EcodialAdvanceCalculation Help
EcodialAdvanceCalculation Help
EcodialAdvanceCalculation Help
Technical help
EcoStruxure Power Design - Ecodial
Table of Contents
1. Legal Information ______________________________________________________________________ 5
2. Important Information__________________________________________________________________ 6
3. Component names _____________________________________________________________________ 7
4. Main changes following the Cenelec TR50480 report _______________________________________ 8
4.1. Modification of voltage factor c __________________________________________________________ 8
4.2. Elimination of the no-load factor m _______________________________________________________ 8
4.3. Calculation of short-circuit currents with parallel-connected transformers ________________________ 8
4.4. Contribution of asynchronous motors to short-circuit currents__________________________________ 8
5. Types of system earthing________________________________________________________________ 9
5.1. Types of system earthing & recommendation ______________________________________________ 10
6. Types of transformer losses ____________________________________________________________ 10
6.1. Immersed-type transformers ___________________________________________________________ 10
6.2. Dry-type transformers _________________________________________________________________ 10
7. Diversity factor Ks_____________________________________________________________________ 11
7.1. Switchboard busbars __________________________________________________________________ 11
7.2. Distribution BTS ______________________________________________________________________ 11
7.3. Diversity factor and operating mode _____________________________________________________ 11
8. Switchgear status and operating modes _________________________________________________ 12
9. Discrimination ________________________________________________________________________ 13
9.1. Discrimination of LV protective devices ___________________________________________________ 13
9.2. Discrimination of residual-current protective devices ________________________________________ 14
9.3. Discrimination between MV and LV protective devices _______________________________________ 15
10. Cascading____________________________________________________________________________ 16
10.1. Default and individual parameter settings _______________________________________________ 16
10.2. Attempts to find a cascading solution ___________________________________________________ 16
10.3. Limits on cascading _________________________________________________________________ 16
10.4. Other configurations for which cascading is not attempted __________________________________ 16
11. Check on the thermal stress in cables ____________________________________________________ 17
11.1. Principle __________________________________________________________________________ 17
11.2. Necessary measures against thermal stress ______________________________________________ 17
12. Switchgear Functions __________________________________________________________________ 18
12.1. Withdrawable circuit breakers and switches _____________________________________________ 18
12.2. Electrical operating mechanisms for circuit breakers and switches ____________________________ 18
12.3. Remote opening of switches __________________________________________________________ 18
1. Legal Information
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis,
evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither
Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein. If you have any suggestions for improvements or amendments or have found errors in this
publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
2. Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
3. Component names
The default prefix of component names is defined in accordance with standard IEC 81346-2.
This standard defines the following rules depending on the type of equipment.
ZT
Incomer:
Outgoer:
TN-C system
TT system
IT system
TN-C system earthing is not recommended on the sites where there is a risk of fire or explosion.
7. Diversity factor Ks
The IEC 60439-1 standard defines simultaneity factor values that can be used in the absence of more precise
information for prefabricated electrical panels and busbars.
EcoStruxure Power Design-Ecodial does not apply these values by default to calculate the operating currents for
pipes and busbars. This must be changed by the user manually.
The determination of ks factors is the responsibility of the designer, since it requires a detailed knowledge of the
installation and the conditions in which the individual circuits are to be exploited.
For this reason, it is not possible to give precise values for general application.
When a part of the network is not supplied in a given operating mode, it is shown in blue in the single-line diagram.
Given that the "closed" status condition is the most common in installations, only the "open" status condition is shown
in the single-line diagram.
9. Discrimination
9.1. Discrimination of LV protective devices
9.1.1.Principle
Tripping curve
Non-tripping curve
If the selectivity limit current is lower than the short-circuit current that can occur on the circuit protected by the
downstream protective device, discrimination is said to be partial.
If the selectivity limit current is higher than the maximum short-circuit current that can occur on the circuit protected by
the downstream protective device, discrimination is said to be total for the given installation.
9.1.3.Means to achieve total discrimination
If the curves cross in the crossing detection zone, i.e. below the downstream instantaneous-setting current, the
settings on the protective devices may be adjusted to achieve discrimination. Use of time-delayed trip units makes this
easier.
If the discrimination limit is in the table zone, the rating of the upstream protective device must be increased. In this
case, EcoStruxure Power Design - Ecodial retains the circuit design current Ib as the reference for the thermal setting
of the protective device to avoid oversizing the cable.
The sensitivity of the downstream device must also meet the condition below:
sensitivity (I∆n) x 2 ≤ fault current (Ief).
≥ 2 → current discrimination OK
Ikmin
9.2.2.Partial discrimination
When the sensitivity discrimination condition is not met, discrimination is said to be partial.
However if the breaking-time discrimination condition is not met, there is no discrimination between the two residual-
current protective devices (even if the sensitivity discrimination condition is met).
Depending if the MV protective device is a fuse or relay the rules to ensure discrimination between MV and LV are
slightly different.
For MV fuse:
all parts of the minimum pre-arcing fuse curve must be located to the right of the CB curve by a factor of 1.35
or more (e.g. where, at time T, the CB curve passes through a point corresponding to 100 A, the fuse curve at
the same time T must pass through a point corresponding to 135 A, or more, and so on...),
and all parts of the fuse curve must be above the CB curve by a factor of 2 or more (e.g. where, at a current
level I the CB curve passes through a point corresponding to 1.5 seconds, the fuse curve at the same current
level I must pass through a point corresponding to 3 seconds, or more, etc.).
The factors 1.35 and 2 are based on standard maximum manufacturing tolerances for MV fuses and LV circuit-
breakers.
Where a LV fuse-switch is used, similar separation of the characteristic curves of the MV protective device and LV
fuses must be respected.
10. Cascading
10.1. Default and individual parameter settings
On the Project parameters tab, in the zone for device selection, it is possible to request that the system attempt to
set up cascading for all final protection devices, i.e. those immediately upstream of the loads. It is on the final circuits
that there is the greatest number of outgoers and consequently that cascading can provide the greatest benefits.
In addition, there is an individual parameter for each circuit breaker in the installation, among the circuit-breaker
properties, to activate or deactivate system attempts to establish cascading.
No cascading
No cascading
No search for a
cascading solution
Ikmin
i²t phase
i²t neutral
i²t PE
If withdrawability is not required, EcoStruxure Power Design - Ecodial proposes solutions without taking the feature
into account.
In the results zone, EcoStruxure Power Design - Ecodial indicates whether a withdrawable version exists for each
device.
If the option is not required, EcoStruxure Power Design - Ecodial proposes solutions without taking the option into
account.
In the results zone, EcoStruxure Power Design - Ecodial indicates whether the option exists for each device.
If the option is not requested, EcoStruxure Power Design - Ecodial selects only devices that cannot be remotely
opened.
In the absence of an indication (parameter set to Any), EcoStruxure Power Design - Ecodial proposes solutions
without taking the option into account.
In all cases, EcoStruxure Power Design - Ecodial indicates in the results zone whether each device can be remotely
opened or not.
If visible break is required on a switch, EcoStruxure Power Design - Ecodial selects only switches offering the function.
If it is not required, EcoStruxure Power Design - Ecodial selects only devices not offering the function.
In the absence of an indication (parameter set to Any), EcoStruxure Power Design - Ecodial proposes solutions
without taking the function into account.
In all cases, EcoStruxure Power Design - Ecodial indicates for each device in the results zone whether the function is
available.
Type A
Tripping is provided for residual sinusoidal alternating currents and specified residual pulsating direct currents.
Type B
Tripping is provided for currents identical to those for class A and for residual direct currents produced by three-phase
rectification.
In addition, Schneider Electric offers the following types of residual-current devices in its catalogue:
SI (super immunised) with reinforced immunity to nuisance tripping in polluted networks,
SiE designed for environments with severe operating conditions.
The table below presents the recommended type and immunity level as a function of the external conditions and the
level of disturbances on the electrical network.
EcoStruxure Power Design - Ecodial offers a choice between the two possibilities.
If no choice is made (parameter set to Any), the proposed solutions include both integrated and separate devices that
are compatible with the breaking device.
• The necessary assessment of the electrical installation is required to know the ‘high sensitivity
residual current protection’.
• Use the residual current protection devices with a sensitivity I∆n less than or equal to 30 mA.
The situations and applications presented below require highly-sensitivity residual-current devices, i.e. devices with a
sensitivity I∆n less than or equal to 30 mA.
• The necessary assessment of the electrical installation is required to know the ‘medium sensitivity
residual current protection’.
• Use the residual current protection devices with a sensitivity I∆n less than or equal to 300 mA or
500 mA.
The situations and applications presented below require medium-sensitivity residual-current devices, i.e. devices with
a sensitivity I∆n less than or equal to 300 mA or 500 mA.
15.3. Procedure if the cumulative voltage drop for a load exceeds the permissible
value
If the calculated, cumulative voltage drop exceeds the maximum, permissible value, EcoStruxure Power Design -
Ecodial displays a message to signal the detected error.
To clear the detected error, reduce the voltage-drop tolerances for the upstream circuits supplying the load ( Circuit
voltage-drop tolerances).
In the example below, the calculated voltage Below, the voltage-drop tolerance for cable WD3
drop for load AA7 is 6.06%, i.e. greater than the has been reduced to 3%. EcoStruxure Power
maximum permissible value of 6%. The Design - Ecodial consequently increases the size
tolerance for circuit voltage drops is set to 5%. of the cable and the voltage drop for load AA7 is
now less than 6% (4.98%).
∆u ∆u tolerance
+3.86% 5% → 3%
∆u
+ 1.93%
To maintain the maximum voltage drop for AA7 to less than 6%, it is necessary to reduce the voltage drops on the
upstream circuits (WD3 and WD7) by reducing the voltage-drop tolerance(s).
There are two possible methods.
Reduce the tolerances for all upstream circuits, in which case the size (cross-sectional area) of all upstream circuits
will be increased.
Reduce the tolerance for a single upstream circuit, namely the circuit selected by the designer as the best for an
increase in size.
EcoStruxure Power Design - Ecodial presents in the results zone of the window:
the installation-method number,
the reference method used,
a complete description of the installation method,
a diagram.
For example in a circuit where the requested design current is 220A, using a Compact NSX250 with Mircologic 2.2 trip
unit the cable sizing can be made taking into account:
In = 250 A, the cable is sized to 95 mm²,
Or Ir = 220 A, the cable is sized to 70 mm².
If the concerned circuit itself contains several conductors per phase, the grouping factor is automatically set to the
right value by EcoStruxure Power Design - Ecodial.
1 cable of 120 mm² per phase, and is installed 2 cables of 120 mm² per phase and is installed
in a cable tray with 2 other circuits in a cable tray with 2 other circuits
The number of additional touching circuit has to The number of additional touching circuit has to
be set to 2 be set to 2
Then the grouping factor will be set by Then the grouping factor will be set by
EcoStruxure Power Design - Ecodial for 3 EcoStruxure Power Design - Ecodial for 4
touching circuits (the concerned circuit + 2 touching circuits (2 for the concerned circuit + 2
additional circuits) additional circuits)
Many devices in a wide range of fields include this type of circuit. They are the main causes of H3 harmonics.
Field Devices
Residential TV, hi-fi, video, microwave ovens, compact fluorescent lamps (CFL), etc.
Services Microcomputers, printers, photocopiers, fax machines, CFLs, etc.
Industry Switch-mode power supplies, variable-speed drives, CFLs, etc.
16.6.2. Impact of neutral protection on cable sizes
Table 52-D1 and §523.5.3 of standard IEC 60364 sums up the rules for neutral protection, selection of cable sizes and
the factors for permissible-current reduction in cables when H3 harmonics are present.
THDI ≤ 15% 15% < THDI ≤ 33% 33% < THDI ≤ 45% THDI > 45%
S neutral = S phase /2 S neutral = S phase S phase = Sneutral S phase = Sneutral
is permissible (1) S phase is decisive S neutral is decisive S neutral is decisive
Neutral protected Factor = 0.86 IBneutr al = 3 X THDi x IBneutr al = 3 X THDi x I Bphase
IBphas e Factor = 1
Factor = 0.86
For 4P3d+OSN trip units, the Irphase /Irneutral ratio is constant at 0.63.
EcoStruxure Power Design - Ecodial includes a function to waiver thermal protection for circuit breakers supplying
loads.
In this case, two types of circuit breakers are proposed by EcoStruxure Power Design - Ecodial:
circuit breakers without thermal protection and equipped with an MA trip unit,
circuit breakers equipped with a control unit enabling inhibition of thermal protection (e.g. Micrologic 5 or
equivalent).
In that case, EcoStruxure Power Design - Ecodial sizes the circuit breaker and the cable to accept 1.5 times the
design current of the circuit.
20. Calculation
20.1. Calculation of LV-source phase impedances, based on Ik3max
Ik3max is used to calculate the phase impedances on the upstream network, represented by the LV source.
c max ⋅ Ur
ZL =
3 ⋅ Ik3max
R L = Z L ⋅ PFsc
XL = Z L 2 − R L 2
Depending on the type of system earthing, there are a number of dependencies between the different short-circuit
currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
EcoStruxure Power Design - Ecodial checks the consistency between the parameters ( Consistency of LV-source
input parameters).
These equations are also valid for the impedance of the PEN conductor in the TN-C system (with a distributed
neutral).
Depending on the type of system earthing, there are a number of dependencies between the different short-circuit
currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
EcoStruxure Power Design - Ecodial checks the consistency between the parameters ( Consistency of LV-source
input parameters).
U U
cmin × r cmax × r
3 3
ZPE = -
Ief Ik3max
U U
cmin × r cmax × r
R PE = 3- 3 × PF
sc
Ief Ik3max
XPE = ZPE 2 − RPE 2
Depending on the type of system earthing, there are a number of dependencies between the different short-circuit
currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
EcoStruxure Power Design - Ecodial checks the consistency between the parameters ( Consistency of LV-source
input parameters).
U U
cmin × α × r cmax × r
3 3
ZPE = -
2 × Ief2min Ik3max
U U
cmin × α × r cmax × r
3 3
RPE = - × PFsc
2 × Ief2min Ik3max
XPE = ZPE 2 − RPE 2
Depending on the type of system earthing, there are a number of dependencies between the different short-circuit
currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
EcoStruxure Power Design - Ecodial checks the consistency between the parameters ( Consistency of LV-source
input parameters).
The ratio Gh/Sn is calculated by EcoStruxure Power Design - Ecodial for each capacitor bank, taking into account the
loads declared as harmonic loads.
The ratio Gh/Sn can also be entered directly for each capacitor bank. In this case, the values are locked and will not
be modified by EcoStruxure Power Design - Ecodial in the event of changes in the installation.
If Gh/Sn exceeds 50%, a special study must be carried out to determine the type of capacitor bank because harmonic
filtering must be installed.
For more information: Electrical Installation Wiki.
Type Definition
Type 1 Deterioration of the contactor and the relay is acceptable under two conditions:
no danger to operating personnel,
no danger to any components other than the contactor and the relay
Type 2 Only minor welding of the contactor or starter contacts is permissible and the contacts
must be easily separated. Following type-2 coordination tests, the switchgear and
controlgear functions must be fully operational.
When the switchgear and controlgear includes both the circuit breaker and contactor functions, coordination is
considered to be total.
The short-circuit currents Ik3max, Ik2max and Ik1max are calculated in compliance with Cenelec TR50480 technical
report.
For the double-fault current, EcoStruxure Power Design - Ecodial check that the breaking capacity at the phase-to-
phase voltage is greater than:
the current Ief calculated in compliance with Cenelec TR50480 technical report
0.15 times the 3-phase short-circuit current at the point considered if this current is less than or equal to 10
000 A,
0.25 times the 3-phase short-circuit current at the point considered if this current is greater than 10 000 A.
The short circuit set of values stay same across The short circuit set of values vary across tap off
any tap off points points based on there distance from origin.
When designing systems where the details When designing systems where BTS riser needs
about the BTS are not know at the design time, to be used, it is advised to use Non Uniform BTS
it is advised to use Uniform BTS as it will take as the tap off points will not be equidistance from
into consideration derated voltage drop and each other.
short circuit set
Important note: The busbar trunking system selected by EcoStruxure Power Design - Ecodial will remain the same
irrespective of whether a uniform / non uniform distribution type is chosen as far as the voltage drop is acceptable.
EcoStruxure Power Design - Ecodial does not distinguish between uniform and non uniform from a schematic
perspective (SLD).
In case of BTS where feeder distribution is non uniform, the component voltage drop and short circuit set represented
in the report section, shows the total cumulative values of the tap off points along with the component’s voltage drop
and short circuit set.
EcoStruxure Power Design - Ecodial selects the fuses rating according to voltage and transformer power in order to:
break short-circuit current across the terminal of the transformer secondary,
prevent unexpected tripping due to transformer inrush current.
With:
Is = current setting,
T = time delay setting at 10 x Is.
k α β
SIT 0,14 0,02 2,97
VIT 13,5 1 1,5
LTI 120 1 13,33
EIT 80 2 0,808
UI 315,2 2,5 1
1000
100
10
t (s)
1
1 10 100 1000 10000 100000
0,1
0,01
0,001
I (A)
31. UPS
31.1. UPS inputs connection
In EcoStruxure Power Design - Ecodial only on-line UPS are available, for more information on this technology:
Electrical Installation Wiki.
EcoStruxure Power Design - Ecodial proposes 2 possibilities for the inputs connection:
common, in that case Normal and Bypass are connected and fed by one feeder circuit with one common
upper protection,
separated, in that case Normal and Bypass are connected to separate upstream feeder.
The default value proposed by EcoStruxure Power Design - Ecodial depends on the UPS characteristics and power:
for small UPS (low power) the connections are common by default,
for medium and high power UPS the connections are separated by default.
When the default value is “Common” it’s possible to change it to “Separated”, in that case the lock next to the
parameter closes .
Common Normal and Bypass connection Separated Normal and Bypass connection
Here is an example with 2 feeders connected downstream an USP with respective power demand:
- 100 kVA,
- 10 kVA.
Taking into account the diversity factor of 0.9 on bubsar WC15 the total power demand for the UPS is 99 kVA.
The following table shows the solutions proposed by EcoStruxure Power Design - Ecodial depending the requested
level of redundancy.
In case of a solution with common bypass, the number of bypass displayed by EcoStruxure Power Design - Ecodial
will be lower than the number of UPS unit.
One bypass per UPS unit Common bypass for several units
• Class I tests: They are conducted using nominal discharge current (In), voltage
impulse with 1.2/50 μs waveshape and impulse current Iimp.
The class I tests is to simulate partial conducted lightning current impulses.
SPDs subjected to class I test methods are generally recommended for locations
at points of high exposure, e.g., line entrances to buildings protected by lightning
Protection systems.
• Class II tests: They are conducted using nominal discharge current (In), voltage
impulse with 1.2/50 μs waveshape
• Class III tests: They are conducted using the combination waveform (1.2/50 and
8/20 μs).
SPDs tested to class II or III test methods are subjected to impulses of shorter duration. These SPDs are generally
recommended for locations with lesser exposure.
This option is used to enable or disable the surge protection device calculation for the installation.
If the option chosen in "Yes"
• One or more surge protection devices are calculated for the installation based on the risk assessment
of the installation
• High level risk assessment of the installation is carried out by the software to ensure that the correct
category / class of the surge arrester is chosen.
o In the cases where a lightning protection system is used for the installation ( i.e. there is a
lightning rod on the building or within 50m of the building), the designer needs to provide the
correct value of Imax i.e. either 12.5kA or 25kA ( as per IEC 62305-2). Minimum required is
12.5kA / pole
o In the cases where there is no lightning protection system used for the installation, the
designer needs to choose the correct value of overvoltage risk for the installation. The
categories are
Low
• Imax = 20kA
• Building located in an urban or suburban grouped housing area
Medium
• Imax = 40 kA
• Building located in plains
High
• Imax = 65kA
• Building located in an area where there is a special risk ( pylon, tree,
mountainous region, mountain peak, damp area or pond )