SPD 300W Im

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DIN Rail Mountable

Switching Power Supply


Out-
put
Output Power 300 watts

* 8mm (0.31") for A type


* 4~5mm (0.197") for B type

Input
Connector size range
* AWG24 - 10 for A type
- Input connector can
withstand torque at
maximum 1.01Nm (9lb-in)
- Output connector can withstand
Technical Data torque at maximum 0.621Nm (5.5lb-in)
* AWG24 - 12 for B type
Installation and Operation - Input connector can withstand torque at
maximum 0.50Nm (4.5lb-in)
- Output connector can withstand torque at
maximum 0.79Nm (7lb-in)
Use copper conductors only, 60/75 oC (140/167°F)
Max. surrounding air temperature of 50 oC (122°F) for UL 508

SPD243001x

24 : Output Voltage
24 .... 24Vdc output
48 .... 48Vdc output

x : Blank .... Screw Terminal type


B .......... Detachable Connector type
Installation Connection / Internal fuse
Safety notes Application Connection
This unit is a primary switched-mode power supply designed Data for permitted loads, cable cross-sections and stripping:
for use in panel-board installations or building-in see enclosed leaflet " Technical Data " (See Fig. 3).
Read Instructions! applications where access to the supply is restricted (shock- Use only commercial cables designed for the indicated voltage
Before working with this unit, read these instructions carefully and hazard protection). It must only be installed and put into service and current values!
completely. Make sure that you have understood all the information! appropriately by qualified personnel. With flexible cables: make sure that all stranded cable are secured
in the terminal.
Mounting Ensure proper polarity at output terminals!
Disconnect system from supply network Mounting Grounding
Before any installation, maintenance or modification work: Do not operate without PE connection! To comply with
Permissible mounting position: see Fig. 1 keep free ventilation
Disconnect your system from the supply network. Ensure that cannot hole, leave space for cooling! Recommended to have 25mm EMC and safety standards (CE mark, approvals), the unit must
be re-connected inadvertently! free space at all sides for ventilation / cooling: only be operated if the PE terminal is connected to the
see supplementary sheet "Technical Data". non-fused earth conductor.
Secondary side is not earthed; if necessary the + or - terminal
Before start of operation Snap on support rail (See Fig. 2) can be earthed optionally.
Ensure appropriate installation Tilt the unit slightly rearwards.
Warning! Improper installation / operation impair safety and result
Fit the unit over top hat rail. Internal fuse
Slide it downward until it hits the stop. The internal input fuse serves to protect the unit and must
in operational difficulties or complete failure of the unit.
Press against the bottom front side for locking. not be replaced by the user. In case of an internal defect, the
The unit must be installed and put into service appropriately by qualified
Shake the unit slightly to check the locking action. unit must be returned to the manufacturer for safety reasons.
personnel. Compliance with the relevant regulations must be ensured.
Before operation is begun the following conditions must be ensured,
in particular: Front elements Removal
Connection to main power supply in compliance with VDE0100 Operation indicator Removal from DIN Rail
and EN50178.
The green LED lights up while the PSU working properly. Insert a flat screwdriver into the slot in the clamp. Pull down
With stranded wires: all strands must be secured in the terminal
the clamp out until the clamp clicks, and turn the switching
blocks (Potential danger of short circuit).
Unit and power supply cables must be properly fused; if necessary DC output low indicator power supply bottom out. (See Fig. 4)
a manually controlled disconnecting element must be used to disengage The red LED lights up while the output voltage is too low.
from supply mains.
The non-fused earth conductor must be connected to the " " Potentiometer
terminal (protection class 1). Setting the output voltage.
All output lines must be rated for the power supply output current
and must be connected with the correct polarity.
Sufficient air-cooling must be ensured. All specifications are typical at norminal line, full load,
Technical Data Output Specification
Use in a pollution degree 2 environment. 25oC; Unless otherwise noticed.
Output Accuracy...................... +0 ~ 1%
This equipment is suitable for use in class I, division 2, groups A, B, Line Regulation ....................... ± 0.5%
C, and D or non hazardous locations only. Load Regulation ...................... ± 1% for single mode
Warning-explosion hazard-substitution of components may impair Output Eff. Inrush Current ± 5% for parallel mode
suitability for class I, division 2. Vo [V] Io [A] Ripple & Noise ......................... 100 mV
Power [typ.] 115Vac 230Vac Voltage Trim Range .................. 22.5 ~ 28.5 Vdc for 24V models
Warning-explosion hazard-do not disconnect equipment unless power 47 ~ 56 Vdc for 48V models
has been switched off or it is known to be the non-hazardous area. 24 12.5 89% DC ON Indicator....................... Green LED
300 < 35A < 65A DC LOW Indicator..................... Red LED
48 6.25 90% Parallel Operation..................... 3 unit max.
In operation: No modifications! Turn on time............................ <1000ms
As long as the unit is in operation: do not modify the General Specification Voltage Fall time....................... <150ms
installation! The same applies also to the secondary side. Risk of Voltage Rise time...................... <150ms
Isolation ................................ 3000 Vac / 4242 Vdc Hold up time............................ > 25ms
electric arcs and electric shock (fatal)! Isolation Resistance................. 100 M ohm Case material.......................... Metal
Only (dis) connect plug connectors when Operation amb. Temperature .... -30 ~ +71 C
o
Control And Protection
the power is off! Storage Temperature ............... -40 ~ +85 C
o
Input Internal Fuse.................. T8A / 250 Vac
o
Derating................................. +56 ~ +71 C (see Fig. 5) Output Short Circuit ................ Fold Forward
Output Over Load .................... 120 % ~ 145 %
Convection cooling Relative Humidity .................... 20 - 95% RH
Do not cover any ventilation holes! Cooling .................................. Free air convection Approvals And Standard
Leave sufficient space around the unit for cooling! Temperature Coefficient ........... 0.03% / C
o UL / cUL................................. UL 508 Listed, UL 60950-1 Recognized
ISA 12.12.01
See supplementary sheet "Technical Data" and Fig. 1 Dimension.............................. L124.5 x W83.5 x D123.6 [mm] for A type TUV. ...................................... EN 60950-1
L143.5 x W83.5 x D123.6 [mm] for B type EN 61558-1, EN 61558-2-17
Weight................................... 1400g CE ......................................... EN 61000-6-3, EN 55022 class B
Warning: High voltage! Store energy! EN 61000-3-2, EN61000-3-3
Fig. 5 Derating EN 61000-6-2, EN 55024
The unit contains unprotected conductors carrying a lethal high voltage, Input Specification EN 61000-4-2, -3, -4, -5, -6, -8, -11

Power out [ % ]
and components storing substantial amounts of energy. Improper 100
EN 61204-3
handling may result in an electric shock or serious burn! Input Voltage Rated ................ 115/230 Vac ( Auto Select ) 62.5
The unit must not be opened except appropriately trained Input Voltage Range ................ 115 Vac (90 ~ 132 Vac ),
personnel! 230 Vac (180 ~ 264 Vac), or 210 ~ 375 Vdc
Do not introduce any object into the unit! Rated Input Curren.t................. 6.0/3.0 A 0
Keep away from fire and water! Line Frequency......................... 47-63 Hz -30 56 71
Power Factor........................... 0.75@230 Vac Temperature [ oC ]

11/2010 DM247-A1