Current Relay
Current Relay
Current Relay
GE Appliance Controls
GENERAL INFORMATION
3ARR2, 3ARR12, 3ARR12P, 3ARR18
Current Type Motor Starting Relays
2
g Basic Current Type Starting Relay
GE Consumer & Industrial
GE Appliance Controls
Materials
PTCR type starting devices are essentially The electrical contacts are silver/cadmium
timing devices and do not recognize the oxide (Ag/CdO) composition for reliable
variations in the acceleration time of the making and breaking of the start winding
motor under varying load conditions. circuit.
There are three types of GE Current Type There are several options of terminal types,
Starting Relays available. All three are of depending on the particular basic model
the same solenoid actuated types. Each type (like 3ARR2, 3ARR12, and 3ARR18).
has special features for specific Quick-Connect terminals are the most
applications. commonly used. However, screw type
terminals are available on some models.
3ARR2 - Utilizes auxiliary terminals for See the specification sheet for the specific
wiring harness flexibility. model type.
3ARR12 – More cost effective for specific On some models, there are spare terminals
function. Has low and high contact rating for auxiliary connections.
capability.
For compressor applications, a “plug-in”
3ARR12P – Plugs onto motor connections version of the 3ARR12 relay is available
on compressor shells. Available in high which plugs directly onto the 3-pin
rating. terminals on the compressor shell.
3
Relay Internal Circuits Electrical Contact Ratings:
Endurance
Motor Curves
Imr
Transfer Speed
Crossover Speed
Pickup Current
6
g GE Consumer & Industrial
GE Appliance Controls
7
Dropout Current Other information required is the electrical
circuitry of the relay, mounting means,
Value of current in the main winding numbers and types of terminals, etc.
at which the relay drops out, de- The coil must withstand continuous main
energizing the start winding. winding current without exceeding the
allowable heat rise. Wire size can be
Must be higher than the main winding adjusted to meet the requirements. It must
current at full load speed with maximum also be of low enough resistance so that it
supply voltage. will not affect the motor performance.
The maximum start winding current with The only real control of the calibration of
maximum supply voltage and maximum the relay is the coil design, which is “wire
motor speed. size and number of turns”. There are only
minor adjustments to the plunger
Application Procedure assemblies which may be made . However,
the fact that normally, the only
General specifications are maximum pickup and
minimum dropout. A correct coil design is
There are various procedures used to relatively easy to make.
select the correct functional elements and
characteristics of the relay to be applied, Current Type Starting Relays involve
depending on the amount of information compromises to ensure that specific
available. The more operating performance requirements are not violated.
information available, the better. This means reviewing data and preliminary
calculations and refining them to provide
Key information required to make an optimum relay characteristics.
application is the basic model type;
3ARR2, 3ARR12, 3ARR12P, or 3ARR18. Coil Group Selection
Within the 3ARR12 type, a decision is
required as to whether the “K” version is If the customer has already determined
required for a higher electrical rating of what pickup and dropout currents are
the contacts. required, coil design selection may be
determined by a review of coil designs
A very important item of information is already on drawing, and selecting a coil
the Motor Curves that the relay will be which fits the customer specification
used with. These provide the main closely. The customer can verify its
winding current vs. motor speed, and acceptability.
torque vs. speed from zero to full speed
RPM. It is these curves which determine Each of the relay basic models has a
the pick up and drop out specifications for drawing listing all of the coils that have
the relay. been applied, along with the calibration
data, wire diameter and number of turns.
8
g
On current relays, coils are generally
GE Consumer & Industrial
GE Appliance Controls
“drop”, or “sag” in the supply voltage when
listed as “groups”. However, unlike the motor is started.
potential relays where the coil is a
separate component, the current relay For the dropout current, the dropout
coil is just wire wound around the body, or current of the relay must be higher than full
case of the relay which is already load current (motor running) of a “cold”
assembled with other functional motor with maximum expected supply
components. voltage.
Consequently, a coil group for a current
relay is a listing of the wire size, number of It also must not be so high as to take the
turns, and the pickup and dropout current start winding out of the circuit before the
values. motor has enough torque from the run
winding to bring the motor up to full speed
Calibration Specifications– From Motor after the start winding is de-energized.
Curves
Because of the nature of the design and
If a new coil design is required, samples the calibration requirements, the current
must be made and approved. relay has a rather small differential
between pickup and dropout. Normally,
If calibration characteristics are not the pickup calibration will be within 2% to
known, the Motor Curves must be used to 10% of the dropout value.
determine the correct calibration for the
application. Coil Design
The design procedure for current relay Once the pickup and dropout currents are
coils is somewhat different from that of determined from the Motor Curves,
the potential relay. reviewing the existing Coil Groups from
basic model types may yield a presently
On a current relay, when the motor is used coil group designation.
stopped, the relay contacts are open.
When the motor is energized, the relay Any coil which is selected from existing coil
must pick up and close its contacts in groups or as a new design from the Motor
order to have the start winding in the Curves must be evaluated for heat rise
circuit during the starting operation. This when the motor is running at full speed.
means that the pickup current must be The coil of the relay has main winding
less than the current in the main winding current flowing at all times the motor is
at zero motor speed. running.
The value selected must be for a hot Once the coil wire size and number of turns
motor with the minimum expected supply have been selected, the manufacturers full
voltage. Normally, a safety factor is load running current must not cause the
added to keep the relay from dropping temperature of the coil windings to exceed
out prematurely if there is a temporary the maximum allowable. If the rise is too
9
high, then the coil must be made with a
larger wire size to reduce resistance. Mounting Location
Only the necessary increase in wire size The relay should not be mounted in a
should be made, since larger wire sizes location where there is close proximity to
increase the bulk of the coil. The size of large pieces of magnetic material which
the coil must not be greater than the may link the magnetic flux of the relay and
dimensions of the relay. change the calibration If another location is
not possible, the calibration of the relay
Another consideration of wire size is that may be modified to compensate for the
the coil resistance should be maintained effect.
at ½ ohm or less so that it does not impair
the performance of the motor. The relay should not be located where it is
subject to severe vibration or shock which
Effects of Frequency (50/60 Hz) may alter the function.
In the case of current relays, the The relay must be mounted in a vertical
frequency of the supply does not have position since gravity is the means of
any significant effect on calibration or coil dropping out, or resetting the relay for the
rating as it does on potential relays. On next cycle. If the mounting position is not
potential relays, where the coils have vertical, the plunger will ride on the inside
many thousands of coil turns, the of the case where friction will affect the
inductive reactance makes substantial calibration of the relay.
effects on the electrical impedance of the
Mounting Brackets
coil and consequently, on the calibration
and rating.
Mounting means and brackets vary
depending on the basic model type. For
However, on current relays where there
the 3ARR12 and 3ARR18 type relays, some
are relatively few coil turns, usually 60 or
of the mounting brackets are
less, inductive reactive reactance is not a
interchangeable.
significant factor. So it is ignored, and
relays can be used interchangeably on 50
See Appendix “B” for some typical
Hz or 60 Hz, assuming that the
mountings for the various model types.
calibrations are correct for both
applications and the motor currents are
There are applications where the customer
equivalent.
provides the mounting means, and no
bracket is supplied.
It should be noted that a 50 Hz , two-pole
motor has a synchronous speed of 3,000
If there are special mounting requirements
RPM, whereas a 60 Hz two-pole motor has
not covered by standard mounting means,
a synchronous speed of 3,600 RPM.
any special tooling will be the customer’s
responsibility.
10