F 650
F 650
F 650
F650
Controller System
Cost effective solution for protection,
Applications
• Primary protection and control for distribution feeders on • Load shedding schemes based on voltage and frequency
solidly grounded, high impedance grounded or resonant elements
(Peterson Coil) grounded systems • Back-up protection for transmission lines, feeders and
• Bus blocking/Interlocking schemes transformers
• High-speed fault detection for arc flash mitigation • Distributed Generation (DG) interconnect protection, including
• Throw over schemes (bus transfer scheme applications) active and passive anti-islanding
Features
Features
Protection and Control Monitoring & Metering
• Time, instantaneous & directional phase, neutral, ground • Fault locator, record of last 10 faults -metering - current,
and sensitive ground overcurrent voltage, power, energy, frequency and harmonics
• Manual close with cold load pickup control via PLC,
Forward Power and Directional Power Units • Breaker operation & trip failure
• Load encroachment supervision • Total breaker arcing current
• Wattmetric ground fault detection • Event recorder - 479 Events
• Positive and negative sequence based over/under voltage • High resolution oscillography and Data Logger, with
elements programmable sampling rate
• Four-shot autorecloser with synchronism check
• Metering: V I Hz W VA PF
• Breaker control and breaker failure
• Demand: Ia , Ib , Ic , Ig, Isg, I2, MW, MVA
• Abnormal frequency protection (Rate of change, under
and over frequency) • Configurable graphical HMI interface
• Broken conductor and locked rotor • Alarm Panel
• Synchrocheck - V, , & Hz
EnerVista™ Software
• Up to 64 Programmable digital inputs and up to 16 digital
• Sophisticated software for configuration and commissioning
outputs
• Document and software archiving
• Trip Circuit Supervision
g
• EnerVista™ Integrator providing easy integration of data in the
F650 into new or existing monitoring and control systems
Multilin
311
F650 Feeder/Bay Protection System
1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
25
1 50 BF Breaker Failure
50PH/PL Phase Instantaneous Overcurrent (High/Low)
1 2 2 50N Neutral Instantaneous Overcurrent
50G 51G 67G 50G Ground Instantaneous Overcurrent
3 3 3
1 50SG Sensitive Ground Instantaneous Overcurrent
50SG 51SG 50IG 67SG METERING 50IG Isolated Ground Instantaneous Overcurrent
3 3 3 3
3V_0
51N Neutral Time Overcurrent
51G Ground Time Overcurrent
3
51SG Sensitive Ground Time Overcurrent
51PH/V Voltage Restraint Phase Time Overcurrent
47 27 59 VTFF 81U 81O 81R 51PL/V
3 3 3 1 3 3 3
59NH 59/59X Bus/Line Overvoltage
3 59NH/NL Neutral Overvoltage - High/Low
67P Phase Directional Overcurrent
59NL
67N Neutral Directional Overcurrent
F650 Digital Bay Controller 3
67G Ground Directional Overcurrent
EN F650 BLOCK F.CDR
312 www.GEMultilin.com
F650 Feeder/Bay Protection System
and "Low Level" used to executing complex Broken Conductor via setting the requested thresholds.
protection schemes. The function can be F650 incorporates a broken or fallen EnerVista™ software allows easy
initiated/blocked via digital inputs as well conductor detection function. The relay configuration of all the interlocking and
as communications. uses the ratio between the negative switching sequences. A graphic HMI
The relay also provides for control of one or sequence current, I2, and the positive interface provides access to monitoring,
two breakers from faceplate pushbuttons, sequence current I1. In normal and metering and alarm panel screens.
remote communications or contact inputs. balanced load situations, this ratio is zero,
Virtual Inputs/Outputs
A breaker pole discrepancy is included in the while in severe load fault conditions, an
breaker control scheme. Breaker position is unbalance is produced and this ratio Traditionally, protective relay logic has
indicated by LEDs on the faceplate. increases. been relatively limited. Use virtual inputs
and outputs in conjunction with the
Load Encroachment In order to avoid trips or pickup with programmable logic capabilities of the
very weak loads, there is a current level F650 for unusual applications involving
Feeders may experience very heavy load
threshold (I2/I1) to inhibit the operation of interlocks, blocking, or supervisory
increases due to various contingency
functions, to minimize the requirement for
www.GEMultilin.com 313
F650 Feeder/Bay Protection System
of other F650 devices via the IEC61850 Breaker Arcing Current (I2t) applications. IEC61850 is built on over
GSSE messaging. User secure peer-to- 7 years of GE leadership in UCA 2.0
The relay estimates the total interrupted
peer communications to develop complex implementation.
current as an accumulation of the RMS
schemes in distributed logic and I/Os. current measured during the time period IEC61850 allows for the seamless
taken to open the breaker after a trip. connection of IEDs from multiple vendors.
In addition to device interoperability, these
Monitoring and Metering It calculates the per-phase wear on the
protocols are designed to control the
breaker contacts to establish a threshold.
The F650 provides advanced monitoring When the breaker maintenance threshold substation via a LAN instead of through
and metering that includes: is exceeded the relay can be set to trigger discrete wiring to an RTU. Peer-to-peer
an alarm. communication over Ethernet enables
VT Fuse Failure distributed control with several IEDs and
Use the VT Fuse Failure feature to issue Communications eliminates the need for an RTU to remote
an alarm and/or to block voltage driven The F650 includes up to three communication SCADA master. High-speed message
protection functions that can operate ports that operate simultaneously. transfer eliminates the need for large and
incorrectly due to an abrupt partial or total Redundant ports are also available for costly hard-wired interconnection.
Distribution Feeder Protection
voltage loss. This loss is caused by the special applications. F650 features an
voltage transformers secondary circuit RS232 front port (COM2) and a choice
protection fuse failure. Different methods of rear RS485, plastic/glass fiber optics EnerVista™ Software
are used to detect the different types of VT (COM1 and COM2). Additionally, this The EnerVista™ Suite is an industry-leading
fuse failure. module may incorporate a port for CAN bus set of software programs that simplifies
communications, used for the connection every aspect of using the F65 relay. The
Trip Circuit Monitoring
to the remote CAN BUS I/O module. F650 EnerVista™ suite provides all the tools to
F650 can be used to monitor the integrity COM3 features 10/100 BaseTX and 100 monitor the status of your the protected
of both the breaker trip and closing Base FX single or redundant Ethernet asset, maintain the relay, and integrate
coils and circuits. The supervision inputs ports. information measured by the F650 into DCS
monitor both the battery voltage level,
Protocols supported by the F650 include or SCADA monitoring systems. Convenient
while the outputs monitor the continuity of
IEC61850, DNP 3.0, Modbus RTU, ModBus COMTRADE and Sequence of Events viewers
the trip and/or closing circuits, by applying
TCP/IP and IEC 60870-5-104. These are an integral part of the 650 Setup
a small current through the circuits.
protocols make it easy to connect to software included with every F650 relay,
a Utility automation system and are to carry out postmortem event analysis to
Basic Metering ensure proper protection system operation.
integrated into the F650, eliminating
Metered values include: the need for external protocol converter
• Current: Ia, Ib, Ic, In, Ig, Isg devices. EnerVista™ Launchpad
• Phase-to-phase and phase-to-ground EnerVista™ Launchpad is a powerful
voltages for bus and line: Van, Vbn, Vcn, Security software package that provides users with
Vbb, Vab, Vbc, Vca Independent passwords for protection and all of the setup and support tools needed
control allow restricting access via keypad for configuring and maintaining GE Multilin
• Active power (per-phase and total): Wa,
Wb, Wc, W and display, or EnerVista™ software. products. The setup software within
Launchpad allows configuring devices in
• Reactive power (per-phase and total): Multi-Language real-time by communicating using serial,
VAra, VArb, VArc, VAr
The F650 supports multiple languages. Ethernet, or modem connections, or offline
• Total active, reactive and apparent by creating setting files to be sent to devices
French, Chinese, Russian language options
energy: MWh, MVArh, MVah at a later time.
are available on the local display, front
• Power factor (per-phase and total) panel, and EnerVista™ setup software, as Included in Launchpad is a document
• Frequency well as the product instruction manual. archiving and management system that
Easily switch between English and an ensures critical documentation is up-to-date
• Demand
additional user selectable language on the and available when needed. Documents
Ia, Ib, Ic, Ig, Isg, Va, Vb, Vc and Vx signals are local display. made available include:
available locally and remotely and can be
stored in the oscillography record or data • Manuals
Interoperability With Embedded
logger. IEC61850 Protocol • Application Notes
314 www.GEMultilin.com
F650 Feeder/Bay Protection System
User Interface
LEDs
• Multicolor programmable LEDs with label panel
• Local/Remote/Off pushbutton with LEDs
Front Port
• Electrically isolated front USB communication port
The F650 uses a “shuttle“ control for ease of use. A choice of text or graphic display, and up to five configurable keys are available for frequently
performed control functions. Up to 15 programmable LEDs are available. The F650 can incorporate (option “N” for the second position of the order-
ing code) a Graphical display with IEC Symbols.
Dimensions
www.GEMultilin.com 315
F650 Feeder/Bay Protection System
COM1
+ - + - RS485 A(-)
A5 VA
BACKUP B(+)
POWER READY POWER BACKUP READY GND
A6 VA
CAN COM2
RS485 A(-)
VOLTAGE INPUTS
A7 VB B(+)
TX
FIBER
A8 VB RX
g
1
A9 VC TX
COM1
Multilin FIBER
RX
A10 VC TX
Distribution Feeder Protection
COM2
FIBER
1 RX
B1 IA
TX
F650 FIBER
CAN
RX
B2 IA
Digital Bay Controller
B3 IB GND
COM1
RS485 A(-)
B4 IB B(+)
CURRENT INPUTS
GND
CAN
B5 IC CABLE CAN L
CAN H
B6 IC
10/100 UTP RJ45
ETHERNET 1
B9 IG
TX
100FX ST
B10 IG RX
1 10/100 UTP RJ45
ETHERNET 2
B11 ISG TX
100FX ST
RX
B12 ISG
+ H19
IRIG-B
A11 VX
BUS V
- H20
A12 VX
RS-232 FRONT 1
A C
B
C A
GROUNDING
52 B SCREW
A5 VA
A6 VA SLOT G
BOARD TYPE 1, 4 ,5 BOARD TYPE 1 BOARD TYPE 4 BOARD TYPE 5
VOLTAGE INPUTS
AI3
G7 + CC7 O3 G25 CC23 G25 - G25
ANALOG INPUTS
SLOT F
BOARD TYPE 1, 4 ,5 BOARD TYPE 2 BOARD TYPE 1 BOARD TYPE 2 BOARD TYPE 4 BOARD TYPE 5
F1 + CC1 F1 + COIL 1 F19 O1 F19 CC17 F19 SHIELD 1/4 F19
V O1
F2 + CC2 F2 - 52/a F20 F20 CC18 F20 F20
COIL 1
+
AI1
F3 + CC3 F3 + COIL 1 F21 O2 F21 CC19 F21 - F21
V
F4 + CC4 F4 - 52/b F22 F22 CC20 F22 + F22
O2 AI2
F5 + CC5 F5 + CC1 F23 O3 F23 CC21 F23 - F23
USER CONFIGURABLE INPUTS
CONFIGURABLE OUTPUTS
+
USER CONFIGURABLE INPUTS
AI3
USER CONFIGURABLE INPUTS
I +
AI8
F17 + CC15 F17 + COIL 2 O8 F35 F35 CC31 F35 - F35
V O8
F18 + CC16 F18 - 52/b F36 F36 CC32 F36 SHIELD 5/8 F36
316 www.GEMultilin.com
F650 Feeder/Bay Protection System
Technical Specifications
Protection Protection Minimum voltage threshold:
PHASE/NEUTRAL AND GROUND TIMED OVERCURRENT ISOLATED GROUND INSTANTANEOUS overCURRENT 3 to 300 in steps of 1V
(51PH/51PL/51N/51G) (50IG) Logic: Any/two/all phases logic selectable by
Current: Fundamental Phasor (w/o harmonics) or RMS setting
Rated current : For connection to 1 or 5 A CTs. Current Input: Fundamental Phasor (without harmonics) Supervised by breaker:
Pickup level : 0.05 to 160.00 A in steps of 0.01 A Voltage Input: Fundamental Phasor (without harmonics) Selectable by setting
Reset Dropout level: 97% to 98% of the pickup level Current Pickup level: 0.005 to 0.400 A in steps of 0.001 A Timing accuracy: ±3.5% of operation time or 50 ms.
Accuracy: ±0.5% of the reading ±10 mA from 0.05 Voltage Pickup level: 2 to 70 V in steps of 1 V (whichever is greater)
to10A Dropout level : 97 to 98% of the pickup level Protection
±1.5% of the reading for values higher Pickup level: for voltage 2 to 70 V in steps of 1 V
than 10A Dropout Level: 97-98% of the pickup level AUXILIARY OVERVOLTAGE (59X)
Operation curves Level Accuracy: ±1.5% of the reading ± 1 mA from 0.005 Pickup level: 3 to 300 in steps of 1 V
IEEE extremely/very/moderately inverse to 16 A Reset dropout level: 97% to 98% of the pickup level
IEC Curve A/B/C/Long-Time Trip delay: 0.00 to 900.00 s. in steps of 0.01 s. Accuracy: ±1% of the reading, from 10 to 208 V
Inverse/ Short-Time Inverse Time to instantaneous 0.00 to 900.00 s. in steps of Timing accuracy: ±3.5% of operation time or 50 ms
ANSI extremely/very/normally/moderately 0.01 s. (whichever is greater)
inverseI2t Operate time: <50 ms at 3 x Pickup at 50 Hz, typically AUXILIARY UNDERVOLTAGE (27x)
IAC extremely / very / moderately inverse Timing accuracy: at 0 ms time delay (no intentional Pickup level: 3 to 300 in steps of 1 V
Definite time delay): 50ms at non-zero time delay: Reset dropout level: 97% to 98% of the pickup level
Rectifier curve ±3% of operate time or 50 ms (which Accuracy: ±1% of the reading, from 10 to 208 V
User curve FlexCurve™ A/B/C/D ever is greater) Operation curves:
Reset time type: Instantaneous or time delayed according Snapshot Events: Selectable by setting Fixed time or inverse curve
to IEEE PHASE DIRECTIONAL UNITS (67P) Timing accuracy: ±3.5% of operation time or 50 ms
Snapshot events: Selectable by setting (whichever is greater)
Timer accuracy: From 1.03 times the pickup, ±3% of Directionality: Forward and reverse selectable by setting
Polarizing: Quadrature Voltage: FREQUENCY (81U ,81O)
operation time or 50 ms. (whichever is
greater) ABC seq: Phase A (VBC), Phase B (VCA), Pickup level: 20 to 65 Hz in steps of 0.01 Hz
Voltage restraint: Selectable by setting Phase C (VAB) Reset dropout level: 30 mHz higher/lower than the
ACB seq: Phase A (VCB), Phase B (VAC), pickup level
www.GEMultilin.com 317
F650 Feeder/Bay Protection System
Switchgear
Switchgear number: 1 to16
Switchgear: 1 to16 (configurable).
318 www.GEMultilin.com
F650 Feeder/Bay Protection System
CAN PORT:
Type: Cable or Multimode glass F.O. port mechanical characteristics
with ST connectors Metallic package in 1/2 19" rack 6 units high
Fiber Wave length: 1300 nm Protection class IP52 (according to IEC 529)
Isolation: 2kV
ETHERNET PORT: control
Type:
Model B: 10/100BaseTX self-negotiable Graphical display: English, Spanish, French and Chinese
Model C: 10/100BaseTX + 100Base FX with Basic display: English, Spanish, French, Chinese and Cyrilic
ST connectors
Model D: 10/100BaseTX + Double PACKAGING
100BaseFX with ST connectors
(physical media redundancy) Approximate weight:
Model E: Redundant 10/100BaseTX Net: 11 lbs (5 kg)
Protocols: ModBus® TCP/IP Ship: 13.2 lbs (6 kg)
DNP over TCP/IP and UDP/IP
IEC 60870-5-104 ENVIRONMENTAL
IEC61850 Temperature:
Http, ftp, tftp (allow the use of a Storage: -40 to +80° C
standard Internet browser) Operation: -20 to +60° C
NOTES: Humidity: Up to 95% without condensing
In Models C and D, the 10/100BaseTX port is selected
by an internal switch. Two indicating LEDs for trans-
mission and reception are included approvals
CE: Conforms to EN/IEC 60255, 61010
UL: UL508 Certicfied under E234610
www.GEMultilin.com 319
F650 Feeder/Bay Protection System
Ordering
F650 * * * F * G * * * * * * Description
DISPLAY B Basic alfanumeric Text Display
M Graphic Display (without IEC symbols)
N Graphic Display with IEC symbols
Rear Serial Communications Board 1 F None
A Redundant RS485
P Redundant plasticfiber optic
G Redundant glass fiber optic
X Redundant RS485 + fiber remote CAN bus I/O
Y Redundant plastic fiber optic + fiber remote CAN bus I/O
Z Redundant glass fiber optic + fiber remote CAN bus I/O
C Cable Remote CAN Bus I/O
M RS485 + cable Remote CAN Bus I/O
Rear Ethernet Communications board 2 B 10/100 Base TX
C 10/100 Base TX + 100 Base FX
D 10/100 Base TX + Redundant 100 Base FX
E Redundant 10/100 Base TX
I/O BOARD IN SLOT F 1 16 Digital Inputs + 8 Outputs
2 8 Digital Inputs + 8 Outputs + 2 trip/close circuit
supervision circuits
Distribution Feeder Protection
4 32 Digital Inputs
5 16 Digital Inputs + 8 Analog Inputs
I/O BOARD IN SLOT G 0 None
1 16 Digital Inputs + 8 Outputs
4 32 Digital Inputs (See Note 1)
5 16 Digital Inputs + 8 Analog Inputs (See Note 1)
Auxiliary Voltage LO 24-48 Vdc (range 19.2 - 57.6)
HI 110- 250 Vdc (range 88 – 300)
120-230 Vac (range 96 – 250)
LOR Redundant LO
HIR Redundant HI
Language - English/English
C Chinese/English (See Note 2)
F French/English
P Russian/English (See Note 2)
S Spanish/English
COMMUNICATION PROTOCOL - Modbus ® RTU, TCP/IP, DNP 3.0 Level 2, IEC 60870-5-104
3 IEC 60870-5-103, Modbus ® RTU, TCP/IP
6 IEC61850, Modbus ® RTU and TCP/IP, DNP 3.0 Level 2,
IEC 60870-5-104
ENVIRONMENTAL PROTECTION - Without Harsh (Chemical) Environment Conformal Coating
H Harsh (Chemical) Environment Conformal Coating
ENHANCED DISPLAY - Display with RS232
E Enhanced Display with Front USB port
SPECIAL MODELS:
MOD001: 6A output contacts instead of 16A..
(*) Notes:
(1) The number selected for option G must be equal or higher than the number selected for option F for models including boards 4 and 5.
(2) Display options with language selection:
Graphic display (M & N): available for English, French, Spanish and Chinese languages. For chinese only IEC symbols option is available (N in ordering code).
Basic display (B): available for English, French, Spanish, Russian and Chinese languages
Ordering Note: This order code is valid for the latest version of F650 hardware and firmware version. The older hardware and previous firmware versions are still available and may be ordered through the usual channels.