NAME OF THE WORK:-Design, Supply and Installation of 2X500 MVA ICT for Out Door Type,400/220 KV GIS Grid Sub-station at
(Ramkrushnapur),Bhadrak.in Odisha State of India under PACKAGE-3 Under Japan International Cooperation Agency (JICA)’s ODA Loan.
Loan Agreement No: [ID-P245] - FB No: [CPC/JICA/ICB/03 /18-19]- Reference Identification No: [OPTCL/JICA/PKG-3]
Schedule No. 1. Plant Supplied from Abroad (Sub-station )
NAME OF THE BIDDER
2 Nos.(FDR-2,TFR-2,B/C-1)
SUPPLY OF FOLLOWING EQUIPMENTS 2
SL. NO. Code1 UNIT
In Foreign Total Price
(As per Technical Specification)
CIP
Currency
420kV, 3150A, 63kA, 3 Sec, Single phase, SF6 gas Insulated Bus Duct
outside GIS Bay along with associated Support structure arrangement
bends, joints, accessories, & its earthing arrangement with earthing strips
1.3 RM 900
of adequate size (as per IEEE Std 80-2013 to protect operating staff
against any hazardous touch voltages and electro-magnetic
interferences) etc. as per the technical specification.
420kV, 3150A, 63kA, SF6/Air BUSHING (Bushing shall be of Polymer /
composite insulator type and shall be seamless sheath of a silicone
rubber compound. The hollow silicone composite insulators shall comply
1.4 No 18
as per IEC 61462 and IEC 62217. The design of the composite insulators
shall be tested and verified according to IEC 61462) FOR CONNECTING
GIS TO AIS along with support structure.
Online continuous Partial Discharge Monitoring System (PDM):
420kV GIS equipment system shall have Online continuous Partial
Discharge Monitoring System (PDM) system to provide an automatic
facility for the simultaneous collection of PD data at multiple points on the
GIS & its associated GIB ducts and Voltage Transformers adopting UHF
technique & the data stored shall provide a historical record of the
progress of PD sources and shall identify the areas of maximum activity.
1.5 Set 1
PDM system shall be interfacing with UHF PD couplers provided. The PD
Monitoring PC Work Station along with all accessories shall be
considered. Power supply to PDM PC shall have protection against
surges, overload and short circuit. A dedicated on-line UPS system shall
also be provided as a backup during supply interruption, to ensure trouble-
free & reliable running of the PDM System for a minimum of 15 minutes
duration.
3150A, 50kA for 3s, Double Busbar Circuit Breaker (Circuit breaker
shall be E2-C2-M2 class as per IEC 62271-100) arrangement.
245kV OUTDOOR GIS EQUIPMENT as per latest IEC standard & type
2 tested equipment as per technical specification, with open future
proof & flexible system in line with IEC 61850 & IEC 62271-203.
245kV, 3150A, 50 kA, 3 sec, single phase, SF6 gas Insulated Bus Duct
outside GIS Bay along with associated Support structure arrangement
bends, joints,accessories, & its earthing arrangement with earthing strips
2.5 RM 1000
of adequate size (as per IEEE Std 80-2013 to protect operating staff
against any hazardous touch voltages and electro-magnetic
interferences) as per the technical specification.
245kV,3150A, 50kA SF6/Air BUSHING (Bushing shall be of Polymer /
composite insulator type and shall be seamless sheath of a silicone
rubber compound. The hollow silicone composite insulators shall comply
2.6 No 21
as per IEC 61462 and IEC 62217. The design of the composite insulators
shall be tested and verified according to IEC 61462) FOR CONNECTING
GIS TO AIS along with support structure.
Portable Partial Discharge Monitoring System (PDM):
245kV system shall have Portable Partial Discharge Monitoring System
(PDM) & shall be capable for measuring PD in charged GIS environment,
bandwidth in order of 100MHz–2GHz & provision to select a wide range of
intermediate bandwidths and the principle of operation shall be based on
2.7 UHF principle of detection. The Detection and measurement of PD and Set 1
bouncing particles having in built large coloured LCD for displaying and
storing facility in the instrument for further analysis to locate actual source
of PD such as free conducting particles, floating components, voids in
spacers, particle on spacer surfaces etc.
3.1 420 KV, 3150 A, 63 KA, Center break ISOLATORS WITH EARTH SWITCH Nos 4
420KV 1 phase Solid core bus post insulator (AIS) as per technical
3.2 NOS 6
specification.
3.3 245 KV, 2000A, 40KA, Center break ISOLATORS WITH EARTH SWITCH NOS 4
245KV 1 phase Solid core bus post insulator (AIS) as per technical
3.4 NOS 6
specification.
400KV metal oxide surge arrrestor, 20 KA , Long duration discharge
3.5 NOS 18
class IV , 12KJ/KV at 336KV as per technical specification.
216KV metal oxide surge arrrestor, 10KA Long duration discharge class
3.6 NOS 21
III , 10 KJ/KV at 216KV as per technical specification.
30 KV, METAL OXIDE SURGE ARRESTOR, 10kA, Long duration
3.7 NOS 9
discharge class III (AIS) as per technical specification.
36 KV ,1250A, 31.5 KA for 1 sec, isolator (single isolator with earth
3.8 SET 2
switch) including post insulators as per technical specification
4 36KV GIS equipment
36KV, 1250A, 31.5kA for 3 sec, SF6 gas insulated transformer bay module
each comprising of SF6 gas insulated Vacuum circuit breaker , current
4.1 transformer , bus-bar disconnectors with common grounding switch , SF6 gas SET 3
monitoring system for complete bay (having 33 KV Bus Bar of 2000 Amp) to
complete transformer bay module suitable for cable connection to transformer.
36KV, 1250A , 31.5kA for 3 sec, (33 KV Bus Bar 2000 Amp) SF6 gas
insulated bus-coupler bay module comprising of SF6 gas insulated vacuum
circuit breaker , current transformer , disconnector switches & bus bars each
4.2 enclosed in bus enclosures running along the length of the switch gear to inter- Nos 1
connect each of circuit breaker bay module. Each busbar set shall be complete
with potential transformer , disconnectors, SF6 gas monitoring system for the
complete bus etc.
XLPE Power Copper conductor cable for the GIS system (36
4.3 KV class) and cable termination kit for Indoor & outdoor
36KV Indoor type termination kits (GIS side) suitable for 1CX 630
4.3.3 NOS 3
sq. mm
36 kV Outdoor type termination Kits (33 KV Transformer side)
4.3.4 NOS 3
suitable for 1CX 630 sq. mm
36 kV Indoor type termination Kits (GIS side) suitable for 1CX300
4.3.5 NOS 6
Sq.mm
36 kV Outdoor type termination Kits (33 KV Station Transformer
4.3.6 NOS 6
side) suitable for 1CX300 Sq.mm
4.4 36 KV Bus Post Insulator as per technical specification Nos 9
All type of Terminal clamp & connectors suitable for 36 KV, 1250 A for
4.5 station transformers. LOT 1
Yard AC Kiosk :5000 mm (L)x4000mm (W)x 3300mm (H) with AC, as per
19.1 Nos. 4
the Specification;
Gate way panel for Sub-Station Automation (in PRP as per the
specification & indicative drg ) system (for All 400 , 220 & 33 KV side bays
including the future bays),other accessories (comprising servers, engg.
Station, works station (Main & standby), Remote station control, Colour
Laser jet Printers & dot matrix printer for local station as per requirement
and also for remote station, Ethernet Switches , LIU, Red Box, Multimode
19.2 glass fibre Doublle jacket armoured optical cables, special cables like SET 1
F.O patch cord & armoured FO cables of adequate length etc required for
the system in all respect as per latest IEC 61850 standard, Inverters of
required capacity & rating (3KVA-Input shall be both A.C & D.C and
output shall be A.C) etc as per TS. A Full HD LED screen of 70 inches
for display including all type of accessories & as per technical
specification.
BCU for Substation Auxilliary System (Datas for monitoring of Station AC,
19.3 Station DC, Lighting, Fire fighting, Air conditioning, Diesel generator etc. SET 1
as per the site requirement)
19.4 GPS System with PTP, IRIG-B, SNTP SET 1
400 KV SIDE PROTECTION & OTHER PANELS as per Technical
19.5
specification.
FEEDER PROTECTION PANEL (MAIN-I , MAIN-II & BACK-UP
19.5.1 PROTECTION WITH AUTO RECLOSURE DISTANCE PROTECTION NOS 4
with Bay control unit (BCU) for substation automation system.
TRANSFORMER PROTECTION PANEL (DIFFERENTIAL I &II , REF I &
II & BACK-UP PROTECTION for HV & IV side CONSIDERING HV ,IV &
19.5.2 SET 2
LV side for 500 MVA 400/220/33 KV ICT) with Bay control units (BCU) for
substation automation system.
TIE BREAKER PROTECTION PANEL with Bay control unit (BCU) for
19.5.3 NOS 3
substation automation system.
BUS-BAR PROTECTION PANEL ( Including Provision of bus bar
19.5.4 modules for the future bays and to be integrated with the Automation NOS 1
system)
19.6 220 KV SIDE PROTECTION & OTHER PANELS
FEEDER PROTECTION PANEL (MAIN-I , MAIN-II & BACK-UP
19.6.1 PROTECTION WITH AUTO RECLOSURE DISTANCE PROTECTION NOS 4
with Bay control unit (BCU) for substation automation system.
TRANSFORMER PROTECTION PANEL (DIFFERENTIAL I &II , REF I &
19.6.2 II & BACK-UP PROTECTION for HV & LV side CONSIDERING HV & LV NOS 1
side for 40 MVA220/33 KV Power Trnsformer) with Bay control units
(BCU)COUPLER
BUS for substation automation PANEL
PROTECTION system. with Bay control unit (BCU) for
19.6.3 NOS 1
substation automation system.
BUS-BAR PROTECTION PANEL ( Provision of bus bar modules for the
19.6.4 NOS 1
future bays and to be integrated with the Automation system)
19.7 33 KV SIDE PROTECTION PANELS
33 KV BUS COUPLER PROTECTION Panel with Bay control protection
unit (BCPU) with with all other relays & component required for complete
19.7.1
prtection,control etc as per TS and also suitable for substation automation
No 1
system.
STATION TRANSFORMER PROTECTION PANEL (BACK-UP
PROTECTION CONSIDERING 2X500 KVA 33/0.43 KV ) with
Bay control protection units (BCPU) with with all other relays &
19.7.2 SET 1
component required for complete prtection,control etc as per TS and
also suitable for substation automation system. [2nos. Feeeder bays
in one panel]
20 AC & DC SYSTEM
20.1 AC SYSTEM
MAIN AC DB,(HAVING A 1600 A,50KA,DRAWOUT TYPE ACB WITH 3
O/C,E/F,U/V RELAYING FACILITY and MECH& ELECT INTERLOCK
20.1.1 FACILITY CONSIDERING Main-1,2 & DG INDOOR TYPE AS PER SET 1
SPECIFICATION.(MAIN DB-1,MAIN DB-2 WITH B/C & PROVISION FOR
D.G INCOMING)
ACDB (HAVING 800A MCCB) AS PER SPECIFICATION (AC DB-1,AC
20.1.2 SET 1
DB-2 WITH B/C)
MAIN LIGHTING DISTRIBUTION BOARD (HAVING 250A MCCB AS
20.1.3 SET 1
INCOMER)AS PER SPECIFICATION (WITH DB-1,DB-2 & B/C)
INDOOR LIGHTING DISTRIBUTION BOARD AS PER SPECIFICATION.
20.1.4 SET 1
(WITH DB-1,DB-2 & B/C)
20.1.5 EMERGENCY LIGHTING DISTRIBUTION BOARD SET 1
20.1.6 INDOOR RECEPTACLE BOARD SET 2
20.2 DC SYSTEM
220 V DC BOARD (HAVING 100A DC MCCB AS INCOMER, E/F (EARTH
LEAKAGE), UNDER & OVER VOLTAGE AS PER SPECIFICATION (DC
20.2.1 DB-1,DC DB-2 & B/C). Consider separate source(DC1 & DC 2) to each SET 1
panels & accordingly sufficient nos. of DC output from DB-1 & 2 to be
considered.
20.2.2 220 V DC EMERGENCY DISTRIBUTION BOARD SET 1
20.2.3 BATTERY (645 AH PLANTE TYPE) for 220 V DC SET 2
BATTERY CHARGER FOR 645 AH, 220 V DC (FLOAT & FLOAT CUM
BOOST) (including provision of series dropper diodes with heat sinks &
20.2.4 SET 2
other protection facility at the DC Load terminal end in order to feed 220
V to the load).
DE MINERALISED PLANT of 30 L/Hr FOR MAKING DISTLED WATER
21 SET 1
FOR BATTERY BANKS
PORTABLE ALUMINIUM LADDER EXTENDABLE TYPE OF ADEQUATE
HEIGHT TO BE USED FOR MAINTENANCE OF EQUIPMENT INSIDE
22 NOS 2
SWITCH YARD.(REFER TS-VOL-IIA-SCOPE OF WORKAT SL NO. 19)
400/220 KV 500 MVA ICT (inclusive of all costs towards type test
charges, Mandatory spares, Spanners & Special tools, Oil storage tank,
Nitrogen Injection system for protection against Fire & Explosion, On line
32 NOS 2
insulating oil drying system , On line Dissolved Gas (Multi-gas) and
Moisture Analyser, accessories, etc as specified in the Technical
specification)
33 EQUIPMENT and MATERIALS for GIS
33.1 ACCESSORIES
SF6 Gas handling plant of adequate capacity as per the Technical
33.1.1 SET 1
specification.
SF6 gas service cart with all accessories as per the Technical
33.1.2 SET 1
specification.
33.2 TESTING EQUIPMENT
33.2.1 GIS testing equipment as per the Technical specification. SET 1
34 ESSENTIAL TOOLS and SPARES for GIS
34.1 SPARES for 420KV GIS
34.1.1 Single phase voltage transformer SET 1
34.1.2 Single phase set of 5 cores current transformer including enclosure SET 1
34.1.3 Enclosure insulators and main circuit of busbar SET 1
34.1.4 Tripping and closing coils SET 3
34.1.5 SF6 Pressure gauges SET 2
34.1.6 SF6 Pressure relief devices SET 2
34.1.7 Auxiliary contacts for circuit breaker SET 1
34.1.8 Auxiliary contacts for DS and ES SET 1
34.1.9 SF6 gas in steel bottle 52 kg / bottle NOS 2
34.1.10 Spring charge motor for circuit breakers UNIT 1
Complete drive mechanism for disconnect switches and grounding
34.1.11 UNIT 1
switches
34.1.12 Motor for disconnect switches and grounding switches UNIT 1
34.1.13 Complete drive mechanism for fast acting grounding switches UNIT 1
34.1.14 Motor for fast acting grounding switches UNIT 1
34.1.15 Rupture disc for circuit breakers / potential transformer NOS 1
Set of spares for local control cabinet including M.C.B., fuses, time relays,
34.1.16 SET 1
auxiliary relays and terminals
34.1.17 Rupture disc for other compartments NOS 2
34.2 SPARES for 245KV GIS
34.2.1 Single phase voltage transformer SET 1
34.2.2 Single phase set of 5 cores current transformer including enclosure SET 1
34.2.3 Enclosure insulators and main circuit of busbar SET 1
34.2.4 Tripping and closing coils SET 3
34.2.5 SF6 Pressure gauges SET 2
34.2.6 SF6 Pressure relief devices SET 2
34.2.7 Auxiliary contacts for circuit breaker SET 1
34.2.8 Auxiliary contacts for DS and ES SET 1
34.2.9 Spring charge motor for circuit breakers UNIT 1
Complete drive mechanism for disconnect switches and grounding
34.2.10 UNIT 1
switches
34.2.11 Motor for disconnect switches and grounding switches UNIT 1
34.2.12 Complete drive mechanism for fast acting grounding switches UNIT 1
34.2.13 Motor for fast acting grounding switches UNIT 1
34.2.14 Rupture disc for circuit breakers / potential transformer NOS 1
Set of spares for local control cabinet including M.C.B., fuses, time relays,
34.2.15 SET 1
auxiliary relays and terminals
34.2.16 Rupture disc for other compartments NOS 2
34.3 SPECIAL TOOLS
34.3.1 SF6 gas leak detector as per the Technical specification. SET 1
34.3.2 SF6 gas analyzer as per the Technical specification. SET 1
34.3.3 Milli volt drop measurement applicance SET 1
34.3.4 One set of Box Spanner SET 1
34.3.5 One set of adjustable Spanner SET 1
34.3.6 SF6 gas bottle locking, measuring and filling assembly with all hose SET 2
34.3.7 One set of pipe grooving tools for the hydraulic operating mechanism SET 1
34.3.8 Infrared camera as per the Technical specification. SET 1
TOTAL OF SUBSTATION-SCHEDULE-1 -Plant (to Schedule No. 6 Grand Summary)
Name of Bidder:_______________________________
Signature of Bidder:_____________________________
1
Bidders shall enter a code representing the country of origin of all imported plant and equipment.
2
Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid, or ITB 34.1 in Two-Stage Bid. Create and use as many
columns for Unit Price and Total Price as there are currencies.
Country of Origin Declaration Form
Item Description Code Country
ODISHA POWER TRANSMISSION CORPORATION LIMITED
NAME OF THE WORK:-Design, Supply and Installation of 2X500 MVA ICT for Out Door Type,400/220 KV GIS Grid Sub-station at
(Ramkrushnapur),Bhadrak.in Odisha State of India under PACKAGE-3 Under Japan International Cooperation Agency (JICA)’s
ODA Loan.
Loan Agreement No: [ID-P245] - FB No: [CPC/JICA/ICB/03 /18-19]- Reference Identification No: [OPTCL/JICA/PKG-3]
Schedule No. 2. Plant Supplied from Within the Employer’s Country (Sub-station )
NAME OF THE BIDDER
2 Nos.(FDR-2,TFR-2,B/C-1)
SUPPLY OF FOLLOWING EQUIPMENTS
SL. NO.
(As per Technical Specification)
UNIT Unit Price1 Total Price1
3150A, 50kA for 3s, Double Busbar Circuit Breaker (Circuit breaker
shall be E2-C2-M2 class as per IEC 62271-100) arrangement.
245kV OUTDOOR GIS EQUIPMENT as per latest IEC standard & type
2 tested equipment as per technical specification, with open future
proof & flexible system in line with IEC 61850 & IEC 62271-203.
245kV, 3150A, 50kA for 3 sec (Busbar, CB, Disconnector, Grounding
Switch & CT), SF6 gas insulated ICT Feeder Bay Module each comprising
of SF6 gas insulated Single Pole Circuit Breaker (1 Set), Single Phase
Current Transformer (6 Nos), Motorised Busbar 3 Phase Disconnector (2
Nos), Motorised Disconnector (1 No), Motorised safety Grounding switch
(3 Nos), Local Control Cubicle, SF6 gas monitoring system for complete
bay, SF6 bus duct termination arrangement (3 Nos), PD sensor (adequate
number of UHF sensors in the offered GIS equipment for detection of
2.1 Partial discharge (of 5 pC and above) as per IEC 60270 through Partial Set 3
Discharge (PD) monitoring system), different gas compartment, O-ring &
gaskets, Nuts, Bolts & Washers for Outdoor use, Absorbent, Limit Switch,
SF6 Gas, etc. to complete ICT Feeder Bay Module & its earthing
arrangement with earthing strips of adequate size (as per IEEE Std 80-
2013 to protect operating staff against any hazardous touch voltages and
electro-magnetic interferences) as per the technical specification.
245kV, 3150A, 50kA for 3 sec (CB, Disconnector, Grounding switch & CT),
SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas
insulated Single Pole Circuit Breaker (1 Set), Single Phase Current
Transformer (6 Nos), Motorised 3 Phase Disconnector (2 Nos), Motorised
safety Grounding switch (2 Nos), Local Control Cubicle, SF6 gas
monitoring system, PD sensor (adequate number of UHF sensors in the
offered GIS equipment for detection of Partial discharge (of 5 pC and
2.4 above) as per IEC 60270 through Partial Discharge (PD) monitoring Set 1
system), different gas compartment, O-ring & gaskets, Nuts, Bolts &
Washers for Outdoor use, Absorbent, Limit Switch, SF6 Gas, etc. to
complete Bus Coupler Bay Module & its earthing arrangement with
earthing strips of adequate size (as per IEEE Std 80-2013 to protect
operating staff against any hazardous touch voltages and electro-magnetic
interferences) as per the technical specification.
245kV, 3150A, 50 kA, 3 sec, single phase, SF6 gas Insulated Bus Duct
outside GIS Bay along with associated Support structure arrangement
bends, joints,accessories, & its earthing arrangement with earthing strips
2.5 RM 1000
of adequate size (as per IEEE Std 80-2013 to protect operating staff
against any hazardous touch voltages and electro-magnetic interferences)
as per the technical specification.
245kV,3150A, 50kA SF6/Air BUSHING (Bushing shall be of Polymer /
composite insulator type and shall be seamless sheath of a silicone rubber
compound. The hollow silicone composite insulators shall comply as per
2.6 No 21
IEC 61462 and IEC 62217. The design of the composite insulators shall be
tested and verified according to IEC 61462) FOR CONNECTING GIS TO
AIS along with support structure.
Portable Partial Discharge Monitoring System (PDM):
245kV system shall have Portable Partial Discharge Monitoring System
(PDM) & shall be capable for measuring PD in charged GIS environment,
bandwidth in order of 100MHz–2GHz & provision to select a wide range of
intermediate bandwidths and the principle of operation shall be based on
2.7 UHF principle of detection. The Detection and measurement of PD and Set 1
bouncing particles having in built large coloured LCD for displaying and
storing facility in the instrument for further analysis to locate actual source
of PD such as free conducting particles, floating components, voids in
spacers, particle on spacer surfaces etc.
3.1 420 KV, 3150 A, 63 KA, Center break ISOLATORS WITH EARTH SWITCH Nos 4
420KV 1 phase Solid core bus post insulator (AIS) as per technical
3.2 NOS 6
specification.
3.3 245 KV, 2000A, 40KA, Center break ISOLATORS WITH EARTH SWITCH NOS 4
245KV 1 phase Solid core bus post insulator (AIS) as per technical
3.4 NOS 6
specification.
400KV metal oxide surge arrrestor, 20 KA , Long duration discharge class
3.5 NOS 18
IV , 12KJ/KV at 336KV as per technical specification.
216KV metal oxide surge arrrestor, 10KA Long duration discharge class III
3.6 NOS 21
, 10 KJ/KV at 216KV as per technical specification.
30 KV, METAL OXIDE SURGE ARRESTOR, 10kA, Long duration
3.7 NOS 9
discharge class III (AIS) as per technical specification.
36 KV ,1250A, 31.5 KA for 1 sec, isolator (single isolator with earth switch)
3.8 SET 2
including post insulators as per technical specification
4 36KV GIS equipment
36KV, 1250A, 31.5kA for 3 sec, SF6 gas insulated transformer bay module
each comprising of SF6 gas insulated Vacuum circuit breaker , current
transformer , bus-bar disconnectors with common grounding switch , SF6 gas
4.1 SET 3
monitoring system for complete bay (having 33 KV Bus Bar of 2000 Amp) to
complete transformer bay module suitable for cable connection to transformer.
36KV, 1250A , 31.5kA for 3 sec, (33 KV Bus Bar 2000 Amp) SF6 gas
insulated bus-coupler bay module comprising of SF6 gas insulated vacuum circuit
breaker , current transformer , disconnector switches & bus bars each enclosed in
4.2 bus enclosures running along the length of the switch gear to inter-connect each of Nos 1
circuit breaker bay module. Each busbar set shall be complete with potential
transformer , disconnectors, SF6 gas monitoring system for the complete bus etc.
XLPE Power Copper conductor cable for the GIS system (36
4.3
KV class) and cable termination kit for Indoor & outdoor
36 KV XLPE 630 SQ. MM single core copper Cable as per tech
4.3.1 spec (for connectivity from 33 KV side of 220/33 KV Transformer to Mtr 600
33 KV GIS panel)
33KV CABLE 300 SQ. MM single core copper as per tech spec
(for 33 KV connectivity from GIS equipment to Station Transformer
4.3.2 Mtr 1500
(two nos station trafo) & outgoing feeders upto DP structure end)
36KV Indoor type termination kits (GIS side) suitable for 1CX 630
4.3.3 NOS 3
sq. mm
36 KV Cable termination kit including Cable to Air Bushing suitable for
4.3.4 outdoor for 33 KV side of Transformer suitable for 1CX630 Sqmm copper cable. NOS 3
Yard AC Kiosk :5000 mm (L)x4000mm (W)x 3300mm (H) with AC, as per
19.1 Nos. 4
the Specification;
Gate way panel for Sub-Station Automation (in PRP as per the
specification & indicative drg ) system (for All 400 , 220 & 33 KV side bays
including the future bays),other accessories (comprising servers, engg.
Station, works station (Main & standby), Remote station control, Colour
Laser jet Printers & dot matrix printer for local station as per requirement
and also for remote station, Ethernet Switches , LIU, Red Box, Multimode
19.2 glass fibre Doublle jacket armoured optical cables, special cables like F.O SET 1
patch cord & armoured FO cables of adequate length etc required for the
system in all respect as per latest IEC 61850 standard, Inverters of
required capacity & rating (3KVA-Input shall be both A.C & D.C and output
shall be A.C) etc as per TS. A Full HD LED screen of 70 inches for
display including all type of accessories & as per technical specification.
BCU for Substation Auxilliary System (Datas for monitoring of Station AC,
19.3 Station DC, Lighting, Fire fighting, Air conditioning, Diesel generator etc. as SET 1
per the site requirement)
19.4 GPS System with PTP, IRIG-B, SNTP SET 1
400 KV SIDE PROTECTION & OTHER PANELS as per Technical
19.5
specification.
FEEDER PROTECTION PANEL (MAIN-I , MAIN-II & BACK-UP
19.5.1 PROTECTION WITH AUTO RECLOSURE DISTANCE PROTECTION NOS 4
with Bay control unit (BCU) for substation automation system.
TRANSFORMER PROTECTION PANEL (DIFFERENTIAL I &II , REF I &
II & BACK-UP PROTECTION for HV & IV side CONSIDERING HV ,IV &
19.5.2 SET 2
LV side for 500 MVA 400/220/33 KV ICT) with Bay control units (BCU) for
substation automation system.
TIE BREAKER PROTECTION PANEL with Bay control unit (BCU) for
19.5.3 NOS 3
substation automation system.
BUS-BAR PROTECTION PANEL ( Including Provision of bus bar
19.5.4 modules for the future bays and to be integrated with the Automation NOS 1
system)
19.6 220 KV SIDE PROTECTION & OTHER PANELS
FEEDER PROTECTION PANEL (MAIN-I , MAIN-II & BACK-UP
19.6.1 PROTECTION WITH AUTO RECLOSURE DISTANCE PROTECTION NOS 4
with Bay control unit (BCU) for substation automation system.
TRANSFORMER PROTECTION PANEL (DIFFERENTIAL I &II , REF I &
II & BACK-UP PROTECTION for HV & LV side CONSIDERING HV & LV
19.6.2 NOS 1
side for 40 MVA220/33 KV Power Trnsformer) with Bay control units
(BCU) for substation automation system.
BUS COUPLER PROTECTION PANEL with Bay control unit (BCU) for
19.6.3 NOS 1
substation automation system.
BUS-BAR PROTECTION PANEL ( Provision of bus bar modules for the
19.6.4 NOS 1
future bays and to be integrated with the Automation system)
19.7 33 KV SIDE PROTECTION PANELS
33 KV BUS COUPLER PROTECTION Panel with Bay control protection
unit (BCPU) with with all other relays & component required for complete
19.7.1
prtection,control etc as per TS and also suitable for substation automation
No 1
system.
STATION TRANSFORMER PROTECTION PANEL (BACK-UP
PROTECTION CONSIDERING 2X500 KVA 33/0.43 KV ) with
Bay control protection units (BCPU) with with all other relays &
19.7.2 SET 1
component required for complete prtection,control etc as per TS and
also suitable for substation automation system. [2nos. Feeeder bays
in one panel]
20 AC & DC SYSTEM
20.1 AC SYSTEM
MAIN AC DB,(HAVING A 1600 A,50KA,DRAWOUT TYPE ACB WITH 3
O/C,E/F,U/V RELAYING FACILITY and MECH& ELECT INTERLOCK
20.1.1 FACILITY CONSIDERING Main-1,2 & DG INDOOR TYPE AS PER SET 1
SPECIFICATION.(MAIN DB-1,MAIN DB-2 WITH B/C & PROVISION FOR
D.G INCOMING)
ACDB (HAVING 800A MCCB) AS PER SPECIFICATION (AC DB-1,AC DB-
20.1.2 SET 1
2 WITH B/C)
MAIN LIGHTING DISTRIBUTION BOARD (HAVING 250A MCCB AS
20.1.3 SET 1
INCOMER)AS PER SPECIFICATION (WITH DB-1,DB-2 & B/C)
INDOOR LIGHTING DISTRIBUTION BOARD AS PER SPECIFICATION.
20.1.4 SET 1
(WITH DB-1,DB-2 & B/C)
20.1.5 EMERGENCY LIGHTING DISTRIBUTION BOARD SET 1
20.1.6 INDOOR RECEPTACLE BOARD SET 2
20.2 DC SYSTEM
220 V DC BOARD (HAVING 100A DC MCCB AS INCOMER, E/F (EARTH
LEAKAGE), UNDER & OVER VOLTAGE AS PER SPECIFICATION (DC
20.2.1 DB-1,DC DB-2 & B/C). Consider separate source(DC1 & DC 2) to each SET 1
panels & accordingly sufficient nos. of DC output from DB-1 & 2 to be
considered.
20.2.2 220 V DC EMERGENCY DISTRIBUTION BOARD SET 1
20.2.3 BATTERY (645 AH PLANTE TYPE) for 220 V DC SET 2
BATTERY CHARGER FOR 645 AH, 220 V DC (FLOAT & FLOAT CUM
BOOST) (including provision of series dropper diodes with heat sinks &
20.2.4 SET 2
other protection facility at the DC Load terminal end in order to feed 220 V
to the load).
DE MINERALISED PLANT of 30 L/Hr FOR MAKING DISTLED WATER
21 SET 1
FOR BATTERY BANKS
PORTABLE ALUMINIUM LADDER EXTENDABLE TYPE OF ADEQUATE
HEIGHT TO BE USED FOR MAINTENANCE OF EQUIPMENT INSIDE
22 NOS 2
SWITCH YARD.(REFER TS-VOL-IIA-SCOPE OF WORKAT SL NO. 19)
CARTWHEEL MOUNTED ALUMINIUM LADDER OF ADEQUATE
23 NOS 1
HEIGHT TO BE USED FOR MAINTENANCE OF EQUIPMENT .
WATER COOLER WITH WATER PURIFIER (with R.O & ultra violet
24 NOS 1
purification system of ISI mark) SYSTEM
MAINTENANCE & TESTING EQUIPMENT (REFER TS-VOL-IIA-16.
Maintenance & Testing Equipment (ANNEXURE-II & ANNEXURE-III)
25 LOT 1
INDICATED IN -SCHEDULE OF REQUIREMENTS OF MAINTENANCE
EQUIPMENT).
SET
26 WALKIE TALKIE SET 2
/PAIR
OFFICE FURNITURE (REFER TS-VOL-IIA-SCOPE OF WORKAT SL
NO. 18 ANNEXURE - IV ,INDICATED IN SCHEDULE OF
27 REQUIREMENTS OFFICE FURNITURE) & PLACING IN CONTROL LOT 1
ROOM,CONFERENCE ROOM,OFFICE ROOMS,LIBRARY,TESTING
LAB,etc.
FIRE FIGHTING EQIPMENT: (Main Pump, Jockey Pump, DG Set cum
Pump, Control Panel for Fire Fighting System, switcyard equipment and
buildings. HVW system & hydrant sytsem, complete with all piping, valves,
28 LOT 1
fittings etc inside pump house for Fire protection sytem of substation) as
per the technical spec.
400/220 KV 500 MVA ICT (inclusive of all costs towards type test charges,
Mandatory spares, Spanners & Special tools, Oil storage tank, Nitrogen
Injection system for protection against Fire & Explosion, On line insulating
32 NOS 2
oil drying system , On line Dissolved Gas (Multi-gas) and Moisture
Analyser, accessories, etc as specified in the Technical specification)
Name of
Bidder:_______________________________
Signature of
Bidder:_____________________________
1
Prices of Items quoted in Schedule No.1 shall not be quoted again in Schedule No. 2 and shall have a remark against the said row "Quoted
in Schedule No.-1".
ODISHA POWER TRANSMISSION CORPORATION LIMITED
NAME OF THE WORK:-Design, Supply and Installation of 2X500 MVA ICT for Out Door Type,400/220 KV GIS Grid Sub-station at
(Ramkrushnapur),Bhadrak.in Odisha State of India under PACKAGE-3 Under Japan International Cooperation Agency (JICA)’s ODA
Loan.
Loan Agreement No: [ID-P245] - FB No: [CPC/JICA/ICB/03/18-19]- Reference Identification No: [OPTCL/JICA/PKG-3]
Schedule No. 4. Installation and Other Services (Sub-station )
NAME OF THE BIDDER
Nos.(FDR-2,TFR-2,B/C-1)
ERECTION,TESTING & COMMISSIONING OF FOLLOWING Foreign Local Foreign
SL. NO. UNIT Local Currency
EQUIPMENT/MATERIALS ALONG WITH CIVIL WORKS (As per Currency Currency Currency
Technical Specification) Portion
Portion Portion Portion
1 2 3 (1x2) (1x3)
PART A CIVIL WORKS
1 CONTOUR SURVEY,AND LEVELING, BACK FILLING
Contour survey and furnishing contour map including supply of all
1.1 materials, Labour and T&P SQ.MTRS. 55000
Flooring with double charged vitrified tiles with dado in all the rooms,Bath
and toilets shall be provided with anti skid ceramic tiles(wall of the same
7.3 also to be provided with ceramic tiles),Acid proof industrial tiles to be Lot 1
provided on the floor and wall of the battery room as per technical spec &
approved drawings.
External and internal wall painting with primer coat as per technical spec
mentioned in the civil section. External: One coat weather coat primer +
two coats of weather coat colour paint.
7.4 Internal: Two coats wall putty+solvent thinable white primer of one Lot 1
coat+two coats colour paint.
Battery Room:The left over portion of walls and ceiling of Battery room shall
be acid proof paints as per specification & approved drawings.
External and internal wall (External (18mm thk ) and internal (12 mm thk) wall and
ceiling plastering as per technical spec mentioned in the civil section) and Building
7.5 internal & external & ceiling paintings as per technical spec mentioned in the civil Lot
section. The ceiling of Battery room shall be acid proof paints as per specification
& approved drawings.
Provision of ceiling in the control room area as per specification mentioned
7.6 Lot 1
in the civil section & approved drawings.
Doors and windows shall be of sliding type with locking facility and shall be of
aluminium with glaze of 6mm & windows shall have aluminium grills. Windows
7.7 shall be provided with vertical window blinder to protect from the sun ray. As per Lot 1
technical spec & approved drawing.
Provision of PHD and other fittings of reputed make for the control room building
(in Toilets,wash room,overhead water tank of adequate capacity etc) of reputed
make,provision of rain water discharge pipes at different locations and etc as per
requirement and approved drawing. There shall be septic tank and soak pit of
required capacity including complete sewage system as per approved drawing &
technical specification & as per instruction of Engg- in-Charge. It includes supply
of all types of materials of reputed make, labour etc to complete the work. Toilets
7.8 Lot 1
for Gents & Ladies to be provided including all good quality reputed fittings as per
technoical specification. The toilets & wash room shall have antiskid floor tiles &
wall tiles of seramic upto height of 8 feet.Provision of rain water discharge pipes at
different locations and two nos of over head water tank of 2000 ltrs capacity etc as
per requirement and approved drawing. All bath room & toilet shall have water &
termite proof doors and provision of sliding louvers with exhaust fan.
Internal concealed wiring (including supply of flexible copper FRP 1.1 KV PVC
wire,conduits & its accessories,modular type switches & switch board,Junction
boxes with required MCB & Earth leakage detector switcghear etc),fixing of
7.9 lighting fixtures & switchgear ,ceiling fans of 1400 sweep and regulators( including Lot 1
supply) ,exhaust fan (including supply), Erection of all Lighting FIXTURES &
LAMPS (LED), D.C emergency lighting (including supply), as per approved
drawing and direction of Engineer In charge.
Supply, fitting and fixing of stainless steel pf 304 grade in hand railing using 50mm
dia of 2mm thick circular pipe with balustrade of size 32mmx32mmx32mm
@0.90mtr C/C and stainless square pipe bracing of size 32mmx32mmx32mm in
7.10 Lot 1
three rows in staircase as per approved design and specification, buffing,polishing
etc with cost, conveyance, taxes of all materials, labour, T&P etc required for the
complete in all respect
7.11 Installation of smoke and heat detection system of the building. Lot 1
Roads: Design, construction of roads and walkways/ shoulders within sub-
station(Switch yard area,colony area,approach road,control room building
area, main gate to the switch yard gate etc) as per specification, layout and
8 approved drawings complete. This also includes excavation in all types of
soil or rocks,back filling,and disposal of excess earth as per the direction of
Engineer In charge. Provision of drains on both the side of the roads for
easy discharge of rain water.
3.75 mtrs concrete road with shoulder at both the side & shall have drain
on both side of the road as per technical specification indicated in the civil
8.1 Mtrs 600
section( Periphery roads outside switch yard fencing and colony roads)
7 mtrs concrete road with shoulder at both the side as per technical
specification indicated in the civil section(from the switch yard main gate to
8.2 Mtrs 1100
power transformer,approach road & infront of GIS cum control room
building & Shall have drain on both side of the road.
Drainage system:Collection of rainfall data, Design, construction of storm
water drainage scheme (RCC type), road-culverts,Shall have drain on both
side of the road and drains crossing cable trenches etc. as per
specification and approved drawing. This also includes excavation in all
9
types of soil or rocks,back filling,and disposal of excess earth as per the
direction of Engineer In charge. All the switch yard bays , roads water
drainage shall be connected to the main surface drain. As per approved
drawing and specification.
9.1 Storm water drain Mtrs. 700
9.2 Road-culverts, drain crossings Lots 1
9.3 Cable trench crossing Lots 1
Foundations for transformers :Design, engineering, supply of labour,
material, equipments and construction of Auto-transformer/Transformer
foundation including piling if any, all associated works, rail tracks, jacking
pads,anchor block RCC and PCC, miscellaneous structural steel including
oil collection pits, MS grating(if required), gravel filling, and other items etc.
not mentioned herein, but specifically required for the completion of the
work as per technical specification and approved drawing. (Rate shall be
10 inclusive of cement, reinforcement steel, angles,flats and form work
etc.)(all cement concrete shall have RCC ratio 1:1.5:3). Transformer RCC
foundation and Rail Track should be extended upto the approaching road
(However,the height of RCC foundation beyond transformer main plinth
area should be same as height of concrete road as per item under 4.2).
This also includes excavation in all types of soil or rocks,back filling,and
disposal of excess earth as per the direction of Engineer In charge.
19.8 Provision of Water Tank for fire fighting below ground. Lot 1
SECURITY SHED & CUM VISITOR ROOM: Design, engineering,
procurement of labour, material including all associated works for
construction of Security shed near main gate,watch tower shed at the
corners of switch yard as per the approved drawing and instruction of
Engineer in charge. This also includes excavation in all types of soil or
rocks,back filling,and disposal of excess earth as per the direction of
23 Engineer In charge. Internal electrification including supply of lighting
fixtures,fan with regulators and provision of incoming AC supply from the
main ACDB/outdoor kiosks installed for street light or colony quarters. Also
includes painting of the building (in side and out side) as per
recommended for colony building in the specification. (* REMARKS : FOR
SUPPLY OF ALL THE CABLES AS INDICATED ARE COVERED IN THE
supply)}
SECURITY SHED:The size of the security shed shall be 3.5 mtrsX5mtrs
and height of 3.5mtrs RCC roof,Fly ash Brick masonary works,plastering
and painting and fixing of MS doors and windows. Internal concealed
wiring (including supply of flexible copper FRP 1.1 KV PVC wire,conduits &
its accessories,modular type switches & switch board,Junction boxes with
required MCB & Earth leakage detector switcghear etc),fixing of lighting
fixtures & switchgear ,ceiling fans of 1400 sweep and regulators( including
23.1 supply) and provision of incoming AC supply from the main ACDB/outdoor Nos 1
kiosks installed for street light or colony quarters. Also includes painting of
the building (in side and out side) as per recommended for colony building
in the specification. (* REMARKS : FOR SUPPLY OF ALL THE CABLES
AS INDICATED ARE COVERED IN THE supply)}
BORE WELL & PUMP HOUSE:Design, engineering, procurement of
labour, material including all associated works for construction of two nos.
bore wells for control room building including switch yard and colony
quarters as per specification and approved drawing and instruction of
Engineer in charge. This includes supply and fixing and commissioning of
two nos 5 HP submersible water pump with starter and other protection.
Construction of two nos pump house at ideal location for fixing of the
electrical starter units. The pump house be of RCC roof and having walls of
Fly ash Brick masonry and plastering and painting of external & internal
walls with MS door having locking arrangement & window. Internal
24 concealed wiring (including supply of flexible copper FRP 1.1 KV PVC LOT 1
wire,conduits & its accessories,modular type switches & switch board. The
size of the room shall be 2.5mtrsX2.5 mtrs having height of 3 mtrs. as per
approved drawing and specification. There shall be approach road to the
pump house. This includes supply of materials,labours and T&P &
excavation of all type of soils including rock and disposal of excess
materials as per instruction of Engineer In charge Supply & laying of LV
XLPE 3.5CX 35 sq mm cable from ACDB to pump house, control gear &
earthing of the system etc to complete the scheme as per approved
drawing & instruction of Engineer-in charge.
COLOUR CODING, BAY MARKING Etc:Design, engineering, procurement
of labour, material including all associated works for the followings. This
should be as per direction of site In charge. a)Color coding (red,Yellow &
Blue) for equipments,Bus gantry &column of entire switch yard. Good
25 quality weather proof sticker may be used for identification. b)Each bay Lot 1
should be identified with the help of bay marker sign board, suitably
grouted. MS sign board with stand to be installed. Proper painting and
lettering to be done of the entire switch yard area.
STORE SHED:Design, engineering, procurement of labour, material
including all associated works for construction of store shed as per
specification and approved drawing. This also includes excavation in all
types of soil or rocks,back filling,and disposal of excess earth as per the
specification,approved drawing and direction of Engineer In charge. One
no store shed of floor size 10X10 mtr having Fly ash Brick walls and
plastering with RCC roof. The flooring shall be of 75 mm thickness PCC
(mix ratio1:2:4) over RR masonry works (as per standard practice of
flooring). Provision of adequate nos of MS racks (proper paintings also to
be done as per the direction of site in charge) for keeping the spare
26 materials. The height of the shed shall be 4mtrs above the plinth. Internal Lot 1
concealed wiring (including supply of flexible copper FRP 1.1 KV PVC
wire,conduits & its accessories,modular type switches & switch
board,Junction boxes with required MCB & Earth leakage detector
switcghear etc),fixing of lighting fixtures & switchgear ,ceiling fans of 1400
sweep and regulators( including supply) and provision of incoming AC
supply from the main ACDB/outdoor kiosks installed for street light or
colony quarters. Also includes painting of the building (in side and out side)
as per recommended for colony building in the specification. (* REMARKS :
FOR SUPPLY OF ALL THE CABLES AS INDICATED ARE COVERED IN
THE supply)}
PLATFORM FOR STORING EQUIMENTS:Design, engineering,
procurement of labour, material including all associated works for
construction of a platform for storing of bushings,Instrument transformers
etc, as per specification and approved drawing.This also includes
excavation in all types of soil or rocks,backfilling,and disposal of excess
earth as per the specification,approved drawing and direction of Engineer NOS 1
27
In charge. One no platform outside the store shed RR masonry
(compacted) with PCC at the top for storing the transformer bushings,
Instrument transformers, transformer oil drums etc. The floor size of the
platform shall be 15mtrX10 mtr with Galvanised Corrugated Sheet (Tata
Make) top cover and associated MS supporting structure duly painted.
28 Anti-Weed Treatment
28.1 Supply of labour,T&P,Chemicals and other necessary arrangements for
anti-weed treat of the switch-yard areas,controlroom etc. as per the
instruction of Engineer-in-Charge.The chemical to be sprayed as per the Sq Mtrs 24000
standard practice adopted for antiweed treatment of sub-station area & as
per the technical specification.
VEHICLE PARKING SHED: The size of the parking area shall be 15mtrs X
15 mtrs, out of the entire area there shall be provision of shed for 5 mtrs X
15 mtrs and rest of the area shall be without shed. 100 mm thick
29 Lot 1
PCC(1:2:4) flooring after the preparing the foundation base & Roof of the
parking place shall be RCC & Parking shed shall be as per TS-E6-Civil &
as per the direction of Engineer in Charge.
Construction of township/colony (residential quarters) for staff and
employees of the employer. Layout, design, survey, levelling, site dressing
and clearing of the area, soil investigation, excavation, PCC, RCC, Fly ash
Brick work, plastering ,flooring(flooring shall be with vitrified tiles of reputed
make with a dado of minimum6 inches),fixing of doors windows and
window grills, including all labour, T&P, material like cement ,sand
aggregate, Fly ash Bricks, reinforcements etc with all bought items required
for completion of the quarters as per approved construction drawings with
all facilities for supply of drinking water. The outer paint shall be applied
with weather coat synthetic enamel paint as per the standard practice of
application and the inner paint shall be applied with distemper of approved
quality as per the instruction and approval of the same by OPTCL. This
also includes excavation in all types of soil or rocks,back filling,and
30 disposal of excess earth as per the direction of Engineer In charge. Internal
electrical wiring with fixing of light fixtures and fans with electronic
regulators and exhaust fans as per technical specification and approved
drawing. Construction of over head RCC tank(1000 ltrs capacity one for
each quarters), sewerage disposal and connection with main sewerage/
septic tank and soak pit, storm water and surface drainage, culverts, roads,
with suitable radius on the curves and its connection with main road the
substation, street lighting, internal lighting, internal plumbing and sanitation
including internal/external finishing of quarters etc. required for completion
of the town ship. (RCC column structure frame and the Fly ash Bricks to be
used shall be fly ash Fly ash Brick, all the door and window frame & panels
shall be aluminium with adequate size as indicated in the TS and also as
per the National Building Code adopted.
30.1 "D" type Quarter As per technical specification: 1 no quarter on
ground floor & 1 no quarter on First floor ,the size of each quarter
plinth area shall be 120 Sq Mtrs(appox)
30.1.1 "D" type Quarter As per technical specification: 1 no quarter on
ground floor & the size of quarter plinth area shall be 120 Sq SQ.MTRS 120
Mtrs(appox)
30.1.2 "D" type Quarter As per technical specification: 1 no quarter on First
floor & the size of quarter plinth area shall be 120 Sq Mtrs(appox) SQ.MTRS 120
"E" type Quarter As per technical specification (one no. two storied
flat. Each flat shall be with 2 nos quarters on ground floor & 2 Nos
30.2
quarters on 1st floor).(There shall be 4 Nos quarters to be
accommodated in one flat as E1,E2,E3 & E4)
"E" type Quarter As per technical specification: 2 nos quarters on
30.2.1 ground floor (Each quarter size plinth area shall be 73 Sq Mtrs(appox) SQ.MTRS 146
420kV,3150A, 63KA for 3 sec (Busbar, CB, Disconnector, Grounding switch, CT & PT),
SF6 gas insulated Complete Diameter module (2 Nos Feeder) each comprising of SF6 gas
insulated Single Pole Circuit Breaker (3 Sets) with CSD (Control Switching Device), Single
Phase Current Transformer (18 Nos), Single Phase Potential Transformer (4 Winding) (6
Nos), Motorised 3 Phase Disconnector (6 Sets), Motorised safety Grounding switch (8
Nos), Motorised 3 Phase Disconnector with high speed fault making Motorised Grounding
switch (2 Nos), Local Control Cubicle, SF6 gas monitoring system for complete diameter,
SF6 bus duct termination arrangement, online PD sensor (adequate number of UHF
1.1 Set 3
sensors in the offered GIS equipment for detection of Partial discharge (of 5 pC and
above) as per IEC 60270 through Partial Discharge (PD) monitoring system), different gas
compartment, O-ring & gaskets, Nuts, Bolts & Washers for Outdoor use, Absorbent,Limit
Switch, SF6 Gas, etc. to complete diameter module & its earthing arrangement with
earthing strips of adequate size (as per IEEE Std 80-2013 to protect operating staff against
any hazardous touch voltages and electro-magnetic interferences) as per the technical
specification.
420kV,3150A, 63KA for 3 sec (Busbar, Disconnector, Grounding Switch & Bus PT), 3
Phase Isolated, SF6 gas insulated, metal enclosed busbars Complete Diameter module (2
Nos BUS-PT) in bus enclosures running along the length of the switchgear to interconnect
each of circuit breaker diameter module. Each busbar set shall be complete with Potential
Transformer (4 Winding), Motorised 3 Phase Disconnector (1 No), Motorised Busbar
safety Grounding switch (1 No), Local Control Cubicle, SF6 gas monitoring system online
PD sensor (adequate number of UHF sensors in the offered GIS equipment for detection
1.2 Set 1
of Partial discharge (of 5 pC and above) as per IEC 60270 through Partial Discharge (PD)
monitoring system), different gas compartment, O-ring & gaskets, Nuts, Bolts & Washers
for Outdoor use, Absorbent, Limit Switch, SF6 Gas, etc. to complete diameter module & its
earthing arrangement with earthing strips of adequate size (as per IEEE Std 80-2013 to
protect operating staff against any hazardous touch voltages and electro-magnetic
interferences) as per the technical specification.
420kV, 3150A, 63kA, 3 Sec, Single phase, SF6 gas Insulated Bus Duct outside GIS Bay
along with associated Support structure arrangement bends, joints, accessories, & its
1.3 earthing arrangement with earthing strips of adequate size (as per IEEE Std 80-2013 to RM 900
protect operating staff against any hazardous touch voltages and electro-magnetic
interferences) etc. as per the technical specification.
420kV, 3150A, 63kA, SF6/Air BUSHING (Bushing shall be of Polymer / composite insulator
type and shall be seamless sheath of a silicone rubber compound. The hollow silicone
1.4 composite insulators shall comply as per IEC 61462 and IEC 62217. The design of the No 18
composite insulators shall be tested and verified according to IEC 61462) FOR
CONNECTING GIS TO AIS along with support structure.
Online continuous Partial Discharge Monitoring System (PDM):
420kV GIS equipment system shall have Online continuous Partial Discharge Monitoring
System (PDM) system to provide an automatic facility for the simultaneous collection of
PD data at multiple points on the GIS & its associated GIB ducts and Voltage Transformers
adopting UHF technique & the data stored shall provide a historical record of the progress
of PD sources and shall identify the areas of maximum activity. PDM system shall be
1.5 Set 1
interfacing with UHF PD couplers provided. The PD Monitoring PC Work Station along with
all accessories shall be considered. Power supply to PDM PC shall have protection against
surges, overload and short circuit. A dedicated on-line UPS system shall also be provided
as a backup during supply interruption, to ensure trouble-free & reliable running of the
PDM System for a minimum of 15 minutes duration.
3150A, 50kA for 3s, Double Busbar Circuit Breaker (Circuit breaker shall be E2-C2-
M2 class as per IEC 62271-100) arrangement.
2 245kV OUTDOOR GIS EQUIPMENT as per latest IEC standard & type tested
equipment as per technical specification, with open future proof & flexible system in
line with IEC 61850 & IEC 62271-203.
245kV, 3150A, 50kA for 3 sec (Busbar, CB, Disconnector, Grounding Switch & CT), SF6
gas insulated ICT Feeder Bay Module each comprising of SF6 gas insulated Single Pole
Circuit Breaker (1 Set), Single Phase Current Transformer (6 Nos), Motorised Busbar 3
Phase Disconnector (2 Nos), Motorised Disconnector (1 No), Motorised safety Grounding
switch (3 Nos), Local Control Cubicle, SF6 gas monitoring system for complete bay, SF6
bus duct termination arrangement (3 Nos), PD sensor (adequate number of UHF sensors
in the offered GIS equipment for detection of Partial discharge (of 5 pC and above) as per
2.1 Set 3
IEC 60270 through Partial Discharge (PD) monitoring system), different gas compartment,
O-ring & gaskets, Nuts, Bolts & Washers for Outdoor use, Absorbent, Limit Switch, SF6
Gas, etc. to complete ICT Feeder Bay Module & its earthing arrangement with earthing
strips of adequate size (as per IEEE Std 80-2013 to protect operating staff against any
hazardous touch voltages and electro-magnetic interferences) as per the technical
specification.
245kV, 3150A, 50kA for 3 sec (Busbar, CB, Disconnector, Grounding switch, CT & PT),
SF6 gas insulated Line Feeder Bay Module each comprising of SF6 gas insulated Single
Pole Circuit Breaker (1 Set), Single Phase Current Transformer (6 Nos), Single phase Line
Potential Transformer (4 winding) (3 Nos), Motorised 3 Phase Busbar Disconnector (2
Nos), Motorised safety Grounding switch (2 Nos), Motorised 3 Phase Disconnector with
high speed fault making Motorised Grounding switch (1 No), Local Control Cubicle, SF6
gas monitoring system for complete bay, SF6 bus duct termination arrangement (3 Nos),
2.2 PD sensor (adequate number of UHF sensors in the offered GIS equipment for detection Set 4
of Partial discharge (of 5 pC and above) as per IEC 60270 through Partial Discharge (PD)
monitoring system), different gas compartment, O-ring & gaskets, Nuts, Bolts & Washers
for Outdoor use, Absorbent, Limit Switch, SF6 Gas, etc. to complete Line Feeder Bay
Module & its earthing arrangement with earthing strips of adequate size (as per IEEE Std
80-2013 to protect operating staff against any hazardous touch voltages and electro-
magnetic interferences) as per the technical specification.
245kV, 3150A, 50kA for 3 sec (Busbars, Disconnector, Grounding switch & bus PT), 1
Phase Isolated Bus-PT Bay Module comprisig of SF6 gas insulated metal enclosed
busbars each enclosed in bus enclosures running along the length of the switchgear to
interconnect each of circuit breaker bay module. Each busbar set shall be complete with
Single phase bus Potential Transformer (4 winding) (3 Nos), Motorised 3 Phase
Disconnector (1 No) , Motorised Busbar safety Grounding switch (1 No), Local Control
Cubicle, SF6 gas monitoring system PD sensor (adequate number of UHF sensors in the
2.3 Set 1
offered GIS equipment for detection of Partial discharge (of 5 pC and above) as per IEC
60270 through Partial Discharge (PD) monitoring system), different gas compartment, O-
ring & gaskets, Nuts, Bolts & Washers for Outdoor use, Absorbent, Limit Switch, SF6 Gas,
etc. to complete the bus & its earthing arrangement with earthing strips of adequate size
(as per IEEE Std 80-2013 to protect operating staff against any hazardous touch voltages
and electro-magnetic interferences) as per the technical specification.
245kV, 3150A, 50kA for 3 sec (CB, Disconnector, Grounding switch & CT), SF6 gas
insulated Bus Coupler Bay Module comprising of SF6 gas insulated Single Pole Circuit
Breaker (1 Set), Single Phase Current Transformer (6 Nos), Motorised 3 Phase
Disconnector (2 Nos), Motorised safety Grounding switch (2 Nos), Local Control Cubicle,
SF6 gas monitoring system, PD sensor (adequate number of UHF sensors in the offered
GIS equipment for detection of Partial discharge (of 5 pC and above) as per IEC 60270
2.4 Set 1
through Partial Discharge (PD) monitoring system), different gas compartment, O-ring &
gaskets, Nuts, Bolts & Washers for Outdoor use, Absorbent, Limit Switch, SF6 Gas, etc. to
complete Bus Coupler Bay Module & its earthing arrangement with earthing strips of
adequate size (as per IEEE Std 80-2013 to protect operating staff against any hazardous
touch voltages and electro-magnetic interferences) as per the technical specification.
245kV, 3150A, 50 kA, 3 sec, single phase, SF6 gas Insulated Bus Duct outside GIS Bay
along with associated Support structure arrangement bends, joints,accessories, & its
2.5 earthing arrangement with earthing strips of adequate size (as per IEEE Std 80-2013 to RM 1000
protect operating staff against any hazardous touch voltages and electro-magnetic
interferences) as per the technical specification.
245kV,3150A, 50kA SF6/Air BUSHING (Bushing shall be of Polymer / composite insulator
type and shall be seamless sheath of a silicone rubber compound. The hollow silicone
2.6 composite insulators shall comply as per IEC 61462 and IEC 62217. The design of the No 21
composite insulators shall be tested and verified according to IEC 61462) FOR
CONNECTING GIS TO AIS along with support structure.
Portable Partial Discharge Monitoring System (PDM):
245kV system shall have Portable Partial Discharge Monitoring System (PDM) & shall be
capable for measuring PD in charged GIS environment, bandwidth in order of
100MHz–2GHz & provision to select a wide range of intermediate bandwidths and the
2.7 principle of operation shall be based on UHF principle of detection. The Detection and Set 1
measurement of PD and bouncing particles having in built large coloured LCD for
displaying and storing facility in the instrument for further analysis to locate actual source of
PD such as free conducting particles, floating components, voids in spacers, particle on
spacer surfaces etc.
3.1 420 KV, 3150 A, 63 KA, Center break ISOLATORS WITH EARTH SWITCH Nos 4
3.2 420KV 1 phase Solid core bus post insulator (AIS) as per technical specification. NOS 6
3.3 245 KV, 2000A, 40KA, Center break ISOLATORS WITH EARTH SWITCH NOS 4
3.4 245KV 1 phase Solid core bus post insulator (AIS) as per technical specification. NOS 6
400KV metal oxide surge arrrestor, 20 KA , Long duration discharge class IV , 12KJ/KV at
3.5 NOS 18
336KV as per technical specification.
216KV metal oxide surge arrrestor, 10KA Long duration discharge class III , 10 KJ/KV at
3.6 NOS 21
216KV as per technical specification.
30 KV, METAL OXIDE SURGE ARRESTOR, 10kA, Long duration discharge class III (AIS)
3.7 NOS 9
as per technical specification.
36 KV ,1250A, 31.5 KA for 1 sec, isolator (single isolator with earth switch) including post
3.8 SET 2
insulators as per technical specification
4 36KV GIS equipment
36KV, 1250A, 31.5kA for 3 sec, SF6 gas insulated transformer bay module each comprising of
SF6 gas insulated Vacuum circuit breaker , current transformer , bus-bar disconnectors with common
4.1 grounding switch , SF6 gas monitoring system for complete bay (having 33 KV Bus Bar of 2000 SET 3
Amp) to complete transformer bay module suitable for cable connection to transformer.
36KV, 1250A , 31.5kA for 3 sec, (33 KV Bus Bar 2000 Amp) SF6 gas insulated bus-coupler bay
module comprising of SF6 gas insulated vacuum circuit breaker , current transformer , disconnector
switches & bus bars each enclosed in bus enclosures running along the length of the switch gear to
4.2 Nos 1
inter-connect each of circuit breaker bay module. Each busbar set shall be complete with potential
transformer , disconnectors, SF6 gas monitoring system for the complete bus etc.
Laying and termination of EHV/HV XLPE Power copper conductor cable for the
GIS system as per IS7098 & IEC60840 including installation of indoor & outdoor
4.3
cable termination kit and associated cable accessories & clamps as per technical
specification and direction of Engineer-in -charge.
36 KV XLPE 630 SQ. MM single core copper Cable as per tech spec (for
4.3.1 connectivity from 33 KV side of 220/33 KV Transformer to 33 KV GIS panel) Mtr 600
including installation of indoor & outdoor cable termination kit
33KV CABLE 300 SQ. MM single core copper as per tech spec (for 33 KV
connectivity from GIS equipment to Station Transformer (two nos station trafo) &
4.3.2 Mtr 1500
outgoing feeders upto DP structure end) including installation of indoor & outdoor
cable termination kit .
4.4 HV Test Charges for 33 KV GIS LOT 1
4.5 36 KV Bus Post Insulator as per technical specification NOS 9
5 BUS BAR & CIRCUIT MATERIALS
All types of HARDWARES & FITTINGS/SPACERS/CLAMPS &
5.1 CONNECTORS FOR 400KV SIDE OF THE GIS S/S. Lot 1
G.I Cable Trays including support GI angle suitable for different sections
along with its accessories as per TS. Details of No. of tiers are indicated in
7 the TS-Civil Section accordingly the requirement can be ascertained.
40 Mtrs heigh Monopole Lighting cum Lightning Mast including LED lighting
11.2.2 MT 21
fixtures with control gear panel etc suitable for wind zone-V.
Total weight of different type of GI Nuts and bolts for the above structures
11.3 MT 11.6
Laying of Power and Control Cable including fixing of cable with terminal
connections both at equipments and control panels with supply of and
fixing of lugs, Ferrules, clamps, connectors, glands, fixing of cable trays,
including supply of N&B, Link plates, Cable Markers, Plaster of Paris, M-
12
Seal compounds etc for sealing purpose and all necessary arrangements,
laying of Earthing Flats, earthing ,laying of Cable trench slabs and
chequered plate etc for the cable trench,Cable scheduled and cable
diagram to be prepared by the contractor
POWER CABLES,1.1KV,XLPE & PVC FRLS ,FLAT STRIP ARMOURED,
12.1 ALUMINIUM CONDUCTOR (As per Specification)
14.5 SMPS based Battery Charger of 75A suitable for 48V VRLA Battery set No 1
2.5 sq. mm muti strand 2 core control cable(power supply,Transducer/MFT
14.6 Metre 600
PT supply)
14.7 2.5 sq. mm multi strand 4 core control cable(Transducer/MFT CT supply) Metre 600
14.8 1.5 sq. mm multi strand 10 core control cable(Digital Input) Metre 500
14.9 10 sq. mm 2 core multi strand control cable(Battery) Metre 300
14.10 48V DCDB No 1
14.11 Earth Flat, Cable Tray, Telephone cable, Foundation rail, Junction Box,. Lot 1
SUPPLY OF STATION TRANSFORMER & OTHER MATERIALS FOR
15 MEETING THE AUXILIARY SUPPLY OF THE SUB-STATION AS PER
TECHNICAL SPECIFICATION
STATION TRANSFORMER 33KV/0.43 V,500 KVA (Confirming to Energy
15.1 NOS 2
Efficiency Level 2 -AS PER SPECIFICATION & relevant IS)
One no. 4 pole structure (HDG Type) alongwith other equipment & materials
for two nos station transformers:
1.4 Pole structure (using 200X100 mm RS Joist)
2. Channel & Angle FOR BRACING OF, CHANNEL for the SA & Isolator & HG
fuse etc.
3. 90 KN Disc/composite long rod Insulators for 33 KV (48 nos./12 sets) for bus,
Bus stringing using ACSR moose conductor & tension hardwares,other clamps &
connectors etc as per requirement.
4. 2sets of 33 KV Isolator (800 AMP) for 33 KV side of station trafo.
5. 2sets of 33 KV HG FUSE.
15.2 6. 125 Sq mm AAAC conductor suitable for connection between HG fuse & station SET 2
transformer bushing.
7. 2 sets of LT OUT DOOR KIOSK MADE OUT OF 3mm CRCA sheet Gl
MARSHALLING BOX suitable for outdoor mounting. The bus bar suitable for 1000
AMP shall be arranged in the out door kiosk and other Facility like two sets of 400
Amps MCCB for incoming & outgoing with required sizes of terminal studs for
power cable termination & any other accessories required.
AII materials shall be As per relevant latest IS & as per the direction of Engg. in
charge
Yard AC Kiosk :5000 mm (L)x4000mm (W)x 3300mm (H) with AC, as per the
20.1 Nos. 4
Specification;
Gate way panel for Sub-Station Automation (in PRP as per the specification & indicative
drg ) system (for All 400 , 220 & 33 KV side bays including the future bays),other
accessories (comprising servers, engg. Station, works station (Main & standby), Remote
station control, Colour Laser jet Printers & dot matrix printer for local station as per
requirement and also for remote station, Ethernet Switches , LIU, Red Box, Multimode
20.2 glass fibre Doublle jacket armoured optical cables, special cables like F.O patch cord & SET 1
armoured FO cables of adequate length etc required for the system in all respect as per
latest IEC 61850 standard, Inverters of required capacity & rating (3KVA-Input shall be
both A.C & D.C and output shall be A.C) etc as per TS. A Full HD LED screen of 70
inches for display including all type of accessories & as per technical specification.
BCU for Substation Auxilliary System (Datas for monitoring of Station AC, Station DC,
20.3 Lighting, Fire fighting, Air conditioning, Diesel generator etc. as per the site requirement) SET 1
BUS COUPLER PROTECTION PANEL with Bay control unit (BCU) for substation
20.6.3 automation system. NOS 1
BUS-BAR PROTECTION PANEL ( Provision of bus bar modules for the future bays and
20.6.4 NOS 1
to be integrated with the Automation system)
20.7 33 KV SIDE PROTECTION PANELS
33 KV BUS COUPLER PROTECTION Panel with Bay control protection unit (BCPU) with
20.7.1 with all other relays & component required for complete prtection,control etc as per TS No 1
and also suitable for substation automation system.
STATION TRANSFORMER PROTECTION PANEL (BACK-UP
PROTECTION CONSIDERING 2X500 KVA 33/0.43 KV ) with Bay control
20.7.2 protection units (BCPU) with with all other relays & component required for SET 1
complete prtection,control etc as per TS and also suitable for substation automation
system. [2nos. Feeeder bays in one panel]
21 AC & DC SYSTEM
21.1 AC SYSTEM
MAIN AC DB,(HAVING A 1600 A,50KA,DRAWOUT TYPE ACB WITH 3
O/C,E/F,U/V RELAYING FACILITY and MECH& ELECT INTERLOCK
21.1.1 FACILITY CONSIDERING Main-1,2 & DG INDOOR TYPE AS PER SET 1
SPECIFICATION.(MAIN DB-1,MAIN DB-2 WITH B/C & PROVISION FOR
D.G INCOMING)
ACDB (HAVING 800A MCCB) AS PER SPECIFICATION (AC DB-1,AC DB-
21.1.2 2 WITH B/C) SET 1
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid, or ITB 34.1 in Two-Stage Bid.
ODISHA POWER TRANSMISSION CORPORATION LIMITED
NAME OF THE WORK:-Design, Supply and Installation of 2X500 MVA ICT for Out Door Type,400/220 KV GIS Grid Sub-station at
(Ramkrushnapur),Bhadrak.in Odisha State of India under PACKAGE-3 Under Japan International Cooperation Agency (JICA)’s ODA Loan.
Loan Agreement No: [ID-P245] - FB No: [CPC/JICA/ICB/03 /18-19]- Reference Identification No: [OPTCL/JICA/PKG-3]
Schedule No. 6. Grand Summary
NAME OF THE BIDDER
Total Price1
Item Description
Foreign Local
1 Total Schedule No. 1. Plant,
Supplied from Abroad (Substation)
2 Total Schedule No. 2. Plant, Supplied from Within the Employer’s
Country (substation)
3 Total Schedule No. 3. Design Services (Not Applicable)
4
Total Schedule No. 4. Installation and Other Services (substation)
5 Total Schedule No. 5. Provisional Sums (Not to be considered for
Evaluation)
Name of Bidder:__________________________
Signature of Bidder:__________________________
1
Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bidding, or ITB 34.1 in Two-Stage Bidding. Create and use as many columns for Foreign
ODISHA POWER TRANSMISSION CORPORATION LIMITED
NAME OF THE WORK:-Design, Supply and Installation of 2X500 MVA ICT for Out Door Type,400/220 KV GIS Grid Sub-station at (Ramkrushnapur),Bhadrak.in
Odisha State of India under PACKAGE-3 Under Japan International Cooperation Agency (JICA)’s ODA Loan.
Loan Agreement No: [ID-P245] - FB No: [CPC/JICA/ICB/03 /18-19]- Reference Identification No: [OPTCL/JICA/PKG-3]
Schedule No. 7. Recommended Spare Parts
NAME OF THE BIDDER
Unit Price
DESCRIPTION OF ITEMS
Sl. No. SUPPLY OF SPARES FOR THE FOLLOWING EQUIPMENTS. Unit Quantity CIP Ex-Works Price Total Price in INR
(As per Technical Specification) (foreign parts) Local Parts
TOTAL
Name of Bidder:________________________________
Signature of Bidder:_____________________________
Note: Recommended Spares shall not be taken in to consideration for evaluation purpose.
ODISHA POWER TRANSMISSION CORPORATION LIMITED
NAME OF THE WORK:-Design, Supply and Installation of 2X500 MVA ICT for Out Door Type,400/220 KV GIS Grid Sub-station at
(Ramkrushnapur),Bhadrak.in Odisha State of India under PACKAGE-3 Under Japan International Cooperation Agency (JICA)’s
ODA Loan.
Loan Agreement No: [ID-P245] - FB No: [CPC/JICA/ICB/03 /18-19]- Reference Identification No: [OPTCL/JICA/PKG-3]
Schedule No. 8. Details of Taxes & Duties
NAME OF THE BIDDER
Total Amount of Taxes /Duty/
Sl No Description of Applicable Tax/Levy Tax @ __%
Levies
Details of Taxes and levies on the direct / bought out
1 transactions between Bidder and ODISHA POWER
TRANSMISSION CORPORATION LTD included in the Bid
(i) TOTAL IGST
(ii) TOTAL CGST
(III) TOTAL OGST
(iv) TOTAL Any other tax
TOTAL OF TAXES AND DUTIES [Sum (i) to (iv)
Details of Taxes and levies on the direct / bought out
transactions between Bidder and ODISHA POWER
2 TRANSMISSION CORPORATION LTD included in the Bid
Price above but as may be payable by ODISHA POWER
TRANSMISSION CORPORATION LTD (Schedue- 4)
(i) TOTAL IGST
(ii) TOTAL CGST
(III) TOTAL OGST
(iv) TOTAL Any other tax
TOTAL OF TAXES AND DUTIES [Sum (i) to (iv)
4 F. Total Bid Price: (including Taxes & Duties and other Name of Bidder:________________________________
Signature of Bidder:_____________________________