ACS800 FirmwareManual 28022007 PDF
ACS800 FirmwareManual 28022007 PDF
ACS800 FirmwareManual 28022007 PDF
Firmware Manual
ACS800 Motion Control Application Program 7.x
ACS800 Motion Control Application Program 7.x
Firmware Manual
Table of Contents
Table of Contents
Start-up
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
How to start-up the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
How to control the drive through the I/O interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
How to perform the ID Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
ID Run Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Control panel
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Overview of the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Panel operation mode keys and displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Status row . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Drive control with the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
How to start, stop and change direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
How to set speed reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Actual signal display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
How to select actual signals to the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
How to display the full name of the actual signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
How to view and reset the fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
How to display and reset an active fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
About the fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Parameter mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
How to select a parameter and change the value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
How to adjust a source selection (pointer) parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Function mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
How to upload data from a drive to the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
How to download data from the panel to a drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
How to set the contrast of the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Drive selection mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
How to select a drive and change its panel link ID number . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reading and entering packed boolean values on the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table of Contents
6
Table of Contents
7
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Speed control performance figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Torque control performance figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Hexagonal motor flux . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Programmable protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
AI<Min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Panel Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Position limit error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Position error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
External Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Motor Thermal Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Motor temperature thermal model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Use of the motor thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Stall Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Underload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Motor Phase Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Earth Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Communication Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Encoder signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Preprogrammed faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
DC overvoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
DC undervoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Drive temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Short circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Input phase loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Overfrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Internal fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Operation limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Supervisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Power limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Parameter lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table of Contents
8
Table of Contents
9
Application macros
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Overview of macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Factory macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Default control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
User macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Table of Contents
10
Fieldbus control
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Setting up communication through a fieldbus adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Setting up communication through the Standard Modbus Link . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Communication set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Modbus addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Setting up an Advant Fieldbus 100 (AF 100) connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Optical component types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Communication Set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Drive control parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Drive control parameters to be checked and adjusted for fieldbus control . . . . . . . . . . . . . 216
Actual Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
The fieldbus control interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
The Control Word and the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Fieldbus references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Reference handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Table of Contents
11
Block diagram: Control data input from fieldbus when a type Rxxx fieldbus adapter is used . . 221
Block diagram: Actual value selection for fieldbus when a type Rxxx fieldbus adapter is used 222
Block diagram: Control data input from fieldbus when a type Nxxx fieldbus adapter is used . . 223
Block Diagram: Actual value selection for fieldbus when a type Nxxx fieldbus adapter is used 224
Communication profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
ABB Drives communication profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Control word for ABB Drives communication profile (05.01 MAIN CONTROL WORD) . . . . 226
Status word for ABB Drives communication profile (06.01 MAIN STATUS WORD) . . . . . . 227
Generic Drive communication profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Drive commands supported by the Generic Drive communication profile . . . . . . . . . . . . . . 230
Diverse status, fault, alarm and limit words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
06.02 AUXILIARY STATUS WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
06.11 POS STATUS WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
06.12 POS STATUS WORD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
06.13 LIMIT WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
06.14 LIMIT WORD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
06.15 LIMIT WORD INV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
06.16 AUX STATUS WORD3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
07.11 FAULT WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
07.12 FAULT WORD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
07.13 FAULT WORD POS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
07.14 FAULT WORD 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
07.15 FAULT WORD 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
07.16 SYSTEM FAULT WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
07.17 INT board INIT FAUL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
07.18 INT FAULT INFO WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
07.19 INT SC INFO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
07.20 ALARM WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
07.21 ALARM WORD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
07.23 ALARM WORD 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
07.24 ALARM WORD 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
07.25 ALARM WORD 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
07.26 FAULT WORD 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Fault tracing
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Warning and fault indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
How to reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Warning messages generated by the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Warning messages generated by the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Fault messages generated by the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Table of Contents
12
Table of Contents
13
Compatibility
The manual is compatible with Motion Control Application Program version
APXR7200.
Safety instructions
Follow all safety instructions delivered with the drive.
• Read the complete safety instructions before you install, commission, or use
the drive. The complete safety instructions are given at the beginning of the
Hardware Manual.
• Read the software function specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are
given in this manual in the subsection describing the related user-adjustable
parameters.
Reader
The reader of the manual is expected to know the standard electrical wiring
practices, electronic components, and electrical schematic symbols.
Contents
The manual consists of the following chapters:
• Start-up instructs in setting up the application program, and how to start, stop and
regulate the speed of the drive.
• Control panel gives instructions for using the panel.
• Basic program features contains the basic feature descriptions and the reference
lists of the user settings and diagnostic signals.
• Motion control features contains the motion control feature descriptions.
• Application macros contains a short description of each macro together with
a connection diagram.
• Actual signals and parameters describes the actual signals and parameters of the
drive.
• Fieldbus control describes communication through the serial communication
links.
• Fault tracing lists the warning and fault messages with the possible causes and
remedies.
• Control block diagrams contains speed, torque, synchron and position control
block diagrams.
Start-up
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID Run needs to be performed during the drive start-up. (ID Run is essential
only in applications which require the ultimate in motor control accuracy.)
POWER-UP
Apply mains power. The control panel first shows the panel CDP312 PANEL Vx.xx
identification data … .......
…after which the display suggests starting the Language Selection. 1 -> 0.0 rpm O
(If no key is pressed for a few seconds, the display starts to alternate between the
Actual Signal Display and the suggestion on selecting the language.)
The drive is now ready for the start-up.
Start-up
16
Press ACT to remove the suggestion on starting the language 1 -> 0.0 rpm O
selection. SPEED 0.0 RPM
TORQUE 0.00 %
The drive is now ready for the limited start-up. MODE ACK SPEED
Enter the motor data from the motor nameplate: Note: Set the motor data
to exactly the same value
as on the motor
ABB Motors nameplate.
3 motor M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F IP 55
V Hz kW r/min A cos IA/IN t E/s
690 Y 50 30 1475 32.5 0.83
400 D 50 30 1475 56 0.83
660 Y 50 30 1470 34 0.83 380 V
380 D 50 30 1470 59 0.83 mains
415 D 50 30 1475 54 0.83
440 D 35 1770 59 0.83
voltage
60
Cat. no 3GAA 202 001 - ADA
Start-up
17
When the motor data has been entered, two displays (warning and 1 -> 0.0 rpm O
information) start to alternate. Move to next step without pressing ACS800
** WARNING **
any key.
ID MAGN REQ
Start-up
18
Start-up
19
PRELIMINARY SETTINGS
Ensure the Factory macro is active. See parameter 99.02.
Ensure the control connections are wired according to the connection See chapter Application
diagram given for the Factory macro. macros.
Ensure the drive is in external control mode. Press the LOC/REM key to In External control, there is
change between external and local control. no L visible on the first row
of the panel display.
Regulate the speed by adjusting the voltage of analogue input AI1. 1 ->1242.0 rpm I
SPEED 1242.00 rpm
TORQUE 10.00 %
MODE ACK SPEED
Start-up
20
ID Run Procedure
Note: If parameter values (Group 10 to 98) are changed before the ID Run, check
that the new settings meet the following conditions:
• 20.01 MIN SPEED < 0 rpm
• 20.02 MAX SPEED > 80% of motor rated speed
• 20.05 MAX CURRENT > 100% · Ihd
• 20.07 TORQ MAX LIM > 50%
• Ensure that the panel is in the local control mode (L displayed on the status row).
Press the LOC/REM key to switch between modes.
• Change the ID Run selection to STANDARD or REDUCED.
• Press ENTER to verify selection. The following message will be displayed on the
control panel:
1 L ->1242.0 rpm O
ACS800
**WARNING**
ID RUN SEL
• To start the ID Run, start the drive. The Run Enable signal must be active (see
parameter 10.07 RUN ENABLE).
In general it is recommended not to press any control panel keys during the ID run.
However:
• The Motor ID Run can be stopped at any time.
Start-up
21
Control panel
No. Use
ENTER 1 Start
2 Stop
7 6 3 1 3 Activate reference setting
LOC RESET REF
Control panel
22
Parameter Mode
Function Mode
Status row
The figure below describes the status row digits.
Control panel
23
Control panel
24
Control panel
25
2. To select a row (a blinking cursor indicates the selected 1 L -> 1242.0 rpm I
row). SPEED 1242.00 rpm
TORQUE 10.00 %
MODE ACK SPEED
3. To enter the actual signal selection function. ENTER 1 L -> 1242.0 rpm I
1 ACTUAL SIGNALS
06 TORQUE
10.00 %
5.a To accept the selection and to return to the Actual Signal 1 L -> 1242.0 rpm I
ENTER
Display Mode. SPEED 1242.00 rpm
CURRENT 8.00 A
MODE ACK SPEED
5.b To cancel the selection and keep the original selection. 1 L -> 1242.0 rpm I
ACT PAR
SPEED 1242.00 rpm
TORQUE 10.00 %
The selected keypad mode is entered.
FUNC DRIVE
MODE ACK SPEED
Control panel
26
1. To display the full name of the three actual signals. Hold 1 L -> 1242.0 rpm I
SPEED
ACT TORQUE
MODE ACK SPEED
2. To return to the Actual Signal Display Mode. Release 1 L -> 1242.0 rpm I
SPEED 1242.00 rpm
ACT TORQUE 10.00 %
MODE ACK SPEED
Note: The fault history cannot be reset if there are active faults or warnings.
3. To select the previous (UP) or the next fault/warning 1 L -> 1242.0 rpm I
(DOWN). 2 LAST FAULT
+DC OVERVOLT (3210)
1121 H 1 MIN 23 S
Control panel
27
WARNING! If an external source for start command is selected and it is ON, the
drive will start immediately after fault reset. If the cause of the fault has not been
removed, the drive will trip again.
Control panel
28
Parameter mode
In the Parameter Mode, the user can
• view the parameter values
• change the parameter settings.
The panel enters the Parameter Mode when the user presses the PAR key.
Note: Some parameter values cannot be changed while the drive is running. If this is
attempted, the following warning will be displayed:
**WARNING**
WRITE ACCESS DENIED
PARAMETER SETTING
NOT POSSIBLE
6b. To cancel the new setting and keep the original value, 1 L -> 1242.0 rpm O
ACT PAR
press any of the mode selection keys. 11 CONTROL PLACES
The selected mode is entered. 02 EXT1 CONTROL MODE
FUNC DRIVE
SPEED
Control panel
29
ENTER
2. To scroll between the inversion, group, index and bit 1 L ->1242.0 rpm O
fields.1) 12 DIGITAL INPUTS
04 PROGRAMMABLE DI1
[±000.000.00]
1)
Control panel
30
Function mode
In the Function Mode, the user can
• upload the drive parameter values and motor data from the drive to the panel
• download group 10 to 97 parameter values from the panel to the drive 1)
• adjust the contrast of the display.
The panel enters the Function Mode when the user presses the FUNC key.
1) The parameter groups 98, 99 and the results of the motor identification are not included by default. The restriction
prevents downloading of unfit motor data. In special cases it is, however, possible to download all. For more information,
please contact your local ABB representative.
Control panel
31
Note:
• Upload before downloading.
• Ensure the DTC software (see par. 33.01 SOFTWARE VERSION) of the
destination drive are the same as the software versions of the source drive.
• Before removing the panel from a drive, ensure the panel is in remote operating
mode (change with the LOC/REM key).
• Stop the drive before downloading.
2. Select the upload function (a flashing cursor indicates the 1 L -> 1242.0 rpm O
selected function). UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
Control panel
32
2. Ensure the drive is in local control (L shown on the first row 1 L -> 1242.0 rpm I
LOC
of the display). If necessary, press the LOC/REM key to SPEED 1242.00 rpm
REM
change to local control. TORQUE 10.00 %
MODE ACK SPEED
4. Select the download function (a flashing cursor indicates 1 L -> 1242.0 rpm O
the selected function). UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
2. Select a function (a flashing cursor indicates the selected 1 L -> 1242.0 rpm O
function). UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
5.b Cancel the new setting and retain the original value by 1 L -> 1242.0 rpm O
pressing any of the mode selection keys. ACT PAR UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
The selected mode is entered. FUNC DRIVE
Control panel
33
Note: The default ID number setting of the drive should not be changed unless the
drive is to be connected to the panel link with other drives on-line.
3. To connect to the last displayed drive and to enter another 1 L -> 1242.0 rpm I
mode, press one of the mode selection keys. ACT PAR SPEED 1242.00 rpm
TORQUE 10.00 %
FUNC
MODE ACK SPEED
The selected mode is entered.
Control panel
34
Bit 15 Bit 0
Control panel
35
Standard I/O
AF 100 Interface
Local control
The control commands are given from the control panel keypad or from the
DriveWindow PC tool when the drive is in local control. L indicates local control on
the panel display. In local mode the drive is always speed controlled.
1 L ->1242 rpm I
The control panel always overrides the external control signal sources when used in
local mode.
External control
When the drive is in external control, the commands are given through the standard
I/O terminals (digital and analogue inputs), optional I/O extension modules and/or
the fieldbus interface.
External control is indicated by a blank on the panel display.
1 ->1242 rpm I
The user can connect the control signals to two external control locations, EXT1 or
EXT2. Depending on the user selection, either one is active at a time.
Settings
Panel key Additional information
LOC/REM Selection between local and external control
Parameter
10.01 EXT1 START FUNC... Start and stop source for EXT1
10.03 EXT1 START IN2
10.04 EXT2 START FUNC... Start and stop source for EXT2
10.06 EXT2 START IN2
11.01 CNTROL PLACE SEL Selection between EXT1 and EXT2
11.02 EXT1 CONTROL MODE Control mode for external control location 1 (EXT1):
SPEED/TORQUE/MIN/MAX/ADD/POSITION/SYNCHRON.
11.03 EXT2 CONTROL MODE Control mode for external control location 2 (EXT2):
SPEED/TORQUE/MIN/MAX/ADD/POSITION/SYNCHRON.
12.01 DI/O EXT MODULE1 Activation of the optional I/O and serial communication
12.02 DI/O EXT MODULE2
12.03 DI/O EXT MODULE3
13.16 AI/O EXT MODULE
70.01 COMM MODULE LINK
70.02 COMM PROFILE
Diagnostics
Actual signals Additional information
01.01 CTRL LOCATION Active external control location: EXT1, EXT2 or Local.
06.01 MAIN STATUS WORD Selected external control location: EXT1/EXT2.
bit 11
DI1 / Std IO
...
DI7 / Std IO
DI1/ DIO ext 1
...
DI3 / DIO ext 3 Selector
n IN1
PROG DI1
... 3WIRE
PROG DI16 EXT1 Start/Stop
MAIN DS
M/F
Fb. selection
See chapter 10.01
Fieldbus control.
Master/Follower
link
CH2
DI1 / Std IO = Digital input DI1 on the standard I/O terminal block
DI1 / DIO ext 1 = Digital input DI1 on the digital I/O extension module 1
PROG DI1 = Programmable digital input DI1
The figure below shows the parameters that select the control location EXT1/EXT2.
Selector
n
SPEED
TORQUE
MIN
11.02 EXT1 Switch
MAX
ADD CONTROL
POSITION MODE
SYNCHRON
Selector EXT1/EXT2
n
11.01
11.03 EXT2 CNTROL PLACE SEL
CONTROL
MODE
It is possible to scale the external reference so that the signal minimum and
maximum values correspond to a speed other than the minimum and maximum
speed limits.
Selection Torque Speed Position Synchron
reference reference reference reference
NOT SEL 0% = 0% 0 rpm = 0 rpm - -
AI1 100% = 100% 100% =
AI2 of the nominal parameter 19.01
motor torque value
AI3
EXT AI1
EXT AI2
MAIN DS REF1 10000 = 100% 20000 =
MAIN DS REF2 of the nominal parameter 19.01
motor torque value
AUX DS REF1
AUX DS REF2
AUX DS REF3
M/F REF1 See parameters
19.12...19.15
and group 41
SYNCHRON
REFERENCE
M/F REF2 -
PROG AI1-7 10000 = 100% 20000 = -
parameter 19.01
value
MEASURED SPEED - 1 rpm = 1 rpm
ENC2 See parameters
19.12...19.14
and group 41
SYNCHRON
REFERENCE
ENC 2 SYNC GEAR -
ZERO - - 0=0
POS REF TABLE See parameters
19.12...19.14
MAIN DS REF12 See parameters
19.12...19.15
PROG AI1 - - See parameters -
19.12...19.15
PROG AI6 - - - See parameters
19.12...19.15
and group 41
SYNCHRON
REFERENCE
Settings
Parameter Additional information
Group 11 CONTROL PLACES Control mode selection
Group 19 SIGNAL CALC Speed scaling etc.
Group 21 SPEED REFERENCE Speed reference source, type and scaling
Group 22 ACCEL/DECEL Speed reference acceleration and deceleration ramps
Group 24 TORQUE CONTROL Torque reference ramp times
Group 32 SUPERVISION Reference supervision
Group 40 POS REFERENCE Position reference
Group 41 SYNCHRON REFERENCE Synchron reference
Diagnostics
Actual signal Additional information
Groups 03 CONTROL VALUES and Reference values in different stages of the reference
04 POS CTRL VALUES processing chain
Parameter
Group 14 RELAY OUTPUTS Active reference / reference loss through a relay output
Group 15 ANALOGUE OUTPUTS Reference value
Settings
Parameter Additional information
Group 13 ANALOGUE INPUTS Processing of the standard inputs
21.02....21.04 SPEED REF1...3 AI as speed reference source
24.01...24.03 TORQ REF1...2 AI as torque reference source
28.07 START TORQ REF SEL AI in a mechanical brake control function
Group 35 MOT TEMP MEAS AI in a motor temperature measurement
40.12 POS SPEED MUL SEL AI as positioning speed multiplier source
Diagnostics
Actual value Additional information
02.01 AI1 [V] Values of standard inputs
02.03 AI2 [mA]
02.05 AI3 [mA]
02.07 EXT AI1 [mA] Values of optional inputs
02.09 EXT AI2 [mA]
02.02 AI1 SCALED Scaled analogue input values
02.04 AI2 SCALED
02.06 AI3 SCALED
02.08 EXT AI1 SCALED
02.10 EXT AI2 SCALED
06.07 AI SUP STATUS
Warning
AI < MIN FUNC Analogue control signal below minimum allowed value
Fault
I/O COMM ERR Communication loss to I/O
Settings
Parameter Additional information
13.16 AI/O EXT MODULE Communication to analogue I/O extension module
(optional)
Group 15 ANALOGUE OUTPUTS AO value selection and processing (standard outputs)
Group 35 MOT TEMP MEAS AO in motor temperature measurement
Note: If motor 1 temperature measurement is selected by parameter 35.01, analogue output AO1
value is set to a constant current value.
Any actual signal can be selected as the source for analogue output. See section
Actual signals on page 46.
Diagnostics
Actual value Additional information
02.11 AO1 [mA], 02.12 AO2 [mA] Values of the standard outputs
02.13 EXT AO1 [mA], 02.14 EXT AO2 [mA] Values of the optional outputs
Warning
POINTER ERROR Source selection (pointer) parameter points to a
non-existing parameter index.
Fault
I/O COMM ERR Communication loss to I/O
Settings
Parameter Additional information
Group 10 START/STOP DI as start/stop, run enable and reset signal source
11.01 CNTROL PLACE SEL DI as external control EXT1/EXT2 change signal source
Group 12 DIGITAL INPUTS Processing of the inputs
16.03 USER MACRO IO CHG DI as external user macro change signal source
Group 20 LIMITS DI as speed reference enable command / torque limit source
Group 21 SPEED REFERENCE DI as speed reference selection signal source
22.01 ACC/DEC SEL DI as acceleration and deceleration time selection signal source
23.04 PI PAR 1/2 SEL DI as PI controller parameter set 1/2 selection signal source
24.04 TORQ REF NEG SEL DI as torque reference inversion signal source
28.02 BRAKE ACKNOWLEDGE DI as mechanical brake acknowledgement signal source
30.02 EXTERNAL FAULT DI as external fault source
30.04 MOT THERM P MODE DI in motor overtemperature supervision
Group 40 POS REFERENCE DI as positioning reference source
42.03 DYN LIM ENA DI as dynamic limiter enable command source
Group 43 HOMING DI as homing control signal source
Diagnostics
Actual value Additional information
06.04 RMIO DI STATUS Values of the standard digital inputs
06.05 EXT DI STATUS Values of the optional digital inputs
06.06 PROG DI STATUS Values of programmable digital inputs
Warning
POINTER ERROR Source selection (pointer) parameter points to a non-existing
parameter index.
Fault
I/O COMM ERR Communication loss to I/O
Settings
Parameter Additional information
Group 14 RELAY OUTPUTS RO value selections
12.01 DI/O EXT MODULE1 Activation of optional relay outputs
12.02 DI/O EXT MODULE2
12.03 DI/O EXT MODULE3
Any actual signal can be selected as the source for relay output. See section Actual
signals on page 46.
Diagnostics
Actual value Additional information
06.09 RMIO RO STATUS Standard relay output states
06.10 EXT RO STATUS Optional relays output states
Warning
POINTER ERROR Source selection (pointer) parameter points to a non-existing
parameter index.
Fault
I/O COMM ERR Communication loss to I/O
Actual signals
Several actual signals are available, including
• drive output frequency, current, voltage and power
• motor speed and torque
• mains voltage and intermediate circuit DC voltage
• active control location (Local, EXT1 or EXT2)
• reference values
• drive temperature
• operating time counter (h), kWh counter
• digital I/O and Analogue I/O status.
Three signals can be shown simultaneously on the control panel display. It is also
possible to read the values through the serial communication link or through the
analogue/relay outputs.
Settings
Parameter Additional information
Group 10 START/STOP Actual signal as start / stop / run enable signal
11.01 CNTROL PLACE SEL Actual signal as external control EXT1/EXT2 change signal
Group 14 RELAY OUTPUTS Selection of an actual signal to a relay output
Group 15 ANALOGUE Selection of an actual signal to an analogue output
OUTPUTS
16.03 USER MACRO IO CHG Actual signal as external user macro change signal
Group 20 LIMITS Actual signal as speed reference enable command / torque limit
Group 21 SPEED REFERENCE Actual signal as speed reference selection signal
22.01 ACC/DEC SEL Actual signal as acceleration and deceleration time selection signal
23.04 PI PAR 1/2 SEL Actual signal as PI controller parameter set 1/2 selection signal
24.04 TORQ REF NEG SEL Actual signal as torque reference inversion signal
26.04 FLUX REF PTR Actual signal as flux reference
28.02 BRAKE ACKNOWLEDGE Actual signal as mechanical brake acknowledgement signal
30.02 EXTERNAL FAULT Actual signal as external fault signal
30.04 MOT THERM P MODE Actual signal in motor overtemperature supervision
Group 32 SUPERVISION Actual signal in supervision
Group 40 POS REFERENCE Actual signal as positioning reference
42.03 DYN LIM ENA Actual signal as dynamic limiter enable command
Group 43 HOMING Actual signal as homing control signal
Group 92 DSET TR ADDR Selection of an actual signal to a dataset (serial communication)
Diagnostics
Actual value Additional information
Groups 01 ACTUAL SIGNALS… Lists of actual signals
07 ALARMS AND FAULTS
Motor identification
The performance of Direct Torque Control is based on an accurate motor model
determined during the motor start-up.
A motor Identification Magnetisation is automatically done the first time the start
command is given. During this first start-up, the motor is magnetised at zero speed
for several seconds to allow the motor model to be created. This identification
method is suitable for most applications.
In demanding applications a separate Identification Run can be performed.
Settings
Parameter 99.08 ID RUN
Umains
TM fout UDC
(Nm) (Hz) (Udc) UDC
160 80 520
120 60 390
fout
80 40 260
TM
40 20 130
t(s)
1.6 4.8 8 11.2 14.4
UDC= Intermediate circuit voltage of the drive, fout = output frequency of the drive,
TM = Motor torque
Loss of supply voltage at nominal load (fout = 40 Hz). The intermediate circuit DC voltage drops to the
minimum limit. The controller keeps the voltage steady as long as the mains is switched off. The drive
runs the motor in generator mode. The motor speed falls but the drive is operational as long as the
motor has enough kinetic energy.
Note: Cabinet assembled units equipped with main contactor option have a “hold
circuit” that keeps the contactor control circuit closed during a short supply break.
The allowed duration of the break is adjustable. The factory setting is five seconds.
Automatic Start
Since the drive can detect the state of the motor within a few milliseconds, the
starting is immediate under all conditions. There is no restart delay. E.g. the starting
of turbining pumps or windmilling fans is easy.
Settings
Parameter 10.11 START FUNCTION
DC Magnetising
When DC Magnetising is activated, the drive automatically magnetises the motor
before starting. This feature guarantees the highest possible breakaway torque, up
to 200% of motor nominal torque. By adjusting the premagnetising time, it is possible
to synchronise the motor start and e.g. a mechanical brake release. The Automatic
Start feature and DC Magnetising cannot be activated at the same time.
Settings
Parameters 10.11 START FUNCTION and 10.12 CONST DC MAGN TIME
Flux Braking
The drive can provide greater deceleration by raising the level of magnetisation in
the motor. By increasing the motor flux, the energy generated by the motor during
braking can be converted to motor thermal energy. This feature is useful in motor
power ranges below 15 kW.
Motor TBr
speed TN (%)
TBr = Braking torque
No Flux Braking 60 TN = 100 Nm
40
Flux Braking
20
Flux Braking No Flux Braking
t (s) f (Hz)
50 Hz / 60 Hz
2
40 3
4
5
0 f (Hz)
5 10 20 30 40 50
The drive monitors the motor status continuously, also during the Flux Braking.
Therefore, Flux Braking can be used both for stopping the motor and for changing
the speed. The other benefits of Flux Braking are:
• The braking starts immediately after a stop command is given. The function does
not need to wait for the flux reduction before it can start the braking.
• The cooling of the motor is efficient. The stator current of the motor increases
during the Flux Braking, not the rotor current. The stator cools much more
efficiently than the rotor.
Settings
Parameter 26.02 FLUX BRAKING
Flux Optimisation
Flux Optimisation reduces the total energy consumption and motor noise level when
the drive operates below the nominal load. The total efficiency (motor and the drive)
can be improved by 1...10%, depending on the load torque and speed.
Settings
Parameter 26.01 FLUX OPTIMIZATION
Settings 2 t (s)
n
nN
%
A B C D
A: Undercompensated t
B: Normally tuned (autotuning)
C: Normally tuned (manually). Better dynamic performance than with B
D: Overcompensated speed controller
The figure below is a simplified block diagram of the speed controller. The controller
output is the reference for the torque controller.
Derivative
acceleration
compensation
Proportional,
integral + Torque
Speed + Error +
reference - value + reference
Derivative
Settings
Parameter groups 23 SPEED CTRL and 20 LIMITS
Diagnostics
Actual signal 01.03 SPEED
10
< 5 ms t(s)
TN = rated motor torque
Tref = torque reference
Tact = actual torque
Settings
Parameter 26.03 HEX FIELDWEAKENING
AI<Min
AI<Min function defines the drive operation if an analogue input signal falls below the
preset minimum limit.
Settings
Parameters 13.28 AI MIN FUNCTION and 13.29 AI MIN ACTIVATION
Panel Loss
Panel Loss function defines the operation of the drive if the control panel selected as
control location for the drive stops communicating.
Settings
Parameter 30.01 PANEL LOSS
Position error
The position error supervision is active in Position and Synchron modes. The drive is
tripped on a fault if the position error is exceeded.
Settings
Parameter 32.10 POS ERROR WINDOW
External Fault
External Faults can be supervised by defining one digital input as a source for an
external fault indication signal.
Settings
Parameter 30.02 EXTERNAL FAULT
50
Temp. t Zero speed load
rise
Speed
100%
63%
t
Motor thermal time
Note: It is also possible to use the motor temperature measurement function. See
sections Motor temperature measurement through the standard I/O on page 58 and
Motor temperature measurement through an analogue I/O extension on page 60.
Stall Protection
The drive protects the motor in a stall situation. It is possible to adjust the supervision
limits (frequency, time) and choose how the drive reacts to the motor stall condition
(warning indication / fault indication & stop the drive / no reaction).
Settings
Parameters 30.09 STALL FUNCTION...30.11 STALL TIME
Underload Protection
Loss of motor load may indicate a process malfunction. The drive provides an
underload function to protect the machinery and process in such a serious fault
condition. Supervision limits - underload curve and underload time - can be chosen
as well as the action taken by the drive upon the underload condition (warning
indication / fault indication & stop the drive / no reaction).
Settings
Parameters 30.12 UNDERLOAD FUNC...30.14 UNDERLOAD CURVE
Communication Fault
The Communication Fault function supervises the communication between the drive
and an external control device (e.g. a fieldbus adapter module).
Settings
Parameters 70.03 COMM MOD FLT FUNC and 70.07 MAIN DS TIMEOUT
Encoder signal
It is possible to choose how the drive reacts when encoder phase signal is missing
(warning indication / fault indication & stop the drive / no reaction).
Note: This supervision is only for RTAC-03.
Settings
Parameters 50.05 ENC1 CABLE CHECK and 50.15 ENC2 CABLE CHECK
Preprogrammed faults
Overcurrent
The overcurrent trip limit for the drive is 1.65 to 2.17 · Imax depending on the drive
type.
DC overvoltage
The DC overvoltage trip limit is 1.3 ·U1max, where U1max is the maximum value of the
mains voltage range. For 400 V units, U1max is 415 V. For 500 V units, U1max is
500 V. For 690 V units, U1max is 690 V. The actual voltage in the intermediate circuit
corresponding to the mains voltage trip level is 728 VDC for 400 V units, 877 VDC
for 500 V units, and 1210 VDC for 690 V units.
DC undervoltage
The DC undervoltage trip limit is 0.65 · U1min, where U1min is the minimum value of
the mains voltage range. For 400 V and 500 V units, U1min is 380 V. For 690 V units,
U1min is 525 V. The actual voltage in the intermediate circuit corresponding to the
mains voltage trip level is 334 VDC for 400 V and 500 V units, and 461 VDC for
690 V units.
Drive temperature
The drive supervises the inverter module temperature. There are two supervision
limits: warning limit and fault trip limit.
Short circuit
There are separate protection circuits for supervising the motor cable and the
inverter short circuits. If a short circuit occurs, the drive will not start and a fault
indication is given.
Ambient temperature
The drive will not start and a fault indication CTRL B TEMP is given if the ambient
temperature is above 88°C.
Overfrequency
If the drive output frequency exceeds the preset level, the drive is stopped and a
fault indication is given. The preset level is 50 Hz over the operating range absolute
maximum speed limit.
Internal fault
If the drive detects an internal fault, the drive is stopped and a fault indication is
given.
Operation limits
ACS800 has adjustable limits for speed, current (maximum), torque (maximum) and
DC voltage.
Settings
Parameter group 20 LIMITS
Supervisions
The drive monitors whether certain user selectable variables are within the
user-defined limits. The user may set limits for speed, current etc.
Settings
Parameter group 32 SUPERVISION
Diagnostics
Signals/Parameters Additional information
Group 06 STATUS WORDS Supervision limit indicating bits in a packed boolean word
Group 14 RELAY OUTPUTS Supervision limit indication through a relay output
Group 92 DSET TR ADDR Selection of an actual signal to a dataset
Power limit
The maximum allowed motor power is 1.5 · Phd or Pcont whichever value is greater
(varies depending on the drive type). If the limit is exceeded, the motor torque is
automatically restricted. The function protects the input bridge of the drive against
overload.
Parameter lock
The user can prevent parameter adjustment by activating the parameter lock.
Settings
Parameters 16.01 PARAMETER LOCK and 16.02 PASS CODE
AI1+
Motor AI1-
T T T
AO1+
AO1-
10 nF
(>630 VAC)
WARNING! According to IEC 664, the connection of the motor temperature sensor
to the RMIO board, requires double or reinforced insulation between motor live parts
and the sensor. Reinforced insulation entails a clearance and creepage distance of
8 mm (400 / 500 VAC equipment). If the assembly does not fulfil the requirement,
• the RMIO board terminals must be protected against contact and they may not be
connected to other equipment
or
• the temperature sensor must be isolated from the RMIO board terminals.
Settings
Parameter Additional information
35.01 MOT 1 TEMP AI1 SEL Settings of motor 1/2 temperature measurement
…35.03 MOT 1 TEMP FLT L
35.04 MOT 2 TEMP AI1 SEL
…35.06 MOT 2 TEMP FLT L
Other
Parameters 13.01 AI1 MIN to 13.05 AI1 FILT TIME (AI1 processing) and 15.01 RMIO AO1 FUNC to
15.07 RMIO AO1 FILTER TIME (AO1 processing) are not effective.
Note: If motor 1 temperature measurement is selected by parameter 35.01, analogue output AO1
value is set to a constant current value.
At the motor end the cable shield should be earthed through a 10 nF capacitor. If this is not possible,
the shield is to be left unconnected.
Diagnostics
Actual values Additional information
01.18 MOTOR 1 TEMP Temperature value
01.19 MOTOR 2 TEMP
07.20 ALARM WORD 1 Warning bit state (T MEAS ALM)
07.14 FAULT WORD 4 Fault bit states (MOTOR 1/2 TEMP)
07.23 ALARM WORD 4 Warning bit states (MOTOR 1/2 TEMP)
Warnings
MOTOR 1 TEMP / Excessive motor temperature
MOTOR 2 TEMP
T MEAS ALM Motor temperature measurement out of acceptable range
Faults
MOTOR 1 TEMP / Excessive motor temperature
MOTOR 2 TEMP
RAIO module
One sensor
AI1+
Motor
AI1-
T
AO1+
AO1-
10 nF
(> 630 VAC)
SHLD
AI1+
Motor AI1-
T T T
AO1+
AO1-
10 nF
(> 630 VAC)
SHLD
WARNING! According to IEC 664, the connection of the motor temperature sensor
to the RAIO module, requires double or reinforced insulation between motor live
parts and the sensor. Reinforced insulation entails a clearance and creepage
distance of 8 mm (400 / 500 VAC equipment). If the assembly does not fulfil the
requirement,
• the RAIO module terminals must be protected against contact and they may not
be connected to other equipment
or
• the temperature sensor must be isolated from the RAIO module terminals.
Settings
Parameter Additional information
35.01 MOT 1 TEMP AI1 SEL Settings of motor 1/2 temperature measurement
…35.03 MOT 1 TEMP FLT L
35.04 MOT 2 TEMP AI1 SEL
…35.06 MOT 2 TEMP FLT L
35.08 AI/O MOTOR TEMP Activation of optional analogue I/O for motor temperature
measurement
Other
Parameters 13.16 AI/O EXT MODULE1 to 13.20 EXT AI1 MAX SCALE (EXT AI1 processing) and
15.15 EXT AO1 FUNC to 15.21 EXT AO1 FILTER TIME (EXT AO1 signal selection and processing)
are not effective.
Note: If motor 1 temperature measurement is selected by parameter 35.01, analogue output AO1
value is set to a constant current value.
At the motor end the cable shield should be earthed through a 10 nF capacitor. If this is not possible,
the shield is to be left unconnected.
Diagnostic
Actual values Additional information
01.18 MOTOR 1 TEMP Temperature value
01.19 MOTOR 2 TEMP
07.20 ALARM WORD 1 Warning bit state (T MEAS ALM)
07.14 FAULT WORD 4 Fault bit states (MOTOR 1/2 TEMP)
07.23 ALARM WORD 4 Warning bit states (MOTOR 1/2 TEMP)
Warnings
MOTOR 1 TEMP / Excessive motor temperature
MOTOR 2 TEMP
T MEAS ALM Motor temperature measurement out of acceptable range
Faults
MOTOR 1 TEMP / Excessive motor temperature
MOTOR 2 TEMP
Example
The figure below shows a brake control application example.
WARNING! Make sure that the machinery into which the drive with brake control
function is integrated fulfils the personnel safety regulations. Note that the frequency
converter (a Complete Drive Module or a Basic Drive Module, as defined in IEC
61800-2), is not considered as a safety device mentioned in the European
Machinery Directive and related harmonised standards. Thus, the personnel safety
of the complete machinery must not be based on a specific frequency converter
feature (such as the brake control function), but it has to be implemented as defined
in the application specific regulations.
7 +24 V
1 5
Start command
External speed
reference
Inverter modulating 7
2
Motor magnetised tmd
tcd
Open brake
command
4
Internal speed
reference (actual tod 3 6
motor speed) ncs
Torque reference
Ts
time
Ts Start torque at brake release (parameters 28.07 START TORQ REF SEL and 28.08
START TORQ REF)
tmd Motor magnetising delay
tod Brake open delay (parameter 28.03 BRAKE OPEN DELAY)
ncs Brake close speed (parameter 28.05 ABS BRAKE CLS SPD)
tcd Brake close delay (parameter 28.04 BRAKE CLOSE DELAY)
State shifts
From any state
1) (rising edge)
NO
MODULATION 0/0/1
2)
OPEN
BRAKE 1/1/1
3)
A
5)
RELEASE RFG
INPUT 1/1/0
4)
RFG INPUT
TO ZERO 1/1/1
7)
10)
6)
11) CLOSE
BRAKE 0/1/1
RFG = Ramp Function 12)
A
Generator in the speed 13)
control loop (reference 8) 9)
handling).
BRAKE
ACK FAULT 0/0/1
State (Symbol NN )
X/Y/Z
- NN: State name
- X/Y/Z: State outputs/operations
X = 1 Open the brake. The relay output set to brake on/off control energises.
Y = 1 Forced start. The function keeps the internal Start on until the brake is closed in spite of the
status of the external Start signal.
Z=1 Ramp in zero. Forces the used speed reference (internal) to zero along a ramp.
Settings
Parameter Additional information
Group 28 BRAKE CTRL Brake function settings
Diagnostics
Actual value Additional information
05.01 MAIN CONTROL Ramp in zero bit
WORD
06.16 AUX STATUS State of bit “brake open/close command“
WORD 3
07.14 FAULT WORD 4 Fault bit state
07.23 ALARM WORD 4 Warning bit state
Warnings
BRAKE ACKN Unexpected state of brake acknowledge signal
Faults
BRAKE ACKN Unexpected state of brake acknowledge signal
External control
External control
signals
signals
n 3 n 3
Supply Supply
3 3
Master/Follower
Follower fault 2 2 Link Follower fault 2 2 Master/Follower
supervision supervision Link
3 3
Supply Supply
3
3
External control
signals
n 3
Supply
3
Follower fault 2 2 Master/Follower
supervision Link
3
Supply
3
Settings
Parameter Additional information
Group 11 CONTROL PLACES Control mode selection
Group 21 SPEED REFERENCE Speed control settings
Group 23 SPEED CTRL
Group 24 TORQUE CONTROL Torque control settings
Groups 40 POS REFERENCE...49 Position/Synchron control settings
POS PAR TABLE
Diagnostics
Actual signal Additional information
01.02 CTRL MODE ACK Active control mode
n
NOT SEL
AI1
AI2
AI3 Selector
21.02
EXT AI1
EXT AI2 Selector 21.05 21.06 E
MAIN DS REF1 + A
MAIN DS REF2 n + 0 0 A
AUX DS REF1 E
AUX DS REF2 21.01 B 0 1 B
AUX DS REF3
C 1 0 C
M/F REF1 21.07
M/F REF2 21.03
D 1 1 D
MEASURED SPEED 21.08
ENC2 Selector
ENC2 SYNC GEAR
PROG AI1...AI7 n Limiter
Switch
SPEED
REF
INPUT
21.04 NEG 03.01
20.03, 20.04
21.09
Settings
Parameter Additional information
Group 21 SPEED REFERENCE Speed reference selection
Diagnostics
Actual signal Additional information
Group 01 ACTUAL SIGNALS Basic signals for monitoring of the drive
Group 03 CONTROL VALUES Speed and torque reference monitoring signals.
Selector
NOT SEL
AI1 n
AI2
AI3
EXT AI1 Selector
EXT AI2 24.03
MAIN DS REF1
MAIN DS REF2 Selector
+
AUX DS REF1
AUX DS REF2 +
n
AUX DS REF3 24.01
M/F REF1 Limiter
M/F REF2
MEASURED SPEED 24.02
ENC2 Switch
ENC2 SYNC GEAR
PROG AI1...AI7
NEG
20.03, 20.04 Ramp
24.04
Limiter
TOR REF1
TORQ RAMP UP 24.05
03.09
TORQ RAMP DOWN 24.06
300%
-300%
Settings
Parameter Additional information
Group 24 TORQUE CONTROL Torque reference selection
Diagnostics
Actual signal Additional information
Group 01 ACTUAL SIGNALS Basic signals for monitoring of the drive
Group 03 CONTROL VALUES Speed and torque reference monitoring signals.
Reference
40.11 POS REF
table: EXTERNAL/ FILT TIME
groups Selector LOCAL
45...49 DISTANCE
SWITCH POS INTERP
0 INPUT TO TRGET
START +
4.05 4.07
PROG AI1
. FUNCTION
+
Fieldbus . 40.04 POS 40.04 POS
START FUNC
reference REF SEL
LOCAL:
SPEED
19.15 CONTROLLED
POSITION SCALING SYNCHRON
ERROR
Control panel / 4.11
DriveWindow
FEEDRATE OVERRIDE, correction factor for the positioning speed (par. 40.11)
Settings
Parameter Additional information
Group 40 POS REFERENCE Position reference selection
Groups 45 POS REF TABLE... Position reference set selection
49 POS PAR TABLE
Diagnostics
Actual signal Additional information
Group 04 POS CTRL VALUES Position monitoring signals
06.11 POS SATUS WORD 1 Position status word
06.12 POS SATUS WORD 2
Parameters 40.01 POS ENABLE SEL and 40.03 POS START SEL control the
operation of the position profile generator. The following figure shows the positioning
commands and signals when parameter 40.02 POS START FUNC is set to
NORMAL.
The following figure shows the positioning commands and signals when parameter
40.02 POS START FUNC is set to PULSE.
Reference sets
The reference table contains 16 reference sets. Each reference set consists of
• position reference
• positioning speed reference
• positioning acceleration reference
• positioning deceleration reference
• position profile generator control signals.
The table below shows how reference sets 1...16 are selected with parameters
40.06 POS TABLE SEL1...40.09 POS TABLE SEL4. The references sets are
defined by parameter groups 45 POS REF TABLE to 49 POS PAR TABLE. One set
is used at a time.
Par 40.09 Par 40.08 Par 40.07 Par 40.06 Function
0 0 0 0 Reference set 1
0 0 0 1 Reference set 2
0 0 1 0 Reference set 3
0 0 1 1 Reference set 4
0 1 0 0 Reference set 5
0 1 0 1 Reference set 6
0 1 1 0 Reference set 7
0 1 1 1 Reference set 8
1 0 0 0 Reference set 9
1 0 0 1 Reference set 10
1 0 1 0 Reference set 11
1 0 1 1 Reference set 12
1 1 0 0 Reference set 13
1 1 0 1 Reference set 14
1 1 1 0 Reference set 15
1 1 1 1 Reference set 16
The table below shows the POINTER REF set by parameter 40.04 POS REF SEL.
Reference PROG AI FbEq
position reference PROG AI1 See par. 19.15
positioning speed reference PROG AI2 See par. 19.01
positioning acceleration reference PROG AI3 1 = 0.1 rev/s2
positioning deceleration reference PROG AI4 1 = 0.1 rev/s2
position profile generator control signals PROG AI5 1=1
Switch Synchron
gear
ENC2
M/F REF1
SYNC GEAR INPUT
VIRTUAL MAST 04.09 x SYNC POS REF
PROG AI6 y 04.08
SYNC GEAR NUM
41.02
41.01 SYNC GEAR DEN
41.03
SYNC POS REF SEL
Settings
Parameter Additional information
Group 41 SYNCHRON REFERENCE Synchron reference selection
Diagnostics
Actual signal Additional information
Group 04 POS CTRL VALUES Position monitoring signals
06.11 POS SATUS WORD 1 Position status
06.12 POS SATUS WORD 2
Dynamic limiter
Dynamic limiter controls the position reference ramping in the position control and
synchron control modes. Dynamic limitation of the position reference causes a
synchron error (04.11 SYNCHRON ERROR). The error is accumulated and fed back
to the position profile generator.
Settings
Parameter Additional information
42.03 DYN LIM ENA Dynamic limiter enabling
Diagnostics
Actual signal Additional information
06.11 POS STATUS WORD 1 bit 12 Dynamic limiter enable
Homing control
Homing control is usually needed in positioning applications. The internal actual
position is set to zero at power-up (the physical position of the motor is not
changed). Normally, before first homing, the actual position of the driven machinery
does not correspond to the internal zero position in the drive position control.
Homing establishes a correspondence between these two positions. Incremental
encoder is needed in homing control.
Besides the standard homing procedure (sequential logic), which is normally
performed only once after the drive power-up, there are three cyclic position system
correction functions and three preset functions available. The cyclic functions can be
used e.g. to compensate position errors due to slip between the load and motor side.
The preset functions are used to set the position system according to a parameter
value or actual position.
It is also possible to execute positioning directly after the standard homing position
latch or to enable/disable actual position latch during homing.
Because all homing functions use the same latching function, only one can be
performed at a time. In applications where two functions are required, the user can
switch on-line between two selected functions.
Standard homing
The homing procedure can be started from any operating mode when the drive is
running. Homing is started by the rising edge (OFF to ON) of the input selected with
parameter 43.04 HOMING START SEL. The signal has to stay ON for the duration of
the whole procedure. Parameter 43.10 SPEED REF HOMING selects the speed
reference for the homing. When the latching conditions are fulfilled (43.05 LATCH
POS ACT SEL), the drive sets the position system to the value of parameter 43.09
HOME POSITION and returns to the original operating mode. The following figure
illustrates the sequential logic of standard homing.
RUNNING
The behaviour of the drive after the homing procedure depends on the previous
active operating mode:
Previous mode Behaviour
TORQUE Previous torque reference is used immediately.
or
If the selected position start source is ON and the position profile generator
is enabled: The motor runs to the selected position target reference using
the selected dynamic parameter set in the reference table. See parameter
groups 46 POS SPEED TABLE...48 POS DEC TABLE.
Dependent on the positioning format and parameter 41.04 SYNCHRON
SYNCHRON FUNC setting. Generally, the follower motor is synchronised with the master
motor using the dynamic limiter settings.
Example 1: Proximity switch signal (43.05 LATCH POS ACT SEL) is zero when
homing is started.
Parameter Setting Information
19.13 POS UNIT REVOLUTIONS All position values are in revolutions.
19.12 POSITION FORMAT LINEAR Positioning is between minimum position 42.02
POSITION MIN and maximum position 42.01
POSITION MAX.
43.01 HOMING MODE SEL FALSE Homing mode according to par. 43.02 HOMING
MODE 1
43.02 HOMING MODE1 STANDARD Sequential homing logic
43.04 HOMING START SEL DI5 Source of the start command
43.05 LATCH POS ACT SEL DI6 Source of the actual position latching command
(proximity switch signal source)
43.09 HOME POSITION 0 rev Home position
43.10 SPEED REF HOMING -150 rpm Speed reference
Example 2: Proximity switch signal (43.05 LATCH POS ACT SEL) is ON when
homing is started. See parameter settings in example 1 above.
Preset functions
With preset function the actual position of the driven machinery is set to the
requested preset position value. The physical position of the driven machinery is not
changed, but the new position value is used as home position.
There are three different preset functions:
Position system of the driven machinery is set to the value defined by
• 04.02 POSITION ACT VAL (= actual encoder position).
• 04.09 GEAR INPUT (= synchron control reference for the synchron gear). See
chapter Control block diagrams.
• 43.09 HOME POSITION.
Pre-latch function
Pre-latch function is used to enable or disable the actual position latch. Actual
position latch is allowed only after the pre-latch signal is activated. This function is
used for example in standard homing when encoder zero pulse is used for latching.
The source for the pre-latch signal is selected by parameter 43.12 PRE LATCH POS
ACT. If parameter value is set to FALSE, actual position latch is disabled.
Example:
Digital input DI4 is defined as pre-latch source and digital input DI6 as actual position
latch source. When pre-latch signal is zero, actual position latch command has no
effect. When pre-latched signal is active (0->1), the next rising edge of the digital
input DI6 ends the homing.
Parameter Setting Information
19.13 POS UNIT REVOLUTIONS All position values are in revolutions.
19.12 POSITION LINEAR Positioning is between minimum position 42.02
FORMAT POSITION MIN and maximum position 42.01
POSITION MAX.
43.01 HOMING MODE FALSE Homing mode according to parameter 43.02
SEL HOMING MODE 1
43.02 HOMING MODE1 STANDARD Sequential homing logic
43.04 HOMING START DI5 Source of the start command
SEL
43.05 LATCH POS ACT DI6 Source of the actual position latching command
SEL (proximity switch signal source)
43.09 HOME POSITION 0 rev Home position
43.10 SPEED REF -150 rpm Speed reference
HOMING
43.12 PRE LATCH POS DI4 Source of the pre-latch command
ACT
43.13 PRELATCH PULSE First rising edge of the input selected by parameter
FUNCTION 43.12 PRE LATCH POS ACT activates the pre-latch.
t1 t2
MASTER FOLLOWER
(motor) (load) Digital input DI5
90
Proximity switch DI5 04.16 LATCHED MAS REF -30
60° 360 = 0
04.17 CYCLIC POSIT ERR
t1 Position ref.90° 330
0
04.11 SYNCHRON ERROR
x°
t2
x° - 30°
X°- 30°
t1: Rising edge of digital input DI5 signal (proximity switch signal) is detected when
the master (motor) position should be 60°. The used position reference is 90° (stored
to signal 04.16 LATCHED MAS REF).
The Master Reference Correction function calculates the position error 04.17
CYCLIC POSIT ERR, which is the difference between the master (motor) position
and the reference position:
04.17 CYCLIC POSIT ERR = 43.08 POS MAS PROBE - 04.16 LATCHED MAS REF
= 60° - 90° = -30°
The error is added to 04.11 SYNCHRON ERROR. The synchron error is corrected
using the positioning parameter and the dynamic limiter settings.
t2: Error has been corrected and the follower (load) is in line with the master (motor).
Cyclic function is ready for a new correction if necessary.
DI1 M
3~
PROXIMITY
90° SWITCH
t1
Example 1:
The following figure shows a conveyer system where a box should be positioned.
The conveyer belt is marked every 40 mm.
ACS 600
40 mm
M
3~
PROXIMITY
SWITCH
Note: Only after the active correction is finished, the next position latching is
enabled.
Example 2: Rollover axis application. Master and follower proximity switches are
located at 0°.
Parameter Setting Information
19.12 POSITION FORMAT ROLLOVER AXIS Positioning is between 0 and 1 revolutions, i.e. after
360°, the position calculation starts from 0° again.
19.13 POS UNIT DEGREE All position values are in degrees.
41.02 SYNC GEAR NUM Same as for 41.03 Synchron gear ratio is 1.
SYNC GEAR DEN
43.01 HOMING MODE SEL FALSE Homing mode according to parameter 43.02
HOMING MODE 1
43.02 HOMING MODE1 CORR M/F DIST Cyclic master/follower distance correction
43.05 LATCH POS ACT SEL DI6 Source of the actual position latching command
(proximity switch signal source)
43.06 LATCH MAS REF SEL DI5 Source of the master position reference latching
command (proximity switch signal source)
43.07 POS ACT PROBE 0° Reference position for the actual position probe
43.08 POS MAS PROBE -120° Reference position for the master position probe,
i.e. follower is 120° [(0°-120°)-(0°-0°)] behind the
master.
t1 t2 t3
30
DI5* DI6* CYC POS ACT ERR
0° 360 = 0
04.11 SYNCHRON ERROR 340
t2 0
x°
-30°
Master reference position
-100°
04.02 POS ACT VAL
Real actual position -130°
t1: Rising edge of digital input DI5 signal (proximity switch signal) is detected when
the master position is 0°. The follower position is -130° (stored to signal 04.16
LATCHED MAS REF).
t2: Rising edge of digital input DI6 signal (proximity switch signal) is detected when
the follower position is 0°. The actual position of the encoder is -30° (stored to signal
04.15 LATCHED ACT POS). Distance between the follower position and the actual
position is 0° - (-30°) = 30°.
According to parameter 43.07 POS ACT PROBE and 43.08 POS MAS PROBE
settings the follower should be 120° behind the master.
The following phase shift between the master and follower is calculated and stored
as reference error 04.17 CYCLIC POSIT ERR.
(43.08 POS MAS PROBE - 04.16 LATCHED MAS REF)) - (43.07 POS ACT PROBE
- 04.15 LATCHED ACT POS) = [-120° - (130°)] - [0° - (-30°)] = -20°
This error is added to 04.11 SYNCHRON ERROR. The synchron error is corrected
using the positioning parameters.
t3: Error has been corrected and the follower is 120° behind the master. Cyclic
function is ready for a new correction if necessary.
Note 1: Only after the active correction is finished, the next position latching is
enabled.
Note 2: The cyclic corrections are always performed along the shortest path. This
must be taken into account in all rollover applications.
Note 3: In rollover applications, the correction range is limited to ±180°
Example 3: Linear axis application
Two conveyer systems are synchronised using two encoders. The follower is in
synchron control and follows the master encoder 2 position.
Note: In linear axis applications only the difference between the master and follower
positions is corrected.
The dashed line presents a Master/Follower application, i.e. the Follower reference
is taken from the Master drive via the Master/Follower link (parameter 41.01 SYNC
POS REF SEL is set to M/F REF instead of ENC2).
MASTER
10 mm
LATCHED MAS REF
Proximity switch
DDCS
Encoder 2
M
3~
FOLLOWER
DI5 LATCHED ACT POS
EXT M1 DI1 Proximity switch
Encoder 1
M
3~
t1 t2 t3
EXT MI DI1
Digital input DI5
03.06 SPEED MEAS ENC1
40 mm
04.08 SYNC POS REF 30 mm
20 mm
04.02 POS ACT VAL
t1: Rising edge of digital input DI1 of external module 1 signal (proximity switch
signal) is detected. The follower position is 20 mm (stored to signal 04.16 LATCHED
MAS REF.)
t2: Rising edge of digital input DI5 signal (proximity switch signal) is detected when
the follower position is 40 mm (stored to signal 04.15 LATCHED ACT POS).
According to parameter 43.07 POS ACT PROBE and 43.08 POS MAS PROBE
settings the follower should be 10 mm behind the master.
The following correction is calculated and stored as reference error 04.17 CYCLIC
POSIT ERR:
(43.07 POS ACT PROBE - 43.08 POS MAS PROBE) - (04.16 LATCHED MAS REF)
- 04.15 LATCHED ACT POS)] = (15 mm - 25 mm) - (20 mm - 40 mm)] = 10 mm
This error is added to 04.11 SYNCHRON ERROR. The synchron error is corrected
using the positioning parameters.
t3: Error has been corrected and the follower is 10 mm behind the master. Cyclic
function is ready for a new correction if necessary.
Encoder
The Motor Encoder Gear parameters 19.07 MOTOR GEAR NUM and 19.08
MOTOR GEAR DEN are set as follows:
Note: Since the measured speed is also used for the DTC control motor model,
incorrect gear parameters will cause unexpected behaviour of the drive.
M
3~
The Load Encoder Gear parameters 19.09 LOAD GEAR NUM and 19.10 LOAD
GEAR DEN are set as follows:
Note: The sign of the programmed gear ratio has to match the sign of the
mechanical gear ratio.
Because the speed control uses the motor speed, an inverted gear ratio is applied to
the position control output (speed reference) as follows:
Note: It is emphasised that all position relevant parameters are load side related,
e.g. the setting of parameter 42.04 POS SPEED MAX (dynamic limiter speed
limitation) of 300 rpm denotes that, with a load gear ratio of 1:10, the motor can run
at up to 3000 rpm.
Settings
Group 19 SIGNAL CALC
CAM disk
The electronic CAM disk establishes together with the gear box a relationship
between the master and follower positions. The follower motor speed is fully
controlled at every point throughout one revolution (0...360 degrees). The follower
position is related to the master motor shaft position. The physical unit of this relation
depends on the scaling method selected by parameter 19.13 POS UNIT.
The following diagram shows an example of the CAM disk table in synchron control.
While the master rotates 360°, the follower first rotates 180° clockwise and then 180°
counterclockwise.
CAM disk table
Master Follower
position position Follower position (degrees)
0 0 360
20 20
40 20
300
60 40
80 40
100 60 240
120 90
140 120 180
160 150
180 180 120
200 150
220 120 60
240 90
260 60
280 40 0
300 40
0 60 120 180 240 300 360
320 20 Master position (degrees)
340 20
360 0
The number of CAM table rows is restricted to 1024. The number of rows also
defines the number of tables: 1024 rows = 1 table, 512 rows = 2 tables, etc. Each
row stores one motor position or other data in 24-bit format.
The CAM disk table is downloaded into the drive flash memory with a special PC
tool, DriveCAM. See DriveCam 1 User’s Guide [3AFE68641616 (English)].
See also chapter Control block diagrams.
The CAM disk table can be used with various functions where a signal must be
modified according to the actual position throughout one revolution. In addition to the
basic CAM function (master/follower), CAM disk table can be used in position speed
multiplicator and cyclic load compensation applications.
Master/Follower
CAM disk can be used for example in a flying shear application presented in
the following figure.
360
315
270
225
180
135
90
45
0
0 45 90 135 180 225 270 315 360
Master position (degrees)
Settings
Parameter Additional information
41.05 CAM DISK SEL CAM disk selection in synchron control
41.06 CAM DISK TBL SEL
100
87.5
75
62.5
50
37.5
25
12.5
0
0 45 90 135 180 225 270 315 360
Interpolator position (degrees)
Settings
Parameter Additional information
40.13 POS SPEED CAM CAM table selection in positioning speed
40.14 POS SPEED CAM SEL multiplicator application
75
50
25
-25
-50
-75
-100
45 90 135 180 225 270 315 360
Actual position (degrees)
Settings
Parameter Additional information
24.07 CYC LOAD COMP CAM disk selection in cyclic load compensation
24.08 CYC LOAD COMP SEL
Settings
Parameter Additional information
20.15 P DOWN BRAKE LIM DC voltage limit
41.01 SYNC POS REF SEL Synchron reference from virtual master
Diagnostics
Actual signal Additional information
06.11 bit 9 (PDB ACTIVE) DC voltage is below the level defined by parameter 20.15
P DOWN BRAKE LIM. This bit can be configured as an
emergency stop signal source for example by using the run
enable function (10.07 RUN ENABLE).
04.18 SYNC REF VIRTUAL Synchron reference from virtual master
Application macros
Overview of macros
Application macros are preprogrammed parameter sets. While starting up the drive,
the user typically makes the essential changes and saves the result as a user
macro.
The table below contains a summary of the macros and describes suitable
applications.
User The user can save the customised standard macro i.e. the parameter settings
including group 99, and the results of the motor identification into the permanent
memory, and recall the data at a later time. Two user macros are essential when
switching between two different motors is required.
Factory macro
All drive commands and reference settings can be given from the control panel or
from an external control location. The active control location is selected with the
LOC/REM key of the panel. The drive is speed-controlled.
In external control, the control location is EXT1 (see par. 11.01 CNTROL PLACE
SEL). The reference signal is connected to analogue input AI1 and Start/Stop signal
is connected to digital input DI1.
Acceleration and deceleration ramps are defined by parameters 22.02 ACCEL
TIME1 and 22.03 DECEL TIME1. Two analogue signals (speed and current) and
three relay output signals (ready, running and inverted fault) are available.
The default signals on the display of the control panel are SPEED, TORQUE and
CTRL MODE ACK.
Application macros
102
1)
See parameter 10.09 START X20
INTERL FUNC. 1 VREF Reference voltage -10 VDC
2 GND 1 kohm < RL < 10 kohm
X21
1 VREF Reference voltage 10 VDC
2 GND 1 kohm < RL < 10 kohm
3 AI1+ Speed reference 0(2) … 10 V, Rin > 200 kohm
4 AI1-
5 AI2+ By default, not in use. 0(4) … 20 mA, Rin =
6 AI2- 100 ohm
7 AI3+ By default, not in use. 0(4) … 20 mA, Rin =
8 AI3- 100 ohm
rpm 9 AO1+ Motor speed 0(4) … 20 mA = 0 … motor nom.
10 AO1- speed, RL < 700 ohm
A 11 AO2+ Output current 0(4) … 20 mA = 0 … motor
12 AO2- nom. current, RL < 700 ohm
X22
1 DI1 Stop/Start
2 DI2 EXT1/EXT2 control place selection
3 DI3 By default, not in use.
4 DI4 By default, not in use.
5 DI5 By default, not in use.
6 DI6 By default, not in use.
7 +24 V +24 VDC, max. 100 mA
8 +24 V
9 DGND1 Digital ground
10 DGND2 Digital ground
11 DI7 Start interlock (0 = stop) 1)
X23
1 +24 V Auxiliary voltage output, non-isolated,
2 GND 24 VDC, 250 mA
X25
1 RO11 Relay output 1
2 RO12 Ready
3 RO13
X26
1 RO21 Relay output 2
2 RO22 Running
3 RO23
X27
1 R031 Relay output 3
Fault 2 R032 Inverted fault
3 R033
Application macros
103
User macros
In addition to the Factory macro, it is possible to create two user macros. The user
macro allows the user to save the parameter settings including group 99, and the
results of the motor identification into the permanent memory, and recall the data at
a later time. The panel reference is also saved, if the macro is saved and loaded in
Local control mode. Remote control location setting is saved into the user macro, but
Local control location setting is not.
To create User Macro 1:
• Adjust the parameters. Perform the motor identification if not performed yet.
• Save the parameter settings and the results of the motor identification by
changing parameter 99.02 APPLICATION MACRO to USER 1 SAVE (press
ENTER). The storing takes 20 s to 1 min.
Note: If user macro save function is executed several times, the drive memory fills
up and file compression starts. File compression can last up to 10 minutes. Macro
saving will be completed after the file compression. (Operation is indicated on the
last row of the control panel display by blinking dots).
To recall the User Macro:
• Change parameter 99.02 APPLICATION MACRO to USER 1 LOAD.
• Press ENTER to load.
The user macro can also be switched via digital inputs (see parameter 16.03 USER
MACRO IO CHG).
Note: User macro load restores also the motor settings in parameter group 99
START UP and the results of the motor identification. Check that the settings
correspond to the used motor.
Example: The user can switch the drive between two motors without having to
adjust the motor parameters and to repeat the motor identification every time the
motor is changed. The user needs only to adjust the settings and perform the motor
identification once for both motors and then to save the data as two user macros.
When the motor is changed, only the corresponding User macro needs to be loaded,
and the drive is ready to operate.
Application macros
104
Application macros
105
Actual signal Signal measured or calculated by the drive. Can be monitored by the
user. No user setting possible.
FbEq Fieldbus equivalent: The scaling between the value shown on the panel
and the integer used in serial communication.
Fieldbus addresses
01 yy
10...41 25 · (xx - 6) + yy
52...97 18 · (xx + 6) + yy + 6
3-WIRE Source of the start and stop commands are selected by parameters 2
10.02 EXT1 START IN1 and 10.03 EXT1 START IN2. The start/stop is
controlled as follows:
Par. 10.02 Par.10.03 Command
0 -> 1 1 Start
any 1 -> 0 Stop
any 0 Stop
3-WIRE Source of the start and stop commands are selected by parameters
10.05 EXT2 START IN1 and 10.06 EXT2 START IN2. The start/stop is
controlled as follows:
Par. 10.05 Par.10.06 Command
0 -> 1 1 Start
any 1 -> 0 Stop
any 0 Stop
RAMP The application program stops the drive along the deceleration ramp 1
defined in group 22 ACCEL/DECEL.
COAST The application program stops the drive by cutting off the motor power 2
supply (the inverter IGBTs are blocked). The motor rotates freely to zero
speed.
WARNING! If the brake control function is on, the application
program uses ramp stop in spite of the selection COAST STOP
(see parameter group 28 BRAKE CTRL).
OFF2 STOP The application program stops the drive by cutting off the motor power 3
supply (the inverter IGBTs are blocked). The motor rotates freely to zero
speed. The drive will restart only when the Run Enable signal is on and
the start signal is switched on (the program receives the rising edge of
the start signal).
OFF3 STOP The application program stops the drive along the ramp defined by 4
parameter 22.07 OFF3 RAMP TIME. The drive will restart only when the
Run Enable is on and the start signal is switched on (the program
receives the rising edge of the start signal).
10.09 START INTERL FUNC Defines how the Start Interlock input on RMIO board affects the drive OFF2 STOP
operation. The source for the Start Interlock signal is selected by
parameter 10.18 START INTERLOCK.
OFF2 STOP Drive running: 1 = Normal operation. 0 = Stop by coasting. 1
Drive stopped: 1 = Start allowed. 0 = No start allowed.
Restart after OFF2 STOP: Start Interlock input = 1 and the drive receives
rising edge of the Start signal.
OFF3 STOP Drive running: 1 = Normal operation. 0 = Stop by ramp. The ramp time is 2
defined by parameter 22.07 OFF3 RAMP TIME.
Drive stopped: 1 = Normal start. 0 = No start allowed.
Restart after OFF3 STOP: Start Interlock input = 1 and the drive receives
rising edge of the Start signal.
10.11 START FUNCTION Selects the motor starting method. AUTO
AUTO Automatic start guarantees optimal motor start in most cases. It includes 1
the flying start function (starting to a rotating machine) and the automatic
restart function (stopped motor can be restarted immediately without
waiting the motor flux to die away). The drive motor control program
identifies the flux as well as the mechanical state of the motor and starts
the motor instantly under all conditions.
Speed controller
Speed Speed
remains live.
Speed controller Motor is
switched off. Motor decelerated
coasts to stop. to true 0 speed.
AI MAX SCALE
AI MIN AI measurement / V, mA
AI MAX
AI MIN SCALE
-400…400% Value in percent -40000…40000
13.04 AI1 MAX SCALE Defines the %-value that corresponds to the maximum value of 100%
analogue input AI1. See parameter 13.03 AI1 MIN SCALE.
-400...400% Value in percent -40000…40000
13.05 AI1 FILT TIME Defines the filter time constant for analogue input AI1. 0.1 s
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
Note: The signal is also filtered due to the signal interface hardware
(1 ms time constant). This cannot be changed by any parameter.
0.00…10.00 s Filter time constant 0...1000
13.06 AI2 MIN Defines the minimum value for analogue input AI2. 0 mA
0…20.41 mA Current 0…20410
13.07 AI2 MAX Defines the maximum value for analogue input AI2. 20 mA
0…20.41 mA Current 0…20410
13.08 AI2 MIN SCALE Defines the %-value that corresponds to the minimum value of analogue -100%
input AI2. See parameter 13.03 AI1 MIN SCALE.
-400...400% Value in percent -40000…40000
13.09 AI2 MAX SCALE Defines the %-value that corresponds to the maximum value of 100%
analogue input AI2. See parameter 13.03 AI1 MIN SCALE.
-400...400% Value in percent -40000…40000
LAST SPEED The drive generates warning AI < MIN FUNC and freezes the speed to 4
the level the drive was operating at (i.e. activates Main Control Word bit
5 RAMP_HOLD).
WARNING! Make sure that it is safe to continue operation in
case the analogue input signal is lost.
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
Note: Even if 0 s is selected as the minimum value, the signal is still
filtered with a time constant of 1 ms due to the signal interface hardware.
This cannot be changed by any parameters.
15.08 RMIO AO2 FUNC Selects the analogue output AO2 signal current scaling method. NORMAL
NORMAL Input signal defined by par. 15.12 RMIO AO2 MIN SCALE corresponds 1
to output signal defined by par. 15.10 RMIO AO2 MIN.
ABS Absolute value is taken from the input signal value. Zero input signal 2
corresponds to output signal defined by par. 15.10 RMIO AO2 MIN.
15.09 RMIO AO2 SEL Selects the source or constant value for analogue output AO2. 01.05
-255.255.31…+255.255.31 See parameter 15.02 RMIO AO1 SEL.
/ C.-32768…C.32767
15.10 RMIO AO2 MIN Defines the minimum value of the analogue output signal AO2. 0 mA
0...20 mA Current 0…2000
speed 0
t1 t1
speed
control 0
P-part t2 t2 t2 t2
t1 = ZERO DETECT DELAY = 250 ms
t2 = SPEED HOLD TIME = 4 ms
S-curve ramp:
par. 22.06 > 0 s
time
par. 22.02 par. 22.06
23.03 23.03
Speed ref
23.02 23.02
23.03 23.02
-Speed ref
23.02 23.03
NORMAL SYMMETRIC
NO Inactive 0
NORMAL Active. Speed error is calculated using the signed speed values. 1
Error value
Controller output
Controller e = Error value
output = Kp · e
t
0.0…250.0 Gain 0…25000
23.06 INTEGRATION TIME1 Defines an integration time for the speed controller. The integration time 2.5 s
defines the rate at which the controller output changes when the error
value is constant. The shorter the integration time, the faster the
continuous error value is corrected. Too short an integration time makes
the control unstable.
The figure below shows the speed controller output after an error step
when the error remains constant.
%
Controller output
Gain = Kp = 1
TI = Integration time > 0
Kp · e TD= Derivation time = 0
Kp · e e = Error value
t
TI
0.01…999.97 s Integration time 10…999970
Controller output
De
Kp · TD ·
Ts Kp · e
Error value
Kp · e e = Error value
t
TI
0.0…9999.8 ms Derivation time 1 = 1 ms
23.08 GAIN2 See parameter 23.05 GAIN1. 10
See parameter 23.05 GAIN1.
23.09 INTEGRATION TIME2 See parameter 23.06 NTEGRATION TIME1. 2.5 s
See parameter 23.06 NTEGRATION TIME1.
23.10 DERIVATION TIME2 See parameter 23.07 DERIVATION TIME1. 0 ms
See parameter 23.07 DERIVATION TIME1.
No Drooping
100% } par. 23.11 DROOP RATE
Drooping
100%
Speed Controller Drive load
Output / %
% % Speed reference
Actual speed
t t
Start/Stop
Motor magnetised
Actual speed
1 = brake close speed
2 = brake close delay
3 = extended run time
1
t
2 3
28.10 LOW REF BRK HOLD Activates a brake hold function and defines the hold delay for it. The 0s
function stabilises the operation of the brake control application when
the motor operates near zero speed and there is no measured speed
feedback available (pulse encoder).
LAST SPEED The drive generates warning PANEL LOSS and freezes the speed to the 3
level the drive was operating at (i.e. activates Main control Word bit 5
RAMP_HOLD).
WARNING! Make sure that it is safe to continue operation in
case of a panel communication break.
30.02 EXTERNAL FAULT Activates the external fault or selects the source for an external fault YES
signal.
0 = Fault (EXTERNAL FLT) trip. Motor coasts to stop.
1 = No external fault
NO Inactive 1
YES Fault active 2
DI1 Digital input DI1 3
DI2 Digital input DI2 4
DI3 Digital input DI3 5
DI4 Digital input DI4 6
DI5 Digital input DI5 7
DI6 Digital input DI6 8
EXT M1 DI1 Digital input DI1 of extension module 1 9
EXT M1 DI2 Digital input DI2 of extension module 1 10
EXT M1 DI3 Digital input DI3 of extension module 1 11
EXT M2 DI1 Digital input DI1 of extension module 2 12
EXT M2 DI2 Digital input DI2 of extension module 2 13
EXT M2 DI3 Digital input DI3 of extension module 2 14
EXT M3 DI1 Digital input DI1 of extension module 3 15
EXT M3 DI2 Digital input DI2 of extension module 3 16
EXT M3 DI3 Digital input DI3 of extension module 3 17
USER MODE The protection is based on the user-defined motor thermal model and 2
the following basic assumptions:
- The motor is at ambient temperature (30°C) when power is switched
on.
- The motor temperature increases if it operates in the region above the
load curve.
-The motor temperature decreases if it operates in the region below the
load curve. This applies only if the motor is overheated.
The user-defined thermal model uses the motor thermal time constant
(parameter 30.05 MOTOR THERM TIME) and the motor load curve
(parameters 30.06...30.08). User tuning is typically needed only if the
ambient temperature differs from the normal operating temperature
specified for the motor.
WARNING! The model does not protect the motor if it does not
cool properly due to dust and dirt.
6 DI6
7 +24 VDC
T
Motor
6 DI6
7 +24 VDC
T 10 nF
Motor
Temperature t
100%
63%
t
Motor thermal time constant
256.0…9999.8 s Time constant 256…9999
30.06 MOTOR LOAD CURVE Defines the load curve together with parameters 30.07 ZERO SPEED 100%
LOAD and 30.08 BREAK POINT. The load curve is used in the user-
defined thermal model (see the selection USER MODE of parameter
30.04 MOT THERM P MODE).
I/IN I = Motor current
(%) IN = Nominal motor current
150
30.06
100
50
30.07
TM/TN
TM = Motor torque
(%) TN= Nominal motor torque
100 ƒN = Nominal motor frequency
80 3
70%
60 2
50%
40 1 5
30%
20
4
0
ƒN 2.4 * ƒN
100
35.02 MOT 1 TEMP ALM L Defines the alarm limit for motor 1 temperature measurement. Alarm 110°C
indication MOTOR 1 TEMP is given when the limit is exceeded.
-10…180 °C or Limit in °C or ohms. °C: Parameter 35.01 MOT 1 TEMP AI1 SEL is -10…5000
0...5000 ohm 1XPT100, 2XPT100, 3XPT100. Ohm: Parameter 35.01 is 1...3 PTC.
35.03 MOT 1 TEMP FLT L Defines the fault trip limit for motor 1 temperature measurement. Fault 130°C
indication MOTOR 1 TEMP is given when the limit is exceeded.
-10…180 °C or Limit in °C or ohms. °C: Parameter 35.01 is 1XPT100, 2XPT100, -10…5000
0...5000 ohm 3XPT100. Ohm: Parameter 35.01 is 1...3 PTC.
40.05 POS REF ADD Defines the additional target position reference. This reference can also 0 rev
be used in synchron control to determine the phase shift angle.
See par. 19.13 Position reference See par. 19.15
0 -> 1 = rising edge of the selected signal stores the actual position value
to the selected target (= reference table).
-100% 0 rpm
-200% -100 rpm
-300% -200 rpm
*The SYNC GEAR ADD ratio is limited to 2.
This means that the gear ratio can be changed between -2...2.
If analogue input scaling is set to -100...100%, available speed range is
0...200 rpm which means that the gear ratio can be changed between
0...2.
PROG AI and dataset integer values:
-98304 : -2
0:1
32768 : 2
NOT USED Not selected 0
bit number 5 2
binary value 0010 0100
decimal value 25 + 22 = 32 + 4 = 36
hex value 20 + 4 = 24H
s
s
t
4.06 POS INTERP
t
OUTPUT
0 = The position system is not returned into the rollover axis range.
... ... ... ...
49.16 POS PAR TABLE16 Determines the behaviour of the positioning interpolator when position
reference set 16 is in use. See parameter 49.01 POS PAR TABLE1.
See parameter 49.01 POS PAR TABLE1.
50 ENCODER MODULES Encoder connection
50.01 ENCODER MODULE1 Activates the communication to the optional pulse encoder module 1. NO
NTAC Communication active. Module type: NTAC module. Connection 0
interface: fibre optic DDCS link.
Note: Module node number must be set to 16. For directions, see
Installation and Start-up Guide for NTAC-0x/NDIO-0x/NAIO-0x Modules
[3AFY58919730 (English)].
NO Inactive 1
RTAC-SLOT1 Communication active. Module type: RTAC. Connection interface: option 2
slot 1 of the drive.
RTAC-SLOT2 Communication active. Module type: RTAC. Connection interface: option 3
slot 2 of the drive.
RTAC-DDCS Communication active. Module type: RTAC. Connection interface: 4
Optional I/O module adapter (AIMA) that communicates with the drive
through a fibre optic DDCS link.
Note: Module node number must be set to 16. For directions, see
RTAC-01 Pulse Encoder Interface User's Manual [3AFE64486853
(English)].
LAST SPEED Protection is active. The drive generates warning COMM MODULE and 4
freezes the speed to the level the drive was operating at (i.e. activates
Main Control Word bit 5 RAMP_HOLD).
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
70.04 CH0 NODE ADDR Defines the node address for channel CH0. No two nodes on-line may 1
have the same address. The setting needs to be changed when a
master station is connected to channel CH0 and it does not
automatically change the address of the follower. Examples of such
masters are an ABB Advant Controller or another drive.
1...254 Address 1...254
70.05 CH0 HW CONNECTION Selects the topology of the DDCS channel CH0 link. RING
RING Devices are connected in a ring. 0
STAR Devices are connected in a star. 65535
70.06 CH0 BAUD RATE Selects the communication speed of channel 0. 1 Mbit/s
8 Mbit/s 8 megabits per second 0
4 Mbit/s 4 megabits per second 1
2 Mbit/s 2 megabits per second 2
1 Mbit/s 1 megabit per second 3
70.07 MAIN DS TIMEOUT Defines the time delay before a communication break fault is activated 100 ms
(see parameter 70.03 COMM MOD FLT FUNC). Time count starts when
the link fails to update the message.
0...60000 ms Time 1 = 1 ms
70.08 CH2 M/F FUNC Defines the role of the drive in the Master/Follower link. See section NOT IN USE
Master/Follower use of several drives on page 66.
NOT IN USE The Master/Follower link is inactive. 1
MASTER Master drive 2
FOLLOWER Follower drive 3
STANDBY Follower drive which reads the control signals through a fieldbus 4
interface, not from the Master/Follower link as usual.
LAST SPEED Protection is active. The drive generates warning COMM MODULE and 4
freezes the speed to the level the drive was operating at (i.e. activates
Main Control Word bit 5 RAMP_HOLD).
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
70.11 CH2 T-OUT DELAY The time delay before a communication break fault of CH2 is activated. 100 ms
0...60000 ms Time 1 = 1 ms
70.12 MASTER SIGNAL2 Selects the signal which is sent by the Master to the Follower drive(s) as 401
reference 1 (to dataset 41 index 2).
0...30000 Parameter index 401 denotes par. 4.01 POS ACT ENC. 0...30000
Note: If the Follower drive is in synchron control, this parameter must be
set to 401.
70.13 MASTER SIGNAL3 Selects the signal which is sent by the Master to the Follower drive(s) as 303
reference 2 (to dataset 41 index 3).
0...30000 Parameter index 303 denotes par. 03.03 SPEED REF4. 0...30000
70.14 CH3 NODE ADDR Node address for channel CH3. No two nodes on-line may have the 1
same address. Typically the setting needs to be changed when the drive
is connected in a ring which consists of several drives and a PC with the
DriveWindow program running.
1...254 Address 1...254
70.15 CH3 HW CONNECTION Selects the topology of the DDCS channel CH3 link. RING
RING Devices are connected in a ring. 0
STAR Devices are connected in a star. 65535
83 ADAPT PROG CTRL Control of the Adaptive Program execution. For more information, see
the Adaptive Program Application Guide [3AFE64527274 (English)].
83.01 ADAPT PROG CMD Selects the operation mode for the Adaptive Program.
STOP Stop. The program cannot be edited. 1
RUN Run. The program cannot be edited. 2
EDIT Stop to edit mode. Program can be edited. 3
83.02 EDIT COMMAND Selects the command for the block placed in the location defined by
parameter 83.03. The program must be in editing mode (see parameter
83.01).
84.02 FAULTED PAR Points out the faulted parameter in the Adaptive Program. -
84.05 BLOCK1 Selects the function block for Block Parameter Set 1. See the Adaptive
Program Application Guide [3AFE64527274 (English)].
ABS 11
ADD 10
AND 2
BITWISE 26
COMPARE 16
COUNT 21
DPOT 23
EVENT 20
FILTER 13
MASK-SET 24
MAX 17
MIN 18
MULDIV 12
NO 1
OR 3
PI 14
PI-BAL 15
PI BIPOLAR 25
RAMP 22
SR 5
SWITCH-B 7
S
P P Q
cos ( 30 ) = ---- = ------------------------
S 2 2 30°
P +Q
P
Positive reference 30° denotes capacitive load.
Negative reference 30° denotes inductive load.
P = signal 01.09 POWER value
Parameter 24.03 values are converter to degrees by the line-side
converter application program: -3000...30000 = -30°...30°. Value -10000/
10000 equals to -30°/30°, since the range is limited to -3000/3000.
-10000...10000 Reference value. See par.
description.
95.02 LCU DC REF Defines the intermediate circuit DC voltage reference for the line-side
converter. This reference is written into line-side converter parameter
23.01 DC VOLT REF. For more information, see IGBT Supply Control
Program 7.x Firmware manual [3AFE68315735 (English)].
0...1100 V Voltage 1=1V
95.03 LCU PAR1 SEL Selects the line-side converter address from which the actual signal
02.28 LCU ACT SIGNAL1 is read from.
0…9999 Line-side converter parameter index. For more information, see IGBT 0…9999
Supply Control Program 7.x Firmware manual [3AFE68315735
(English)].
95.04 LCU PAR2 SEL Selects the line-side converter address from which the actual signal
02.29 LCU ACT SIGNAL2 is read from.
0…9999 Line-side converter parameter index. For more information, see IGBT 0…9999
Supply Control Program 7.x Firmware manual [3AFE68315735
(English)].
99 START UP Language selection. Definition of motor set-up data.
99.01 LANGUAGE Selects the display language. ENGLISH
Fieldbus control
System overview
The drive can be connected to an external control system – usually a fieldbus
controller – via an adapter module mounted in expansion slot 1 of the drive or via a
fieldbus adapter connected to channel CH0 of an RDCO (DDCS Communication
Option) module. (For connection to an Advant Fieldbus 100 system, an external
AF 100 interface is used.)
Fieldbus
Controller
Fieldbus
ACS800 Other
devices
Fieldbus Adapter *) *) *)
Rxxx
Slot 1 *) Either an Rxxx or Nxxx, and
RMIO Board
Data Flow
Control Word (CW)
References
Process I/O (Cyclic)
Status Word (SW)
Actual Values
The drive can be set to receive all of its control information through the fieldbus
interface, or the control can be distributed between the fieldbus interface and other
available sources, e.g. digital and analogue inputs.
Fieldbus control
210
COMMUNICATION INITIALISATION
70.02 COMM ABB DRIVES ABB DRIVES or Selects the communication profile used by
PROFILE GENERIC GENERIC the drive. See section Communication
profiles on page 225.
51.02 (FIELDBUS These parameters are adapter module-specific. For more information, see the module manual.
PARAMETER 2) Note that not all of these parameters are necessarily visible.
•••
51.26 (FIELDBUS
PARAMETER 26)
51.27 FBA PAR (0) DONE – Validates any changed fieldbus parameter
REFRESH* (1) REFRESH settings. After refreshing, the value reverts
automatically to DONE.
51.28 FILE CPI FW xyz (binary coded – Displays the CPI firmware revision of the
REV* decimal) fieldbus adapter configuration file stored in
the memory of the drive. The CPI firmware
version of the fieldbus adapter (refer to par.
51.32) must contain the same or a later CPI
version to be compatible. x = major revision
number; y = minor revision number;
z = correction number. Example: 107 =
revision 1.07.
Fieldbus control
211
51.29 FILE CONFIG xyz (binary coded – Displays the fieldbus adapter module
ID* decimal) configuration file identification stored in the
memory of the drive. This information is
drive application program-dependent.
51.30 FILE CONFIG xyz (binary coded – Displays the fieldbus adapter module
REV* decimal) configuration file revision stored in the
memory of the drive. x = major revision
number; y = minor revision number;
z = correction number. Example: 1 =
revision 0.01.
51.31 FBA STATUS (0) IDLE – Displays the status of the adapter module.
(1) EXEC. INIT IDLE = Adapter not configured.
(2) TIME OUT
EXEC. INIT = Adapter initialising.
(3) CONFIG
ERROR TIME OUT = A timeout has occurred in the
(4) OFF-LINE communication between the adapter and
(5) ON-LINE the drive.
(6) RESET CONFIG ERROR = Adapter configuration
error. The major or minor revision code of
the CPI firmware revision stored in the
adapter differs from that stated in the
configuration file in the memory of the drive.
OFF-LINE = Adapter is off-line.
ON-LINE = Adapter is on-line.
RESET = Adapter performing a hardware
reset.
*Parameters 51.27 to 51.33 are only visible with a type Rxxx fieldbus adapter installed.
After the parameters in group 51 COMM MODULE DATA have been set, the drive
control parameters (see section Drive control parameters on page 216) must be
checked and adjusted where necessary.
The new settings will take effect when the drive is next powered up, or when
parameter 51.27 FBA PAR REFRESH is activated.
Fieldbus control
212
COMMUNICATION INITIALISATION
70.02 COMM ABB DRIVES ABB DRIVES Selects the communication profile used by
PROFILE GENERIC the drive. See section Communication
profiles on page 225.
COMMUNICATION PARAMETERS
52.02 BAUDRATE 600; 1200; 2400; – Communication speed for the Standard
4800; 9600; 19200 Modbus Link
After the parameters in group 52 STANDARD MODBUS have been set, the drive control
parameters (shown in section Drive control parameters on page 216) should be
checked and adjusted where necessary.
Fieldbus control
213
Modbus addressing
In the Modbus controller memory, the Control Word, the Status Word, the
references, and the actual values are mapped as follows:
Data from fieldbus controller to drive Data from drive to fieldbus controller
Fieldbus control
214
Fieldbus control
215
Communication Set-up
The communication between the drive and the AF 100 interface is activated by
setting parameter 70.01 COMM MODULE LINK to ADVANT.
Table 3 Communication set-up parameters for AF 100 connection.
Parameter Alternative Settings Setting for Control Function/Information
through CH0
COMMUNICATION INITIALISATION
70.03 COMM MOD ABB DRIVES ABB DRIVES Selects the communication profile used by
FLT FUNC GENERIC the drive. See section Communication
profiles on page 225.
After the communication activation parameters have been set, the AF 100 interface
must be programmed according to its documentation, and the drive control
parameters (see section Drive control parameters on page 216) checked and
adjusted where necessary.
In an Optical ModuleBus connection, the channel 0 address (parameter 70.04
CH0 NODE ADDR) is calculated from the value of the POSITION terminal in the
appropriate database element (for the AC 80, DRISTD) as follows:
1. Multiply the hundreds of the value of POSITION by 16.
2. Add the tens and ones of the value of POSITION to the result.
For example, if the POSITION terminal of the DRISTD database element has the
value of 110 (the tenth drive on the Optical ModuleBus ring), parameter 70.01 must
be set to 16 × 1 + 10 = 26.
In an AC 80 DriveBus connection, the drives are addressed 1 to 12. The drive
address (set with parameter 70.04 CH0 NODE ADDR) is related to the value of the
DRNR terminal of ACSRX PC element.
Fieldbus control
216
10.01 EXT1 MAIN DS WORD1 Enables the fieldbus Control Word (except bit 11) when EXT1 is selected
START FUNC as the active control location. See also par. 10.16 NET CONTROL.
10.04 EXT2 MAIN DS WORD1 Enables the fieldbus Control Word (except bit 11) when EXT2 is selected
START FUNC as the active control location.
10.16 NET 0 or 1 Value 1 overrides the setting of par. 10.01 EXT1 START FUNC so that the
CONTROL fieldbus Control Word (except bit 11) is enabled when EXT1 is selected as
the active control location.
Note: Setting is not saved into permanent memory.
10.17 NET 0 or 1 1 = fieldbus reference REF1 overrides the speed reference defined by par.
REFERENCE group 21 SPEED REFERENCE. EXT1 must be selected as the active
control location with par. 11.01 CNTROL PLACE SEL and the drive control
mode must be set to SPEED by par. 11.02 EXT1 CONTROL MODE.
Note: The setting is not saved into permanent memory (will reset to zero
when power is switched off).
40.04 POS REF MAIN DS REF12 Position target reference from fieldbus
SEL
Fieldbus control
217
12.04... Source for freely programmable boolean information, (i.e. when PROG
12.20 DI1...16 has been selected).
PROGRAMMABLE Example: User macro change through fieldbus:
DI1...16 Parameter 16.03 USER MACRO IO CHG value is set to PROG DI1 and
parameter value 12.04 PROGRAMMABLE DI1 is set to +05.02.12.
10.15 RESET PROG DI2 Enables fault reset through fieldbus Control Word (05.02) bit 7 RESET.
12.05 +05.02.07
PROGRAMMABLE
DI2
16.05 DONE Saves parameter value changes (including those made through fieldbus
PARAMETER SAVE control) to permanent memory.
SAVE
70.03 COMM MOD FAULT Determines drive action in case fieldbus communication is lost.
FLT FUNC NO Note: The communication loss detection is based on monitoring of
CONST SP1 received Main data sets (whose sources are selected with parameters
LAST SPEED 90.04 MAIN DS SOURCE and 90.05 AUX DS SOURCE respectively).
70.07 MAIN DS 0…60000 ms Defines the time delay before a communication break fault is activated.
TIMEOUT
90.01 AUX DS 0…30000 Defines the drive parameter into which the value of fieldbus reference
REF3 REF3 is written.
Format: xxyy, where xx = parameter group (10 to 89), yy = parameter
Index. E.g. 3001 = parameter 30.01.
90.02 AUX DS 0…30000 Defines the drive parameter into which the value of fieldbus reference
REF4 REF4 is written.
Format: See 90.01 AUX DS REF3 above.
90.03 AUX DS 0…30000 Defines the drive parameter into which the value of fieldbus reference
REF5 REF5 is written.
Format: See 90.01 AUX DS REF3 above.
Fieldbus control
218
90.04 MAIN DS 1...255 If 70.01 COMM MODULE LINK is set to CUSTOMISED, this parameter
SOURCE selects the source from which the drive reads the Main Reference data set
(comprising the fieldbus Control Word, fieldbus reference REF1, and
fieldbus reference REF2).
90.05 AUX DS 1...255 If 70.01 COMM MODULE LINK is set to CUSTOMISED, this parameter
SOURCE selects the source from which the drive reads the Auxiliary Reference data
set (comprising fieldbus references REF3, REF4 and REF5).
92.01 MAIN DS 6.01 The Status Word is transmitted as the first word of the Main Actual Signal
STATUS WORD data set.
92.02 MAIN DS 0…30000 Selects the Actual signal or parameter value to be transmitted as the
ACT1 second word (ACT1) of the Main Actual Signal data set.
Format: (x)xyy, where (x)x = actual signal group or parameter group, yy =
actual signal or parameter index. E.g. 104 = actual signal 1.04
FREQUENCY; 2202 = parameter 22.02 ACCEL TIME 1.
Note: With the Generic Drive communication profile active (par. 70.02 =
GENERIC), this parameter is fixed to 103 (actual signal 1.03 SPEED – in
DTC motor control mode).
92.03 MAIN DS 0…30000 Selects the Actual signal or parameter value to be transmitted as the third
ACT2 word (ACT2) of the Main Actual Signal data set.
Format: See 92.02 MAIN DS ACT1 above.
92.04 MAIN DS 0…30000 Selects the Actual signal or parameter value to be transmitted as the first
ACT3 word (ACT3) of the Auxiliary Actual Signal data set.
Format: See 92.02 MAIN DS ACT1 above.
92.05 MAIN DS 0…30000 Selects the Actual signal or parameter value to be transmitted as the
ACT4 second word (ACT4) of the Auxiliary Actual Signal data set.
Format: See 92.02 MAIN DS ACT1 above.
92.06 AUX DS 0…30000 Selects the Actual signal or parameter value to be transmitted as the third
ACT5 word (ACT5) of the Auxiliary Actual Signal data set.
Format: See 92.02 MAIN DS ACT1 above.
92.07 MSW BIT13 0…30000 Selects the status information to be transmitted as bit 13 of the 06.01
SEL MAIN STATUS WORD.
92.08 MSW BIT14 0…30000 Selects the status information to be transmitted as bit 14 of the 06.01
SEL MAIN STATUS WORD.
Actual Values
Actual Values (ACT) are 16-bit words containing information on selected operations
of the drive. The functions to be monitored are selected with the parameters in group
92 DSET TR ADDR. The scaling of the integers sent to the master as Actual Values
depends on the selected function; please refer to Actual signals and parameters.
Note: Only 04.02 POS ACT VAL of position actual signals is supported by group 92
DSET TR ADDR. Set 402 to parameters 92.02 MAIN DS ACT1 and 92.03 MAIN DS ACT2.
Fieldbus control
219
The 16 MSB of 04.02 POS ACT VAL are written to MAIN DS ACT 1 and 16 LSB are
written to MAIN DS ACT2.
*Index Main Reference data set DS1 *Index Main Actual Signal data set DS2
1 1st word Control Word (Fixed) 4 1st word Status Word (Fixed)
2 2nd word Reference 1 speed/torque ref 5 2nd word Actual 1 **par. 92.02
3 3rd word Reference 2 speed/torque ref 6 3rd word Actual 2 par. 92.03
*Index Auxiliary Reference data set DS3 *Index Aux. Actual Signal data set DS4
7 1st word Reference 3 par. 90.01, 10 1st word Actual 3 Par. 92.04
speed/torque ref
8 2nd word Reference 4 par. 90.02, 11 2nd word Actual 4 Par. 92.05
speed/torque ref
9 3rd word Reference 5 par. 90.03, 12 3rd word Actual 5 Par. 92.06
speed/torque ref
*The index number is required when data word allocation to process data is defined
via the fieldbus parameters at group 51 COMM MODULE DATA. This function is
dependent on the type of the fieldbus adapter.
**With the Generic Drive communication profile active, Actual 1 is fixed to actual
signal 01.03 SPEED.
Fieldbus control
220
The update time for the Main Reference and Main Actual Signal data sets is 6
milliseconds; for the Auxiliary Reference and Auxiliary Actual Signal data sets, it is
100 milliseconds.
Fieldbus references
All references (REF) except position references are 16-bit signed integers.
A negative reference (indicating reversed direction of rotation) is formed by
calculating the two’s complement from the corresponding positive reference value.
The table below shows the fieldbus reference scaling:
Reference handling
With the Generic Drive communication profile, the limit “Max.Ref.” is defined by
parameter 99.06 MOTOR NOM SPEED.
For information on the scaling of the fieldbus reference, see the manual delivered
with the fieldbus adapter (Generic Drive profile).
Fieldbus control
Block diagram: Control data input from fieldbus when a type Rxxx DI1
fieldbus adapter is used IN1
3-WIRE 11.01
MAIN DS WORD1
M/F LINK
10.01 05.02
70.03 COMM MOD FLT FUNC DI1 DATASET MCW
DATA 70.07 MAIN DS TIMEOUT IN1
Fieldbus Words 1 … n ** SET 3-WIRE
Adapter TABLE MAIN DS WORD1
M/F LINK
Slot1 NO MAIN 10.04
Word 1 1
(Control word) DS 1 FIELD- REFERENCE
2
Word 2 BUS DATA SET
3 2.15 MAIN DS REF1
(Speed ref) 4 ADVANT
DS CW 2.16 MAIN DS REF 2
Word 3 5 DS 2 STD
PAR MODBUS REF1 2.17 AUX DS REF 1
3 6 15.02, 15.09,
7 2.18 AUX DS REF 2
… CUSTOM- REF2 15.16, 15.23,
8 DS 3 ISED 2.19 AUX DS REF 3
DS 20.09, 20.10,
Word n 9 22.04, 22.05,
PAR 10 70.01
n 26.04, 32.02,
11 DS 4
32.05, 32.08
12
13
14 DS 5 PARAMETER
15 90.01 TABLE
90.03 •••
70.03 COMM MOD FLT FUNC
70.07 MAIN DS TIMEOUT Analogue Output
AO2 (see 15.08)
•••
Fieldbus control
222
Block diagram: Actual value selection for fieldbus when a type Rxxx
fieldbus adapter is used
Fieldbus control
DATA SET
TABLE
•••
10.01 92.04 Fieldbus specific selectors
in Group 51 ***
••• AUXILIARY Addresses for words 3 … n in
ACTUAL SIGNAL format xxyy
DATA SET xx Address
••• 92.05 ACT3 00 yy = word no. in data set
table
ACT4
01 … xx = par. group
ACT5
••• 99 yy = par. index
in parameter table
99.99 92.06
DI1 11.02
•
DATA 30.18 COMM FAULT FUNC •
COMM.CW •
SET 30.19 MAIN REF DS T-OUT
TABLE 10.01 03.01
NO DI1 MAIN CW
3 words FIELD- MAIN •
DS 1 •
Fieldbus (6 bytes) BUS REFERENCE COMM.CW •
Adapter ADVANT DATA SET
10.02
(CH0) DS 2 STD
CW AI1
MODBUS
1 REF1 •
• CUSTOM- • 01.11
3 words DS 3 • ISED COMM.REF •
• REF2 EXT REF1
(6 bytes)
255 11.03
90.04 98.02
DS 4 AI1
•
• 01.12
COMM.REF •
Modbus EXT REF2
•••
Controller 11.06
40001 3 words
40002 DS 81
(6 bytes)
40003 Standard NO
Modbus FIELD-
DS 82 Bits PARAMETER
Link BUS
13…15 90.01 TABLE
(RMBA) ADVANT
40007 (Slot 1/2) AUXILIARY Relay Outputs
3 words STD
40008 DS 83 REFERENCE (see 14.01…14.03) 10.01
(6 bytes) MODBUS
40009 DATA SET
1
• CUSTOM-
DS 84 • ISED REF3
• 10.02
255
98.02 REF4
90.05
••• REF5
90.02 •••
Analogue Output
AO1 (see 15.01)
30.18 COMM FAULT FUNC 89.99
30.20 COMM FLT RO/AO
30.21 AUX REF DS T-OUT
•••
90.03
Analogue Output
AO2 (see 15.06)
223
Fieldbus control
Block Diagram: Actual value selection for fieldbus when a type Nxxx
224
fieldbus adapter is used
Fieldbus control
DATA SET
TABLE
ACTUAL SIGNAL/
PARAMETER 92.01* DS 1
TABLE
MAIN 3 words
DS 2
1.01 (6 bytes) Fieldbus
ACTUAL SIGNAL
DATA SET Adapter
92.02 STATUS WORD* DS 3 (CH0)
1.02
ACT1**
ACT2 3 words
DS 4
••• (6 bytes)
92.03 •••
3.99
Modbus
DS 81 Controller
•••
40004
3 words
DS 82 40005
10.01 (6 bytes) Standard
92.04 40006
Modbus
DS 83 Link
••• AUXILIARY
ACTUAL SIGNAL 40010
DATA SET 3 words
DS 84 40011
99.99 (6 bytes)
92.05 40012
ACT3
ACT4
•••
ACT5
92.06
Communication profiles
The ACS800 supports two communication profiles:
• ABB Drives communication profile
• Generic Drive communication profile.
The ABB Drives communication profile should be selected with type Nxxx fieldbus
adapter modules, and when the manufacturer-specific mode is selected (via the
PLC) with type Rxxx fieldbus adapter modules.
The Generic Drive profile is supported by type Rxxx fieldbus adapter modules only.
Fieldbus control
226
Control word for ABB Drives communication profile (05.01 MAIN CONTROL WORD)
The Control Word for the ABB Drives communication profile. The upper case
boldface text refers to the states shown in the ABB Communications Profile figure
below.
Bit Name Value Enter STATE/Description
0 OFF1 CONTROL 1 Enter READY TO OPERATE.
0 Stop along currently active deceleration ramp (22.03/22.05). Enter OFF1 ACTIVE;
proceed to READY TO SWITCH ON unless other interlocks (OFF2, OFF3) are active.
1 OFF2 CONTROL 1 Continue operation (OFF2 inactive).
0 Emergency OFF, coast to stop. Enter OFF2 ACTIVE; proceed to SWITCH-ON
INHIBITED.
2 OFF3 CONTROL 1 Continue operation (OFF3 inactive).
0 Emergency stop, stop within time defined by par. 22.07. Enter OFF3 ACTIVE; proceed
to SWITCH-ON INHIBITED.
Warning: Ensure motor and driven machine can be stopped using this stop mode.
3 INHIBIT_ 1 Enter OPERATION ENABLED.
OPERATION Note: The Run Enable signal must be active; see parameter 10.07 RUN ENABLE.
0 Inhibit operation. Enter OPERATION INHIBITED.
4 RAMP_OUT_ 1 Normal operation. Enter RAMP FUNCTION GENERATOR: OUTPUT ENABLED.
ZERO 0 Force Ramp Function Generator output to zero. Drive ramps to stop (current and DC
voltage limits in force).
5 RAMP_HOLD 1 Enable ramp function. Enter RAMP FUNCTION GENERATOR: ACCELERATOR
ENABLED.
0 Halt ramping (Ramp Function Generator output held).
6 RAMP_IN_ 1 Normal operation. Enter OPERATING.
ZERO 0 Force Ramp Function Generator input to zero.
7 RESET 0⇒1 Fault reset if an active fault exists. Enter SWITCH-ON INHIBITED. Effective, if
parameter 10.15 RESET is set to PROG DI3 and 12.06 PROGRAMMABLE DI3 is set
to +005.002.07.
0 Continue normal operation.
8 INCHING_1 1 Not in use
1⇒0 Not in use
9 INCHING_2 1 Not in use
1⇒0 Not in use
10 REMOTE_CMD 1 Fieldbus control enabled
0 Control Word <> 0 or Reference <> 0: Retain last Control Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control enabled.
Reference and deceleration/acceleration ramp are locked.
11 EXT CTRL LOC 1 Select External Control Location EXT2. Effective, if parameter 10.01 CNTRL PLACE
SEL is set to PROG DI4 and 12.07 PROGRAMMABLE DI4 is set to +005.002.11.
0 Select External Control Location EXT1. Effective, if parameter 10.01 CNTRL PLACE
SEL is set to PROG DI4 and 12.07 PROGRAMMABLE DI4 is set to +005.002.11.
12…15 Reserved
Fieldbus control
227
Status word for ABB Drives communication profile (06.01 MAIN STATUS WORD)
The Status Word for the ABB Drives communication profile. The upper case
boldface text refers to the states shown in the ABB Communications Profile figure
below.
Bit Name Value STATE/Description
0 RDY_ON 1 READY TO SWITCH ON
0 NOT READY TO SWITCH ON
1 RDY_RUN 1 READY TO OPERATE
0 OFF1 ACTIVE
2 RDY_REF 1 OPERATION ENABLED
0 OPERATION INHIBITED
3 TRIPPED 1 FAULT
0 No fault
4 OFF_2_STA 1 OFF2 inactive
0 OFF2 ACTIVE
5 OFF_3_STA 1 OFF3 inactive
0 OFF3 ACTIVE
6 SWC_ON_INHIB 1 SWITCH-ON INHIBITED
0
7 ALARM 1 Warning/Alarm
0 No Warning/Alarm
8 AT_SETPOINT 1 OPERATING. Actual value equals reference value (= is within tolerance
limits).
0 Actual value differs from reference value (= is outside tolerance limits).
9 REMOTE 1 Drive control location: REMOTE (EXT1 or EXT2).
0 Drive control location: LOCAL.
10 ABOVE_LIMIT 1 Actual speed (01.03 SPEED) value equals or exceeds the supervision
function 1 limit (32.03 SUP FUNC1 LIMIT). Valid in both directions regardless
of parameter 32.01 SUPERVISION FUNC1 and 32.02 SUP FUNC1 VALUE
values.
0 Actual speed value is within supervision limit.
11 EXT CTRL LOC 1 External Control Location EXT2 selected
0 External Control Location EXT1 selected
12 EXT RUN ENABLE 1 External Run Enable signal received
0 No External Run Enable received
13, 14 Freely See parameters 92.07 MSW BIT13 SEL and 92.08 MSW BIT14 SEL.
programmable
15 1 Communication error detected by fieldbus adapter module (on fibre optic
channel CH0).
0 Fieldbus adapter (CH0) communication OK
Fieldbus control
228
SWITCH-ON
MAINS OFF INHIBITED (SW Bit6=1)
ABB Drives
Power ON (CW Bit0=0)
Communication
NOT READY Profile
TO SWITCH ON (SW Bit0=0)
A B C D
CW = Control Word
SW = Status Word
n = Speed
(CW=xxxx x1xx xxxx x110)
I = Input Current
(CW Bit3=0)
RFG = Ramp Function Generator
READY TO f = Frequency
OPERATION SWITCH ON (SW Bit0=1)
INHIBITED (SW Bit2=0)
from any state
operation
(CW=xxxx x1xx xxxx x111)
inhibited
Fault
READY TO
FAULT
OPERATE (SW Bit1=1) (SW Bit3=1)
n(f)=0 / I=0
(CW Bit4=0)
OPERATION
C D
ENABLED (SW Bit2=1)
A
(CW Bit5=0) (CW=xxxx x1xx xxx1 1111)
D RFG: OUTPUT
ENABLED
B
(CW Bit6=0) (CW=xxxx x1xx xx11 1111)
RFG: ACCELERATOR
ENABLED
C
(CW=xxxx x1xx x111 1111)
OPERATING
(SW Bit8=1)
D
Fieldbus control
229
Fieldbus control
230
Fieldbus control
231
0 Reserved
1 OUT OF WINDOW Speed difference is out of the window (in speed control)*.
2 Reserved
4 Reserved
6 1 START NOT Drive has not been started after changing the motor
DONE parameters in group 99 START UP.
11 ZERO SPEED Absolute value of motor actual speed is below zero speed limit
(4% of synchronous speed).
14…15 Reserved
Fieldbus control
232
3 Reserved
4 POS SYN CYC OK Synchron error is within the window defined by par. 32.15
SYNC ERR WINDOW and cyclic correction has been
performed (CYC_DONE_ONES).
5 POS SYN ERR OK Synchron error is within the window defined by par. 32.15
SYNC ERR WINDOW.
6 Reserved
7 SYNC ERR CMP Synchron control mode is used and synchron error is within
the window defined by par. 32.15 SYNC ERR WINDOW.
8 POS RUN OK Synchron error is within the window defined by par. 32.15
SYNC ERR WINDOW and position controller input 04.14
POSITION ERROR is within the window defined by par.
32.11 POSITION WINDOW.
10. Reserved
11 ACT POS PRELATCH Pre-latch is active. Bit is set to zero after standard homing
or actual position correction.
Fieldbus control
233
0 POS SW1 Actual position value equals or exceeds par. 32.12 POS
THRESHOLD 1 value.
1 POS SW2 Actual position value equals or exceeds par. 32.13 POS
THRESHOLD 2 value.
2 POS SW3 Actual position value equals or exceeds par. 32.14 POS
THRESHOLD 3 value.
4 IN POS WIN Distance to target is with the window defined by par. 32.11
POSITION WINDOW.
13 CYC DONE ONCE Cyclic correction has been performed at least once.
Fieldbus control
234
1 POWER MIN LIM Limitation defined by par. 20.12 P GENER LIM is active.
Fieldbus control
235
8 OVERLOAD CUR Maximum inverter overload current limit. See par. 20.05
MAX CURRENT.
Fieldbus control
236
6 OPEN BRAKE The Open Brake command is ON. See parameter group 28
BRAKE CTRL.
10 RUNNING Running: Start signal on, Run Enable signal on, no active
fault.
12...15 Reserved
0 SHORT CIRC For the possible causes and remedies, see chapter Fault
tracing.
1 OVERCURRENT
2 DC OVERVOLT
3 ACS800 TEMP
4 EARTH FAULT
5 THERMISTOR
6 MOTOR TEMP
8 UNDERLOAD For the possible causes and remedies, see chapter Fault
tracing.
9 OVERFREQ
11…15 Reserved
Fieldbus control
237
0 SUPPLY PHASE For the possible causes and remedies, see chapter Fault
tracing.
1 NO MOT DATA
2 DC UNDERVOLT
3 Reserved
4 RUN DISABLED For the possible causes and remedies, see chapter Fault
tracing.
5 ENCODER FLT
6 I/O COMM
7 CTRL B TEMP
8 EXTERNAL FLT
9 OVER SWFREQ
11 PPCC LINK
12 COMM MODULE
13 PANEL LOSS
14 MOTOR STALL
15 MOTOR PHASE
1 POS LIM ERR Actual position error. Minimum and maximum position
values are defined by parameters 42.01 POSITION MAX or
42.02 POSITION MIN.
2...15 Reserved
0 Reserved
1 MOTOR 1 TEMP For the possible causes and remedies, see chapter Fault
tracing.
2 MOTOR 2 TEMP
3 BRAKE ACKN
4…15 Reserved
Fieldbus control
238
0 BR BROKEN For the possible causes and remedies, see chapter Fault
tracing.
1 BR WIRING
2 BC SHORT CIR
3 BR OVERHEAT
4 BC OVERHEAT
5 IN CHOKE TEMP
6 PP OVERLOAD
7 INV DISABLED
8 TEMP DIF
9 POWERF INV xx /
POWERFAIL
10 INT CONFIG
11 Reserved
12 ENCODER2 FLT For the possible causes and remedies, see chapter Fault
tracing.
13 INV OVERTEMP
14…15 Reserved
Fieldbus control
239
15 Reserved
Fieldbus control
240
U V W
1 2 3
INT INT INT
U V W U V W U V W ...
Fieldbus control
241
0 START INHIBI For the possible causes and remedies, see chapter Fault
tracing.
1 Reserved
2 THERMISTOR For the possible causes and remedies, see chapter Fault
tracing.
3 MOTOR TEMP
4 ACS800 TEMP
5 ENCODER ERR
6 T MEAS ALM
7...11 Reserved
12 COMM MODULE For the possible causes and remedies, see chapter Fault
tracing.
13 Reserved
14 EARTH FAULT For the possible causes and remedies, see chapter Fault
tracing.
15 Reserved
Fieldbus control
242
0 Reserved
1 UNDERLOAD For the possible causes and remedies, see chapter Fault
tracing.
2, 3 Reserved
4 ENCODER For the possible causes and remedies, see chapter Fault
tracing.
5,6 Reserved
9 MOTOR STALL For the possible causes and remedies, see chapter Fault
tracing.
10 AI < MIN FUNC
11, 12 Reserved
13 PANEL LOSS For the possible causes and remedies, see chapter Fault
tracing.
14, 15 Reserved
0 Reserved
1 MOTOR 1 TEMP For the possible causes and remedies, see chapter Fault
tracing.
2 MOTOR 2 TEMP
3 BRAKE ACKN
4 Reserved
5 MACRO CHANGE For the possible causes and remedies, see chapter Fault
tracing.
6…15 Reserved
Fieldbus control
243
0 REPLACE FAN For the possible causes and remedies, see chapter Fault
tracing.
1 SYNCRO SPEED
2 BR OVERHEAT
3 BC OVERHEAT
4 IN CHOKE TEMP
5 PP OVERLOAD
6 INV DISABLED
7 CUR UNBAL
9 DC BUS LIM
13 Reserved
14 ENCODER2 ERR For the possible causes and remedies, see chapter Fault
tracing.
15 BATT FAILURE
0 INV OVERTEMP For the possible causes and remedies, see chapter Fault
tracing.
1 MOD BOARD T
2 MOD CHOKE T
3 ENC1 CABLE
4 ENC2 CABLE
5...15 Reserved
0 MOD BOARD T For the possible causes and remedies, see chapter Fault
tracing.
1 MOD CHOKE T
2 ENC1 CABLE
3 ENC2 CABLE
4...15 Reserved
Fieldbus control
244
Fieldbus control
245
Fault tracing
Safety
WARNING! Only qualified electricians are allowed to maintain the drive. The Safety
Instructions on the first pages of the appropriate hardware manual must be read
before you start working on the drive.
How to reset
The drive can be reset either by pressing the keypad RESET key, by digital input or
fieldbus, or switching the supply voltage off for a while. When the fault has been
removed, the motor can be restarted.
Fault history
When a fault is detected, it is stored in the Fault History. The latest faults and
warnings are stored together with the time stamp at which the event was detected.
See chapter Control panel for more information.
Fault tracing
246
ACS800 TEMP Drive IGBT temperature is excessive. Fault trip Check ambient conditions.
(4210) limit is 100%. Check air flow and fan operation.
07.20 bit 4 Check heatsink fins for dust pick-up.
Check motor power against unit power.
AI < MIN FUNC Analogue control signal is below minimum Check for proper analogue control signal
(8110) allowed value due to incorrect signal level or levels.
failure in control wiring. Check control wiring.
07.21 bit 10
Programmable Check Fault Function parameters.
Fault Function
13.28 and 13.29
BACKUP USED PC-stored backup of drive parameters is Wait until download is completed.
(FFA3) downloaded into use.
BATT FAILURE APBU branching unit memory backup battery With parallel connected inverters, enable
(5581) error caused by backup battery by setting the actuator 6 of
07.24 bit 15 - incorrect APBU switch S3 setting switch S3 to ON.
- too low battery voltage. Replace backup battery.
BC OVERHEAT Brake chopper overload Stop drive. Let chopper cool down.
(7114) Check parameter settings of resistor overload
07.24 bit 3 protection function (see parameter group 27
BRAKE CHOPPER).
Check that braking cycle meets allowed limits.
Check that drive supply AC voltage is not
excessive.
BRAKE ACKN Unexpected state of brake acknowledge See parameter group 28 BRAKE CTRL.
(FF74) signal. Check connection of brake acknowledgement
07.23 bit 3 signal.
Programmable
Fault Function
28.06
BR OVERHEAT Brake resistor overload Stop drive. Let resistor cool down.
(7112) Check parameter settings of resistor overload
07.24 bit 2 protection function (see parameter group 27
BRAKE CHOPPER).
Programmable
Fault Function Check that braking cycle meets allowed limits.
27.02, 27.04 and
27.05
CALIBRA REQ Calibration of output current transformers is Calibration starts automatically. Wait for a
(FF36) required. while.
Fault tracing
247
COMM MODULE Fieldbus or channel CH2 (Master/Follower link) Check status of fieldbus communication. See
(7510) communication brake chapter Fieldbus control, or appropriate
fieldbus adapter manual.
07.20 bit 12
Check parameter settings:
Programmable
Fault Function - group 51 COMM MODULE DATA (for fieldbus
70.03, 70.07 and adapter), or
70.10 - group 52 STANDARD MODBUS (for
Standard Modbus Link)
- group 70 COMM INTERFACE.
Check cable connections.
Check if master communicates.
CUR UNBAL xx Drive has detected excessive output current Check there are no power factor correction
(2330) unbalance in inverter unit of several parallel capacitors or surge absorbers in motor cable.
connected inverter modules. This can be Check that there is no earth fault in motor or
07.20 bit 14 and
caused by external fault (earth fault, motor, motor cables:
07.18
motor cabling, etc.) or internal fault (damaged
Programmable - measure insulation resistance of motor and
inverter component). xx (2...12) refers to faulty
Fault Function motor cabes.
inverter module number.
30.16 If no earth fault can be detected, contact your
local ABB representative.
DC BUS LIM Drive limits torque due to too high or too low Informative alarm
(3211) intermediate circuit DC voltage.
07.24 bit 9
EARTH FAULT Drive has detected load unbalance typically Check there are no power factor correction
(2330) due to earth fault in motor or motor cable. capacitors or surge absorbers in motor cable.
07.20 bit 14 Check that there is no earth fault in motor or
motor cables:
Programmable
Fault Function - measure insulation resistance of motor and
30.16 motor cabes.
If no earth fault can be detected, contact your
local ABB representative.
ENC1 CABLE Pulse encoder 1 phase signal is missing. Check pulse encoder 1 and its wiring.
(7310) Check pulse encoder interface module and its
07.25 bit 1 wiring.
Programmable
Fault Function
50.05
ENC2 CABLE Pulse encoder 2 phase signal is missing. Check pulse encoder 2 and its wiring.
(7382) Check pulse encoder interface module and its
07.25 bit 2 wiring.
Programmable
Fault Function
50.15
ENCODER A<>B Pulse encoder phasing is wrong: Phase A is Interchange connection of pulse encoder
(7302) connected to terminal of phase B and vice phases A and B.
versa.
07.21 bit 4
Fault tracing
248
ENCODER ERR Communication fault between pulse encoder Check pulse encoder and its wiring, pulse
(7301) and pulse encoder interface module and encoder interface module and its wiring and
between module and drive. parameter group 50 ENCODER MODULES
07.20 bit 5
settings.
Programmable
Fault Function
50.04
ENCODER2 ERR Communication fault between pulse encoder Check pulse encoder and its wiring, pulse
(7381) and pulse encoder interface module and encoder interface module and its wiring and
between module and drive. parameter group 50 ENCODER MODULES
07.24 bit 14
settings.
Programmable
Fault Function
50.14
HW RECONF RQ Inverter type (e.g. sr0025_3) has been Wait until alarm POWEROFF! activates and
(FF38) changed. The inverter type is usually changed switch control board power off the to validate
at the factory or during drive implementation. inverter type change.
ID MAGN Motor identification magnetisation is on. This Wait until drive indicates that motor
(FF31) warning belongs to normal start-up procedure. identification is completed.
ID MAGN REQ Motor identification is required. This warning Start Identification Magnetisation by pressing
(FF30) belongs to normal start-up procedure. Drive Start key, or select ID Run and start (see
expects user to select how motor identification parameter 99.08 ID RUN).
should be performed: By Identification
Magnetisation or by ID Run.
ID N CHANGED Drive ID number has been changed from 1. Change ID number back to 1. See chapter
(FF68) Control panel.
ID RUN FAIL Motor ID Run is not completed successfully. Check maximum speed (parameter 20.02 MAX
(FF84) SPEED). It should be at least 80% of motor
nominal speed (parameter 99.05 MOTOR
NOM FREQ).
ID RUN SEL Motor Identification Run is selected, and drive Press Start key to start Identification Run.
(FF33) is ready to start ID Run. This warning belongs
to ID Run procedure.
IN CHOKE TEMP Excessive input choke temperature Stop drive. Let it cool down.
(FF81) Check ambient temperature.
07.24 bit 4 Check that fan rotates in correct direction and
air flows freely.
Fault tracing
249
INV OVERTEMP Converter module temperature is excessive. Check ambient temperature. If it exceeds
(4290) 40°C, ensure that load current does not
exceed derated load capacity of drive. See
07.25 bit 0
appropriate hardware manual.
Check converter module cooling air flow and
fan operation.
Cabinet installation: Check cabinet air inlet
filters. Change when necessary. See
appropriate hardware manual.
Modules installed in cabinet by user: Check
that cooling air circulation in cabinet has been
prevented with air baffles. See module
installation instructions.
Check inside of cabinet and heatsink of
converter module for dust pick-up. Clean when
necessary.
IO CONFIG Input or output of optional I/O extension or Check option module parameter settings
(FF8B) fieldbus module has been selected as signal (70.01 COMM MODULE LINK, 70.02 COMM
interface in application program but PROFILE, 12 DIGITAL INPUTS, 13
communication to appropriate I/O extension ANALOGUE INPUTS, 50 ENCODER
module has not been set accordingly. MODULES).
INV DISABLED Optional DC switch has opened while drive Close DC switch.
(3200) was stopped. Check AFSC-0x Fuse Switch Controller unit.
07.24 bit 6
MACRO CHANGE Macro is restoring or User macro is being Wait until drive has finished task.
(FF69) saved.
MOT CUR LIM Drive limits motor current according to current Informative alarm
(2300) limit defined by parameter 20.05 MAX Check parameter 20.05 MAX CURRENT
CURRENT. settings.
07.24 bit 10
MOTOR STALL Motor is operating in stall region due to e.g. Check motor load and drive ratings.
(7121) excessive load or insufficient motor power. Check Fault Function parameters.
07.21 bit 9
Programmable
Fault Function
30.09...30.11
MOTOR STARTS Motor Identification Run starts. This warning Wait until drive indicates that motor
(FF34) belongs to ID Run procedure. identification is completed.
Fault tracing
250
MOTOR TEMP Motor temperature is excessive due to Check motor ratings, load and cooling.
(4310) excessive load, insufficient motor power, Check start-up data.
inadequate cooling or incorrect start-up data.
07.20 bit 3 Check Fault Function parameters.
Programmable
Fault Function
30.03...30.08
MOTOR 1 TEMP Measured motor temperature has exceeded Check value of alarm limit.
(4312) alarm limit set by parameter 35.02 MOT 1 Check that actual number of sensors
TEMP ALM L. corresponds to value set by parameter.
07.23 bit 1
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOTOR 2 TEMP Measured motor temperature has exceeded Check value of alarm limit.
(4313) alarm limit set by parameter 35.05 MOT 2 Check that actual number of sensors
TEMP ALM L. corresponds to value set by parameter.
07.23 bit 2
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOT POW LIM Drive limits motor power according to limits Informative alarm
(FF86) defined by parameters 20.11 and 20.12. Check parameter 20.11 P MOTORING LIM
07.24 bit 12 and 20.12 P GENER LIM settings.
MOT TORQ LIM Drive limits motor torque according to Informative alarm
(FF58) calculated motor pull-out torque limit and Check parameter 20.07 TORQ MAX LIM1 and
minimum and maximum torque limits defined 20.08 TORQ MIN LIM1 settings.
07.24 bit 11
by parameters 20.07 and 20.08.
If LIMIT WORD 1 bit 0 TORQ MOTOR LIM
is 1,
- check motor parameter settings (parameter
group 99 START UP).
- ensure that ID run has been completed
successfully.
PANEL LOSS Control panel selected as active control Check panel connection (see appropriate
(5300) location for drive has ceased communicating. hardware manual).
07.21 bit 13 Check control panel connector.
Replace control panel in mounting platform.
Programmable
Fault Function Check Fault Function parameters.
30.01
POINTER ERROR Source selection (pointer) parameter points to Check source selection (pointer) parameter
(FFD0) non-existing parameter index. settings.
->POWEROFF! Inverter type (e.g. sr0025_3) has been Switch control board power off to validate
(FF39) changed. The inverter type is usually changed inverter type change.
at the factory or during drive implementation.
Fault tracing
251
REPLACE FAN Running time of inverter cooling fan has Replace fan.
(4280) exceeded its estimated life time.
07.24 bit 0
START INHIBI Optional start inhibit hardware logic is Check start inhibit circuit (AGPS board).
(FF7A) activated.
07.20 bit 0
START INTERL No Start Interlock signal received. Check circuit connected to Start Interlock input
(FF8D) on RMIO board.
SYNCRO SPEED Value of motor nominal speed set to parameter Check nominal speed from motor rating plate
(FF87) 99.06 MOTOR NOM SPEED is not correct: and set parameter 99.06 exactly accordingly.
Value is too near synchronous speed of motor.
07.24 bit 1
Tolerance is 0.1%. This warning is active only
in DTC mode.
TGT POS LIM Target position exceeds set limits. Check position limit parameters 42.02
(8612) POSITION MIN and 42.01 POSITION MAX.
07.22 bit 0
THERMISTOR Motor temperature is excessive. Motor thermal Check motor ratings and load.
(4311) protection mode selection is THERMISTOR. Check start-up data.
07.20 bit 2 Check thermistor connections to digital input
Programmable DI6.
Fault Function
30.03 and 30.04
T MEAS ALM Motor temperature measurement is out of Check connections of motor temperature
(FF91) acceptable range. measurement circuit. See chapter Basic
program features for circuit diagram.
07.20 bit 6
Fault tracing
252
UNDERLOAD Motor load is too low. This can be caused by Check for problem in driven equipment.
(FF6A) release mechanism in driven equipment. Check Fault Function parameters.
07.21 bit 1
Programmable
Fault Function
30.12...30.14
DOWNLOADING Download function of panel has failed. No data Make sure panel is in local mode.
FAILED has been copied from panel to drive. Retry (there might be interference on link).
Contact local ABB representative.
DRIVE Program versions in panel and drive do not Check program versions. See parameter group
INCOMPATIBLE match. It is not possible to copy data from 33 INFORMATION.
DOWNLOADING panel to drive.
NOT POSSIBLE
DRIVE IS Downloading is not possible while motor is Stop motor. Perform downloading.
RUNNING running.
DOWNLOADING
NOT POSSIBLE
(4) = Panel type not compatible with drive Check panel type and drive application
application program version. program version. Panel type is printed on
panel cover. Application program version is
stored in parameter 33.01 SOFTWARE
VERSION.
NO FREE ID Panel Link already includes 31 stations. Disconnect another station from link to free ID
NUMBERS ID number.
NUMBER
SETTING NOT
POSSIBLE
NOT UPLOADED No upload function has been performed. Perform upload function before downloading.
DOWNLOADING See chapter Control panel.
NOT POSSIBLE
UPLOADING Upload function of panel has failed. No data Retry (there might be interference on link).
FAILED has been copied from drive to panel. Contact local ABB representative.
WRITE ACCESS Certain parameters do not allow changes while Stop motor, then change parameter value.
DENIED motor is running. If tried, no change is
PARAMETER accepted, and warning is displayed.
SETTING NOT
POSSIBLE Parameter lock is on. Open parameter lock (see parameter 16.01
PARAMETER LOCK).
Fault tracing
253
ACS800 TEMP Drive IGBT temperature is excessive. Fault trip Check ambient conditions.
(4210) limit is 100%. Check air flow and fan operation.
07.11 bit 3 Check heatsink fins for dust pick-up.
Check motor power against unit power.
ACS TEMP xx y Excessive internal temperature in inverter unit Check ambient conditions.
(4210) of several parallel inverter modules. xx (1...12) Check air flow and fan operation.
refers to faulty inverter module number and y
07.11 bit 3 and Check heatsink fins for dust pick-up.
refers to faulty phase (U, V, W).
07.18 Check motor power against unit power.
AI < MIN FUNC Analogue control signal is below minimum Check for proper analogue control signal
(8110) allowed value due to incorrect signal level or levels.
failure in control wiring. Check control wiring.
07.12 bit 10
Programmable Check Fault Function parameters.
Fault Function
13.28 and 13.29
BC SHORT CIR Short circuit in brake chopper IGBT(s) Replace brake chopper.
(7113) Ensure brake resistor is connected and not
07.15 bit 2 damaged.
BRAKE ACKN Unexpected state of brake acknowledge signal See parameter group 28 BRAKE CTRL.
(FF74) Check connection of brake acknowledgement
07.14 bit 3 signal.
Programmable
Fault Function
28.06
BR BROKEN Brake resistor is not connected or it is Check resistor and resistor connection.
(7110) damaged. Check that resistance rating meets
07.15 bit 0 Resistance rating of brake resistor is too high. specifications. See drive hardware manual.
Fault tracing
254
CHOKE OTEMP Excessive temperature of drive output filter. Let drive cool down.
(FF82) Supervision is in use in step-up drives. Check ambient temperature.
Check filter fan rotates in correct direction and
air flows freely.
COMM MODULE Fieldbus or channel CH2 (Master/Follower link) Check status of fieldbus communication. See
(7510) communication brake chapter Fieldbus control, or appropriate
07.12 bit 12 fieldbus adapter manual.
Programmable Check parameter settings:
Fault Function - group 51 COMM MODULE DATA (for fieldbus
70.03, 70.07 and adapter), or
70.10 - group 52 STANDARD MODBUS (for
Standard Modbus Link)
- group 70 COMM INTERFACE.
Check cable connections.
Check if master communicates.
CTRL B TEMP Control board temperature is above 88°C. Check ambient conditions.
(4110) Check air flow.
07.12 bit 7 Check main and additional cooling fans.
CURR MEAS Current transformer failure in output current Check current transformer connections to Main
(2211) measurement circuit. Circuit Interface Board, INT.
CUR UNBAL xx Drive has detected excessive output current Check motor.
(2330) unbalance in inverter unit of several parallel Check motor cable.
connected inverter modules. This can be
07.11 bit 4 and Check that there are no power factor correction
caused by external fault (earth fault, motor,
07.18 or surge absorbers in motor cable.
motor cabling, etc.) or internal fault (damaged
Programmable inverter component). xx (2...12) refers to faulty
Fault Function inverter module number.
30.16
DC HIGH RUSH Drive supply voltage is excessive. When Check supply voltage level, drive rated voltage
(FF80) supply voltage is over 124% of unit voltage and allowed voltage range of drive.
rating (415, 500 or 690 V), motor speed rushes
to trip level (40% of nominal speed).
Fault tracing
255
DC UNDERVOLT Intermediate circuit DC voltage is not sufficient Check mains supply and fuses.
(3220) due to missing mains phase, blown fuse or
rectifier bridge internal fault.
07.12 bit 2
DC undervoltage trip limit is 0.6 · U1min, where
U1min is minimum value of mains voltage
range. For 400 V and 500 V units, U1min is
380 V. For 690 V units, U1min is 525 V. Actual
voltage in intermediate circuit corresponding to
mains voltage trip level is 307 VDC for 400 V
and 500 V units, and 425 VDC for 690 V units.
EARTH FAULT Drive has detected load unbalance typically Check motor.
(2330) due to earth fault in motor or motor cable. Check motor cable.
07.11 bit 4 Check there are no power factor correction
Programmable capacitors or surge absorbers in motor cable.
Fault Function
30.16
ENC1 CABLE Pulse encoder 1 phase signal is missing. Check pulse encoder 1 and its wiring.
(7310) Check pulse encoder interface module and its
07.26 bit 0 wiring.
Programmable
Fault Function
50.05
ENC2 CABLE Pulse encoder 2 phase signal is missing. Check pulse encoder 2 and its wiring.
(7382) Check pulse encoder interface module and its
07.26 bit 1 wiring.
Programmable
Fault Function
50.15
ENCODER A<>B Pulse encoder phasing is wrong: Phase A is Interchange connection of pulse encoder
(7302) connected to terminal of phase B and vice phases A and B.
versa.
ENCODER FLT Communication fault between pulse encoder Check pulse encoder and its wiring, module
(7301) and pulse encoder interface module and and its wiring and parameter group 50
between module and drive. ENCODER MODULES settings.
07.12 bit 5
Programmable
Fault Function
50.04
Fault tracing
256
ENCODER2 FLT Communication fault between pulse encoder Check pulse encoder and its wiring, module
(7381) and pulse encoder interface module and and its wiring and parameter group 50
between module and drive. ENCODER MODULES settings.
07.15 bit 12
Programmable
Fault Function
50.14
EXTERNAL FLT Fault in external device. (This information is Check external devices for faults.
(9000) configured through one of programmable Check Fault Function parameters.
digital inputs.)
07.12 bit 8
Programmable
Fault Function
30.02
FAN OVERTEMP Excessive temperature of drive output filter fan. Stop drive. Let it cool down.
(FF83) Supervision is in use in step-up drives. Check ambient temperature.
Check fan rotates in correct direction and air
flows freely.
FORCED TRIP Generic Drive Communication Profile trip See appropriate communication module
(FF8F) command manual.
ID RUN FAIL Motor ID Run is not completed successfully. Check maximum speed (parameter 20.02 MAX
(FF84) SPEED). It should be at least 80% of motor
nominal speed (parameter 99.06).
IN CHOKE TEMP Excessive input choke temperature Stop drive. Let it cool down.
(FF81) Check ambient temperature.
07.15 bit 5 Check that fan rotates in correct direction and
air flows freely.
INT CONFIG Number of inverter modules is not equal to Check status of inverters. See 07.18 INT
(5410) original number of inverters. FAULT INFO WORD on page 240.
07.15 bit 10 Check fibre optic cables between APBU and
inverter modules.
INV DISABLED Optional DC switch has opened while drive Close DC switch.
(3200) was running or start command was given. Check AFSC-0x Fuse Switch Controller unit.
07.15 bit 7
Fault tracing
257
INV OVERTEMP Converter module temperature is excessive. Check ambient temperature. If it exceeds
(4290) 40°C, ensure that load current does not
07.15 bit 13 exceed derated load capacity of drive. See
appropriate hardware manual.
Check converter module cooling air flow and
fan operation.
Cabinet installation: Check cabinet air inlet
filters. Change when necessary. See
appropriate hardware manual.
Modules installed in cabinet by user: Check
that cooling air circulation in cabinet has been
prevented with air baffles. See module
installation instructions.
Check inside of cabinet and heatsink of
converter module for dust pick-up. Clean when
necessary.
Reset and restart after problem is solved and
let converter module cool down.
I/O COMM ERR Fieldbus adapter (Rxxx type) communication Check connections.
(7000) error. Check fieldbus adapter parameters. See
07.12 bit 6 section Setting up communication through a
fieldbus adapter module on page 210.
LINE CONV Fault on line side converter Shift panel from motor side converter control
(FF51) board to line side converter control board.
07.11 bit 10 See line side converter manual for fault
description.
MOD CHOKE T Overtemperature in choke of liquid cooled R8i Check inverter fan.
(FF89) inverter module. Check ambient temperature.
7.26 bit 1 Check liquid cooling system.
MOTOR PHASE One of motor phases is lost due to fault in Check motor and motor cable.
(FF56) motor, motor cable, thermal relay (if used) or Check thermal relay (if used).
internal fault.
07.12 bit 15 Check Fault Function parameters. Disable this
Programmable protection.
Fault Function
30.15
MOTOR STALL Motor is operating in stall region due to e.g. Check motor load and drive ratings.
(7121) excessive load or insufficient motor power. Check Fault Function parameters.
07.12 bit 14
Programmable
Fault Function
30.09...30.11
Fault tracing
258
MOTOR TEMP Motor temperature is too high (or appears to be Check motor ratings, load and cooling
(4310) too high) due to excessive load, insufficient Check start-up data.
motor power, inadequate cooling or incorrect
07.11 bit 6 Check Fault Function parameters.
start-up data.
Programmable
Fault Function
30.03...30.08
MOTOR 1 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4312) fault limit set by parameter 35.03 MOT 1 TEMP Check that actual number of sensors
FLT L. corresponds to value set by parameter.
07.14 bit 1
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOTOR 2 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4313) fault limit set by parameter 35.06 MOT 2 TEMP Check that actual number of sensors
FLT L. corresponds to value set by parameter.
07.14 bit 2
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
NO MOT DATA Motor data is not given or motor data does not Check motor data given by parameters
(FF52) match with inverter data. 99.03...99.07.
07.12 bit 1
Fault tracing
259
OVERFREQ Motor is turning faster than highest allowed Check minimum/maximum speed settings.
(7123) speed due to incorrectly set minimum/ Check adequacy of motor braking torque.
maximum speed, insufficient braking torque or
07.11 bit 9 Check applicability of torque control.
changes in load when torque reference is
used. Check need for brake chopper and resistor(s).
OVER SWFREQ Switching frequency is too high. Check motor parameter settings (parameter
(FF55) group 99 START UP).
07.12 bit 9 Ensure that ID run has been completed
successfully.
PANEL LOSS Control panel or DrivesWindow selected as Check panel connection (see appropriate
(5300) active control location for drive has ceased hardware manual).
communicating. Check control panel connector.
07.12 bit 13
Programmable Replace control panel in mounting platform.
Fault Function Check Fault Function parameters.
30.01 Check DrivesWindow connection.
PARAM CRC CRC (Cyclic Redundancy Check) error Switch control board power off and on again.
(6320) Reload the firmware to the control board.
Replace the control board.
POSITION ERR Calculated position error exceeds limit set by Check setting of parameter 32.10 POS
(8500) parameter 32.10 POS ERROR WINDOW. ERROR WINDOW.
07.13 bit 0 Motor is stalled. Check that no torque limits are exceeded
during positioning.
POS LIM ERR Actual position value exceeds limits set by Check minimum and maximum position limits.
(8502) parameters 42.02 POSITION MIN and 42.01 Check parameters in group 43 HOMING.
07.13 bit 1 POSITION MAX.
POWERFAIL INT board powerfail in several inverter units in Check that INT board power cable is
(3381) parallel connected inverter modules. connected.
07.15 bit 9 Check that POW board is working correctly.
Replace INT board.
POWERF INV xx INT board powerfail in inverter unit consisting Check that INT board power cable is
(3381) of several parallel inverter modules. xx refers connected.
to inverter module number. Check that POW board is working correctly.
07.15 bit 9 and
07.18 Replace INT board.
PPCC LINK Fibre optic link to INT board is faulty. Check fibre optic cables or galvanic link. With
(5210) frame sizes R2...R6 link is galvanic.
07.12 bit 11 If RMIO is powered from external supply,
ensure that supply is on.
PPCC LINK xx INT board fibre optic connection fault in Check connection from inverter module Main
(5210) inverter unit consisting of several parallel Circuit Interface Board, INT to PPCC
inverter modules. xx refers to inverter module Branching Unit, PBU. (Inverter module 1 is
07.12 bit 11 and
number. connected to PBU INT1 etc.)
07.18
Fault tracing
260
RUN DISABLED No Run enable signal received. Check setting of parameter 10.07 RUN
(FF54) ENABLE. Switch on signal or check wiring of
selected source.
07.12 bit 4
SC INV xx y Short circuit in inverter unit of several parallel Check motor and motor cable.
(2340) inverter modules. xx (1...12) refers to faulty Check power semiconductors (IGBT power
07.11 bit 0 and inverter module number and y refers to faulty plates) of inverter module.
07.18 and 07.19 phase (U, V, W).
SHORT CIRC Short-circuit in motor cable(s) or motor Check motor and motor cable.
(2340) Check there are no power factor correction
07.11 bit 0 capacitors or surge absorbers in motor cable.
SLOT OVERLAP Two option modules have same connection Check connection interface selections in
(FF8A) interface selection. groups 70 COMM INTERFACE, 51 COMM
MODULE DATA and 12 DIGITAL INPUTS.
START INHIBI Optional start inhibit hardware logic is Check start inhibit circuit (AGPS board).
(FF7A) activated.
06.02 bit 8
THERMAL MODE Motor thermal protection mode is set to DTC See parameter 30.04 MOT THERM P MODE.
(FF50) for high-power motor.
THERMISTOR Motor temperature is excessive. Motor thermal Check motor ratings and load.
(4311) protection mode selection is THERMISTOR. Check start-up data.
07.11 bit 5 Check thermistor connections.
Programmable Check thermistor cabling.
Fault Function
30.03…30.04
Fault tracing
261
UNDERLOAD Motor load is too low due to e.g. release Check for problem in driven equipment.
(FF6A) mechanism in driven equipment. Check Fault Function parameters.
07.11 bit 8
Programmable
Fault Function
30.12…30.14
USER MACRO No User Macro saved or file is defective. Create User Macro.
(FFA1)
07.16 bit 1
Fault tracing
262
Fault tracing
263
Symbol Description
21.04
Switch
23.05...23.07
A Speed controller settings
ACC COMPENSATION 23.12
23.08...23.10
Selector
Switch
Table 1
Selector
05.01 B6
RAMP_IN_ZERO
11.01
11.03 EXT2 CNTROL PLACE SEL
CONTROL
MODE
265
MAX SPEED
20.02 06.02 B10 TORQ CONTROL
Power limit
OVERVOLTAGE CTRL 20.13 POWER MAX LIM
06.14 B0, B1 POWER MIN LIM
UNDERVOLTAGE CTRL 20.14
Selector
Switch
Table 1
Table 2
41.05 CAM
DISK SEL
41.06
CYC DISK TBL SEL
Synchron
Switch CAM table
gear
ENC2
M/F REF1
SYNC GEAR INPUT
VIRTUAL MAST 04.09 x SYNC POS REF
y 04.08
SYNC GEAR NUM E
41.02
SYNC POS REF SEL 41.01 SYNC GEAR DEN
41.03
The following block diagram presents the synchron reference chain:
267
Selector
Switch
NOT SEL Selector
Table 1 AI1
AI2
AI3 n
Table 2 EXT AI1
40.13 POS EXT AI2
SPEED CAM MAIN DS REF1
MAIN DS REF2 40.12 POS
The following block diagram presents the position reference chain:
40.04 SPEED
AUX DS REF1
POS SPEED CAM SEL AUX DS REF2 MUL SEL
AUX DS REF3
M/F REF1
M/F REF2
PROG AI1-7
SPEED FEED GAIN SPEED FEED FORW
42.08 4.13
X
DYN LIM ENA
Switch
42.03
D POSITION Position Inverted gear
Dynamic limiter ERROR controller
POS CTRL REF + x y
.
+
E 4.12 4.14 z v
.
+ A
11.01 42.04, 42.05 SYNCHRON –
42.06, 42.07 ERROR 19.07, 19.10
CONTROL
PLACE SEL 4.11 42.09 POS
4.02 19.09, 19.08
POS ACT VAL CTRL GAIN
Load gear Switch
ENC1 ENC1
x
y
ENC2
19.09, 19.10
19.11 POS
ACT SEL
ENC2
Motor gear
50.11
50.12 Filter
ENC2 03.07 SPEED MEAS ENC2
50.13
50.14 SPEED MOTOR ACCELERATIO
d
1.03 1.07
dt
The following block diagram presents the load and motor gear calculations:
19.16 MOTOR
SP FILT TIM
269