Digital Axle Counter: Presented by Chandru.S Sse/Sig/Sa
Digital Axle Counter: Presented by Chandru.S Sse/Sig/Sa
Digital Axle Counter: Presented by Chandru.S Sse/Sig/Sa
Presented by
CHANDRU.S
SSE/SIG/SA
RDSO SPECCIFICATION
RDSO SPECIFICATION SPN/177/2003
UNIVERSALAXLE COUNTER
DIGITAL AXLE COUNTER
HIGH AVAILABLITY SINGLE SECTION DIGITAL A/C
BLOCK PROVING SYSTEM
MULTISECTION SECTION DIGITAL A/C
ADVANTAGES OF AXLE COUNTER
STATION STATION
A B
BLOCK SECTION
TYPICAL 10 - 20 KM
AS
4 4 4 4
PULSE 1
TX1 MODEM To 2nd unit of
SCC1 MLB1 V . 21 SSDAC
RX1
AXLE
DETECTORS RELAY READ BACK
(21KHz)
AXLE
DETECTORS
(23KHz) DC-DC
CONVERTOR
LEGEND
SCC 1 & 2 : SIGNAL CONDITIONER CARD
MLB 1 & 2 : MICROCONTROLLER LOGIC BLOCK BATTERY
TX1, TX2 : TRANSMITTER COILS
24V
RX1, RX2 : RECEIVER COILS
SSDAC WORKING
GENERATION OF CARRIER SIGNAL FOR Tx COILS
POWER SUPPLY:
Both VR & PR Q type, 24V, 1000 are used along with the system.
PHASE DETECTION(710P)
SSDAC MODEL DACF-710A
a) Amplitude Modulation type Axle detectors are used. The track circuit
relay connection into the system is required for trolley suppression.
b) The SSDAC remains unaffected with all types of insulated push
trolleys.
c) The SSDAC goes into disturbed state (ERROR condition) for non
insulated trolleys.
When train passes amplitude varies by 10% to 15%
Resetting voltage in the system is by means of 48V DC.
TX1 RX1
TX2 RX2
FIXING OF DEFLECTOR PLATES
Deflector plates
on both sides to
be fitted
INSTALLATION OF COUNTING UNIT
Electronic Counting
unit
RESET BOX
Alphanumeric 20 x 2 row LCD Display for
Axle Counts of Local and Remote unit
Section Status
It consists of
24V, 40 AH Battery and 24V, 5A Battery charger or
24V, 5A output from one of the modules of IPS.
2 core, 25 sq. mm Power cable for connection from
battery to SSDAC unit.
PRECOMMISSIONING CHECKLIST
Pre commissioning checklist needs to be filled & signed by railways & firm
should be sent to firm & RDSO. Main points includes
Use of 1000 ohms relays at location
Use of Diodes at location for PR & repeater relays
Condition of rail
Drilling of holes in straight line
Loss in quad cable at 1KHz should be <20db
Insulation of quad cable >10Mohms
Use of Axle counter type Battery charger
Proper Earth as specified in manual
Effect of trolley movement should be recorded at time of commissioning
Training
SSDAC Communication
COMMUNICATION BETWEEN TWO SSDAC UNITS IS IN THE FORM
OF DATA PACKETS
DATA PACKETS CONSISTS OF
COUNT CHANGE INFORMATION
COUNT UPDATE INFORMATION
RESET INFORMATION, IF ANY
ERROR INFORMATION, IF ANY
TRANSMISSION ON CABLE OR VOICE CHANNELS ON OFC OR
RADIO BY MEANS OF V.21 MODEM (FULL DUPLEX)
SSDAC Monitoring
CARD WISE DISPLAY OF ERRORS BY MEANS OF LEDs
FUNCTION WISE LEDs IN EACH CARD
RS 232 PORT FOR ONLINE MONITORING
EVENT LOGGER CARD WITH SOFTWARE FOR LOGGED DATA
ANALYSIS
ONLINE DISPLAY OF SECTION STATUS, COUNTS DISPLAY &
ERROR CODE WITH ERROR DIESCRIPTION ON 20 X 2
ALPHANUMERIC LCD DISPLAY
TOOLKIT PORTABLE DATA ANALYZER
Portable data
Analyzer tool with
data analysis
software
Serial cable
48
Down Loading Data from SSDAC
Equipment
SSDAC
RDSO/SPN/177/2005
(710A/P) is latest & fully compatible with
RDSO/SPN/177/2003
(700AP)
RECOMMENDED TOOLKIT
(1 set of tool kit to be purchased separately for every
10 sets of SSDAC systems)
1 Portable data analyzer for downloading event logger
data for analysis and report generation.
2 Pure sine wave Digital multimeter make Fluke model
187/ Rishabh model 28S / Kusum Meco model 859CF
or Equivalent
3 Train simulator, Model TS 267P CEL make
4 Extender card (Card No. 557)
5 Dummy wheel (as per Drg No. L007750A3, D14)
6 Ring spanner 17-19,24-26
7 Open end spanner 17-19, 24-26
8 Socket spanner with handle
TOOLKIT MULTIMETER & TRAIN
SIMULATOR
DIGITAL MULTIMETER
TRAIN SIMULATOR FOR
PHASE & AMPLITUDE
52
TOOLKIT SPANNERS & DUMMY
WHEEL
Ring spanner 17-19,24-
26
Open end spanner 17-
19, 24-26
Socket spanner with
handle
Screw Driver No. 902
Screw Driver No. 935
Dummy Wheel
53
SINGLE SECTION DIGITAL AXLE COUNTER
MOTHERBOARD CARD
LAYOUT CHANGE FOR RESET INTERLOCKING.
RESET BOX
NEW RESET BOX (RB 259A) INCLUDES
LCD DISPLAY FOR CRC AND SOFTWARE VERSION
SECTION STATUS
COUNTS DISPLAY OF LOCAL AND REMOTE UNIT
ERROR DISPLAY OF LOCAL AND REMOTE UNIT
FLASHING PREPARATORY LED ON ACTUATION OF RESET IN LOCAL
UNIT AND BECOMES STEADY ON ACHIEVEING OF PREPARATORY
RESET STATE.
HARDWARE COMPATIBILITY
NEW RESET BOX IS NOT COMPATIBLE TO OLD RESET BOX
SVPD
ADDITIONAL MODULE FOR RESET BOX HAS BEEN ADDED.s
SOFTWARE VERSION S006
COUNTING OF MOTOR TROLEY WHEEL HAS BEEN ENABLED.
23 KHz
1 2 1 2
LSB LSB
3 4 4 8
10 20
5 6
MSB MSB
40 80
7 8
CLASSIFICATION OF ERROR CODES
The link error is detected when the link between the two SSDAC
units is open or loss of carrier detect or
CD.
This is displayed as error No. 30.
ACTION REQUIRED
The Cyclic Redundancy Error is displayed when data of the packets gets corrupted.
Due to this the CRC of the packet does not matches.
ACTION REQUIRED
IF OFC
3 >= -30 db
980 Hz > 15 mv
Receive
4 >= 30 db
1650 Hz > 15 mv
ACTION REQUIRED
ACTION REQUIRED
ACTION REQUIRED
ACTION REQUIRED
ACTION REQUIRED
ACTION REQUIRED
ACTION REQUIRED
No display
corrupted display.
ACTION REQUIRED
Check modem
Apply reset to display.
Replace reset box.
DOS & DONT
DOS
The inter connection drawings are to be followed for connecting the Transmitter & Receiver coils
Tx1 is 21 KHz, Tx2 is 23 KHz & Rx1 and Rx2 coils are 21 KHz & 23 KHz, respectively.
Ensure that Receiver and Transmitter coil cables have been laid in different pipes.
Ensure that both the TX coils & Rx coils are having proper alignment on Rail.(88mm from top of rail)
Ensure that packing of sleepers with ballast on both sides of Axle detector is proper.(400mm)
Check that metal sheaths of the outdoor cable are connected to earth at both ends
The recommended cables for wiring of the system at site should be used.
The steady Battery voltage 24V should be maintained.
The cable connections should not be connected loosely.
The M.S Circular connectors of SSDAC are checked and maintained firmly.
The SSDAC & Reset box is provided with sealing arrangement. They should be sealed at site.
Resetting should be done only after ensuring that there is no train in the section
DONT
Dont install the Axle detectors near the rail joint (should be more than 6 sleepers
away).
Dont install the Axle detectors where the rail is badly worn out.(<8mmfor 52kg
and13mm 60kg )
Dont cut or join the Transmitter / Receiver cables supplied along with the coil. It
would result in change of frequency of signal.
Dont lay the TX and RX coil cables in the same pipe.
Dont use any other outdoor cable other than the recommended cables.
Avoid installing the Axle detectors on curve of rail / too much slope of rail to the
possible extent.
Dont remove the cards from SSDAC units under power ON condition of system.
Remove card if necessary after Switching OFF the power to the unit.