Datasheet PLC Siemens S7-1200
Datasheet PLC Siemens S7-1200
Datasheet PLC Siemens S7-1200
Display
with display No
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 500 mA; Typical
Inrush current, max. 12 A; at 28.8 V DC
Encoder supply
24 V encoder supply
● 24 V Permissible range: 20.4V to 28.8V
Output current
Current output to backplane bus (DC 5 V), max. 1 600 mA; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W
Memory
Type of memory EEPROM
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
● Hardware clock (real-time clock) Yes
● Deviation per day, max. +/- 60 s/month at 25 °C
● Backup time 480 h; Typical
Digital inputs
Digital outputs
Number of digital outputs 10
● of which high-speed outputs 4; 100 kHz Pulse Train Output
integrated channels (DO) 10
short-circuit protection No; to be provided externally
Limitation of inductive shutdown voltage to L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Output voltage
● for signal "0", max. 0.1 V; with 10 kOhm load
● for signal "1", min. 20 V
Output current
● for signal "1" rated value 0.5 A
Analog inputs
Number of analog inputs 2
Integrated channels (AI) 2; 0 to 10 V
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● Cable length, shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Cable length
● Cable length, shielded, max. 100 m; Shielded, twisted wire pair
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Communication functions
S7 communication
● supported Yes
● as server Yes
● As client Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
● UDP Yes
Web server
● supported Yes
● User-defined websites Yes
Integrated Functions
Number of counters 6
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Number of pulse outputs 4
Limit frequency (pulse) 100 kHz
Galvanic isolation
Galvanic isolation digital inputs
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-4
● Interference immunity on signal lines acc. to Yes
IEC 61000-4-4
Surge immunity
● on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011
Ambient conditions
Free fall
● Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Dimensions
Width 110 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 415 g