Insulating Oil
Insulating Oil
Insulating Oil
INSULATING OIL
Insulating oil distillate can be thought of as being similar to domestic fuel but
with the high volatile ends removed. It thus has a much higher flash point and
much narrower boiling range than fuel oil.
The distillate stock contains many unstable components, which tends to oxidize
quite readily. These are removed by one of several solvent extraction refining
prosses to produce clear, bright and stable oil. The purpose of refining is to
remove as much of the unstable materials as possible and thereby increase the
oxidation stability of the oil, which is necessary for long service life.
In order to fulfill these functions, mineral insulating oil must meet these
requirements:
The measured value of the electric strength depends essentially on the apparatus
and procedure used.
The test described below consists in subjecting the oil, contained in a specified
apparatus, to an a.c electric field with a continuously increasing rate of voltage
rise, till the oil breaks down.
2. GENERAL
The test is, in principle, the same for all classes of oil (for transformers, for oil-
filled cables, for circuit breakers, for capacitors), whether new or used. It is
mainly intended for the acceptance of new oils at the time of their delivery: its
application is restricted to oils having a viscosity of not more than 50 centistokes
at 20 deg. C.
3. SAMPLING
The oil is sampled at the place where it is considered to be the most polluted for
example, at the lowest point of the receptacle holding it.
The test is carried out on the oil as received, without drying or degreasing.
3
5. TEST CELL
6. ELECTRODES
The copper, brays, bronze or stainless steel polished electrode arc either spherical
(12.5mm to 13.0mm diameter) as given in fig. 1 or spherical surfaced of the shape
and dimensions given in fig. 2. The electrodes are mounted on a horizontal axis
and are 2.5mm apart.
The gap between them is set to an accuracy of plus minus 1mm by means of
thickness gauges. The axis of the electrodes is immersed to a depth of
approximately 40mm.
When it is not in use, it is recommended to store the apparatus full of dry oil in a
clean dry place, protected from dust.
If it has not been used for some time, it is thoroughly cleaned: the electrodes are
removed, cleaned and finally rinsed with dry clean new oil. Replacement of the
electrodes is carried out with the greatest care, avoiding all direct contact with the
fingers.
Immediately before use, the cell is cleaned by rinsing with the test oil (several
times, if possible) before proceeding to the final filling under the conditions laid
down in clause 7.
The vessel containing the test oil is gently agitated and turned over several times
in such a way as to ensure as far as possible a homogeneous distribution of the
impurities contained in the oil without causing the formation of air bubbles.
Immediately after this, the sample is poured down into the test cell, slowly in
order to avoid air bubbles forming e.g by means of a clean, dry glass rod. The
operation is carried out in a dry place free from dust.
The oil temperature at the time the test shall be the same as that ambient air,
preferably in the neighborhood of 20 deg. C (15 to 25 deg. C) and noted.
4
9. TEST METHOD
In the latter case the automatic switch shall break the voltage within 0.02 second.
The breakdown voltage is the voltage reached during the test at the time the first
spark occurs between electrodes, whether it is transient or established.
The test shall be carried out six times on the same cell filling.
The first application of the voltage is made as quickly as possible after the cell has
been filled, provided there are no longer any air bubble in the oil, and at the latest
ten minutes after filling. After each breakdown, the oil is gently stirred between
the electrodes by means of a clean, dry glass rod, avoiding as far as possible the
production of air bubble. For the five subsequent tests, the voltage is re-applied
one minute after the disappearance of any air bubble that may have been formed.
If the observation of the disappearance of air bubbles is not possible, it is
necessary to wait five minutes before a new breakdown test is started.
The dielectric strength is the arithmetic mean of the six results which have been
obtained.
The characteristic of the electrical apparatus shall comply with the following
requirements:
10.1 TRANSFORMER
The test voltage may be obtained by using a step-up transformer supplied from an
a.c (40 to 62 Hz) low voltage source. The primary voltage is gradually increased,
either manually or by an automatic control device.
To protect the equipment and to avoid decomposition of the oil at the instant of
breakdown, a resistance limiting the breakdown current may be inserted it series
with the test cell.
The primary circuit of the high voltage transformer is fitted with a circuit breaker
operated by the current flowing. Following the breakdown of the sample, and with
a delay not more than 0.02 second. The circuit breaker is fitted with a no-voltage
release coil to protect the equipment.
For the purpose of this document, the magnitude of the test voltage is defined as
its peak value divided by square root two.
The ratio of the voltage derived from the sphere gap to the voltage indicated on
the auxiliary instrument may be dependent upon the presence of the test cell or of
the sphere gap and it is importance that the test cell (or an equivalent load) should
be it’s the circuit during the calibration.
6
The sphere gap may be disconnected during the actual test if its presence is
known to have a negligible influence on the voltage ratio.
11.0 RESULTS
The report shows, expressed in kilovolts, the breakdown voltages obtained during
all the tests which have been carried out, and the average of the results. The report
shall mention the type of electrodes used, the frequency of the test voltage and the
oil temperature.
The following notes, on the care necessary in making a reliable test for the
breakdown voltage of a sample of oil, are mainly intended for the guidance of
those whose experience in the subject may be limited. They should be read in
conjunction with the relevant specification.
Transformer and switchgear oil may be rendered unsuitable for further use by four
main causes:
Low dielectric strength may result from many causes, the most common of which
is foreign particles or fibers and water in combination. Individually their effect
may be relatively small, but together, a contamination of only a few parts in a
million can cause considerable lowering of the breakdown voltage of the oil. High
acidity, sludge and free water should not be tolerated, but they will not necessarily
reduce the dielectric strength below acceptable or specified levels.
Only an experienced worker can judge the condition of an insulating oil from its
appearance, but a general guide may be obtained from the following observations.
The necessity for scrupulous cleanliness in the apparatus and during the process
of sampling, cannot be over emphasized. The measurement of the dielectric
strength of the sample is as dependent on the cleanliness of the test cell and
sampling apparatus as the condition of the oil itself.
Glass sampling vessels should be cleaned with chromic acid cleaning solution.
The glass sampling should then be washed with distilled water, drained, dried in a
warm oven and cooled (if necessary by blowing with clean dry air to prevent
condensation of moisture). In the absence of chromic acid, hot soapy water may
be used followed by a thorough rinsing with hot water and dried in a warm oven.
Trichlorethylene, n-heptane or a light petroleum spirit is also suitable. Chromic
acid or water should not be used for the cleansing of steel sampling vessels and
thiefs.
Corks, leather washers or other absorbent materials must be kept clear of contact
with water.
Water should not be used for the cleaning of test cells since the intricate electrode
assemblies are liable to trap moisture, cleansing glass or moulded resin vessels
should be with n-heptane, trichlorethylene or a light petroleum spirit followed by
drying in a warm oven and cooling where necessary with clean dry air. Care
should be taken that the sealing washers do not become permanently
contaminated with the cleaning solution. Prospect vessels should be thoroughly
washed out with clean oil only.
Once a clean test cell has been obtained, it should preferably be kept filled with a
high dielectric strength clean sample of oil. The previously tested sample can
frequently be used for this purpose. A lid is provided for the cell and this should
always be kept in place to prevent atmospheric pollution.
Should an inferior sample of oil be tested, the cell and sampling bottles must be
cleaned, as suggested above, before taking further samples.
8
Always run off a small quantity of oil into a bottle or test tube for a check on the
appearance of the oil. Attention to this point may prevent contamination of a clean
test cell or samplings bottle.
When a sample is required from a tank or drum, the oil should be set to flow at a
steady rate into the sampling bottle and after being swilled around the sides and
neck, it should be discarded. Without altering the rate of flow of the oil the
quantity required for the test should then be run off while taking extreme care to
prevent the ingress of atmospheric dust, cloth fibers or moisture.
Since the oil taken from a drain cock will inevitably contain an excess of settled
out solid impurities and will not necessarily be representative of the bulk of the
oil, it should either be run until clear or an intermediate sample should be drawn
by means of a thief.
Apabila ujian ini dijalankan dengan sempurna, keadaan status alatubah atau
perkakasuis boleh diketahui dan perancangan senggaraan atau membaikpulih
boleh dijadualkan. Dengan cara ini kita dapat menjimatkan kos membaiki
kerosakan.
Ujian ini dijalankan mengikut spesifikasi IEC 156/63 atau BS 5874/80. Ujian ini
dijalankan untuk menentukan ketahanan minyak penebatan apabila voltan tinggi
AC dikenakan (inject) sebelum berlaku pecah-tebat (breakdown).
Pengujian cara ini adalah yang paling biasa digunakan ditempat kerja.
Ujian ini dapat menentukan kandungan lembapan, habok atau lain-lain objek luar
seperti benda-benda ‘fibrous’.
Ujian ini dijalankan dengan mengambil contoh minyak didalam bekas yang
mengandungi dua elektrod dan dijarakkan mengikut spesifikasi tertentu. Voltan
tinggi dialirkan kepada kedua-dua elektrod dan dilaraskan sehingga kedua-dua
elektrod itu flash-over. Flash-over yang terjadi menandakan tahap voltan tinggi
berkenaan yang dapat dikenakan kepada contoh minyak tersebut.
Ujian asid ialah ukuran kandungan asid didalam minyak penebatan. Ujian ini
biasanya dijalankan didalam makamal, berfungsi untuk mengesan tindakbalas
kimia apabila minyak bercampur dengan kekotoran seperti enapan (sludge).
i). Secara fizikal warna minyak dapat menggambarkan minyak itu sendiri tetapi
ini bukan petunjuk yang tepat dan tidak dapat digunakan sebagai ukuran yang
tertentu.
ii) Secara fizikal kita boleh melihat kandungan air (droplets) didalam minyak
i. Alirkan sedikit minyak yang hendak diuji kedalam bekas berkaca untuk
mempastikan warna minyak berkenaan. Ini dapat mengelakkan bekas
penguji tidak tercemar
ii. Apabila contoh minyak diambil dari tong atau tangki, minyak tersebut
mesti dialirkan tanpa henti kedalam bekas contoh untuk tujuan
pembersihan. Tanpa menghentikan aliran minyak tersebut, ambil minyak
yang diperlukan untuk pengujian
iii. Contoh minyak yang diambil dari injap keluar (drain cock) lazimnya akan
mengandungi kekotoran yang berlebihan, minyak yang mula-mula
mengalir dibuang, selepas itu barulah contoh minyak diambil untuk
pengujian
iv. Jangan gunakan bahan bergetah atau gasket sebagai penutup kepada bekas
contoh minyak tersebut
v. Jangan biarkan contoh minyak terdedah kepada cahaya matahari