a brief description of the problem.
• Label the outside of the package with the RMA number for quicker processing.
• Unless otherwise directed by your B&W PGG representative, send your package back to the
manufacturing site at the following address:
B&W PGG
11864 Canon Blvd.
Suite 105
Newport News, VA 23606-4223
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 14
Index
Configuration, 10 packaging, 14
Ethernet cable, 6 specifications, 11
Hardware Requirements, 6 Power Requirements, 6
Installation Safety notice, 3
new install, 7 Specifications, 11
overview, 6 SQ-300i
replacing a larger interface, 9 connect to, 10
IP address, 6 Subnet mask, 6
Location Requirements, 6 Technical support, 13
Mounting the Operator Interface, 7 Touch screen, 5
Operator interface Wiring, 10
overview, 5
© 2011 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. 8700700-001CM Rev. B 1/11 15