F60
F60
F60
Multilin
Distribution Feeder Protection
APPLICATIONS
Primary protection and control for feeders on solidly, impedance or resonant (Peterson Coil) grounded systems Bus blocking/Interlocking schemes Distribution load shedding schemes based on voltage and frequency elements High-speed fault detection for arc flash mitigation Throw over schemes (bus transfer scheme applications) Back-up protection for transmission lines, feeders and transformers Distributed Generation (DG) interconnect protection
FEATURES
Protection and Control
High impedance fault detection (Downed Conductor Detection) Directional, time, instantaneous, phase, neutral, negative sequence & ground overcurrent protection Load encroachment supervision Wattmetric ground fault detection Thermal overload, Incipient cable fault detection and broken conductor Four-shot autorecloser with synchronism check Breaker control and breaker failure Abnormal frequency protection (Rate of change, under and over frequency)
Communications
Networking interfaces 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, IEEE C37.94 Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus TCP/IP, IEC60870-5-104 Direct I/O secure, high-speed data exchange between URs, for DG, distribution automation applications Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports
EnerVista Software
Graphical Logic Designer and Logic Monitor to simplify designing and testing procedures Document and software archiving toolset to ensure reference material and device utilities are up-to-date EnerVista Integrator providing easy integration of data in the F60 into new or existing monitoring and control systems
Digital Energy
301
The F60 offers an integrated protection, control, metering and monitoring package that can directly connect into DCS or SCADA monitoring control systems such a View Point Monitoring
The Hi-Z element in the F60, unique to Multilin, provides reliable detection of faults caused by downed conductors. Sophisticated algorithms developed over the past 20 years, detect downed conductors, tree branch contacts, and insulation fault in underground cables. This unique, field proven algorithm incorporates artificial intelligence to maximize dependability. Key benefits of Hi-Z detection in the F60: Reliable detection of faults caused by downed conductors
Fast response to hazardous situations Dependable and secure operation using artificial intelligence Detection of arcing faults Easy integration by addition of a Hi-Z module to a new or existing F60 relay
Function
Synchronism Check Phase Undervoltage FUNCTION Auxiliary Undervoltage Synchrocheck Sensitive Directional Power Phase Undervoltage Thermal Overload Auxiliary Undervoltage Breaker Directional Power Sensitive Failure Breaker Failure Disturbance Detector Disturbance Detector Overcurrent Ground Instantaneous Ground Instantaneous Overcurrent Neutral Instantaneous Overcurrent Neutral Instantaneous Overcurrent Phase Instantaneous Overcurrent Phase Instantaneous Overcurrent Negative Sequence Instantaneous Negative Sequence Instantaneous Overcurrent Overcurrent Ground Time Overcurrent Ground Time Overcurrent Neutral Time Overcurrent Neutral Time Overcurrent Phase Time Overcurrent Negative Sequence Time Overcurrent Phase Time Overcurrent AC Circuit Breaker Negative Sequence Time Overcurrent Neutral Overvoltage AC Circuit Breaker Phase Overvoltage Neutral Overvoltage Auxiliary Overvoltage Negative Sequence Overvoltage Phase Overvoltage Neutral Directional Overcurrent Auxiliary Overvoltage Phase Directional Negative Sequence Overvoltage Negative Sequence Directional Neutral Directional Overcurrent Overcurrent Automatic Recloser Overcurrent Phase Directional Overfrequency Negative Sequence Directional Overcurrent Underfrequency Automatic Recloser Overfrequency Underfrequency
52 79 81U
6
CLOSE Monitoring
TRIP
32
2
49
50N
2
81O
4
27P
2
FlexElement
METERING
Transducer Inputs
59P
1
50G
2
51G
2
59N
1
27X
59X 25
2
59_2
1
302
www.GEDigitalEnergy.com
FIBER/COPPER
CB2
F60-2
The following are some of the key applications where voltage elements can be used: Source transfer schemes Load shedding schemes Back up capacitor bank protection and control
Auto transfer schemes can be implemented using programmable Flexlogic and wiring between relays can be eliminated using peer to peer communication.
IOC elements with separate outputs for each phase. Each TOC element has the following programmable characteristics: Pickup current level for trip, alarm, or control Choice of 17 curve shapes (including FlexCurves) and curve multipliers Instantaneous or linear reset time characteristic to coordinate with upstream transformer damage curves and downstream reclosers and fuses. Voltage restraint to increase sensitivity The majority of distribution systems are either solidly grounded or grounded through a low impedance. Fast fault clearance is required due to the ground fault impact . Following functions are incorporated in the F60 to provide secure ground protection: Neutral IOC and TOC Ground IOC and TOC The F60 allows use of directional elements for supervision of ground overcurrent protection elements and provide sensitive tripping for faults in one direction. Typical application for directional overcurrent includes: Isolation of faulted feeders in ring bus or parallel feeder arrangements Prevention of back-feeding utility source fault from industrial plant generators.
Sensitive high-speed ground fault protection for transformers For neutral directional sensing, the residual current of the phase CTs is used as the operating current. For current polarization, a residual CT is used to measure zerosequence current. For voltage polarization, the calculated or measured zero sequence voltage can be used. The maximum torque angle is programmable.
Load Encroachment
The Load Encroachment function in the F60 provides the capability to manage load growth in feeders. The load encroachment element can be set for the feeders expected maximum load, reducing the likelihood of false tripping for load conditions while maintaining dependability to trip for legitimate faults. It allows the phase overcurrent elements to be set to see end-of-line phase faults in heavily loaded feeder applications.
www.GEDigitalEnergy.com
303
FlexLogicTM Designer
Advanced Automation
The F60 incorporates advanced automation features including powerful FlexLogic programmable logic, communication, and SCADA capabilities that far surpass what is found in the average feeder relay. The F60 integrates seamlessly with other UR relays for complete system protection, including the unit and auxiliary transformers, and balance of plant protection.
FlexLogic
FlexLogic is the powerful UR-platform programming logic engine that provides the ability of creating customized protection and control schemes thereby minimizing the need, and the associated costs, of auxiliary components and wiring. Using FlexLogic, the F60 can be programmed to provide required tripping logic along with custom scheme logic for auto transfer schemes (Main-Tie-Main), loadshedding based on frequency, voltage and communication, loop restoration schemes, other remedial action schemes and dynamic setting group changes.
Flexlogic allows the F60 to operate and control breakers and other auxiliary devices needed to fit most feeder protection schemes and applications.
to power derived from zero-sequence voltage and current in a direction specified by the element characteristic angle. Power can be selected as active, reactive, or apparent. Therefore, the element may be used to sense either forward or reverse ground faults
Scalable Hardware
The F60 is available with a multitude of I/O configurations to suit the most demanding application needs. The expandable modular design allows for easy configuration and future upgrades. Flexible, modular I/O covering a broad range of input signals and tripping schemes Types of digital outputs include triprated Form-A and Solid State Relay (SSR) mechanically latching, and Form-C outputs RTDs and DCmA inputs are available to monitor equipment parameters such as temperature & pressure
Autorecloser
Two autoreclose elements are provided for use with distribution lines in three-pole tripping schemes with up to two breakers. Up to four selectable recloser shots are possible prior to locking out.
304
www.GEDigitalEnergy.com
angle. The F60 also measures up to the 25th harmonic on voltage and current, suitable for power quality applications.
Comprehensive device health diagnostic performed during startup Monitors the CT/VT input circuitry to validate the integrity of all signals
Communications
The F60 provides advanced communications technologies for remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides highbandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available redundant Ethernet option and the embedded managed Ethernet switch provide the means of creating fault tolerant communication architectures in an easy, cost-effective manner without the need for intermediary communication hardware. The F60 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems.
Use the F60 with integrated IEC 61850 to lower costs associated with feeders protection, control and automation. GE Energys leadership in IEC 61850 comes from thousands of installed devices and follows on seven years of development experience with UCA 2.0. Replace expensive copper wiring between devices with direct transfer of data using GOOSE messaging for transfer tripping, interlocking schemes, loop restoration, and loadshedding schemes. Configure systems based on IEC61850 and also monitor and troubleshoot them in real-time with EnerVista Viewpoint Engineer Integrate Multilin IEDs and generic IEC61850-compliant devices seamlessly in EnerVista Viewpoint Monitoring
Source CB1
Fault 1 CB2
CB3
Reverse zone interlocking protection - By using the IEC61850/ GOOSE or hi-speed Direct I/O capability blocking signals can be transferred upstream, allowing minimal coordination delays. Fast clearance can be provided for Fault 1 and still maintain coordination for Fault 2.
Fault 2
www.GEDigitalEnergy.com
305
and continuously at runtime to test its own major functions and critical hardware. These diagnostic tests monitor for conditions that could impact security and availability of protection, and present device status via SCADA communications and front panel display. Providing continuous monitoring and early detection of possible issues helps improve system uptime.
IEC61850 DNP3.0 Ethernet Global Data (EGD) IEC 60870-5-104 Modbus RTU, Modbus TCP/IP
EnerVista Launchpad
EnerVista Launchpad is a powerful software package that provides users with all of the setup and support tools needed for configuring and maintaining Multilin products. The setup software within Launchpad allows configuring devices in real-time by communicating using serial, Ethernet, or modem connections, or offline by creating setting files to be sent to devices at a later time. Included in Launchpad is a document archiving and management system that ensures critical documentation is up-to-date and available when needed. Documents made available include: Manuals Application Notes Guideform Specifications Brochures Wiring Diagrams FAQs Service Bulletins
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use and full-featured monitoring and data recording software package for small systems. Viewpoint Monitoring provides a complete HMI package with the following functionality: Plug-&-Play Device Monitoring System Single-Line Monitoring & Control Annunciator Alarm Screens Trending Reports Automatic Event Retrieval Automatic Waveform Retrieval
Multi-Language
The F60 supports English, French, Russian, Chinese and Turkish Languages on the front panel, EnerVista setup software, and product manual. Easily switch between English and an additional language on the local displays without uploading new firmware.
EnerVistaTM Software
The EnerVista Suite is an industry-leading set of software programs that simplifies every aspect of using the F60 relay. The EnerVista suite provides all the tools to monitor the status of your the protected asset, maintain the relay, and integrate information measured by the F60 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR Setup software included with every UR relay, to carry out postmortem event analysis and to ensure proper protection of system operation.
Viewpoint Engineer
Viewpoint Engineer is a set of powerful tools that will allow the configuration and testing of UR relays at a system level in an easy-to-use graphical drag-anddrop environment. Viewpoint Engineer provides the following configuration and commissioning utilities: Graphical Logic Designer Graphical System Designer Graphical Logic Monitor Graphical System Monitor
Record the operation of the internal F60 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during faults and disturbances.
Analyze feeder faults and disturbances using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.
306
www.GEDigitalEnergy.com
Typical Wiring
Viewpoint Maintenance
Viewpoint Maintenance provides tools that will create reports on the operating status of the relay, simplify the steps to download fault and event data, and reduce the work required for cyber-security compliance audits. Tools available in Viewpoint Maintenance include: Settings Security Audit Report Device Health Report Single Click Fault Data Retrieval
H1
V I
A B C
52
CONNECTION
H2 SURGE H3
EnerVista Integrator
EnerVista Integrator is a toolkit that allows seamless integration of Multilin devices into new or existing automation systems. Included in EnerVista Integrator is: OPC/DDE Server GMultilin Drivers Automatic Event Retrieval Automatic Waveform Retrieval
H8b
H4
F60
W5a W5c W6a W6c W5b W7a W7c W8a W8c W7b
W8b
SURGE 6A
H5
H6
W1
V I
W2
W3
W4
6C
P1
6D
P2
P3
P4
U5a U5c U6a U6c U5b U7a U7c U8a U8c U7b U8b
B1b B1a B2b B3a B3b B5b HI B6b LO B6a B8a B8b
P5
P6
P7
SURGE
RS-232 DB-9
P8
(front)
6K
M1
DC
M2
M3
M4
Fibre * Optic
Tx1 Tx2
10BaseFL
Rx1
M5
10BaseFL
Rx2
M6
10BaseT
RS485
com
M7
BNC BNC
M8
Minimum
832769A5.CDR
X W V U T S R P N M L K J
6
G
8
D
9 CPU
PROVIDED
User Interface
The F60 front panel provides extensive local HMI capabilities. The local display is used for monitoring, status messaging, fault diagnosis, and device configuration. User configurable messages that combine text with live data, can be displayed when user-defined conditions are met.
LED Indicators
www.GEDigitalEnergy.com
6B
H1a H1b H1c H2a H2b H2c H3a H3b H3c H4a H4b H4c H5a H5b H5c H6a H6b H6c
W1a W1b W1c W2a W2b W2c W3a W3b W3c W4a W4b W4c P1a P1b P1c P2a P2b P2c P3a P3b P3c P4a P4b P4c P5a P5b P5c P6a P6b P6c P7a P7b P7c P8a P8b P8c M1a M1b M1c M2a M2b M2c M3a M3b M3c M4a M4b M4c M5a M5b M5c M6a M6b M6c M7a M7b M7c M8a M8b M8c
TC 1
TC 2
UR TXD RXD
COMPUTER
SGND
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
CONNECTOR
CONNECTOR
B
1 Power Supply
307
F 6a
F 7a
F 5a
F 5a
F 6a
F 7a
F 2b
F 3a
F 3b
F 4a
F 8a
F 8c
F 4b
IG
F 1a
F 1b
F 6c
F 7c
F 2a
F 7c
F 3c
F 5c
F 5c
F 6c
F 2c
VB
VC
VB
VA
VA
VC
VX
VX
IG5
IC5
IC1
IB5
IB1
IG1
VA
VB
VA
VB
VC
VC
IA5
IA1
IB
IA
IC
F 4c
F 1c
Ordering
Base Unit CPU
F60 - * ** - H * * - F ** - H** - M**-P**- U** -W** For Full Sized Horizontal Mount
F60 E G H J K N S
Software Options
Mount / Coating
00 03 06 07
User Interface
H A V B
K L M N Q T U V F W Y
H H L
RH 8F 8G 8H 8J 8L 8M 8N 8R 81 XX 4A 4C 4D 4L 67 6C 6D 6E 6F 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5C 5E 5F
8L 8M 8N 8R 8Z XX 4A 4C 4D 4L 67 6C 6D 6E 6F 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5C 5E 5F XX 4A 4C 4D 4L 67 6C 6D 6E 6F 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5C 5E 5F XX 4A 4C 4D 4L 67 6C 6D 6E 6F 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5C 5E 5F XX 4A 4C 4D 4L 67 6C 6D 6E 6F 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5C 5E 5F 7A 7B 7C 7H 7I 7J 7S 7W 76 77 2S 2T
Base Unit RS485 + RS485 (IEC61850 option not available) RS485 + Multi-mode ST 10BaseF RS485 + Mutli-mode ST Redundant 10BaseF RS485 + Multi-mode ST 100BaseFX RS485 + Multi-mode ST Redundant 100BaseFX RS485 + 10/100 BaseT RS485 + 6 port, 100 Mbps, Managed Ethernet Switch No Software Options IEC61850 PMU IEC61850 + PMU Horizontal (19" rack) - Standard Horizontal (19" rack) - Harsh Chemical Environment Option Vertical (3/4 size) - Standard Vertical (3/4 size) - Harsh Chemical Environment Option Enhanced English Front Panel Enhanced English Front Panel with User-Programmable Pushbuttons Enhanced French Front Panel Enhanced French Front Panel with User-Programmable Pushbuttons Enhanced Russian Front Panel Enhanced Russian Front Panel with User-Programmable Pushbuttons Enhanced Chinese Front Panel Enhanced Chinese Front Panel with User-Programmable Pushbuttons Vertical Front Panel with English display Enhanced Turkish Front Panel Enhanced Turkish Front Panel with User-Programmable Pushbuttons 125 / 250 V AC/DC 125/250 V AC/DC with redundant 125/250 V AC/DC power supply 24 - 48 V (DC only) Standard 4CT/4VT Sensitive Ground 4CT/4VT Standard 8CT Sensitive Ground 8CT Standard 4CT/4VT w/ enhanced diagnostics Sensitive Ground 4CT/4VT w/ enhanced diagnostics Standard 8CT w/ enhanced diagnostics Sensitive Ground 8CT w/ enhanced diagnostics HI-Z 4CT (high impedance fault detection) 8 Port IEC 61850 Process Bus Module No module 4 Solid State (No Monitoring) MOSFET Outputs 4 Solid State (Current w/opt Voltage) MOSFET Outputs 16 Digital Inputs with Auto-Burnish 14 Form-A (No Monitoring) Latchable Outputs 8 Form-A (No Monitoring) Outputs 8 Form-C Outputs 16 Digital Inputs 4 Form-C Outputs, 8 Digital Inputs 8 Fast Form-C Outputs 4 Form-C & 4 Fast Form-C Outputs 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs 8 RTD Inputs 4 dcmA Inputs, 4 RTD Inputs 8 dcmA Inputs 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels G.703, 2 Channels RS422, 2 Channels IEEE C37.94, 820 nm, multimode, LED, 1 Channel IEEE C37.94, 820 nm, multimode, LED, 2 Channel 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC) 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)
Ordering Note: To view the latest options available for the F60, or to order the UR Classic Front Panel, please visit our online store for more details.
110928-v5
308
www.GEDigitalEnergy.com