MT-500 Series: MT-506T, MT-506L Installation Instruction 1.0 Installation and Startup Guide
MT-500 Series: MT-506T, MT-506L Installation Instruction 1.0 Installation and Startup Guide
MT-500 Series: MT-506T, MT-506L Installation Instruction 1.0 Installation and Startup Guide
MT-506T, MT-506L
Installation Instruction
Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC
output modules, contactors, starters and relays, and any other source of electrical interference are located
away from the back of the unit.
Particular note should be taken to the position of variable speed drives and switching power supplies.
Their input and load cables should be screened to a central star earth point.
2
If wiring is to be exposed to lightning or surges, use appropriate surge
suppression devices.
Keep AC, high energy, and rapidly switching DC wiring separate from
signal wires.
Equip ungrounded DC supplies with a resistor and capacitor in parallel to
earth ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1MOhm and 4700pF.
Connection To make a connection, strip about 3/8” of insulation off the end of the wire,
turn the connector screw counterclockwise until the gap is wide open, insert
the wire all the way in, and turn the screw clockwise until it’s tight.
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the
‘0V‘ terminal.
2.2.2 Grounding Requirements
Chassis ground must be used. DC ground is not directly coupled to Earth
ground internally. It is preferable not to ground DC negative return to chassis
ground as poor site earths can introduce noise into a system, but if necessary
an earth connection should be made, from the power supply return point to
the central star earth point. Ground conductors should be as short and as large
in size as possible. The conductors must always be large enough to carry the
maximum short circuit current of the path being considered. Ground
conductors should be connected to a tree from a central star earth ground
point. This ensures that no ground conductor carries current from any other
branch.
2.2.3 CE Requirements
To make an MT-500 comply with EMC directives, and to reduce susceptibility to electrical
interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the
power connector. This ground connection should be run directly to the central star earth connection
point (as recommended in most Installation Instructions).
2.2.4 Safety Guidelines
This section presents recommended installation practices, and procedures. Since no two
applications are identical, these recommendations should be considered as guidelines.
Hardware WARNING!
Considerations
The system designer should be aware that devices in Controller systems could
fail and thereby create an unsafe condition. Furthermore, electrical
interference in an operator interface, such as an MT-500, can lead to
equipment start-up, which could result in property damage and/or physical
injury to the equipment operator.
If you, or your company, use any programmable control systems that require
an operator or attendant, you should be aware that this potential safety hazard
exists and take appropriate precautions. Although the specific design steps
depend on your particular application, the following precautions generally
apply to installation of solid-state programmable control devices. In addition,
these precautions conform to the guidelines for installation of Controllers as
recommended in the NEMA ICS 3-304 Control Standards.
Programming To conform with ICS Safety Recommendations, checks should be placed in
Considerations the controller to ensure that all writable registers that control critical parts
of plant or machinery have limit checks built into the program, with an
out-of-limit safe shut down procedure to ensure safety of personnel.
ICS 3-304.81 Safety Recommendations:
Consideration should be given to the use of an emergency stop function, which is independent of the programmable
controller.
Where the operator is exposed to the machinery, such as in loading or unloading a machine tool, or where the machine
cycles automatically, consideration should be given to the use of an electromechanical override or other redundant means,
3
independent of the programmable controller, for starting and interrupting the cycle.
If provision is required for changing programs while the equipment is in operation, consideration should be given to the
use of locks or other means of assuring that only authorized personnel can make such changes.
These recommendations are intended as safeguards against the failure of critical components and the effects of such
failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation. *
z The ICS 3-304.81 Safety Recommendations are reproduced by permission of the National Electrical
Manufacturers Association from NEMA ICS 3-304
4
2.3.2 Connection to a Personal Computer
The 9 Pin, Female, SUB-D, PC [RS-232] & PLC [RS-485] Port on the back of the unit is the
programming port (PC Connector) and RS485/422 communications port for connecting to a controller.
Connection This port can be connected to a Computer via a special DB9 Female to
DB9 Female download cable (P/N: MT5_PC, optional).
Port Activation This port is activated automatically by the PC during on line simulation,
download and upload activities.
The Programmer Port cannot simulate, download or upload to the
MT-500 while it is on line with the controller at the same time. The
MT-500 must be put into “RDS” mode with the EasyManager applet
first.
Pin Designations Pin assignment of the 9 Pin, Male, SUB-D PC [RS-232] &PLC
[RS-485] Port. (Only MT5XXXE4 has AUX RS485)
Pin# Symbol PLC[RS485] PLC[RS485] Aux[RS485] PC[RS232]
4 wire 2 wire (only E4 series)
1 Rx- Rx- Data-
PC [RS-232] &
PLC [RS-485] 2 Rx+ Rx+ Data+
3 Tx- Tx-
4 Tx+ Tx+
5 GND Signal Ground
6 Data- Data-
7 TxD Transmit
8 RxD Receive
9 Data+ Data+
5
2.3.3 Dip Switch
SW1 SW2 Mode
ON ON Touch Screen Test mode
OFF ON RDS (Remote Debug & Simulation) mode
ON OFF Touch Adjust (Touch screen calibration)
mode
OFF OFF Application (On line operation) mode
* SW3, SW4 unused
z Touch Screen Test mode: In this mode when you touch the screen, the screen will display a “+” sign.
So you can test the touch screen was accurate.
z RDS (Remote Debug & Simulation) mode: Used for simulation and download/upload.
When E series insert a CF card will appear a “CF” button on screen right and bottom side.
Press this button to startup the project download procedure.
On MT506LV45 screens, press the “BRIGHT” button or the “DARK” button to adjust LCD contrast.
z Touch Adjust (Touch screen calibration) mode: Used to calibrate the touch screen.
z Application (On line operation) mode: This is the normal operating mode of the MT500; the MT500
will start from the startup window of the project download.
2.4 CE Requirements
EU directives that apply to the MT-500 Series:
z EMC Directive (89/336/EEC, 92/31/EEC, 93/68/EEC) electromagnetic emissions and immunity
z Machinery Directive (89/392/EEC, 91/368/EEC, 93/44/EEC, 93/ 68/EEC) machine safety
z MT500 products will be CE-marked to indicate compliance with the EMC Directive.
The MT-500 Series has been designed to operate satisfactorily in electromagnetic noise (immunity) and
without emitting high levels of electrical noise into the environment (emission). The units are designed to
meet European Community standards when installed per the wiring instructions in this manual.
Compatibility
The MT-500 has been designed to meet electromagnetic compatibility for industrial
Standards environments.
• CISPR (EN 55011) Group 1, Class A Radiated Emissions levels
• EN50081-2 Generic emission standard, industrial environment (Also US FCC Class A)
• EN50082-2 Generic immunity standard, industrial environment
6
3.0 Specifications
MT506TE MT506TV MT506LV
Hardware Specification
Display 5.6" TFT 5.6" TFT 5.7" Blue
Brightness 500 cd/m2 500 cd/m2 120 cd/m2
Color 256 color 256 color 4 gray scale
Contrast Ratio 150:1 150:1 15:1
Resolution (WxH dots) 320 x 234 320 x 234 320 x 240
Back light CCFLx1 CCFLx1 CCFLx1
CCFL life time (Average) 30,000 hr. 30,000 hr. 50,000 hr. min.
Touch panel 4 wires resistive type
Touch Accuracy 1.5mm
Surface Hardness 4H
HMI-PC (RS-232)
Serial port
HMI-PLC (RS-232/485)
AUX port HMI-AUX(RS-232/RS-485 2w) N/A
Ethernet port 10Mbps N/A
Compact Flash card slot Yes N/A
Processor 32bit RISC CPU 200MHz
Flash Memory 2MB
Recipe memory 128KB
RTC Yes
Parallel printer port N/A
System Diagnostic Power failure detection
General Specification
Input Power 24±5% VDC
Power Consumption 250 mA@24VDC 250 mA@24VDC 200 mA @24VDC
CE Complies with EN50081-2 and EN50082-2 standards
FCC Complies with FCC Class A
Voltage resistance 500VAC (1 min.)
Isolation resistance Exceed 50MΩ at 500VDC
Vibration endurance 10 to 25 Hz (X,Y,Z direction 2G 30minutes)
Protection structure IP65 front panel (O ring seal)
Operating Temperature 0~45°C
Operation humidity 10-90% RH (non –condense)
Enclosure Plastic
Dimensions WxHxD 204x150x48mm
Panel cutout dimension 192 x 138 mm
Weight Approx. 0.84 kg
Software
Screen Editor Software EasyBuilder 500 V2.7.0 or later
7
4.0 Dimensions of MT-506
Panel-mounting clamp,
4 places (only 1 shown)
(Panel)
Panel-mounting clamp
slots, 4 places
a b c d
PC [RS232]
PLC[RS485]
PLC[RS232]
ETHERNET
Cutout dimensions:
MT-506T / S / L:
192mm [7.56"] W x 138mm [5.43"] H
Reset DIP SW
FUSE 1A
+24V
FG
0V