Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Datasheet PLC Siemens S7-1200

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8
At a glance
Powered by AI
The document provides detailed specifications for the SIMATIC S7-1200 CPU 1214C, including its onboard I/O, memory, processing capabilities, and other key features.

The CPU has 14 digital inputs that can operate at up to 100 kHz, 10 digital outputs (4 of which can operate at up to 100 kHz), 2 analog inputs, 75KB of program/data memory, and 100KB of work memory.

The CPU supports programming in LAD, FBD and SCL languages.

Datasheet 6ES7214-1AG40-0XB0

SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC,


ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0 - 10V DC,
POWER SUPPLY: DC 20.4 - 28.8 V DC, PROGRAM/DATA
MEMORY: 75 KB

Display
with display No

Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V

Input current
Current consumption (rated value) 500 mA; Typical
Inrush current, max. 12 A; at 28.8 V DC

Encoder supply
24 V encoder supply
● 24 V Permissible range: 20.4V to 28.8V

Output current
Current output to backplane bus (DC 5 V), max. 1 600 mA; Max. 5 V DC for SM and CM

Power losses
Power loss, typ. 12 W

Memory
Type of memory EEPROM

6ES7214-1AG40-0XB0 Changes preserved


Page 1/8 05.02.2015 © Copyright Siemens AG
Usable memory for user data 75 kbyte
Work memory
● Integrated 100 kbyte
● expandable No
Load memory
● Integrated 4 Mbyte
● Plug-in (SIMATIC Memory Card), max. 2 Gbyte; with SIMATIC memory card
Backup
● present Yes; maintenance-free
● without battery Yes

CPU processing times


for bit operations, typ. 0.085 µs; / Operation
for word operations, typ. 1.7 µs; / Operation
for floating point arithmetic, typ. 2.3 µs; / Operation

CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code

Data areas and their retentivity


retentive data area in total (incl. times, counters, 10 kbyte
flags), max.
Flag
● Number, max. 8 kbyte; Size of bit memory address area

Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte

Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules

Time of day
Clock
● Hardware clock (real-time clock) Yes
● Deviation per day, max. +/- 60 s/month at 25 °C
● Backup time 480 h; Typical

Digital inputs

6ES7214-1AG40-0XB0 Changes preserved


Page 2/8 05.02.2015 © Copyright Siemens AG
Number of digital inputs 14; Integrated
● of which, inputs usable for technological 6; HSC (High Speed Counting)
functions
integrated channels (DI) 14
m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 VDC at 2.5 mA
Input current
● for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
— Parameterizable 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1
/ 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at "0" to "1", min. 0.1 µs
— at "0" to "1", max. 20 ms
for interrupt inputs
— Parameterizable Yes
for counter/technological functions
— Parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80
kHz & 3 @ 30 kHz
Cable length
● Cable length, shielded, max. 500 m; 50 m for technological functions
● Cable length unshielded, max. 300 m; For technological functions: No

Digital outputs
Number of digital outputs 10
● of which high-speed outputs 4; 100 kHz Pulse Train Output
integrated channels (DO) 10
short-circuit protection No; to be provided externally
Limitation of inductive shutdown voltage to L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Output voltage
● for signal "0", max. 0.1 V; with 10 kOhm load
● for signal "1", min. 20 V
Output current
● for signal "1" rated value 0.5 A

6ES7214-1AG40-0XB0 Changes preserved


Page 3/8 05.02.2015 © Copyright Siemens AG
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", max. 1 µs
● "1" to "0", max. 3 µs
Switching frequency
● of the pulse outputs, with resistive load, max. 100 kHz
Relay outputs
● Max. number of relay outputs, integrated 0
Cable length
● Cable length, shielded, max. 500 m
● Cable length unshielded, max. 150 m

Analog inputs
Number of analog inputs 2
Integrated channels (AI) 2; 0 to 10 V
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● Cable length, shielded, max. 100 m; twisted and shielded

Analog outputs
Number of analog outputs 0
Cable length
● Cable length, shielded, max. 100 m; Shielded, twisted wire pair

Analog value creation


Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), 10 bit
max.
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs

Encoder
Connectable encoders
● 2-wire sensor Yes

1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes

6ES7214-1AG40-0XB0 Changes preserved


Page 4/8 05.02.2015 © Copyright Siemens AG
Autocrossing Yes
Functionality
● PROFINET IO Device Yes
● PROFINET IO Controller Yes
PROFINET IO Controller
● Prioritized startup supported
— Number of IO Devices, max. 16

Communication functions
S7 communication
● supported Yes
● as server Yes
● As client Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
● UDP Yes
Web server
● supported Yes
● User-defined websites Yes

Test commissioning functions


Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters
Forcing
● Forcing Yes
Diagnostic buffer
● present Yes
Traces
● Number of configurable Traces 2; Up to 512 KB of data per trace are possible

Integrated Functions
Number of counters 6
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Number of pulse outputs 4
Limit frequency (pulse) 100 kHz

Galvanic isolation
Galvanic isolation digital inputs

6ES7214-1AG40-0XB0 Changes preserved


Page 5/8 05.02.2015 © Copyright Siemens AG
● Galvanic isolation digital inputs 500V AC for 1 minute
● between the channels, in groups of 1
Galvanic isolation digital outputs
● Galvanic isolation digital outputs 500V AC for 1 minute
● between the channels, in groups of 1

Permissible potential difference


between different circuits 500 V DC between 24 V DC and 5 V DC

EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-4
● Interference immunity on signal lines acc. to Yes
IEC 61000-4-4
Surge immunity
● on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011

Degree and class of protection


Degree of protection to EN 60529
● IP20 Yes

Standards, approvals, certificates


CE mark Yes
UL approval Yes
cULus Yes
RCM (formerly C-TICK) Yes
FM approval Yes
Marine approval
● Marine approval Yes

Ambient conditions
Free fall
● Drop height, max. (in packaging) 0.3 m; five times, in dispatch package

6ES7214-1AG40-0XB0 Changes preserved


Page 6/8 05.02.2015 © Copyright Siemens AG
Ambient temperature in operation
● during operating phase, minimum -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Storage/transport temperature
● Min. -40 °C
● max. 70 °C
Air pressure
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
● Permissible operating height -1000 to 2000 m
Relative humidity
● Operation, max. 95 %; no condensation
● Permissible range (without condensation) at 25 95 %
°C
Vibrations
● Vibrations 2G wall mounting, 1G DIN rail
● Operation, checked according to IEC 60068-2- Yes
6
Shock test
● checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak
value), duration 11 ms
Pollutant concentrations
— SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Cycle time monitoring
● can be set Yes

Dimensions
Width 110 mm
Height 100 mm
Depth 75 mm

Weights
Weight, approx. 415 g

6ES7214-1AG40-0XB0 Changes preserved


Page 7/8 05.02.2015 © Copyright Siemens AG
last modified: 05.02.2015

6ES7214-1AG40-0XB0 Changes preserved


Page 8/8 05.02.2015 © Copyright Siemens AG

You might also like