(3) Description of each part (5) Installation and wiring

DOP-103BQ (front view) Precautions:


 Incorrect installation may result in malfunction.
 To ensure the HMI is well ventilated, make sure there is sufficient space between the HMI and the
adjacent objects or walls.
 This product should be used on a case / platform which conforms to enclosure Type 4X standard (for
High color‧Wide screen‧User-friendly indoor use only).
 The maximum panel thickness for mounting must be no greater than 5 mm.
DOP-103BQ Delta Electronics Inc,
No.18, Xinglong Rd., Taoyuan City Installation steps:
33068, Taiwan Step 1: Step 2:
Put the waterproof gasket into the HMI and then Place the fasteners into the slots and tighten the
Instruction Sheet insert the HMI into the panel cutout. screws until reaching the panel cutouts.

(1) General precautions


Thank you for purchasing this product. This instruction sheet provides information about the DOP-100
series HMI. Before using this product, please read through this instruction sheet carefully to ensure the
correct use of the product. Please keep this sheet handy for quick reference whenever needed. Before
finishing reading this sheet, please follow the instructions below:
 Install the product in an indoor location, which is free of vapor, corrosive and inflammable gas and
liquids. A Operation / display area
 Please refer to the wiring diagram when connecting the wires.
 Ensure your HMI is correctly grounded. The grounding method must comply with the national DOP-103BQ (rear view)
electrical standard (please refer to NFPA 70: National Electrical Code, 2005 Ed.).
 Do not disassemble the HMI or change the wiring when power is on.
 Do not touch the power supply when power is on, or it may cause electric shock.
 When the HMI displays a low power notification and requires a battery change, please contact Step 3: Step 4:
your local distributor or Delta Customer Service Center for the replacement. Do not change the Tighten the screws with the torque less than For heat dissipation, please keep a minimum
batteries by yourself. 0.5 N-M / 0.7 N-M to avoid damage to the plastic clearance of 60 mm on the rear of the HMI.
 This product can be used with other industrial automation equipment. Please read through this case.
sheet carefully and install the product according to the instructions to avoid danger. DOP-103BQ torque: 4.41 lb-inch (0.5 N-M)
 Cleaning method: please use a dry cloth to clean the product.
 This product must be used at an altitude below 2,000 m.
 If the equipment is used in a manner not specified by the manufacturer, the protection provided by
the equipment may be impaired.
 For repair and maintenance, please contact Delta Electronics, Inc. Address: No.18, Xinglong Rd.,
Taoyuan City, Taiwan. TEL: +886-3-3626301.
If you have any inquiry during operation, please contact our local distributors or Delta sales
representatives. The content of this instruction sheet may be revised without prior notice. Please consult
our distributors or download the latest version at Delta’s website (http://www.delta.com.tw/ia).

(2) Communication port pin assignment


A USB slave B USB host
DOP-103BQ COM port
Power input terminal
C D COM1
MODE1 MODE2 MODE3 (24 AWG wire min.)

COM Port Pin COM1 COM2 COM1 COM2 COM1 COM2 Wiring:
RS-232 RS-485 RS-485 RS-485 RS-232 RS-422
(4) Mounting dimensions
Type Wire gauge (AWG) Stripped length Torque
1 - - D+ - - TXD+ Solid 24 - 12 7 - 8 mm 5 kg-cm (4.3 lb-in)
DOP-103BQ
2 RXD - - - RXD -
Stranded 24 - 12 7 - 8 mm 5 kg-cm (4.3 lb-in)

3 TXD - - - TXD -

4 - D+ - D+ - RXD+
Please refer to the following diagram when wiring the power connector. The temperature
5 GND GND GND rating of the cable must be greater than 75oC (167oF).
6 - - D- - - TXD-

7 RTS - - - RTS -

8 CTS - - - CTS -

9 - D- - D- - RXD-

Note: mark “-” means connection is not required.

Operation temperature: 0oC to 50oC (32oF to 122oF)


Storage temperature: -20oC to 60oC (-4oF to 140oF)
(6) Hardware specifications

Model DOP-103BQ

Panel type 4.3" TFT LCD (65535 colors)

Resolution 480 x 272 pixels


Display

Backlight LED backlight (half-life under room temperature 25oC > 20,000 hours) *1

Display range 95.04 x 53.856 mm

Brightness 400 cd/m² (Typ.)

CPU ARM Cortex-A8 (800 MHz)

Flash ROM 256 Mbytes

RAM 256 Mbytes

Touchscreen 4-wire resistive touchscreen > 1,000,000 operated

Buzzer Multi-tone frequency (2 K – 4 KHz) / 80 dB

Network interface N/A

USB 1 USB slave Ver 2.0; 1 USB host Ver 2.0

SD N/A

COM1 RS-232 (supporting flow control) / RS-485*2


Serial
communication COM2 RS-422 / RS-485*2
port
COM3 N/A

Auxiliary function key N/A

Calendar Built-in

Cooling method Natural cooling


CE / UL (please use shielding network cable and magnetic ring with the filter of
Approvals
300 ohm / 100 MHz)
Panel waterproof level IP65 / NEMA 4
DC +24V (-15% to +15%) (please use an isolated power supply)
Operation voltage*2
Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation)
Leakage current 500 VAC for 1 minute (between DC24V terminal and FG terminal)
*2
Power consumption 5.67W (Max) *3

Backup battery 3V lithium battery CR2032 × 1


About 3 years or more at 25oC
Backup battery life
(subject to operation temperature and condition)

Operation temperature 0oC to 50oC (32oF to 122oF)

Storage temperature -20oC to +60oC (-4oF to 140oF)


10% to 90% RH [0oC - 40oC], 10% to 55% RH [41oC - 50oC];
Operating environment
pollution degree: 2
Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with amplitude
Vibration resistance
3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G
Conforms to IEC60068-2-27:
Shock resistance
11 ms, 15 G Peak, in X, Y, Z directions each for 6 times
Dimension
137 x 103 x 37.1
(W) x (H) x (D) mm
Mounting dimension
118.8 x 92.8
(W) x (H) mm
Weight Approx. 280g

Note:
1. The half-life of the backlight is defined as the maximum luminance being reduced by 50% when the
maximum drive current is supplied to the HMI. The life of LED backlight shown here is estimated at the
room temperature of 25oC with ambient humidity.
2. The withstand voltage of the isolated power circuit is 1500V peak for 1 minute.
3. The HMI power consumption is the power consumed when the HMI is not connecting with other
peripheral devices. To ensure normal operation of the HMI, the recommended capacity of the power
supply is 1.5 to 2 times of the specified power consumption.
4. Isolated power supply is recommended.
5. For DOPSoft programming software for DOP-100 series and the user manual, you can download them
at http://www.delta.com.tw/ia.
6. DOP-100 series can be used with other industrial automation equipment. Please read through this
sheet carefully and install the product according to the instructions to avoid danger.